R2B-P3-206-02-P-NC-00001 - Rev.1 - Complex Control Loop Description (FCC)
R2B-P3-206-02-P-NC-00001 - Rev.1 - Complex Control Loop Description (FCC)
(FCC)
BETWEEN
AND
This document, including any patented or patentable features, embodies confidential information of Samsung Ingeniería Manzanillo, S.A. de
C.V. and its use is conditioned upon the user’s agreement not to reproduce the document in whole or in part. Nor the material described thereon
nor to use the document for any purpose other than specifically permitted in writing by Samsung Ingeniería Manzanillo, S.A. de. C.V.
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
REVISION HISTORY
Rev DATE DESCRIPTION
* Notes:
Table of Contents
1. INTRODUCTION ....................................................................................................................................................... 5
2. ABBREVIATION ........................................................................................................................................................ 6
3.10 Main air blower surface condenser (SPE-21020) level control ....................................................................... 19
3.39 Wet gas compressor surface condenser (SPE-21201) level control ............................................................... 59
4. REFERENCE .......................................................................................................................................................... 71
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
1. INTRODUCTION
PTI-Infraestructura de Desarrollo, S.A. de C.V. will construct a new refinery at Dos Bocas Paraiso,
Tabasco RDB to process heavy Maya crude oil (22 °API), based on a Delayed Coking/FCC
configuration to maximize distillate production. The refinery will have a single crude train with a
processing capacity of 340,000 BPSD. The main purpose of the RDB Project is produce valuable
products such as propane, propylene, gasoline and diesel and others, in order to reduce imports of
fuels from abroad.
This document provides detailed operating and control features of the Fluid Catalyst Cracking Unit
(Unit 21000) at the Dos Bocas Refinery. The objective of the unit is to convert heavy crude oil
fractions into lighter, more valuable hydrocarbon products at high temperature and moderate
pressure in the presence of a finely divided silica / alumina based catalyst, and to produce light
hydrocarbon gases (C2-) which are normally used within the refinery as fuel gas, LPG olefins and
paraffins, gasoline, light cycle oil (LCO), and clarified oil (CLO, sometimes referred to as main
column bottoms).
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
2. ABBREVIATION
PV : PROCESS VALUE
SV : SET VALUE
OP : OUTPUT VALUE
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: FV-21057
LIC-21007
FI-21059
FY-21060
FIC-21057
FT-21057
LT-21007
PFD: R2B-P3-206-02-A-DFP-00001
P&ID: R2B-P3-206-02-A-DTI-00074
R2B-P3-206-02-A-DTI-00074A
R2B-P3-206-02-A-DTI-00075A
3.1.1 Objective
To control the Boiler Drum Level (in Flue Gas Steam Generator SPE-21012) by adjusting the Boiler
feed water flow rate to the Flue Gas Steam Generator SPE-21012.
summer FY-21060 sends signal as setpoint to FIC-21057 which is the set point for controls the valve
FV-21057.
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: PDV-21011
PDIC-21011
TIC-21008
HY-21017
TT-21008
PDT-21011
PFD: R2B-P3-206-02-A-DFP-00003
P&ID: R2B-P3-206-02-A-DTI-00061
R2B-P3-206-02-A-DTI-00061A
3.2.1 Objective
To control the Direct Fired Air Heater (BA-21001) Outlet temperature
Tags: XV-21529
PIC-21528A/B
PY-21529
IGV-21528
PT-21528
PT-21529
PFD: R2B-P3-206-02-A-DFP-00002
P&ID: R2B-P3-206-02-A-DTI-00080
R2B-P3-206-02-A-DTI-00080A
R2B-P3-206-02-A-DTI-00080B
R2B-P3-206-02-A-DTI-00081
3.3.1 Objective
To control the discharge pressure of Fluffing Air compressor (GB-21002) by GB-21002 PLC.
Tags: PV-21046A/B
PIC-21046
PY-21046A/B
PT-21046
PFD: R2B-P3-206-02-A-DFP-00013
P&ID: R2B-P3-206-02-A-DTI-00070
3.4.1 Objective
To control the Dry Gas header supply pressure
PFD: R2B-P3-206-02-A-DFP-00003
P&ID: R2B-P3-206-02-A-DTI-00012
3.5.1 Objective
To control the flow of Raw oil and Atomizing Steam to Regenerator
Tags: SPE-21004
PDIC-21039
PIC-21017
PDY-21039C
PT-21017
PDT-21039
ZI-21001A/B
PFD: R2B-P3-206-02-A-DFP-00001
R2B-P3-206-02-A-DFP-00003
P&ID: R2B-P3-206-02-A-DTI-00062
R2B-P3-206-02-A-DTI-00068
R2B-P3-206-02-A-DTI-00073
3.6.1 Objective
To control the Regenerator (DC-21002) pressure and maintain the differential pressure between
the Reactor (DC-21001) and Regenerator
Tags: SPE-21001
TIC-21056
TY-21056
PDIC-21020
TT-21056
PDT-21020
PFD: R2B-P3-206-02-A-DFP-00003
P&ID: R2B-P3-206-02-A-DTI-00064
R2B-P3-206-02-A-DTI-00072
3.7.1 Objective
To control the flow of Regenerated catalyst and Reactor temperature
Tags: SPE-21002
LIC-21005
LY-21005
PDIC-21038
PDT-21038
LT-21005
PFD: R2B-P3-206-02-A-DFP-00003
P&ID: R2B-P3-206-02-A-DTI-00067
R2B-P3-206-02-A-DTI-00068
3.8.1 Objective
To control the flow of Spent catalyst and Reactor catalyst bed level
Tags: SPE-21003A/B
DIC-21006
DY-21006A/B
PDIC-21018/21019
HS-21004/21005
HIC-21004/21005
PDT-21018
PDT-21019
DT-21006
PFD: R2B-P3-206-02-A-DFP-00003
P&ID: R2B-P3-206-02-A-DTI-00063
3.9.1 Objective
To control the flow of recirculation catalyst
PFD: R2B-P3-206-02-A-DFP-00001
P&ID: R2B-P3-206-02-A-DTI-00078
3.10.1 Objective
To control the level of Main air blower surface condenser
Valve Opening
100
%
LV-21010A
LV-21010B
Controller Output
0% 5% 50%
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: XY-21018
P&ID: R2B-P3-206-02-A-DTI-00011
3.11.1 Objective
To configure a “Regenerator Catalyst Distance to Flapper Valves” function.
Tags: XY-21019
P&ID: R2B-P3-206-02-A-DTI-00011
3.12.1 Objective
To configure a “Start-Up Regenerator Superficial Velocity” function.
Tags: XY-21020
P&ID: R2B-P3-206-02-A-DTI-00011
3.13.1 Objective
To configure a “Regenerator Cyclone Inlet Velocity” function.
Tags: XY-21021
P&ID: R2B-P3-206-02-A-DTI-00011
3.14.1 Objective
To configure a “Regenerator Catalyst Circulation Rate” function.
Tags: XY-21022
P&ID: R2B-P3-206-02-A-DTI-00011
3.15.1 Objective
To configure a “Regenerator Density Compensated Catalyst Level” function.
Tags: XY-21023
P&ID: R2B-P3-206-02-A-DTI-00011
3.16.1 Objective
To configure a “Reactor Catalyst Level Clearance below Vent Pipes” function.
Tags: XY-21024
P&ID: R2B-P3-206-02-A-DTI-00011
3.17.1 Objective
To configure a “Reactor Cyclone Inlet Velocity” function.
Tags: XY-21025
P&ID: R2B-P3-206-02-A-DTI-00011
3.18.1 Objective
To configure a “Two Acceleration Zone Velocities” function.
Tags: FV-21101
FIC-21101
LIC-21100
TV-21110A/B
TIC-21110
TY-21110A/B
TV-21103A/B
TIC-21103
FT-21101
LT-21100
TT-21103
TT-21110
TY-21103A/B
PFD: R2B-P3-206-02-A-DFP-00005
R2B-P3-206-02-A-DFP-00006
P&ID: R2B-P3-206-02-A-DTI-00101
R2B-P3-206-02-A-DTI-00103
R2B-P3-206-02-A-DTI-00104
R2B-P3-206-02-A-DTI-00105
3.19.1 Objective
To control Feed flow (Hydrotreated Gas Oil from storage) to Raw Oil Feed Surge Drum (FA-21101)
and heat the charge to the desired reactor riser inlet temperature.
drum (FA-21101) will be displayed in HDTGO DCS. When LAH-21100 is activated, operators shall
communicate with FCC operators and gas oil should be transferred to storage after confirming
upset condition in FCC unit.
TV-21103A and TV-21103B is controlled by TIC-21103 which measures temperature of Raw oil
on shell side outlet of Main Column Bottoms-Raw Oil Exchangers (EA-21104A/B). The TIC-21103
controls with split range as follows;
Low temperature signal closes TV-21103B (Shell side bypass).
High temperature signal closes TV-21103A (Shell side inlet).
Tags: FV-21116
LIC-21106
FI-21114
FY-21115
FIC-21116
LT-21006
FT-21115
FT-21114
PFD: R2B-P3-206-02-A-DFP-00006
P&ID: R2B-P3-206-02-A-DTI-00110
3.20.1 Objective
To control the Main Column Bottoms Steam Generators EA-21108A level by adjusting the Boiler feed
water flow rate to the Steam generator (EA-21108A).
Tags: FV-21120
LIC-21109
FI-21118
FY-21119
FIC-21120
LT-21109
FT-21118
FT-21120
PFD: R2B-P3-206-02-A-DFP-00006
P&ID: R2B-P3-206-02-A-DTI-00111
3.21.1 Objective
To control the Main Column Bottoms Steam Generators EA-21108B level by adjusting the Boiler feed
water flow rate to the Steam generator (EA-21108B).
Tags: FV-21125
LIC-21112
FI-21123
FY-21124
FIC-21125
LT-21112
FT-21123
FT-21125
PFD: R2B-P3-206-02-A-DFP-00006
P&ID: R2B-P3-206-02-A-DTI-00112
3.22.1 Objective
To control the Main Column Bottoms Steam Generators EA-21108C level by adjusting the Boiler feed
water flow rate to the Steam generator (EA-21108C).
Tags: FV-21111A/B
FIC-21111
FY-21111A/B/C
FY-21111
FI-21104
FI-21112
FT-21112
FT-21104
PFD: R2B-P3-206-02-A-DFP-00005
P&ID: R2B-P3-206-02-A-DTI-00108
3.23.1 Objective
To control the flow of filtered Main Column Bottoms product to storage tank and Delayed Coker Unit.
Tags: FV-21130
FIC-21130
LIC-21117
FT-21130
LT-21117
PFD: R2B-P3-206-02-A-DFP-00006
P&ID: R2B-P3-206-02-A-DTI-00117
R2B-P3-206-02-A-DTI-00118
3.24.1 Objective
To control the flow of Circulating Heavy Cycle Oil return to Main Column (DF-21101).
Tags: TV-21152A/B
TIC-21152
TT-21152
PFD: R2B-P3-206-02-A-DFP-00007
P&ID: R2B-P3-206-02-A-DTI-00124
3.25.1 Objective
To control the temperature of Light Cycle Oil product going to Intermediate Distillate
Hydrodesulfurization Unit (by others)
Tags: FV-21135A/B
FIC-21135
FI-21136/21137
FY-21135A/B/C
FT-21136
FT-21137
PFD: R2B-P3-206-02-A-DFP-00007
P&ID: R2B-P3-206-02-A-DTI-00124
R2B-P3-206-02-A-DTI-00125
3.26.1 Objective
To control the flow of Light Cycle Oil product going to Intermediate Distillate Hydrodesulfurization Unit
(by others) and Storage Tank.
Tags: FV-21142
FIC-21142
LIC-21124
LT-21124
FT-21142
PFD: R2B-P3-206-02-A-DFP-00008
P&ID: R2B-P3-206-02-A-DTI-00128
R2B-P3-206-02-A-DTI-00131
3.27.1 Objective
To control the level in Main Column Receiver (FA-21102) by controlling flow of Unstabilized gasoline
liquid from the Main Column Receiver (FA-21102) to Gas Concentration Unit.
3.27.2 Functional Description
The unstabilized gasoline liquid in the Main Column Receiver (FA-21102) not used as reflux is pumped
to the gas concentration section on level control.
It operates off a level controller LIC-21124 on the Main Column receiver and FIC-21142 acting on FV-
21142 in order to maintain the level.
The FIC-21142 receives output from LIC-21124 to control FV-21142.When the process value from
LIC-21124 increases, the set point to the FIC-21142 increases and FV-21142 starts to open.
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: FV-21127
FIC-21127
TIC-21130
TT-21130
FT-21127
PFD: R2B-P3-206-02-A-DFP-00006
P&ID: R2B-P3-206-02-A-DTI-00117
3.28.1 Objective
To control the overhead vapor temperature of Main Column (DF-21101)
Tags: XY-21100/21102/21104/21106/21108/21110/21112
3.29.1 Objective
To configure a “Exchanger Fouling” function.
Tags: XY-21101/21103/21105/21107/21109/21111/21113
3.30.1 Objective
To configure a “Exchanger Tube Velocity” function.
Tags: PV-21200A/B
PIC-21200
PY-21200A/B
PT-21200
PFD: R2B-P3-206-02-A-DFP-00010
P&ID: R2B-P3-206-02-A-DTI-00201
3.31.1 Objective
To control the pressure of Water Break Tank
Tags: FV-21213
FIC-21213
LIC-21208
LT-21208
FT-21213
PFD: R2B-P3-206-02-A-DFP-00010
P&ID: R2B-P3-206-02-A-DTI-00213
R2B-P3-206-02-A-DTI-00214
3.32.1 Objective
To control the level in High Pressure Receiver (FA-21204) by controlling flow of liquid hydrocarbons
from the High Pressure Receiver (FA-21204) to Stripper (DS-21201).
Tags: FV-21217
FIC-21217
LIC-21212
LT-21212
FT-21217
PFD: R2B-P3-206-02-A-DFP-00011
P&ID: R2B-P3-206-02-A-DTI-00215
R2B-P3-206-02-A-DTI-00218
3.33.1 Objective
To control the flow of Circulating Rich Gasoline to Primary Absorber (DA-21201)
Tags: TV-21217A/B
TIC-21217
FV-21222
FIC-21222
LIC-21222
TT-21217
FT-21222
LT-21222
PFD: R2B-P3-206-02-A-DFP-00012
P&ID: R2B-P3-206-02-A-DTI-00223
R2B-P3-206-02-A-DTI-00229
3.34.1 Objective
To control the temperature of Debutanizer Bottoms product to Debutanizer Bottoms Cooler (EC-21203)
inlet and level of Debutanizer (DF-21201) Bottom
2) Debutanizer level:
The FIC-21222 receives output from LIC-21222 to control FV-21222.When the process value from
LIC-21222 increases, the set point to the FIC-21222 increases and FV-21222 starts to open.
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: FV-21225
FIC-21225
FIC-21224
FT-21224
FT-21225
PFD: R2B-P3-206-02-A-DFP-00012
P&ID: R2B-P3-206-02-A-DTI-00226
R2B-P3-206-02-A-DTI-00227
3.35.1 Objective
To control the overhead vapor flow rate from Stripper (DS-21201)
Tags: FV-21231
FIC-21231
TIC-21229
FT-21231
TT-21229
PFD: R2B-P3-206-02-A-DFP-00012
P&ID: R2B-P3-206-02-A-DTI-00229
R2B-P3-206-02-A-DTI-00232
3.36.1 Objective
To control the reflux flow rate to Debutanizer (DF-21201)
Tags: FV-21232
FIC-21232
LIC-21224
TV-21242A/B
TIC-21242
TY-21242A/B
TT-21242
LT-21224
FT-21232
PFD: R2B-P3-206-02-A-DFP-00012
P&ID: R2B-P3-206-02-A-DTI-00230
R2B-P3-206-02-A-DTI-00232
3.37.1 Objective
To control the level of Debutanizer Receiver (FA-21206) and the outlet temperature to Merox unit
Tags: PV-21219A/B
PIC-21219
PY-21219A/B/C
PT-21219
PFD: R2B-P3-206-02-A-DFP-00012
P&ID: R2B-P3-206-02-A-DTI-00230
3.38.1 Objective
To control the pressure of Debutanizer (DF-21201)
PFD: R2B-P3-206-02-A-DFP-00010
P&ID: R2B-P3-206-02-A-DTI-00234
3.39.1 Objective
To control the level of Wet gas compressor surface condenser
Tags: FV-21402
FIC-21402
LIC-21400
LY-21400A/B
PFD: R2B-P3-206-02-A-DFP-00018
P&ID: R2B-P3-206-02-A-DTI-00401
R2B-P3-206-02-A-DTI-00402
3.40.1 Objective
To control the level of C3/C4 Splitter (DF-21401)
Tags: FV-21403
FIC-21403
LIC-21401
FY-21403
LT-21401
FT-21403
PFD: R2B-P3-206-02-A-DFP-00018
P&ID: R2B-P3-206-02-A-DTI-00402
3.41.1 Objective
To control the level of C3/C4 Splitter Reboiler Condensate Drum (FA-21404)
Tags: FV-21407
FIC-21407
LIC-21402
FV-21405
FIC-21405
TIC-21402
LT-21402
FT-21407
FT-21405
TT-21402
PFD: R2B-P3-206-02-A-DFP-00018
P&ID: R2B-P3-206-02-A-DTI-00402
R2B-P3-206-02-A-DTI-00403
R2B-P3-206-02-A-DTI-00405
3.42.1 Objective
To control the level of C3/C4 Splitter Receiver (FA-21401) and maintain reflux to the C3/C4 Splitter
(DF-21401)
21405. The FIC-21405 receives output setpoint from TIC-21402 to control FV-21405.When the
process value from TIC-21402 increases, the set point to the FIC-21405 increases and FV-21405
starts to open.
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: FV-21411
FIC-21411
LIC-21405
FY-21411
LT-21405
FT-21411
PFD: R2B-P3-206-02-A-DFP-00019
P&ID: R2B-P3-206-02-A-DTI-00407
3.43.1 Objective
To control the level of Deethanizer Reboiler Condensate Drum (FA-21405)
Tags: FV-21410
FIC-21410
LIC-21406
LT-21406
FT-21410
PFD: R2B-P3-206-02-A-DFP-00019
R2B-P3-206-02-A-DFP-00020
P&ID: R2B-P3-206-02-A-DTI-00407
3.44.1 Objective
To control the level of Deethanizer (DF-21402)
Tags: FV-21413
FIC-21413
LIC-21408
LT-21408
FT-21413
PFD: R2B-P3-206-02-A-DFP-00019
P&ID: R2B-P3-206-02-A-DTI-00408
R2B-P3-206-02-A-DTI-00409
3.45.1 Objective
To control the level of Deethanizer Receiver (FA-21402) and provide reflux to Deethanizer (DF-21402)
3.45.2 Functional Description
Deethanizer overhead material gets condensed partially through a water-cooled exchanger,
Deethanizer Condenser (EA-21406) and enters into the vessel, Deethanizer Receiver (FA-21402)
which is operated at the controlled pressure of 22.8 kg/cm2g. The liquid stream from receiver is
pumped by, Deethanizer Reflux Pumps (GA-21402 A/B) and sent as total reflux to the Deethanizer
column.
Level controller LIC-21408 on the Deethanizer Receiver (FA-21402) resets FIC-21413 acting on FV-
21413 in order to maintain the level.
The FIC-21413 receives output setpoint from LIC-21408 to control FV-21413.When the process value
from LIC-21408 increases, the set point to the FIC-21413 increases and FV-21413 starts to open.
PHASE II OF REFINERY IN DOS BOCAS
(FCC)
Tags: FV-21415
FIC-21415
LIC-21412
LT-21412
FT-21415
PFD: R2B-P3-206-02-A-DFP-00019
R2B-P3-206-02-A-DFP-00020
P&ID: R2B-P3-206-02-A-DTI-00410
R2B-P3-206-02-A-DTI-00411
3.46.1 Objective
To control the level of C3 Splitter (DF-21403)
Tags: FV-21420
FIC-21420
PIC-21412
FV-21417
FV-21422
FIC-21417
FIC-21422
FY-21422
FV-21416
FIC-21416
LIC-21414
AIC-21400
PFD: R2B-P3-206-02-A-DFP-00020
P&ID: R2B-P3-206-02-A-DTI-00411
R2B-P3-206-02-A-DTI-00412
R2B-P3-206-02-A-DTI-00413
R2B-P3-206-02-A-DTI-00415
3.47.1 Objective
To control the split between propylene and propane from C3 Splitter
Tags: PV-21522A/B
PIC-21522
PFD: R2B-P3-206-02-A-DFP-00020
P&ID: R2B-P3-206-02-A-DTI-00503
3.48.1 Objective
To control the pressure of Treated Dry Gas KO Drum (FA-21502) and regulate the Fuel gas flow to
Header
4. REFERENCE
Attachment 1. 9038069-623-04-(N) Control Center Equip Rev 00
Attachment 2. 9038070-623-04-(N) Control Center Equip Rev 00
Attachment 3. 9038071-623-04-(N) Control Center Equip Rev 00
Attachment 4. 9038072-623-04-(N) Control Center Equip Rev 00
Attachment 5. 9038073-623-04-(N) Control Center Equip Rev 00
Revision Attachment 1.
Indication PROJECT SPECIFICATION
UOP Engineering Department
9038069 — 623-N SHEET 1
Notes:
In the functions which follow, various constants and DCS variables are required. Tables I through III list
constants and variables which are used throughout the calculations. Table IV lists intermediate calculated
variables which are also used throughout the calculations. Function-specific constants and variables are
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
Physical constants are universal constants which should never change. Adjustable constant are constants
which might be periodically updated by the unit supervisor after the unit is operating (recommended initial
values are provided). Dimensional constants are constants which should be determined based on the
contractor’s as-built mechanical drawings and instrumentation specifications.
Notes:
I1
0.00085 0.00085
Inerts Entrained with Spent Catalyst
lb/1000 lbcatalyst kg/1000kgcatalyst
I2 Inerts Entrained with Regenerated catalyst 0.00135 0.00135
lb/1000 lbcatalyst kg/1000kgcatalyst
M Rx Molecular Weight of Reactor Products 69.1 lb/lbmole 69.1 kg/kgmole
Notes:
Notes:
The distance below the flapper valves is equal to the differential range of level at the flapper valves
minus the level reading divided by the ratio of dense phase density to water density.
ind f
transcr H2O + (L tap − FVelev ) cat dense + (FVelev − U tap ) cat dilute
100
h =
cat dilute − cat dense
Notes:
2. Configure a “Start-Up Regenerator Superficial Velocity” function to calculate the superficial linear
velocity based on changes in measured flow into the Regenerator and its operating temperature and
pressure.
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
At constant inlet flow rates a decrease in absolute Regenerator operating temperature results in a
proportional decrease in superficial linear velocity even though the mass flow remains the same.
At constant inlet flow rates a decrease in absolute pressure results in an inversely proportional increase in
superficial linear velocity even though the mass flow remains the same.
The computation is provided by summing the air flow rates (corrected to actual conditions), dividing by
the area of the Regenerator and correcting for time units of seconds.
Q t Ps (To + Tf )
( + )
V =
Pb Pf Ts
3600 A t
Notes:
3. Configure a “Regenerator Cyclone Inlet Velocity” function. Note UDV is a “user defined variable”
supplied by UOP during unit startup.
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
Q t Ps (To + Tf )
( + )
V =
Pb Pf Ts
3600 A t
Notes:
H S + H N + H F + H Rx
CCR = ( )
Cp C (TRC − TRX )
The computations shall be made as follows:
TRC =
o o
Regenerated Catalyst Temperature - DCS variable F C
TI-21037
TSC =
o o
Spent Catalyst Temperature - DCS variable F C
TI-21045
Notes:
5. Configure a “Reactor Density Compensated Catalyst Level” function to calculate the actual height of
the Reactor Catalyst Level based on changes in measured density in the Reactor.
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
An increase in the density in the Reactor catalyst bed results in an increase in the differential pressure
measured by level transmitter, while the actual height of the catalyst bed remains constant.
ind f
transcr H2O − (U tap − L tap ) cat dilute
100
h =
cat dense − cat dilute
Notes:
The distance below the VSS Top of Window is equal to the differential range of level at the VSS Top of
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
Window minus the level reading divided by the ratio of dense phase density to water density.
ind f
transcr H2O + (L tap − TWelev ) cat dense + (TWelev − U tap ) cat dilute
100
h =
cat dilute − cat dense
cat dilute = Flowing Reactor Vapor Space Density - adjustable 0.1 lb/ft3 1.60 kg/m3
constant
Notes:
8. Configure two Acceleration Zone Velocities functions to compute the riser velocity in the Reactor Riser
acceleration zone. The Acceleration Zone Velocity is proportional to the mass flow in the riser divided
by the riser cross sectional area and the flowing density.
Notes:
9. Each compressor alarm listed in UOP Project Specification 508, this project, shall activate an individual
control center alarm which shall occur simultaneously with the activation of the associated alarm on the
local panel. Additional alarms, as required by the compressor vendor, shall also be repeated in the
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
11. Configure a summing function. The system is designed so that for every weight unit of steam make a
weight unit of feed water is introduced and the level controller signal is only used to compensate for
blowdown and error in steam or water flow measurement. A moderate proportional band and slow reset
on the level controller is required so that sudden changes in level will not affect the feedwater flow
controller. Only average level changes are to affect the boiler feedwater flow controller.
LIC-21007.OP
FYsummer = C FI steam + (Range of FIC boiler feedwater ) (Level Controller Output - 50)
FY-21060.OP FI-21059.PV FIC-21057 100
Where:
• FYsummer is the output of the summer, and is the remote setpoint to FICboiler feedwater, the boiler feedwater flow
controller.
• C is a factor to convert the mass flow of produced steam to an equivalent quantity of boiler feedwater,
depending on the units of measurement.
• FIsteam is the steam flow indication in mass units.
• The level controller output is in units of percent.
• A bias signal - set at 50% - is subtracted from the level controller output to enable the level controller to
adjust for both increasing and decreasing level.
The boiler feedwater flow controller shall be capable of independent flow control when not in cascade
mode.When the boiler feedwater flow controller is not in cascade mode, the setpoint of the level
controller shall track the level indication, and the level controller output shall track the result of the
following equation:
FIC-21057.SV FI-21059.PV
100 (Setpoint of FIC boiler feedwater - C FI steam )
Level Controller Output = 50 +
LIC-21007.OP
Range of FIC boiler feedwater
FIC-21057
Notes:
12. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
13. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Direct Fired Air Heater Emergency Shutdown”. Switch shall be wired
such that in:
Position Label Description
1 NORMAL The switch contact is closed and the shutdown circuit is
energized.
2 SHUTDOWN The switch contact is open and the shutdown circuit is
deenergized for shutdown.
14. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Raw Oil Feed Low Flow”. Switch shall be wired such that in:
Position Label Description
1 NORMAL The switch contacts are open and the bypass circuit is
deenergized.
2 BYPASS The switch contacts are closed and the bypass circuit is
energized.
Provide a backlighted nameplate, HL-21900A engraved “Raw Oil Feed Low Flow Shutdown
Bypassed”. Nameplate to be illuminated when the switch is in the bypass position.
Notes:
15. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved per distribution list below. Switch shall be wired such that in:
Position Label Description
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
1 See below The switch contact is closed, and the shutdown circuit is
energized.
2 See below The switch contact is open, and the shutdown circuit is
deenergized for shutdown.
** See UOP Project Specification 660, this project, for the UOP FCC Emergency Interlock System.
Switch function shall not be implemented in the software of a distributed control system. Only hard-
wired switches are permitted.
16. Provide a three-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “UOP FCC Emergency Interlock System Operational Mode Selection”.
Switch shall be wired such that in:
Position Label Description
1 RAW OIL The switch contact is closed and the feed shutdown circuit
is energized.
2 STARTUP The switch contact is closed and the startup naphtha
NAPHTHA shutdown circuit is energized.
3 DIVERT / The switch contact is closed and the Emergency Interlock
RESET System is de-energized.
Provide a backlighted nameplate, HL-21903A engraved “Feed to Reactor Bypassed”. Nameplate is to
be illuminated when the switch is not in the “Raw Oil” position. See UOP Project Specification 660,
this project, for the UOP FCC Emergency Interlock System. Switch function shall not be implemented
in the software of a distributed control system. Only hard-wired switches are permitted.
17. Provide a spring return pushbutton. When depressed, the contact closes and the UOP FCC Emergency
Interlock System may be reset manually from the control center. Provide nameplate engraved “UOP
FCC Emergency Interlock System - Shutdown Reset”. See UOP Project Specification 660, this
project, for the UOP FCC Emergency Interlock System.
Notes:
18. Provide a three-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Diverter Valve Position Selection”. Switch shall be wired such that in:
Position Label Description
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
Notes:
1. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Raw Oil Pumps Manual Stop”. Switch shall be wired such that in:
Position Label Description
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
2. Configure an “Exchanger Fouling” function to calculate the fouling trend based on changes in
measured flow into the exchanger and its operating temperature for the following services.
Tag Number Service
XY-21100 Circulating Main Column Bottoms-Raw Oil Exchanger A EA-21104A
XY-21106 Main Column Bottoms Product-Raw Oil Feed Exchanger No.1 EA-21101A/B
W (T1 − T2 )
UA =
LMTD
LMTD =
GTTD − LTTD
=
(T1 − T4 ) − (T2 − T3 )
GTTD T1 − T4
LN LN
LTTD T2 − T3
English Metric
where: Description Units Units
GTTD = The Greater Terminal Difference - (T1 – T4) °F °C
LMTD = Log Mean Temperature Difference
LTTD = The Lesser Terminal Difference - (T2 – T3) °F °C
T1 = Exchanger Tube Side Inlet - DCS variable °F °C
T2 = Exchanger Tube Side Outlet - DCS variable °F °C
T3 = Exchanger Shell Side Inlet - DCS variable °F °C
T4 = Exchanger Shell Side Outlet - DCS variable °F °C
Notes:
3. Configure an “Exchanger Tube Velocity” function to calculate the velocity based on changes in
measured flow into the exchanger and its operating temperature for the following services.
Tag Number Service
XY-21101 Circulating Main Column Bottoms-Raw Oil Exchanger A EA-21104A
XY-21107 Main Column Bottoms Product-Raw Oil Feed Exchanger No.1 EA-21101A/B
sg b
Q K
sg f
V=
π d2
3600 N T
4
English Metric
where: Description Units Units
d= Internal Diameter of Tubes in Exchanger - constant ft m
NT = Number of Tubes in First Pass of Exchanger - constant
Q= Circulating Main Column Bottoms Volumetric Flow - DCS variable bpd m3/h
(at Base Temperature)
sg b = Base Specific Gravity of Fluid – constant (at Base Temperature)
sg f = Flowing Specific Gravity of Fluid – constant (at Flowing Temperature)
V= Exchanger Velocity - calculated ft/s m/s
= Pi – ratio of the circumference of a circle to its diameter - constant 3.1416 3.1416
Notes:
4. Configure a summing function. The system is designed so that for every weight unit of steam make a
weight unit of feed water is introduced and the level controller signal is only used to compensate for
blowdown and error in steam or water flow measurement. A moderate proportional band and slow reset
on the level controller is required so that sudden changes in level will not affect the feedwater flow
controller. Only average level changes are to affect the boiler feedwater flow controller.
LIC-21106.MV
LIC-21109.MV
FYsummer = C FI steam + (Range of FIC boilerfeedwater )
LIC-21112.MV
(Level Controller Output - 50)
FY-21115.MV FI-21114.PV FIC-21116 100
FY-21119.MV FI-21118.PV FIC-21120
Where: FY-21124.MV FI-21123.PV FIC-21125
• FYsummer is the output of the summer, and is the remote setpoint to FICboiler feedwater, the boiler feedwater flow
controller.
• C is a factor to convert the mass flow of produced steam to an equivalent quantity of boiler feedwater,
depending on the units of measurement.
• FIsteam is the steam flow indication in mass units.
• The level controller output is in units of percent.
• A bias signal - set at 50% - is subtracted from the level controller output to enable the level controller to
adjust for both increasing and decreasing level.
The boiler feedwater flow controller shall be capable of independent flow control when not in cascade
mode.
When the boiler feedwater flow controller is not in cascade mode, the setpoint of the level controller
shall track the level indication, and the level controller output shall track the result of the following
equation: FIC-21116.SV FI-21114.PV
FIC-21120.SV FI-21118.PV
Notes:
5. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Main Column Bottoms Circulation Pump C Emergency Shutdown”.
Switch shall be wired such that in:
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
6. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Main Column Bottoms Circulation Pump A Emergency Shutdown”.
Switch shall be wired such that in:
Position Label Description
1 NORMAL The switch contact is closed and the shutdown circuit is
energized.
2 SHUTDOWN The switch contact is open and the shutdown circuit is
deenergized for shutdown.
7. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Main Column Bottoms Circulation Pump B Emergency Shutdown”.
Switch shall be wired such that in:
Position Label Description
1 NORMAL The switch contact is closed and the shutdown circuit is
energized.
2 SHUTDOWN The switch contact is open and the shutdown circuit is
deenergized for shutdown.
Notes:
1. Each compressor alarm listed in UOP Project Specification 508, this project, shall activate an individual
control center alarm which shall occur simultaneously with the activation of the associated alarm on the
local panel. Additional alarms, as required by the compressor vendor, shall also be repeated in the
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
2. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Notes:
1. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
2. Each compressor alarm listed in UOP Project Specification 508, this project, shall activate an individual
control center alarm which shall occur simultaneously with the activation of the associated alarm on the
local panel. Additional alarms, as required by the compressor vendor, shall also be repeated in the control
center in this manner.
3. Configure a summing function which will add the flow signals from FIC-21417 (Net Overhead Liquid)
and FI-21418 (Reflux). The output signal of the summing function is the measurement signal to FIC-
21422 controller (Total Overhead Liquid).
The function of this system is to automatically increase or decrease the reflux flow by the same quantity
as any decrease or increase of the net overhead liquid flow. Thus the total overhead liquid flow rate is
unchanged unless the level in the receiver changes. A change in the net overhead liquid flow rate will
result in an immediate corresponding change in the reflux flow rate.
Notes:
1. Provide an adjustable timer to start the Prewash Water Injection Pumps and Prewash Caustic Injection
Pumps (as selected by the Hand-Off-Auto switches in the field, provided by others) via relay XY-
21301A and XY-21301C, to start the Caustic Injection Pumps (as selected by the Hand-Off-Auto
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
switches in the field, provided by others) via relay XY-21301B, and to initiate the flow of Lean Caustic
to the Caustic Prewash Circulation via set point selector XY-21301D.
When the timer is on, set point selector XY-21301D will put the Lean Caustic to Caustic Prewash
Circulation flow controller FIC-21309 into automatic mode with the set point selected by the operator.
When the timer is off, FIC set point will be set to zero, its FAL will be set inactive, and it will be put into
manual with an output of zero. Also, the selected Prewash Water Injection Pumps, and Prewash Caustic
Injection Pump, will stop via relay XY-21301A and XY-21301C, and the selected Caustic Injection
Pumps, will stop via relay XY-21301B. The timer will initially be set to be on for 60 minutes and off for
the remainder of a 24 hour period and shall be adjustable by the operator in one minute increments.
2. Provide an adjustable timer to start Merox WS-2 Injection Pump (as selected by the Hand-Off-Auto
switch in the field, provided by others). The timer will initially be set to be on for 45 minutes and off for
the remainder of a 24 hour period and shall be adjustable by the operator in one minute increments.
3. Provide a pump running indicator in the distributed control system for each service listed below. The
running indicator will be actuated by contacts in the associated motor starter.
4. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Lean Caustic to Extractor Plus Extraction Section Low Flow”. Switch
shall be wired such that in:
Position Label Description
1 NORMAL The switch contacts are open and the bypass circuit is
deenergized.
2 BYPASS The switch contacts are closed and the bypass circuit is
energized.
Notes:
Provide a backlighted nameplate, HL-21968A engraved “Lean Caustic to Extractor Plus Extraction
Section Low Flow Shutdown Bypassed”. Nameplate to be illuminated when the switch is in the bypass
position.
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
5. Provide a two-position selector switch with cover shield. Contractor shall determine contact rating.
Provide nameplate engraved “Disulfide Separator Vent Gas Emergency Diversion”. Switch shall be
wired such that in:
Position Label Description
1 NORMAL The switch contact is closed and the circuit is energized.
2 DIVERTED The switch contact is open and the circuit is deenergized,
thus diverting the vent gas to the Exhaust Head.