0% found this document useful (0 votes)
103 views

Esquematico de Control SDV-360

1. The document is a diagram showing the components of an actuator system in the failed closed position, including two solenoid valves (A and B), limit switches, pressure switches, and electrical connections. 2. It provides instructions for operating the actuator system in three different modes: remote operation using high/low pressure, remote operation only, and automatic closing only. 3. The diagram labels and explains the components of the system and how energizing or de-energizing the solenoid valves causes the actuator to open or close depending on the mode selected.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
103 views

Esquematico de Control SDV-360

1. The document is a diagram showing the components of an actuator system in the failed closed position, including two solenoid valves (A and B), limit switches, pressure switches, and electrical connections. 2. It provides instructions for operating the actuator system in three different modes: remote operation using high/low pressure, remote operation only, and automatic closing only. 3. The diagram labels and explains the components of the system and how energizing or de-energizing the solenoid valves causes the actuator to open or close depending on the mode selected.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

1 2 3 4

DRAWN WITH ALL COMPONENTS SHOWN IN FAILED POSITION


SYMBOLS ACTUATOR CLOSING DIRECTION: CW FAIL MODE: CLOSE
L/S LIMIT SWITCH
P/S PRESSURE SWITCH CUSTOMER
SA SOLENOID VALVE "A" 2 CLOSE

CONDUIT OPERATION INSTRUCTION


SB SOLENOID VALVE "B" BY OTHERS CONNECTION
HIGH PRESSURE AIR LINE 3/4"NPT 1. REMOTE OPERATION WITH HIGH/LOW PRESSURE CLOSE
PILOT PRESSURE AIR LINE
BALL VALVE ITEM 9 IN POSITION 1-2
EC EC L/S BALL VALVE ITEM 24 IN POSITION 1-2
EC ELECTRICAL CONNECTIONS
ENERGIZE BOTH SOLENOIDS TO OPEN THE ACTUATOR
D DE-ENERGIZE EITHER SOLENOID TO CLOSE THE ACTUATOR
WHEN SENSING PRESSURE IS LOWER THAN LOW SET OR
D
HIGHER THAN HIGH SET THE ACTUATOR WILL CLOSE
P/S EC
1 2. REMOTE OPERATION ONLY
BALL VALVE ITEM 9 IN 1-2
EC BALL VALVE ITEM 24 IN POSITION 1-3
4 ENERGIZE BOTH SOLENOIDS TO OPEN THE ACTUATOR
DE-ENERGIZE EITHER SOLENOID TO CLOSE THE ACTUATOR
3
6 7 5
3. AUTOMATIC CLOSING ONLY
BY OTHERS
BALL VALVE ITEM 9 IN POSITION 1-3
BALL VALVE ITEM 24 IN POSITION 1-2
THE ACTUATOR WILL CLOSE WHEN SENSING PRESSURE
CONTROL CABINET WILL BE LOWER THAN LOW SET OR HIGHER THAN HIGH SET
CLOSE
24VDC 9
P/S EC 8 1
2 3
L/S EC EC
EC
C EC P/S C
10
MOUNTED ON EC P/S
PARTIAL STROKE
24VDC
DEVICE
1/4"FNPT
SA EC 14
BY OTHERS EC EC 11 12

24VDC
BY OTHERS 1/4"OD
SB EC 13
P/S 24

30
15 1
26 2 3
EC 1/2"OD 18
50 ALL TUBE CONNECTIONS ARE SWAGELOK TYPE
33 BALL VALVE (DRAIN)
31 19 25 32 BACK UP TANK 1

B 1173 PSI
SET
427 PSI
SET
30
26
PRESSURE RELIEF VALVE
BALL VALVE
1
B
1/2"FNPT
16 25
24
PRESSURE SENSOR (LOW PRESSURE SET)
BALL VALVE (AUTOMATIC FUNCTION ON/OFF)
1
1
20 23 BALL VALVE 1
32 EC 22 CHECK VALVE 1
21 BALL VALVE 1

21 23 20
19
FILTER REGULATOR
PRESSURE SENSOR (HIGH PRESSURE SET)
1
1
18 BALL VALVE 1

22 17 PRESSURE SWITCH 120 PSI SET (LOW SUPPLY PRESSURE) 1

17 16
15
BALL VALVE
PRESSURE SWITCH (BACK UP TANK LOW PRESSURE )
1
1
14 SOLENOID DIRECTIONAL CONTROL VALVE "A" 1
EC P/S 13 SOLENOID DIRECTIONAL CONTROL VALVE "B" 1
12 PRESSURE SWITCH (SOLENOID "A" FAILURE) 1
11 PRESSURE SWITCH (SOLENOID "B" FAILURE) 1
10 JUNCTION BOX 1
SUPPLY PRESSURE SENSING PRESSURE 9 BALL VALVE (REMOTE OPERATION ON/OFF) 1
1/2"FNPT 1/4"FNPT
CUSTOMER CONNECTION CUSTOMER CONNECTION 8 PILOT VALVE 1
7 SOLENOID VALVE (PARTIAL STROKE ON/OFF) 1
6 LIMIT SWITCH 1
5 BLEED CONTROL VALVE 1
4 PRESSURE SWITCH 80 PSI SET (ACTUATOR DE-PRESSURIZED) 1

A 3
2
QUICK EXHAUST VALVE
LIMIT SWITCH
1
1
A
1 ROTORK SR.ACTUATOR 1
ITEM DESCRIPTION QTY

LIST OF PARTS
SR.ACTUATOR,DCV,L/S,F/R,
www. .com BACKUP TANK
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: AK Schematic Diagram No Issue
BATH, BA1 3JQ ROCHESTER Date : 031113 No
02 031113 RS ITEM 26 ADDED
01 011713 RS FIRST ISSUE
Iss Date Chkd Revision Details
ENGLAND
Tel:01225-733200
NY 14624, USA
Tel:585-247-2304
Job No : B51878
MI No : --
PS21599 02