Electrical Network Protection Protection Guide
Electrical Network Protection Protection Guide
Protection guide
Guide
Anewpathforachieving
yourelectricalinstallations
A comprehensive offer
TheProtectionGuidecompletestheperfectlycoordinated
offerofproductswhichmeetallmediumandlowvoltage
electricaldistributionrequirements.Alloftheseproductshave
beendesignedtoworktogether:electrical,mechanicaland
communicationcompatibility.
Theelectricalinstallationisthusbothoptimisedandhasimproved
performance:
bbetterservicecontinuity,
bincreasedpersonnelandequipmentsafety,
bguaranteedupgradeability,
befficientmonitoringandcontrol.
Youthereforehavealltheadvantagesathandintermsof
knowhowandcreativityforachievingoptimised,safe,upgradeable
andcompliantinstallations.
SchneiderElectricisassociatingitself
withyourknow-howandyourcreativity
toproduceoptimised,safe,upgradeable
andcompliantinstallations
For a real partnership with you
Auniversalsolutiondoesn’texistbecauseeachelectrical
installationisspecific.Thevarietyofcombinationsonofferallows
youtotrulycustomisethetechnicalsolutions.
Youareabletoexpressyourcreativityandputyourknow-howto
bestadvantagewhendesigning,manufacturingandexploitingan
electricalinstallation.
Protection guide Contents
Presentation 2
Power-system architecture
Selection criteria 4
Examples of architectures 5
Neutral earthing
Five neutral earthing systems 6
Isolated neutral 7
Resistance earthing 8
Low reactance earthing 9
Compensation reactance earthing 10
Solidly earthed neutral 11
Short-circuit currents
Introduction to short-circuits 12
Types of short-circuit 14
Short-circuit across generator terminals 16
Calculation of short-circuit currents 17
Equipment behaviour during short-circuits 18
Sensors
Phase-current sensors (CT) 19
Phase-current sensors (LPCT) 21
Residual-current sensors 22
Voltage transformers (VT) 23
Protection functions
General characteristics 24
List of functions 26
Associated functions 27
Discrimination
Time-based discrimination 28
Current-based discrimination 30
Logic discrimination 31
Directional protection discrimination 32
Differential protection discrimination 33
Combined discrimination 34
Power-system protection
Single-incomer power systems 36
Dual-incomer power systems 38
Open loop power systems 40
Closed loop power systems 41
Busbar protection
Types of faults and protection functions 42
Link (line and cable) protection
Types of faults and protection functions 44
Transformer protection
Types of faults 46
Protection functions 47
Recommended settings 48
Examples of applications 49
Motor protection
Types of faults 50
Protection functions 51
Recommended settings 53
Examples of applications 54
Generator protection
Types of faults 55
Protection functions 56
Recommended settings 58
Examples of applications 59
Capacitor protection
Types of faults 60
Protection functions 61
Recommended settings and examples of applications 62
Appendices
Glossary - Key words and definitions 64
Bibliography 66
Definitions of symbols 67
Index of technical terms 68
1
Presentation Protection guide 0
The design of protection for a power system can be broken down into two distinct
steps:
b definition of the protection system, also called the protection-system study,
b determination of the settings for each protection unit, also called protection
coordination or discrimination.
b measurement sensors (current and voltage) supplying the data required to detect
faults,
b protection relays in charge of continuously monitoring the electrical status
Measurement of the power system up to and including the formulation and emission of orders
to the trip circuit to clear the faulty parts,
Processing
Sensor
b switchgear in charge of clearing faults, such as circuit breakers or combinations
of switches or contactors and fuses.
The protection-system study determines the devices to be used to protect against
Protection
relay
the main faults affecting the power system and the machines:
b phase-to-phase and phase-to-earth short-circuits,
Fig. 1. Protection system.
b overloads,
b faults specific to rotating-machines.
The protection-system study must take the following parameters into account:
b power system architecture and size, as well as the various operating modes,
b the neutral-earthing systems,
b the characteristics of current sources and their contributions in the event of a fault,
b the types of loads,
b the need for continuity of service.
2
Presentation Protection guide 0
Power-system study
This is a theoretical section presenting the information required to carry out a protection-
system study covering the following points:
b power-system architecture - what are the main architectures used in medium-voltage
DE57358
51
51N
power systems?
A
b neutral earthing systems - what are the main neutral earthing systems in medium
voltage and what are the selection criteria?
b short-circuit currents - what are their characteristics, how are they calculated
and how do electrical devices react?
49 b measurement sensors - how should instrument transformers for current
and voltage be used?
B 51
b protection functions - what functions do protection units provide
51N
b power systems,
b busbars,
b lines and cables,
12
b transformers,
14
27D
27R b motors,
b generators,
46
b capacitors,
48-51LR
49RMS
26 51
and the protection units required for each type of fault, with setting
recommendations and application examples.
63 51G
49T 66
87T
38/
M 49T
3
Power-system Selection criteria 0
architecture
4
Power-system Examples of architectures 0
architecture
DE55362EN
or
NO Unless indicated
otherwise, all switchgear
is NC.
NO
NO
NC
DE55363EN
DE55364EN
or
NO
NC NO NO NC
NC NC
or
NO
NO NC NO NC NO NO NC
NC
NO
NC NC
DE55365EN
DE55366EN
or or
NO NO
NC NC NC NO NC NC NC NC NC NC NC NC
G G G
DE55367EN
DE55368EN
NO
NC NC
or or source
NO NO changeover
NC
5
Neutral earthing Five neutral earthing systems 0
Fault current that is too high produces a whole series of consequences related to
the following:
b damage caused by the arc at the fault point; particularly the melting of magnetic
circuits in rotating machines,
Fig. 1. Equivalent diagram of a power system b thermal withstand of cable shielding,
with an earth fault. b size and cost of earthing resistor,
b induction in adjacent telecommunication circuits,
b danger for people created by the rise in potential of exposed conductive parts.
Unfortunately, optimizing one of these requirements is automatically to the
disadvantage of the other. Two typical neutral earthing methods accentuate
this contrast:
b isolated neutral, which eliminates the flow of earth fault current through the neutral
but creates higher overvoltages,
b solidly earthed neutral, which reduces overvoltage to a minimum, but causes high
fault current.
As for the operating considerations, according to the neutral earthing method used:
b continued operation may or may not be possible after a persisting first fault,
b the touch voltages are different,
b protection discrimination may be easy or difficult to implement.
An in-between solution is therefore often chosen, i.e. neutral earthing
via an impedance.
6
Neutral earthing Isolated neutral 0
Block diagram
There is no intentional earthing of the neutral point, except for measurement
or protection devices.
DE57202
Operating technique
V
In this type of power system, a phase-to-earth fault only produces a low current
through the phase-to-earth capacitances of the fault-free phases (fig. 1).
It can be shown that Ik1 = 3 • C • ω • V where:
b V is the phase-to-neutral voltage,
b C is the phase-to-earth capacitance of a phase,
b ω is the angular frequency of the power system defined as ω = 2 • π • f
C C C
Ik1
The fault current Ik1 can remain for a long time, in principle, without causing
any damage since it is not more than a few amperes (approximately 2 A per km
Ic
for a 6 kV single-core cable with a cross-section of 150 mm2 , XLPE insulation and a
capacitance of 0.63 mF/km). Action does not need to be taken to clear this first fault,
Fig. 1. Capacitive fault current in isolated neutral system. making this solution advantageous in terms of maintaining service continuity.
However, this entails the following consequences:
b the insulation must be continuously monitored and faults that are not yet cleared
must be indicated by an insulation monitoring device or by a neutral voltage
displacement protection unit (ANSI 59N) (fig. 2),
b subsequent fault tracking requires complex automatic equipment for quick
identification of the faulty feeder and also maintenance personnel qualified
DE55203EN
Advantage
The basic advantage is service continuity since the very low fault current does not
I MD
cause automatic tripping for the first fault; it is the second fault that requires tripping.
Drawbacks
b The failure to eliminate transient overvoltages through the earth can be a major
Fig. 2. Insulation monitoring device (IMD).
Protection function
IrsdA
The faulty feeder may be detected by a directional earth fault protection unit
(ANSI 67N) (fig. 3).
The diagram shows that discrimination is implemented by a comparison of the
phase displacement angle between the residual voltage and residual currents, for
the faulty feeder and for each fault-free feeder.
The current is measured by a core balance CT and the tripping threshold is set:
IrsdA IrsdB b to avoid nuisance tripping,
b lower than the sum of the capacitive currents of all the other feeders.
This makes it difficult for faults to be detected in power systems that are limited
67N 67N
A B
in size, consisting of only a few hundreds of meters of cable.
Ik1 Applications
This solution is often used for industrial power systems (ð 15 kV) that require service
continuity.
It is also used for the public distribution systems in Spain, Italy and Japan.
7
Neutral earthing Resistance earthing 0
Block diagram
A resistor is intentionally connected between the neutral point and earth.
Operating technique
DE57205
In this type of power system, the resistive impedance limits the earth fault current Ik1
and still allows satisfactory evacuation of overvoltages.
However, protection units must be used to automatically clear the first fault. In power
systems that supply rotating machines, the resistance is calculated so as to obtain
a fault current Ik1 of 15 to 50 A. This low current must however be IRN Š 2 Ic (where
RN Ic is the total capacitive current in the power system) to reduce switching surges and
allow simple detection.
IRN Ik1
In distribution power systems, higher values are used (100 to 300 A) since they are
easier to detect and allow the evacuation of lightning overvoltages.
Advantages
Ic
b This system is a good compromise between low fault current and satisfactory
Fig. 1. Earthing with accessible neutral:
overvoltage evacuation.
resistor between neutral and earth.
b It does not require equipment with phase-to-earth insulation sized for the phase-
to-phase voltage.
b The protection units are simple and selective and the current is limited.
DE55200
Drawbacks
b The service continuity of the faulty feeder is downgraded and earth faults must be
cleared as soon as they occur (first fault tripping).
b The higher the voltage and the current limited, the higher the cost of the earthing
RN resistor.
Neutral earthing
b If the neutral point is accessible (star-connected windings with an accessible
neutral), the earthing resistor may be connected between the neutral and earth (fig. 1)
Fig. 2. Earthing with accessible neutral:
Protection functions
RN
To detect a fault current Ik1 that is low, protection functions other than phase
RN overcurrent are required (fig. 5).
These “earth fault’’ protection functions detect fault current:
b directly in the neutral earthing connection 1,
Earthing with inaccessible neutral:
b or in the power system by the vector sum of the 3 currents measured by:
Fig. 3. Limiting resistor Fig. 4. Limiting resistor on
8
Neutral earthing Low reactance earthing 0
Block diagram
A reactor is intentionally connected between the neutral point and earth.
For power system voltages greater than 40 kV, it is preferable to use a reactor rather
than a resistor because of the difficulties arising from heat emission in the event
of a fault (fig. 1).
Operating technique
DE57209
In this type of power system, an inductive impedance limits earth fault current Ik1 and
still allows satisfactory evacuation of overvoltages. However, protection units must
be used to automatically clear the first fault.
To reduce switching surges and allow simple detection, the current IL must be much
higher than the total capacitive current of the power system Ic.
LN In distribution systems, higher values are used (300 to 1000 A) since they are easier
to detect and allow the evacuation of lightning overvoltages.
ILN Ik1
Advantages
b This system limits the amplitude of fault currents.
Ic
Drawbacks
b The continuity of service of the faulty feeder is downgraded; earth faults must be
cleared as soon as they occur (first fault tripping).
b When earth faults are cleared, high overvoltages may occur due to resonance
between the power system capacitance and the reactance.
Neutral earthing
b If the neutral point is accessible (star-connected windings with an accessible
neutral), the earthing reactance may be connected between the neutral and earth.
b When the neutral is not accessible (delta-connected winding) or when the protection
system study shows that it is appropriate, an artificial neutral point is created by
DE55210
a neutral point coil connected to the busbars; it consists of a zigzag coil with
an accessible neutral (fig. 2).
The impedance between the two parts of the winding, essentially inductive and low,
limits the current to values that remain greater than 100 A.
A limiting resistor may be added between the coil neutral point and earth to reduce
the amplitude of the fault current (HV insulation).
Protection functions
LN
b The protection setting is in the range of 10 to 20% of the maximum fault current.
b The protection function is less restrictive than in the case of resistance earthing,
especially considering the high value of ILN given that Ic is less than the limited
Fig. 2. Earthing with inaccessible neutral. current.
Applications
Public and industrial MV distribution systems (currents of several hundred amperes).
9
Neutral earthing Compensation reactance
earthing 0
Block diagram
A reactor tuned to the total phase-to-earth capacitance of the power system
is inserted between the neutral point and earth so that the fault current is close
to zero if an earth fault occurs (fig. 1).
DE57211
Operating technique
This system is used to compensate for capacitive current in the power system.
The fault current is the sum of the currents flowing through the following circuits:
b reactance earthing circuit,
b fault-free phase capacitances with respect to earth.
R LN The currents compensate for each other since:
Ik1
b one is inductive (in the earthing circuit),
b the other one is capacitive (in the fault-free phase capacitances).
They therefore add up in opposite phase.
ILN+IR Ic In practice, due to the slight resistance of the coil, there is a low resistive current
of a few amperes (fig. 2).
Advantages
Fig. 1. Earth fault in power system with compensation
reactance earthing.
IL b The system reduces fault current, even if the phase-to-earth capacitance is high:
spontaneous extinction of non-permanent earth faults.
DE55212EN
currentinthereactor
b The touch voltage is limited at the location of the fault.
Ik1 b The installation remains in service even in the event of a permanent fault.
b The first fault is indicated by detection of current flowing through the coil.
Drawbacks
V0
IR residualvoltage
b The cost of reactance earthing may be high since the reactance needs
to be modified to adapt compensation.
Ic
b It is necessary to make sure that the residual current in the power system during
capacitivecurrent
Fig. 2. Vector diagram of currents during an earth fault.
the fault is not dangerous for people or equipment.
b There is a high risk of transient overvoltages on the power system.
b Personnel must be present to supervise.
b It is difficult to implement protection discrimination for the first fault.
Protection function
Fault detection is based on the active component of the residual current.
The fault creates residual currents throughout the power system, but the faulty
circuit
is the only one through which resistive residual current flows.
In addition, the protection units must take into account repetitive self-extinguishing
faults (recurrent faults).
When the earthing reactance and power system capacitance are tuned
(3 LN • C • ω2 = 1)
b fault current is minimal,
b it is a resistive current,
b the fault is self-extinguishing.
The compensation reactance is called an extinction coil, or Petersen coil.
Application
Public and industrial MV distribution systems with high capacitive current.
10
Neutral earthing Solidly earthed neutral 0
Block diagram
An electrical connection with zero impedance is intentionally set up between
the neutral point and earth.
DE57213
Operating technique
Since the neutral is earthed without any limiting impedance, the phase-to-earth fault
current Ik1 is practically a phase-to-neutral short-circuit, and is therefore high (fig. 1).
Tripping takes place when the first insulation fault occurs.
Advantages
b This system is ideal for evacuating overvoltages.
IN
Ik1
b Equipment with insulation sized for phase-to-neutral voltage may be used.
b Specific protection units are not required: the normal phase overcurrent protection
Ic units can be used to clear solid earth faults.
Protection function
Impedant faults are detected by a delayed earth fault protection unit (ANSI 51N),
set in the range of the rated current.
Applications
b This type of system is not used in European overhead or underground MV power
systems, but is prevalent in North American distribution systems. In the North
American power systems (overhead systems), other features come into play
to justify the choice:
v distributed neutral conductor,
v 3-phase or 2-phase + neutral or phase + neutral distribution,
v use of the neutral conductor as a protective conductor with systematic earthing
at each transmission pole.
b This type of system may be used when the short-circuit power of the source is low.
11
Short-circuit currents Introduction to short-circuits 0
Although short-circuits are less and less likely to occur in modern, well-designed,
well-operated installations, the serious consequences they can cause are an incentive
to implement all possible means to swiftly detect and eliminate them.
Ia=I•sin(ωt+α)
DE55356EN
– R •t
The short-circuit current at different points in the power system must be calculated to
design the cables, busbars and all switching and protection devices and determine
Ic=–I•sinα•e L
I
t their settings.
α
Characterization of short-circuits
A number of types of short-circuits can occur in a power system.
b Three-phase short-circuit: a fault between the three phases.
Isc=Ia+Ic This type generally provokes the highest currents (fig. 2).
b Phase-to-earth short-circuit: a fault between a phase and earth.
This type is the most frequent (fig. 3).
Momentfaultoccurs
Fig. 1. Graphical representation of a short-circuit current based b Two-phase short-circuit clear of earth: a fault between two phases (phase-to-
on an equivalent diagram.
phase voltage). The resulting current is lower than for a three-phase short-circuit,
except when the fault is in the immediate vicinity of a generator (fig. 4).
b Two-phase-to-earth short-circuit: a fault between two phases and earth (fig. 5).
Ph1 Ph1
DE57215
Ph2 Ph2
Ph3 Ph3
Fig. 2. Three-phase short-circuit (5% of cases). Fig. 4. Two-phase short-circuit clear of earth.
Ph1 Ph1
DE57216
Ph2 Ph2
Short-circuit current at a given point in the power system is expressed as the rms
Ip value Ik (in kA) of its AC component (fig. 6).
The maximum instantaneous value that short-circuit current can reach is the peak
value Ip of the first half cycle. This peak value can be much higher than 2 • Ik
because of the damped DC component IDC that can be superimposed on the AC
22Ik
Time component.
(t) This DC component depends on the instantaneous value of the voltage at the start
of the short-circuit and on the power system characteristics. The power system
is defined by the short-circuit power, according to the equation:
Fig. 6. Typical short-circuit current curve. Ssc = 3 • Un • Ik (in MVA).
This theoretical value has no physical reality; it is a practical conventional value
comparable to an apparent power rating.
12
Short-circuit currents Introduction to short-circuits 0
Symmetrical components
During normal, balanced symmetrical operation, analysis of three-phase systems is
similar to that of an equivalent single-phase system, characterized by the phase-to-
neutral voltages, phase currents and power system impedances (called cyclical
impedances). As soon as a significant dissymmetry appears in the configuration or
in power system operation, simplification is no longer possible. It is not possible to
establish simple electrical relations in the conductors, using the cyclical
impedances.
In this case, the symmetrical-components method is used, which consists of
expressing the real system as a superposition of three independent, single-phase
power systems, called:
b positive sequence (designated by a subscript 1, e.g. V1),
b negative sequence (designated by a subscript 2, e.g. V2),
b zero-sequence (designated by a subscript 0, e.g. V0).
For each system (positive-, negative- and zero-sequence respectively), voltages
V1, V2, V0 and currents I1, I2, I0 are related by the impedances Z1, Z2, Z0 of the same
system.
The symmetrical impedances are a function of the real impedances, notably
the mutual inductances.
The notion of symmetrical components is also applicable to power.
V1 = V 1 + V 2 + V 0 V1 = 1
--- (V1 + a • V2 + a2 • V3 )
3
V2 = a2 • V 1 + a • V2 + V0 1- (V1 + a2 • V2 + a • V3 )
V 2 = --
3
V3 = a • V1 + a2 • V2 + V0
V0 = 1
--- (V1 + V2 + V3 )
3
where where
2π 2π
j • ------ j • ------
3 a = e 3
a = e
V3
V1 V11 V1 2 V20
ωt
V30
V2 ωt
ωt V3 2 ωt
V21
Decomposition of a three-phase system into symmetrical components
13
Short-circuit currents Types of short-circuit 0
Zsc
U
Ik3 = ----------------------
U √3 • Zsc
where U refers to the phase-to-phase voltage at point F before the fault occurs and
Zsc is the equivalent upstream power system impedance as seen from the fault point.
Zsc
V1
DE55219EN
E Z1
I1
I 1 = --E
---- V2
Z1
Z2
I2 = I0 = 0 I2
V 1 = V2 = V 0 = 0 V0
Z0
I0
Model of a three-phase short-circuit using the symmetrical components.
U The value of this current depends on the impedance ZN between the neutral
and earth. This impedance can be virtually nil if the neutral is solidly earthed
(in series with the earthing resistance) or, on the contrary, almost infinite if the
Zsc
neutral is isolated (in parallel with the power system phase-to-earth capacitance).
Zsc The value of the phase-to-earth fault current is:
3----•----U
Ik1 = ------------------------ ----------------------
( Z 1 + Z 2 + Z 0 + 3Z N)
This calculation is required for power systems in which the neutral is earthed by
ZN
Ik1
an impedance ZN. It is used to determine the setting of the “earth fault” protection
devices which must break the earth-fault current.
If Z1, Z2 and Z0 are negligible with respect to ZN, then:
U
Ik1 = ---------------------
Fig. 2. Phase-to-earth short-circuit. 3 • ZN
This is the case, for example, when Ik1 is limited to 20 A in an MV power system
supplied by a high-power transformer (10 MVA).
I 1 = I 2 = I 0 = ---------------------E
----------------------- V1
DE55220EN
Z 1 + Z 2 + Z 0 + 3Z E Z1
I1
E( Z + Z + 3Z )
V 1 = -------------2------------0------------------- V2
Z 1 + Z 2 + Z 0 + 3Z
Z2
–Z • E I2
V 2 = ---------------------2-----------------------
Z 1 + Z 2 + Z 0 + 3Z V0
–Z • E Z0
V 0 = ---------------------0----------------------- I0
Z 1 + Z 2 + Z 0 + 3Z
3Z
14
Short-circuit currents Types of short-circuit 0
Z1 + Z 2
U In a power system supplied by a transformer (fault far from the sources), the value of
Zsc the two-phase short-circuit current at a point within the power system is:
Ik2 = -------U
-----------
2 • Zsc
The two-phase short-circuit current is weaker than three-phase short-circuit current,
Ik2
E
I 1 = ----------------------------
DE55224EN
Z1 + Z2 + Z
Fig. 1. Two-phase short-circuit clear of earth. V1
–E E Z1
I 2 = ----------------------------
Z1 + Z2 + Z I1
Z
I0 = 0 V2
Z2
E( Z + Z ) I2
V 1 = --------------2--------------
Z1 + Z2 + Z V0
E•Z Z0
V 2 = --------------------2-------- I0
Z1 + Z2 + Z
V0 = 0
U For a solid short-circuit (fault far from the sources), the value of the two-phase-
to-earth short-circuit is:
Zsc
Ik2E 3•U
IkE2E = ---------------------------
(Z + 2Z )
Zsc V1
DE55225EN
E ( Z + Z + 3Z ) Z1
IkE2E I 1 = -------------------------------2------------0----------------------------------- E
Z 1 • Z 2 + (3Z + Z0 ) • ( Z 1 + Z 2 ) I1
ZN
–E (Z + 3 Z ) V2
I2 = ---------------------------------------0--------------------------------------- Z2
Z 1 • Z 2 + (3Z + Z0 ) • ( Z 1 + Z 2 )
I2
–E • Z V0 3Z
I 0 = -----------------------------------------------2-------------------------------
Z 1 • Z 2 + ( 3Z + Z0 ) • ( Z 1 + Z 2) Z0
Fig. 2. Two-phase-to-earth short-circuit. I0
15
Short-circuit currents Short-circuit across generator
terminals 0
Subtransient Transient Steady-state after the start of the fault. It increases progressively and the current becomes weaker,
passing through three characteristic stages:
b subtransient (approximately 0.01 to 0.1 second), the short-circuit current
(rms value of the AC component) is high, 5 to 10 times the rated continuous current.
b transient (between 0.1 and 1 second), the short-circuit current drops to between
I1
I2 b steady-state, the short-circuit current drops to between 0.5 and 2 times the rated
t current.
The given values depend on the power rating of the machine, its excitation mode and,
I3 for the steady-state current, on the value of the exciting current, therefore on the
t load on the machine at the time of the fault.
What is more, the zero-sequence impedance of the AC generators is generally
2 to 3 times lower than their positive-sequence impedance. The phase-to-earth
short-circuit current is therefore greater than the three-phase current.
By way of comparison, the steady-state three-phase short-circuit current across
the terminals of a transformer ranges between 6 and 20 times the rated current,
Momentfaultoccurs
to assess, in particular their low, decreasing value makes protection setting difficult.
Current
DE55228EN
Subtransientcomponent
Transientcomponent
Steady-statecomponent
DCcomponent
Total-currentcurve
t
Subtransient Transient Steady-state
Fig. 2. Decomposition of the short-circuit current.
16
Short-circuit currents Calculation of short-circuit currents 0
Fig. 1. Graphic representation of short-circuit quantities and comprises two components (fig. 1):
as per IEC 60909. b an AC component, decreasing to its steady-state value, caused by the various
rotating machines and a function of the combination of their time constants,
b a DC component, decreasing to zero, caused by the initiation of the current
and a function of the circuit impedances.
Practically speaking, one must define the short-circuit values that are useful
in selecting system equipment and the protection system:
b I’’k: rms value of the initial symmetrical current,
Type of I’’k b Ib: rms value of the symmetrical current interrupted by the switching device when
short-circuit the first pole opens at t min (minimum delay),
b Ik: rms value of the steady-state symmetrical current,
3-phase ----•------Un
--c ------- b Ip: maximum instantaneous value of the current at the first peak,
b IDC: DC value of the current.
3 • Z1
These currents are identified by subscripts 3, 2, 2E, 1, depending on the type of short-
2-phase circuit, respectively three-phase, two-phase clear of earth, two-phase-to-earth,
c----•----Un
-- --------
phase-to-earth.
Z1 + Z2
2-phase-to-earth
c • Un • 3 • Z2
-----------------------------------------------------
-------------- The method, based on the Thevenin superposition theorem and decomposition into
symmetrical components, consists in applying to the short-circuit point an equivalent
Z1 • Z2 + Z2 • Z0 + Z1 • Z0
source of voltage in view of determining the current. The calculation takes place in
Phase-to-earth three steps.
-c •----
------ --------•
Un ----------3--
Z1 + Z2 + Z0
b Define the equivalent source of voltage applied to the fault point. It represents the
Short-circuit currents as per IEC 60909 (general situation). voltage existing just before the fault and is the rated voltage multiplied by a factor
taking into account source variations, transformer on-load tap changers and the
Type of I’’k subtransient behavior of the machines.
short-circuit b Calculate the impedances, as seen from the fault point, of each branch arriving
at this point. For positive and negative-sequence systems, the calculation does not
take into account line capacitances and the admittances of parallel, non-rotating
3-phase
c----•----Un
--- --------
3 • Z1 loads.
b Once the voltage and impedance values are defined, calculate the characteristic
2-phase ----•
c Un
------
----- minimum and maximum values of the short-circuit currents.
2 • Z1
The various current values at the fault point are calculated using:
2-phase-to-earth b the equations provided,
c-----•----Un
---------•
----------3
-
b a summing law for the currents flowing in the branches connected to the node:
Z 1 + 2Z0
v I’’k, see the equations for I’’k in the tables opposite, where voltage factor c is defined
Phase-to-earth by the standard; geometric or algebraic summing,
c-----•----Un
---------•----------3
-
v ip = κ • 2 • I’’k, where k is less than 2, depending on the R/X ratio of the positive-
2Z1 + Z 0
Short-circuit currents as per IEC 60909 (distant faults). sequence impedance for the given branch; peak summing,
v Ib = μ • q • I’’k, where m and q are less than 1, depending on the generators
and motors, and the minimum current interruption delay; algebraic summing,
v Ik = I’’k, when the fault is far from the generator,
v Ik = λ • Ir, for a generator, where Ir is the rated generator current and λ is a factor
depending on its saturation inductance; algebraic summing.
17
Short-circuit currents Equipment behaviour
during short-circuits 0
Characterization
There are 2 types of system equipment, based on whether or not they react when
Current(I) a fault occurs.
DE55227EN
Passive equipment
This category comprises all equipment which, due to its function, must have
the capacity to transport both normal current and short-circuit current.
IAC
18
Sensors Phase-current sensors (CT) 0
Protection and measuring devices require The role of a phase-current sensor is to provide its secondary winding with a current
proportional to the measured primary current. They are used for both measurements
and protection.
data on the electrical rating of the equipment
to be protected. There are two types of sensors:
For technical, economic and safety reasons, b current transformers (CT),
this data cannot be obtained directly b current transformers with a voltage output (LPCT).
S2 5PR and 10PR are the standard accuracy classes for protection CTs.
b Class PX is another way of specifying CT characteristics based on the “knee-point
P2 voltage”, the secondary resistance and the magnetizing current (see next page, fig. 1,
Ip: primary current CT response in saturated state).
Is: secondary current (proportional to Ip and in phase)
Rated output
Fig. 1. Current transformer. This is the apparent power in VA that the CT is intended to supply to the secondary
circuit at the rated secondary current without causing the errors to exceed the values
specified.
It represents the power consumed by all the connected devices and cables.
If a CT is loaded at a power lower than its rated output, its actual accuracy level
is higher than the rated accuracy level. Likewise, a CT that is overloaded loses accuracy.
Short time withstand current
Expressed in kA rms, the maximum current permissible for 1 second (Ith)
(the secondary being short-circuited) represents the thermal withstand of the CT
to overcurrents. The CT must be able to withstand the short-circuit current for the time
required to clear it. If the clearing time t is other than 1 sec., the current the CT can
withstand is I th ⁄ t
Electrodynamic withstand expressed in kA peak is at least equal to 2.5 • Ith
Normal values of rated primary currents (in A):
10 - 12.5 - 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 and multiples or decimal submultiples.
(1) Also to be taken into account are elements related to the type of assembly,
characteristics of the site (e.g. temperature, etc.), power frequency, etc.
19
Sensors Phase-current sensors (CT) 0
Vk 10%
R
C
T
Is
+
R
RCT Rwire
w
ire
+
Im
R
S1 50%
lo
E Lm Vs Rload
ad
S2
Isecondary Imagnetizing
Isat Isn ImatVk 1.5Im
P2
Fig. 1. Equivalent diagram of a CT secondary current... and CT magnetization curve.
x1.5 x1.5
I I
Isetting Isaturation Iscmax Isaturation
Fig. 2. Fig. 3.
Differentialprotection
Fig. 4.
20
Sensors Phase-current sensors (LPCT) 0
Module
(%)
DE55337EN
5%
1.5%
0.75%
Module
0.5%
Ip
Phase
(min)
90'
60'
45'
Phase
30'
Ip
5A 20A 100A 1kA 1.25 10 40
kA kA kA
Fig. 2. LPCT accuracy characteristics.
21
Sensors Residual-current sensors 0
Irsd
The residual current is equal to three times the zero-sequence current I0.
I1 Ir sd = 3 • I0 = I1 + I 2 + I3
+++
Neutral
Special core A few amperes
51G 51G
balance CT
DE57339
DE57340EN
Irsd Irsd
++
Neutral
Toroidal CT + 10% of InCT (DT)
interposing ring 5% of InCT (IDMT)
DE57341EN
Irsd Irsd
22
Sensors Voltage transformers (VT) 0
In isolated neutral systems, all phase-neutral VTs sufficiently loaded to avoid the risk
DE57346
of ferromagnetic resonance.
(1) Elements related to the type of assembly, characteristics of the site (e.g. temperature), etc.
must also be taken into account.
Vrsd = 3 • V0 = V1 + V2 + V3 (fig. 3)
Vrsd
V1 The occurrence of this voltage signals the existence of an earth fault.
It can be measured or calculated:
b measurement using three voltage transformers whose primaries are star connected
V2 and the secondaries, in an open delta arrangement, supply the residual voltage (fig. 4),
b calculation by the relay, using three voltage transformers whose primaries and
secondaries are star connected (fig. 5).
Fig. 3. Definition of residual voltage.
DE57348
DE57349
59N V1 59N
V2
Vrsd
V3
23
Protection functions General characteristics 0
Characteristics (fig. 2)
The protection function work mode involves characteristic times (IEC 60255-3):
DE57270
b operating time: this is the time between the application of the characteristic quantity
I S 0 St (at twice the threshold setting) and the switching of the output relay (instantaneous
output),
I>Is
Si
b overshoot time: this is the difference between operating time and the maximum
time during which the characteristic quantity can be applied with no tripping,
Fig. 1. Relay operating principle. b reset time: this is the time between a sudden decrease in the characteristic quantity
(example of ANSI 51 phase overcurrent protection relay) and the switching of the output relay.
Note: other non-standardized terms are commonly found as well, the definitions of which may
vary from one manufacturer to another: reclaim time, no response time, instantaneous tripping
time, memory time.
2Is
Threshold
Is t
Si Operatingtime Resettime
t
0
I Overshoottime
2Is
Is
t
Maximumnotriptime
I
DE55271
Is
d•Is
t
t
0
24
Protection functions General characteristics 0
Settings
Some protection functions may be set by the user, in particular:
b tripping set point: it sets the limit of the observed quantity that actuates
the protection function.
b tripping time:
v definite time delay (DT)
The example in figure 1, applied to a current relay, shows that above the current
threshold Is, the protection tripping time is constant (time delay setting T).
t Currentthreshold
DE55273EN
No Delayed
operation operation
T
Delay
I
Is
No Delayed
operation operation
T
Delay
I
Is 10•Is
There are several types of curves, determined by equations and defined by the
various standardization organizations: for example, the IEC defines the following
(fig. 3):
- standard inverse time (SIT),
- very inverse time (VIT),
- extremely inverse time (EIT).
t
DE55275
EIT
VIT
SIT
I
Is 10•Is
Fig. 3. IDMT tripping curves.
25
Protection functions List of functions 0
The main protection functions are listed with a brief definition in the table below.
They are listed in numerical order by ANSI C37.2 code.
26
Protection functions Associated functions 0
Control logic
b indication functions,
b metering functions,
b diagnosis functions, This function is used to implement logic discrimination by the sending and/or reception
of “blocking signals” by different protection units.
b communication functions,
for enhanced operation of power systems.
Logic functions
These functions perform logic equation operations to generate additional data
All of these functions may be provided
by the same digital protection unit. or orders used for the application.
Operation functions
These functions make operation more convenient for the user.
b Transformer on-load tap changers,
b Reactive energy regulation,
b Fault locator (ANSI 21FL),
b Capacitor bank control,
b Remaining operating time before thermal overload tripping.
Metering functions
These functions provide information required for a good understanding
of power system operation.
b Phase current,
b Tripping current,
b Residual current,
b Differential and through currents,
b Current THD (total harmonic distortion),
b Phase-to-neutral and phase-to-phase voltages,
b positive sequence, negative sequence and residual voltages,
b Voltage THD (total harmonic distortion),
b Frequency,
b Active, reactive and apparent power,
b Power factor (cos j),
b Active and reactive energy,
b Peak demand current, active and reactive power,
b Temperature,
b Motor starting time,
b Disturbance recording.
Communication functions
These functions are used for the exchange of available data by the different power
system components (measurements, states, control orders…).
27
Discrimination Time-based discrimination 0
or back-up.
Discriminationinterval∆T
Advantages
51 TA=1.1s
A
Drawbacks
However, when there are a large number of cascading relays, since the protection
unit located the furthest upstream has the longest time delay, the fault clearing time
becomes prohibitive and incompatible with equipment short-circuit current withstand
51 TC=0.5s
C
and external operating necessities (e.g. constraint imposed by utility).
51 TD=0.2s
D
Phase-to-phasefault
28
Discrimination Time-based discrimination 0
Application
This principle is used in radial power systems. (fig. 1)
The time delays set for time-based discrimination are activated when the current
DE57243
DE55244EN
51 IsC,TC
C TA
∆T
TB
∆T
TC
Fig. 1. Radial power system with time-based discrimination.
I
IsC IsB IsA IscC IscB IscA
max max max
t C B A
DE55245
∆T
∆T
I
IsC IsB IsA IscC IscB IscA
max max max
29
Discrimination Current-based discrimination 0
Principle
Current-based discrimination uses the principle that within a power system,
the further the fault is from the source, the weaker the fault current is.
Operating mode
A current protection unit is installed at the starting point of each section: the
threshold is set to a value lower than the minimum short-circuit current caused by a
fault in
the monitored section, and higher than the maximum current caused by a fault
downstream (outside the monitored area).
Advantages
With these settings, each protection device is only activated by faults located
immediately downstream, within the monitored zone, and is not sensitive to faults
outside that zone.
For sections of lines separated by a transformer, it can be of benefit to use this system
since it is simple, cost-effective and quick (tripping with no delay).
An example is given below (fig.1):
IscBmax < IsA < IscAmin
IsA = current setting
IscB on the transformer primary is proportional to the maximum short-circuit current
on the secondary.
Time delays TA and TB are independent, and TA may be shorter than TB.
Drawbacks
The upstream protection unit (A) does not provide back-up for the downstream
protection unit (B).
In practice, it is difficult to define the settings for two cascading protection units, and
still ensure satisfactory discrimination, when there is no notable decrease in current
between two adjacent areas. This is the case in medium voltage power systems,
except for sections with transformers.
Application
The following example concerns current protection of a transformer between
two cable sections.
The overcurrent protection setting I s satisfies the relation:
1.25 I scBmax < IsA < 0.8 I scAmin
Discrimination between the two protection units is ensured.
t B A
DE57246EN
IscAmin IscBmax
51 IsA,TA 51 IsA,TA TB
A A
TA
I
IsB IscB IsA IscA
max min
Discriminationcurves
51 IsB,TB
B
Condition Condition
IsA<IscAmin IsA>IscBmax
30
Discrimination Logic discrimination 0
Principle
This system was developed to solve the drawbacks of time-based discrimination.
This principle is used when short fault clearing time is required (fig. 1).
DE57247EN
Operating mode
The exchange of logic data between successive protection units eliminates the need
for discrimination intervals, and thereby considerably reduces the tripping time of the
circuit breakers closest to the source.
51 In radial power systems, the protection units located upstream from the fault are
activated; those downstream are not. The fault point and the circuit breaker to be
tripped can therefore be clearly located.
Each protection unit activated by a fault sends:
b a blocking signal to the upstream level (an order to increase the upstream relay
time delay),
b a tripping order to the related circuit breaker unless it has already received a
51
Phase-to-phase b when a fault appears between A and B, protection unit A trips after the delay TA.
fault
Advantages
Fig. 1. Logic discrimination principle. Tripping time is not related to the location of the fault within the discrimination chain
or to the number of protection units in the chain.
This means that discrimination is possible between an upstream protection unit
with a short time delay and a downstream unit with a long time delay. For example,
a shorter time delay may be used at the source than near the loads.
DE57248EN
Drawbacks
Since logic signals must be transmitted between the different levels of protection
TA
IsA
units, extra wiring must be installed. This can be a considerable constraint when
A inst.
the protection units are far apart each other, in the case of long links, for example
(several hundreds of meters long).
This difficulty may be bypassed by combining functions: logic discrimination
Blockingsignal
in the nearby switchboards and time-based discrimination between zones
that are far apart (refer to chapter on combined logic + time-based discrimination).
Application
TB+T3
(back-up)
TB
This principle is often used to protect medium voltage power systems that include
IsB
inst.
radial branches with several levels of discrimination.
B
31
Discrimination Directional protection
discrimination 0
Principle
In a looped power system, in which faults are fed from both ends, it is necessary
to use a protection unit that is sensitive to the direction of the flow of fault current
in order to locate and clear the fault selectively. This is the role of directional
Cable
DE57249EN
Operating mode
67 Is,T The protection actions differ according to the direction of the current (figs. 1 and 2),
i.e. according to the phase displacement of the current in relation to a reference given
by the voltage vector; the relay therefore needs both current and voltage data.
I
The operating conditions, namely the position of the tripping and no tripping zones,
Vref are adapted to fit the power system to be protected (fig. 3).
Example of the use of directional protection units (fig. 4):
Circuit breakers D1 and D2 are equipped with directional protection units
that are activated if the current flows from the busbars to the cable.
Busbar
Directional protection principle If a fault occurs at point 1, it is only detected by the protection unit at D1.
The protection unit at D2 does not detect it, because of the detected current direction.
Fig. 1. Protection unit active.
Advantage
The solution is simple and may be used in a large number of cases.
67 Is,T
I
Drawback
Vref Voltage transformers must be used to provide a phase reference to determine
the direction of the current.
Application
Busbar
This principle is used to protect parallel incomers and closed loop power systems
Directional protection principle and also for certain cases of earth fault protection.
Fig. 2. Protection unit not active.
IbusbarsVcable
Notrippingzone
Vref 1
67 67
Vref
IcableVbusbars D1 D2
Busbars
2
Directional protection principle Directional protection
Fig. 3. Detection of current direction. Fig. 4. Example of two parallel incomers.
32
Discrimination Differential protection
discrimination 0
Principle
These protection units compare the current at the two ends of the monitored section
of the power system (fig. 1).
DE57253EN
A Operating mode
Any amplitude or phase difference between the currents indicates the presence
IA of a fault: The protection units only react to faults within the area they cover and
are insensitive to any faults outside that area. This type of protection is therefore
selective by nature.
Instantaneous tripping takes place when IA-IB ≠ 0
In order for differential protection to work, it is necessary to use current transformers
Protected
87
zone
specifically sized to make the protection units insensitive to other phenomena.
What makes differential protection units stable is that they do not pick up as long as
there are no faults in the zone being protected, even if a differential current is detected:
b transformer magnetizing current,
IB
DE55256EN
zone Is
Rs Ithrough
∆I
IA IB Idifferential
Protected
DE57255EN
DE55257EN
zone
Threshold%It
Is
∆I/I Ithrough
Advantages
b Protection sensitive to fault current less than the rated current of the protected
equipment.
b Zone protection that can trip instantaneously.
Drawbacks
b The cost of the installation is high.
b It takes skill to implement the system.
b An overcurrent back-up function needs to be included.
Application
Differential protection may concern all priority high power components:
motors, generators, transformers, busbars, cables and lines.
33
Discrimination Combined discrimination 0
Protected
zone
TA2
∆T
TB
51 IsB,TB
B TA1
I
Fig. 1. Current-based + time-based discrimination.
IsB IsA2 IscB IsA1 IscA
TA2
∆T
TB
TB
IsB TA1
B T=0
I
Fig. 2. Logic + back-up time-based discrimination. IsB IsA IscB IscA
51 0.1s 0.7s
C
51 0.4s 0.4s
D
Fig. 3. Comparison of combined (logic + time-based)
discrimination and time-based discrimination tripping times.
34
Discrimination Combined discrimination 0
protection units. The protection unit at D2 does not detect it, because of the detected
H1 H2 current direction. D1 trips. The H2 protection unit drops out, H1 trips and the faulty
section H1-D1 is isolated.
TH1 = TH2
51 51
TD1 = TD2
TH = TD + ΔT
1
67 67
D1 D2
51 BSIG 51
Logic + directional discrimination
The example shows that the orientation of blocking signals depends on the direction
DE57264EN
Fault at D2 end:
b tripping at D2 and B,
Vref
Fault at D1 end:
51 BSIG 51
b tripping at D1 and B,
D1 67 D2
b D2 is blocked by B (BSIG: blocking signal).
Vref
b a phase overcurrent or earth fault protection unit at A as back-up for the differential
protection unit,
b a current protection unit at B to protect the downstream zone,
51 IsA,TA
A
b time-based discrimination between the protection units at A and B, with
TA = TB + ΔT.
This provides back-up for the differential protection function, but double-wound
Protected current transformers are sometimes necessary.
Note: time-based discrimination may be replaced by logic discrimination.
zone 87
51 IsB,TB
B
35
Power-system protection Single-incomer power systems 0
Phase-to-earth faults
earthing arrangement.
The following types of systems will be
examined: single-incomer, dual-incomer, Resistance earthing on the transformer (fig.2)
Earth fault protection units (ANSI 51N) are installed on the feeders, incomer and
neutral earthing connection.
open loops and closed loops.
Time-based discrimination is used between the different protection units.
These units are necessarily different from phase fault protection units since the fault
currents are in a different range.
The feeder protection units are set selectively in relation to the incomer protection
unit, which is itself set selectively in relation to the neutral earthing protection unit
(in accordance with discrimination intervals).
The fault current flows through the capacitances of the fault-free feeders
and the earthing resistance.
All the fault-free feeder sensors detect capacitive current.
To prevent inadvertent tripping, the protection unit on each feeder is set higher than
the feeder’s capacitive current.
b fault at 3: the D1 circuit breaker is tripped by the protection unit linked to it,
b fault at 4: the A circuit breaker is tripped by the incomer protection unit,
b fault at 5: the protection unit on the neutral earthing connection trips circuit breaker H
on the transformer primary circuit. (fig. 1).
The protection unit at D must be selective in relation to the downstream protection units:
if the delay required for protection A is too long, logic discrimination should be used.
The neutral earthing protection unit at H acts as back-up should the incomer
protection unit at A fail to trip.
The incomer protection unit at A acts as back-up should a feeder protection unit
at D fail to trip.
DE57230
DE57231EN
H
t D A 51G t D A H
TH
5 ∆T
51 IsA,TA
TA 51G TA
∆T ∆T
A
TD A TD
I I
51 IsD,TD
51G 51G 51G
1 3
Capacitivecurrent
Resistivecurrent
Fig. 1. Phase-to-phase fault protection. Fig. 2. Phase-to-earth fault protection (resistance-earthed neutral at transformer).
36
Power-system protection Single-incomer power systems 0
sequence generator.
Time-based discrimination is used between the different protection units.
The feeder protection units and incomer protection unit are set selectively in relation
3 to the earthing impedance protection unit. As in the previous case, the protection
unit on each feeder is set higher than the feeder’s capacitive current.
51G IsA,TA
In the event of a fault on feeder 1, only the D1 feeder circuit breaker trips.
In the event of fault on the busbars 2, only the protection unit on the earthing
connection detects the fault. It trips circuit breaker A.
A
In the event of fault on the transformer secondary circuit 3, the incomer protection
units detects the fault. It trips circuit breaker H.
2 Note: when circuit breaker A is open, the transformer secondary circuit neutral
is isolated. It may be necessary to protect it by a neutral voltage displacement
D2 D1
Reactance-earthed neutral
Fig. 1. Phase-to-earth fault protection The same procedure is used as for resistance-earthing at the transformer or busbars.
(resistance-earthed neutral at busbars).
Isolated neutral (fig. 2)
A fault, regardless of its location, produces current which flows through the capacitance
of the fault-free feeders.
In industrial power systems, this current is generally weak (a few amperes), allowing
DE57233EN
Directional earth fault protection can be used to selectively trip the fault feeder.
59N
Compensated neutral
The power system is earthed at the transformer. Faults are detected by a specific
directional earth fault protection unit (ANSI 67NC), which monitors the active
residual current and recognizes faults during their initial transient phase.
37
Power-system protection Dual-incomer power systems 0
H1 H2
51 TH 51 TH The two incomers A1 and A2 are equipped with phase overcurrent protection units
(ANSI 51) set selectively in relation to the feeders, i.e.
TA Š TD + ΔT.
T1 T2 They are also equipped with directional protection units (ANSI 67) with delays set
at TR < TA – ΔT.
Time-based discrimination is used between the incomer A protection units
and feeder D protection units.
3
Current-based discrimination is used between the power supply H protection units
and incomer A protection units.
67 TR 67 TR
This means that a fault at 1 is cleared by the tripping of D2 after a delay TD.
51 TA 51 TA
A fault at 3 is detected by the A1 directional protection unit which trips at the time TR,
2 allowing continued operation of the fault-free part of the power system.
D1 D2 However, the fault at 3 is still fed by T1. At the time TH Š TA + ΔT,
H1 is tripped by the phase overcurrent protection unit linked to it.
51 TD 51 TD
H1 H2 set higher than the incomer and feeder protection units, with time delays such that
51G TN 51G TN TN Š TD + ΔT.
Time-based discrimination is used between the different protection units.
This means that a fault at 4 is cleared by the tripping of D1.
A fault at 5 is cleared by the tripping of A1, A2, H1 and H2 by the protection units
located on the neutral earthing connections of the 2 transformers.
A fault at 6 is detected by the A1 directional protection unit which trips at the time TR,
6
allowing continued operation of the fault-free part of the power system.
However, the fault at 6 continues to be supplied up to the time TN at which
67N TR 67N TR
51G TD 51G TD 51G TD Time-based discrimination is used between the different protection units.
The system operates in the same way as in single-incomer power systems.
Isolated neutral
4
The system operates in the same way as in single-incomer power systems.
Compensated neutral
Only one earthing coil is in service at a given time to ensure power system
capacitance matching; this is similar to single-incomer power systems.
38
Power-system protection Dual-incomer power systems 0
Decoupling
When electrical installations are supplied by the utility and an independent power
source, interference between the two sources as a result of events such as a utility
failure or earth faults should be avoided. The consequences include voltage and
frequency fluctuations and current and power exchanges between the different circuits.
Protection functions are often advocated or imposed in the distributors’ technical
guides.
There are several methods of decoupling two sources:
b monitoring of the active power direction and protection by a reverse power
protection relay (ANSI 32P),
b monitoring of voltage amplitude and under or overvoltage protection
(ANSI 27 or 59),
25 b monitoring of frequencies and underfrequency (ANSI 81L) or overfrequency
(ANSI 81H) protection,
b protection against phase shifts caused by faults (ANSI 78),
Fig. 1. Power system coupling protection.
39
Power-system protection Open loop power systems 0
In distribution systems that include The power system is operated as an open loop and protection is provided at the ends
of the loops, which are equipped with circuit breakers (fig. 1).
The switching devices used on the substations are switches.
substations supplied in open loops,
protection is provided at the head Faults cause power outages.
of the loop. Phase overcurrent and earth fault protection units (ANSI 51 and 51N) are installed
on the circuit breakers at the head of each loop.
A fault occurring in a cable that connects 2 substations may trip either of these circuit
breakers depending on the position of the loop opening.
The protection is often completed by an automated device that:
b clears the fault (with the power off) by opening the devices located at the ends
of the faulty cable, after the faulty cable has been located by the fault detector,
b closes the circuit breaker that has tripped at the head of the loop,
b closes the device that ensured the normal opening of the loop in order to restore
power to the fault-free downstream half of the loop.
The power system can be put back into its initial operating state after the faulty circuit
has been repaired.
The outage may last from a few seconds to a few minutes depending on whether
the loop is reconfigured automatically or manually.
DE57238EN
51 51
51N 51N
C C
C C
C C
C C
O C
40
Power-system protection Closed loop power systems 0
In distribution systems that include The power system may be operated in closed loops, with each section protected by
circuit breakers at the ends of the section. Most faults do not cause power outages.
Various protection solutions may be used.
substations supplied in closed loops,
protection is provided for different sections.
Differential protection (fig. 1)
Each cable is equipped with a line differential protection unit (ANSI 87L) and each
substation is equipped with a busbar differential protection unit (ANSI 87B).
This type of protection is very quick.
If the neutral is resistance-earthed, the sensitivity of the differential protection units
must cover phase-to-earth faults.
DE57239EN
C C
87L 87L
C C
87B 87B
C C
51 51
51N 51N
67 67 67 67
67N 67N 67N 67N
67 67 67 67
67N 67N 67N 67N
41
Busbar protection Types of faults and
protection functions 0
A
to protection unit A.
Protection unit B trips after 0.4 s.
However, a fault at point 4 is only detected by protection unit A, which trips after 0.1 s;
2 with backup protection provided if necessary in 0.7 s.
Differential protection
51
51N TB=0.4s
Differential protection (ANSI 87B) is based on the vector sum of the current entering
B and leaving the busbars for each phase. When the busbars are fault-free, the sum
1 is equal to zero, but when there is a fault on the busbars, the sum is not zero and
the busbar supply circuit breakers are tripped.
This type of protection is sensitive, fast and selective.
51 b With percentage-based, low impedance differential protection, the difference
is calculated directly in the relay. The threshold setting is proportional to the through
C 51N TC=0.1s
current and CTs with different ratios may be used. However, the system becomes
Fig. 1. Time-based discrimination. complicated when the number of inputs increases.
b With high impedance differential protection (fig. 3), the difference is calculated
TA1=0.1s TA2=0.7s in the cables, and a stabilization resistor is installed in the differential circuit. The CTs
51 51 are sized to account for saturation according to a rule given by the protection relay
DE57282EN
51 TB=0.4s
B
51 TC=0.1s
C
Rs
51 87B
51 51 51
42
Busbar protection Types of faults and
protection functions
0
Breaker failure
The breaker failure function (ANSI 50BF) provides backup when a faulty breaker
fails to trip after it has been sent a trip order: the adjacent incoming circuit breakers
are tripped.
The example (fig. 1) shows that when a fault occurs at point 1 and the breaker
that has been sent the trip order fails, the breaker failure protection function is faster
than action by upstream protection time-based discrimination: 0.6 s instead of 0.7 s.
51 0.7s 51 0.7s
DE57284EN
Faulty
breaker
43
Link (line and cable) Types of faults and
protection protection functions 0
DE57286
46
51 87L
51Nor67N
87L
44
Link (line and cable) Types of faults and
protection protection functions 0
Distance protection
Distance protection (ANSI 21) against faults affecting line or cable sections is used
in meshed power systems (parallel links, several sources).
It is selective and fast, without requiring time-based discrimination. Sensitivity
DE57279EN
depends on the short-circuit power and the load. It is difficult to implement when the
21 type of link is not the same throughout (overhead line + cable).
It operates according to the following principle:
b measurement of an impedance proportional to the distance from the measurement
A point to the fault,
b delimitation of impedance zones which represent line sections of different lengths
(fig.1),
b tripping by zone with time delay.
The example in figure 2 shows the following for the protection unit at point A in line
0% 21
section AB:
b an impedance circle at 80% of the length of the line (zone 1), inside which tripping
is instantaneous,
b an impedance band between 80% and 120% of the length of the line (zone 2),
in which tripping is delayed (200 ms),
b an impedance circle at 120% of the length of the line (zone 3), outside which
there is long-time delayed backup tripping of protection unit B outside AB,
b an impedance circle at 120% downstream to provide backup for downstream
protection,
b When there is communication between the protection units at the ends,
Zone1 tripping can take place instantaneously between 0 and 100%.
X ZL
DE55280EN
Zone3
T3
Zone2
T2
Zone1
T1 LoadZ
R
80%
Zone2 Downstreamzone
21
B
100%
Fig. 2. Impedance circles.
21
Recloser
The recloser function (ANSI 79) is designed to clear transient and semi-permanent
faults on overhead lines and limit down time as much as possible. The recloser
function automatically generates circuit breaker reclosing orders to resupply
Zone2
L
Fig. 1. Distance protection principle.
45
Transformer protection Types of faults 0
The transformer is a particularly important The main faults that can affect transformers are:
b overloads,
b short-circuits,
power system component.
Transformers requires effective protection b frame faults.
against all faults liable to damage them,
whether of internal or external origin. Overloads
The choice of a protection unit is often Overloads may be caused by an increase in the number of loads supplied
based on technical and cost considerations simultaneously or by an increase in the power drawn by one or more loads.
related to the power rating. Overloads result in overcurrent of long duration, causing a rise in temperature that is
detrimental to the preservation of insulation and to the service life of the transformer.
Short-circuits
Short-circuits can occur inside or outside the transformer.
Internal short-circuits: faults between different phase conductors or faults
between turns of the same winding. The fault arc damages the transformer winding
and can cause fire. In oil transformers, the arc causes the emission of
decomposition gas.
If the fault is slight, a small amount of gas is emitted and the accumulation of gas
can become dangerous.
A violent short-circuit can cause major damage liable to destroy the winding and also
the tank frame by the spread of burning oil.
External short-circuits: phase-to-phase faults in the downstream connections.
The downstream short-circuit current creates electrodynamic stress in the transformer
that is liable to have a mechanical effect on the windings and lead to an internal fault.
Frame faults
I I
Imax Imax
DE55288EN
Frame faults are internal faults. They may occur between the winding and the tank
frame or between the winding and the magnetic core.
Imax
They cause gas emission in oil transformers. Like internal short-circuits, they can cause
transformer damage and fire. The amplitude of the fault current depends on the
2
upstream and downstream neutral earthing arrangements, and also on the position
% % of the fault in the winding:
0 100% 0 50% 100% b in star connected arrangements (fig.1), the frame fault current varies between 0
and the maximum value depending on whether the fault is at the neutral or phase
end of the winding.
b in delta connected arrangements (fig. 2), the frame current varies between 50 and
100% of the maximum value depending on whether the fault is in the middle or at the
end of the winding.
Transformer energizing creates a transient peak inrush current that may reach 20
winding.
times the rated current with time constants of 0.1 to 0.7 seconds. This phenomenon
is due to saturation of the magnetic circuit which produces a high magnetizing
Ic
current. The peak current is at its highest when energizing takes place as the voltage
–t
DE55289
-----
goes through zero and there is maximum remanent induction on the same phase.
ˆ • ( t) = Ie
ie ˆ • eτ e
of 5th harmonics.
46
Transformer protection Protection functions 0
Overloads
Overcurrent of long duration may be detected by a definite time or IDMT delayed
overcurrent protection unit (ANSI 51) that provides discrimination with respect
to the secondary protection units.
DE57290
The dielectric temperature is monitored (ANSI 26) for transformers with liquid
insulation and the winding temperature is monitored (ANSI 49T) for dry type
transformers.
87T Thermal overload protection (ANSI 49RMS) is used for more sensitive monitoring
of temperature rise: heat rise is determined by simulation of the release of heat
according to the current and thermal inertia of the transformer.
For MV/LV transformers, overloads may be detected on the low voltage side
by the long time trip function of the main LV circuit breaker.
Short-circuits
Several protection functions may be implemented.
Fig. 1. Transformer differential protection.
b For oil transformers, devices that are sensitive to gas emission or oil movement
t
(ANSI 63) caused by short-circuits between turns of the same phase or phase-to-phase
DE57291EN
51
51 short-circuits:
50 50 v Buchholz relays for free breathing HV/HV transformers,
v gas and pressure detectors for hermetically sealed HV/LV transformers.
b Transformer differential protection (ANSI 87T) (fig.1) which provides fast protection
against phase-to-phase faults. It is sensitive and used for vital high power transformers.
I
Transformerenergizing Max.LV Max.HV To avoid nuisance tripping, the 2nd harmonic of the differential current is measured
curve Isc Isc to detect transformer energizing (H2 restraint) and the 5th harmonic is measured
to detect overfluxing (H5 restraint).
Fig. 2. Transformer overcurrent protection. The use of this protection function with neural network technology provides
the advantages of simple setting and stability.
b An instantaneous overcurrent protection unit (ANSI 50) (fig. 2) linked to the circuit
breaker located on the transformer primary circuit provides protection against violent
DE57292
short-circuits. The current threshold is set higher than the current due to short-circuits
on the secondary winding, thereby ensuring current-based discrimination.
51G b HV fuses can be used to protect transformers with low kVA ratings.
Frame faults
b Tank frame fault (fig. 3)
Fig. 3. Transformer tank frame fault protection. This slightly delayed overcurrent protection unit (ANSI 51G), installed on the
transformer frame earthing connection (if the setting is compatible with the neutral
earthing arrangement), is a simple, effective solution for internal winding-to-frame
faults. In order for it to be used, the transformer must be isolated from the earth.
DE57293
b earth fault protection (ANSI 51N) located on the upstream power system for frame
faults that affect the transformer primary circuit.
b earth fault protection (ANSI 51N) located on the incomer of the switchboard being
supplied, if the neutral of the downstream power system is earthed on the busbars
(fig. 4).
These protection functions are selective: they are only sensitive to phase-to-earth
faults situated in the transformer or on the upstream and downstream connections.
b restricted earth fault protection (ANSI 64REF) if the downstream power system
Fig. 4. Earth fault protection. Fig. 5. Restricted earth fault neutral is earthed at the transformer (fig. 5). This is a differential protection function
protection. that detects the difference between residual currents measured at the neutral
earthing point and at the three-phase output of the transformer.
b neutral point earth protection (ANSI 51G) if the downstream power system is
earthed at the transformer (fig. 6).
DE57294
b neutral voltage displacement protection (ANSI 59N) may be used if the downstream
power system neutral is isolated from the earth (fig. 7).
59N
51G
47
Transformer protection Recommended settings 0
48
Transformer protection Examples of applications 0
DE57295
DE57296
51G 49RMS
26 50
26 51
63 63 51G(2x)
DE57298
49RMS 49RMS
50 26 50
26 51 63 51
63 51N 49T 51G(2x)
51G(2x) 64REF
87T
49
Motor protection Types of faults 0
Motors are the interface between electrical Motors are affected by:
b faults related to the driven loads,
b power supply faults,
and mechanical equipment. They are
connected to the machines they drive b motor internal faults.
and are therefore exposed to the same
environment. Faults related to the driven loads
Motors may be subjected to internal Overloads
mechanical stress due to their moving parts. If the power drawn is greater than the rated power, there is overcurrent in the motor
A single faulty motor can disrupt an entire and an increase in losses, causing a rise in temperature.
Excessive starting time and frequency of starts
Motor starting creates substantial overcurrents which are only admissible for short
production process. Modern motors have
optimized characteristics which make them durations. If a motor starts too frequently or if starting takes too long due to insufficient
unsuitable for operation other than according motor torque compared to load torque, overheating is inevitable and must be avoided.
to their rated characteristics. This means Blocking
Rotation suddenly stops due to blocking of the driven mechanism. The motor draws
the starting current and stays blocked at zero speed. There is no more ventilation and
that they are relatively fragile electrical loads
that need to be carefully protected. overheating occurs very quickly.
There are asynchronous motors (mainly Loss of load
squirrel-cage motors or wound-rotor motors) Loss of pump priming or a break in load coupling causes no-load operation of the motor,
which does not directly harm the motor. However, the pump itself is quickly damaged.
and synchronous motors (motors with DC
Power supply faults
rotor excitation).
Loss of supply
Questions concerning synchronous motors
are the same as those that concern This causes motors to operate as generators when the inertia of the driven load
asynchronous motors plus those that is high.
concern generators. Voltage sag
This reduces motor torque and speed: the slow-down causes increased current
and losses. Abnormal overheating therefore occurs.
Unbalance
3-phase power supply may be unbalanced for the following reasons:
b the power source (transformer or AC generator) does not supply symmetrical
3-phase voltage,
b all the other consumers together do not constitute a symmetrical load and
this unbalances the power supply system,
b the motor is powered by two phases after a fuse has blown on one phase,
b The phase order is reversed, changing the direction of motor rotation.
Power supply unbalance creates negative sequence current which causes very high
losses and quick rotor overheating.
When the voltage is re-supplied after a motor power failure, the motor sustains
remanent voltage that may lead to overcurrent when the motor starts again or even
a mechanical break in transmission.
50
Motor protection Protection functions 0
Overloads
Overloads may be monitored the following:
b IDMT overcurrent protection (ANSI 51),
b thermal overload protection (ANSI 49RMS), which involves overheating
due to current,
b RTD temperature monitoring (ANSI 49T).
Successive starts
The successive starts protection function (ANSI 66) is based on the number of starts
within a given interval of time or on the time between starts.
Speed variation
Additional protection may be provided by the direct measurement of rotation speed
by mechanical detection on the machine shaft.
The underspeed protection function (ANSI 14) detects slow-downs or zero speed
resulting from mechanical overloads or locked rotors.
The overspeed protection function (ANSI 12) detects racing when the motor is
driven by the load, or a loss of synchronization for synchronous motors.
Loss of supply
Loss of supply is detected by a directional active power protection unit (ANSI 32P).
Voltage sag
This is monitored by a delayed positive sequence undervoltage protection unit
(ANSI 27D).
The voltage threshold and delay are set to allow discrimination with the power
system’s short-circuit protection units and to tolerate normal voltage sags such as
those that occur during motor starting. The same protection function may be shared
by several motors in the switchboard.
Unbalance
Protection is provided by the detection of negative sequence current by an IDMT
or definite time protection unit (ANSI 46).
The phase rotation direction is detected by the measurement of negative sequence
overvoltage (ANSI 47).
Resupply
Motor remanence is detected by a remanent undervoltage protection unit (ANSI 27R)
which enables resupply when the voltage drops below a certain voltage threshold.
51
Motor protection Protection functions 0
Overheating of bearings
The bearing temperature is measured by RTDs (ANSI 38).
Field loss
51 For synchronous motors: refer to the chapter on generators.
Pole slip
For synchronous motors: refer to the chapter on generators.
52
Motor protection Recommended settings 0
53
Motor protection Examples of applications 0
DE57302
DE57303
37 27D
46 27R
48-51LR 46
49RMS 48-51LR
51G 49RMS
66 51
51G
M M 66
67N
DE57305
12 27D
14 27R
27D 32P
27R 32Q
46 40
48-51LR 46
49RMS 48-51LR
26 51 49RMS
63 51G 51
49T 66 51G
87T 66
78PS
87M
38/ 38/
M 49T M 49T
54
Generator protection Types of faults 0
Generator operation can be altered by both Faults such as overloads, unbalance and internal phase-to-phase faults are the same
type for generators and motors.
Only faults specifically related to generators are described below.
faults within the machine and disturbances
occurring in the power system to which
it is connected. External phase-to-phase short-circuits
A generator protection system therefore When a short circuit occurs in a power system close to a generator, the fault current
has a dual objective: to protect the machine looks like the current shown in figure 1.
and protect the power system. The maximum short-circuit current should be calculated taking into account
the machine’s substransient impedance X”d.
The short-circuit current detected by a protection unit with a very short time delay
The generators referred to here are
synchronous machines (AC generators). (about 100 ms) should be calculated taking into account the machine’s transient
impedance X’d.
The short-circuit current in steady state conditions should be calculated taking into
account the synchronous impedance X.
It is low, generally less than the generator’s rated current.
Voltage regulators can often keep it higher than the rated current (2 or 3 times higher)
for a few seconds.
Field loss
When a generator coupled with a power system loses its field, it becomes
desynchronized with respect to the power system. It then operates asynchronously,
t at a slight overspeed, and it draws reactive power.
This causes stator overheating since the reactive current may be high and rotor
overheating since the rotor is not sized for the induced currents.
Loss of synchronism
Fig. 1. Short circuit currents across generator terminals.
The loss of generator synchronization occurs when balanced steady state operation
is disrupted by strong disturbances: for example, when a short-circuit in the power
system causes a drop in the electrical power supplied by the generator and
the generator accelerates, still driven by the prime mover.
Operation as a motor
When a generator is driven like a motor by the power system (to which it is connected),
it applies mechanical energy to the shaft and this can cause wear and damage
to the prime mover.
Generator management
Normal generator management may be disturbed:
b inadvertent energization when the normal starting sequence is not complied with:
the generator, shut down but coupled to the power system, runs like a motor and may
damage the prime mover,
b power management: when there are several parallel sources, the number of
sources must be adapted to suit the power drawn by the loads; there is also the case
of islanded operation of an installation with its own power generation.
55
Generator protection Protection functions 0
Overloads
The overload protection functions for generators are the same as those for motors:
b IDMT overcurrent (ANSI 51),
b thermal overload (ANSI 49RMS),
b RTD temperature monitoring (ANSI 49T).
Unbalance
Protection is ensured, the same as for motors, by IDMT or definite time negative
sequence current detection (ANSI 46).
b As the value of short-circuit current decreases over time to approximately the rated
Is
current, if not lower, in steady state conditions, simple current detection may be
insufficient.
This type of fault can be detected effectively by a voltage-restrained overcurrent
protection device (ANSI 51V), the threshold of which increases with the voltage (fig.1).
0.2Is Operation is delayed.
b When the machine is equipped with a system that maintains the short-circuit at
U
0.3Un Un about 3 In, the use of a phase overcurrent protection unit (ANSI 51) is recommended.
b Another solution consists of using a delayed underimpedance protection unit (ANSI
Fig. 1. Voltage restrained overcurrent protection threshold. 21G), which may also provide back-up (ANSI 21B) for the overcurrent protection unit.
50
A
protection may be provided as follows (fig. 2):
G v instantaneous overcurrent protection (A), validated when the generator circuit
breaker is open, with current sensors on the neutral point side, set lower than
the rated current,
50 v instantaneous overcurrent protection (B), with current sensors on the circuit breaker
B
side, set higher than the generator short-circuit current.
56
Generator protection Protection functions 0
Field loss
Field loss is detected either by a delayed reactive overpower protection unit
(ANSI 32Q) for high power rating systems or by an underimpedance protection unit
(ANSI 40) for “islanded” power systems with generators, or by direct monitoring
of the excitation circuit if it is accessible (ANSI 40DC).
Loss of synchronization
Protection against the loss of synchronization is provided by a specific pole slip
protection function (ANSI 78PS) ; the pole slip measurement principle is based on
either an estimate of machine instability according to the equal-area criterion,
or by the detection of active power swings (fig. 1); an overspeed protection unit
(ANSI 12) may be used as back-up.
Withoutlossofsynchronization
5 7 57
4
DE55310EN
Activepower 4 6 Activepower 6
A2=A1 A3 A2=A1
8 8
Mechanical
power 1 1
(excluding
losses) 9 9
A1 A1
2 3 2 3
Time Internalangle
Withlossofsynchronization
Activepower
Activepower
4 A2 4
10 10
Mechanical 11 A2
power 5 1 5 11
1
(excluding
losses) 9 9
A1 A1
6 6
2 3 2 3
Time Internalangle
1 2 appearanceoffault
3 4 clearingoffault 7 7
4 11 powerswings 8 8
Operation as a motor
This is detected by a relay that detects reverse active power (ANSI 32P) drawn
by the generator.
G Inadvertent energization
The starting of generators according to a normal sequence is monitored by the
DE57309
Power management
The distribution of active power flows can be managed appropriately by the use of
directional active underpower protection units (ANSI 37P), which provide adequate
Fig. 2. Independent operation of an installation with its own control of source and load circuit breaker tripping (example in fig. 2).
generating unit.
57
Generator protection Recommended settings 0
58
Generator protection Examples of applications 0
DE57311
DE57312
38/ 27 38/ 21B
G 49T 32P G 49T 27
32Q 32P
49RMS 40
46 46
51G 49RMS
51V 51
51 51G
59 59
64REF 64REF
Vrsd 67 78PS
67N 81H
81H 81L
81L 87M
DE572314
Vnt
38/ 27 38/ 12
G 49T 32P G 49T 14
32Q 21B
46 27
49RMS 32P
26 51 26 40
63 51G(2x) 63 46
49T 51V 49T 49RMS
59 50N
67 51
67N 51G
81H 59
81L 64G
64REF
78PS
81H
81L
87T
59
Capacitor protection Types of faults 0
Capacitor banks are used to compensate for The main faults which are liable to affect capacitor banks are:
reactive energy drawn by power system b overloads,
b short-circuits,
b frame faults,
loads and occasionally in filters to reduce
harmonic voltage. Their role is to improve b short-circuit of an individual capacitor.
Overloads
the quality of the power system.
They may be connected in star, delta and
double star arrangements, depending on An overload is due to continuous or temporary overcurrent:
the level of voltage and the total rated power b continuous overcurrent due to:
v an increase in the supply voltage,
of the loads. v the flow of harmonic current due to the presence of non-linear loads such as static
A capacitor comes in the form of a case converters (rectifiers, variable speed drives), arc furnaces, etc.,
with insulating terminals on top. It comprises b temporary overcurrent due to energizing of a capacitor bank step.
individual capacitors (fig. 1) which have Overloads result in overheating which has an adverse effect on dielectric withstand
and leads to premature capacitor aging.
limited maximum permissible voltages
(e.g. 2250 V) and are mounted in groups: Short-circuits
b in series to obtain the required voltage A short-circuit is an internal or external fault between live conductors, phase-to-phase
withstand, (delta connection of capacitors) or phase-to-neutral (star connection).
b in parallel to obtain the desired power The appearance of gas in the gas-tight case of the capacitor creates overpressure
which may lead to the opening of the case and leakage of the dielectric.
rating.
Frame faults
There are 2 types of capacitor banks:
A frame fault is an internal fault between a live capacitor component and the frame
b without internal protection,
b with internal protection where a fuse made up of the metal case that is earthed for safety purposes.
is added for each individual capacitor. The fault current amplitude depends on the neutral earthing arrangement and
on the type of connection (star or delta).
Similar to an internal short-circuit, the appearance of gas in the gas-tight case
of the capacitor creates overpressure which may lead to the opening of the case
and leakage of the dielectric.
Group
DE57316EN
1 V
n–1
Group
2 V
Group
3 V
n–1
Group
n
Fig. 2. Capacitor bank without internal fuses. Fig. 3. Capacitor bank with internal
fuses.
60
Capacitor protection Protection functions 0
Overloads
b Extended overcurrents due to increases in the supply voltage can be avoided
by overvoltage protection (ANSI 59) that monitors the power-system voltage.
This protection may cover the capacitor itself or a larger part of the power system.
Given that the capacitor can generally accommodate a voltage of 110% of its rated
voltage for 12 hours a day, this type of protection is not always necessary.
b Extended overcurrents due to the flow of harmonic current are detected by an overload
protection of one the following types:
v thermal overload (ANSI 49RMS),
v time-delayed overcurrent (ANSI 51), provided it takes harmonic frequencies
into account.
b The amplitude of short overcurrents due to the energizing of a capacitor bank step
is limited by mounting impulse inductors in series with each step.
Short-circuits
Short-circuits are detected by time-delayed overcurrent protection (ANSI 51).
Current and time-delay settings make it possible to operate with the maximum
permissible load current as well as close and switch capacitor bank steps.
Frame faults
This type of protection depends on the neutral earthing arrangement.
If the neutral is earthed, time-delayed earth fault protection (ANSI 51G) is used.
61
Capacitor protection Recommended settings
and examples of applications 0
Recommended settings
Faults Suitable protection functions ANSI code Setting information
Overloads Overvoltage 59 Threshold ð 110% Un
Thermal overload 49 RMS Threshold ð 1.3 In
Time constant in the 10-minute range
Time-delayed overcurrent 51 Threshold ð 1.3 In, IDMT curve
Short-circuits Time-delayed overcurrent 51 Threshold approximately 10 In
Time delay approximately 0.1 s (DT)
Frame faults Time-delayed earth fault 51N/51G Threshold ð 20% I maximum earth fault
Threshold Š 10% CT rating is supplied by 3 CTs, with H2 restraint
Time delay approximately 0.1 s (DT)
Capacitor Time-delayed overcurrent 51 Threshold approx. 1 A, depending on the application
component Time delay approximately 1 s (DT)
short-circuit
Examples of applications
DE57320
51G
Delta compensation
DE57321
DE57322
49RMS 49RMS
51,51G 51,51G
51 59
62
Capacitor protection 0
63
Appendices Glossary
Key words and definitions
0
64
Appendices Glossary
Key words and definitions
0
65
Appendices Bibliography 0
66
Appendices Definitions of symbols 0
67
Appendices Index of technical terms 0
A I
aperiodic component 18 IEC 60909 17
B L
blocking signal 27, 31, 34, 35, 41, 42 line 18, 33, 44, 45
breaking capacity 18 load shedding 43
busbars 4, 5, 33 LPCT 19, 21
C M
cable 18, 33, 41, 44, 45 making capacity 18
capacitor 18, 27, 60, 61, 62 motor
capacitor bank 27 asynchronous 14, 50, 54, 55
characteristic angle 25 synchronous 14, 50, 53, 54
circuit breaker 17, 18, 27, 36–43, 45
circuit-breaker failure 43 N
coil neutral
extinction 10 compensated 6, 26, 37, 38
neutral point 9 impedant 26, 56, 58
Petersen 10 isolated 6, 7, 23
contactor 2, 18, 52, 54 solidly earthed 11, 37, 38
core balance CT 7, 8, 22, 26 neutral earthing 6-11
coupling 35, 39, 46, 57 neutral point 6–11, 37, 47, 48, 52, 56
current
residual 10, 22 O
short-circuit 12–19, 28, 30 overfluxing 47
current sensors 19-22, 33 overload 44, 47, 51, 56, 61
overvoltage 6–12, 61
D
decoupling 19, 26, 39 P
differential protection power
busbars 26 active 27, 39, 51, 53, 57, 58
generator 26 apparent 19, 23
high impedance 33, 58 rated output 19
line 26 reactive 53, 55, 57, 58
motor 26 short-circuit 11, 12, 45
percentage-based 48, 58 power system
restricted earth fault 26, 47, 48, 56, 58 architecture 3, 4, 5
transformer 26 loop 4, 5, 32, 35, 40, 41
discrimination radial 4, 5, 29, 31, 36
combined 34, 36 power factor 27
current-based 30, 34, 47 protection
differential 35 100% generator stator 26
directional 35 busbars 42, 43
logic 34, 35, 36 capacitor 60–62
time-based 28, 29, 31, 34, 35, 38 circuit breaker failure 26
differential 20, 26, 33, 35, 41, 42, 44, 47, 52, 53, 56
E directional active overpower 26
earthing 6–11 directional active underpower 26, 58
directional reactive overpower 26, 53, 58
F directional reactive underpower 26
fault, characterization 12, 18 distance 26, 45
fuse 18, 47, 50, 52, 60 excessive starting time and locked rotor 26, 51
field loss 26, 50, 52, 53, 55, 57, 58
G generator 55–59
generator 14–17, 33, 55–59 inadvertent generator energization 26
links 44, 45
H motor 50–54
harmonics 46, 47, 56, 58, 60 negative sequence / unbalance protection 26, 44, 53, 58
negative sequence overvoltage 26
68
Appendices Index of technical terms 0
R
rate of change of frequency 26, 39, 43
recloser 26, 45
residual voltage 7, 23, 37, 47, 52, 56
restraint
current 33
H2 (second harmonic) 22, 25, 47, 48, 62
H5 (fifth harmonic) 47
voltage 26, 56, 58
restricted earth fault 26, 47, 48, 56, 58
69
Appendices Notes 0
70
Appendices Notes 0
71
Appendices Notes 0
72
ART.065193 © 2008 Schneider Electric - All rights reserved
01/2008
CG0021EN