Oil Analysis Variout Tests

The document discusses various tests that can be performed on transformer oil, including dissolved gas analysis, acidity, electric strength, fibre estimation, colour, PCB analysis, metal in oil analysis, furfuraldehyde analysis, and water content. Dissolved gas analysis is described as the most reliable tool for detecting incipient faults in transformers by analyzing fault gases dissolved in the oil. High acidity, moisture content, and fibers can accelerate degradation of insulation. Metal particle analysis in oil can help determine the location and type of faults. Together, oil analysis tests can detect transformer issues early and improve reliability.

Uploaded by

Hiren Vasani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views

Oil Analysis Variout Tests

The document discusses various tests that can be performed on transformer oil, including dissolved gas analysis, acidity, electric strength, fibre estimation, colour, PCB analysis, metal in oil analysis, furfuraldehyde analysis, and water content. Dissolved gas analysis is described as the most reliable tool for detecting incipient faults in transformers by analyzing fault gases dissolved in the oil. High acidity, moisture content, and fibers can accelerate degradation of insulation. Metal particle analysis in oil can help determine the location and type of faults. Together, oil analysis tests can detect transformer issues early and improve reliability.

Uploaded by

Hiren Vasani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

Transformer Oil Analysis

As well as the oil analysis package, Vibrotech Reliability Services also provide the full range of tests available for
transformer oils. Tests include the provision of sample bottles.

The full list and explanation of Transformer oil tests are detailed below:

Transformer Oil Tests


1. Dissolved Gas Analysis
2. Acidity
3. Electric Strength
4. Fibre Estimation
5. Colour
6. Polychlorinated Biphenyl Analysis
7. Metal in Oil Analysis
8. Furfuraldehyde Analysis
9. Water Content
10. Resistivity

Dissolved Gas Analysis

Dissolved Gas Analysis is widely accepted as the most reliable tool for the earliest detection of incipient faults in
transformers and tap selector units. Hydrocarbon (mineral-based) oils and silicones are used as insulation fluids
in transformers because of their high dielectric strength, heat transfer properties and chemical stability. Under
normal operating conditions very little decomposition of the dielectric fluid occurs. However, when a thermal or
electrical fault develops, dielectric fluid and solid insulation will partially decompose. The low molecular weight
decomposition gases include hydrogen, methane, ethane, ethane, ecetylene, carbon monoxide and carbon
dioxide. These fault gases are soluble in the dielectric fluid. Analysis of the quantity of each of the fault gases
present in the fluid allows identification of fault processes such as corona, sparking, overheating and arcing.

Acidity

The acidity level of transformer oil is measured to BS2000 Part1:1982 (also IP 1/74 method A).

High acidities accelerate the degradation of the paper insulation and causes corrosion of the steel tanks. Oil
Analysis Services normally suggests changing the oil when the acidity approaches 0.3mgKOH/g, but expresses
concern when it reaches 0.1mgKOH/g. It is believed that acidity increases exponentially with time.

Electric Strength

A measure of the ability of an insulating fluid to withstand electric stress (voltage) without failure. Fluids with high
dielectric strength (usually expressed in volts or kilovolts), are good electrical insulators.

Fibre Estimation

An estimation of the fibre content in an oil sample is made by passing polarised light through the oil, clearly
showing the fibres and any sediment which is present in the oil. The fibres are classed as being long(greater than
5mm), medium(2 to 5 mm) or short(less than 2 mm), and the number of fibres present is classed as few(1 to 5) or
many(more than10). Sediment is classed as being either light, medium or heavy.

The presence of fibres in an oil sample, especially in combination with a high water content, may result in a poor
electric strength measurement. This is because wet fibres are drawn into the electrical field and cause arcing to
occur.

Fibres (& moisture) can easily be picked up during sampling and as such, it is important to ensure that sampling
is correctly carried out. By following the sampling technique recommended by us, the oil sample will be more
representative of the bulk oil in the transformer and test results will be more reliable. We can supply the sampling
devices in order to ensure that samples that are collected are representative.
Colour

In the past, there used to be a British Standard which gave a range of colours from 1-10; 1 being white/yellow
and 10 being dark brown/black heavily oxidised oil. We use a similar colour range to gauge if there is any sudden
deterioration in the oil during the time it is being analysed for different species.

Colour has also been useful in the past as a cross check of the sample identity. For example, a sudden change
from dark to light colour can indicate an oil change or incorrect sample designation.

Polychlorinated Biphenyl Analysis

In the past, PCB’s were insulating liquids used for their non-flammable properties, mainly in transformers where a
fire would be unacceptable, and as the dielectric fluid in capacitors. Unfortunately, the mineral oil used in
transformers, switchgear etc. has become cross-contaminated over the years bys PCB fluid being placed in dirty
mineral oil tanks, by using oil conditioning equipment for both mineral and PCB liquids and by capacitors leaking
into mineral oil systems.

PCB’s are fairly non-biodegradable and do tend to collect in food chains and as a result, legislation has been
brought in to prevent widespread contamination. Liquids containing over 50mg/kg(or 50 ppm by weight) must be
classed as injurious substances and disposal must be by high temperature incineration, which is expensive. In
fact oil suppliers have agreed not to supply oil containing more than 10mg/kg and by the same token, any oil
taken away over 10mg/kg is expensive to dispose of even though it may not be as high as 50/mg/kg.

We use capillary column chromatography to determine the PCB concentration in oil. Oil Analysis Services
identifies the three main types of PCB i.e. 1242, 1254 and 1260 and reports the total PCB content present.

Metal in Oil Analysis

Metal in oil analysis of transformer oil is used to complement dissolved gas analysis(DGA). When gas in oil
analysis indicates the presence of a possible fault, metal in oil analysis will help determine the fault type and
pinpoint its location.

High energy faults not only degrade the transformer’s insulation(oil, paper, wood etc) but can generate metal
particles that will disperse in the oil. These particles will be distributed throughout the transformer, mainly due to
oil circulation. Certain transformer components produce specific metal particles. These metal particles will be
found alone or in differing combinations and concentrations. The type of particles will help to narrow the list of
components involved in the fault.

Metals that may be found in transformer oil are: aluminium, copper, iron, lead, silver, tin and zinc. For example,
copper would be found in the windings and also any bronze or brass components. Lead is found in soldered
joints, connectors and other peripheral components. Iron is located in the transformer core and tank, whereas
aluminium can be found in the windings, corona shields and ceramic bushings. Lugs, bolts, connectors and some
peripheral components may also contain tin, silver and zinc.

Metal in oil analysis can be performed using different methods. Atomic absorption spectroscopy(AA) and
inductive coupled plasma spectrometry(ICP) are two examples of the techniques used to measure metal
concentrations in oil. Typically the metal particles contained in the sample will be burned at high temperatures to
produce free metal atoms. The presence of these atoms in a flame(AA) or in a plasma(ICP) can be quantified by
measuring the absorption(AA) or emission(ICP) of discrete frequencies in the radiation spectrum by the free
metal atoms against a known standard. We use an inductively Coupled Plasma Emission Spectrometer(ICP) to
measure the metal concentrations in oil.

There are no established threshold levels for metal in oil, but as data is being generated and cases documented,
metal in oil analysis is becoming another proven tool used to detect transformer faults well before they escalate
into major problems.

One metal in oil analysis report is not enough to get a true picture of the units health. Subsequent tests should be
performed to trend the results and look for developing problems. Results are provided in history table form and
can be represented graphically.

Furfuraldehyde Analysis

Provided the oil inside a transformer has been well maintained and there is no serious defect, the life of a
transformer often depends upon the state of the paper insulation on the windings. It has been shown that in oil,
as the paper degrades and becomes weaker, furfuraldehyde is one of the many degradation products. It has also
been shown that a linear relationship exists between the logarithm of the mass of furfuraldehyde produced and
the resulting degree of polymerisation(DP) or strength of the paper. When the DP falls to approximately 250, the
paper insulation is very brittle and the transformer can be considered to have reached the end of its service life.
Therefore by measuring the furfuraldehyde concentration in the oil, the remaining service life of the transformer
can be estimated.

Water Content

The water content of an oil sample is measured using an automatic Mitsubishi moisture meter, which is based on
the Karl Fischer titration and coulometric end-point. All laboratories use these instruments now to measure
dissolved water and probably over 90% use the Mitsubishi model. The instrument is calibrated electronically but
is checked with the aid of standard water in methanol solutions. The water content is given in mg/kg(ppm).

For an oil sample originating from a 33kV transformer, the water content is normally considered to be a little high
when it reaches 25mg/lg(ppm) and too high when it reaches 30mg/kg)ppm). These limits vary depending upon
the source of the oil sample.

Moisture, in combination with the fibre in main tanks and selectors and carbon in diverters, dramatically reduces
the electric strength of the oil to very unsafe levels which can result in plant failure.

In tests conducted on a population of 100 primary transformers ranging from 132kV down to 33kV all with on load
tap changers, the loss due to failure of selectors and main tank windings averaged about one per year. During
the following period of 8 years in which moisture was monitored on an annual basis and controlled, with 30 ppm
set as the value at which units were llovaced, the loss was reduced by approximately 90%, average moisture
content being about 18 ppm.

Establishing the importance of moisture did not negate the sue of DGA. DGA was adopted as a very useful
partner to moisture analysis and testing was carried out on an annual basis. This enabled fault trends to be
monitored and remedial action to be taken before fault damage and supply loss occurred. It also allowed capital
replacement programs for the plant to be more accurately determined.

Resistivity

The resistivity of a liquid is a measure of its electrical insulating properties under conditions comparable to those
of the test.

High resistivity reflects low content of free ions and ion-forming particles and normally indicates a low
concentration of conductive contaminants.

These characteristics are very sensitive to the presence in the oil of soluble contaminants and ageing products.

Resistivity is normally carried out at ambient temperature but useful additional information can be obtained if the
test is carried out at ambient and a higher temperature such as 90degrees celcius.

Unsatisfactory results at both temperatures indicate a greater extent of contamination than a poor value at the
lower temperature only, and the oil is therefore less likely to be restored to a satisfactory level by drying and low
temperature filtration.