0% found this document useful (0 votes)
209 views4 pages

02 Calculation External Static Pressure For Riser Duct High Speed

The document provides ductwork design calculations for three fans - Fan B1, Fan B2, and the combination of Fans B1 and B2. It includes air flow rates, duct sizes, lengths and fittings for each system. The total external static pressure is calculated as 206 Pa for Fan B1, 323 Pa for Fan B2, and 64 Pa for the riser duct serving both fans.

Uploaded by

Pho Pheara
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
209 views4 pages

02 Calculation External Static Pressure For Riser Duct High Speed

The document provides ductwork design calculations for three fans - Fan B1, Fan B2, and the combination of Fans B1 and B2. It includes air flow rates, duct sizes, lengths and fittings for each system. The total external static pressure is calculated as 206 Pa for Fan B1, 323 Pa for Fan B2, and 64 Pa for the riser duct serving both fans.

Uploaded by

Pho Pheara
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

RISER DUCT : 64 Pa

BRANCH DUCT FROM FAN ( B2 ) : 323 Pa

BRANCH DUCT FROM FAN ( B1 ) : 206 Pa

TOTAL EXTERANAL STATIC PRESSURE FOR EACH FAN

FAN B2 : 387 Pa

FAN B1 : 270 Pa
EXTERNAL STATIC PRESSURE CALCULATION (RISER DUCT)

AIR AIR DUCT DUCT EQUIVALENT FRICTION DUCT VELOCITY COEFFICEINT TOTAL
PERIMETER DUCT SIZE
ITEM DESCRIPTOIN FLOW FLOW VELOCITY AREA DIA. LOSS LENGTH PRESSURE LOSS PRESSURE

m3/h L/s m/s m² m mm (Ø) mm Pa/m m Pa Pa

DUCT ( 1 FAN B2 ) 80400 22333.33 12.22 1.83 6.00 2150 X 850 1218 0.96 1.12 89.91 1.07

1 FITTING (Transition:2150x850 to 2050x750) 80400 22333.33 12.22 1.83 6.00 2150 X 850 1218 0.96 89.91 0.071 6.38

DUCT 80400 22333.33 14.53 1.54 5.60 2050 X 750 1098 1.51 0.35 127.02 0.53

2 FITTING (Transition:2150x850 to 2050x750) 80400 22333.33 12.22 1.83 6.00 2150 X 850 1218 0.96 89.91 0.071 6.38

DUCT 80400 22333.33 12.22 1.83 6.00 2150 X 850 1218 0.96 1.55 89.91 1.48

DUCT ( 2 FAN B2+B1 ) 142860 39683.33 21.71 1.83 6.00 2150 X 850 1218 2.89 1.12 283.86 3.23

3 FITTING (Transition:2150x850 to 2050x750) 142860 39683.33 21.71 1.83 6.00 2150 X 850 1218 2.89 283.86 0.071 20.15

DUCT ( 2 FAN B2+B1 ) 142860 39683.33 25.81 1.54 5.60 2050 X 750 1098 4.57 0.35 401.04 1.60

4 FITTING (Transition:2150x850 to 2050x750) 142860 39683.33 21.71 1.83 6.00 2150 X 850 1218 2.89 283.86 0.071 20.15

DUCT ( 2 FAN B2+B1 ) 142860 39683.33 21.71 1.83 6.00 2150 X 850 1218 2.89 1.00 283.86 2.89

TOTAL EXTERNAL STATIC PRESSURE (Pa) 64

Fitting ASHRAE Fitting Loss of


Type of Fitting Parameters
Number No. Coefficent

1 Transition ER4-1 L=0.2, A0/A1=0.84, Ø=28° 0.071


2 Transition ER4-1 L=0.2, A0/A1=0.84, Ø=28° 0.071
3 Transition ER4-1 L=0.2, A0/A1=0.84, Ø=28° 0.071
4 Transition ER4-1 L=0.2, A0/A1=0.84, Ø=28° 0.071

INTERPOLATION FORMULA

𝑋1 − 𝑋 𝑌1 − 𝑌
=
𝑋2 − 𝑋 𝑌2 − 𝑌

C
(𝑌2 −𝑌1)
Y = 𝑌1 + 𝑋 − 𝑋1
(𝑋2−𝑋1)

FIND C AT 28°
X1 = 20 Y1 = 0.15
X = 28 Y= 0.222
X2 = 30 Y2 = 0.24

FIND C AT 0.84 OF AREA


X1 = 0.5 Y1 = 0.222
X = 0.84 Y= 0.071
X2 = 1 Y2 = 0
EXTERNAL STATIC PRESSURE CALCULATION (B1F FAN)

AIR AIR DUCT DUCT EQUIVALENT FRICTION DUCT VELOCITY COEFFICEINT TOTAL
PERIMETER DUCT SIZE
ITEM DESCRIPTOIN FLOW FLOW VELOCITY AREA DIA. LOSS LENGTH PRESSURE LOSS PRESSURE

m3/h L/s m/s m² m mm (Ø) mm Pa/m m Pa Pa

DUCT 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 11.00 181.22 26.09

SUPPLY AIR GRILLE 28 28.00

SILENCER 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 181.22 0.04 7.25

FITTING (Elbow, Mitered) 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 181.22 0.16 28.99

FITTING (Elbow, Mitered) 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 181.22 0.16 28.99

NON RETURN DAMPER 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 181.22 0.04 7.25

FIRE DAMPER 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 181.22 0.19 34.43

FITTING (Tee) 62460 17350.00 17.35 1.00 4.00 1000 X 1000 1000 2.37 181.22 0.25 45.30

TOTAL EXTERNAL STATIC PRESSURE (Pa) 206


EXTERNAL STATIC PRESSURE CALCULATION (B2F FAN)

AIR AIR DUCT DUCT EQUIVALENT FRICTION DUCT VELOCITY COEFFICEINT TOTAL
PERIMETER DUCT SIZE
ITEM DESCRIPTOIN FLOW FLOW VELOCITY AREA DIA. LOSS LENGTH PRESSURE LOSS PRESSURE

m3/h L/s m/s m² m mm (Ø) mm Pa/m m Pa Pa

DUCT 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 11.00 300.26 42.45

SUPPLY AIR GRILLE 28 28.00

SILENCER 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 300.26 0.04 12.01

FITTING (Elbow, Mitered) 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 300.26 0.16 48.04

FITTING (Elbow, Mitered) 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 300.26 0.16 48.04

NON RETURN DAMPER 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 300.26 0.04 12.01

FIRE DAMPER 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 300.26 0.19 57.05

FITTING (Tee) 80400 22333.33 22.33 1.00 4.00 1000 X 1000 1000 3.86 300.26 0.25 75.07

TOTAL EXTERNAL STATIC PRESSURE (Pa) 323