LS (Susol ACB) Up To 1150vac - Catalog - EN - 202011 Nov 25, 2020V1.0

The document discusses an air circuit breaker (ACB) suitable for renewable energy applications up to 1150V. It features frame sizes up to 3200 amps for the E-Frame and 1600 amps for the D-Frame. The ACB provides smart connectivity and electrical status monitoring through an integrated Smart Trip Unit. It is designed for use in harsh environments like high altitudes and is commonly used in photovoltaic, energy storage, and wind power facilities.

Uploaded by

Truong Hung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
285 views20 pages

LS (Susol ACB) Up To 1150vac - Catalog - EN - 202011 Nov 25, 2020V1.0

The document discusses an air circuit breaker (ACB) suitable for renewable energy applications up to 1150V. It features frame sizes up to 3200 amps for the E-Frame and 1600 amps for the D-Frame. The ACB provides smart connectivity and electrical status monitoring through an integrated Smart Trip Unit. It is designed for use in harsh environments like high altitudes and is commonly used in photovoltaic, energy storage, and wind power facilities.

Uploaded by

Truong Hung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

ACB up to 1150Vac

Air Circuit Breaker


up to 1150Vac
For renewable application and high altitude
Air Circuit Breaker up to 1150Vac
Latest “AV” series of LS ELECTRIC is suitable for PV, ESS, Wind Power Facilities in harsh
environment conditions(high altitude, etc).
It also provides smart connectivity and delivers electrical status with Smart Trip Unit
(New digital OCR applications).

2
ACB up to 1150Vac

Air Circuit Breaker


up to 1150Vac

ACB up to 1150Vac Features


• E-Frame: (~ 3200AF)
• D-Frame: (~ 1600AF)
• 1150Vac, 1000Vac, 900Vac, 800Vac
• PV market, high altitude area, wind power
• New OCR (STU)
• Instrumentation precision
- Current/Voltage: 0.5%
- Power: Class 1.0

AV-16D□ AV-32E□
Ampere Frame
~ 1600AF ~ 3200AF
(A) 400 / 630 / 800 /
200 / 400 / 630 /
Rated current (In) 1000 / 1250 /
800 / 1000 /
at 40℃ (A) 1600 / 2000 /
1250 / 1600
2500 / 3200
1150V (kA) 30 50
Rated ultimate
1000V (kA) 42 * 65 *
breaking
900V (kA) 50 * 75 *
capacity (Icu)
800V (kA) 50 * 75 *
* DEKRA CB TBD.

Contents
▪Features 02
▪Air Circuit Breakers 04
▪Smart Trip Unit 09
▪Dimensions 10

3
Air Circuit Breakers

ACB ordering

AV 10 D 3 10 A

Ampere Frame sizes & Rated current


Type No. of poles Connections
Frame phase array (CT SPEC.)
Circuit Breakers 06 630AF 630~1600AF 3 3-pole type (D) Without Draw-out type
D 3P/4P 00
AV 08 800AF 4 4-pole type (D, W) OCR & CT A Automatic connection
Standard RST(N)
10 1000AF 02 200A Fixed type
630~1600AF
13 1250AF 04 400A H Horizontal type
W 4P Reverse
16 1600AF phase type (N)RST 06 630A V Vertical type
08 800A Mixed type
M
10 1000A Horizontal Vertical

13 1250A Mixed type


N
16 1600A Vertical Horizontal

P Front type

06 630AF 630~3200AF 3 3-pole type (E) Without


E 3P/4P Standard 00
08 800AF 4 4-pole type (E, X) OCR & CT
RST(N)
10 1000AF 04 400A
630~3200AF
13 1250AF 06 630A
X 4P Reverse
16 1600AF phase type (N)RST 08 800A
20 2000AF 10 1000A
25 2500AF 13 1250A
32 3200AF 16 1600A
20 2000A
25 2500A
32 3200A
H = 430mm

D
=
37
5m
m

W = 334mm W = 412mm

D-Frame ~ 1600AF E-Frame ~ 3200AF


50kA @900VAC * 75kA @900VAC *
30kA @1150V 50kA @1150V
* DEKRA CB TBD.

4
ACB up to 1150Vac

M1 D1 D1 AX SS1 U1 AL

Auxiliary contact and


Motor power Input power Trip power STU UVT
charge method
MA No motor D0 No input coil D0 No trip coil AX Standard type OFF – Charge 3a3b Refer to U0 No UVT
M1 AC/DC 100V~130V D1 AC/DC 100V~130V D1 AC/DC 100V~130V AC Standard type ON – Charge 3a3b page 7 U1 AC/DC 100V~130V
M2 AC/DC 200V~250V D2 AC/DC 200V~250V D2 AC/DC 200V~250V BX Standard type OFF – Charge 5a5b U2 AC/DC 200V~250V
M3 DC 125V D3 DC 125V D3 DC 125V BC Standard type ON – Charge 5a5b U3 DC 125V
M4 DC 24V~30V D4 DC 24V~30V D4 DC 24V~30V HX High capacity OFF – Charge 5a5b U4 DC 24V~30V
M5 DC 48V~60V D5 DC 48V~60V D5 DC 48V~60V HC High capacity ON – Charge 5a5b U5 DC 48V~60V
M6 AC 380V~415V D6 AC 380V~480V D6 AC 380V~480V CC Standard type ON – Charge 6a6b U6 AC 380V~480V
M7 AC 440V~480V D7 AC 48V D7 AC 48V JC High capacity ON – Charge 6a6b U7 AC 48V
M8 AC 48V GX High capacity OFF – Charge 3a3b * UVT Delay is composed from AC/
DC 48V
GC High capacity ON – Charge 3a3b
TX TCS OFF – Charge 4a4b
TC TCS ON – Charge 5a5b

Option
Symbol
Model Option description
AL AL1 + MRB
A1 AL1 + MRB + RES(AC 110~130V)
A2 AL1 + AL2 + MRB
A3 AL1 + MRB + RES(DC 110~125V)
A4 AL1 + MRB + RES(AC 200~250V)
A5 AL1 + MRB + AUTO RESET
A6 AL1 + AL2 + MRB + AUTO RESET
A7 AL1 + MRB + RES(DC 110~125V) + AUTO RESET *DC only
A8 AL1 + MRB + RES(AC 200~250V) + AUTO RESET *AC only
A9 AL1 + MRB + RES(AC 110~130V) + AUTO RESET *AC only
Y2 AL1 + AL2 + MRB(2b contact)
Y6 AL1 + AL2 + MRB + AUTO RESET(2b contact)
Z2 AL1 + AL2 + MRB(1a1b contact)
Z6 AL1 + AL2 + MRB + AUTO RESET(1a1b contact)
C C Counter
S CS2 Charge switch communication
B B On/Off Button lock
M MI Mechanical interlock)
D DI or MOC Door Interlock or MOC (Mechanism operated cell switch)
K K1 Key Lock
K2 K2 Key Interlock Set
K3 K3 Key Lock Double
R RCS Ready to Close switch
T TM Temperature Monitoring
H1 SHT2 AC/DC 100~130V
H2 SHT2 AC/DC 200~250V
H3 SHT2 DC 125V
Note 1) H4 SHT2 DC 24~30V
H1 SHT2 DC 48~60V
H6 SHT2 AC 380~480V
H7 SHT2 AC 48V
Note 1) Double shunt coil not applicable when using UVT

5
Air Circuit Breakers

ACB Cradle ordering

AL H16D 3 A H E S

Proprietary Rated current and Number of Installation Installation


Cradle shape Shape
format main frame poles method method
LS ACB Cradle H06~16D AH–06~16D 3 3-pole type S W ith ARC Cover
Note)
Automatic Up and down Without safety
A H E
H06~32E AH–06~32E 4 4-pole type connection horizontal type shutter

Up and down With safety


V F
vertical type shutter

Up horizontal type,
M
down vertical type

Up vertical type,
N down horizontal
type

Up and down flat


P
Note) Susol ACB is supplied as an arc cover standard. surface type

6
ACB up to 1150Vac

Trip Unit ordering

N type
N H 0
STU Communication & short circuit detection Control power & frequency
N Normal H No communication + ground fault (Residual earth fault protection) 0 No control power, 60 Hz

Accident indication can be confirmed only by LED 5 No control power, 50 Hz

A type
A H 0
STU Communication & earth leakage detection Control power & frequency
A Ammeter H No communication + ground fault (Residual earth fault protection) 0 No control power, 60 Hz

* Communication is impossible U No communication + earth leakage detection (Earth leakage protection) 1 AC/DC 110V ~ 220V, 60Hz
without control power (AD0, AJ0,
AY0, AO0, AB0, AD5, AJ5.AY5, AO5, F No communication + exterior CT ground fault 5 No control power, 50 Hz
AB5 cannot be implemented)
W No communication + PTA 6 AC/DC 110V~220V, 50Hz
* There is no L, S, I, G output
contact, without control power, D No communication + ground fault (Residual earth fault protection)
(only OCR LED can be checked) -
No output contact for AH0, AH5, J Communication + earth leakage detection (Earth leakage protection)
AM0, AM5, AF5, AW0, AW5
Y Communication + exterior CT ground fault
O Communication + NCT can be used
B Communication + PTA
V No communication + PTA (Ship)

P type
P S 1
STU Communication + Gext, relay element other than NCT Control power & frequency
P Power meter S Communication + Gext, relay element other than NCT 1 AC/DC 110V ~ 220V, 60Hz
J Communication + earth leakage detection (Earth leakage protection) 6 AC/DC 110V ~ 220V, 50Hz
Y Communication + exterior CT ground fault
O Communication + NCT can be used

S type
S S 1
STU Communication + Gext, relay element other than NCT Control power & frequency
S Supreme meter S Communication + Gext, relay element other than NCT 1 AC/DC 110V ~ 220V, 60Hz
J Communication + earth leakage detection (Earth leakage protection) 6 AC/DC 110V ~ 220V, 50Hz
Y Communication + exterior CT ground fault
O Communication + NCT can be used

7
Air Circuit Breakers

Technical data

Characteristics

Number of poles (P) 3/4

Rated operational voltage (Ue) (Vac) 1150

Rated insulation voltage (Ui) (V) 1250

Rated impulse withstand voltage (Uimp) (kV) 12kV

Version Fixed / Withdrawable

Suitability for isolation

Degree of pollution IEC60661-1 3

Certification CB certification according to IEC 60947-2

Brand name Susol AV

Model AV-06D AV-08D AV-10D AV-13D AV-16D AV-06E AV-08E AV-10E AV-13E AV-16E AV-20E AV-25E AV-32E

Ampere Frame (AF) 630 800 1000 1250 1600 630 800 1000 1250 1600 2000 2500 3200

200 400 630 630 800 400 400 630 630 800 1000 1250 1600
Rated current 400 630 800 800 1000 630 630 800 800 1000 1250 1600 2000
(A)
(In max) 630 800 1000 1000 1250 800 1000 1000 1250 1600 2000 2500
1250 1600 1250 1600 2000 2500 3200

1150V (kA) 30 50

Rated ultimate breaking 1000V (kA) 42 * 65 *


capacity (Icu) 900V (kA) 50 * 75 *

800V (kA) 50 * 75 *

Rated serivce breaking


(%) 100
capacity (Ics)

Rated short-timewithstand 1s (kA) 30 50


current (Icw) 3s (kA) 30 50

Rated making capacity (Icm) (%) 100

Utilization category (according to IEC 60947-2) B

Total < Icw max. 70


Breaking
Operation time (ms) time ≥ Icw max. 30

Closing time max. 80

Mechanical and Electrical Life cycle

Endurance (times) Mechanical 12,500


(Without maintenance) Electrical 1,000

Demension and Weight


Without cradle (kg) 37/45 44/49
Drawout
Weight (3P/4P) With cradle (kg) 70/85 88/104

Fixed (kg) 34/44 45/56

External Dimensions Drawout 3P(4P) (mm) 430×334(419)×375 430×412(527)×375


(H×W×D) Fixed 3P(4P) (mm) 300×300(385)×295 300×378(493)×295

* DEKRA CB TBD.
8
Smart Trip Unit ACB up to 1150Vac

Overview

With the world's best measurement accuracy and increased relay elements, the relay operation stability is
enhanced, and the abnormal self-diagnosis function prevents mis-trips and ensures the stability of abnormal
conditions through alarms. NFC and Bluetooth built-in and Smart add-on modules can be configured. Monitoring
and monitoring is possible through service access anytime, anywhere by securing a Smart LV solution through
ICT convergence technology.

Type N Type A Type P Type S

Exterior

Current • L (N), S, I, G, PTA, Gext • L (N), S1, S2, I, G, PTA, Gext


• L (N), S, I, G, PTA • L (N), S, I, G, PTA, Gext
Instrumentation relay • D, S (V), IU • D, S (V) 1, S (V) 2
precision:
Voltage • UV1, UV2, OV1, OV2,
Current/voltage: 0.5% - - • UV, OV, RV, VU
relay RV, VU
Power: Class 1.0
Frequency •U
 F1, UF2, OF1, OF2,
- - • UF, OF, ROCOF
relay ROCOF

Power
- - • RP, RQ, OP, OQ, UP • RP, RQ1, RQ2, OP, OQ, UP
relay

Group • A, B (can be changed by


- - -
control communication)

Relay fine
- - • L, S, I Pickup current -
adjustment

• Control
 by DI and • Control by DI and • Control by DI and
ERMS -
communication communication communication

• Supports L relay • Supports L relay • Supports


 L relay • Supports L relay
IDMTL
element Thermal and DT, element Thermal and DT, element Thermal and DT, element Thermal and DT,
support
SIT, VIT, EIT, EIT5 SIT, VIT, EIT, EIT5 SIT, VIT, EIT, EIT5 SIT, VIT, EIT, EIT5

Trip
information
• L, S, I, G/PTA, SP • L, S, I, G/Gext/PTA, SP • L, S, I, G/Gext/PTA, SP • L , S, I, G/Gext/PTA, SP
maintenance
LED

• 32 accident events • 127 accident events • 127


 accident events
Screen - indicated [Accident indicated [Accident indicated [Accident
phase/current/time] phase/current/time] phase/current/time]
Accident record

• 127 accident events • 127 accident events • 127


 accident events
• 127 accident events indicated indicated indicated
Memory indicated [Accident • 6 accident events • 6 accident events • 6 accident events
phase/current/time] indicated [Does not indicated [Does not indicated [Does not
support Selfpower support Selfpower support Selfpower

9
Dimensions

1600AF Fixed type (200~1600A : AV-06~16D)

Front view

3P 4P

Vertical type

3P 4P

<Conductor>

Door Frame: DF (AH-D/E) 10-Ø9


Panel Door
Door Frame
315(Panel cutting 치수)
100

293(Panel cutting 치수)


108
170
100

165 165
(73)
Cradle bottom

Note) The dimensions are for fixed type.

10
ACB up to 1150Vac

1600AF Fixed type (200~1600A : AV-06~16D)

Horizontal type

3P 4P

<Conductor>

Front connection
type

3P 4P

<Conductor>

11
Dimensions

1600AF Draw-out type (200~1600A : AV-06~16D)

Front view

3P 4P

Vertical type

3P 4P

<Conductor>

Door Frame: DF (AV-D/E)


<External size> <Mounting hole> <Side View> <Panel cutting>

Note) The dimensions are for drawout type.

12
ACB up to 1150Vac

1600AF Draw-out type (200~1600A : AV-06~16D)

Horizontal type

3P 4P

<Conductor>

Front connection
type

3P 4P

<Conductor>

13
Dimensions

3200AF Fixed type (400~3200A : AV-06~32E)

Front view

3P 4P

Vertical type

3P 4P

<Conductor>

14
ACB up to 1150Vac

3200AF Fixed type (400~3200A : AV-06~32E)

Horizontal type

3P 4P

<Conductor>

Front connection
type

3P 4P

<Conductor>

15
Dimensions

3200AF Draw-out type (400~3200A : AV-06~32E)

Front view

3P 4P

Vertical type

3P 4P

<Conductor>

16
ACB up to 1150Vac

3200AF Draw-out type (400~3200A : AV-06~32E)

Horizontal type

3P 4P

<Conductor>

Front connection
type

3P 4P

<Conductor>

17
Memo

18
ACB up to 1150Vac

19
www.lselectric.co.kr

 Headquarter  Overseas Branches


127 LS-ro (Hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do, 14119, Korea • LS ELECTRIC Tokyo Office (Japan)
Tel: 81-3-6268-8241 E-Mail: [email protected]
 Seoul Office
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea • LS ELECTRIC Beijing Office (China)
Tel. 82-2-2034-4916, 4684, 4429 Tel: 86-10-5095-1631 E-Mail: [email protected]
 Overseas Subsidiaries • LS ELECTRIC Shanghai Office (China)
Tel: 86-21-5237-9977 E-Mail: [email protected]
• LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241 E-Mail: [email protected] • LS ELECTRIC Guangzhou Office (China)
• LS ELECTRIC (Dalian) Co., Ltd. (Dalian, China) Tel: 86-20-3818-2883 E-Mail: [email protected]
Tel: 86-411-8730-5872 E-Mail: [email protected]
• LS ELECTRIC Chengdu Office (China)
• LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-28-8670-3201 E-Mail: [email protected]
Tel: 86-510-6851-6666 E-Mail: [email protected]
• LS ELECTRIC Vietnam Co., Ltd. • LS ELECTRIC Qingdao Office (China)
Tel: 84-93-631-4099 E-Mail: [email protected] (Hanoi) Tel: 86-532-8501-2065 E-Mail: [email protected]
Tel: 84-24-3823-7890 E-Mail: [email protected] (Hochiminh) • LS ELECTRIC Nanjing Office (China)
• LS ELECTRIC Middle East FZE (Dubai, U.A.E.) Tel: 86-25-8467-0005 E-Mail: [email protected]
Tel: 971-4-886-5360 E-Mail: [email protected]
• LS ELECTRIC Bangkok Office (Thailand)
• LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands) Tel: 66-90-950-9683 E-Mail: [email protected]
Tel: 31-20-654-1424 E-Mail: [email protected]
• LS ELECTRIC America Inc. (Chicago, USA) • LS ELECTRIC Jakarta Office (Indonesia)
Tel: 1-800-891-2941 E-Mail: [email protected] Tel: 62-21-2933-7614 E-Mail: [email protected]
• LS ELECTRIC Moscow Office (Russia)
Tel: 7-499-682-6130 E-Mail: [email protected]
• LS ELECTRIC America Western Office (Irvine, USA)
Tel: 1-949-333-3140 E-Mail: [email protected]

Specifications in this catalog are subject to change without notice due to


2020. 11 continuous product development and improvement.
ⓒ2020. 11 LS ELECTRIC Co., Ltd. All rights reserved. / English (01) 2020. 11 Staffcom