IO Module UI-16 Specification Sheet
IO Module UI-16 Specification Sheet
Introduction
The UI-16 is a universal input, 16 channel I/O
module.
Figure: Two-piece design
The universal inputs are ideal for any mix of Hot-connect and Hot-swap
temperature, pressure, flow, status points, and
Because critical applications require 24-hour
similar point types in a building control system. As
operation, Schneider Electric designed the I/O
counter inputs they are commonly used in energy
modules for hot-connection of terminal bases and
metering applications. As supervised inputs they
hot-swapping of the modules to their bases. This
are used for security applications where it is critical
design ensures continuous power and
to know whether or not a wire has been cut or
communication during service operations.
shorted. These events provide a separate indication
of alarms and trouble conditions to the system.
Auto-addressing
The auto-addressing feature eliminates the need for
Function
© 2014 Schneider Electric. All rights reserved.
Specifications
Input channels ........................................................................................................................................16
DC input supply power ......................................................................................................................1.8 W
DC input supply voltage ..................................................................................................................24 VDC
Environment
Ambient temperature, operating .............................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage .........................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity...............................................................................................95 % RH non-condensing
Material
Plastic rating................................................................................................................................UL94-5VB
Enclosure....................................................................................................................Eco Friendly ABS/PC
Enclosure rating...................................................................................................................................IP 20
Mechanical
Dimensions including terminal base ..............................90 W x 114 H x 64 D mm (3.6 W x 4.5 H x 2.5 D in.)
Part numbers
UI-16, I/O module
16 universal inputs .........................................................................................................SXWUI16XX10001
TB-IO-W1, terminal base for I/O module
(Required for each I/O module)......................................................................................SXWTBIOW110001
Accessory part numbers
DIN-RAIL-CLIP, DIN-rail end clip
package of 25 pieces ....................................................................................................SXWDINEND10001
PRINTOUT-A4-W1, printout sheets for terminal labels
A4 sheet size, 100 sheets, 18 labels per sheet...............................................................SXWTERLBL10011
PRINTOUT-LTR-W1, printout sheets for terminal labels
Letter sheet size, 100 sheets, 16 labels per sheet ..........................................................SXWTERLBL10012
S-CABLE-L, S-cable extension cord for Automation Server I/O bus L shaped connectors
1.5 m............................................................................................................................SXWSCABLE10002
S-CABLE-L, S-cable extension cord for Automation Server I/O bus L shaped connectors
0.75 m..........................................................................................................................SXWSCABLE10003
Universal inputs
The universal inputs of the UI-16 I/O module are
designed to read several different types of inputs.
Input types:
• Digital
• Counter
• Supervised
• Voltage
• Current
• Temperature
• Resistive
Digital inputs end of the cable close to the field contact, so that
The external connection of a digital input is shown the point where there is a risk that the circuit is
in the following figure. defeated is between the resistors and the I/O
module.
• Series only
• Parallel only
• Series and parallel
Each type of supervised input connection provides
a different capability in regards to what form of
tamper/trouble can be detected regardless of
switch contact open or closed condition.
Figure: Digital input external connection A single resistor, which is connected in series with
the switch, can only detect tamper/trouble in the
K is the monitored external switch. form of a short circuit across the wire pair. The
external connection of a series only supervised
VS = 24 V input connection is shown in the following figure.
RPU = 10 kohm
Counter inputs
A counter input utilizes the same hardware
configuration as the digital input as shown in the
figure above.
Supervised inputs
Supervised inputs are contact closing inputs
supplemented with the supervision of the field
wiring integrity. This supervision is a required
feature in many security system applications. The
supervised inputs provide the ability to detect
specific forms of tampering or trouble with the wire Figure: Series only external connection
connections to the field contacts. The supervision is
achieved with a combination of 1 or 2 resistors K is the monitored external switch.
attached to the contact in the field. The resistor
combination creates continuous current flow VS = 5 V
through the field contact loop and presents a
defined set of expected resistance values for each RPU = 10 kohm
of the defined conditions. If someone is attempting
to defeat the monitoring of the field contact by short A single resistor, which is connected in parallel with
© 2014 Schneider Electric. All rights reserved.
circuiting the wire with a jumper or cutting the wire, the switch, can only detect tamper/trouble in the
the objective is to detect and indicate such a form of an open circuit in the field wiring loop. The
condition. The resistors need to be located at the external connection of a parallel only supervised
input connection is shown in the following figure.
Voltage inputs
The external connection of a voltage input is shown
in the following figure.
Figure: Parallel only external connection Figure: Voltage input external connection
RSH = 47 ohm
VS = 5 V Temperature inputs
RPU = 10 kohm The external connection of a temperature input is
shown in the following figure.
Thermistor VS RPU
type
Resistive inputs
The external connection of a resistive input is
shown in the following figure.
Thermistor VS RPU
type
20 kohm 5V 10 kohm
Specifications
Universal inputs
LED polarity ..................................Software selectable, if the LED is activated when the input is high or low
LED color ................................................................................................Red or green, software selectable
Counter
Range .......................................Dry contract switch closure or open collector/open drain, 24 VDC, 2.4 mA
Minimum pulse width ........................................................................................................................20 ms
Maximum frequency ..........................................................................................................................25 Hz
LED polarity ..................................Software selectable, if the LED is activated when the input is high or low
LED color ................................................................................................Red or green, software selectable
Supervised
5 V circuit, 1 or 2 resistors
Monitored switch combinations...........................................Series only, parallel only, and series and parallel
Resistor range.........................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor is assumed to have the same value +/- 5 %
Voltage
Range.......................................................................................................................................0 to 10 VDC
Accuracy .........................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution..............................................................................................................................12 bit, 2.7 mV
Impedance...................................................................................................................................100 kohm
Reliability check .....................................................................................................................................Yes
Current
Range.........................................................................................................................................0 to 20 mA
Accuracy ....................................................................................................+/-(0.03 mA + 0.4 % of reading)
Resolution...............................................................................................................................12 bit, 5.6 μA
Impedance ......................................................................................................................................47 ohm
Reliability check .....................................................................................................................................Yes
Resistive
10 ohm to 10 kohm accuracy .................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 to 60 kohm accuracy.........................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Reliability check .....................................................................................................................................Yes
Temperature
Range .........................................................................................................-50 to +150 °C (-58 to +302 °F)
© 2014 Schneider Electric. All rights reserved.
Resolution...........................................................................................................................................12 bit
Reliability check .....................................................................................................................................Yes
Supported thermistors
Honeywell ......................................................................................................................................20 kohm
Type I (Continuum) .........................................................................................................................10 kohm
Type II (I/NET).................................................................................................................................10 kohm
Type III (Satchwell)..........................................................................................................................10 kohm
Type IV (FD)................................................................................................................................... 10 kohm
For protection from excess current that could be • Individual 24 VDC power sources to the field
produced by field wiring, follow these instructions: must be current limited to maximum of 4
amps for UL compliant installations, and no
• Connect one RET terminal on each of the I/O more than 6 amps in other areas.
modules to a common chassis/power ground
• For more information on wiring, see
rail in the control panel using a size 16 AWG,
Automation Server Family Hardware Guide.
1.3 mm, or larger wire.
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2004/108/EC Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following This equipment complies with the rules, of the Official Journal of the European Union, for
two conditions: (1) This device may not cause harmful interference. (2) This device must governing the Self Declaration of the CE Marking for the European Union as specified in
accept any interference received, including interference that may cause undesired the above directive(s) per the provisions of the following standards: IEC/EN 61326-1
operation. Product Standard, IEC/EN 61010-1 Safety Standard.
Industry Canada
ICES-003 WEEE - Directive of the European Union (EU)
This is a Class B digital device that meets all requirements of the Canadian Interference This equipment and its packaging carry the waste of electrical and electronic equipment
Causing Equipment Regulations. (WEEE) label, in compliance with European Union (EU) Directive 2002/96/EC, governing
the disposal and recycling of electrical and electronic equipment in the European
community.
C-Tick (Australian Communications Authority (ACA))
AS/NZS 3548
This equipment carries the C-Tick label and complies with EMC and radio UL 916 Listed products for the Unites States and Canada, Open Class Energy
communications regulations of the Australian Communications Authority (ACA), governing Management Equipment.
the Australian and New Zealand (AS/NZS) communities.
© 2014 Schneider Electric. All rights reserved.