EXT RC.. 24 Datasheet en AP

The document describes the EXT-RC series of proportional and floating thermostats used to control room temperature in commercial applications. It has an LCD display that shows temperature and settings, and can control cooling, heating, or ventilation. It provides on/off or modulating control of temperature and has options for single or three-speed fan control.

Uploaded by

Cuajinike1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views3 pages

EXT RC.. 24 Datasheet en AP

The document describes the EXT-RC series of proportional and floating thermostats used to control room temperature in commercial applications. It has an LCD display that shows temperature and settings, and can control cooling, heating, or ventilation. It provides on/off or modulating control of temperature and has options for single or three-speed fan control.

Uploaded by

Cuajinike1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

EXT-RC..

-24
Application
EXT-RC series of proportional and floating thermostats are
used to control room temperature in commercial applications.

Features
• LCD with green backlight
• Detects and displays room temperature
• On/Off, modulating control for cooling or heating valve
• Room temperature setting
• Fahrenheit (°F) or Celsius (°C) display
• Selectable single or three speed fan control
• Remote sensor input

Technical data
Electrical data Power AC 24V ±10%, 50Hz/60Hz
Rated power < 1W
Output signal AC 24V x 2 (0.5A resistive)
EXT-RCP-24 0-10 VDC (5mA)/ 4-20 mA (600Ω)
Output signal AC 24V x 2 (0.5A resistive)
EXT-RCF-24 floating point control
Input signal Dry contact (NO)
Functional data Set temperature range 0° to 99.5° adjustable
Accuracy displayed 0.1°
Accuracy ±0.5°
Sensor type NTC
Display LCD
Dimensions Dimensions See <<Dimensions>>

Basic Features
Working modes Cooling , Heating , Ventilating , Auto
Fan speed 3 speed ( Low , Medium , High ) / Auto

Operation Instructions
On/Off Press button.
Setpoint Press to reduce the setpoint, press to
increase the setpoint in 0.5°C increments. The
setpoint will be confi rmed automatically after 5
seconds and then will return to display status.
Press or to check setpoint.
Mode Press to change the working mode-Cooling ,
Heating , Vent .
Fan speed Press to select the desired speed-low ,
medium ,high ,or auto .If single speed fan is
chosen, only medium speed will be available.
Auto fan speed The fan speed will be changed automatically to
the following: Low speed- when room temperature
is 1° difference with setpoint. Med. speed- when
room temperature is 2° difference with setpoint.
High speed- when room temperature is 3°
difference with setpoint.
Sleep Thermostat will go into sleep function after
programming.
To set sleep mode Press button for 3 seconds until display
shows. A countdown will start in the center of the
screen. Use or to adjust the desired sleep
time. The maximum setting is 48 hours.
Thermostat will return to working status after 5
seconds. will flash to start countdown. The
setpoint will be replaced by the sleep setpoint.
V1.0 12.2018•Subject to modification

To quit sleep mode When the thermostat is in sleep function, will


flash. Press or to quit.
Keypad lock Press and for 10 seconds. This will activate
the display. under this function, the keypad is
locked. To unlock, press and for 10 seconds
until disappears.
Set parameters With thermostat off, press for 10 seconds to
enter the menu to set all parameters.

1
EXT-RC..-24

Parameter Settings
Parameter Description Default Range
1 Power on status (0: off, 1: on, 2: hold) 2 -
2 Fan speed (0: single speed, 1: three speed) 1 -
3 Fan mode (DA: When the 0 -
temperature reaches the set-
point, the valve will close with the
fan still running. DB: When the
temperature reaches the set-
point, the valve will close and the
fan will shut off.)
4 Sensor selection (0: internal, 1: remote) 0 -
5 Temp. display (0: Celsius, 1: Fahrenheit) 0 -
6 Temperature calibration 0 -20 to +20
7 Minimum setpoint 5° / 41° 0 to 99
8 Maximum setpoint 35° / 96° 0 to 99.5
9 Dead band 2 -

Modulating Output Options

Location ON OFF
1 120 ohm resistance between AB wires No resistance between AB wires
2 Port 1 modulation 0-20 mA Off
3 Port 1 modulation 0-10 VDC Off
4 Port 2 modulation 0-20 mA Off
5 Port 3 modulation 0-10 VDC Off
Note: Switch (5 pole switch on PCB)

Dimensions (mm)

Wiring Diagrams

COM ~
M 0-10V
L /4-20mA L
~ TR
V+ ~
24VAC N 24VAC TR
Modulating Control N
CLOSE
VC Cooling/Heating

OPEN
VO A A
Floating Control
Cooling/Heating
L B L B
HI Input HI Input
MED Input
MED Input

Fan LOW RS Fan LOW RS


Remote Sensor
EXT-RCF-24 EXT-RCP-24 Remote Sensor

EXT-RCF-24
V1.0 12.2018•Subject to modification

EXT-RCP-24

2
EXT-RC..-24

Installation Manual

1 Open the back panel with a screwdriver. 2 Connect the wires per the wiring diagram.

3 Secure the base with the screws provided. 4 Reattach the front panel.

V1.0 12.2018•Subject to modification