OC SC Test Test On Transformer
OC SC Test Test On Transformer
The ammeter reading gives the no load current I . As no load current I is quite small compared to
e e
rated current of the transformer, the voltage drops due to this electric current then can be taken as
negligible.
Since, voltmeter reading V can be considered equal to secondary induced voltage of the transformer.
1
The input power during test is indicated by watt-meter reading. As the transformer is open circuited,
there is no output hence the input power here consists of core losses in transformer and copper loss
in transformer during no load condition. But as said earlier, the no load current in the transformer is
quite small compared to full load current so copper loss due to the small no load current can be
neglected. Hence the wattmeter reading can be taken as equal to core losses in transformer. Let us
consider wattmeter reading is P . o
P = V /R
o 1
2
m
1|Page
If, Z is shunt branch impedance of transformer.
m
Then, Z = V / I .
m 1 e
These values are referred to the LV side of transformer as because the test is conduced on LV side of
transformer. These values could easily be referred to HV side by multiplying these values with
square of transformation ratio.
Therefore it is seen that the open circuit test on transformer is used to determine core losses in
transformer and parameters of shunt branch of theequivalent circuit of transformer.
the voltage, applied for full load current in short circuit test on transformer, is quite small compared
to rated primary voltage of the transformer, the core losses in transformer can be taken as negligible
here.
Let’s, voltmeter reading is V . The input power during test is indicated by watt-meter reading. As the
sc
transformer is short circuited, there is no output hence the input power here consists of copper
2|Page
losses in transformer. Since, the applied voltage V is short circuit voltage in the transformer and
sc
hence it is quite small compared to rated voltage so core loss due to the small applied volate can be
neglected. Hence the wattmeter reading can be taken as equal to copper losses in transformer. Let us
consider wattmeter reading is P . sc
P = R .I
sc e L
2
Then, Z = V / I .
e sc L
Then, X = Z – R
e
2
e
2
e
2
These values are referred to the HV side of transformer as because the test is conduced on HV side of
transformer. These values could easily be referred to LV side by dividing these values with square of
transformation ratio.
Therefore it is seen that the Short Circuit test on transformer is used to determine copper loss in
transformer at full load and parameters of approximate equivalent circuit of transformer.
3|Page