EXT RC.. 24 Datasheet en AP
EXT RC.. 24 Datasheet en AP
-24
Application
EXT-RC series of proportional and floating thermostats are
used to control room temperature in commercial applications.
Features
• LCD with green backlight
• Detects and displays room temperature
• On/Off, modulating control for cooling or heating valve
• Room temperature setting
• Fahrenheit (°F) or Celsius (°C) display
• Selectable single or three speed fan control
• Remote sensor input
Technical data
Electrical data Power AC 24V ±10%, 50Hz/60Hz
Rated power < 1W
Output signal AC 24V x 2 (0.5A resistive)
EXT-RCP-24 0-10 VDC (5mA)/ 4-20 mA (600Ω)
Output signal AC 24V x 2 (0.5A resistive)
EXT-RCF-24 floating point control
Input signal Dry contact (NO)
Functional data Set temperature range 0° to 99.5° adjustable
Accuracy displayed 0.1°
Accuracy ±0.5°
Sensor type NTC
Display LCD
Dimensions Dimensions See <<Dimensions>>
Basic Features
Working modes Cooling , Heating , Ventilating , Auto
Fan speed 3 speed ( Low , Medium , High ) / Auto
Operation Instructions
On/Off Press button.
Setpoint Press to reduce the setpoint, press to
increase the setpoint in 0.5°C increments. The
setpoint will be confi rmed automatically after 5
seconds and then will return to display status.
Press or to check setpoint.
Mode Press to change the working mode-Cooling ,
Heating , Vent .
Fan speed Press to select the desired speed-low ,
medium ,high ,or auto .If single speed fan is
chosen, only medium speed will be available.
Auto fan speed The fan speed will be changed automatically to
the following: Low speed- when room temperature
is 1° difference with setpoint. Med. speed- when
room temperature is 2° difference with setpoint.
High speed- when room temperature is 3°
difference with setpoint.
Sleep Thermostat will go into sleep function after
programming.
To set sleep mode Press button for 3 seconds until display
shows. A countdown will start in the center of the
screen. Use or to adjust the desired sleep
time. The maximum setting is 48 hours.
Thermostat will return to working status after 5
seconds. will flash to start countdown. The
setpoint will be replaced by the sleep setpoint.
V1.0 12.2018•Subject to modification
1
EXT-RC..-24
Parameter Settings
Parameter Description Default Range
1 Power on status (0: off, 1: on, 2: hold) 2 -
2 Fan speed (0: single speed, 1: three speed) 1 -
3 Fan mode (DA: When the 0 -
temperature reaches the set-
point, the valve will close with the
fan still running. DB: When the
temperature reaches the set-
point, the valve will close and the
fan will shut off.)
4 Sensor selection (0: internal, 1: remote) 0 -
5 Temp. display (0: Celsius, 1: Fahrenheit) 0 -
6 Temperature calibration 0 -20 to +20
7 Minimum setpoint 5° / 41° 0 to 99
8 Maximum setpoint 35° / 96° 0 to 99.5
9 Dead band 2 -
Location ON OFF
1 120 ohm resistance between AB wires No resistance between AB wires
2 Port 1 modulation 0-20 mA Off
3 Port 1 modulation 0-10 VDC Off
4 Port 2 modulation 0-20 mA Off
5 Port 3 modulation 0-10 VDC Off
Note: Switch (5 pole switch on PCB)
Dimensions (mm)
Wiring Diagrams
COM ~
M 0-10V
L /4-20mA L
~ TR
V+ ~
24VAC N 24VAC TR
Modulating Control N
CLOSE
VC Cooling/Heating
OPEN
VO A A
Floating Control
Cooling/Heating
L B L B
HI Input HI Input
MED Input
MED Input
EXT-RCF-24
V1.0 12.2018•Subject to modification
EXT-RCP-24
2
EXT-RC..-24
Installation Manual
1 Open the back panel with a screwdriver. 2 Connect the wires per the wiring diagram.
3 Secure the base with the screws provided. 4 Reattach the front panel.