Sheet

1 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

This instruction is a guidance to get the MSD-drive parameterized and commissioned.

Prerequisites:
• A connected servo drive +24V
• A PC with installed operating software Drive Administrator 5.4.56
• An USB cable interface or an Ethernet cable
• A Servo motor with resolver connected to the servo drive
• A data set file or a commissioning file customized for the intended application
• A valid setting list for verification of the parameter set up
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

2 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

CONTENTS

1. Establish a connection and start a new project.............................................................. 3


1.1 TCP/IP connection ...........................................................................................................................................4

2. Parameterize the servo drive .......................................................................................... 10


2.1 Loading a data set file in firmware V2 .........................................................................................................11

2.2 Loading a commissioning file in firmware V123 or V124 ..........................................................................13

3. Verifying parameters and I/O-configuration .................................................................. 15

4. Save parameter settings into the servo drive ............................................................... 26


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

5. Copy parameter settings and create a data set file ...................................................... 27


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

6. Test run speed limitation ................................................................................................ 29

8. Diagnose .......................................................................................................................... 31

9. Technical notes ............................................................................................................... 32


9.1 Restart of servo drive ....................................................................................................................................32

10. Installation of firmware ................................................................................................. 33

11. Revert the computers TCP/IP settings ........................................................................ 34


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

3 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

1. Establish a connection and start a new project


Start the program Drive Administrator 5.4.56. During start up this dialog box appears.

Select “Create a new


project” and press “OK“
button.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Enter a suitable name of the project in the field “Project


name”, e.g. Tuapse 1-Pilot, Tuapse1-Main or Tuapse1-VGV
depending on the application.

Then press “OK” button

To establish a connection with the driver, you need to select


USB or TCP/IP, and then press OK button.

If you choose TCP/IP connection, please follow step 1.1 to


1.10 below. If you choose USB, click OK button and skip
step 1.1 – 1.10.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

4 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

For USB connection, you will need a USB Type-A Male to


Type-B

For TCP/IP connection you will need a standard Ethernet


cable.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

1.1 TCP/IP connection

1.1 Open Windows Start menu and search for


ncpa.cpl

1.2 Click on the search result or press Enter key


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

5 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

1.3 Right click on the network


adapter that is plugged in to
MOOG driver and choose
“Properties” from the drop
down menu.

You will need administrative


rights on your computer to
change the Network adapter
properties. If you receive a
warning, click “Yes” button.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

1.4 Click on the row “Internet


Protocol Version 4 (TCP/IPv4)

1.5 Click on “Properties” button


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

6 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

1.6 Click on “Use the following


IP address” and enter the
following:

IP address: 192.168.39.6
Subnet mask: 255.255.255.0
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

1.7 Click on OK button

Close Network Connections window and continue with the


“Drive Administrator 5.4.56” software
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

7 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

1.8 Choose the TCP/IP option


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

1.9 Choose “Connect a single


device with well-known IP
address” and click on OK button

1.10 Enter the IP address of


MOOG driver (default is
192.168.39.5) and click on OK
button
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

8 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

First time using DA 5.4.56 this dialog box


appears.

Skip initial commissioning by pressing the


right button “Don’t perform initial
commissioning”.

By first marking the checkbox you will


skip this dialog next time starting DA.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

In case of successful communication the following desktop appears.


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

9 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

You can configure your desktop as you like by moving or hiding the different windows.
If you feel lost, there is always a way back to the standard desktop.

To load standard desktop, click on


“actual device” and then “Load
standard desktop”.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

10 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

2. Parameterize the servo drive


A drive installed with firmware version V2 is parameterized with a data set file (.dmdvadj).
The firmware version must be V2.20-01before the file is loaded into the drive.

A drive installed with firmware version V123 or V124 is parameterized with a commissioning
file (.comdvarc). The commissioning file automatically updates the firmware version to
V124.00-05 and sets the parameters in one step.

First check the firmware version


by pressing the “Drive
description” button.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

If the firmware version starts with


V2, the servo drive must be
parameterized by loading a data
set file according to chapter 2.1.

If the firmware version starts with


V123 or V124, the servo drive
must be parameterized by loading
a commissioning file according to
chapter 2.2.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

11 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

2.1 Loading a data set file in firmware V2


The firmware version must be V2.20-01. If not, you need to install correct version according
to chapter 10.

To load the data set file for the


actual application, click on “Actual
device” and then “Load setting
from file”
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Browse to and select the data set


file for the intended application
and press “Open”.

Press “OK”
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

12 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

After a successful installation of


the dataset file, a pop-up
message showing “0 error(s)
detected” is displayed.

Press “OK” button to finish the


setup.

It’s also recommended to restart


the drive, see chapter 9.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

13 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

2.2 Loading a commissioning file in firmware V123 or V124


The firmware version must be V123.15-01or higher. If the firmware version is V123.05-03,
you must first install correct version according to chapter 10.

To load the commissioning file for


the actual application, click on
“Actual device” and then “Load
device commissioning file”
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Browse to and select the


commissioning file for the intended
application and press “Open”.

After confirming file selection, the


upload of the commissioning file
will start. A pop-up window of the
progress appears.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

14 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Finally after a successful installation of the


commissioning file, the following message will
appear. Just press either button to finish set up.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

15 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

3. Verifying parameters and I/O-configuration

1. 2. 3. 4. 5. 6. 7.

Before commissioning, correct


parameters and settings in the
following subject areas are required:
1. Power stage
2. Motor
3. Encoder
4. Control
5. Motion profile
We reserve all rights in this document and in the information

6. I/O
contained therein. Reproduction, use or disclosure to third

7. Limits
© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

8. Alarms & Warnings

Start to verify the parameters by


open “Power stage” area.
8.

In the “Power stage” area, verify


following parameters:

307-Mains voltage
302-Switching frequency
752-Online derating of switching freq.

By holding the mouse over the


parameter field, the parameter Id and
name will appear.

Go on and press “Options” button


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

16 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Verify parameter:

425-Nominal mains voltage

Go back one step by pressing “back”


button.

Right click somewhere in the free area


and then “Switch to list view”.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Verify parameter:

759-Undervoltage threshold level*


*Only available in firmware V124

Then open “Motor” area.

In the “Motor” area start to verify


parameters:

450-Motor type
490-Motor movement

Go on and press the button “Show motor


data”.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

17 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Verify parameters:

456-Rated voltage
457-Rated current
458-Rated speed
455-Rated frequency
460-Rated torque
461-Motor inertia
470-Stator resistance
471-Stator inductance

Now, press the button “Show motor


parameters”.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

In this view verify parameters:

463-Pole pairs
462-Rated flux

Go back two steps by pressing “back”


button.

Press “Motor protection” button


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

18 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

In the “Motor” area finally verify parameters:

732.1-Temperature sensor connection


732.0-Motor temperature sensor
731.1-Maximum temperature

Open “Encoder” area


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

In the “Encoder” area verify parameters:

520-Encoder for commutation


349-Encoder offset
521-Encoder for speed control loop
522-Encoder for position control loop

Then press one of the buttons “Options”

Verify parameters:

506-Encoder type
560-Number of pole pairs
561-Encoder signal correction

Now, right click somewhere in the free area.


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

19 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Choose “Switch to list view”


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

Finishing the “Encoder area” by verifying


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

parameter:

565-Line delay compensation

Go on to “Control” area

In the “Control area” verify parameter:

300-Control mode

Then press “Speed control” button


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

20 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Parameters to be verified are:

320-Speed control gain


321-Speed control integration time
350.1-Feedback selection
350.0-Observer Method

Don’t pay attention to the remaining


parameters in this area.

Open “Motion profile” area


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

In the “Motion profile” area press the


“Basic settings” button.

Verify all basic settings parameters:

159-Motion control via


165-Motion reference via
144-Motor control start condition
301-Profile mode
2243-Profile type
370-Interpolation type
306-Sampling time for interpolation
167-Speed override factor
335-Reversing lock
755-Reference filter type*
* only available in firmware V124
A 087 0474-B 00-03 MS Word 97

Go back one step by pressing “back”


button
GS/AS with the Latest revision Archive HG/UPS
same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

21 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Now, press the “Stop ramps” button

Verify all stop ramps parameters:


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

2219-Reaction at control off


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

2220-Reaction at disable reference


2221-Reaction at halt command
2218-Reaction at quick stop command
2242-Quick stop ramp deceleration
2222-Reaction at fault

Open “I/O” area

In the “I/O” area, start to verify the I/O


configuration by pressing the “Digital
inputs” button.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

22 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Verify correct setup for the digital inputs


ENPO and ISD00-ISD06, parameters:

100-Function of digital input ENPO


101-Function of digital input ISD00
102-Function of digital input ISD01
103-Function of digital input ISD02
104-Function of digital input ISD03
105-Function of digital input ISD04
106-Function of digital input ISD05
107-Function of digital input ISD06

Also verify activation at high or low signal


by correct marked check box.

In this view finally verify each input’s filter


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

time according to parameters:


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

118.0 to 118.7-Digital input filter time

Go back one step by pressing the “back”


button.

Now press the “digital outputs” button.


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

23 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Verify correct setup for the digital outputs


OSD00-OSD02 and RELOUT1,
parameters:

122-Function of digital output OSD00


123-Function of digital output OSD01
124-Function of digital output OSD02
126-Function of digital output RELOUT1

Also verify activation at high or low signal


by correct marked check box.

Go back one step by pressing the “back”


button.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Press “Motor brake output” button

Verify the function of the Motor brake


output by parameters:

125-Function of motor break output


748-Cable break detection

Go back one step by pressing the “back”


button.

Press the “Analog inputs” button


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

24 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Verify correct setup for the analog


parameters:

109-Function of analog input ISA00


110-Function of analog input ISA01
405-Analog input ISA00 filter time
406-Analog input ISA01 filter time

Then press input ISA00 ”Options”


button.

Verify input ISA00 configuration by


parameters:

173.1-Scale factor
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

174.1-Offset
© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

175.1-Backlash threshold
177.0-Acceleration ramp
177.1-Deceleration ramp

Open “Limits” area

Verify parameter:

329-Speed control maximum torque

Don’t pay attention to the remaining


parameters.

Go back to the beginning by pressing


the “Overview” button.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

25 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Open the “Alarms & warnings” area

In the “Alarms & warnings” area, open


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

the folder Id 30 “Error reactions”


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

Verify correct value of parameters:

30.6-Reaction on over temp motor


30.45-Reaction on lock violate

Don’t pay attention to the remaining


parameters.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

26 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

4. Save parameter settings into the servo drive

To save the actual setting into the


servo drive, click on “Actual
device” and then “Save setting
inside device”.

This has to be done if parameters


during online mode have been
changed.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

27 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

5. Copy parameter settings and create a data set file

To take a copy of the actual set


up of the servo drive, click on
“Actual device” and then “Copy
setting to file”.

First time the settings are copied,


following dialog box appears.
We reserve all rights in this document and in the information

Choose, “To save as parameter


contained therein. Reproduction, use or disclosure to third

setting file”.
© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

Enter a suitable file name, e.g.


“Tuapse1-Main” and press the
“Save” button.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

28 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Press “OK” button to create the


file.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

29 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

6. Test run speed limitation


Before the first test run assure that:

• The servo drive is wired to appropriate terminals


• The servo drive is loaded with a correct parameter setup for the actual application
• The maximum motor speed is temporarily limited.

To temporarily lower the motor speed open “I/O” area.

Press the “Analog inputs” button.


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Press input ISA00 “Options” button.

Temporarily change scale factor


parameter 173.1 to 300 r/min.

To take effect changes must be done


while the drive is disabled from control
system.

Save changes into the drive (see


chapter 4).

After a successful test run, restore the


parameter.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

30 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

7. Offset adjustment
In each application offset must be adjusted individually.

Before offset adjustment assure that:

• 0V is applied on channel ISA0


• The servo drive is enabled

As in chapter 6, open “I/O” area and


navigate until the desktop below
appears.

The correct offset value is obtained by


testing different values of parameter
We reserve all rights in this document and in the information

174.1 until the motor is standing still.


contained therein. Reproduction, use or disclosure to third

One decimal is fully sufficient.


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

Entry of a new value followed by the


Return key is having an immediate
effect.

The motor movement is observed


directly on the motor shaft or by
watching “Actual position” in the Cockpit
window.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

31 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

8. Diagnose

The servo drive is equipped with a display indicating different system states. Under normal
conditions and with no errors the drive indicates one of system states as follows:

Automatic initializing during start up of device

Drive initialized, power stage not ready

Ready to switch on, power stage ready


We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.

Drive enabled, ready for set point

In case of a fault the display indicates “Er” followed by a decimal No describing the type of
fault and then a second No describing the location of the fault. The error message will
alternately be displayed in a flashing sequence. In this example the fault means:

Error number 05=Over current


Error location 01=Software monitoring

The flashing codes are described in the operational manual.

At the same time the fault appears in Drive Administrator when online. A pop-up window is
opened with further information about the fault.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

32 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

9. Technical notes

9.1 Restart of servo drive


Sometimes a restart of the servo drive is required. The restart can be done in two ways.
Either by switching off the control voltage +24V for a few seconds or online via the Drive
Administrator program.

For online restart:


Click on “Actual device” and then
“Restart”.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

© Siemens Industrial Turbomachinery AB


Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

33 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

10. Installation of firmware


If the servo drive’s firmware version differs from V2.20-01 or if the version is V123.05-03, it
must be replaced. To identify current version, see chapter 2.

Firmware versions other than above and beginning with V2.XX-XX must be exchanged to
V2.20-01 using the V2-20-01.hex file.

Firmware version V123.05-03 must be upgraded to V123.15-01 using the V123-15-01.hex


file.

To perform the steps below you need a copy of the actual firmware file and an online
connection.
We reserve all rights in this document and in the information

To install correct firmware, click on


contained therein. Reproduction, use or disclosure to third

“Extras” and then “Firmware loader”.


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

Press “Start firmware upload” button.


A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand
Sheet

34 (34)
Respons. dept Date Reg.
Commissioning instruction
MOOG MSD 3200 RAE 2010-07-05
Prepared
Lars Källström
This document is issued in Pulse.

Browse to and select the actual hex


file. Then press “Open”.

The change of firmware will take


around 5 minutes. As a last moment
the servo drive will do a restart with
the parameters set to factory default.

Parameterization is done according


to chapter 2.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third

11. Revert the computers TCP/IP settings


© Siemens Industrial Turbomachinery AB
Parties without express authority is strictly forbidden.

If you choose TCP/IP as communication option to the driver, you might want to reset your
computers Network Adapter settings back to its previous settings when you have finished
your work with the Drive Administrator software.

Follow the steps 1.1 to 1.5 above and then


click the options “Obtain an IP address
automatically” and “Obtain DNS server
address automatically”.

Click OK button.
A 087 0474-B 00-03 MS Word 97

GS/AS with the Latest revision Archive HG/UPS


same Doc.no yes A
B Chapt.10 added/110415/LKm
Approved C Adapted to DA 5.4.21/120224/LKm No.
2010-09-30
Jonas Vogel D Adapted to new firmware release/140917/LKm 1CS101232
Checked E TCP/IP added/150604/JF
2010-09-28
Calle Ristenstrand

You might also like