Outdoor Unit Layout Guide - Data Books - English
Outdoor Unit Layout Guide - Data Books - English
technical data
technical data
1PXFSJOQVU L8
4VDUJPOUFNQFSBUVSFPGPVUEPPSVOJU ¡$
Original Layout
$LUWHPSHUDWXUHDQGDLUIORZVLPXODWLRQUHVXOWV TOP
VIEW
0SJHJOBM-BZPVU *NQSPWFE-BZPVU
%JTDIBSHFEBJSJTESBXOCBDLJO 'SFTIBJSJTTVQQMJFEGSPNCPUITJEFT
Original Layout
Fresh air
$LUWHPSHUDWXUHDQGDLUIORZVLPXODWLRQUHVXOWV TOP
VIEW
0SJHJOBM-BZPVU *NQSPWFE-BZPVU
%JTDIBSHFEBJSJTESBXOCBDLJO 'SFTIBJSBMTPTVQQMJFEGSPNDFOUSF
Original Layout
Fresh air
$LUWHPSHUDWXUHDQGDLUIORZVLPXODWLRQUHVXOWV SIDE
VIEW
0SJHJOBM-BZPVU *NQSPWFE-BZPVU
'SFTIBJSBMTP
%JTDIBSHFEBJSJT TVQQMJFEGSPN
ESBXOCBDLJO VOEFSOFBUI
Original Layout
Fresh air
$LUWHPSHUDWXUHDQGDLUIORZVLPXODWLRQUHVXOWV SIDE
VIEW
0SJHJOBM-BZPVU *NQSPWFE-BZPVU
%JTDIBSHFEBJSJT
ESBXOBHBJO 'SFTIBJSJTESBXOJO
UISPVHIUIFMPVWSF
Fresh air
Original Layout
$LUWHPSHUDWXUHDQGDLUIORZVLPXODWLRQUHVXOWV SIDE
VIEW
0SJHJOBM-BZPVU *NQSPWFE-BZPVU
'SFTIBJSJTTVQQMJFE
GSPNTJEFTPGUIFXBMM
%JTDIBSHFEBJSJT
ESBXOJO
●Place the discharge level higher than the wall, either by elevating
Fresh air
Fresh air
Outdoor Unit Layout Guide 8
*XLGHOLQHIRUWKHLQVWDOODWLRQRI
959RXWGRRUXQLWVVXUURXQGHGE\ZDOOV
1 . Te c h n i c a l b a c kg ro u n d
When installing VRV outdoor units collectively on the rooftop, the suction temperature increases due to the heat emanated from other outdoor units (air short circuit).
As a result, in cooling system, the COP is lowered because of decreased equipment capacity and increased power consumption. In some cases, outdoor units stop
operations due to abnormally high pressure. When installing these units, choose the most suitable layout for on-site space conditions from the installation options below,
while taking walkway space and ventilation into consideration.
* For other installation patterns, determine the appropriate installation method based on the space conditions, referring to the installation examples below.
For the space in front of the units, please ensure there is enough space for refrigerant piping work. The required installation space shown in the illustrations is based on the
cooling operation at 35°C of outside temperature. When the design outside temperature exceeds 35°C, make the inlet space larger than spaces shown in the illustrations.
3UHFDXWLRQVRQ,QVWDOODWLRQ
D e t e r m i n at i o n o f t h e I n s t a l l at i o n Loc at i o n
S E L E C T I O N O F L O C AT I O N
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
If installed as a household appliance it could cause electromagnetic interference.
The VRV outdoor units should be installed in a location that meets the following requirements:
1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.
2. The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available.
(Refer to below figure and choose one of both possibilities.)
3. There is no danger of fire due to leakage of inflammable gas.
4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in case of a blocked drain pipe).
5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length. (See “Example of connection”.)
6. Select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturb anyone.
7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction.
Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.
-FHFOE
&YBNQMFPGVOJUJOTUBMMBUJPO
Fresh air
'SPOUGBDF
6OJUJOUIFEJBHSBNNN
5PQWJFX 'SPOU
'SPOU
Fresh air
'SPOU
4JEFWJFX
8BMMIFJHIUNN
'SPOU 'SPOU
'SPOU 'SPOU
'SPOU 'SPOU
'SPOU 'SPOU
&YBNQMFPGVOJUJOTUBMMBUJPO
VOJUJOTUBMMBUJPOFYBNQMF
'PSTJOHMFVOJUJOTUBMMBUJPO 'PSJOTUBMMBUJPOJOSPXT
1BUUFSO 1BUUFSO
PSNPSF PSNPSF
1BUUFSO 1BUUFSO
PSNPSF PSNPSF
PSNPSF
'SPOU PSNPSF
PSNPSF PSNPSF 'SPOU PSNPSF PSNPSF
PSNPSF PSNPSF
8BMMIFJHIUVOSFTUSJDUFE
1BUUFSO 1BUUFSO
'PSDFOUSBMJ[FEHSPVQMBZPVU
1BUUFSO
PSNPSF PSNPSF
PSNPSF
PSNPSF 'SPOU PSNPSF PSNPSF
PSNPSF PSNPSF PSNPSF PSNPSF
1BUUFSO
PSNPSF PSNPSF 6OJUNN
I
4VDUJPOTJEF
I
6OJU NN
NN
Notes
1. Heights of walls in case of Patterns 1 and 2 :
Front : 1500mm
Suction side : 500mm
Side : Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature
exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor unit, take the suction side space more broadly
than the space to be shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in
the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available
always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be
installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
Why a
duct is
needed
Note: Refer to guidelines (page 16) for maximum capacity per floor
and maximum number of consecutive floors.
11 Outdoor Unit Layout Guide
S i t u a t i o n 07
)ORRUE\IORRULQVWDOODWLRQ ・When there is some kind of shielding structure in
(Possibility of short circuit occurring)
front of the building(see illustration).
Conditions under which short circuits are likely to occur ・When units are installed in high-rise buildings.
・When a large number of units are installed on every
floor.
$LUWHPSHUDWXUHDQG
DLUIORZVLPXODWLRQUHVXOWV SIDE
VIEW
4VDUJPOUFNQFSBUVSFJODSFBTFTCZnPPS
Note: refer to guidelines (page 16) for maximum capacity per floor
and maximum number of consecutive floors.
Supply fresh air from the side, and orient the suction and discharge sides in different directions.
Fresh
air
Fresh
air Fresh
air
Units in the back row should draw
in air from the back. (Suction side
should be facing the back.)
Note: Do not merge ducts. Only one duct is to be installed on each fan in order to prevent air from being directly
circulated into the neighbouring fan.
1. Technical background
To make sure there is no risk of short-circuits in a system is a key point to bear in mind prior to deciding on the outdoor units layout
with a floor-by-floor installation.
Short-circuits affects the general performance of the equipment and may lead to some shortage in capacity, increase of energy
consumption (as the COP decreases) and in the worse case, lead to a complete stop of the system if suction temperature exceeds a
certain level.
The limitations concerning the outdoors layout described in this document are based on these specific concerns.
16HP/FL
20HP/FL
Conditions: 32HP/FL
40HP/FL
1. The air discharge velocity: 6 m/s. 48HP/FL
64HP/FL
2. Outdoor temperature: 35 Deg.C DB.
96HP/FL
3. Design guideline condition described in 4
satisfied.
Note:
%JTUBODFUPUIFOFBSFTUTUSVDUVSF -
<N>
If actual conditions differ from above, please
contact Daikin Industries Ltd.
)PXUPSFBEUIFHSBQI
/PPCTUBDMFJOGSPOUPGUIFCVJMEJOH )1
*GBOPCTUBDMFJTJOGSPOUPGUIFCVJMEJOH
40HP/FL 40HP/FL
'
'
N
)1VOJUTDBOCFJOTUBMMFEGPS .BYJNVNOVNCFSPGDPOTFDVUJWF
NPSFUIBODPOTFDVUJWFnPPST nPPSTMJNJUFEUP
5. Illustration
Diagram below indicated the minimum distance for the unit layout
in case of a floor-by-floor installation
74
7%
Air velocity
VD: Air discharge effective velocity VS: Air suction effective velocity
Discharge effective surface = Actual discharge surface x Louver opening ratio Suction effective surface = Actual suction surface x
Louver opening ratio
5 m.s-1 ≤ VD ≤ 8 m.s-1 VS ≤ 1.6 m.s-1
Total pressure loss: Less than 58.8 Pa for VRVII and 78.4Pa for VRVIII
Example:
40HP per floor installed, with a structure facing the installation at 5 meters distance.
From graph, maximum number of floors the installation can be safely done: 20 Floors.
njIPMF njIPMF
¨ ¨
¨
¨
%JTDIBSHF %JTDIBSHF
4VDUJPO 4VDUJPO
'SPOU 'SPOU
¨ ¨
¨
¨
%JTDIBSHF
%JTDIBSHF
4VDUJPO
4VDUJPO
'SPOU 'SPOU
Note 1: A gradual curve (large curve) in the discharge duct is effective in preventing friction loss.
Note 2: Use only one duct per fan.
Daikin’s unique position as a manufacturer of air Daikin Europe N.V. is approved by LRQA for its Quality The present publication is drawn up by way of information only and does not
conditioning equipment, compressors and Management System in accordance with the ISO9001 constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
refrigerants has led to its close involvement in standard. ISO9001 pertains to quality assurance regarding compiled the content of this publication to the best of its knowledge. No
environmental issues. For several years Daikin has design, development, manufacturing as well as to services express or implied warranty is given for the completeness, accuracy,
had the intension to become a leader in the provision related to the product. reliability or fitness for particular purpose of its content and the products and
of products that have limited impact on the services presented therein. Specifications are subject to change without
environment. This challenge demands the eco design prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or
and development of a wide range of products and an indirect damage, in the broadest sense, arising from or related to the use
energy management system, resulting in energy and/or interpretation of this publication. All content is copyrighted by Daikin
conservation and a reduction of waste. Europe N.V..
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
VRV® products are not within the scope of the Eurovent
www.daikin.eu certification programme.
BE 0412 120 336
RPR Oostende
q..-.7!Est