This document lists error codes and their meanings for multiple models of air conditioners. It includes codes for cassette type indoor units, split air conditioners with wired controllers, floor standing units, duct type units, and their corresponding outdoor units. The errors cover issues like high/low pressure protection, temperature sensors, fans, communication errors, compressor issues, and more. Most codes are accompanied by a brief 1-2 word explanation of the associated error or fault.
This document lists error codes and their meanings for multiple models of air conditioners. It includes codes for cassette type indoor units, split air conditioners with wired controllers, floor standing units, duct type units, and their corresponding outdoor units. The errors cover issues like high/low pressure protection, temperature sensors, fans, communication errors, compressor issues, and more. Most codes are accompanied by a brief 1-2 word explanation of the associated error or fault.
MULTI VARIABLE AIR CONDITIONERS CASSETTE TYPE INDOOR UNIT
ERROR MODEL NO. MEANING CODE TMV-ND28T/A-T, L0 Indoor Unit Error TMV-ND36T/A-T, L1 Indoor Fan Protection TMV-ND45T/A-T, L2 E-heater Protection TMV-ND50T/A-T, L3 Water Full Protection TMV-ND56T/A-T, TMV-ND63T/A-T, L4 Wired Controller Power Supply Error TMV-ND71T/A-T, L5 Anti-Frosting Protection TMV-ND80T/A-T, L7 No Master Indoor Unit Error TMV-ND90T/A-T, L8 Power Insufficiency Protection TMV-ND100T/A-T, L9 Quantity Of group Control Indoor Units Setting Error TMV-ND112T/A-T, TMV-ND125T/A-T, LA Indoor Units Incompatibility Error TMV-ND140T/A-T, LC Outdoor-Indoor Incompatibility Error TMV-ND160T/A-T, LH Low Air Quantity Warning
SPLIT AIR CONDITIONER INVERTER: WIRED CONTROLLER (OPTIONAL)
ERROR MODEL NO. MEANING CODE E1 High Pressure Protection E2 Anti-Freezing Protection E3 Low Pressure Protection E4 High Discharge Temperature Protection E5 Whole Unit Over-Current Protection E6 Indoor and Outdoor Communication Error E7 Running Mode Conflict TWC 09VRL, E8 Overload Protection TWC12VRL, E9 Indoor Unit Full Water Error TWC18VRL, EU Frequency Restricted/Reduced with IPM Temperature Protection TWC24VRL, En Frequency Restricted/Reduced with IPM Current Protection F0 System Charge Shortage or Blockage Protection F1 Return Air Temperature Sensor Open/Short Circuited F2 Evaporator Temperature Sensor Open/Short Circuited F3 Outdoor Ambient Temperature Sensor Open/Short Circuited Outdoor Unit Condenser Mid-Tube Temperature Sensor F4 Open/Short Circuited F5 Discharge Temperature Sensor Open/Short Circuited SPLIT AIR CONDITIONER INVERTER: WIRED CONTROLLER (OPTIONAL) ERROR MODEL NO. MEANING CODE F6 Frequency Restricted/Reduced with Overload Protection F8 Frequency Restricted/Reduced with Whole Unit Current Protection F9 Frequency Restricted/Reduced with High Discharge Temperature FH Frequency Restricted/Reduced with Anti-Freezing Protection Fo Pump-Down H1 Forced Defrosting H3 Compressor Overheating Protection H5 IPM Current Protection H6 Motor Stalling H7 Compressor Desynchronizing HE Compressor Demagnetization Protection Hc PFC Protection U1 Compressor Phase Current Sensing Circuit Error U3 DC Bus Voltage Drop Error U5 Whole Unit Current Sensing Circuit Error U7 4-Way Valve Reversing Error U8 PG Motor Zero-Crossing Protection LA Outdoor Fan 2 Error Protection TWC 09VRL, Lc Compressor Start-up Failure TWC12VRL, Ld Compressor Phase Loss/Reversal Protection TWC18VRL, LE Compressor Stalling TWC24VRL, LF Over-speeding LP Indoor and Outdoor Units Unmatched L3 Outdoor Fan 1 Error Protection L9 Over-Power Protection Pd Sensor Connection Protection PE Temperature Drift Protection PF Drive Board Temperature Sensor PH DC Bus Over-Voltage Protection PL DC Bus Under-Voltage Protection PP AC Input Abnormal Protection PU Capacitor Charging Error P5 Over Phase Current Protection P6 Drive Board Communication Error P7 IPM Temperature Sensor Open/Short Circuited P8 IPM Temperature Protection P9 AC Contactor Protection b5 Indoor Unit Liquid Valve Temperature Sensor Open/Short Circuited b7 Indoor Gas Valve Temperature Sensor Open/Short Circuited C5 Jumper Error dn Communication Line Misconnected Or Expansion Valve Error DC INVERTER U-MATCH SERIES FLOOR STANDING TYPE UNIT / DC INVERTER U-MATCH SERIES CASSETTE TYPE UNIT / DC INVERTER U-MATCH SERIES DUCT TYPE UNIT / WIRED CONTROLLER XK60 ERROR MODEL NO. MEANING CODE E1 Compressor High Pressure Protection E2 Indoor Anti-Freeze Protection Compressor Low Pressure Protection, Refrigerant Lack Protection E3 and Refrigerant collecting mode FLOOR E4 Compressor High Discharge Temperature Protection STANDING E6 Communication Error INDOOR UNIT: E8 Indoor Fan Motor Error TVH36D3FI, E9 Full Water Protection TVH60D3FI EE Outdoor Memory Chip Error OUTDOOR UNIT: ee Drive Memory Chip Error TUHD36ND3FO, F0 Indoor Ambient Temperature Sensor Error TUHD60ND3FO F1 Evaporator Temperature Sensor Error F2 Condenser Temperature Sensor Error F3 Outdoor Ambient Temperature Sensor Error F4 Discharge Temperature Sensor Error F5 Temperature Sensor Error of Wired Controller CASSETTE TYPE H3 Compressor Overload Protection INDOOR UNIT: H4 Overloading TKH18D3FI, H5 IPM Protection TKH24D3FI, H6 DC Fan Motor Error TKH36D3FI, H7 Drive Desynchronizing Protection TKH48D3FI, Hc PFC Protection TKH60D3FI Lc Activation Failure OUTDOOR UNIT: Ld Compressor Phase Sequence Protection TUHD18ND3FO, LE Compressor Stalling Protection TUHD24ND3FO, LF Power Protection TUHD36ND3FO, Lp Indoor and Outdoor Mismatch TUHD48ND3FO, P0 Drive Reset Protection TUHD60ND3FO, P5 Over-Current Protection P6 Communication Error Between Main Control and Drive DC INVERTER U-MATCH SERIES FLOOR STANDING TYPE UNIT / DC INVERTER U-MATCH SERIES CASSETTE TYPE UNIT / DC INVERTER U-MATCH SERIES DUCT TYPE UNIT / WIRED CONTROLLER XK60 ERROR MODEL NO. MEANING CODE P7 Drive Module Sensor Error DUCT TYPE P8 Drive Module Over Temperature Protection INDOOR UNIT: P9 Zero Passage Protection TFH18D3FI, PA AC Current Protection TFH24D3FI, Pc Drive Current Protection TFH36D3FI, Pd Sensor Connecting Protection TFH48D3FI, PE Temperature Drift Protection TFH60D3FI PF Electric Box Sensor Error OUTDOOR UNIT: PL Bus Low Voltage Protection TUHD18ND3FO, PH Bus High Voltage Protection TUHD24ND3FO, PP Input Voltage Abnormality TUHD36ND3FO, PU Charge Loop Error TUHD48ND3FO, C4 Outdoor Unit Capacity Code Error TUHD60ND3FO, C5 Indoor Unit Capacity Code Error U7 4-Way Valve Direction Changing Protection
WIRED CONTROLLER XK46
ERROR CODES FOR OUTDOOR UNIT b1 Outdoor Ambient Temperature Sensor Error b2 Defrosting Temperature Sensor 1 Error b3 Defrosting Temperature Sensor 2 Error b4 Sub cooler Liquid-out Temperature Sensor Error b5 Sub cooler Gas-out Temperature Sensor Error b6 Gas-Liquid Separator Inlet Temperature Sensor Error b7 Gas-Liquid Separator outlet Temperature Sensor Error b8 Outdoor Humidity Sensor Error b9 Heat Exchanger Gas-out Temperature Sensor Error bA Oil-Return Temperature Sensor Error bC Compressor 1 Top Temperature Sensor Detachment Protection bE Malfunction of Entry Tube Temperature Sensor of Condenser bF Malfunction of Exit Tube Temperature Sensor of Condenser bJ High and Low Pressure Sensors are Connected Inversely bL Compressor 2 Top Temperature Sensor Detachment Protection E0 Outdoor Unit Error E1 High Pressure Protection E2 Discharge Low Temperature Protection E3 Low Pressure Protection E4 Excess Discharge Temperature Protection of Compressor F0 Bad Performance of the Outdoor Main Board F1 High Pressure Sensor Error F3 Low Pressure Sensor Error F5 Compressor 1 Discharge Temperature Sensor Error F6 Compressor 2 Discharge Temperature Sensor Error F7 Compressor 3 Discharge Temperature Sensor Error F8 Compressor 4 Discharge Temperature Sensor Error F9 Compressor 5 Discharge Temperature Sensor Error FA Compressor 6 Discharge Temperature Sensor Error Fb/FU Compressor 2 Top Temperature Sensor Error FC Compressor 2 Current Sensor Error FE Compressor 4 Current Sensor Error FF Compressor 5 Current Sensor Error FH Compressor 1 Current Sensor Error FL Compressor 3 Current Sensor Error FJ Compressor 6 Current Sensor Error FP Malfunction of DC Motor P0 Compressor Drive Board Error P1 Compressor Drive Board Malfunction P2 Protection of Compressor Drive Board Power Supply P3 Protection of Compressor Drive Board Module Reset J1 Compressor 1 Over-Current Protection J2 Compressor 2 Over-Current Protection J3 Compressor 3 Over-Current Protection J4 Compressor 4 Over-Current Protection J5 Compressor 5 Over-Current Protection J6 Compressor 6 Over-Current Protection J7 4-Way Valve Blow-by Protection J8 System Pressure Over-Ratio Protection J9 System Pressure Under-Ratio Protection JA Protection of Abnormal Pressure JC Protection of Water Flow Switch JE Oil Return Pipe is Blocked JF Oil Return Pipe is Leaking JL Protection of Low High-Pressure H2 Protection of Fan Drive Board Power Supply ERROR CODES FOR INDOOR UNIT A0 Unit is Waiting For Debugging. A1 Check the Compressor Operation Parameters. A2 After-Sales Refrigerant Reclaim A3 Defrosting A4 Oil Return A5 Online Testing A8 Vacuum-Pumping Mode Ab Emergency Stop AC Cooling Ad Operation Restriction AF Fan AH Heating AJ Filter Clean Reminder An High Temperature Prevention Control AU Remote Urgent Stop Communication Between Indoor Unit And Outdoor Unit and the C0 Communication Between Indoor Unit And Wired Controller Have Malfunction Communication Error Between Master Control and Inverter C2 Compressor Drive Communication Error Between Master Control and Inverter Fan C3 Motor Drive C4 Error of Lack of Indoor Unit C5 Alarm of Indoor Unit Project Number Collision C6 Alarm of Wrong Number of Outdoor Unit Cb Outflow of Units IP Address CF Error of Multiple Master Indoor Unit CH Rated Capacity is Too High CJ System Addressed is Compatible CL Rated Capacity is Too Low CP Error of Multiple Master Wired Controller CU Communication Error Between Indoor Unit and Remote Receiver d1 Indoor Unit PC-Board Error d3 Ambient Temperature Sensor Error d4 Inlet Pipe Temperature Sensor Error d5 Malfunction of Middle Tube Temperature Sensor d6 Outlet Pipe Temperature Sensor Error d7 Humidity Sensor Error d8 Water Temperature Sensor Error d9 Jumper Cap Error dA Indoor Unit Hardware Address Error db Special Debugging Code dC Capacity DIP Switch Setting Error dE Indoor Unit CO2 Sensor Error dH Wired Controller PC-Board Error dL Outlet Air Temperature Sensor Error L0 Indoor Unit Error L1 Indoor Fan Protection L2 E-Heater Protection L3 Water Full Protection L4 Wired Controller Power Supply Error1 L5 Anti-Frosting Protection L7 No Master Indoor Unit Error L8 Power Insufficiency Protection L9 Quantity of Group Control Indoor Units Setting Error LA Indoor Units Incompatibility Error LC Outdoor-Indoor Incompatibility Error LH Low Air Quantity Warning LP Zero-Crossing Malfunction of PG Motor n3 Compulsory Defrosting n5 Compulsively excursion of Indoor Unit Project Number nJ High Temperature Prevention Under Heating Mode nL Target Low Pressure Modification nP Temperature-Adjusting Value During Defrosting nU Clear the Remote Control Shielding Order of Indoor Unit U2 Outdoor Unit Capacity Code/Jumper Cap Setting Error U3 Phase Sequence Protection Of Power Supply U4 Protection Of Lack of Refrigerant U5 Wrong Address of Compressor Drive Board U6 Valve Abnormal Alarm U8 Indoor Unit Tube Malfunction U9 Outdoor Unit Tube Malfunction UC Outdoor Master Indoor Unit is Successfully Set UE Refrigerant Charging is Ineffective Emergency Operation DIP Switch Setting of the Compressor is UL Wrong TOSOT PHILIPPINES CORPORATION 2162 F.B. HARRISON STREET SAN JOSE, PASAY CITY TELEPHONE NO: (02) 833-0000 Error Code 101 This Error code is for Cassette Type, Duct Type, Floor Standing and Floor Ceiling Inverter.
Model Error code Meaning
E1 Compressor High Pressure Protection E2 Indoor Anti-Freeze Protection Compressor Low Pressure Protection, Refrigerant Lack Protection and CASSETTE TYPE E3 Refrigerant collecting mode INDOOR UNIT: E4 Compressor High Discharge Temperature Protection TKH18D3FI, E6 Communication Error TKH24D3FI, E8 Indoor Fan Motor Error TKH36D3FI, E9 Full Water Protection TKH48D3FI, EE Outdoor Memory Chip Error TKH60D3FI ee Drive Memory Chip Error F0 Indoor Ambient Temperature Sensor Error DUCT TYPE F1 Evaporator Temperature Sensor Error INDOOR UNIT: F2 Condenser Temperature Sensor Error F3 Outdoor Ambient Temperature Sensor Error TFH18D3FI, F4 Discharge Temperature Sensor Error TFH24D3FI, F5 Temperature Sensor Error of Wired Controller TFH36D3FI, H3 Compressor Overload Protection TFH48D3FI, H4 Overloading TFH60D3FI H5 IPM Protection H6 DC Fan Motor Error FLOOR H7 Drive Desynchronizing Protection STANDING Hc PFC Protection INDOOR UNIT: Lc Activation Failure TVH36D3FI, Ld Compressor Phase Sequence Protection TVH60D3FI LE Compressor Stalling Protection LF Power Protection Lp Indoor and Outdoor Mismatch P0 Drive Reset Protection FLOOR CEILING P5 Over-Current Protection INDOOR UNIT: P6 Communication Error Between Main Control and Drive TFH18D3FI, P7 Drive Module Sensor Error TFH24D3FI, P8 Drive Module Over Temperature Protection TFH36D3FI, P9 Zero Passage Protection TFH48D3FI, PA AC Current Protection TFH60D3FI Pc Drive Current Protection Pd Sensor Connecting Protection OUTDOOR UNIT: PE Temperature Drift Protection TUHD18ND3FO, PF Electric Box Sensor Error TUHD24ND3FO, PL Bus Low Voltage Protection PH Bus High Voltage Protection TUHD36ND3FO, PP Input Voltage Abnormality TUHD48ND3FO, PU Charge Loop Error TUHD60ND3FO C4 Outdoor Unit Capacity Code Error C5 Indoor Unit Capacity Code Error U7 4-Way Valve Direction Changing Protection TOSOT PHILIPPINES CORPORATION 2162 F.B. HARRISON STREET SAN JOSE, PASAY CITY TELEPHONE NO: (02) 833-0000
Error Code 101
This Error code is for Wall mounted type Inverter. MODEL: TWC09VRL, TWC12VRL, TWC18VRL, TWC24VRL.
Error code Meaning
E1 High Pressure Protection E2 Anti-Freezing Protection E3 Low Pressure Protection E4 High Discharge Temperature Protection E5 Whole Unit Over-Current Protection E6 Indoor and Outdoor Communication Error E7 Running Mode Conflict E8 Overload Protection E9 Indoor Unit Full Water Error EU Frequency Restricted/Reduced with IPM Temperature Protection En Frequency Restricted/Reduced with IPM Current Protection F0 System Charge Shortage or Blockage Protection F1 Return Air Temperature Sensor Open/Short Circuited F2 Evaporator Temperature Sensor Open/Short Circuited F3 Outdoor Ambient Temperature Sensor Open/Short Circuited F4 Outdoor Unit Condenser Mid-Tube Temperature Sensor Open/Short Circuited F5 Discharge Temperature Sensor Open/Short Circuited F6 Frequency Restricted/Reduced with Overload Protection F8 Frequency Restricted/Reduced with Whole Unit Current Protection F9 Frequency Restricted/Reduced with High Discharge Temperature FH Frequency Restricted/Reduced with Anti-Freezing Protection Fo Pump-Down H1 Forced Defrosting H3 Compressor Overheating Protection H5 IPM Current Protection H6 Motor Stalling H7 Compressor Desynchronizing HE Compressor Demagnetization Protection Hc PFC Protection U1 Compressor Phase Current Sensing Circuit Error U3 DC Bus Voltage Drop Error U5 Whole Unit Current Sensing Circuit Error U7 4-Way Valve Reversing Error U8 PG Motor Zero-Crossing Protection LA Outdoor Fan 2 Error Protection Lc Compressor Start-up Failure Ld Compressor Phase Loss/Reversal Protection LE Compressor Stalling LF Over-speeding LP Indoor and Outdoor Units Unmatched L3 Outdoor Fan 1 Error Protection L9 Over-Power Protection Pd Sensor Connection Protection PE Temperature Drift Protection PF Drive Board Temperature Sensor PH DC Bus Over-Voltage Protection PL DC Bus Under-Voltage Protection PP AC Input Abnormal Protection PU Capacitor Charging Error P5 Over Phase Current Protection P6 Drive Board Communication Error P7 IPM Temperature Sensor Open/Short Circuited P8 IPM Temperature Protection P9 AC Contactor Protection b5 Indoor Unit Liquid Valve Temperature Sensor Open/Short Circuited b7 Indoor Gas Valve Temperature Sensor Open/Short Circuited C5 Jumper Error dn Communication Line Misconnected Or Expansion Valve Error