1. The document outlines requirements for installing a fire alarm system at a site, including that installation personnel must be qualified and certified. 2. PVC insulated cables with a minimum gauge of 2.5mm2 shall be used for wiring the fire alarm system. 3. The site plan shows the layout of the site including locations of the main and emergency entrances/exits and a proposed guard house building.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views

06

1. The document outlines requirements for installing a fire alarm system at a site, including that installation personnel must be qualified and certified. 2. PVC insulated cables with a minimum gauge of 2.5mm2 shall be used for wiring the fire alarm system. 3. The site plan shows the layout of the site including locations of the main and emergency entrances/exits and a proposed guard house building.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

KEY PLAN NOTES

TRUE
THE SITE
NORTH 1. FIRE ALARM SYSTEMS INSTALLATION PERSONNEL SHALL BE SUPERVISED BY
PERSONS WHO ARE QUALIFIED AND CERTIFIED WITH CERTIFICATION IN THE
MAKKA INSTALLATION, INSPECTION, AND TESTING OF FIRE ALARM SYSTEMS.
EMERGENCY
ENTRANCE & EXIT

LAR 6427
MAIN
ENTRANCE & EXIT

PROPOSED
2. PVC INSULATED 2/C X 2.5mm² MINIMUM CABLES SHALL BE USED FOR THE
WIRING OF FIRE ALARM SYSTEM (SCREENED CABLES-105°C HEAT
1 GUARD HOUSE BUILDING
2 4 6

PROPERTY LIMIT
3 5

D
12
FIRE EXIT DOOR
D
12
FIRE EXIT DOOR

RESISTANT). FIRE ALARM CABLE-UL LISTED.


3. MINIMUM SIZE OF CONDUIT SHALL BE 20mmØ EMT UNLESS OTHERWISE

COLLECTING POND
PROPOSED

RUN-OFF WATER
FINISHED PRODUCT
STORAGE BUILDING

NOTED.

SLIDING DOOR

SLIDING DOOR
D

D
13 13

FIRE EXIT DOOR


D
FIRE EXIT DOOR

4. ALL POWER SUPPLIES FOR THE FIRE ALARM SYSTEM SHALL BE IN

12 D
12
SLIDING DOOR

CONFORMITY WITH THE REQUIREMENTS OF NFPA 70 AND NFPA72.

ROLL UP DOOR

ROLL UP DOOR
PROPOSED
MAINTENANCE SERVICES BUILDING

ROLL UP DOOR

ROLL UP DOOR
5. CONTRACTOR SHALL INSTALL DETECTORS AND OTHER DEVICES AS PER
PROPOSED
U&OO
BUILDING
ACTUAL SITE CONDITION AND SHALL COORDINATE WITH OTHER UTILITIES.
PROPOSED
RAW MTERIAL
6. CONTRACTOR SHALL TAKE THE NEAREST POSSIBLE HOME RUN CIRCUITS
FOR EACH LOOP TO FACP.
BUILDING

7. FIRE ALARM CABLE SHALL INSTALL THROUGH THE CONCEALED (PVC) /


8 7

SURFACE (EMT) MOUNTED CONDUITS.


8. DO NOT SCALE FROM THIS DRAWING.
A B C D E F G H I J 9. ALL DIMENSIONS TO BE CHECKED ON SITE AND ANY DISCREPANCIES SHALL
BE REPORTED IMMEDIATELY TO THE ARCHITECT.
10. THE CONTRACTOR SHALL CONFIRM THE FINISH FLOOR LEVEL OF THE
BUILDING PRIOR TO COMMENCEMENT OF WORK AND IN CASE OF ANY
DISCREPANCIES, BRING TO KNOWLEDGE OF THE ENGINEER.
11. THE CONTRACTOR SHALL VERIFY THE LEVELS AND SETTING OUT
COORDINATES WITHIN AND AROUND EACH BUILDING AND CHECK THE
DIMENSIONS INDICATED PRIOR TO EXECUTION.
12. THE CONTRACTOR SHALL OBTAIN ALL APPROVALS AND N.O.C.'S FROM ALL
CONCERNED LOCAL STATUTORY AUTHORITIES AND SHALL INCLUDE FOR
ALL WORKS WITH RESPECT TO THE DIVERSION/PROTECTION OF THE
SERVICES DURING THE PERIOD OF CONSTRUCTION, TO THE SATISFACTION
OF THE CONCERNED AUTHORITIES AND THE ENGINEER.
13. THE CONTRACTOR TO PREPARED SHOP DRAWINGS.
14. FIRE ALARM SYSTEM SHOWN IS ONLY NOTIONAL. FINAL ARRANGEMENT
AND CABLE ROUTING, EQUIPMENT REQUIREMENTS AND CONNECTIONS
SHALL BE AS PER FACP MANUFACTURER RECOMMENDATION IN
COMPLIANCE TO RC GUIDELINES AND NFPA 72 NATIONAL ELECTRICAL
CODE, SUBJECT TO CLIENT APPROVAL.
FIRE ALARM CABLE IN 15. FOR EASE OF ACCESS AND SAFE OPERATION INSTALL FACP AT ENTRANCE
AREA DURING CONSTRUCTION.
20mmØ PVC CONDUIT
TO GUARD HOUSE wp wp DESCRIPTION
SYMBOL
TO FACP PANEL
B B
1 LOCATED @
L3-35 L3-34
1 S SMOKE DETECTOR, ADDRESSABLE, MULTICRITERIA, 135 F FIXED
GUARD HOUSE TEMPERATURE HEAT DETECTION.

B ALARM BELL / SOUNDER, 90dB MINIMUM, WALL-MOUNTED

PULL STATION, ADDRESSABLE, WALL-MOUNTED

ROLL UP DOOR
ROLL UP DOOR

L3-02 L3-03 L3-04 L3-05 L3-06 L3-07


H H H H H H H FIRE ALARM CABLE IN 20mmØ EMT CONDUIT
L3-01
L1-1 L1 - ZONE NUMBER
1 - FIRE ALARM DEVICES SEQUENCE NUMBER
L3-17 L3-15 L3-33

B
B
B

wp L3-16 L3-32
2 L3-18
2
B

L3-19

L3-13 L3-12 L3-11 L3-10 L3-09


ROLL UP DOOR

ROLL UP DOOR
H H H H H H H
L3-14 L3-08

L3-31 L3-29

B
B
L3-30 wp
3 3
SPARE
PARTS

STORAGE ABLUTION
H H STORAGE TEAH
ROOM H H
MECHANICAL H
ELECTRICAL SPARE
H
PARTS
WASH TOILET

L3-20 L3-22 L3-23 L3-24 L3-25 L3-26 L3-28

4 L3-21 B L3-27 B 4

BIA
K IN
wp wp

RA
D
M A

O
O F S A U DI

EMDAD ANTHRACITE DRYING PROJECT


CONSTRUCTION PACKAGES

TANAGHOM CONSULTING
LIC. NO. 2013,P.O BOX: 9021 / CODE: 35811-4692 JUBAIL IND. CITY -
OFFICE NO. 2-12, NABA COMMERCIAL CENTER, AL-FANATEER-/
TEL-/(03) 3472261 / 3473926 / 3473950 //FAX: (03) 3472259/
Website:www.tanaghomconsulting.com

A B C D E F G H I J
Smart Projects Construction Company
P.O. Box 1861| ZIP Code 31952 Khobar
KSA Tel.: +966 13 894 1919|Fax: +966 13 896 5511

MSB GROUND FLOOR FIRE ALARM


(MS) BUILDING
SYSTEM LAYOUT PLAN
1 GROUND FLOOR FIRE ALARM SYSTEM LAYOUT PLAN
3 - 07 - 41J - B08A J 02 14
ANT-21-008-INK-SPCC-R.0
ANT-21-008-SD-GPP-EL-LA-0005-Rev.01
ANT-21-008-SD-GPP-EL-0094-Rev.01
1: 75M 6/7