GE

Grid Solutions

M87x

Technical Manual
Monitoring & Recording IED

Publication reference: M87x/EN M/O


TABLE OF CONTENTS

FIRMWARE VERSION ..........................................................................................................................................vii

INSTALLATION AND MAINTENANCE ....................................................................................................................ix

ASSISTANCE ........................................................................................................................................................ix

COPYRIGHT NOTICE .............................................................................................................................................x

TRADEMARKS ......................................................................................................................................................x

SAFETY SECTION ................................................................................................................................................xii

1.0 DESCRIPTION ................................................................................................................................................1


1.1 Introduction ...............................................................................................................................................1
1.2 Features ....................................................................................................................................................1
1.3 Specifications ............................................................................................................................................1
1.4 Standards and Certifications ....................................................................................................................10
1.4.1 Revenue Accuracy ............................................................................................................................10
1.4.2 Environment .....................................................................................................................................10
2.0 HOUSING AND BACKPLANE .........................................................................................................................14
2.1 Installation ..............................................................................................................................................17
2.2 Initial Inspection ......................................................................................................................................17
2.3 Protective Ground/Earth Connections.......................................................................................................17
2.4 Instrument Mounting ...............................................................................................................................17
2.5 Surge Protection ......................................................................................................................................17
2.6 Cleaning ..................................................................................................................................................17
2.7 Removal and Installation of Modules ........................................................................................................18
3.0 HOST / ANALOG-DIGITAL SIGNAL PROCESSOR MODULE H11/H12 AND A10 ................................................19
3.1 Host board ..............................................................................................................................................19
3.1.1 Serial Port/Front Panel Board ............................................................................................................19
3.1.1a Service Port (P1) ..........................................................................................................................19
3.1.1b Standard Serial Ports (P2, P3, P4) .................................................................................................20
3.1.1c Diagnostic Status LED’s (S1, S2, S3, S4) .........................................................................................21
3.1.1d RS485 Connections .....................................................................................................................21
3.1.2 Self-Test Modes ................................................................................................................................28
3.1.3 System Clock ....................................................................................................................................29
3.2 A10 Analog-Digital Signal Processor Board ...............................................................................................29
3.2.1 Calibration ........................................................................................................................................29
3.2.2 Instantaneous Measurement Principles .............................................................................................29
3.2.2a Sampling Rate and System Frequency ........................................................................................29
4.0 MEASUREMENTS..........................................................................................................................................30
4.1 Current (1/4-Cycle Update) .......................................................................................................................30
4.1.1 Neutral and Residual Current (1/4-Cycle Update) ...............................................................................30
4.2 Voltage Channels (1/4-Cycle Update)........................................................................................................30
4.3 Power Factor (1-Cycle Update) .................................................................................................................31
4.4 Watts / Volt-Amperes (VAs) / VARs (1-Cycle Update) ..................................................................................31
4.4.1 Geometric VA Calculations ................................................................................................................32
4.4.2 Arithmetic VA Calculations ................................................................................................................32
4.4.3 Equivalent VA Calculations ................................................................................................................33
4.5 Energy (1-Cycle Update) ...........................................................................................................................33
4.6 Frequency (1-Cycle Update) .....................................................................................................................34
4.7 Demand Measurements (1-Second Update)..............................................................................................34
4.7.1 Ampere and Fundamental Ampere Demand ......................................................................................35

ii
4.7.2 Volt Demand.....................................................................................................................................35
4.7.3 Power Demands (Total Watts, VARs, and VAs) ....................................................................................36
4.7.4 Voltage THD Demand........................................................................................................................36
4.7.5 Current TDD Demand ........................................................................................................................36
4.7.6 Demand Resets.................................................................................................................................36
4.7.7 Demand Interval ...............................................................................................................................36
4.8 Harmonic Measurements (1-Cycle Update) ...............................................................................................37
4.8.1 Voltage Distortion (THD) (1-Cycle Update) ..........................................................................................37
4.8.2 Current Distortion (THD and TDD) (1-Cycle Update) .............................................................................37
4.8.3 Fundamental Current (1-Cycle Update) ..............................................................................................38
4.8.4 Fundamental Neutral Current (M871 Only) (1-Cycle Update) ...............................................................38
4.8.5 Fundamental Voltage (1-Cycle Update) ..............................................................................................38
4.8.6 Fundamental Watts / Volt-Amperes (VAs) / VARs (1-Cycle Update) ......................................................38
4.8.7 K-Factor (1-Cycle Update) .................................................................................................................39
4.8.8 Displacement Power Factor (1-Cycle Update).....................................................................................39
4.8.9 Phase Angle (1-Cycle Update) ............................................................................................................39
4.8.10 Resistance, Reactance, Impedance (1-Cycle Update)........................................................................39
4.8.11 Slip Frequency (1-Cycle Update) ......................................................................................................39
4.8.12 Individual Phase Harmonic Magnitudes and Phase Angles (1-Cycle Update) .....................................40
4.9 Temperature (1-Second Update)...............................................................................................................40
4.10 Symmetrical Components (1-Cycle Update) ...........................................................................................40
4.11 Supply Voltage and Current Unbalance (1-Cycle Update) .......................................................................40
4.12 Flicker ....................................................................................................................................................40
4.13 Fault Analysis.........................................................................................................................................41
4.13.1 Line Parameters ..............................................................................................................................41
4.13.2 Peak Current ...................................................................................................................................41
4.13.3 Status Indication and Reset .............................................................................................................41
4.13.4 SOELOG Output...............................................................................................................................42
4.13.5 Protocol Output ..............................................................................................................................42
4.14 List of Available Measurements ..............................................................................................................43
5.0 FUNCTIONAL DESCRIPTION .........................................................................................................................47
5.1 Passwords ...............................................................................................................................................47
5.2 Configuration...........................................................................................................................................47
5.3 Triggering ................................................................................................................................................49
5.3.1 Threshold Trigger ..............................................................................................................................49
5.3.1a Trigger Hysteresis .......................................................................................................................49
5.3.2 Digital Input Trigger ..........................................................................................................................51
5.3.3 Edge and Level Triggers ....................................................................................................................51
5.3.4 Manual Trigger .................................................................................................................................52
5.3.5 Logical Combinations of Triggers.......................................................................................................52
5.3.6 Cross Triggering Multiple 70 Series Units (Inter-triggering) ..................................................................52
5.3.7 Fault Distance Triggers .....................................................................................................................52
5.3.8 Periodic Triggers ...............................................................................................................................53
5.4 Recording ................................................................................................................................................54
5.4.1 Waveform Recorder ..........................................................................................................................54
5.4.1a Default Frequency Setting for Waveform Recorder ......................................................................56
5.4.1b Indicating Waveform Records with Digital Outputs ......................................................................56
5.4.1c Retrieving and Deleting Waveform Recorder Files ........................................................................57
5.4.2 Disturbance Recorders ......................................................................................................................57
5.4.2a Indicating Disturbance Records with Digital Outputs ...................................................................58
5.4.2b Retrieving and Deleting Disturbance Recorder Files .....................................................................58
5.4.3 Trend Recorder .................................................................................................................................58
5.4.3a Retrieving Trend Records ............................................................................................................59
5.4.4 Comtrade Format .............................................................................................................................59
5.4.4a Comtrade ZIP Files .......................................................................................................................60
5.4.5 IEEE Long File Naming Convention .....................................................................................................60
5.4.6 Voltage Fluctuation Table (VFT) File.....................................................................................................62
5.4.7 Sequence of Events (SOE) File .............................................................................................................63

iii
5.4.8 Sequence of Events Recorder (SER) File ...............................................................................................64
5.5 M87x File System .....................................................................................................................................65
5.5.1 FTP Server ........................................................................................................................................65
5.5.1a Introduction to FTP .....................................................................................................................65
5.5.1b M87x FTP Implementation ..........................................................................................................66
5.5.2 Zmodem, TELNET, and Command Line Interface ................................................................................67
5.6 Assigning Pulse Outputs to Energy Values ................................................................................................68
5.7 IRIG-B ......................................................................................................................................................68
5.7.1 Overview ..........................................................................................................................................68
5.7.2 Introduction to IRIG Standards ..........................................................................................................69
5.7.2a Time Code Format (Rate Generation) ...........................................................................................69
5.7.2b Format Designation ....................................................................................................................69
5.7.2c Carrier/Resolution .......................................................................................................................70
5.7.2d Coded Expressions .....................................................................................................................70
5.7.3 M87x IRIG-B Implementation .............................................................................................................70
5.7.3a M87x IRIG-B Receiver ..................................................................................................................70
5.7.3b M87x IRIG-B Decoder ..................................................................................................................71
5.7.3c M87x IRIG-B Time Qualifier ..........................................................................................................71
5.7.4 Determining the Correct Year ............................................................................................................71
5.7.5 Methods of Automatic Clock Adjustments ..........................................................................................72
5.7.6 Types of M87x Clock Synchronization ................................................................................................72
5.7.6a Frequency Adjustments and Free Wheeling .................................................................................72
5.7.6b Permanent IRIG-B Source Connection .........................................................................................73
5.7.7 Stages of IRIG-B Synchronization and Accuracy .................................................................................73
5.7.7a Power-Up Stage .........................................................................................................................73
5.7.7b Time Lock Stage .........................................................................................................................73
5.7.7c Frequency Lock Stage .................................................................................................................74
5.7.7d Final Lock Stage .........................................................................................................................74
5.7.8 Notes On Operation ..........................................................................................................................74
5.7.9 IRIG-B Electrical Specifications ..........................................................................................................74
5.7.10 IRIG-B Port Wiring Instructions (Pulse Width Coded, IRIG-B master,....................................................75
Demodulated) ............................................................................................................................................75
5.7.11 Modulated IRIG-B .............................................................................................................................75
5.7.12 Setup Instructions for Use of the M87x Modulated IRIG-B Converter (Sine ..........................................75
Wave, Amplitude Modulated, IRIG-B master) ...............................................................................................75
5.8 Time Sync & Setting ................................................................................................................................76
5.8.1 Time Sync Status Registers ..............................................................................................................76
5.8.2 Manual time setting by Command-Line instruction ........................................................................76
5.8.3 Unsolicited DNP Time set (DNP master sets the IED clock) ..............................................................76
5.8.4 IRIG-B Time sync (time-synchronization via dedicated IED port) ......................................................77
5.8.5 (UCA) Network Time Synchronization - time synchronization over Ethernet .....................................77
5.8.6 SNTP (Simple Network Time Protocol) - time synchronization over Ethernet ....................................77
5.8.7 DNP Time sync (slave requesting DNP time be set) .........................................................................78
5.9 Using the M87x with a Bitronics Analog Output Converter .........................................................................78
5.10 Automatic Event Notification ..................................................................................................................78
5.10.1 Email Notifications ..........................................................................................................................78
5.10.2 Serial Notifications ..........................................................................................................................78
5.10.3 Data Sent .......................................................................................................................................78
5.10.4 Error Recovery ................................................................................................................................79
5.10.5 Example .........................................................................................................................................79
5.10.6 Control Characters...........................................................................................................................79
6.0 POWER SUPPLY V10.....................................................................................................................................80
6.1 Introduction .............................................................................................................................................80
6.2 Features ..................................................................................................................................................80
6.3 Specifications ..........................................................................................................................................80
6.3.1 Environmental ..................................................................................................................................81
6.3.2 Physical ............................................................................................................................................81
6.4 Power Supply and Protective Ground (Earth) Connections .........................................................................82

iv
6.5 Overcurrent Protection.............................................................................................................................82
6.6 Supply/Mains Disconnect .........................................................................................................................82
7.0 SIGNAL INPUT MODULE S10, S11, S12, S1C (M871) S13, S14, S15, S16, S17 (M872) .......................................83
7.1 Introduction .............................................................................................................................................83
7.2 Features ..................................................................................................................................................83
7.3 Specifications ..........................................................................................................................................84
7.4 Current Input (CT) Connections .................................................................................................................90
7.5 Voltage Input (VT) Connections .................................................................................................................91
7.5.1 Overcurrent protection for Voltage input (VT) Connections .................................................................91
7.6 Current Measurements ............................................................................................................................91
7.6.1 Neutral Current (Residual Current) for WYE Connections.....................................................................91
7.7 Voltage Measurements ............................................................................................................................91
7.8 Changing Transformer Ratios ...................................................................................................................92
7.9 User (External Transformer) Gain and Phase Correction ............................................................................92
7.10 Calibration .............................................................................................................................................92
7.11 Installation and Calibration for the S1C Option ........................................................................................92
8.0 ETHERNET MODULE P10, P11, P12 OR E1, E3 OPTION WITH H12 HOST ......................................................104
8.1 Introduction ...........................................................................................................................................104
8.2 Features ................................................................................................................................................105
8.3 Specifications (For P1x Modules Unless Otherwise Noted) .......................................................................105
8.4 Environmental .......................................................................................................................................106
8.5 Physical .................................................................................................................................................106
8.6 Hot Swap (HS) Compatibility (P1x Modules) .............................................................................................106
8.7 Hardware Configuration ........................................................................................................................106
8.8 Cabling ..................................................................................................................................................107
8.9 Connections ..........................................................................................................................................107
8.10 Troubleshooting the Connection ...........................................................................................................107
8.11 Indicators ............................................................................................................................................107
8.12 Software Configuration ........................................................................................................................108
8.13 Technical Details ..................................................................................................................................108
8.13.1 Jumper Settings (P1x) ....................................................................................................................110
8.13.2 Troubleshooting ............................................................................................................................111
8.13.3 PHYSTS Register Contents (P1x) .....................................................................................................111
8.13.4 Statistics Gathered by Ethernet Driver ...........................................................................................113
9.0 DIGITAL INPUT / OUTPUT MODULE P30A, P31, P33 ....................................................................................114
9.1 Introduction ...........................................................................................................................................114
9.2 Features ................................................................................................................................................114
9.3 Specifications ........................................................................................................................................115
9.4 Environmental .......................................................................................................................................116
9.5 Physical .................................................................................................................................................116
9.6 Hot Swap (HS) Compatibility ...................................................................................................................116
9.7 Description .............................................................................................................................................116
9.7.1 P30A ...............................................................................................................................................116
9.7.2 P31 .................................................................................................................................................117
9.7.3 P33 .................................................................................................................................................117
9.8 System Design Considerations ...............................................................................................................117
9.8.1 Input / Output Impedance ................................................................................................................117
9.8.2 Input Assignments ..........................................................................................................................117
9.9 Debounce Time Setting ..........................................................................................................................118
9.10 Setting Digital I/O Module Jumpers.......................................................................................................121
9.10.1 Disassembly of the P30A Module ...................................................................................................121
9.10.2 Disassembly of the P31 Module .....................................................................................................121
9.10.3 CompactPCITM Interface Board (692) Jumper Settings ....................................................................122
...............................................................................................................................................................123
9.10.4 I/O Board (693) Jumper Settings ....................................................................................................123
9.10.5 Health Status Digital Output Setting (Optional assignment of Digital Output 1 of Module 0) .............125

v
9.10.6 Disassembly of the P33 Module .....................................................................................................125
9.10.7 Digital Output Board (803) Jumper Settings....................................................................................125
10.0 TRANSDUCER INPUT MODULE P40 ..........................................................................................................127
10.1 Introduction .........................................................................................................................................127
10.2 Features ..............................................................................................................................................128
10.3 Specifications ......................................................................................................................................129
10.4 Environmental .....................................................................................................................................129
10.5 Physical ...............................................................................................................................................130
10.6 Hot Swap (HS) Compatibility .................................................................................................................130
10.7 Description ...........................................................................................................................................130
10.8 System Design Considerations .............................................................................................................130
10.8.1 Input Type Jumper Settings ...........................................................................................................130
10.8.2 Transducer Input Scaling Configuration .........................................................................................132
10.8.3 Setting the Data Update Rate (Poll rate) for P40 Transducer Inputs .................................................132
Appendix A - Cross Triggering .........................................................................................................................134

Appendix B - Firmware Version History ...........................................................................................................148

vi
FIRMWARE VERSION

The following table provides the most recent firmware and software versions. For best results,
the Configurator version used should match with the firmware version. A complete list of
firmware and software versions is provided on the 70 Series Utilities CD.

NOTE: Host firmware versions 3.0x require 70 Series IEDs with 64 MB SDRAM. Do not attempt to
upgrade older 70 Series IEDs with insufficient memory to v3.0x.

Firmware Versions
Bios DSP Host Utilities Release
Description Version Firmware Firmware Configurator CD Date
M87x Product Release,
New Hardware supported Dual
Bus, Analog I/O 2.1/3.0* 1.21 2.05 2.31 2.43 03/24/06

M87x Product Release, Fault


Location, Adjustable Sample Rate 3.40 1.30 2.17 2.43 2.56 12/21/07

M87x Product Release; Add


Demand per phase for Watts ,VAr,
& VA. Configurator & Biview
improvements w/ modems.
Change to Digital I/O default
watchdog contact (Configurator
setup).
Support new version of hardware
on P3x, P4x modules. 3.40 1.30 2.18 3.00A 2.57 10/17/08
M87x Product Release: Added
1mHz accuracy on M87x.
Improved poll rate to 100ms for a
single P40 transducer inputs
module. Fault distance
configuration is changed. Time
sync with respect to DNP master is
changed from the DNP master
jamming the time to asking the
master what time to jam.
Increased waveform recording
limit from 999 post trigger for
longer recording. 3.40 1.31 2.19 3.02 2.58 09/30/2009
Mx7x Product Release, IEC61850 &
SNTP; Avg 3-Ph Amps and Avg 3-
Ph Volts 3.40 1.30 3.01.0 3.01 3.01 1/30/2009

vii
Firmware Versions
Bios DSP Host Utilities Release
Description Version Firmware Firmware Configurator CD Date
M87x Product Release: Added
1mHz accuracy on M87x.
Improved poll rate to 100ms for a
single P40 transducer inputs
module. Fault distance
configuration is changed. Time
sync with respect to DNP master is
changed from the DNP master
jamming the time to asking the
master what time to jam.
Increased waveform recording
limit from 999 post trigger for
longer recording. 3.40 1.31 3.02.0 3.02 3.02 09/30/2009
M87x Product Release: Added
virtual I/O to DR. Added Peak Fault
Current Measurement. Improved
password security. Added support
for control characters for SMS.
3.40 1.31 3.04 3.04 3.04 10/15/2010

M87x Product Release:


Added support for dual peak
current input range M872 (S16,
S17), IEEE C37.232 naming
convention, periodic triggering,
and 4 IEC 61850 buffered reports. 3.40 1.32 3.05 3.05 3.05 2/28/2011
M87x Product Release:
Increased pre and post trigger
times for DR recorders, modified
base memory to 1MB 3.40 1.32 3.07 3.07 3.07 11/11/2011
M87x Product Release: New H12
Host Processor with and without
E1 and E3 Ethernet options N/A 1.33 4.01 4.01 4.01 3/15/13
M87x Product Release: Support for
IEC 61850 Deadbands N/A 1.33 4.02 4.02 4.02 4/25/13
M87x Product Release:
IEC trigger options DNP3
certification N/A 1.33 4.07 4.04 4.04 10/28/13
M871 Product Release: Support
S1C split core option N/A 1.34 4.082 4.06 4.06 11/14/14
M871 Product Release: Support
new P33 module N/A 1.35 4.09 4.09 4.09 6/22/15
Maintenance Upgrade N/A 1.35 4.10 4.10 4.10 3/10/16
M87x – Add double point
status object for input bit
pairs, add IEC61850
support for P33 module N/A 1.35 4.11 4.11 4.11 6/15/16

Correct Utilities CD Auto-Launch N/A 1.35 4.11 4.11 4.12 7/11/16


Add .csv SER file; maintenance
upgrade N/A 1.35 4.13 4.13 4.13 2/16/17
BiView changes; maintenance
upgrade N/A 1.35 4.15 4.14 4.15 3/21/17
* H10/H11

viii
CERTIFICATION

GE Grid Solutions certifies that the calibration of our products is based on measurements using
equipment whose calibration is traceable to the United States National Institute of Standards
Technology (NIST).

INSTALLATION AND MAINTENANCE

GE Grid Solutions products are designed for ease of installation and maintenance. As with any
product of this nature, installation and maintenance can present electrical hazards and should
be performed only by properly trained and qualified personnel. If the equipment is used in a
manner not specified by GE Grid Solutions, the protection provided by the equipment may be
impaired.

In order to maintain UL recognition, the following Conditions of Acceptability shall apply:

a) Terminals and connectors that shall be connected to live voltages are restricted to non-field
wiring applications only.
b) After installation, all hazardous live parts shall be protected from contact by personnel or
enclosed in a suitable enclosure.

ASSISTANCE

For assistance, contact GE Grid Solutions Worldwide Contact Centre at:

Telephone: +44 1785 250070

Website: https://www.gegridsolutions.com/contact/AlstomGrid.htm

ix
M87x/EN M/O

COPYRIGHT NOTICE

This manual is copyrighted and all rights are reserved. The distribution and sale of this manual
is intended for the use of the original purchaser or his agents. This document may not, in whole
or part, be copied, photocopied, reproduced, translated or reduced to any electronic medium or
machine-readable form without prior consent of GE Grid Solutions, except for use by the original
purchaser.

The product described by this manual contains hardware and software that is protected by
copyrights owned by one or more of the following entities:

Bitronics LLC, 261 Brodhead Road, Bethlehem, PA 18017;


Ardence, Inc., Five Cambridge Center, Cambridge, MA 02142;
SISCO, Inc., 6605 19½ Mile Road, Sterling Heights, MI 48314-1408;
General Software, Inc., Box 2571, Redmond, WA 98073;
Schneider Automation, Inc., One High Street, North Andover, MA 01845;
Triangle MicroWorks, Inc., 2213 Middlefield Court, Raleigh, NC 27615
Greenleaf Software Inc., Brandywine Place, Suite 100, 710 East Park Blvd, Plano, TX 75074

TRADEMARKS

The following are trademarks or registered trademarks GE Grid Solutions:


GE Grid Solutions

The following are trademarks or registered trademarks of Bitronics LLC:


The Bitronics logo Bitronics PowerPlex Triplex Triple-II
MultiComm PowerServe SubCycle Technology SubCycleStuf

The following are trademarks or registered trademarks of the DNP User's Group:
DNP DNP3

The following are trademarks or registered trademarks of the Electric Power Research Institute
(EPRI):
UCA. UCA2

The following are trademarks or registered trademarks of Schneider Automation, Inc.:


MODSOFT Modicon Modbus Plus Modbus Compact 984 PLC

The following are trademarks or registered trademarks of Ardence, Inc.:


Phar Lap the Phar Lap logo

The following are trademarks or registered trademarks of Systems Integration Specialists


Company, Inc. (SISCO):
SISCO MMS-EASE Lite AX-S4MMS

The following are trademarks or registered trademarks of General Software, Inc.:


General Software the GS logo EMBEDDED BIOS Embedded DOS

x
M87x/EN M/O

The following are trademarks or registered trademarks of the PCI Industrial Computer
Manufacturers Group:
CompactPCI PICMG the CompactPCI logo the PICMG logo

xi
M87x/EN M/O

SAFETY SECTION

This Safety Section should be read before commencing any work on the equipment.

Health and safety

The information in the Safety Section of the product documentation is intended to ensure that
products are properly installed and handled in order to maintain them in a safe condition. It is
assumed that everyone who will be associated with the equipment will be familiar with the
contents of the Safety Section.

Explanation of symbols and labels

The meaning of symbols and labels that may be used on the equipment or in the product
documentation is given below.

Installing, Commissioning and Servicing

Equipment connections

Personnel undertaking installation, commissioning or servicing work on this equipment should


be aware of the correct working procedures to ensure safety. The product documentation
should be consulted before installing, commissioning or servicing the equipment.

Terminals exposed during installation, commissioning and maintenance may present a


hazardous voltage unless the equipment is electrically isolated.

If there is unlocked access to the equipment, care should be taken by all personnel to avoid
electric shock or energy hazards.

xii
M87x/EN M/O

Voltage and current connections should be made using insulated crimp terminations to ensure
that terminal block insulation requirements are maintained for safety. To ensure that wires are
correctly terminated, the correct crimp terminal and tool for the wire size should be used.

Before energizing the equipment, it must be grounded (earthed) using the protective ground
(earth) terminal, or the appropriate termination of the supply plug in the case of plug connected
equipment. Omitting or disconnecting the equipment ground (earth) may cause a safety
hazard.

The recommended minimum ground (earth) wire size is 2.5 mm2 (#12 AWG), unless otherwise
stated in the technical data section of the product documentation.

Before energizing the equipment, the following should be checked:

1. Voltage rating and polarity

2. CT circuit rating and integrity of connections

3. Protective fuse rating

4. Integrity of ground (earth) connection (where applicable)

5. Equipment operating conditions

The equipment should be operated within the specified electrical and environmental limits.

Current transformer circuits

Do not open the secondary circuit of a live CT since the high voltage produced may be lethal to
personnel and could damage insulation.

Insulation and dielectric strength testing

Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each
part of the test, the voltage should be gradually reduced to zero, to discharge capacitors,
before the test leads are disconnected.

Removal and insertion of modules

All M87x active circuitry is located on removable modules. Unless a Module is specifically
intended for Hot Swap (see documentation), it must not be inserted into or withdrawn from
equipment while it is energized, since this may result in damage. Hot Swap modules may be
installed and removed under power. Refer to the appropriate section or manual to determine if
the particular module is Hot Swap compatible. For all other modules, remove all power from
the unit before installing or removing any module.

All Hazardous Voltages MUST be removed from the M87x before removing or installing the
Power Supply Module (Vxx) or the Signal Input Module (S1x).

xiii
M87x/EN M/O

All connections to a module must be removed before removing the module. Do not attempt
to install a module with signals connected.

Fiber optic communication

Where fiber optic communication devices are fitted, these should not be viewed directly.
Optical power meters should be used to determine the operation or signal level of the device.

WARNING: EMISSIONS – CLASS A DEVICE (EN55011)


This is a Class A industrial device. Operation of this device in a residential area may cause
harmful interference, which may require the user to take adequate measures.

DECOMMISSIONING AND DISPOSAL

1. Decommissioning

The auxiliary supply circuit in the equipment may include capacitors across the supply
or to ground (earth). To avoid electric shock or energy hazards, after completely
isolating the supplies to the relay (both poles of any dc supply), the capacitors should be
safely discharged via the external terminals before decommissioning.

2. Disposal

It is recommended that incineration and disposal to watercourses is avoided. The


product should be disposed of in a safe manner. Any products containing batteries
should have them removed before disposal, taking precautions to avoid short circuits.
Particular regulations within the country of operation may apply to the disposal of
lithium batteries.

xiv
M87x/EN M/O

1.0 DESCRIPTION

1.1 Introduction

The M87x family of monitoring and recording IEDs with SubCycleTM technology is a major
breakthrough in power measurement technology. The M87x IEDs were designed to expand the
limits of range, speed, and accuracy of measurement, speed of communications, and modularity.
It combines a modular-by-board chassis featuring a CompactPCITM card cage, with a dual
processor measurement system featuring a 32-bit floating point Digital Signal Processor (DSP)
and a 486-based host processor.

1.2 Features

 Extensive measurement set including two sets of voltages and currents with corresponding
power and energy on some models
 Simultaneous support of multiple protocols over multiple physical links
 Two completely independent Disturbance Recorders
 Two separate Waveform Recorders
 Trend Recorder
 Sequence of Event log
 Voltage Fluctuation Table to use for sag and swell reporting
 Two options for analog inputs, 8 voltages with 4 currents and 2 auxiliary voltages or 8
voltages with 6 currents
 128 samples per cycle, 16 bit sampling.
 32-bit floating point DSP, capable of 180 MFLOPS (Million Floating Point Operations Per
Second). A 128-point complex Fast Fourier Transform (FFT) is performed in less than 50
microseconds.
 486-class Host processor.
 Watchdog timer maximizes system reliability.
 4 Configurable serial ports - Three RS232/RS485 ports and one DB9M Service RS232 port
 Fully compatible CompactPCITM backplane and system bus.
 Rugged all-aluminum housing.
 Choice of standard chassis (C07A5) with 3 option cPCI expansion bays, intermediate chassis
(C10A7) with 5 option bays or extended model (C12A8) with 6 option bays.
 Option modules include digital I/O (P30A, P31 and P33), Ethernet (E1/E3, P10, P11, P12), and
transducer input (P40)

1.3 Specifications

Power Supply Input Voltage (Refer to Section 6 on Power supply)

Nominal: 24-250Vdc, 69-240Vac (50/60Hz)

Operating Range: 20-300Vdc, 55-275Vac (45-65Hz)

Burden: 50VA max, 20W max (C07A5)


70VA max, 25W max (C12A8 and C10A7)

1
M87x/EN M/O

(Refer to Section 7 on Signal input modules)


Input Signals (S10, S11, S12, S1C)
CT Current Configuration 4 Inputs. 3 Phase Currents and 1 Neutral.
Inputs (S10) Nominal 5Aac
Peak Current Linear to 100A symmetrical (141A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.04VA @ 5A rms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 4 Inputs. 3 Phase Currents and 1 Neutral.
Inputs (S11) Nominal 1Aac/5Aac
Peak Current Linear to 20A symmetrical (28A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1A rms, 60Hz (0.0016Ω @ 60Hz)/0.04VA @ 5A rms, 60Hz.
Frequency 15-70Hz
CT Current Configuration 4 Inputs. 3 Phase Currents and 1 Neutral.
Inputs (S12) Nominal 1Aac
Peak Current Linear to 4A symmetrical (5.7A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1Arms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 3 Inputs, 3 Phase Currents, or 4 Inputs, 3 Phase Currents and 1 Neutral Current
Inputs (S1C) Nominal 5Aac
Peak Current Linear to 100A symmetrical (141A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden Not applicable

2
M87x/EN M/O

Input Signals (S10, S11, S12, S1C)


Frequency 15-70Hz
VT (PT) AC Configuration 8 Inputs, Measures 2 Buses, 3 or 4 Wire.
Voltage Inputs Nominal 120Vac
(S10, S11, S12)
System Voltage Intended for use on nominal system voltages up to 480V rms phase-to-phase (277V rms
Terminals 9 to
phase-to-neutral).
16
Peak Voltage Reads to 600V peak (425V rms), input-to-case (ground)
Impedance >7.5MΩ, input-to-case (ground)
(cont’d) Voltage 2.5kV rms 1min, input-to-case (ground)
Withstand 2kV rms 1min, input-to-input
Frequency 15-70Hz
AUX Configuration 2 Inputs: VAX1 & VAX2
Measurement Nominal 125Vdc / 120Vac
Voltage Inputs
System Voltage Intended for use on nominal AC system voltages up to 480V rms phase-to-phase (277V rms
(S10, S11, S12)
phase-to-neutral), and DC system voltages up to 250Vdc.
Terminals 17 &
Peak Voltage Reads to 600V peak (425V rms), input-to-case (ground)
18
Impedance >7.5MΩ, input-to-case (ground)
Voltage 2.5kV rms 1min, input-to-case (ground)
Withstand 2kV rms 1min, input-to-input
Frequency DC-70Hz

Input Signals (S13, S14, S15, S16, S17)


CT Current Configuration 6 Inputs. 2 sets of 3 Phase Currents
Inputs (S13) Nominal 5Aac
Peak Current Linear to 100A symmetrical (141A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.04VA @ 5A rms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 2 sets of 3 Phase Currents

3
M87x/EN M/O

Input Signals (S13, S14, S15, S16, S17)


Inputs (S14) Nominal 1Aac/5Aac
Peak Current Linear to 20A symmetrical (28A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1A rms, 60Hz (0.0016Ω @ 60Hz)/0.04VA @ 5A rms, 60Hz.
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 2 sets of 3 Phase Currents
Inputs (S15) Nominal 1Aac
Peak Current Linear to 4A symmetrical (5.7A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1Arms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 3 Phase Currents from 2 Lines with different peak current ranges.
Inputs (S16) Nominal 5Aac
M872 with dual
Peak Current Linear to 20A symmetrical (28A peak)/linear to 100A symmetrical (141A peak) at all rated
peak ranges
temperatures.
20A/100A
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.04VA @ 5A rms, 60Hz (0.0016ohms @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 3 Phase Currents from 2 Lines with different peak current ranges.
Inputs (S17) Nominal 1Aac
M872 with dual
Peak Current Linear to 4A symmetrical (5.7A peak)/linear to 20A symmetrical (28A peak at all rated
peak ranges
temperatures.
4A/20A
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1Arms, 60Hz (0.0016ohms @ 60Hz).
Configuration 6 Inputs. 3 Phase Currents from 2 Lines with different peak current ranges.

4
M87x/EN M/O

Input Signals (S13, S14, S15, S16, S17)


VT (PT) AC Configuration 8 Inputs, Measures 2 Buses, 3 or 4 Wire.
Voltage Inputs Nominal 120Vac
(S13, S14, S15,
System Voltage Intended for use on nominal system voltages up to 480V rms phase-to-phase (277V rms
S16, S17)
phase-to-neutral).
Terminals 9 to
Peak Voltage Reads to 600V peak (425V rms), input-to-case (ground)
16
Impedance >7.5MΩ, input-to-case (ground)
Voltage Withstand 2.5kV rms 1min, input-to-case (ground)
2kV rms 1min, input-to-input
Frequency 15-70Hz

Sampling System
Sample Rate 128 samples per cycle
Data Update Rate Amps, Volts Available every ¼ cycle
Watts, VAs, VARs, PF Available every cycle
Number of Bits 16

Accuracy
Accuracies are specified at nominal Frequency and 25C, unless otherwise specified. Temperature Coefficient <25ppm. All values
are true RMS and include Harmonics to the 63rd (minimum)
Voltage AC: Better than 0.1% of reading (20 to 425V rms, input-to-case). DC (AUX Inputs): +/- 0.2V (24 to 250Vdc,
input-to-case)
Current (S10, S13, S16 Better than 0.1% of reading +/- 500μA (0.5A to 100.0A),
bus 2) Better than 0.1% of reading +/- 1mA (0.05A to 0.5A).
Current (S11, S14, S16 Better than 0.1% of reading +/- 100μA (0.5A to 20.0A),
bus 1, S17 bus 2) Better than 0.1% of reading +/- 250μA (0.05A to 0.5A).
Current (S12, S15, S17 Better than 0.1% of reading +/- 20μA (0.1A to 4.0A),
bus 1) Better than 0.1% of reading +/- 50μA (0.01A to 0.1A).
Current (S1C) External Better than 0.1% of reading +/- 2mA (0.05A to 100.0A, -10C to 70C)
Split-Core CTs

5
M87x/EN M/O

Accuracy
Frequency +/- 0.001 Hertz (accuracy is specified at nominal Frequencies and over operating temperature range)
Phase Angle +/- 0.2 Deg
Power Better than 0.2% of reading (>20% of nominal inputs, 1PF to 0.7PF)

Environmental
Operating Temperature -40C to 70C
Relative Humidity 0-95% non-condensing
Installation Category IC III (Distribution Level) Refer to definitions below.
Pollution Degree Pollution Degree 2 Refer to definitions below.
Enclosure Protection IP20 to IEC60529:1989
Altitude Up to and including 2000m above sea level
Intended Use Indoor use; Indoor/Outdoor use when mounted in an appropriately rated protective enclosure to
NEMA or IP protection classifications, as required for the installation.

Physical
Connections Current (S10, Terminal block with 10-32 Studs for current inputs. Use ring lugs sized for #10 stud.
(Signal Input S11, S12) Accepts #10-16 AWG (5.3-1.3mm2) wire. Recommended Torque: 16 In-Lbs, 1.81 N-m. Current
Modules) inputs are connected to the output from the secondary of permanently installed Current
Transformers (CTs). Grounding of CT signals per ANSI/IEEE C57.13.3-1983 is required.
Current (S13, Terminal block with 8-32 Screws for current inputs. Use ring lugs sized for #10 screw thread.
S14, S15, S16, Accepts #10-22 AWG (5.3-0.33mm2) wire. Recommended Torque: 16 In-Lbs, 1.81 N-m. Current
S17) inputs are connected to the output from the secondary of permanently installed Current
Transformers (CTs). Grounding of CT signals per ANSI/IEEE C57.13.3-1983 is required.
External Split- 6 position removable terminal block, accepts 26-14AWG stranded wire. Recommended Torque 7
Core CTs (S1C) in-lbs, 0.79N-m.

6
M87x/EN M/O

Physical
Overcurrent To maintain the safety features of this product, a 3 Ampere time delay (T) fuse must be connected
protection in series with the ungrounded/non-earthed (hot) side of the supply input connected to the voltage
for Voltage measurement (VT) input of the instrument prior to installation. The fuse must carry a voltage rating
(measurement) appropriate for the power system on which it is to be used. A 3 Ampere slow blow UL Listed fuse in
input (VT) an appropriate fuse holder should be used in order to maintain any UL product approval.
connections
Voltage Removable Terminal Block, accepts #22-12 AWG (0.35 to 3.3mm2) wire, or terminal lugs up to
(CE units) 0.250" (6.35mm) wide. Standard 0.200" (5.08mm) header socket accepts other standard terminal
types. Precautions must be taken to prevent shorting of lugs at the terminal block.
A minimum distance of 1/8" (3mm) is recommended between uninsulated lugs to maintain
insulation requirements. Recommended Torque: 10 In-Lbs, 1.13 N-m
Voltage Removable Terminal Block, accepts #22-12 AWG (0.35 to 3.3mm2) wire, or terminal lugs up to
(non-CE) 0.325" (8.25mm) wide. Standard 0.200" (5.08mm) header socket accepts other standard terminal
types. Precautions must be taken to prevent shorting of lugs at the terminal block.
A minimum distance of 1/8" (3mm) is recommended between uninsulated lugs to maintain
insulation requirements. Recommended Torque: 10 In-Lbs, 1.13 N-m
Class I equipment to IEC61140: 1997

(Refer to Section 10 on -P40 Tranducer input Module)


-P40 Transducer Input Module
Inputs 8 bi-directional, jumper selectable for voltage or current range.
0 – 10V Voltage Range Overload Range: -12.5 V to +12.5 Vdc
Resolution: 0.381 mV
Input Resistance: 10KΩ
0 – 1mA Current Range Overload Range: -2.5 mA to +2.5 mA
Resolution: 0.0763 μA
Input Resistance: 500Ω
4 – 20mA Current Range Overload Range: 0 mA to +25 mA
Resolution: 0.381 μA
Input Resistance: 50Ω
Common Mode Input Range +/- 9V, Input to Chassis
Common Mode Error Vcm DC 0.3% of FS @ 9Vp Common Mode

7
M87x/EN M/O

-P40 Transducer Input Module


Inputs 8 bi-directional, jumper selectable for voltage or current range.
Vcm 50/60Hz AC 0.1% of FS @ 9Vp Common Mode
Accuracy 0.25% of Full Scale Input
Protection Input terminals have internal transzorb clamp and 90V spark gap protection.
Data Update Rate (Poll Rate) 100ms minimum (single P40 module); 500ms minimum (multiple P40 modules)
Input / Output Capacitance, any 470pF
Terminal to Case
Power Supply Requirements 3.3Vdc, 5Vdc, +/-12Vdc (supplied from backplane)
Hot Swap Complies with Hot Swap specification PICMG 2.1 R1.0 for Basic Hot Swap (requires Host
Processor re-boot)
Connections Removable Terminal Blocks, accepts #16-28AWG (1,4-0,09mm) wire. Recommended Torque
Rating is 2.2 In-Lbs, 0.25 N-m. Standard 0.150" (3,81mm) header socket accepts other
standard terminal types. Solid core wire is recommended, or stranded wire with the use of
“bootlace ferrules,” where these are available.
Package CompactPCITM (3U, 4HP) removable module

8
M87x/EN M/O

Definitions:

Installation Category (Overvoltage Category) III: Distribution Level, fixed installation, with smaller
transient overvoltages than those at the primary supply level, overhead lines, cable systems, etc.

Pollution: Any degree of foreign matter, solid, liquid, or gaseous that can result in a reduction of electric
strength or surface resistivity of the insulation.

Pollution Degree 2: Only non-conductive pollution occurs except that occasionally a temporary
conductivity caused by condensation is to be expected.

9
M87x/EN M/O

1.4 Standards and Certifications

1.4.1 Revenue Accuracy

The M87x exceeds the accuracy requirements of ANSI C12.20 and IEC 60687. The accuracy class
of the instrument to each standard is determined by the selected Signal Input Module.

Module Nominal Current Certification


S10, S13, S1C, 5A ANSI C12.20, 0.5CA
S16 bus 2 IEC 60687, 0,5S
S11, S14, S16 5A ANSI C12.20, 0.2CA
bus 1, S17 bus IEC 60687, 0,2S
2 1A ANSI C12.20 0.5CA
IEC 60687, 0,5S
S12,S15, S17 1A ANSI C12.20, 0.2CA
bus 1 IEC 60687, 0,2S

The M87x was tested for compliance with the accuracy portions of the standards only. The
form factor of the M87x differs from the physical construction of revenue meters specified by
the ANSI/IEC standards and no attempt has been made to comply with the standards in whole.
Contact customer service for more information.

1.4.2 Environment

UL/CSA Recognized, File Number E164178 (does not apply for S1C option or for units with
the P33 digital output option):

UL 61010-1, Edition 3, Issue Date 2012/05/11,


SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL,
AND LABORATORY USE - PART 1: GENERAL REQUIREMENTS.
UL 61010-2-030, Edition 1 - Issue Date 2012/05/11,
SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL,
AND LABORATORY USE - PART 2-030: PARTICULAR REQUIREMENTS FOR TESTING AND
MEASURING CIRCUITS.

CSA C22.2 NO. 61010-1-12-CAN/CSA, Edition 3, Issue Date 2012/05/01,


CAN/CSA SAFETY REQUIREMENTS FOR ELECTRICAL
EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE -
PART 1: GENERAL REQUIREMENTS.
CSA C22.2 NO. 61010-2-030-12-CAN/CSA, Edition 1, Issue Date 2012/05/01,
SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL,
AND LABORATORY USE - PART 2-030: PARTICULAR REQUIREMENTS FOR TESTING AND
MEASURING CIRCUITS.

10
M87x/EN M/O

If applicable, the CE mark must be prominently marked on the case label.

European Community Directive on EMC (EMCD) 2014/30/EU, superseding Directive


2004/108/EC (which replaced former directive 89/336/EEC amended by 92/31/EEC,
93/68/EEC, 98/13/EC) and Directive 91/263/EC [TTE/SES]).
European Community Directive on Low Voltage (LVD) 2014/35/EU, superseding
2006/95/EC, (which replaced former Directive 73/23/EEC)

The object of the declaration described above is in conformity with the relevant Union harmonisation legislation:
Directives 2004/108/EC & 2006/95/EC (until April 19th, 2016) and Directives 2014/30/EU &, 2014/35/EU (from April
20th, 2016).

Product and Generic Standards


The following product and generic standards were used to establish conformity:

Low Voltage (Product Safety):


IEC/EN 61010-1, Edition 3, Issue Date 2010
Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use –
Part 1: General Requirements

IEC/EN 61010-2-30, Edition 1 – Issue Date 2010


Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use –
Part 2-030: Particular Requirements for Testing and Measuring Circuits

EMC:
EN 61326-1: 2013 (supersedes EN 61326-1: 2006),
IEC/EN 60255-26: 2013 + AC: 2013 (product standard used in part – reliance on basic EMC
standards) (supercedes IEC 60255-25: 2000 and IEC 60255-26: 2008, which superceded EN
60255-26: 2006, which superceded EN50263: 2000) EN 61000-6-2: 2005 + AC: 2005 (supercedes
EN 61000-6-2: 2005, which superceded EN 50082-2: 1995),
EN 61000-6-4: 2007 + A1: 2011 (IEC date 2010), (which superceded EN 50081-2: 1993).

Radiated Emissions Electric Field Strength


Basic EMC emissions standard (radiated emissions):
EN 55011: 2016, EN 55011: 2009 + A1: 2010, (which superceded EN 55011: 2007 + A2: 2007,
which superceded EN 55011: 1998 + A1:1998 + A2:2002)
Group 1, Class A
Frequency: 30 - 1000 MHz

EN 55011 is applicable for the following EMC product and generic standards:
IEC/EN 60255-26: 2013 + AC: 2013 (supercedes IEC/EN 60255-25: 2000,
EN 61000-6-4: 2007 + A1:2011 (IEC date 2010)

AC Powerline Conducted Emissions


(Applicable on VT inputs - Bus1/ Bus 2 and AUX PWR (Universal Hi Range AC/DC Power supply)

Basic EMC emissions standard (AC powerline conducted emissions):


EN 55011: 2016, EN 55011: 2009 + A1: 2010, (which superceded EN 55011: 2007 + A2:2007,
which superceded EN 55011: 1998 + A1: 1998 + A2: 2002)
Group 1, Class A

11
M87x/EN M/O

Frequency: 150 kHz – 30 MHz

EN 55011 is applicable for the following EMC product and generic standards:
IEC/EN 60255-26: 2013 + AC: 2013 (supercedes IEC/EN 60255-25: 2000,
EN 61000-6-4: 2007 + A1:2011 (IEC date 2010),

Conducted Emissions, Telecommunication ports (Ethernet port)


EN 55032: 2015 + AC: 2016-07,
EN 55032: 2012 + AC: 2013,
EN 55022: 2010 + AC: 2011,
Group 1, Class A
Frequency: 150 kHz – 30 MHz

1 MHz Burst Disturbance Test


IEC60255-22-1: 1988
Class III
Amplitude: 2.5 kV

Electrostatic Discharge (ESD)


EN61000-4-2: 2009 (supersedes EN 61000-4-2: 1995 / A1:1998 / A2: 2001)
Discharge voltage: ± 8 KV Air; ± 4 KV Contact (Additionally meets ± 6kv Contact)

Immunity to Radiated Electromagnetic Energy (Radio-Frequency)


EN61000-4-3: 2006 + A1:2008 + A2:2010, Class III (supersedes EN61000-4-3: 2002 + A1:2002,
which superceded IEC 61000-4.3: 1995; and ENV 50204: 1996, on Immunity to Radiated
Electromagnetic Energy -Digital Radio Telephones 900 MHz & 1890 MHz).

Frequency: 80 – 1000 MHz Amplitude: 10.0 V/m Modulation: 80% AM @ 1kHz


Frequency: 1400-2000 MHz Amplitude: 3.0 V/m Modulation: 80% AM @ 1kHz
Frequency: 2000-2700 MHz Amplitude: 1.0 V/m Modulation: 80% AM @ 1kHz

Digital Radio Telephones


Frequency: 900 MHz/1890 MHz Amplitude: 10.0/3.0 V/m Modulation: 80% AM @ 1kHz

Electrical Fast Transient / Burst Immunity


EN 61000-4-4: 2012 (supersedes EN 61000-4-4: 2004 + A1:2010, which superceded IEC61000-
4-4: 1995)
Burst Frequency: 5 kHz
Amplitude, Input AC Power Ports: Severity Level 4; Amplitude ± 4 kV
Amplitude, Signal Ports: Severity Level 3; Amplitude ± 2 kV
Amplitude, Telecom Ports (Ethernet): ± 1 kV

Current/Voltage Surge Immunity


EN 61000-4-5: 2014 (supersedes EN 61000-4-5: 2006, which superceded EN610000-4-5: 1995 +
A1:2001 and IEC 61000-4-5 : 1995)
Installation Class: 3
Open Circuit Voltage: 1.2 / 50 µs
Short Circuit Current: 8 /20 µs
Amplitude: 2 kV common mode, 1 kV differential mode

12
M87x/EN M/O

Immunity to Conducted Disturbances Induced by Radio Frequency Fields


EN 61000-4-6: 2014 (supercedes EN 61000-4-6: 2009, which superceded EN 61000-4-6: 2007,
which superseded EN 61000-4-6: 1996 + A1:2001 and IEC61000-4-6: 1996)
Level: 3
Frequency: 150 kHz – 80 MHz
Amplitude: 10 VRMS
Modulation: 80% AM @ 1kHz

Power Frequency Magnetic Fields


EN61000-4-8:2010
Amplitude: 30 A/m
Frequency: 50 and 60 Hz

AC Supply Voltage Dips and Short Interruptions


EN 61000-4-11: 2004 (supersedes IEC61000-4-11: 1994)
Duration: 10ms on auxiliary power supply, under normal operating conditions, without de-
energizing.

Surge Withstand Capability Test For Protective Relays and Relay Systems
ANSI/IEEE C37.90.1: 1989 (2.5 kV oscillatory wave)

Vibration
IEC60255-21-1: 1988 Endurance Class: 1

Shock and Bump


IEC60255-21-2: 1988 Bump Class: 1

13
M87x/EN M/O

2.0 HOUSING AND BACKPLANE

The M87x chassis is a modular-by-board design, with a rugged aluminum housing specifically
designed to meet the harsh conditions found in utility and industrial applications. The chassis
features a passive backplane, an embedded and fully compatible CompactPCITM (cPCI) bus
section and proprietary signal input and analog (DSP) processor sections. All active circuitry is
located on removable modules. There are four types of modules: Power Supply, Signal Input, the
Host/Analog-Digital Signal Processor, and cPCI expansion modules. See Figure 1 (below) for the
locations of the module bays in the standard chassis.

Figure 1 - Front View and Module Assignment (C07A5, M871 Only)

The power supply bay utilizes a standard cPCI power connector. The signal input bay uses a self-
aligning 24-pin header. The Analog-Digital Signal Processor board interfaces to the PCI Bus with
a standard cPCI connector, and uses a 24-pin header to connect to the analog signals from the
Signal Input Board. The Host Processor and the cPCI expansion bays have standard cPCI
connectors. The expansion bays are fully compatible, both electrically and mechanically with
cPCI standards. The Backplane board is an eight-layer circuit board, and contains a 5V, 33MHz
cPCI bus. The standard bay assignment for the standard chassis (C07A5) used for the M871 is
shown above. The M871 and M872 are also available in an intermediate chassis (C10A7) that
adds two additional cPCI expansion bays, and an extended chassis, (C12A8) that adds three
additional cPCI expansion bays. The H12 host processor with either of the combined Ethernet
options (E1 or E3) uses a wider front plate incorporating the first of the expansion slots to the left
of the host/analog/Ethernet module.

14
M87x/EN M/O

Figure 2 - Mounting and Overall Dimensions (C07A5)

15
M87x/EN M/O

13.45" (342)
ø 0.25"

2.33"
(59)

5.20"
(132)

2.33"
(59)

0.27" (6.9)
0.23" (5.7) 13.00" (330)

Figure 3 - Mounting and Overall Dimensions (C12A8 and C10A7)

16
M87x/EN M/O

2.1 Installation

WARNING - INSTALLATION AND MAINTENANCE SHOULD ONLY BE PERFORMED BY PROPERLY


TRAINED OR QUALIFIED PERSONNEL.

2.2 Initial Inspection

Bitronics instruments are carefully checked and "burned in" at the factory before shipment.
Damage can occur however, so please check the instrument for shipping damage as it is
unpacked. Notify Bitronics LLC immediately if any damage has occurred, and save any damaged
shipping containers.

2.3 Protective Ground/Earth Connections

There are two chassis ground points that MUST be connected to Earth Ground (refer to Figure 8,
pg. 78). The first is the Protective Ground (Earth) terminal (terminal 2) on the Power Supply input.
The minimum Protective Ground (Earth) wire size is 2.5 mm2 (#12 AWG). The second is the
mounting flange. Bitronics LLC recommends that all grounding be performed in accordance with
ANSI/IEEE C57.13.3-1983.

2.4 Instrument Mounting

The unit should be mounted with four #10-32 (M4) screws. Make sure that any paint or other
coatings on the panel do not prevent electrical contact. The device is intended to be connected
to earth ground at the mounting plate. See Section 2.3.

2.5 Surge Protection

Surge protection devices are incorporated into the power supply. See Section 2.3 for
grounding/earthed recommendations. If the unit is to be powered from a VT, it is recommended
that one side of the VT be grounded at the instrument following ANSI/IEEE C57.13.3-1983. See
Section 6.5 for fuse recommendations.

2.6 Cleaning

Cleaning the exterior of the instrument shall be limited to the wiping of the instrument using a
soft damp cloth applicator with cleaning agents that are not alcohol based, and are
nonflammable and non-explosive.

17
M87x/EN M/O

2.7 Removal and Installation of Modules

All active circuitry is located on removable modules. Hot Swap modules may be installed and
removed under power. Refer to the appropriate section or manual to determine if the particular
module is Hot Swap compatible. For all other modules, remove all power from the unit before
installing or removing any module.

All Hazardous Voltages MUST be removed from the M87x before removing or installing the
Power Supply Module or the Signal Input Module. The Signal Input Module and the Power
Supply may be withdrawn from the housing after removal of the front panel screws.

All connections to a module must be removed before removing the module. Do not attempt
to install a module with signals connected. To remove a cPCI module, use the following
procedure:

1. Remove power from the unit (except Hot Swap modules).


2. Unscrew the M2.5 Phillips front panel screws (note that these are captive screws). The
screw in the handle has been left out intentionally.
3. Pull the red sliding release tab up and outward until handle is unlocked.
4. Push the handle downward (when viewed from the front) to lever out the module.
5. Once the module is disengaged from the backplane connector, carefully withdraw the
module.
6. Be extremely careful when handling the module, especially the backplane connector.

To insert a cPCI module, use the following procedure:

1. Make sure the red sliding release tab is fully extended from the handle, and that the
handle is in the downward position (when viewed from the front).
2. Line up the module with the card guides in the appropriate position (the Host/Analog-
Digital Signal Processor Module MUST be inserted in the right most double width bay).
3. Use the handle to lever the module into the housing.
4. When the module is fully engaged, tighten the M2.5 Phillips front panel screws. The screw
in the handle has been left out intentionally.

18
M87x/EN M/O

3.0 HOST / ANALOG-DIGITAL SIGNAL PROCESSOR MODULE H11/H12 AND A10

The Host/Analog-Digital Signal Processor Module is an assembly consisting of two sections: the
Host board and the Analog-Digital Signal Processor board.

3.1 Host board

The Host CPU module consists of a 486-class microprocessor, four communications ports and a
CompactPCITM master bridge. The H11 host module offers non-volatile memory expansion via
an optional Compact Flash card. The H12 host module utilizes a Compact Flash card, available
in optional sizes, and offers optional Ethernet interfaces (E1 and E3).

3.1.1 Serial Port/Front Panel Board

The Serial Port/Front Panel Board consists of the four serial driver connectors, four status LED’s,
four bi-color serial port LED’s, and a reset button. Port P1 is a PC-AT style 9-pin D connector for
the dedicated RS-232 port, and ports P2, P3, and P4 are universal 150-mil, 6-pin removable
connectors for the RS-232/RS-485 serial ports. P2, P3, and P4 are software (user) configurable
for RS-232 or RS-485 mode. The RS-232 drivers support full and half duplex modes. See Figures
3-6 (pg. 22 -26) for signal assignments.

3.1.1a Service Port (P1)

When connecting to the Service port DB9M (P1) from a PC, a null modem cable is required. The
Service Port can be used with a PC running a terminal emulation program. Upon startup, the
M87x default configuration sets P1 for 9600 baud, 8 data bits, no parity, 1 stop bit and no flow
control handshaking. These parameters are user-configurable. A small number of messages are
sent to P1 and the M87x then outputs system messages. Enter the command mode by pressing
the ENTER key until the system outputs a prompting message. Allowable commands are:

Service Port\Zmodem Commands


c: dir receive time
cd exit reset type
chp1 getlog router trigger dr1
chp2 Goose* send trigger dr2
d: ip serial trigger wv1
date mac setlog trigger wv2
del nsap subnet ver
dio point password software whoami
display on pulse receive vio point
display off reboot status
Note: * This command is for UCA Goose only and is now referred to as GSSE.

Type “help <command>” to find out more about a particular command. The more commonly
used commands are:

ip - Set Internet Protocol (IP) address information in "dotted decimal" format. The IP address

19
M87x/EN M/O

defaults to "192.168.0.254".

subnet – Set the Subnet mask. The Subnet mask defaults to "255.255.255.0".

router – Set the Gateway (Router) address. The Gateway (Router) address defaults to
"192.168.0.1".

nsap - Set the OSI network address (NSAP) in "space delimited octet string" format. The default
address is "49 00 01 42 49 09 01 01" which is a local address not attached to the global OSI
network.

The correct value for your network should be obtained from the network administrator. The
default values are valid for a device that is attached to a local intranet with optional access via
a router (such as a device within a substation).

time - Set the time as 24-hour UTC time. Time is entered as HH:MM:SS. The factory default is set
to GMT.

date – Set the date. Date is entered as MM/DD/YYYY.

serial - Display M87x serial number

exit - Exit command line mode and return to logging mode. If no commands are received for five
minutes the device will revert to logging mode.

3.1.1b Standard Serial Ports (P2, P3, P4)

These ports can be set to RS-232 or RS-485, and support baud rates up to 115200. Set-up of the
Serial Ports can be accomplished by using the 70 Series Configurator. The default configuration
for the serial ports is:

Serial Port Default Settings


Port Protocol Parity Baud IED Address Physical Media
P1 Zmodem/Display/Log None 9600 RS-232
P2 DNP 3.0 None 9600 1 RS-232
P3 Modbus Even 9600 1 RS-232
P4 Zmodem/Display/Log None 9600 RS-232

The configuration of these ports is stored internally in the "COMM.INI" file (Section 5.2). If, for any
reason, the configuration of the serial ports is erroneously set, the factory default settings can be
restored by using FTP. The file "COMM.INI" can be deleted, which will return all ports to the factory
default setting. The settings can then be changed by using the 70 Series Configurator.

Host cable requirements for CE compliance:


On ports P2, P3, and P4, as well as a port that utilizes the externally mounted M87x Modulated
IRIG-B Converter, install snap-on ferrite (Fair-Rite #0461164181 or equivalent) onto each cable
by wrapping the cable through the ferrite opening two times before snapping the ferrite closed.
Tie RS-485 cable shields (pin 5) to earth ground at one point in system.

20
M87x/EN M/O

The recommended torque rating for the terminal block wire fasteners on ports P2-P4 is 2.2 In-
Lbs, 0.25 N-m.

3.1.1c Diagnostic Status LED’s (S1, S2, S3, S4)

There are four LED’s on the front panel: S1, S2, S3, and S4. They perform the following functions:

LED Description
S1 On while flash memory is being written to, otherwise off.
S2 Flashes every 5 power-line cycles, indicates DSP operating properly.
S3 On while CPU is busy. Intensity indicates CPU utilization level.
S4 On during internal self-diagnostics after boot-up.

3.1.1d RS485 Connections

Note that various protocols and services have different port connection requirements. When
making connections to serial ports for Modbus or DNP3 over RS485, 2-wire half duplex is
required. This is because it is necessary to maintain a minimum time period (3 1/3 characters)
from the time the transmitter shuts off to the next message on the bus in order to guarantee
reliable communications. However, when using Zmodem or connecting to the remote display,
asynchronous 2 way communications are required, and therefore a 4-wire full duplex
(technically RS422) connection is needed. See figures 4 and 6 below for RS485 cable wiring
and signal assignment diagrams showing both 2 and 4 wire.
There are special considerations for multi-drop Zmodem connections. Zmodem protocol was
developed for RS232 point-to-point connections so it does not support any standard
convention for addressing. Therefore, it does not facilitate multi-drop communications buses.
In order to make it possible to use one modem to establish remote communications with
multiple 70 Series devices when the Ethernet option (preferred) is not fitted, the following
proprietary convention is employed.

When using HyperTerminal or a dial-up modem with RS485, the port on the IED must be
configured for "Zmodem" protocol, not for "Zmodem/Display/Log". This is done with the pull-
down menu in the Configurator program, see illustration below. Selecting Zmodem also
enables an address to be set for the selected COM port. When daisy-chaining multiple devices
on RS485, each device must have a unique address.

21
M87x/EN M/O

Type the command "connect 01" (use the actual address assigned) to establish
communications with the device in Zmodem protocol using RS485. This command will not be
echoed back as you type it. After striking the enter key, the device will return a command
prompt (for example c:\>, e:\data>, c:\config>, etc.) Once communications are established, you
can now use the command-line interface, exactly as you would with a direct RS232 connection,
to control the device (services supported by Zmodem protocol include: download recording
files, control digital outputs, reset demands, set time and date, etc.). In order to disconnect from
one device and connect to another on the same bus, type the command "exit" to end the
session then type “connect 02” (or whatever address you want to connect to).

22
M87x/EN M/O

Figure 3 - Typical RS-232 & IRIG-B Cable Wiring

23
M87x/EN M/O

Figure 4 - Typical RS-485 Cable Wiring

24
M87x/EN M/O

Figure 4 - Typical RS-485 Cable Wiring

25
M87x/EN M/O

Figure 5 – M870D RS-232 Cable Wiring

26
M87x/EN M/O

Figure 6 - Host Port Signal Assignment

27
M87x/EN M/O

3.1.2 Self-Test Modes

The M87x has several self-tests built in to assure that the instrument is performing accurately. Refer to the appropriate protocol
manual for details on how to retrieve the self-test information. The following table lists possible faults that would be detected by the
self-tests, how the fault is indicated, the effects of the fault and any necessary corrective actions.

Self-Test Bits
Bit # Description Hardware Effect Default Value
Factory gain calibration of Analog-Digital Signal Unit will continue to function using
0(LSB) A10 EEProm A/D Gain = 1
Processor Module checksum error. default values, at reduced accuracy.
Factory offset calibration of Analog-Digital Signal Unit will continue to function using
1 A10 EEProm A/D Offset = 0
Processor Module checksum error. default values, at reduced accuracy.
Factory gain calibration of Signal Input Module Unit will continue to function using
2 S1x EEProm CT/VT Gain = 1
checksum error. default values, at reduced accuracy.
Factory offset calibration of Signal Input Module Unit will continue to function using
3 S1x EEProm CT/VT Offset = 0
checksum error. default values, at reduced accuracy.
Factory phase calibration of Signal Input Module Unit will continue to function using
4 S1x EEProm CT/VT Phase = 0
checksum error. default values, at reduced accuracy.
Factory defined internal ratios of Signal Input Module Unit will continue to function. Assumes Volts Ratio = 60 :1
5 S1x EEProm
checksum error. (Type of Signal Input Module) -S10 Signal Input Module Amps Ratio = 14.136 :1
Unit will continue to function using
6 User defined external transformer ratio checksum error. S1x EEProm User CT = 5:5, VT = 1:1
default values (i.e. w/o user ratios).
Unit will continue to function using
7 User gain correction values checksum error. S1x EEProm User Gain = 1
default values (i.e. w/o user gain).
Unit will continue to function using
8 User phase correction values checksum error. S1x EEProm User Phase = 0
default values (i.e. w/o user phase).
Factory defined board ID for Analog-Digital Signal Assumes default Analog-Digital Signal
9 A10 EEProm Module A10
Processor Module checksum error. Processor Module.
Factory defined board ID for Signal Input Module
10 S1x EEProm Assumes default Signal Input Module. Module -S10
checksum error.
User defined denominators for TDD measurement
11 S1x EEProm Assumes default TDD Denominator. TDD Denom = 5A Secondary
checksum error.
12 DSP program integrity checksum error. A1x DSP Ram Host trips watchdog, unit reboots.
13 DSP stack overflow. A1x DSP Ram Host trips watchdog, unit reboots.
14 Invalid or missing Amp and/or Voltage Scale Factor. H1x Flash File Protocol will use default Scale Factor Scale Factor = 1:1
M87x uses default protocol M87x register set
15 Protocol configuration invalid. H1x Flash File
configuration

28
M87x/EN M/O

3.1.3 System Clock

The M87x has an internal System Clock with a capacitor backed RAM (typical data retention of 7
days at room temperature) when no power is applied to the unit. The clock is located on the Host
board. The time settings may be changed via the Serial Port (P1) or various communication
protocols. Refer to Section 3.1.1a and the appropriate protocol manuals for details.

3.2 A10 Analog-Digital Signal Processor Board

The Analog/DSP board is part of the modular M87x system. This board contains amplifiers, track
and hold circuits, multiplexers, an analog to digital converter, a digital signal processor (DSP), and
a PCI bridge. Analog signals from the CT/VT board are routed through the backplane to the
Analog/DSP board. Once on the board each signal is connected to the track and hold circuitry.
The track and hold circuitry is designed to hold the channel’s present value during the time
required for the analog to digital converter to sample all of the channels. This effectively allows
the M87x to simultaneously sample all of its input channels, eliminating any channel-to-channel
skew. A single 16-bit analog to digital converter is used for all measurements. The DSP uses the
samples to calculate all of the measured parameters. Each sample is corrected for offset and
gain using factory calibration values stored in non-volatile memory on the board. Additionally, a
continuous DC removal is performed on all inputs, except the AUX Voltages. An adaptive
sampling system is used to maintain 128 samples per cycle over the input frequency range of 15
to 70 Hz. See Section 3.2.2.

3.2.1 Calibration

Routine re-calibration is not recommended or required. A field calibration check every few years
is a good assurance of proper operation.

3.2.2 Instantaneous Measurement Principles

The M87x measures all signals at 128 samples/cycle, accommodating fundamental signal
frequencies from 15 to 70 Hz. Samples of all bus signals are taken at the same instant in time,
using a 16-Bit A/D converter, effectively creating 128 "snapshots" of the system voltage and
current per cycle.

3.2.2a Sampling Rate and System Frequency

The sampling rate is synchronized to the frequency of any of the bus voltage or current inputs,
prioritized as follows: V1A-N, V1B-N, V1C-N, V2A-N, V2B-N, V2C-N, IA, IB, IC. This is the frequency reported
as the "System Frequency". The AUX voltage inputs and Neutrals are not used to synchronize the
sampling. The sampling rate is the same for all channels.

The default system frequency may be set in the Configurator to either 50 or 60 Hz. This will have
no effect on the frequency that is reported, or the sample rate when signals are present. It is
used to set the default sample rate when the unit cannot detect any applied signal.

29
M87x/EN M/O

4.0 MEASUREMENTS

Basic measurement quantities are calculated and updated every 1/4 cycle. These quantities
include RMS Amperes and RMS Volts. Watts, VARs, VAs, Power Factor, all harmonic-based
measurements (such as fundamental-only quantities), Energy, Frequency, and Phase Angle are
updated every cycle.

Note: For all of the following measurements, it is important to keep in mind that the specific
protocol used to access the data may affect the data that is available, or the format of that data.
No attempt is made here to describe the method of accessing measurements - always check the
appropriate protocol manual for details.

4.1 Current (1/4-Cycle Update)

The current signals are transformer coupled, providing a true differential current signal.
Additionally, a continuous DC removal is performed on all current inputs. Instrument transformer
ratios can be entered for each current input, as described in the Signal Input Module section
(Section 7). This can be accomplished via a network and protocol (refer to the specific protocol
manual for details) or by using the 70 Series Configurator.

When used on 2-element systems, if there are only 2 currents available to measure, a "0" can be
written to the CT Ratio for the missing phase current. This will cause the M87x to fabricate the
missing phase current from the sum of the other 2 phase currents. This feature is not
recommended for WYE connected systems.

The average of the 3 current phases ((Ia + Ib + Ic)/3) is also available. The Average 3-phase
Amps for bus 1 and bus 2 (M872) are calculated and made available on a per cycle basis.

4.1.1 Neutral and Residual Current (1/4-Cycle Update)

M871 Signal Input Modules have a separate input for neutral current. This channel is measured
just like any of the other current channels, and the result presented as Neutral Current.
Additionally, all M87x units calculate the vector sum of the three phase currents, which is known
as the Residual Current. The Residual Current is equivalent to routing the common current return
wire through the neutral current input on systems without separate current returns for each
phase, with the exception that individual Harmonics are not measured on Residual Current.

On systems without a Neutral CT, the Residual Current measurement can be used as a substitute
for Neutral Current. This allows the Neutral Current input on the M871 to be used to measure
any extra currents in the system.

4.2 Voltage Channels (1/4-Cycle Update)

The M87x uses a unique voltage connection method, which is combined with simultaneous
sampling to provide an extremely flexible voltage measurement system. All voltage inputs are
measured relative to a common reference level (essentially panel ground). See Figure 9 (pg. 89-
96) and Section 7 for input connection information. Because all phase signals are sampled
simultaneously (including currents), these signals can be easily combined to form true Phase-to-

30
M87x/EN M/O

Phase and Phase-to-Neutral differential measurements with extremely low amplitude and phase
errors. It also allows accurate calculation of Bus-to-Bus differential voltages and angles. Each
sample is corrected for offset and gain using factory calibration values stored in non-volatile
memory on the board. Additionally, a continuous DC removal is performed on all inputs, except
the AUX Voltages.

The M87x calculates voltages in PRIMARY units, based on the VT Ratios entered. There are
separate VT Ratios for each input. Ratios can be entered via a network and protocol (refer to the
specific protocol manual for details) or by running the M87x Configurator.

The advantages of this method of voltage measurement are apparent when the M87x is used on
the common 2, 2-1/2, and 3 element systems (refer to Section 4.4). The M87x is always
calculating Line-to-Neutral, Line-to-Line, and Bus-to-Bus voltages with equal accuracy. On 2
element connections, any phase can serve as the reference phase. Further, the M87x can
accommodate WYE connections on one Bus, and DELTA connections on the other Bus.

On 2-1/2 element systems, one of the phase-to-neutral voltages is missing, and the M87x must
create it from the vector sum of the other two phase-to-neutral voltages. In order to configure
the M87x for 2-1/2 element mode and which phase voltage is missing, a "0" is written to the
phase-to-neutral VT Ratio for the missing phase voltage.

The AUX Voltage input measurements (M871 only) are similar to the phase voltages except they
do not have continuous DC removal. Both input-to-ground and input-to-input differential
voltages are measured. Because they do not have continuous DC removal, they can be used to
measure either AC or DC signals, making these measurements useful for Substation battery
monitoring, generator field voltages, local bus voltage measurements, etc.

The average of the 3 voltage phases ((Va + Vb + Vc)/3) is also available. The Average 3-phase
Volts for bus 1 and bus 2 are calculated and made available on a per cycle basis.

4.3 Power Factor (1-Cycle Update)

The per-phase Power Factor measurement is calculated using the "Power Triangle,” or the
per-phase WATTS divided by the per-phase VAs. The Total PF is similar, but uses the Total WATTS
and Total VAs instead. The sign convention for Power Factor is shown in Figure 7 (pg. 33). Note
that the Total PF calculation depends on the Total VA calculation type chosen (Section 4.4).

4.4 Watts / Volt-Amperes (VAs) / VARs (1-Cycle Update)

On any power connection type (2, 2-1/2, and 3 element), the M87x calculates per-element Watts
by multiplying the voltage and current samples of that element together. This represents the dot
product of the voltage and current vectors, or the true Watts. The per-element VAs are calculated
from the product of the per-element Volts and Amps. The per-element VARs are calculated from
fundamental VARs.

In any connection type, the Total Watts and Total VARs is the arithmetic sum of the per-element
Watts and VARs. The sign conventions are shown in Figure 7 (pg. 33).

31
M87x/EN M/O

When used on 2-element systems, the reference phase voltage (typically phase B) input, is
connected to the Neutral voltage input, and effectively causes one of the elements to be zero.
See Figure 9 (pg. 89-96) and Section 7 for input connection information. It is not required to use
any particular voltage phase as the reference on 2-element systems. When used on 2-element
systems the per-element Watts, VARs, and VAs have no direct physical meaning, as they would
on 2-1/2 and 3 element systems where they represent the per-phase Watts, VARs, and VAs.

When used on 2-1/2 element systems, one of the phase-to-neutral voltages is fabricated, as
described in Section 4.2. In all other respects, the 2-1/2 element connection is identical to the 3
element connection.

The M87x may be configured to calculate Total VAs in one of several different ways. The
calculation method may be selected either by sending a command to the M87x via a network
and protocol (refer to the specific protocol manual for details) or by using the 70 Series
Configurator. The three methods, Arithmetic, Geometric, and Equivalent (both for WYE and
DELTA), all yield the same results when used on balanced systems with no harmonics present.
The differences are illustrated below:

4.4.1 Geometric VA Calculations

2 2
GEOMETRIC
= VATOTAL WattsTOTAL + VARsTOTAL

This is the traditional definition of Total VAs for WYE or DELTA systems, and is the default method
for Total VAs calculation. The value of Total VAs calculated using this method does not change
on systems with amplitude imbalance, relative to a balanced system.

There is also a relationship to the Total Power Factor which is described in Section 4.3. Total
Power Factor calculations using the Geometric VA method will still indicate a "1" on a system with
phase amplitude imbalance, or canceling leading and lagging loads.

For example, on a system with a lagging load on one phase and an equal leading load on another
phase, the Geometric VA result will be reduced relative to a balanced system but the Total Power
Factor will still be "1".

4.4.2 Arithmetic VA Calculations

ARITHMETIC VATOTAL= (VA− N × I A ) + (VB − N × I B ) + (VC − N × I C )

The Arithmetic VA calculation is not applicable to DELTA connected systems. The value of Total
VAs calculated using this method also does not change on systems with amplitude imbalance,
relative to a balanced system. The value of Arithmetic VAs will not change on a system with
canceling leading and lagging loads.

There is also a relationship to the Total Power Factor, which is described in Section 4.3. Total
Power Factor calculations using the Arithmetic VA method will still indicate a "1" on a system with
phase amplitude imbalance, but not with canceling leading and lagging loads.

32
M87x/EN M/O

For example, on a system with a lagging load on one phase and an equal leading load on another
phase, the value of the Arithmetic VAs will not change relative to a balanced system, but the Total
Power Factor will be less than "1". The Total Power Factor calculated with Arithmetic VAs will
"see" the reactive elements in this system, while the Total Power Factor calculated with
Geometric VAs will not.

4.4.3 Equivalent VA Calculations

EQUIVALENT WYE VATOTAL


= VA2− N + VB2− N + VC2− N × I A2 + I B2 + I C2

VA2− B + VB2−C + VC2− A × I A2 + I B2 + I C2


EQUIVALENT DELTA VATOTAL =
3

The Equivalent VA calculation has not been as commonly used as other approaches, but has
been discussed extensively in technical papers. It is also referred to as "System Apparent Power".
This approach to the VA calculation may yield results which are surprising to those used to more
traditional methods. A system with amplitude imbalance will yield a greater value of Equivalent
VAs than a balanced system.

There is also a relationship to the Total Power Factor, which is described in Section 4.3.
Essentially, Total Power Factor calculations using the Equivalent VA method will not indicate a "1"
on any system unless the loads are purely resistive, and the amplitudes are balanced. Further,
the Equivalent VA method may yield better results in the presence of harmonics, where Total
Power Factor will also be reduced from "1". Refer to industry standards for more information.

4.5 Energy (1-Cycle Update)

Separate values are maintained for both positive and negative Watt-hours, positive and negative
VAR-hours, and VA-hours, (for each feeder in the M872). These energy quantities are calculated
every cycle from the Total Watts, Total VARs, and Total VAs, and the values are stored into non-
volatile memory every 15 seconds.

Energy values may be reset. All values are reset simultaneously. Refer to the appropriate
protocol manual for details.

33
M87x/EN M/O

4.6 Frequency (1-Cycle Update)

Frequency is calculated every cycle for every input but the Auxiliary Voltages. The M87x monitors
the change in Phase Angle per unit time using the Phase Angle measurement for the
fundamental generated by the FFT. The System Frequency is the frequency of the input used for
synchronizing the sampling rate (Section 3.2.2).

Figure 7 - Sign Conventions for Power Measurements

4.7 Demand Measurements (1-Second Update)

The traditional thermal demand meter displays a value that represents the logarithmic response
of a heating element in the instrument driven by the applied signal. The most positive value since
the last instrument reset is known as the maximum demand (or peak demand) and the lowest
value since the last instrument reset is known as the minimum demand. Since thermal demand
is a heating and cooling phenomenon, the demand value has a response time T, defined as the
time for the demand function to change 90% of the difference between the applied signal and
the initial demand value. For utility applications, the traditional value of T is 15 minutes, although
the M87x can accommodate other demand intervals (Section 4.7.7).

34
M87x/EN M/O

The M87x generates a demand value using modern microprocessor technology in place of
heating and cooling circuits, it is therefore much more accurate and repeatable over a wide
range of input values. In operation, the M87x continuously samples the basic measured
quantities, and digitally integrates the samples with a time constant T to obtain the demand
value. The calculated demand value is continuously checked against the previous maximum and
minimum demand values. This process continues indefinitely, until the demand is reset or until
the meter is reset (or power removed and reapplied). The demand reset and power-up algorithms
are different for each measurement. These routines are further described in following
paragraphs. The maximum and minimum demand values are stored in non-volatile memory on
the Host Processor module.

NOTE: Changing VT or CT ratios does NOT reset demand measurements to zero.

Demand Quantity Phase Reference Function


Amperes (1 & 2) Phase, Neutral, Residual Present, Max
Fundamental Amperes Phase, Neutral, Residual Present, Max
Volts (Bus 1 & 2) Phase - Neutral, Phase - Phase Present, Max, Min
Total Watts (1 & 2) Present, Max, Min
Total VARs (1 & 2) Present, Max, Min
Total VAs (1 & 2) Present, Max, Min
THD Volts (Bus 1 & 2) Phase - Neutral, Phase - Phase Present, Max
TDD Amperes (1 & 2) Phase, Neutral, Residual Present, Max

4.7.1 Ampere and Fundamental Ampere Demand

Present Ampere Demands are calculated via the instantaneous measurement data used to
calculate the per-phase Amperes.

Upon power-up, all Present Ampere Demands are reset to zero. Maximum Ampere Demands are
initialized to the maximum values recalled from non-volatile memory. Upon Ampere Demand
Reset, all per-phase Present and Maximum Ampere Demands are set to zero. When Ampere
Demands are reset, Fundamental Current Demands are also reset.

4.7.2 Volt Demand

Present Volt Demands are calculated via the instantaneous measurement data used to calculate
the per-phase Volts. Upon power-up all Present Volt Demands are reset to zero. The Maximum
Volt Demands and Minimum Volt Demands are initialized to the minimum and maximum values
recalled from non-volatile memory. In order to prevent the recording of false minimums a new
Minimum Volt Demand will not be stored unless two criteria are met. First, the instantaneous
voltage for that particular phase must be greater than 20Vrms (secondary). Second, the Present
Demand for that particular phase must have dipped (Present Demand value must be less then
previous Present Demand value). Upon Voltage Demand Reset, all per-phase Maximum Voltage
Demands are set to zero. Minimum Voltage Demands are set to full-scale.

35
M87x/EN M/O

4.7.3 Power Demands (Total Watts, VARs, and VAs)

Present Total Watt, VAR, and VA Demands are calculated via the instantaneous measurement
data. The Total VA Demand calculation type is based on the instantaneous Total VA calculation
type (Section 4.4)

Upon power-up, all Present Total Watt, VAR, and VA Demands are reset to the average of the
stored Maximum and Minimum values. The Maximum and Minimum Demands are initialized to
the minimum and maximum values recalled from non-volatile memory. Upon a demand reset,
the Maximum and Minimum Demands are set equal to the Present Total Watt, VAR, and VA
Demand values. A demand reset does not change the value of the Present Total Watt, VAR, and
VA Demands.

4.7.4 Voltage THD Demand

Present Voltage THD Demands are calculated via the instantaneous measurement data used to
calculate the per-phase and phase-to-phase Voltage THDs (Section 4.8.1). Voltage THDs are
calculated for both Bus 1 and Bus 2. By applying a thermal demand to the THD measurement,
the M87x provides a more effective method of determining the severity of a harmonic problem.

Upon power-up, all Present Voltage THD Demands are reset to zero. Maximum Voltage THD
Demands are initialized to the maximum values recalled from non-volatile memory. Upon
Harmonic Demand Reset, all per-phase Present and Maximum Voltage THD demands are set to
zero.

4.7.5 Current TDD Demand

Present Current TDD Demands are calculated via the instantaneous measurement data. By
applying a thermal demand to the TDD measurement, the M87x provides a more effective
method of determining the severity of a harmonic problem.

Upon power-up, all Present Current TDD Demands are reset to zero. Maximum Current TDD
Demands are initialized to the maximum values recalled from non-volatile memory. Upon
Harmonic Demand Reset, all per-phase Present and Maximum Current TDD demands are set to
zero.

4.7.6 Demand Resets

The demand values are reset in four groups: current, voltage, power, and harmonics. This can
be accomplished via a network and protocol (refer to the specific protocol manual for details).

4.7.7 Demand Interval

The M87x uses 15 minutes as the default demand interval, however it can be changed. Four
separate, independent demand intervals may be set for current, voltage, power, and harmonics.
The range of demand intervals is 5 to 3600 seconds (1hr). This can be accomplished via a network
and protocol (refer to the specific protocol manual for details) or by using the 70 Series
Configurator. While the Demand Interval is stored internally as a 32-bit number, some protocols

36
M87x/EN M/O

may place further restrictions on the Demand Interval due to limitations on numerical format.
Please refer to the appropriate protocol manual for details.

4.8 Harmonic Measurements (1-Cycle Update)

M87x instruments continually sample all inputs at 128 samples per cycle, and compute a 128-
point Fast Fourier Transform (FFT) every cycle for each input. When combined with high dynamic-
range input of up to 140APEAK and 600VPEAK, this allows the M87x to make extremely accurate
measurements of harmonics, regardless of crest factor. All harmonic and harmonic-based
values are calculated every cycle. Both magnitude and phase of each harmonic are provided.
In the following sections, Harmonic 0 indicates DC, Harmonic 1 indicates the fundamental, and
Harmonic N is the nth multiple of the fundamental.

4.8.1 Voltage Distortion (THD) (1-Cycle Update)

Voltage Harmonic Distortion is measured by phase in several 63


different ways. The equation for Total Harmonic Distortion (THD) is ∑ V h2
given in Equation 1. For Odd Harmonic Distortion, the summation = %THD h= 2
× 100%
only uses harmonics where h is odd. For Even Harmonic Distortion, V1
the summation only uses harmonics where h is even. Note the
denominator is the fundamental magnitude. For Individual
Harmonic Distortion there is no summation, only one component is Equation 1- Voltage
used in the numerator. THD

4.8.2 Current Distortion (THD and TDD) (1-Cycle Update)

Current Harmonic Distortion is measured by phase in several 63


different ways. The first method is Total Harmonic Distortion (THD). ∑ I h2
The equation for THD is given in Equation 2. For Odd Harmonic % =THD h= 2
× 100%
Distortion, the summation only uses harmonics where h is odd. For I1
Even Harmonic Distortion, the summation only
uses harmonics where h is even. Note the denominator is the
fundamental magnitude. Equation 2 - Current
THD
Alternatively, Current Harmonic Distortion can be measured as 63
Demand Distortion, as defined by IEEE-519/519A. Demand ∑ I h2
Distortion differs from traditional Harmonic Distortion in that the %=
TDD h =2
× 100%
denominator of the distortion equation is a fixed value. This fixed IL
denominator value is defined as the average monthly peak
demand. By creating a measurement that is based on a fixed value,
TDD is a "better" measure of distortion problems. Traditional THD is Equation 3 - Current
determined on the ratio of harmonics to the fundamental. While this TDD
is acceptable for voltage measurements, where the fundamental only varies slightly, it is
ineffective for current measurements since the fundamental varies over a wide range. Using
traditional THD, 30% THD may mean a 1 Amp load with 30% Distortion, or a 100 Amp load with
30% Distortion. By using TDD, these same two loads would exhibit 0.3% TDD for the 1 Amp load
and 30% TDD for the 100 Amp load (if the Denominator was set at 100 Amps). In the M87x,
Current Demand Distortion is implemented using Equation 3. The TDD equation is similar to
Harmonic Distortion (Equation 2), except that the denominator in the equation is a user-defined

37
M87x/EN M/O

number. This number, IL, is meant to represent the average load on the system. The denominator
IL is different for each phase and neutral, and is set by changing the four denominator values
within the M87x. Refer to the appropriate protocol manual for specific information.

Note that in Equation 3, if IL equals the fundamental, this Equation becomes Equation
2 - Harmonic Distortion. In the instrument this can be achieved by setting the denominator to
zero amps, in which case the instrument will substitute the fundamental, and calculate Current
THD. For Odd Harmonic Distortion, the summation only uses harmonics where h is odd. For Even
Harmonic Distortion, the summation only uses harmonics where h is even. For Individual
Harmonic Distortions there is no summation, only one component is used in the numerator.

Note that there is a separate, writeable denominator for each current input channel. The TDD
Denominator Registers are set by the factory to 5 Amps (primary), which is the nominal full load
of the CT input with a 1:1 CT. These writeable denominators can be used in conjunction with the
distortion measurements to obtain the magnitudes of harmonics, in other words, convert from
percent to amps. This is simply done by multiplying the percent TDD by the TDD Denominator for
that phase, and the result will be the actual RMS magnitude of the selected harmonic(s). This
technique can also be used if the THD mode (denominator set to zero) is used, by multiplying the
percent THD by the Fundamental Amps for that phase.

4.8.3 Fundamental Current (1-Cycle Update)

Fundamental Amps are the nominal component (50/60 Hz) of the waveform. The M87x measures
the magnitude of the fundamental amps for each phase and neutral. These measurements can
be used in conjunction with the distortion measurements to obtain the magnitudes of harmonics,
in other words, convert from percent to amps. As was mentioned previously, this is simply done
by multiplying the percent THD by the Fundamental Amps for that phase (which is the
denominator), and the result will be the actual RMS magnitude of the selected harmonic.

4.8.4 Fundamental Neutral Current (M871 Only) (1-Cycle Update)

The M871 measures the magnitude of the Fundamental Neutral Current, which is typically the
magnitude of the nominal component (50/60 Hz) of neutral current. The measurement is in
Amperes, and it is a measure of the load imbalance in a three-phase system.

4.8.5 Fundamental Voltage (1-Cycle Update)

Fundamental Volts are the nominal component (50/60 Hz) of the waveform. The M87x measures
the magnitude of the fundamental phase-to-neutral and phase-to-phase volts. These
measurements can be used in conjunction with the distortion measurements to obtain the
magnitudes of harmonics, in other words, convert from percent to volts. This is simply done by
multiplying the percent THD by the Fundamental Volts for that phase (which is the denominator),
and the result will be the actual RMS magnitude of the selected harmonic.

Fundamental Volts and Amps can be used in conjunction to obtain Fundamental VAs, and when
used with Displacement Power Factor can yield Fundamental Watts and Fundamental VARs.

4.8.6 Fundamental Watts / Volt-Amperes (VAs) / VARs (1-Cycle Update)

38
M87x/EN M/O

Fundamental Watt, VAR, and VA Demands are calculated analogous to the True Watts /
Volt-Amperes (VAs) / VARs of Section 4.4, but contain only information about the fundamental.
The Fundamental Total VA calculation type is the same as the True Total VA calculation type
(Section 4.4)

4.8.7 K-Factor (1-Cycle Update)


63
K-Factor is a measure of the heating effects on transformers,
and it is defined in ANSI/IEEE C57.110-1986. Equation 4 is used ∑ I h2 × h2
by the M87x to determine K-Factor, where "h" is the harmonic K − Factor = h=1 63 × 100%
number and "Ih" is the magnitude of the hth harmonic. K-Factor ∑ Ih2

is measured on each of the three phases of amps, however h=1

there is no "Total" K-Factor. K-Factor, like THD and PF, does not
Equation 4 - K-Factor
indicate the actual load on a device, since all three of these
measurements are ratios. Given the same harmonic ratio, the
calculated K-Factor for a lightly loaded transformer will be the same as the calculated K-Factor
for a heavily loaded transformer, although the actual heating on the transformer will be
significantly different.

4.8.8 Displacement Power Factor (1-Cycle Update)

Displacement Power Factor is defined as the cosine of the angle (phi) between the Fundamental
Voltage Vector and the Fundamental Current Vector. The sign convention for Displacement
Power Factor is the same as for Power Factor, shown in Figure 7 (pg. 33).

The Total Displacement Power Factor measurement is calculated using the "Power Triangle,” or
the three-phase Fundamental WATTS divided by the three-phase Fundamental VAs. The per-
phase Fundamental VA measurement is calculated from the product of the per-phase
Fundamental Amp and Fundamental Volts values. The three-phase Fundamental VA
measurement is the sum of the per-phase Fundamental VA values (Arithmetic VAs).

4.8.9 Phase Angle (1-Cycle Update)

The Phase Angle is calculated for the Bus 1 to Bus 2 per-phase Fundamental Voltages and
Fundamental Voltage to Fundamental Current. It is the Bus 1 Fundamental Voltage angle minus
either the Bus 1 Fundamental Current or Bus 2 Fundamental Voltage angle for a given phase.
Values are from -180 to +180 Degrees.

4.8.10 Resistance, Reactance, Impedance (1-Cycle Update)

These measurements are calculated for each phase from the fundamental values of voltage and
current. The Impedance value, combined with the voltage-to-current phase angle, gives the
polar form of the impedance. The Resistance and Reactance represent the rectangular form of
the Impedance.

4.8.11 Slip Frequency (1-Cycle Update)

The Slip Frequency is the difference in the Frequency of a phase of Bus 1 Voltage to Bus 2 Voltage.
Values are + when Bus 1 Frequency is greater.

39
M87x/EN M/O

4.8.12 Individual Phase Harmonic Magnitudes and Phase Angles (1-Cycle Update)

The M87x measures individual Harmonic Magnitudes and Harmonic Phase Angles for all
Currents, Line-to-Neutral Voltages, and Line-to-Line Voltages. The magnitudes are reported in
units of Amperes or Volts, not in percent. The Harmonic Phase Angles are in degrees, and all are
referenced to the Bus 1 VA-N Voltage, which places all Harmonic Phase Angles in a common
reference system. Values are from -180 to +180 Degrees.

4.9 Temperature (1-Second Update)

The M87x measures the internal temperature of the unit using a sensor located on the A10
Analog-Digital Signal processor Board. Values are reported in increments of 0.5C.

4.10 Symmetrical Components (1-Cycle Update)

For each three phase input, Voltage and Current, the M87x generates the positive-sequence,
negative-sequence, and zero-sequence vectors relative to phase A. These vectors represent the
symmetrical components of their respective busses. The sequence component vectors are
calculated by applying the vector operator a to the fundamental vectors of each phase
according to the following set of well-known equations:

Zero-sequence component (vector) E 0 = ( Ea + Eb + Ec) / 3


Positive-sequence component (vector) E1 = ( Ea + a * Eb + a * a * Ec) / 3
Negative-sequence component (vector) E 2 = ( Ea + a * a * Eb + A * Ec) / 3

Where a = cos(120°) + j * sin(120°) and Ea, Eb, and Ec are the fundamental vectors of a given bus.

The configuration parameter phase rotation, swaps the positive and negative sequence
components to accommodate installations with "CBA" phase rotation.

4.11 Supply Voltage and Current Unbalance (1-Cycle Update)

The supply voltage unbalance is evaluated from the symmetrical components, according to
EN61000-4-30:2003. In addition to the positive sequence component under unbalance
conditions, there also exists at least one of the following components: negative sequence
component u2 and/or zero sequence component u0.

The current unbalance is calculated similarly using the current components.

U2
Uu (%) = x100%
U1

4.12 Flicker

Flicker measurements are measured and evaluated according to IEC61000-4-15. Specific


settings for Flicker are found on the “Flicker” page (previously named "Power Quality" tab) of the

40
M87x/EN M/O

Configurator. The Nominal System Frequency should be selected appropriately for the system
in the ”Instrument Transformer Ratio” page (previously the "Advanced" tab) of the Configurator.

4.13 Fault Analysis

Fault location and fault type are determined using a single-ended impedance calculation that is
based upon an algorithm using measured values. Following below are the required line
parameters needed to be entered as well as the outputs obtained in the SOE log and for
protocols. Information on triggering and recording for fault location can be found in section
5.3.7.

4.13.1 Line Parameters

Line parameters for Bus 1 and Bus 2 may be entered independently in the Fault Location Line
Settings area of the 70 Series Configurator (version 2.43 and later). The magnitude and phase
angle of the direct line impedance, Zd (positive sequence), and the residual compensation
factor, kZ0, are required, where Zd is measured in ohms and
kZ0 = (Z0 – Zd) / 3Zd. The zero sequence impedance, Z0, is needed when doing the calculation. In
addition, the user may specify the line length and their preferred units of measure, in place of
per unit values (p.u.), for reporting distance in the SOE log.

4.13.2 Peak Current

When the Fault Analysis module is triggered, it will scan for the maximum fundamental current
values in the 10 cycles before and 20 cycles after the trigger point. The maximums for each of
Phase A, Phase B, Phase C, and Residual current are saved. The results are made available in
the SOE log and protocol registers as noted below. Additionally, the maximum of the three
phase (A, B, C) maximums is saved separately and made available via protocol.

4.13.3 Status Indication and Reset

The availability of measurement points indicating status and which ones can be reset are
indicated as follows:

Fault Type: One point representing the fault type is available on Mx71 (Two points on Mx72
models). The user is able to select Fault Type if it is of interest when creating a user-
configurable point list. The index number will be determined by where the point falls within the
point list. The Fault Type point value represents a set of packed bits. Bit0 represents A-Phase
Involved, Bit1 represents B-Phase Involved, Bit2 represents Phase-C Involved. All other bits (Bit3
– Bit15) always equal Zero. In that way:
(1) A-G fault is indicated by binary value of 1 (0001)
(2) B-G is binary 2 (0010)
(3) A-B is binary 3 (0011)
(4) C-G is binary 4 (0100)
(5) A-C is binary 5 (0101)
(6) B-C is binary 6 (0110)
(7) ABC is binary 7 (0111)

41
M87x/EN M/O

Targets: Four points representing targets are available on Mx71 (Eight points on Mx72 models).
The user will be able to select any of the points that are of interest when creating a user-
configurable point list. Index numbers will be determined by where the points fall within the
point list. Target Points: Fault Completed is set when the module has completed analysis. Fault
Target A, Fault Target B, and Fault Target C are set when their associated phases are involved
in the fault. Target points are single bit binaries. Possible values are 0 and 1.
Fault Counter: One point (Two points on Mx72 models) is available representing the number of
times the fault location algorithm has been triggered. The user will be able to select Fault
Count if it is of interest when creating a user-configurable point list. The index number will be
determined by where the point falls within the point list. The Fault Count point may be read as
a counter change object. This is intended to facilitate notification (via event polling) that the
value of the peak fault current has been freshly updated. The Fault Count Point simply
increments until it rolls over; it cannot be reset.
Target Resets: The above-mentioned Fault Completed point is available to permit the user to
reset targets once all data associated with a fault has been read. The user will be able to select
Reset Targets when creating a user-configurable point. The index number will be determined
by where the point falls within the point list. When the point is reset by writing a zero to it, the
Fault Type point and the Fault Target A,B,C points will be automatically set to zero as well.

Related points for Bus1, Mx72 model Bus2 points are similar:

4.13.4 SOELOG Output

The soelog will report the fault type and fault distance. Distance will be shown as “per unit,”
and in terms of the users preferred length units. For example, if the line length is defined as
100km the soelog entry might look like this:
24 30-Jul-2007 01:10:51.300206 Fault AB1 at 0.4949 of line or 49.49 km

4.13.5 Protocol Output

Configurable registers in Modbus and DNP may be used to view the results of the fault analysis
calculations and the peak fault current. The following measurements have been added:

Measurement Modbus DNP3

Fault Type Bus 1 Modbus register DNP Analog Input


Fault Distance XAN1 Modbus register DNP Analog Input
Fault Distance XBN1 Modbus register DNP Analog Input

42
M87x/EN M/O

Measurement Modbus DNP3

Fault Distance XCN1 Modbus register DNP Analog Input


Fault Distance XAB1 Modbus register DNP Analog Input
Fault Distance XBC1 Modbus register DNP Analog Input
Fault Distance XCA1 Modbus register DNP Analog Input
Fault Type Bus 2 Modbus register DNP Analog Input
Fault Distance XAN2 Modbus register DNP Analog Input
Fault Distance XBN2 Modbus register DNP Analog Input
Fault Distance XCN2 Modbus register DNP Analog Input
Fault Distance XAB2 Modbus register DNP Analog Input
Fault Distance XBC2 Modbus register DNP Analog Input
Fault Distance XCA2 Modbus register DNP Analog Input
Peak Fault Current IA1 Modbus register DNP Analog Input
Peak Fault Current IB1 Modbus register DNP Analog Input
Peak Fault Current IC1 Modbus register DNP Analog Input
Peak Fault Current IR1 Modbus register DNP Analog Input
Peak Fault Current Bus1 Modbus register DNP Analog Input
Peak Fault Current IA2 Modbus register DNP Analog Input
Peak Fault Current IB2 Modbus register DNP Analog Input
Peak Fault Current IC2 Modbus register DNP Analog Input
Peak Fault Current IR1 Modbus register DNP Analog Input
Peak Fault Current Bus2 Modbus register DNP Analog Input
Fault Target A1 DNP Binary Output
Fault Target B1 DNP Binary Output
Fault Target C1 DNP Binary Output
Fault Completed Bus1 Modbus register DNP Binary Output
Fault Count Bus1 Modbus register DNP Analog Input
Fault Target A2 DNP Binary Output
Fault Target B2 DNP Binary Output
Fault Target C2 DNP Binary Output
Fault Completed Bus2 Modbus register DNP Binary Output
Fault Count Bus2 Modbus register DNP Analog Input

The ‘fault type’ registers are a bit-field representation of which phases were driven by the event
system, and are the same information used to generate the faulted phase strings in the soelog.
Bit0 is A, Bit1 is B, Bit2 is C. The ‘fault distance’ registers are integer representations of the per-
unit distance, in DIV1000 or DIV100 format pending exact configuration implementation.

4.14 List of Available Measurements

Please note that not all measurements are available in every M87x model (i.e. neutral
current in M871 only, second set of current measurements and corresponding power,
energy, etc. only in M872)

43
M87x/EN M/O

Available Measurements
Accrued Digital IO Module #0-6, Input 1-16 K-factor Amps B (1 and 2)
Accrued Digital IO Module #0-6, Output 1-8 K-factor Amps C (1 and 2)
Accrued DR1/DR2 Active, Completed, Started K-factor Amps N
Accrued Pulse KWH, KVARH Positive (Bus 1 and 2) K-factor Amps Residual (1 and 2)
Accrued Pulse KWH, KVARH Negative (Bus 1 and 2) Log Interval
Accrued Virtual IO, Inputs 1-32, Outputs 1-32 Meter Type
Accrued WR1/WR2 Active, Completed, Started Misc. Packed Bits
Amps A, B, C, N, Residual (Feeder 1 and 2) Network Time Sync
Any Recorder Active Peak Fault Current Amps A, B, C, Residual, Bus (1 and 2)
Any Recorder Memory Full Phase Angle Amps A Harmonic (1…63 for 1 and 2)
Any Recorder Stored Phase Angle Amps B Harmonic (1…63 for 1 and 2)
Any Recorder Triggered Phase Angle Amps C Harmonic (1…63 for 1 and 2)
Avg. 3-phase Amps (1 and 2) Phase Angle Amps N Harmonic (1…63)
Avg. 3-phase Volts (1 and 2) Phase Angle Volts A Bus1-Bus2
Best Clock Phase Angle Volts A Harmonic (1…63)
Class 0 Response Setup Phase Angle Volts AB Harmonic (1…63)
CT Scale Factor Phase Angle Volts B Bus1-Bus2
CT Scale Factor Divisor Phase Angle Volts B Harmonic (1…63)
Demand (Max.) Amps A, B, C, N, Residual (1 and 2) Phase Angle Volts BC Harmonic (1…63)
Demand (Max.) Fund. Amps A, B, C, N, Resid. (1 and 2) Phase Angle Volts C Bus1-Bus2
Demand (Max.) TDD Amps A, B, C, N, Resid. (1 and 2) Phase Angle Volts C Harmonic (1…63)
Demand (Max.) THD Volts Bus1 AN, BN, CN, AB, BC, CA Phase Angle Volts CA Harmonic (1…63)
Demand (Max.) THD Volts Bus2 AN, BN, CN, AB, BC, CA Phase Angle Volts to Amps A (1 and 2)
Demand (Max.) VARs A, B, C, Total (1 and 2) Phase Angle Volts to Amps B (1 and 2)
Demand (Max.) VAs A, B, C, Total (1 and 2) Phase Angle Volts to Amps C (1 and 2)
Demand (Max.) Volts Bus1 AN, BN, CN, NG, AB, BC, CA Power Factor A, B, C, Total (Bus 1 and 2)
Demand (Max.) Volts Bus2 AN, BN, CN, NG, AB, BC, CA Power Factor Total Arithmetic (Bus 1 and 2)
Demand (Max.) Watts A, B, C, Total (1and 2) Power Factor Total Equivalent L-L (Bus 1 and 2)
Demand (Min.) THD Volts Bus1 AN, BN, CN, AB, BC, CA Power Factor Total Equivalent L-N (Bus 1 and 2)
Demand (Min.) THD Volts Bus2 AN, BN, CN, AB, BC, CA Power Factor Total Geometric (Bus 1 and 2)
Demand (Min.) VARs A, B, C, Total (1 and 2) Protocol Version
Demand (Min.) VAs A, B, C, Total (1 and 2) PT Scale Factor
Demand (Min.) Volts Bus1, AN, BN, CN, NG, AB, BC, CA PT Scale Factor Divisor
Demand (Min.) Volts Bus2, AN, BN, CN, NG, AB, BC, CA Pulse Status- Negative VArHrs (1 and 2)
Demand (Min.) Watts A, B, C, Total (1 and 2) Pulse Status- Negative WHrs (1 and 2)
Demand Amps A, B, C, N, Residual Pulse Status- Positive VarHrs (1 and 2)
Demand Fundamental Amps A, B, C, N, Residual Pulse Status-Positive WHrs (1 and 2)
Demand TDD Amps A, B, C, N, Residual Pulse VAR-Hrs Normal (1 and 2)
Demand THD Volts Bus1 AN, BN, CN, AB, BC, CA Pulse VAR-Hrs Reverse (1 and 2)
Demand THD Volts Bus2 AN, BN, CN, AB, BC, CA Pulse Watt-Hrs Normal (1 and 2)
Demand VARs A, B, C, Total Pulse Watt-Hrs Reverse (1 and 2)
Demand VAs A, B, C, Total Reactance A, B, C (1 and 2)
Demand Volts Bus1 AN, BN, CN, NG, AB, BC, CA Resistance A, B, C, (1 and 2)
Demand Volts Bus2 AN, BN, CN, AB, BC, CA Slip Freq. Volts A Bus1-Bus2
Demand Watts A, B, C, Total Slip Freq. Volts B Bus1-Bus2
Digital IO Module #0-6 Debounce Time Slip Freq. Volts C Bus1-Bus2
Digital IO Module #0-6 Input Point 1-16 SNTP Time Sync
Digital IO Module #0-6 Output Point 1-8 Symmetrical comp. of Bus 1 voltage (mag. and angle)
Digital IO Module #0-6 Status Output Point 1-8 Symmetrical comp. of Bus 2 voltage (mag. and angle)
Displacement Power Factor A, B, C (1 and 2) Symmetrical comp. of current (mag. and angle, 1 & 2)
Displacement Power Factor Total (1 and 2) System Frequency
Displacement Power Factor Total Arithmetic (1 and 2) Tag Register

44
M87x/EN M/O

Available Measurements
Displacement Power Factor Total Equivalent L-L (1 & 2) TDD Amps A, B, C, N, Residual (1 and 2)
Displacement Power Factor Total Equivalent L-N (1 & 2) TDD Denominator A, B, C, N (1 and 2)
Displacement Power Factor Total Geometric (1 & 2) TDD, Even, Amps A, B, C, Residual (1 and 2)
DNP Time Sync TDD, Odd, Amps A, B, C, Residual (1 and 2)
DR 1 Active Temperature
DR1 Memory Full THD Volts Bus1 AN, BN, CN, AB, BC, CA
DR1 Record Count THD Volts Bus2 AN, BN, CN, AB, BC, CA
DR1 Stored THD, Even, Volts Bus1 AN, BN, CN, AB, BC, CA
DR1 Triggered THD, Even, Volts Bus2 AN, BN, CN, AB, BC, CA
DR2 Active THD, Odd, Volts Bus1 AN, BN, CN, AB, BC, CA
DR2 Memory Full THD, Odd, Volts Bus2 AN, BN, CN, AB, BC, CA
DR2 Record Count Time Sync Error (μsec, msec, sec)
DR2 Stored Transducer Input Module # 1-7, Input Point 1-8
DR2 Triggered Trigger Derivative 1-120
DSP Version Unbalance Volts (1 and 2)
Factory Version Hardware Unbalance Amps (1 and 2)
Factory Version Software User Gain Amps A, B, C, N, Residual (1 and 2)
Fault Completed (Bus 1, Bus 2) User Gain Volts Bus1 A, B, C, N
Fault Count (Bus 1, Bus 2) User Gain Volts Bus2 A, B, C, N
Fault Distance AN, BN, CN, AB, BC, CA (Bus 1, Bus 2) User Gain Volts Bus2 Aux1-Gnd, Aux2-Gnd, Aux1-Aux2
Fault Target (A, B, C, Bus 1 and Bus 2) User Phase Correction Amps A, B, C, N, Residual (1 and
2)
Fault Type (Bus 1, Bus 2) User Phase Correction Volts Bus1 AN, BN, CN, NG, AB,
BC, CA
Flicker Short (PST VAN, VBN, VCN Bus 1 and 2) User Phase Correction Volts Bus2 AN, BN, CN, NG, AB,
BC, CA
Flicker Long (PLT VAN, VBN, VCN Bus 1 and 2) User Phase Correction Volts Bus2 Aux1-Gnd, Aux2-Gnd,
Aux1-Aux2
Frequency Amps A, B, C, Residual (1 and 2) VA/PF Calc. Type (1 and 2)
Frequency Volts Bus1 A, B, C VA-Hrs (1 and 2)
Frequency Volts Bus2 A, B, C VAR-Hrs Lag (1 and 2)
Fund. Amps A, B, C, N, Residual (1 and 2) VAR-Hrs Lead (1 and 2)
Fund. VAs Tot. Arith (1 and 2). VARs A, B, C, Total (1 and 2)
Fund. VAs Tot. Equiv. L-L (1 and 2) VAs A, B, C, Total (1 and 2)
Fund. VAs Tot. Equiv. L-N (1 and 2) VAs Tot. Arith. (1 and 2)
Fund. VAs Tot. Geom. (1 and 2) VAs Tot. Equiv. L-L (1 and 2)
Fund. VAs Total (1 and 2) VAs Tot. Equiv. L-N (1 and 2)
Fund. Volts Bus1 AN, BN, CN, AB, BC, CA VAs Tot. Geom. (1 and 2)
Fund. Volts Bus2 AN, BN, CN, AB, BC, CA Virtual Input Point 1-32
Harmonic, Individual, Amps A, B, C, N (1…63 for 1 & 2) Virtual Output Point 1-32
Harmonic, Individual, Bus1, Volts A (1...63) Volts Aux1-Gnd, Aux2-Gnd, Aux1-Aux2
Harmonic, Individual, Bus1, Volts AB (1...63) Volts Bus1 AN, BN, CN, NG, AB, BC, CA
Harmonic, Individual, Bus1, Volts B (1...63) Volts Bus2 AN, BN, CN, NG, AB, BC, CA
Harmonic, Individual, Bus1, Volts BC (1...63) Watt-Hrs Normal (1 and 2)
Harmonic, Individual, Bus1, Volts C (1...63) Watt-Hrs Reverse (1 and 2)
Harmonic, Individual, Bus1, Volts CA (1...63) Watts A, B, C, Total (1 and 2)
Harmonic, Individual, Bus2, Volts A (1...63) Waveform Status
Harmonic, Individual, Bus2, Volts AB (1...63) WV1/WV2 Active
Harmonic, Individual, Bus2, Volts B (1...63) WV1/WV2 Memory Full
Harmonic, Individual, Bus2, Volts BC (1...63) WV1/WV2 Record Count
Harmonic, Individual, Bus2, Volts C (1...63) WV1/WV2 Stored
Harmonic, Individual, Bus2, Volts CA (1...63) WV1/WV2 Triggered

45
M87x/EN M/O

Available Measurements
Health Xfmr Ratio Amps A, B, C, N, Residual (1 and 2)
Heartbeat Xfmr Ratio Future Use
Impedance A, B, C (1 and 2) Xfmr Ratio Volts Bus1 A, B, C, N
IrigB Time Sync Xfmr Ratio Volts Bus2 A, B, C, N
K-factor Amps A (1 and 2) Xfmr Ratio Volts Bus2 Aux1-Gnd, Aux2-Gnd, Aux1-Aux2

46
M87x/EN M/O

5.0 FUNCTIONAL DESCRIPTION

5.1 Passwords

The M87x has implemented the standard Bitronics password scheme. There are three different
access levels:

Level 0: This access level provides read-only access to all settings and data, thus preventing
modification of information that affects system security. The factory default password for level
0 is “AAAA”; this is the same as entering no password.

Level 1: This access level includes the read access of level 0. In addition, the user is permitted to
delete recorder files, and reset energy and demand values. The factory default password for
level 1 is “AAAA”; this is the same as entering no password.

Level 2: This access level includes all lower level functionality. The user is also granted full
read/write/delete access on all files in the M87x, including the configuration files. The factory
default password for level 2 is “AAAA”; this is the same as entering no password.

NOTE: The factory default is to allow level 2 access with no password. For the password scheme
to take effect, the user must change the passwords with the 70 Series Configurator.

5.2 Configuration

Setup of the M87x is most easily performed using the 70 Series Configurator. This software runs
on a PC and allows the PC to communicate to the M87x using a serial port or Ethernet connection.
The M87x configuration is stored internally by means of several configuration files, located in the
directory shown in the following table. Most of these are ASCII text files, and may be saved,
copied, and deleted by any of the various methods of file manipulation, such as FTP, Zmodem,
and the 70 Series Configurator.

If using IEC61850 protocol, the configuration of the IP and SNTP addresses will be determined
based upon a selection the user makes by way of the radio button selections found on the 70
Series Configurator Identity page. The radio buttons provide the user with the flexibility to
decide which software tool will control the IP and SNTP address configuration settings.
Configuration settings are loaded upon reboot from either the Initialization (INI) files or the
Micom Configuration Language (MCL) files, depending upon the radio button selected during
configuration. The IP and SNTP addresses will be loaded either from the respective address
settings stored in the INI file by the 70 Series Configurator or from the address settings stored in
the MCL file by the IEC61850 IED Configurator. Addresses written into the MCL file will be
written back into the INI file when the unit reboots. It is only possible to synchronize the
addresses by reading the address information written into the MCL file back into the INI file
upon reboot. (The IP and SNTP Addresses are rewritten to the INI file though the 70Series
Configurator upon reboot since the IEC61850 IED Configurator does not have the ability to
rewrite information once the configuration is written to the MCL file). There is a mechanism to
automatically sychronize these addresses upon rebooting the M87x, so that the current IP
address for the M87x will be updated on the 70 Series Configurator Identity page. For the case
when the radio button is selected as “IEC61850 IED Configurator (MCL file)” the IP networking
information will appear in grey indicating the IEC61850 IED Configurator is the active tool. Only

47
M87x/EN M/O

the 70 Series Configurator allows the user to select which configurator tool loads the IP and
SNTP addresses.

The configuration files are stored in the M87x directory c:\Config. The 70 Series Configurator will
generate the IED Capability Description (ICD) file and automatically store it on the M87x in
directory c:\Config. If using IEC61850 protocol 2 additional files, an MCL file and an MC2 file, will
be generated by the IEC61850 IED Configurator and will be stored on the M87x in the c:\Config
directory. The MCL files are the Micom Configuration Language files and contain the information
pertaining to the IEC61850 Configuration. The MCL file is stored as the active bank and contains
the IEC61850 configuration and the MC2 file becomes the inactive bank, containing the previous
IEC61850 configuration.

Filename Directory Description


c:\CONFIG\
COMM.INI Contains serial port information.
c:\CONFIG\
DEMANDS.INI Contains demand intervals.
c:\CONFIG\
DIO.INI Contains Digital I/O data, i.e. the Digital I/O debounce time.
c:\CONFIG\
DISPLAY.BIN Contains setup information for communicating with a remote display
c:\CONFIG\
DNP.BIN Contains DNP configurable register information
c:\CONFIG\
DR1.INI Contains setup information for Disturbance Recorder 1
c:\CONFIG\
DR2.INI Contains setup information for Disturbance Recorder 2
c:\CONFIG\ Contains CT/VT ratios, user gains and phase, harmonic denominators, and VA
DSP.INI calculation types.
c:\CONFIG\
IDENTITY.INI Contains Identity info, i.e. device name of M87x, IP address, NSAP address.
c:\CONFIG\
MODBUS.BIN Contains Modbus configurable register information
c:\CONFIG\
PROTOCOL.INI Contains Modbus, Modbus Plus, and DNP protocol setup information.
c:\CONFIG\
SBO.INI Contains UCA2.0 Select Before Operate parameters
c:\CONFIG\
SCALEFAC.INI Contains integer-to-floating point scale factor info for UCA.
c:\CONFIG\
TR1.INI Contains setup information for TR1 recorder.
c:\CONFIG\
VIO.INI Contains Virtual Input/Output setting information.
c:\CONFIG\
WR1.INI Contains Waveform Recorder 1 Configurator parameters
c:\CONFIG\
WR2.INI Contains Waveform Recorder 2 Configurator parameters
c:\CONFIG\
TRIGGER.INI Contains all trigger configuration info
c:\CONFIG\
MEASUSER.INI Contains user defined measurement names
c:\CONFIG\
VFT.INI Contains Voltage Fluctuation Table configuration
c:\CONFIG\
HARDWARE.INI Contains configured hardware info
c:\PERSIST\
SYS_CNFG.INI Contains hardware found by unit

There are also several ".BIN" files in the "c:\CONFIG\" directory which contain information on the
protocol register configuration for Modbus, Modbus Plus and DNP. These files are written by the
70 Series Configurator and are not editable by the user.

AFTER WRITING THE CONFIGURATION FILES, THE M87X MUST BE RESET (REBOOTED) BEFORE
THE NEW CONFIGURATION WILL TAKE EFFECT.

48
M87x/EN M/O

5.3 Triggering

Triggers can be configured in the 70 Series to initiate several different actions:

Waveform Recorders
Disturbance Recorders
Digital Outputs
Virtual Outputs
SOE Entries
Resetting of various measurements (Demands, Energy, etc.)

Up to 120 triggers can be specified, of the following types:

5.3.1 Threshold Trigger

Any measurement can be used to trigger a Waveform Recorder or Disturbance Recorder, or


create an entry in the SOE log. Configuring multiple triggers will cause a logical "OR" to be applied
to the list of triggers. The trigger thresholds are defined by the 70 Series Configurator. The user
specifies the measurement to use, the threshold value, the arithmetic function of the trigger, and
the hysteresis value.

If the measurement is an analog value (such as volts or amperes), the user may choose to trigger
on values greater than or less than the threshold. Additionally, the user may choose a rate-of-
change trigger greater than, less than, or equal to the threshold value. Rate-of-change intervals
are calculated over the interval since the measurement was last updated.

5.3.1a Trigger Hysteresis

Hysteresis is used to prevent chattering of contacts or unintended repeat-triggering of


recorders when a measurement fluctuates near the value where the action is intended to
occur. Refer to the Hysteresis column on the Recorder Triggers page of the 70 Series
Configurator program (below). The hysteresis setting is used to make the trigger occur and re-
initialized at different values. In the example below, since 60.3 Hz - 0.1 = 60.2 Hz, the action
takes place when frequency exceeds 60.3 Hz and re-initializes below 60.2 Hz. When hysteresis
is set to zero (default) the action triggers and resets at the same value.

49
M87x/EN M/O

Configuration of Hysteresis Settings

For example: Suppose an alarm contact is intended to close when the frequency exceeds 60.3
Hz. Frequency is generally regulated very tightly about 60 Hz, so except for the significant
transients that the setting is intended to capture, it would not be unusual for the frequency to
dwell for a prolonged time near 60.3 Hz, fluctuating by only an insignificant amount but
crossing the threshold many times (see illustration below, on the right half of the trace). To
eliminate this chatter, the user might configure the hysteresis to be 0.1 Hz, as shown above.
Then if the frequency were to rise from normal to the high frequency alarm range as illustrated
below, the contact will close exactly as it passes 60.3 and it will remain closed until the
frequency decreases below 60.2, when the contact opens.

The hysteresis function operates symmetrically when used with measurements that trigger
below a threshold. So for Event 2 shown in the 70 Series Configurator screen above, a trigger
would occur when the frequency drops below 59.7 Hz, and reset above 59.8 Hz.

Illustration of Trigger and Reset (or Operate and Release) when using Hysteresis

50
M87x/EN M/O

Hysteresis may be used to constrain chatter in any of the Actions listed on the Recorder Triggers
page (i.e. recorders, contacts, GOOSE messages, SOE Log entries, etc.) It may also be combined
with a setting in the “Min Duration (ms)” column to prevent triggering on short-duration transients
when a trigger might only be desired in connection with steady-state events; tap-changing for
voltage control for example.

5.3.2 Digital Input Trigger

A waveform or disturbance record or an SOE log entry can be triggered by using any of the digital
inputs on the Digital Input/Output Module (Section 9). Any or all of the digital inputs can be used
to trigger a record. Each input can be independently set to trigger on a state transition. Assigning
the digital inputs to initiate a record MUST be performed by using the 70 Series Configurator.

An event triggered from the digital inputs will be subject to the debounce time setting for the
digital input. Digital input traces in the Waveform Recorder files are the instantaneous status of
the inputs, and do not reflect any debounce time settings. If a long debounce time is set, it is
possible to see an event on the digital input that does not cause a trigger.

5.3.3 Edge and Level Triggers

The user can select between Edge and Level Triggers.

An Edge trigger exists for only an instant in time. The time before the trigger is defined the Pre-
trigger period, and the time after the trigger is the Post-trigger period.

A Level trigger has duration in time. The trigger is valid as long as the trigger condition is met.
The time before the trigger is still defined the Pre-trigger period, but the Post-trigger period does
not begin until after the trigger condition is no longer valid.

51
M87x/EN M/O

5.3.4 Manual Trigger

Refer to the appropriate protocol manual for information. Manual Triggers may also be activated
through BiView using Telnet, Zmodem, or under Modbus or DNP3 protocols (depending on what
register set/ point list is chosen). When a manual trigger is initiated, it bypasses the standard
trigger setup, and directly initiates the action specified by that command.

5.3.5 Logical Combinations of Triggers

Triggers can be logically combined in groups to perform actions. Each trigger is assigned to the
same Virtual Output in the Configurator, and the type of logic function (AND or OR) is selected.
That Virtual Output is then configured as a new trigger, with the appropriate action assigned. If
"No Logic" is selected, then only one trigger can be assigned to a particular Virtual Output.

5.3.6 Cross Triggering Multiple 70 Series Units (Inter-triggering)

Under certain circumstances, it is advantageous that a 70 Series device that captures a record,
also functions in a capacity to send out a pre-determined trigger condition. That trigger
condition, which is based on values measured by the instrument, can be used for the purpose
of cross triggering (also referred to as inter-triggering) other 70 Series devices. Cross triggering
is an essential requirement for synchronizing the equipment in a substation, where it is
necessary that multiple instruments sense the occurrence of particular conditions

There are a number of ways to accomplish cross triggering across 70 Series devices. The cross
triggering mechanism can be accomplished by way of a physical interconnection using Digital
I/O, or by way of virtual messaging, which is communicated over an Ethernet network
connection. Refer to Appendix A for examples of setting up cross triggering through either
Digital I/O connections, GSSE messaging [through UCA], or GOOSE messaging [through
IEC61850].

A P30 or P31 module is necessary to set up cross triggering using a Digital I/O interconnection
method. An Ethernet option module is necessary in order to set up either GSSE messaging
[through UCA] or GOOSE messaging [through IEC61850].

Units may both send and receive cross triggers from and to multiple other units.

5.3.7 Fault Distance Triggers

Fault distance calculations are initiated as an action from the configurable Triggers. For a
chosen trigger, select the Fault Distance checkbox, and then the associated phase from the
dropdown box. A simple limit trigger such as RMS Amps A 1 > 2000 can be set to calculate an
A1 fault. Similarly, the Digital Inputs can be used to drive the calculations when connected to
the outputs of a protection device. More complex conditions can be specified with the use of
logic functions. For example:

52
M87x/EN M/O

Here, the first three conditions are logically “anded” together to drive Virtual Output 2. VO2, in
turn, is configured to initiate a fault distance calculation on B1. Line to line fault distances are
calculated when more than one of the A1, B1, C1 events are triggered.

5.3.8 Periodic Triggers

Four independent periodic triggers are available that can be used to initiate all of the actions
listed in section 5.3 above. The timers for these triggers are configured to individually set the
period and start time for each trigger on the Timers page of the 70 Series Configurator as shown
below:

The period can be set in increments of minutes up to a maximum of 24 hours. Likewise, the
time of day for the timer to start can be specified in increments of one minute.

Note that if the number of minutes in a day is not evenly divisible by the configured period, then
the start time has little impact except at boot up. For example, if the period is configured for 7hrs
and the start time is 0430hrs then the first day after the device starts the timer will activate at
0430hrs, 1130hrs, 1930hrs. And then on the second day, it will activate at 0230hrs, 0930hrs,
1630hrs, 2330hrs., etc.

The activation status of the timers is available as a binary point in the list of 'Measurements to
Trigger On' in the Recorder Triggers page (see screen below). The point will transition from 0 to

53
M87x/EN M/O

1 at the timers scheduled activation. It will hold at 1 briefly and then return to 0. These
'Periodic Trigger' points can then be used to trigger any of the actions selected.

5.4 Recording

The M87x has five different methods of recording data. High-speed samples of the input signal
are captured and stored by the two Waveform Recorders, slower-speed measurement data is
stored by the two Disturbance Recorders, long-term load-profile data is stored by the Trend
Recorder, and a voltage fluctuation table (VFT) and a sequence of event (SOE) log can be
created as well.

The Waveform Recorders save the actual samples from the input channels, as well as from the
Digital I/O modules. The two Disturbance Recorders log values at a user configurable rate of 1-
3600 cycles. The Trend Recorder logs values at a user configurable rate of 1 minute -12 hours.
The VFT file records voltage values when pre-selected thresholds are passed, and the SOE file
creates a summary of events in the order they occur.

The Waveform and Disturbance records and the VFT and SOE files are created based on event
conditions. Unlike these other recorders, the trend recorder is not based on triggered
conditions but instead runs constantly when selected to record.

5.4.1 Waveform Recorder

A waveform record can be triggered by a measurement exceeding an upper or lower threshold,


by a manual protocol command, or by a digital or virtual input channel changing state. When a
trigger condition is met, a record is created that contains samples from the input channels. The
waveform record normally contains 20 cycles of pre-trigger and 40 cycles of post-trigger
information. The pre- and post- trigger times are configurable by the user. If additional triggers
occur within the post-trigger period, the waveform record will be extended for the selected
number of post-trigger cycles. Optionally, the user can choose to disable re-triggering.

54
M87x/EN M/O

There is a limit of 2000 cycles (approximately 33.3 seconds at 60Hz) for each waveform record.
(Prior to The M87x will continue to record waveforms until the memory allocated for the
Waveform Recorder is full. Regardless of the number of records stored, if sufficient memory
exists for the designated number of pre-trigger cycles the M87x will create a new record,
although it may not be full-length.

When selecting the COMTRADE File Type for the Configuration settings in the Waveform
Recorder, the user should be aware that certain processing limitations may be encountered
that can result in data loss for a waveform record.

If the host processor encounters large amounts of data due to creating long length waveform
records and is otherwise overloaded with performing other tasks, the data in the queue may be
overwritten before it could be written onto the Flash drive. This is a possibility that may be
encountered when attempting to handle an excessive volume of data, which may not be
handled adequately by the host processor. To reduce the possibility of this occurring especially
during the processing of large amounts of data, it is a good practice to tailor the selection of
the COMTRADE File Type based on the desired length of the file to be recorded. As a guideline
when configuring the waveform recorder, the following are useful recommendations: a Binary
COMTRADE File Type used along with a lower sample rate is better for recording longer length
waveform files; an ASCII COMTRADE File Type is better suited for recording short length
waveform files. Binary format will generate smaller data files then ASCII format. A higher
sample rate can be more useful when recording short files. Use the lowest sample rates
possible when capturing long waveform records.

If the post trigger times appear to be truncated in the COMTRADE file, that would suggest that
the user adjust the waveform recorder’s configuration settings, accordingly. This will usually
alleviate the issues associated with recording long length waveform files.

The Waveform Recorders share storage space with the Disturbance Recorders and the Trend
Recorder. The 70 Series Configurator allows the user to select the maximum available memory
for each recorder function. Note that if the user wishes to change the allocation of memory
among the recorders after recordings have already been made, it is necessary to first
remove the existing files from memory before making any change.

Waveform records are presented in industry standard (IEEE C37.111-1999) Comtrade files
which are stored as compressed .zip files. Waveform records may be retrieved and deleted
from the instrument using the available communications protocols. Please refer to the specific
protocol manual or section 5.5 (Zmodem and FTP) for details. A file cannot be deleted while
being read by another device.

The following table shows the signals that are included in the waveform record. The user can
select a sampling rate of 32, 64 or 128 samples per cycle for all signals on all Mx7x models. An
additional, higher sampling rate of 256 samples per cycle is available when using the M571 or
the M871 models (excludes M572 and M872). Please note, however, that selecting the 256
sample per cycle sampling rate disables all measurements associated with bus 2 voltages
(Volts A2, B2, and C2) and auxiliary voltages (Volts Aux1-Gnd, Aux2-Gnd, and AuxDiff). Because
the sampling rate is synchronized with the system frequency, the sample rate (in samples per

55
M87x/EN M/O

second) will vary with frequency. Note that for M87x units, when a Digital Input from any
module is selected, a total of 16 digital inputs will be added to the Waveform file.

Comtrade Trace WYE Definition DELTA Definition (shown with Phase B


Voltsb 1l A Voltage Bus 1 Phase A to Neutral Voltage Bus 1 PhasefA to B1 )
Volts 1 B Voltage Bus 1 Phase B to Neutral Always = 01
Volts 1 C Voltage Bus 1 Phase C to Neutral Voltage Bus 1 Phase C to B1
Amps 1 A Amps 1 Phase A Current Amps 1 Phase A Current
Amps 1 B Amps 1 Phase B Current Amps 1 Phase B Current
Amps 1 C Amps 1 Phase C Current Amps 1 Phase C Current
Amps N Phase N Current Phase N Current
Volts 2 A Voltage Bus 2 Phase A to Neutral Voltage Bus 2 Phase A to B1
Volts 2 B Voltage Bus 2 Phase B to Neutral Always = 01
Volts 2 C Voltage Bus 2 Phase C to Neutral Voltage Bus 2 Phase C to B1
Amps 2 A Amps 2 Phase A Current Amps 2 Phase A Current
Amps 2 B Amps 2 Phase B Current Amps 2 Phase B Current
Amps 2 C Amps 2 Phase C Current Amps 2 Phase C Current
Aux In 1 Voltage Aux 1 to Ground Voltage Aux 1 to Ground
Aux In 2 Voltage Aux 2 to Ground Voltage Aux 2 to Ground
Dig In 0 1 - X Digital Input Module 0 input 1 - X Digital Input Module 0 input 1 - X
Dig In 1 1 - X Digital Input Module 1 input 1 - X Digital Input Module 1 input 1 - X
Dig In 2 1 - X Digital Input Module 2 input 1 - X Digital Input Module 2 input 1 - X
Dig In 3 1 - X Digital Input Module 3 input 1 - X Digital Input Module 3 input 1 - X
Dig In 4 1 - X Digital Input Module 4 input 1 - X Digital Input Module 4 input 1 - X
Dig In 5 1 - X Digital Input Module 5 input 1 - X Digital Input Module 5 input 1 - X

1When the M87x is used on a DELTA (2-element system), one of the Phase Voltage inputs will be connected to the
Neutral Voltage input, and that Phase-to-Neutral voltage will then be zero. The remaining two Phase-to-Neutral
voltages then become Phase-to-Phase voltages. The reference phase does not have to be Phase B.

5.4.1a Default Frequency Setting for Waveform Recorder

The Nominal System Frequency should be selected appropriately for the system in the
“Instrument Transformer Ratio” page (previously the "Advanced" tab) of the Configurator.
Normally the unit will modify the sample rate to track the frequency of any CT or VT signal
present. However, if there are no signals available for frequency tracking, the unit will default
to the Nominal System Frequency setting.

5.4.1b Indicating Waveform Records with Digital Outputs

Any of the outputs on the Digital Input / Output Module can be configured to indicate the status
of the recorder. Recorder status includes: Recorder Started, Recorder Completed, Recorder
Memory Low, and Recorder Active. When a waveform record is created, the assigned output
relay will be energized. When an output relay is assigned to indicate the presence of a
waveform record, it can no longer be controlled via protocol commands. If power is removed
from the M87x, the relay will revert to the default state. Assigning the digital outputs to
indicate that a waveform record has been created must be performed by using the 70 Series
Configurator. See Section 9 for information concerning output "Normally Open" and "Normally
Closed" settings.

56
M87x/EN M/O

The indication of the status of a waveform record will persist until cleared, except for Recorder
Active, which will reset when the recording is finished. Refer to the appropriate protocol
manual for instructions.

5.4.1c Retrieving and Deleting Waveform Recorder Files

Waveform records may be retrieved and deleted from the instrument using the available
communications protocols. Please refer to the specific protocol manual or section 5.5
(Zmodem and FTP) for details. A file cannot be deleted while being read by another device.

5.4.2 Disturbance Recorders

The M87x includes two individually configurable Disturbance Recorders. The most common
method of triggering a disturbance event is by using the 70 Series Configurator to set an upper
or lower threshold on one of the measurements. A disturbance record can also be initiated by
a digital input or by a protocol-specific manual command. (See protocol manual for details on
available commands.)

The Disturbance Recorder will archive samples of up to 64 user-selected measurements. Any


measurement made by the device may be selected, allowing the user a great deal of flexibility
in configuring the system. Additionally, the user may configure the Disturbance Recorder to
calculate the min/max/avg of the selected measurements over the interval, or store only the
present value at the end of the interval.

The number of disturbance records that can be stored is dependent on the number of
measurements to record, the measurement type, and the number of pre- and post-trigger
samples selected.

57
M87x/EN M/O

Please note how the convention for determining time resolution in oscillography records (WR1,
WR2) in samples per cycle is not relevant to long-time disturbance records (DR2, DR2), where RMS
values are plotted using a sample rate measured in an integer number of cycles for each sample.

If the number of cycles/sample is set to 1, each entry in the Disturbance Record will reflect data
collected over one cycle. The factory default setting provides 20 samples of pre-trigger
recording and 40 samples post-trigger. The pre- and post- trigger times are configurable by
the user, as is the number of cycles per sample. The maximum pre-trigger time is 1800
samples, while the maximum post-trigger time is 300,000 samples. If additional triggers occur
within the post-trigger period, the disturbance record will be extended by the selected number
of post-trigger samples. Optionally, the user can choose to disable re-triggering. The default
cycles/sample setting is 0, which disables the recorder.

The Disturbance Recorders shares storage space with the Waveform Recorder and the Trend
Recorder. The 70 Series Configurator allows the user to select the maximum available memory
for each recorder function, but any record files already made should be removed before
reallocating the memory as mentioned above in the Waveform Recorder section.

Disturbance records are presented in industry standard (IEEE C37.111-1999) Comtrade files
stored as compressed .zip files. Disturbance records may be retrieved and deleted from the
instrument via a network and protocol (refer to the specific protocol manual for details), or by
using the Host Module serial ports and Zmodem (Section 5.5.2).

5.4.2a Indicating Disturbance Records with Digital Outputs

Any of the outputs on the Digital Input / Output Module can be configured to indicate the status
of the recorder. Recorder status includes: Recorder Started, Recorder Completed, Recorder
Memory Low, and Recorder Active. When a waveform record is created, the assigned output
relay will be energized. When an output relay is assigned to indicate the presence of a
disturbance record, it can no longer be controlled via protocol commands. If power is removed
from the M87x, the relay will revert to the default state. Assigning the digital outputs to
indicate that a disturbance record has been created must be performed by using the 70 Series
Configurator. See Section 9 for information concerning output "Normally Open" and "Normally
Closed" settings.

The indication of the status of a waveform record will persist until cleared, except for Recorder
Active, which will reset when the recording is finished. Refer to the appropriate protocol
manual for instructions.

5.4.2b Retrieving and Deleting Disturbance Recorder Files

Disturbance records may be retrieved and deleted from the instrument using the available
communications protocols. Please refer to the specific protocol manual or section 5.5
(Zmodem and FTP) for details. A file cannot be deleted while being read by another device.

5.4.3 Trend Recorder

58
M87x/EN M/O

The M87x stores the values of a user-configurable set of up to 230 parameters every log interval.
The default setting of this interval is 0 minutes, which disables the Trend Recorder. This interval
can be changed from 1 to 720 minutes (12 hrs.) in 1-minute increments. Once the log file has
reached its maximum length, it will wrap around to the beginning and overwrite the oldest entries
in the file. The log file is stored in non-volatile memory, allowing for retrieval of a complete log
file even after power has been cycled to the instrument.

The user may select between recording the instantaneous values only, or storing the minimum,
maximum, and average values recorded during the previous interval. The recorded values are
based on measurements that are updated every cycle.

Trend Recording is always started at the closest time that is an integral multiple of the log interval.

Example:
If the trend interval is set to 15 minutes and the M87x system clock time is 9:18, the first entry will
occur at 9:30. Subsequent entries will be made at 15-minute intervals. If the trend interval is
changed to 5 minutes at 9:37, the next entry will occur at 9:40. Subsequent entries will occur at
5-minute intervals.
For intervals less than 60 minutes, it is recommended that the trend interval be set to a number
that will evenly divide 60 minutes. If the interval is greater than 60 minutes, it should evenly divide
24 hours.

Recommended intervals:
1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 minutes
1, 2, 3, 4, 6, 8, 12 hours

NOTE: If the System Clock setting (Section 3.1.3) is to be changed backwards, it is recommended
that all trend recorder files be retrieved, the time changed, and the trend recorder file be
deleted. If this is not done, the file will effectively contain a section that shows time going
backwards! This will cause problems with the Comtrade file format.

5.4.3a Retrieving Trend Records

The trend file is stored on the unit in a proprietary data format. BiView or the Retriever program
(supplied on the Utilities CD) is required to download & convert the raw trend file stored on the
unit into an industry standard Comtrade file. When downloading the raw file via BiView or
Retriever, the trend file on the unit will automatically be deleted; however both programs will
preserve a copy of the raw trend file on the PC and append the new data every time the trend
file is downloaded.

5.4.4 Comtrade Format

Waveform and Disturbance Records are available in Comtrade file format (C37.111-1999) and
Trend Records can be converted into this format when retrieved using BiView or Retriever
software programs. These are user-selectable binary or ASCII format files. The files are stored
as compressed .zip files to increase storage and decrease user download times. These files may
be retrieved and deleted from the instrument using the available communications protocols.

59
M87x/EN M/O

Please refer to the specific protocol manual or section 5.5 (Zmodem and FTP) for details. A file
cannot be deleted while being read by another device.

The Waveform Recorder file "WR1_nnnn.CFG" or "WR2_nnnn.CFG" will contain the event
parameters including the names of the channels, time of start of file, time of trigger, and
sampling frequency for each cycle. The file "WR1_nnnn.DAT” or "WR2_nnnn.DAT" contains the
time of each sample and the data. The data values are integers and can be scaled back to
primary units using the scale factors in the .CFG file. The file name format, "WR1_nnnn.CFG"
and "WR1_nnnn.DAT,” indexes automatically from "WR1_0001.xxx" to "WR1_9999.xxx".
Similarly, Waveform Recorder 2 files will be stored as "WR2_nnnn.CFG" and "WR2_nnnn.DAT".

Upon power-up (or re-boot), the M87x notes the highest index number in memory, and will
increment by one for the next file. If there are no waveform records, the next one will be
WR1_0001. If there is a WR1_0034 in memory upon re-boot, the next file will be WR1_0035. Note
that if the stored files are deleted, but the M87x is not re-booted, it will continue to index in
sequence as if the files were still there.

The Disturbance Recorder stores files in the same manner as the Waveform Recorder. Files from
Disturbance Recorder 1 will be saved as "DR1_nnnn.CFG" and "DR1_nnnn.DAT,” with the same
indexing sequence as the waveform files. Similarly, Disturbance Recorder 2 files will be stored as
"DR2_nnnn.CFG" and "DR2_nnnn.DAT".

The Trending file "TR1.CFG" will contain the event parameters, including the names of the
channels, time of start of file, and trend interval for each measurement. The file "TR1.DAT"
contains the time of each sample and the data. The data values are integers and can be scaled
back to primary units using the scale factors in the .CFG file.

5.4.4a Comtrade ZIP Files

The .CFG and .DAT files are combined into a single .ZIP file, which is placed in the c:\DATA\ or
e:\DATA directory (see section 5.5). This file may be retrieved using FTP, Zmodem, or protocol
specific file transfer methods. Note that the .ZIP file may take up to 1 minute to appear in the
c:\DATA\ directory after the records are created.

5.4.5 IEEE Long File Naming Convention

The 70 Series IEDs are capable of creating record files that meet the IEEE C37.232-2007
standard for file names. The long filename feature is enabled and configured on the Identity
Page of the 70 Series Configurator. The Identity Page is shown below with factory default
values. Settings relevant to long filename configuration are highlighted in green.

60
M87x/EN M/O

When the long filename feature is enabled, the Disturbance Recorder and Waveform Recorder
functions of the IED will create IEEE C37.232-2007 compatible names for all generated
Comtrade files. Note, that in all cases the IED compresses and stores Comtrade files within a Zip
file. Generation of Comtrade files for the Trend Recorder function is handled by the BiView
software application. BiView retrieves the Trend Recorder data and the Identity configuration
from the IED and then converts to a Comtrade file. BiView will use the long filename
configuration obtained from the IED.
IEEE C37.232-2007 defines the following disallowed characters: ? “ / \< > * | : ; [ ] $ % { } (i.e.,
question mark, quotation mark, forward slash, backward slash, less than, greater than, asterisk,
pipe, colon, semi-colon, brackets, dollar sign, percent, and braces). The 70 Series Configurator
permits the use of these characters on the Identity Page, but they will be replaced with an
underscore (_) in the resulting long filename. Note, the use of periods (.) and commas (,) while
permitted by IEEE C37.232-2007 and properly handled by the 70 Series Configurator, may
produce unexpected results when interpreted by a third party software application.

IEEE C37.232- Source Notes


2007 Field
Start Date Comtrade 'Start Time' from CFG file
Start Time Comtrade 'Start Date' from CFG file
Time Code Always zero No time zone offset
Station ID Identity page 'Station Name' Limited to 32 characters
Device ID Identity page 'Device Description' Limited to 32 characters
Company Name Identity page 'Company Name / Owner' Limited to 32 characters

User 1 Identity page 'Location' Limited to 64 characters

61
M87x/EN M/O

User 2 Original Zip file name Such as DR1_0010 or


WR2_0003
Extension CFG or DAT

5.4.6 Voltage Fluctuation Table (VFT) File

The 70 Series IEDs are capable of creating a VFT file, which is used in conjunction with an external
software package for monitoring Sags and Swells.

The raw data for each voltage channel is derived from 1 cycle RMS values that are updated
each quarter cycle.

Each table contains one bus of voltages, phases A, B, & C


For units that have two buses of volts, two separate tables will be created. This currently
includes M871, M571, M872 Breaker & a Half, and M572 Breaker & a Half.
Reference voltages will not be recorded in the table; therefore the M872 Dual Feeder & M572
Dual Feeder will only have 1 table.
The 70 series will maintain the minimum and maximum value for each voltage channel. When
the voltage for a channel crosses a user configured threshold an entry will be made in the
table. The user can configure up to 30 thresholds but a minimum of 3 thresholds must be
configured. The default configuration for the thresholds are:
- 110% of Nominal
- 90% of Nominal
- 1% of Nominal

A fixed value of 1% of nominal will be used for the hysteresis.


For Dips & Interruptions, the threshold is passed going down on the value the user specifies. On
the way up, the threshold is passed at the value + 1% nominal.

62
M87x/EN M/O

For Swells, the threshold is passed going up on the value the user specifies. On the way down,
the threshold is passed at the value – 1% nominal.

The Voltage Fluctuation Table consists of 2 files:.


- VFTn.DAT
- VFTn.INI
Where n is the number of the bus. Currently n may be 1 or 2.
The DAT file is a text file with one entry per line. Each data value is separated by a semicolon.
The order of the data values is
- Entry Number
- Time Tag seconds
- Time Tag milliseconds
- Phase Code
- Minimum Value
- Maximum Value
- Current value, that has passed threshold
- Voltage Ratio
- Ratio Offset

An example of 1 line
1803;351009204;335;20001002;55.734;55.734;79.932;1.0;0.0

The DAT file will be allowed to grow to 100K. This will result in proximally 1700 entries.

Due to flash drive limitations, the M87x can only have a finite number of entries. To prevent the
file from growing too large, and ensure the newest data is always available, the M87x
overwrites the oldest entry as needed.
Because the DAT file will be circular it will have a virtual end of file marker, thus making it easy
to see where the oldest entry is. The end of file marker will be “**** End of File ****” with out the
quotes, and it will be on a line by itself.

A new “Voltage Fluctuation Thresholds” page in the 70 Series Configurator was created that
allows the user to configure the Voltage Fluctuation Table. The user has the following options
for each bus.

Enable/Disable the Voltage Fluctuation Table


Set the nominal voltage in primary units
Set the thresholds (can have 3-30 thresholds) entered in % of nominal

The files for the Voltage Fluctuation Table are available to download via Ethernet or Serial ports
using BiView, Retriever, Internet Explorer, and HyperTerminal, Zmodem, FTP. The files are not
available via Modbus File Transfer.

5.4.7 Sequence of Events (SOE) File

63
M87x/EN M/O

The M87x creates a record, in chronological order, of all events that occur, including:

Triggers
Health Check status errors
Change of state of status inputs and outputs
Creation of files
Change of configuration
Setting of clock
Record of Boot up

The SOE.LOG file is an ASCII text format file, and typically can be up to 5000 lines.

5.4.8 Sequence of Events Recorder (SER) File

In addition to the SOE file mentioned above, the M87x creates a SER log in .csv format for
compliance with one portion of the NERC PRC-002-2 standard. Following is a summary of what
is included:

A. File Name: SERLOG.CSV


B. File Type: comma separated variable (ASCII)
C. The following single input types are automatically logged to the SERLOG.CSV file if the
"Soe Entry" field is selected on the Recorder Triggers page:
1. Digital Inputs
2. Virtual Inputs
3. GOOSE Inputs

D. One log entry per line where each line is comprised of the following fields:
1. line number
2. date
3. time (rounded to the nearest millisecond)
4. local time code (currently unimplemented, always reads as zero)
5. Substation name (populated with "Station Name" field on Identity page)
6. Device name (populated with "User Defined Measurement Name" on the User
Defined Measurement Names page. The Default Measurement Name will be
used if no User defined name exists)
7. State (populated with "SOE Message field" from the Triggers page associated with
the specific trigger point. If no SOE Message is specified then the field will be
populated with "0" for trigger with "value" field set to 0, and "1" for triggers with
"value" field set to 1)

The following is an example of the contents of the SERLOG.CSV file:


1, 02/08/17, 09:54:13.166, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), 0
2, 02/08/17, 09:55:39.811, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), 1
3, 02/08/17, 09:55:42.638, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), 0
4, 02/08/17, 09:55:45.642, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), 1
5, 02/08/17, 09:55:46.402, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), 0
6, 02/08/17, 10:01:02.342, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), Close
7, 02/08/17, 10:19:50.882, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), ___Open___
8, 02/08/17, 10:19:53.798, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), Close
9, 02/08/17, 10:37:26.855, 0, Hinkson_Creek_substation, DIO#0 Input 1, Close
10, 02/08/17, 10:37:26.859, 0, Hinkson_Creek_substation, DIO#0 Input 2, 0

64
M87x/EN M/O
11, 02/08/17, 10:37:26.863, 0, Hinkson_Creek_substation, DIO#0 Input 3, 0
12, 02/08/17, 10:37:26.863, 0, Hinkson_Creek_substation, DIO#0 Input 4, 0
13, 02/08/17, 10:37:26.863, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 0
14, 02/08/17, 10:37:26.876, 0, Hinkson_Creek_substation, Breaker 6 (DIO_0 Input6), 0
15, 02/08/17, 10:37:26.880, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), _OPEN_
16, 02/08/17, 10:37:26.880, 0, Hinkson_Creek_substation, Breaker 8 (DIO_0 Input8), 0
17, 02/08/17, 10:38:09.217, 0, Hinkson_Creek_substation, Breaker 6 (DIO_0 Input6), 1
18, 02/08/17, 10:38:09.256, 0, Hinkson_Creek_substation, Breaker 6 (DIO_0 Input6), 0
19, 02/08/17, 10:38:09.443, 0, Hinkson_Creek_substation, Breaker 6 (DIO_0 Input6), 1
20, 02/08/17, 10:38:09.577, 0, Hinkson_Creek_substation, Breaker 6 (DIO_0 Input6), 0
21, 02/08/17, 10:38:18.439, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 1
22, 02/08/17, 10:38:18.523, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 0
23, 02/08/17, 10:38:18.585, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 1
24, 02/08/17, 10:38:18.586, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 0
25, 02/08/17, 10:38:18.588, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 1
26, 02/08/17, 10:38:18.590, 0, Hinkson_Creek_substation, Breaker 5 (DIO_0 Input5), 0
27, 02/08/17, 10:38:19.455, 0, Hinkson_Creek_substation, DIO#0 Input 2, 1
28, 02/08/17, 10:38:19.615, 0, Hinkson_Creek_substation, DIO#0 Input 2, 0
29, 02/08/17, 10:38:21.369, 0, Hinkson_Creek_substation, DIO#0 Input 2, 1
30, 02/08/17, 10:38:21.540, 0, Hinkson_Creek_substation, DIO#0 Input 2, 0
31, 02/08/17, 10:38:23.979, 0, Hinkson_Creek_substation, Breaker 7 (DIO_0 Input7), ____CLOSED____
**** End of File ****

5.5 M87x File System

Files are stored in the M87x on internal drives labeled "c:" and "d:". In addition the host module
contains optional compact flash memory which is accessible as drive "e:". Both FTP and
Zmodem may be used to access any drive. Trend Recorder files are stored on the d: drive on
the host module. All other user accessible files will be stored on the c: drive unless the unit is
equipped with optional compact flash memory. In this case these files are stored on the e: drive.
The following directories are relevant to the user.

Directory Function
c:\config Location of Configuration files
c:\upload Location of restart.now file
c:\data or e:\data Location of recorder compressed ZIP files
d:\data Location of trend recorder files

5.5.1 FTP Server

The M87x incorporates an internet-compatible FTP (File Transfer Protocol) data server. This
allows user access to any program or data file that exists on the M87x. It has the following
primary uses:

1. Allows remote software updates to be written to the M87x.


2. Allows determination of the time of last software update.
3. Allows configuration ".INI" files to be written, copied, and deleted from the M87x.
4. Allows Comtrade files to be read and deleted from the M87x.

The M87x can support up to 50 simultaneous FTP connections.

5.5.1a Introduction to FTP

65
M87x/EN M/O

FTP protocol is a standard component of the Internet protocol suite and is used to transfer files
between computer systems. Every Windows/Unix/Linux operating system contains an FTP
Client program that allows simple access to FTP Servers such as the M87x. FTP is accessed
from the command prompt (sometimes referred to as the DOS prompt). A (simplified) sample
session appears on the screen as:

C:\windows> FTP 192.168.0.254


M87x server, enter user name: anonymous
Enter password: BITRONICS (Any password will work)
FTP> binary

Some Operating Systems default to ASCII mode for FTP. Entering "binary" ensures that the FTP
connection will be in the binary mode necessary for communicating with the M87x.

As shown above, the user specifies the IP address of the server, enters a username and
password, and then is presented with the FTP prompt awaiting commands. The following
commands are useful for communicating with the M87x.

Command Function
BINARY Changes FTP to binary mode
CD.. Change current directory to parent directory
CD directoryname Change current directory to directyname
DELETE filename.ext Delete file from Server
DIR filename.ext List directory contents
GET source file destination file Read file from M87x
PUT source file destination file Write file to M87x
QUIT Exit FTP server and return to command prompt

Refer to your local operating system documentation for more details.

5.5.1b M87x FTP Implementation

The M87x FTP server has three privilege levels that determine the allowed FTP operations.

Description Username Password


Read files within the C:\DATA directory “anonymous” or “guest” Any
Read files on any drive or directory Drive\directory Level 0
Read, Write, or Delete files on any drive or directory Drive\directory Level 2

Access to Levels 1 and 2 require the user to enter the starting (root) directory as the "User
Name". For this purpose, the drive name is treated as a directory. The entire "c" drive would be
accessed by entering a User Name of "c" and the appropriate password. Access to a
subdirectory, for example the configuration files, is obtained by entering a User Name of
"c:config" and the password. Note that the FTP protocol does not allow access above the root
directory.

The M87x will remotely restart if the file "c:\upload\restart.now" is written. Restart begins about
12 seconds after the file has been created.

66
M87x/EN M/O

It is recommended that FTP be operated in passive mode. The port numbers used are 20 and
21 (TCP).

Please consult customer service for information on using FTP for updating the M87x firmware
or BIOS.

5.5.2 Zmodem, TELNET, and Command Line Interface

M87x files may be written, read, and deleted by use of Zmodem and the Host module front
panel serial ports (Section 3.1.1). Using the 70 Series Configurator, make sure the serial port you
wish to use is set to Zmodem. By default, ports P1 and P4 are set to Zmodem @ 9600 Baud
(Section 3.1.1b). Connect a terminal, or the serial port of a PC running a terminal emulator
program (such as HyperTerminalTM), to the serial port of the M87x configured for Zmodem.
Make sure the terminal emulator is set-up to connect directly to the serial port of the PC, and
that the baud rate matches that of the M87x port. Allowable commands are:

67
M87x/EN M/O

Service Port/Zmodem Commands


c: display off receive type
cd exit reset trigger dr1
chp1 getlog router trigger dr2
chp2 Goose* send trigger wv1
d: ip serial trigger wv2
date mac setlog ver
del nsap software vio point
dio point password status whoami
dir pulse subnet
display on reboot time
Note: * This command is for UCA Goose only and is now referred to as GSSE.

NOTE 1: When connected to the M87x with a terminal emulator program, remember that the commands
you type are operating on the M87x, not the PC. The terms "RECEIVE" and "SEND" are therefore
from the perspective of the M87x.

NOTE 2: The location of files to be sent to the M87x from the PC must be set in the terminal emulator
program.

NOTE 3: The RECEIVE command must be used before telling the terminal emulator program to transfer a
file to the M87x.

NOTE 4: Some terminal emulator programs cannot transfer more than one file using the "RECEIVE"
command.

NOTE 5: For a complete list of commands, type “help” at the command prompt. For help with a specific
command, type “help” followed by the command (i.e. “help send”).

5.6 Assigning Pulse Outputs to Energy Values

Any relay on the Digital Input/Output Module (Section 9) can be setup to operate as a pulse
output, and assigned to any of the four energy values of Section 4.5. Assigning the digital
outputs to perform a pulse-output function MUST be done by using the M87x Configurator
program. See Section 9 for information concerning output "Normally Open" and "Normally
Closed" settings. Additionally, Digital Outputs assigned to operate as a pulse output can be set
for Energy per Pulse (in KWh/KVARh per pulse).

5.7 IRIG-B

5.7.1 Overview

There is a great need in many power measurement and power quality applications for
synchronizing numerous instruments from various manufacturers to within fractions of a
second. These applications include failure analysis, sequence of event recording, distributed
fault recording, and other synchronized data analysis. One means of synchronizing various
instruments to the same clock source is to connect them to a master time device that
generates a standard time code. This scheme can be expanded upon such that two devices

68
M87x/EN M/O

half a world apart could be synchronized to within fractions of a second if each is connected to
an accurate local time master.

There are several vendors who manufacturer these master time devices and there are many
standardized time synchronization protocols. IRIG-B is one of the more commonly supported
standard time code formats.

5.7.2 Introduction to IRIG Standards

IRIG (InteRange Instrumentation Group) standards consist of a family of serial pulse time clock
standards. These standards were initially developed for use by the U.S. Government for ballistic
missile testing. There are several Time Code Formats within the family such as A, B, E, G, and H.
Each Time Code Format has its own unique bit rate.

There are sub-variations within each Time Code Format that specify the Format Designation,
the Carrier/Resolution, and the Coded Expression formats. All standard IRIG serial time
standards use the IRIG B000 configuration.

The first letter following IRIG specifies the Time Code Format and Rate Designation. The first
number following the letter specifies the Format Designation, the second number specifies the
Carrier/Resolution, and the third number specifies the Coded Expressions.

The M87x’s IRIG interface recognizes and decodes the following standard IRIG formats: IRIG
B000, IRIG B002, and IRIG B003. Additionally, IRIG B120 and IRIG123 formats are recognized
when using the M87x Modulated IRIG-B Converter, part number
M870-MODIRIGBCV, connected to one of the Host module serial ports, P2, P3 or P4.

5.7.2a Time Code Format (Rate Generation)

There are six different IRIG Time Code Formats. The M87x supports Time Code Format B. Time
Code Format B specifies a 100-bit frame and a 1 second time frame (10 milliseconds per bit).
The 100 bits consist of:
1 - time reference bit,
7 - BCD bits of seconds information,
7 - BCD bits of minutes information,
6 - BCD bits of hours information,
10 - BCD bits of days information,
27 - optional control bits,
17 - straight binary bits representing seconds of day information
15 - index bits
10 - position identifier bits

5.7.2b Format Designation

There are two IRIG Format Designations:


0 - Pulse Width Coded
1 - Sine Wave, Amplitude Modulated.

69
M87x/EN M/O

The Pulse Width Coded format is essentially the envelope of the Amplitude Modulated format.
The M87x supports the Pulse Width Coded format. The M87x Modulated IRIG-B Converter, part
number M870-MODIRIGBCV, is necessary when connecting an IRIG-B signal of Amplitude
Modulated format to one of the serial ports, P2, P3, or P4, on the M87x.

5.7.2c Carrier/Resolution

There are six IRIG Carrier/Resolutions:


0 - No Carrier/Index Count Interval
1 - 100 Hz/10 ms
2 - 1 kHz/1 ms
3 - 10 kHz/0.1 ms
4 - 100 kHz/10 μs
5 - 1 MHz/1 μs

Since the M87x does not support the Sine Wave Amplitude Modulated Format Designation, only
the No Carrier/Index Count IRIG Carrier/Resolution is applicable, when connected to an IRIG-B
master using Pulse Width Coded Format. The M87x Modulated IRIG-B Converter serves as the
signal demodulator, essentially converting from sine wave modulated into pulse width coded
format.

5.7.2d Coded Expressions

There are four IRIG Coded Expressions:


0 - BCD, CF, SBS
1 - BCD, CF
2 - BCD
3 - BCD, SBS

The M87x only uses the BCD portion of the expression and as a result can accept any of the
standard IRIG Coded Expressions.

5.7.3 M87x IRIG-B Implementation

The M87x receives the IRIG-B serial pulse code via the serial ports on the Host CPU module
(Section 3.1.1). The IRIG-B signal is decoded by the Host CPU module, and the resulting IRIG
time is compared to the M87x’s time. The M87x processes the time errors and corrects its local
time to coincide with the IRIG time.

5.7.3a M87x IRIG-B Receiver

As previously mentioned, the M87x receives the IRIG-B signal via the standard serial ports
located on the Host CPU’s front panel (Section 3.1.1). Port P2, P3, or P4 can be configured to
accept IRIG-B. The ports can be configured via the 70 Series Configurator software utility.

70
M87x/EN M/O

5.7.3b M87x IRIG-B Decoder

The M87x IRIG Decoder parses the bit stream from the IRIG Receiver into registers that
represent the number of days, minutes, and seconds since the beginning of the present year.
The control bits and straight binary seconds portion of the IRIG pulse stream are ignored. The
M87x transducer compares its present time to the IRIG time and stores the delta time error.
These errors are calculated every IRIG frame (every second) and are accumulated into a sample
buffer until the sample buffer is full. Once the buffer is full, the buffer is passed to the IRIG Time
Qualifier.

5.7.3c M87x IRIG-B Time Qualifier

The M87x IRIG-B Time Qualifier processes the sample buffer of time errors from the IRIG-B
Decoder. If the IRIG-B Time Qualifier detects several sequential time errors greater than 3
seconds, the IRIG-B Time Qualifier forces the M87x to immediately “jam” its clock to the present
IRIG-B time.

If the time errors are less than 3 seconds, the IRIG-B Time Qualifier examines all the errors in the
sample buffer. The error data is subjected to various proprietary criteria to determine an
accurate time offset. If the sample buffer does not meet the qualifying criteria the sample
buffer is discarded and no clock correction is performed. The IRIG-B Time Qualifier continues to
examine and discard sample buffers from the IRIG-B Decoder until it finds one that meets the
accuracy qualifications.

Once a sample buffer is qualified, the IRIG-B Time Qualifier calculates a clock correction value
and slews the M87x’s clock to match the IRIG-B time. The slew time depends on the magnitude
of the clock correction. The time required to slew the M87x’s clock to match the IRIG time is
approximately 30 times the clock correction value.

Slewing the clock ensures that time always moves forward. The clock may speed up or slow
down to attain proper synchronization, but it never moves backward. This ensures that the
ordering of events is always preserved while changing the clock. Ordering of events cannot be
guaranteed when the clock is jammed.

The IRIG-B Decoder does not sample the IRIG bit stream and build a sample buffer while the
M87x clock is slewing. All IRIG frames received during the M87x’s clock slew are ignored until
the slew has completed.

5.7.4 Determining the Correct Year

The IRIG-B standard provides days of year, minutes of day, and seconds of minute information.
The IRIG standard does not provide any year information. IEEE-1344 specifies a bit pattern that
is encoded into the IRIG control bit steam that specifies year information. The M87x IRIG driver
is capable of decoding the IEEE-1344 year information from the control bits when connected to
an IEEE-1344 compatible IRIG master. If the IRIG master that is connected to the M87x is not
IEEE-1344 compatible, the IEEE-1344 compatibility configuration switch in the M87x COM port
configuration should be turned off. This will prevent the M87x from incorrectly interpreting the
control bits as year information.

71
M87x/EN M/O

If the IRIG master is not IEEE-1344 compatible, the M87x assumes that the year stored in its
non-volatile capacitor backed-up clock is correct. If the M87x back-up clock fails or the M87x’s
year is incorrectly set, the IRIG-B Driver will assume that the year is the year reported by the
M87x’s clock.

If the M87x is connected to an IRIG master that is not IEEE-1344 compatible and the year
reported by the M87x’s clock is incorrect, the IRIG Driver may also set the M87x’s day incorrectly
(due to leap year) when it tries to synchronize the device time to the IRIG time. The time,
however, will still synchronize correctly. As a result, if the M87x’s backup fails (or the year was
not set correctly), any data time-stamped by the M87x or any waveform captures stored may
have the wrong year and day but will have the correct time accurate to several microseconds.
This data can still be synchronized to other events from other devices by simply adding the
correct day and year offsets to the time.

5.7.5 Methods of Automatic Clock Adjustments

The automated clock adjustments controlled by the IRIG interface include “jamming” the clock
and “slewing” the clock. Depending on the magnitude of the M87x’s absolute clock error the
clock adjustment algorithms will either jam the clock by directly writing a new value into the
clock registers or slew the clock smoothly by adding or subtracting small adjustments to the
clock registers over a period of time.

5.7.6 Types of M87x Clock Synchronization

There are various degrees (or states) of time synchronization. Upon power up, the device relies
on the value stored in the capacitor backed-up clock to set the correct time, and the crystal
frequency correction constant stored in non-volatile memory to correct the crystal’s frequency.
The M87x will keep time starting from the values read from the clock. There will be an
accumulated time error based upon the frequency error of the Real Time Clock crystal. The
crystal frequency correction constant provides a means for correcting for this error. If the M87x
was never synchronized to an external source (i.e. IRIG-B or network synchronization protocol),
the M87x will not have a value for the crystal frequency correction constant and the crystal
error will be the M87x’s clock error.

5.7.6a Frequency Adjustments and Free Wheeling

The M87x has the capability to add a correction factor to compensate for the crystal’s effective
frequency error rate. This frequency adjustment is accomplished by first determining the
crystal’s error rate and then correcting the clock to reflect that error. The IRIG-B interface
serves as an external accurate time source to determine the crystal’s typical error rate. The
frequency error is calculated and stored in non-volatile memory on the M87x’s Host CPU board.

When an M87x is connected to an IRIG-B source, it will automatically calculate and store the
crystal’s error in non-volatile memory on the Host CPU board. M87x transducers utilize this
constant to maintain a more accurate clock. If the IRIG-B source is removed the M87x will no
longer receive time corrections from the IRIG-B source, but the device clock will keep much
better time due to the frequency correction constant. This mode of operation is referred to as
“Free Wheeling.”

72
M87x/EN M/O

Although “Free Wheeling” with constant frequency compensation provides a more accurate
M87x clock, it will still drift and is less accurate than having a constant IRIG-B source connected
to the M87x. The frequency error of the crystal will change with time and temperature. Having
a permanent real time IRIG-B clock source allows for constant minute adjustments to the M87x
clock.

5.7.6b Permanent IRIG-B Source Connection

Having a permanently connected IRIG-B source provides the most accurate M87x clock. In
addition to correcting the frequency for the crystal error, the M87x will constantly receive
corrections to compensate for any drift that may still occur. This provides for a typical clock
error of less than 10 microseconds.

5.7.7 Stages of IRIG-B Synchronization and Accuracy

There are four basic stages of synchronization with an IRIG-B source: power-up, time lock,
frequency lock, and final lock.

5.7.7a Power-Up Stage

Upon Power-up, the M87x obtains the time from its non-volatile capacitor backed-up clock. This
clocks resolution is limited to seconds. Therefore, even if the clock was error free when it was
turned off, the M87x could have an error of up to one second when it is powered-up. The
typical crystal error rate is about 20 microseconds per second (20ppm). Therefore, if we
assume that the M87x clock was keeping perfect time before it was reset (or powered down), it
would typically be in error by:

(20 microseconds) x (number of seconds off) + 0.5 seconds after power is restored.

The M87x would start with this error and continue to drift by the frequency offset error. If the
M87x were never connected to an IRIG-B source (or other clock synchronizing source), the drift
would be equal to the crystal’s frequency error. If the M87x previously stored a frequency
correction constant in non-volatile memory, the device will include the compensation and drift
by a smaller amount equal to the true crystal frequency error minus the correction constant.

5.7.7b Time Lock Stage

Once the M87x begins to receive IRIG-B frames, validates a sample buffer, and calculates a
clock correction value, it will enter the Time Lock Stage of synchronization. If the clock
correction value exceeds 120 seconds, the clock is jammed with the present IRIG-B time.
Otherwise, the M87x clock is slewed to match the IRIG-B time.

The accuracy of this initial slew depends on whether a frequency correction constant was
previously stored in non-volatile memory, and if so how accurate the constant is. The M87x will
use this constant in the slew calculation to approximate the rate to change the clock to adjust
to the specified IRIG-B correction error.

73
M87x/EN M/O

The M87x will remain in the Time Lock Stage for approximately five minutes plus the time
required to perform the initial clock slew. The clock slew requires approximately 30 times the
clock correction value. For example, if the initial clock correction error was 1.5 seconds, the
Time Lock Stage would require approximately 6 minutes (5 minutes plus 45 seconds to slew).

The M87x enters the Frequency Lock Mode after completing the first IRIG-B clock correction.
The M87x’s clock is typically synchronized to within 1 millisecond of the true IRIG-B time after
the Time Lock Stage is completed.

5.7.7c Frequency Lock Stage

The M87x enters the Frequency Lock Stage of synchronization when it receives the third valid
clock correction value from the IRIG-B interface. At this time the M87x calculates a crystal
frequency correction constant based on the clock correction value. The crystal frequency
correction constant is stored in non-volatile memory to provide improved clock accuracy
during ”Free Wheeling” . The crystal frequency correction constant along with the clock
correction value is used to slew the clock to synchronize to the IRIG-B source.

The Frequency Lock Stage requires approximately five minutes. Once the M87x slews its clock
with the correct crystal frequency correction constant, the M87x’s clock is typically
synchronized to within 50 microseconds of the IRIG-B time source. The M87x then enters the
Final Lock Stage of synchronization.

5.7.7d Final Lock Stage

In the Final Lock Stage of synchronization, the M87x typically receives clock correction values
from the IRIG-B interface every five minutes. The M87x continues to make slight adjustments to
its crystal frequency correction constant to accommodate for small frequency drifts due to age
and temperature. At this point, the M87x clock is typically synchronized to within less than 10
microseconds of the IRIG-B source.

5.7.8 Notes On Operation

1. A new crystal frequency correction constant will be written to non-volatile memory every
four hours while a valid IRIG-B connection exists.

2. The capacitor backed-up clock will be corrected every hour while a valid IRIG-B
connection exists.

3. Network Time Synchronization requests are refused while a valid IRIG-B connection
exists.

5.7.9 IRIG-B Electrical Specifications

Absolute Maximum Input Voltage: -25 Volts to +25 Volts

74
M87x/EN M/O

Receiver Input Threshold Low: 0.8 Volts (min)


Receiver Input Threshold High: 2.4 Volts (max)
Receiver Input Hysteresis: 0.6 Volts (typical)
Receiver Input Resistance: 5 kΩ (typical)

5.7.10 IRIG-B Port Wiring Instructions (Pulse Width Coded, IRIG-B master,
Demodulated)

The IRIG-B master can be connected to Ports P2, P3, or P4 of the M87x’s Host CPU module
when IRIG-B signals of format IRIG B000, IRIG B001, or IRIG B003 are used. The selected Port
must be configured for IRIG-B via the 70 Series Configurator software utility. To connect the
IRIG-B master to a Port (Figure 3, pg. 22):
- Connect the IRIG-B signal to terminals 2 and 4.
- Connect the IRIG-B signal common to terminal 6.
- Terminal 5 provides a connection to earth ground via a 100Ω resistor for
shielding.

5.7.11 Modulated IRIG-B

The M87x may be used with Modulated IRIG-B systems, provided that the external Modulated
IRIG-B adapter is used (P/N M870-MODIRIGBCV)

5.7.12 Setup Instructions for Use of the M87x Modulated IRIG-B Converter (Sine
Wave, Amplitude Modulated, IRIG-B master)

The M87x Modulated IRIG-B Converter is a demodulating adapter used with the M87x Host
module for connection from an IRIG-B master that uses an amplitude-modulated sine wave,
and meets one of the input formats specified below. The setup required in order to use the
M87x Modulated IRIG-B Converter is described by the following information, which includes the
Converter specifications:

Input impedance: >10KΩ

Input Format : IRIG-B120, B123,


1kHz modulated sine wave, amplitude 3Vpp – 10Vpp,
modulation ratio 3:1

Power: Supplied by M87x serial port

Time skew: 600 μsec.

Use: Plug Converter into M87x serial port (P2, P3, or P4).
Fasten Converter to the M87x by tightening 2 hold down screws.
The recommended torque rating is 2.2 In-Lbs, 0.25 N-m.
Connect BNC to clock source.

Configuration: On the “Port Assignment” page (previously “serial port” tab) set the
appropriate port to IRIG-B.

75
M87x/EN M/O

On the IRIG-B page set the Absolute Time Offset to 620 μsec. (This offset
value includes the 600 μsec time skew attributed to the converter). The
number used for the Absolute Time Offset may need to be increased,
depending on time skew contributed by clock source and cable lengths.
The remaining items on the IRIG-B page can initially be left at the default
values. If there are problems with acquiring synchronization with the
IRIG-B source, turning on the debug messages may help in diagnosing the
problem. (Refer to section 3.1.1a; Debug messages are turned on when
service port P1 is running in logging mode). Depending on the installation
it may be necessary to relax some of the qualifying parameters to achieve
synchronization. If necessary, first increase the Max Skew setting from 5
μsec to 8 – 10 μsec. If this does not help it may be necessary to reduce
the Quality Factor from 0.7 to 0.5 or less.

5.8 Time Sync & Setting

The 70 Series IED utilizes an on-board clock to time stamp communications, SOE Log entries,
and data samples in the Waveform, Disturbance, and Trend Recorders. A variety of external
references may be used to synchronize the on-board clock to either local or Universal
Coordinated Time (UTC) with a high degree of accuracy.

5.8.1 Time Sync Status Registers

Pre-defined status registers indicate the current state for each of the various time
synchronization methods used in 70 Series IEDs
The following time sync registers will return status values of ‘0’ if a time sync master is inactive
and ‘1’ if a time sync master is active:

Status Registers
IrigB Time Sync
Network Time sync (UCA)
SNTP Time Sync
DNP Time Sync

The 70 Series DNP and Modbus manuals define the status register locations within Appendix B
for these time sync status points.

5.8.2 Manual time setting by Command-Line instruction

The command-line instruction is the manual method for setting the IED clock through service
port P1. The “time” instruction in the command-line interface is used to set time for the IED’s
internal clock. Refer to section 3.1.1a in order to set the IED clock.

5.8.3 Unsolicited DNP Time set (DNP master sets the IED clock)
DNP Time set is supported by the 70 Series IED. The IED clock simply free-wheels at its
characteristic rate between DNP time updates. Each DNP set-time instruction simply "sets" the
clock as it is received. Setting the clock via DNP supersedes any other time-sync method that

76
M87x/EN M/O

might be in use.

5.8.4 IRIG-B Time sync (time-synchronization via dedicated IED port)


Detailed information on IRIG-B time sync can be found starting in section 5.7. IRIG-B is expected
to produce the greatest accuracy relative to other time sync methods currently supported. A
status bit, named ‘IrigB Time Sync’, is set to indicate the IED is being synchronized via IRIG-B as
long as the IED continues to receive valid IRIG updates. While this bit is set, time-sync signals
received from (UCA) Network Time Sync, SNTP, and Requested DNP are ignored.
It should be noted that the IED host is not able to distinguish between the Modulated and
Unmodulated IRIG-B signals applied to the input port. Demodulation is accomplished by a
dedicated circuit. The host processor makes no determination as to which type of external
IRIG-B signal is applied. Unmodulated IRIG-B would provide a slightly more accurate time
signal then Modulated IRIG-B, due to additional time latency that is introduced in the de-
modulation process.

5.8.5 (UCA) Network Time Synchronization - time synchronization over Ethernet

The M87x real-time clock may be synchronized to a UCA network time-sync master. The
network time sync functions as described in IEEE TR-1550 Part 2 Appendix B and is roughly
analogous to the IRIG-B described in Section 5.6, in that the M87x continually “trains” it’s
internal clock to eliminate errors. An algorithm progressively adjusts the on-board clock to
improve its accuracy with subsequent time updates received from the master. This allows the
M87x to “Free Wheel” accurately in the event the UCA network time-sync master is unavailable.

5.8.6 SNTP (Simple Network Time Protocol) - time synchronization over Ethernet

Time synchronization is supported using SNTP (Simple Network Time Protocol); this protocol is
used to synchronize the internal real time clock in substation devices , (i.e., control systems,
relays, IEDs). Up to 2 SNTP servers, using optional many-cast (or any-cast) mode of operation,
are supported, along with configurable polling times. SNTP servers can be polled for
configurable time, but only one at a time.

The SNTP page in 70 the Series Configurator software tool allows the user the option of
selecting which tool will be used to load the SNTP (and IP) settings. Radio buttons are provided
for that purpose. SNTP (and IP) settings can be loaded from either the 70Series Configurator (INI
file) or the IEC61850 IED Configurator (MCL file). When using the 70Series Configurator, the
initial default configuration will load SNTP settings from the 70Series Configurator (INI file). If
IEC61850 protocol is used, it is possible for the user to change the radio button selected in
order to indicate that the IEC61850 IED Configurator (MCL file) be used to load these settings
instead. If the settings on the 70Series Configurator SNTP page grey out, it is an indication that
the SNTP server addresses may have been set through the other Configurator’s software.

Additionally on the SNTP page of the 70 Series Configurator software, the user may specify that
an offset from the SNTP server time be applied when synchronizing. A common use for this
feature is to allow the 70 Series device to operate in local time when synchronizing with an
SNTP server operating in UTC time. To further support local time, the application of Daylight
Savings adjustments may also be configured.

77
M87x/EN M/O

5.8.7 DNP Time sync (slave requesting DNP time be set)

A slave may request thatDNP time be set in order to have the DNP master set the DNP time.

5.9 Using the M87x with a Bitronics Analog Output Converter

The M87x may be used with any of the Bitronics AOC units (NAO8101, NAO8102, NAO8103, or
NAO8104). The AOC may be connected to any of the three Host Serial Ports P2, P3, or P4
(Section 3.1.1). The serial port must be configured for the appropriate protocol and register set
for the AOC that will be connected. Setting up the serial ports is accomplished by using the
M87x Configurator. AOC units will only function with the M871 configured for the Bitronics
Legacy register set. When using AOCs that communicate via Modbus (NAO8101 and NAO8103)
the M87x COM port must be set for an RxD to TxD Delay of 10ms for proper operation. A
separate AOC may be connected on each serial port. Serial port and connection information is
shown in Figures 3 and 4 (pg. 22-24). As stated previously, the AOC address must match the
protocol address assigned to the M87x communications port.

Protocol Baud Parity Media


DNP 9600 NONE RS485
Modbus 9600 EVEN RS485

5.10 Automatic Event Notification

The 70 Series is capable of sending an Automatic Notification via email, or over a serial port.
The action of automatic notification may be selected in response to any of the available
triggers, similar to triggering a recording or activating an output contact. The type of
notification (email or serial) is selected in the “Automatic Notification settings" page of the
Configurator.

5.10.1 Email Notifications

A valid SMTP (email) server IP address must be entered. This server must exist on the local
network in order for emails to be sent. Email addresses can then be entered for up to 3 users.

5.10.2 Serial Notifications

The 70 Series can be configured to send text strings out a serial port P2 or P3. These text
strings can be used for various purposes, including operating a modem. This could be used to
send a page to a numeric pager, for example.

5.10.3 Data Sent

The 70 Series meter will send the user-configured string out the specified COM port. It is the
user’s responsibility to ensure the string is properly formatted to communicate through any
port switches, modem switches, and/or modems. The user is also responsible for ensuring the
string specified is meaningful to the user or device that will be receiving it.

If the 70 Series meter is not configured to have a COM port send notifications, then no serial

78
M87x/EN M/O

notifications will be sent.

If the 70 Series meter has multiple COM ports configured to send notifications, then the
notifications will be sent out each port configured for notifications.

5.10.4 Error Recovery

There is no provision to confirm that a message has been successfully transmitted to an end
user or device. There may be a busy signal, an answering machine may take the call, or
another device may be using the phone line.

5.10.5 Example

Here is an example of a string that can be configured to send the numeric message 123 to a
pager with the phone # 610-555-1212, and then hang up:

ATDT6105551212,,,,,,,,,123,,,,ATH<cr>

Note that it is typically important to enter the <cr> (carriage return character) for the string to
be properly recognized by the modem. Information on modem control characters is available
from your modem manufacturer.

5.10.6 Control Characters

Control characters can be entered in the Configurator by typing “\x” followed by the
hexadecimal representation of the ASCII code for the desired character. For example, the
control-Z character is represented by a hexadecimal 1A; therefore, “\x1a” should be entered
into the serial data string where a control-Z is desired.

If the characters “\x” are desired to appear in the serial data string rather than a control
character, then this special sequence can be escaped by entering “\\x”. The characters “\x” will
appear in the serial data string.

79
M87x/EN M/O

6.0 POWER SUPPLY V10

Figure 8 - Power Supply Connections

6.1 Introduction

The V10 power supply can operate from any voltage between 20-300Vdc or 55-275Vac
(45-65Hz). It is therefore possible to power the M87x with AC or DC station power or an auxiliary
VT, provided the voltage remains above 55Vac or 20Vdc. The power supply creates 3.3V, 5V, and
+/-12Vdc outputs and consists of an isolated flyback converter that provides at least 12.5W of
output power at 3.3Vdc and/or 5Vdc.

6.2 Features

 25W minimum output power from the combined 5V and 3.3V supplies.
 +/-12Vdc capable of delivering up to 500mA.
 Standard cPCI power connector.
 Removable terminal block accepts bare wire or terminal lugs.
 5Vdc and 3.3Vdc power indicator LEDs.

6.3 Specifications

Input (Auxiliary) Voltage

Nominal: 24-250Vdc, 69-240Vac (50/60Hz)

Operating Range: 20-300Vdc, 55-275Vac (45-65Hz)

Output Voltage: 3.3Vdc, 5Vdc, and +/-12Vdc

80
M87x/EN M/O

Maximum Output Power and Current (5V and 3.3V supplies are independent):

Min Interruption
Nominal Max Output Power Max Output Current Ride-Through*
Vin 3.3V 5V Total 3.3V 5V ms
24Vdc 12.5W 12.5W 25W 3.75A 2.5A 2.5ms
48Vdc 17.5W 17.5W 35W 5.3A 3.5A 6.5ms
69Vac 17.5W 17.5W 35W 5.3A 3.5A 10ms
125Vdc 17.5W 17.5W 35W 5.3A 3.5A 35ms
120Vac 17.5W 17.5W 35W 5.3A 3.5A 50ms
250Vdc 17.5W 17.5W 35W 5.3A 3.5A 140ms
230Vac 12.5W 12.5W 25W 3.75A 2.5A 220ms
240Vac 12.5W 12.5W 25W 3.75A 2.5A 230ms

* M871 -V10 -S10 -H10 -A10 -P11 -P30 (all relays energized)

The +12Vdc output is derived from the 3.3Vdc output, and the -12Vdc output is derived from the
5Vdc output. The +/- 12Vdc outputs are capable of providing up to 500mA, however, they must
be de-rated to avoid exceeding the maximum power limits of the 3.3Vdc and 5Vdc outputs
respectively.

6.3.1 Environmental

Operating Temperature: -40C to 70C

Relative Humidity: 0-95% non-condensing

Installation Category: IC III (Distribution Level), Pollution Degree 2. Refer to definition on


page 9.

6.3.2 Physical

Input Connections: Removable terminal block accepts #26-12 AWG (0,15-3,3mm2) wire,
or terminal lugs up to 0.325" (8,25mm) wide. Recommended
minimum wire size is #18 AWG (0,5 mm2). Recommended Torque
Rating for the terminal block wire fasteners is 10 In-Lbs, 1.13N-m.
Precautions must be taken to prevent shorting of lugs at the terminal
block. A minimum distance of 0.1” (2.5mm) is recommended
between un-insulated lugs to maintain insulation requirements.
Standard 0.200" (5,08mm) header socket accepts other standard
terminal types.

Backplane Connections: Standard cPCI-specified power connector

81
M87x/EN M/O

6.4 Power Supply and Protective Ground (Earth) Connections

Power and chassis ground is applied to three screws on a barrier strip on the front of the Power
Supply input module. Connection of the chassis ground is required (see Section 2.3). There are
two chassis ground points that MUST be connected to Earth Ground. One is the Protective
Ground (Earth) terminal (terminal 2) on the Power Supply input, and the other is the mounting
flange. Bitronics LLC recommends that all grounding be performed in accordance with ANSI/IEEE
C57.13.3-1983.

6.5 Overcurrent Protection

To maintain the safety features of this product, a 3 Ampere time delay (T) fuse must be connected
in series with the ungrounded/non-earthed (hot) side of the supply input prior to installation. The
fuse must carry a voltage rating appropriate for the power system on which it is to be used. A 3
Ampere slow blow UL Listed fuse in an appropriate fuse holder should be used in order to
maintain any UL product approval.

6.6 Supply/Mains Disconnect

Equipment shall be provided with a Supply/Mains Disconnect that can be actuated by the
operator and simultaneously open both sides of the mains input line. The Disconnect should be
UL Recognized in order to maintain any UL product approval. The Disconnect should be
acceptable for the application and adequately rated for the equipment.

82
M87x/EN M/O

7.0 SIGNAL INPUT MODULE S10, S11, S12, S1C (M871) S13, S14, S15, S16, S17 (M872)

7.1 Introduction

The Signal Input Module provides the terminal blocks, current transformers, and voltage input
dividers for the signals to be measured. Compensation for normal variations in input circuits is
achieved by storing calibration constants in non-volatile memory (EEPROM), which resides on the
Signal Input Board. These constants are factory-programmed to provide identical signal gain
(attenuation) in each of the 14 signal input paths. Checksums are incorporated into the EEPROM,
which are read periodically by the microcontroller to check the integrity of the calibration
constants.

7.2 Features

 Utility-grade current input terminal block with 10-32 studs (M871) or 8-32 screws (M872)
 Current shunts are #12 AWG SIS, 600V wire, crimped ring-lugs with brazed seams
 Option for split-core CTs (external) for the M871
 Voltage measurements to 424V rms line-to-neutral (730V rms line-to-line)
 7kV, 7.5MΩ input resistors on voltage inputs.
 Removable voltage input terminal block accepts bare wire or terminal lugs.
 Non-volatile memory backup of CT/VT calibration data

83
M87x/EN M/O

7.3 Specifications
Input Signals (S10, S11, S12, S1C)
CT Current Configuration 4 Inputs. 3 Phase Currents and 1 Neutral.
Inputs (S10) Nominal 5Aac
Peak Current Linear to 100A symmetrical (141A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.04VA @ 5A rms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 4 Inputs. 3 Phase Currents and 1 Neutral.
Inputs (S11) Nominal 1Aac/5Aac
Peak Current Linear to 20A symmetrical (28A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1A rms, 60Hz (0.0016Ω @ 60Hz)/0.04VA @ 5A rms, 60Hz.
Frequency 15-70Hz
CT Current Configuration 4 Inputs. 3 Phase Currents and 1 Neutral.
Inputs (S12) Nominal 1Aac
Peak Current Linear to 4A symmetrical (5.7A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1Arms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 3 Inputs, 3 Phase Currents, or 4 Inputs, 3 Phase Currents and 1 Neutral Current
Inputs (S1C) Nominal 5Aac
Peak Current Linear to 100A symmetrical (141A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden Not applicable
Frequency 15-70Hz

84
M87x/EN M/O

Input Signals (S10, S11, S12, S1C)


VT (PT) AC Configuration 8 Inputs, Measures 2 Buses, 3 or 4 Wire.
Voltage Inputs Nominal 120Vac
(S10, S11, S12)
System Voltage Intended for use on nominal system voltages up to 480V rms phase-to-phase (277V rms
Terminals 9 to
phase-to-neutral).
16
Peak Voltage Reads to 600V peak (425V rms), input-to-case (ground)
Impedance >7.5MΩ, input-to-case (ground)
(cont’d) Voltage 2.5kV rms 1min, input-to-case (ground)
Withstand 2kV rms 1min, input-to-input
Frequency 15-70Hz
AUX Configuration 2 Inputs: VAX1 & VAX2
Measurement Nominal 125Vdc / 120Vac
Voltage Inputs
System Voltage Intended for use on nominal AC system voltages up to 480V rms phase-to-phase (277V rms
(S10, S11, S12)
phase-to-neutral), and DC system voltages up to 250Vdc.
Terminals 17 &
Peak Voltage Reads to 600V peak (425V rms), input-to-case (ground)
18
Impedance >7.5MΩ, input-to-case (ground)
Voltage 2.5kV rms 1min, input-to-case (ground)
Withstand 2kV rms 1min, input-to-input
Frequency DC-70Hz

Input Signals (S13, S14, S15, S16, S17)


CT Current Configuration 6 Inputs. 2 sets of 3 Phase Currents
Inputs (S13) Nominal 5Aac
Peak Current Linear to 100A symmetrical (141A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.04VA @ 5A rms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 2 sets of 3 Phase Currents
Inputs (S14) Nominal 1Aac/5Aac

85
M87x/EN M/O

Input Signals (S13, S14, S15, S16, S17)


Peak Current Linear to 20A symmetrical (28A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1A rms, 60Hz (0.0016Ω @ 60Hz)/0.04VA @ 5A rms, 60Hz.
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 2 sets of 3 Phase Currents
Inputs (S15) Nominal 1Aac
Peak Current Linear to 4A symmetrical (5.7A peak) at all rated temperatures.
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1Arms, 60Hz (0.0016Ω @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 3 Phase Currents from 2 Lines with different peak current ranges.
Inputs (S16) Nominal 5Aac
M872 with dual
Peak Current Linear to 20A symmetrical (28A peak)/linear to 100A symmetrical (141A peak) at all rated
peak ranges
temperatures.
20A/100A
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.04VA @ 5A rms, 60Hz (0.0016ohms @ 60Hz).
Frequency 15-70Hz
CT Current Configuration 6 Inputs. 3 Phase Currents from 2 Lines with different peak current ranges.
Inputs (S17) Nominal 1Aac
M872 with dual
Peak Current Linear to 4A symmetrical (5.7A peak)/linear to 20A symmetrical (28A peak at all rated
peak ranges
temperatures.
4A/20A
Overload 30Aac continuous. Withstands 400Aac for 2 seconds.
Isolation 2500Vac, minimum.
Burden 0.0016VA @ 1Arms, 60Hz (0.0016ohms @ 60Hz).
Configuration 6 Inputs. 3 Phase Currents from 2 Lines with different peak current ranges.
VT (PT) AC Configuration 8 Inputs, Measures 2 Buses, 3 or 4 Wire.

86
M87x/EN M/O

Input Signals (S13, S14, S15, S16, S17)


Voltage Inputs Nominal 120Vac
(S13, S14, S15, System Voltage Intended for use on nominal system voltages up to 480V rms phase-to-phase (277V rms
S16, S17) phase-to-neutral).
Terminals 9 to Peak Voltage Reads to 600V peak (425V rms), input-to-case (ground)
16
Impedance >7.5MΩ, input-to-case (ground)
Voltage Withstand 2.5kV rms 1min, input-to-case (ground)
2kV rms 1min, input-to-input
Frequency 15-70Hz

Sampling System
Sample Rate 128 samples per cycle
Data Update Rate Amps, Volts Available every ¼ cycle
Watts, VAs, VARs, PF Available every cycle
Number of Bits 16

Accuracy
Accuracies are specified at nominal Frequency and 25C, unless otherwise specified. Temperature Coefficient <25ppm. All values
are true RMS and include Harmonics to the 63rd (minimum)
Voltage AC: Better than 0.1% of reading (20 to 425V rms, input-to-case). DC (AUX Inputs): +/- 0.2V (24 to 250Vdc,
input-to-case)
Current (S10, S13, S16 Better than 0.1% of reading +/- 500μA (0.5A to 100.0A),
bus 2) Better than 0.1% of reading +/- 1mA (0.05A to 0.5A).
Current (S11, S14, S16 Better than 0.1% of reading +/- 100μA (0.5A to 20.0A),
bus 1, S17 bus 2) Better than 0.1% of reading +/- 250μA (0.05A to 0.5A).
Current (S12, S15, S17 Better than 0.1% of reading +/- 20μA (0.1A to 4.0A),
bus 1) Better than 0.1% of reading +/- 50μA (0.01A to 0.1A).
Current (S1C) External Better than 0.1% of reading +/- 2mA (0.05A to 100.0A, -10C to 70C)
Split-Core CTs
Frequency +/- 0.001 Hertz (accuracy is specified at nominal Frequencies and over operating temperature range)

87
M87x/EN M/O

Phase Angle +/- 0.2 Deg


Power Better than 0.2% of reading (>20% of nominal inputs, 1PF to 0.7PF)

Environmental
Operating Temperature -40C to 70C
Relative Humidity 0-95% non-condensing
Installation Category IC III (Distribution Level) Refer to definitions below.
Pollution Degree Pollution Degree 2 Refer to definitions below.
Enclosure Protection IP20 to IEC60529:1989
Altitude Up to and including 2000m above sea level
Intended Use Indoor use; Indoor/Outdoor use when mounted in an appropriately rated protective enclosure to
NEMA or IP protection classifications, as required for the installation.

Physical
Connections Current (S10, Terminal block with 10-32 Studs for current inputs. Use ring lugs sized for #10 stud.
(Signal Input S11, S12) Accepts #10-16 AWG (5.3-1.3mm2) wire. Recommended Torque: 16 In-Lbs, 1.81 N-m. Current
Modules) inputs are connected to the output from the secondary of permanently installed Current
Transformers (CTs). Grounding of CT signals per ANSI/IEEE C57.13.3-1983 is required.
Current (S13, Terminal block with 8-32 Screws for current inputs. Use ring lugs sized for #10 screw thread.
S14, S15, S16, Accepts #10-22 AWG (5.3-0.33mm2) wire. Recommended Torque: 16 In-Lbs, 1.81 N-m. Current
S17) inputs are connected to the output from the secondary of permanently installed Current
Transformers (CTs). Grounding of CT signals per ANSI/IEEE C57.13.3-1983 is required.
External Split- 6 position removable terminal block, accepts 26-14AWG stranded wire. Recommended Torque 7
Core CTs (S1C) in-lbs, 0.79N-m.
Overcurrent To maintain the safety features of this product, a 3 Ampere time delay (T) fuse must be connected
protection in series with the ungrounded/non-earthed (hot) side of the supply input connected to the voltage
for Voltage measurement (VT) input of the instrument prior to installation. The fuse must carry a voltage rating
(measurement) appropriate for the power system on which it is to be used. A 3 Ampere slow blow UL Listed fuse in
input (VT) an appropriate fuse holder should be used in order to maintain any UL product approval.
connections

88
M87x/EN M/O

Physical
Voltage Removable Terminal Block, accepts #22-12 AWG (0.35 to 3.3mm2) wire, or terminal lugs up to
(CE units) 0.250" (6.35mm) wide. Standard 0.200" (5.08mm) header socket accepts other standard terminal
types. Precautions must be taken to prevent shorting of lugs at the terminal block.
A minimum distance of 1/8" (3mm) is recommended between uninsulated lugs to maintain
insulation requirements. Recommended Torque: 10 In-Lbs, 1.13 N-m
Voltage Removable Terminal Block, accepts #22-12 AWG (0.35 to 3.3mm2) wire, or terminal lugs up to
(non-CE) 0.325" (8.25mm) wide. Standard 0.200" (5.08mm) header socket accepts other standard terminal
types. Precautions must be taken to prevent shorting of lugs at the terminal block.
A minimum distance of 1/8" (3mm) is recommended between uninsulated lugs to maintain
insulation requirements. Recommended Torque: 10 In-Lbs, 1.13 N-m
Class I equipment to IEC61140: 1997

89
M87x/EN M/O

7.4 Current Input (CT) Connections

The current input terminal block for units with internal CTs features 10-32 terminals (M871) or
8-32 screws (M872) to assure reliable connections. Current from the inputs flow through the
current transformers via #12 AWG SIS, 600V wire, and crimped ring-lugs with brazed seams.
This results in a robust current input with negligible burden to ensure that the user’s external CT
circuit can never open-circuit, even under extreme fault conditions. The M871 has four
independent current inputs, one for each phase being measured, plus neutral while the M872
has 6 independent current inputs for two sets of three-phase measurement. Current signals
are connected directly to #10-32 studs (M871) or #8-32 screws (M872) on the current input
terminal block on the front of the Signal Input module. See Section 7.3 for connection
recommendations. It is intended that the instrument connect to the output from the secondary
of permanently installed Current Transformers (CTs). Grounding of CT signals per ANSI/IEEE
C57.13.3-1983 is required. The current input terminal block

For the M871 with split-core CTs, external split core CT secondary wires connect to the current
terminal block. The current inputs for this model are touch safe. No internal current isolation is
provided within the meter. DO NOT CONNECT Hazardous Live voltages to the current input
terminal block. Only connect the external Split Core CT secondary current outputs to the
meter’s current input terminal block. Isolation is provided from the external Split Core CTs.
Recommended torque is 9 In-Lbs, 1.02 N-m

Signal Input Module S1C Used with Split-Core CTs

90
M87x/EN M/O

7.5 Voltage Input (VT) Connections

The voltage terminal block is removable after unscrewing the mounting screws on the ends of
the block. Voltage signals are measured using a 7.5MΩ resistor divider with a continuous voltage
rating of 7kV. This ideal impedance provides a low burden load for the VT circuits supplying the
signals. Wiring diagrams, which represent the various measurement configurations that are
applicable for the instrument, are provided in Figure 9. Grounding of VT & CT signals per
ANSI/IEEE C57.13.3-1983 is recommended. The polarity of the applied signals is important to the
function of the instrument.

The Auxiliary Voltage Input channels (M871 only) are physically identical to the other voltage
inputs on the Signal Input Module.

7.5.1 Overcurrent protection for Voltage input (VT) Connections

To maintain the safety features of this product, a 3 Ampere time delay (T) fuse must be connected
in series with the ungrounded/non-earthed (hot) side of the supply input connected to the
voltage measurement (VT) input of the instrument prior to installation. The fuse must carry a
voltage rating appropriate for the power system on which it is to be used. A 3 Ampere slow blow
UL Listed fuse in an appropriate fuse holder should be used in order to maintain any UL product
approval.

7.6 Current Measurements

The M871 has four current inputs, and the M872 has 6 current inputs, with an internal CT on each
channel. These inputs can read to a maximum of 100ARMS (symmetrical), or 141APEAK, for the S10
and S13 and S16 (bus 2) input modules under all temperature and input frequency conditions.
No range switching is used, allowing a high dynamic range. Refer to section 7.3 for the current
measurement input ranges and specifications for the signal input modules that are offered.

7.6.1 Neutral Current (Residual Current) for WYE Connections

The M871 directly measures the neutral current from the neutral CT. Residual current is
calculated from the vector sum of the 3 per-phase currents on both the M871 and the M872.

7.7 Voltage Measurements

The M87x inputs are a unique advancement in voltage measurement technique. All three phases,
and the neutral, are measured relative to a common reference point (essentially panel ground).
Because all signals are sampled at the same instant in time, common mode signals can be
removed by subtraction of samples in the DSP, instead of the more traditional difference amplifier
approach. This greatly simplifies the external analog circuitry, increases the accuracy, and allows
measurement of the Neutral-to-Ground voltage at the panel. The 7kV input divider resistors are
accurate to within +/- 25ppm/DegC, and have a range of 600VPEAK, from any input to panel
ground.

A signal must be present on any of the phase-voltage or current inputs for the M87x to attain
Frequency lock.

91
M87x/EN M/O

7.8 Changing Transformer Ratios

The M87x has the capability to store values for Current Transformer (CT) and Potential
Transformer (VT) turns ratios. The VT and CT values are factory set to 1:1 CT and 1:1 VT. These
values can be entered into the M87x over the network or via the Configurator software, and will
be stored in internal non-volatile memory located on the Signal Input Module. All measurements
are presented in primary units, based on these ratios. Refer to the appropriate protocol manual
for information on changing transformer ratios.

7.9 User (External Transformer) Gain and Phase Correction

It is possible to correct for both gain and phase errors in external current and voltage instrument
transformers connected to the M87x, when these errors are known. These Correction Factors
can be entered via a protocol or by using the 70 Series Configurator Software.

User Gain Correction is a multiplier (from -2 to +2) that can be used to adjust for known gain
errors in the system. User Gain Correction is "1" by default. For example, a gain correction of
1.01 would increase the effective ratio by 1%. Entering a negative number will reverse the phase
of an input.

User Phase Correction is used to adjust for known phase errors in the system. User Phase
Correction is measured in degrees from -180 to 180. The default value is "0". When a User Phase
Correction is entered, it will have an effect on Watts and VARs, Fundamental Watts and VARs, PF
and Displacement PF, and the phase angles reported for fundamental values. It will have no
effect on the magnitudes of phase-to-phase Fundamental Volts.

7.10 Calibration

Routine re-calibration is not recommended or required. A field calibration check every few years
is a good assurance of proper operation.

7.11 Installation and Calibration for the S1C Option

Each M871 with the S1C option is calibrated at the factory with a set of external split core
CT's. During this process four calibration constants are generated for each CT. As with all
previous M871 input options, these constants are stored in the M871 non-volatile
memory. Additionally, these constants are now also printed to a label affixed to each CT along
with the M871 Serial Number and the phase (A,B,C,N) the CT was calibrated on.

For normal installation, connect the external split core CT to the M871 input terminal with the
matching serial number and phase. As noted above, the factory calibration is already stored in
the M871 and accuracy will meet published specifications.

If for some reason the above installation method cannot be used, then the M871 factory
calibration may be altered. Locate the four calibration constants (GH, GL, PH, PL) on the label of
the external split core CT. Note the M871 serial number and phase to which the CT is
attached. Connect to the M871 with the Configurator. On the Split Core CT Calibration page,
enter the four calibration constants (GH, GL, PH, PL) into the appropriate locations.

92
M87x/EN M/O

After save and reboot, the entered calibration will replace the original factory
calibration. Accuracy will be comparable to original and within published specifications.

93
M87x/EN M/O

Figure 9 - Signal Connections (M871)

94
M87x/EN M/O

Figure 9 - Signal Connections (M871)

95
M87x/EN M/O

Figure 9 - Signal Connections (M871)

96
M87x/EN M/O

Figure 9 - Signal Connections (M871)

97
M87x/EN M/O

Figure 9 - Signal Connections (M871)

98
M87x/EN M/O

Figure 9 - Signal Connections (M871)

99
M87x/EN M/O

A
B
BUS (POTENTIALS COMMON TO BOTH FEEDERS)
C

VOLTAGE VOLTAGE “Reference” potentials


9 13 VR1 and VR2 are
VA1 VR1 intended for synch-
check across the
10 respective feeder-
FEEDER 1

FEEDER 2
14
VB1 VRN1 breakers.

11 15
VC1 VR2

12 16
VN1 VRN2
BUS 1 BUS 2

4 24
A HI A HI
5 25
B HI B HI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
CLO CLO

CURRENT CURRENT

CB CB

A B C A B C
LOAD LOAD

2-Element 3-Wire (Delta) configured for Dual Feeder Common Bus

A
B
BUS (POTENTIALS COMMON TO BOTH FEEDERS)
C
N
VOLTAGE VOLTAGE “Reference” potentials VR1
and VR2 are intended for
9 13
VA1 VR1 synch-check across the
respective feeder-breakers.
10
FEEDER 1

FEEDER 2
14
VB1 VRN1

11 15
VC1 VR2

12 16
VN1 VRN2
BUS 1 BUS 2

4 24
AHI AHI
5 25
BHI BHI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
CLO CLO

CURRENT CURRENT

CB CB

A B C N A B C N
LOAD LOAD

3-Element 4-Wire (Wye) configured for Dual Feeder Common Bus

Figure 9 - Signal Connections (M872)

100
M87x/EN M/O

A
B CB CB CB
C

VOLTAGE VOLTAGE

9 13
VA1 VA2

10 14
VB1 VB2

11 15
VC1 VC2

12 16
VN1
BUS 1 BUS 2 VN2

4 24
A HI A HI
5 25
B HI BHI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
CLO CLO

CURRENT CURRENT

2-Element 3-Wire (Delta) configured for Breaker-and-a-Half (current connections shown)

A
B CB CB CB
C

VOLTAGE VOLTAGE

9 13
VA1 VA2

10 14
VB1 VB2

11 15
VC1 VC2

12 16
VN1
BUS 1 BUS 2 VN2

4 24
AHI AHI
5 25
BHI BHI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
A B C CLO CLO
A B C
LINE 1 CURRENT CURRENT LINE 2

2-Element 3-Wire (Delta) configured for Breaker-and-a-Half (voltage connections shown)

Figure 9 - Signal Connections (M872)

101
M87x/EN M/O

A
B CB CB CB
C
N

VOLTAGE VOLTAGE

9 13
VA1 VA2

10 14
VB1 VB2

11 15
VC1 VC2

12 16
VN1
BUS 1 BUS 2 VN2

4 24
A HI A HI
5 25
B HI BHI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
CLO CLO

CURRENT CURRENT

3-Element 4-Wire (Wye) configured for Breaker-and-a-Half (current connections shown)

A
B CB CB CB
C
N

VOLTAGE VOLTAGE

9 13
VA1 VA2

10 14
VB1 VB2

11 15
VC1 VC2

12 16
VN1
BUS 1 BUS 2 VN2

4 24
AHI AHI
5 25
BHI BHI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
A B C N CLO CLO
A B C N
LINE 1 CURRENT CURRENT LINE 2

3-Element 4-Wire (Wye) configured for Breaker-and-a-Half (voltage connections shown)

Figure 9 - Signal Connections (M872)

102
M87x/EN M/O

A
B CB CB CB
C
N

VOLTAGE VOLTAGE

9 13
VA1 VA2

10 14
VB1 VB2

11 15
VC1 VC2

12 16
VN1
BUS 1 BUS 2 VN2

4 24
A HI AHI
5 25
B HI B HI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
A B C N CLO CLO
A B C N
LINE 1 CURRENT CURRENT LINE 2

2½ Element (Wye) configured for Breaker-and-a-Half (voltage connections shown, with B-phase missing) Current
connections are the same as for 3-element 4-wire (wye) shown on the preceding page.
When configuring the unit, set the VT ratio for the missing phase equal to 0. This will cause the M872 to calculate the voltage of
the missing phase from the vector sum of the two phases present (assumes balanced voltage).

A
B
BUS (POTENTIALS COMMON TO BOTH FEEDERS)
C
N
VOLTAGE VOLTAGE “Reference” potentials VR1
and VR2 are intended for
9 13
VA1 VR1 synch-check across the
respective feeder-breakers.
10
FEEDER 1

FEEDER 2
14
VB1 VRN1

11 15
VC1 VR2

12 16
VN1 VRN2
BUS 1 BUS 2

4 24
AHI AHI
5 25
BHI BHI
6 26
CHI CHI

1 21
ALO ALO
2 22
BLO BLO
3 23
CLO CLO
CURRENT CURRENT

CB CB

A B C N A B C N
LOAD LOAD

2½ Element (Wye) configured for Dual Feeder Common Bus (shown with B-phase missing).
When configuring the unit, set the VT ratio for the missing phase equal to 0. This will cause the M872 to calculate the voltage of
the missing phase from the vector sum of the two phases present (assumes balanced voltage).

Figure 9 - Signal Connections (M872)

103
M87x/EN M/O

8.0 ETHERNET MODULE P10, P11, P12 OR E1, E3 OPTION WITH H12 HOST

8.1 Introduction

The CompactPCITM high-speed Ethernet interface is available as an option for the M87x as either
a stand-alone module when used with the H11, or consolidated with the H12 host module (H12E1
or H12E3). Both the stand-alone board and the consolidated options meet or exceed all
requirements of ANSI/IEEE Std 802.3 (IEC 8802-3:2000) and additionally meet the requirements
of the EPRI Substation LAN Utility Initiative "Statement of Work" version 0.7. The Ethernet interface
is also compliant with IEC 61850 Part 3 and Part 8-1 TCP/IP T-profile for physical layer 1 (Ethernet
copper interface) and physical layer 2 (for P12 with 100 Megabit fiber). These documents define
an interface designed to inter-operate with other devices with little user interaction ("Plug-and-
Play").

M87x instruments with the H11 host module are offered with three versions (P1x) of the Ethernet
interface board:

• The P10 features a 10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-
TX) which automatically selects the most appropriate operating conditions via auto-
negotiation.
• The P11 has the features of P10 plus a 10 Mb fiber-optic port (10BASE-FL) operating at
820 nm (near infra-red) using ST connectors.
• The P12 has the features of P10, plus a 100 Mb fiber-optic port (100BASE-FX) operating at
1300 nm (far infra-red) using ST connectors.

All interfaces are capable of operating either as half-duplex (compatible with all Ethernet
infrastructure) or full-duplex interfaces (which allow a potential doubling of network traffic). Note
that only one port may be connected to a network at one time.

With the H12 host module, the E1 consolidated option mirrors the functionality and performance
of the P10, while the E3 option performs like the P12 module.

The 70 Series IEDs come preconfigured for TCP/IP interface with an IP address, a SUBNET mask,
and a ROUTER (GATEWAY) address. They also have a preconfigured NSAP address for an OSI
network. It is very important that the network have no duplicate IP or NSAP addresses.
Configuration of these addresses may be accomplished by using UCA, by using the 70 Series
Configurator, or via a front panel serial port using a terminal emulator such as HyperTerminalTM
or ProCommTM. Please refer to sections 3.1.1 and 5.5.2 that provide additional information and
commands for changing these addresses.

If using the IEC61850 protocol the IP address may be configured from either the 70 Series
Configurator software or from the IEC61850 IED Configurator software. A user radio button
selection is provided on the 70 Series Configurator Identity page, giving a user the flexibility to
decide which software tool will control the IP address configuration setting, which is loaded upon
reboot. IP address configuration settings will be stored in either the INI file or MCL file. The INI
files are loaded by the 70 Series Configurator and the MCL file is loaded by the IEC61850 IED
Configurator.

104
M87x/EN M/O

The units are pre-configured for TCP/IP with an IP address/subnet mask/gateway address of:

192.168.0.254 / 255.255.255.0 / 192.168.0.1

and for OSI with an NSAP of:

49 00 01 42 49 09 01 01

The 70 Series IEDs use the following port numbers for each type of protocol:

PROTOCOL PORT NUMBER


DNP 20000 (TCP, UDP)
FTP (recommend passive mode) 20, 21 (TCP)
Modbus 502 (TCP)
MMS (UCA & 61850) 102 (TCP)
SMTP (electronic mail) 25 (TCP)
SNTP (network time sync) 123 (UDP)
Telnet 23 (TCP)

8.2 Features

 10/100 Megabit auto-negotiable copper interface with RJ-45 connector (P1x, E1, E3).
 Optional 10 Megabit fiber optic interface with ST connector for 62/125um glass fiber (P11)
 Optional 100 Megabit fiber optic interface with ST connector for 62/125um glass fiber (P12
and E3)
 Compliant to IEEE 802.3-1996 and IEEE 802.3u-1995
 Compliant to UCA Utility Initiative Statement Of Work Rev 7
 Compliant with IEC61850 Part 3 and Part 8-1 TCP/IP T-profile physical layer option 1 (copper)
 Compliant with IEC61850 Part 3 and Part 8-1 TCP/IP T-profile physical layer option 2 (100 Mb
fiber - P12 only).
 Fully automatic port switching with manual override capability
 Six indicator LEDs (P1x)/Two indicator LEDs (E1, E3)
 Protected, utility-grade copper interface

8.3 Specifications (For P1x Modules Unless Otherwise Noted)

Ethernet Connection:

(-P10/ E1) 10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-TX)

(-P11) 10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-TX)
820 nm 10 Mb fiber-optic port (10BASE-FL).

(-P12/E3) 10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-TX) 1300 nm
100 Mb fiber-optic port (100BASE-FX).

Indicator LEDs: P1x: Link, 10/100Mb, Collision, Duplex, Transmit, Receive

105
M87x/EN M/O

E1: Activity, Link; E3: Activity, Duplex

Bus Interface: Standard 5V CompactPCITM Backplane

Power Requirements: 50mA @ 3.3Vdc and 500mA @ 5Vdc (supplied from backplane)

Hot Swap (P1x only): Complies with Hot Swap specification PICMG 2.1 R1.0 for Basic Hot
Swap (requires Host Processor re-boot).

This product contains fiber optic transmitters that meet Class I Laser Safety requirements
in accordance with the US FDA/CDRH and international IEC-825 standards.

8.4 Environmental

Operating Temperature: -40 to 70C

Relative Humidity: 0-95% non-condensing

Installation Category: IC III (Distribution Level), Pollution Degree 2. Refer to definition on


page 9.

8.5 Physical

Connections: RJ45 (copper), ST connectors (62/125um glass fiber)

Package: CompactPCITM (3U, 4HP) removable module (P1x only)


Option integrated into H12 host module (E1, E3 options)

8.6 Hot Swap (HS) Compatibility (P1x Modules)

The blue Hot Swap LED located on the front panel is illuminated to indicate when it is
permissible to extract a board in systems that support the Full Hot Swap System Model. The
M87x currently supports the Basic Hot Swap System Model. The Basic Hot Swap System Model
does not illuminate the blue LED. The blue LED will turn on briefly when a card is inserted into
an energized device or when the device is reset. If the blue LED remains illuminated after
insertion into an M87x or remains illuminated after the S10 Host module has booted, the
associated card is malfunctioning.

8.7 Hardware Configuration

Configuration of the Ethernet interface is not normally required. The M87x is normally able to
detect and adapt to any type of equipment attached to it. Under very rare circumstances, the
user will need to manually configure the link for P1x modules using a jumper block on the
Ethernet interface board. For the vast majority of cases, the factory default jumper settings
(which is equivalent to having no jumpers installed) will provide the best possible link speed and
reliability. The factory default locations for the two jumpers are 1-2 and 5-6. Section 8.13.1
details other jumper setting suitable for special situations.

106
M87x/EN M/O

8.8 Cabling

The Ethernet interface uses a RJ-45 connector for copper interfaces and ST connectors for the
optional fiber interfaces. "Straight-through" copper cables rated Category 5 (Cat5) or above up
to 100 meters (328 feet) in length can be used The cable used for the P1x modules MUST be
100Ω STP (shielded twisted pair) for proper EMI/RFI performance. For the E1 or E3 options UTP
(unshielded twisted pair) cable is satisfactory for the network connection. If a connection to a
non-networked PC is desired, a "cross-over" cable can be used between the Ethernet card and
the PC. Category 3 (Cat3) cable is not recommended due to the lack of upgradeability to 100
Mb Ethernet. Fiber-optic cable up to 2000 meters (6500 feet) in length (412 meters or 1350 feet
for 100 Mb half-duplex) can be used. The cable should be multimode glass with a 62.5 mm core
and 125 mm cladding (62/125), ST connectors for the M87x end and proper terminations for the
network end (either ST or SC). The M87x supports only one Ethernet connection.

8.9 Connections

Copper network connections are made by simply plugging in the two cable ends. Ensure that
the network end terminates in a port that is not labeled "uplink". An optical connection is made
by connecting the TX port of the Ethernet interface to the RX port of the network hub or switch.
The RX port then connects to the TX port. Use of external equipment using SC connectors is
possible by using properly terminated cable or adapters. A few seconds after connection,
green LINK indicators at each device should illuminate to indicate a proper connection has
been established.

8.10 Troubleshooting the Connection

If a link is not established, verify that the RX and TX signals are not swapped (either by
misapplying a "cross-over" cable or an "uplink" port or swapping the optical cables). If a
connection is still not made, refer to Section 8.13.2 for suggestions.

8.11 Indicators

The Ethernet interface has six LEDs for use by users on the P1x modules, but only two LEDs on
the E1 or E3 option.

LED FUNCTION
P1x E1 E3E3
LK LNK Indicates a valid Physical connection. Must be on before any communicates takes place.
100 On when operating at 100 Mb, off for 10 Mb. Valid only when LINK is on.
COL Flashes when an Ethernet collision occurs. See explanation below.
FULL FULL On when operating in full-duplex mode, off for half-duplex.
TX Flashes when packet is being transmitted
RX Flashes when any packet is being received (even packets not addressed to this device).
ACT ACT Flashes activity when packets are transmitted and received

The collision LED, in particular, is a good indication of network health. It lights whenever the
M87x and another device attempt to use the link at the same time (by definition, full duplex links
cannot have collisions). Collisions are an expected part of normal half-duplex Ethernet
operations and the hardware transparently retries up to 16 times to send the message. If

107
M87x/EN M/O

collisions occur more often than about once per second, it indicates a very heavily loaded
network which is probably delivering messages late. If a large number of collisions occur, it is
suggested that either the network speed be increased to 100 Mb or the hubs replaced with
Ethernet switches.

8.12 Software Configuration

The M87x is able to determine the capabilities of the network equipment if the equipment
supports auto-negotiation. If auto-negotiation is not supported, the M87x will be able to
determine the network speed through a process known as parallel detection, but it cannot
determine the duplex capability. In order to allow the M87x to operate in half or full-duplex, the
user must supply the choice for the cases where the mode cannot be determined. Each
communication protocol will supply a method to individually set the 10 Mb and 100 Mb duplex
values for these cases. Half-duplex is always the safest choice since it is compatible with all
legacy equipment. Full-duplex allows a potential doubling of the network speed and an
extension of the 100 Mb fiber length. Consult your network administrator before setting the
duplex configuration to full since this can cause serious network problems if misapplied.

8.13 Technical Details

Bitronics has secured a block of Ethernet addresses from the IEEE. They are of the form:

00-D0-4F-xx-xx-xx

The actual unique 48-bit address is marked on the circuit board above the jumper block.

The remainder of this section may be skipped by casual users and is pertinent only to P1x
modules. The Ethernet board uses an AMD 79C972 ("Pcnet Fast+") media access controller
(MAC) which interfaces directly to shared PCI memory on the cPCI bus. It interfaces to a
National DP83843 ("PHYTER") Physical Layer Controller (PHY) via an on-board MII interface. The
PHY interfaces directly to the magnetics module of the copper interface and the 100BASE-FX
optical transceiver. It indirectly interfaces to the 10 Mb optics via a Micro Linear ML4669
10BASE-FL to 10BASE-T adapter. The user jumper block connects to the PHYTER AN0/AN1 pins
and allows all 9 combinations of these pins to be used. The Ethernet software driver allows
access to a modified copy of the 16-bit PHYSTS (PHY status) within the PHY for link type
determination.

The Ethernet driver automatically manages link state changes. If the link is ever determined to
be lost, it continuously searches for a new link. This search begins by resetting the PHY to allow
the jumper block setting to be used. If this fails to provide a link, the PHY is configured to auto-
negotiate while advertising all combinations or 100BASE-TX, 10BASE-T, half-duplex, and full-
duplex. This will attempt linkage using both auto-negotiation and parallel detection. If this fails
and 10BASE-FL is supported, the PHY is reconfigured for forced 10 Mb mode to allow the 4669
to transmit an optical link idle signal (some network vendor’s equipment refuse to generate the
optical link idle unless they receive a link idle). If 100BASE-FX is supported, the PHY is
reconfigured for forced 100 Mb mode using the PECL signals and an unscrambled data stream.

108
M87x/EN M/O

Once a link is established, the link type is tested. If the link was established through auto-
negotiation, which did not provide an indication of duplex capability, it is set according to the
user configuration as described in the previous section.

109
M87x/EN M/O

8.13.1 Jumper Settings (P1x)

The jumper block allows setting of the Ethernet card to emulate less capable equipment or to
force speed and/or duplex of the network interface. For most systems, the factory default (no
jumpers) will provide the best connection. Use of other modes should be done only after careful
consideration.

JUMPER MODE
100FX AN1 AN0
none 1-3 none Force 10BASE-T (or 10BASE-FL) half duplex
none 3-5 none Force 10BASE-T (or 10BASE-FL) full duplex
none none 2-4 Force 100BASE-TX (or 100BASE-FX) half duplex
none none 4-6 Force 100BASE-TX (or 100BASE-FX) full duplex

none none none Auto-negotiate 10BASE-T half+full duplex, 100BASE-TX half+full duplex (FACTORY DEFAULT)
none 1-3 2-4 Auto-negotiate 10BASE-T half+full duplex
none 1-3 4-6 Auto-negotiate 100BASE-TX half+full duplex
none 3-5 2-4 Auto-negotiate 10BASE-T half-duplex + 100BASE-TX half-duplex
none 3-5 4-6 Auto-negotiate 10BASE-T half
7-8 none 2-4 Force 100BASE-FX half duplex
7-8 none 4-6 Force 100BASE-FX full duplex

Figure 10 - Ethernet Board Jumper Locations (Rev 1 and Later Boards)

110
M87x/EN M/O

8.13.2 Troubleshooting

If the Link LED fails to illuminate, this is an indication that there is trouble with the connection
and communication will not proceed without solving the problem. If a copper connection is
used between the M87x and the hub/switch, check the following items:
 Verify that the connectors are fully engaged on each end.
 Verify that the cable used is a "straight-through" cable connected to a "normal" port.
Alternatively, a "cross-over" cable could be connected to an "uplink" port (this could later
cause confusion and is not recommended).
 Verify that both the M87x and hub/switch are powered.
 Try another cable.
 If a long CAT-5 cable is used, verify that is has never been kinked. Kinking can cause
internal discontinuities in the cable.
 Try removing the jumpers (the factory default).

If a fiber-optic connection is used:


 Verify that the hub/switch matches the Ethernet card port. A 100BASE-FX port will NEVER
inter-operate with the 10BASE-FL port (fiber auto-negotiation does not exist).
 Try swapping the transmit and receive connector on one end.
 Verify that the hub/switch uses the proper optical wavelength (10BASE-FL should be 820 nm
and 100BASE-FX should be 1300 nm). Note that the Ethernet card may take up to 12
seconds before it enables the 10BASE-FL transmitter, but it leaves the transmitter on for
about 5 seconds before giving up.

If a copper connection is used to an off-board fiber converter:


 Verify that the LINK LED on the converter is lit on at least one side. Both sides need to be lit
for a valid connection to be established.
 At least one brand of converters will not output an optical idle unless it receives a forced 10
Mb copper link pulse (for some reason, auto-negotiation pulses confuse it). Some
hubs/switches will not output an optical idle unless they receive an optical idle. This then
inhibits the converter from outputting a copper link pulse enabling the M87x to link. In this
condition, no device completes the link. To get around this condition, some device needs to
start a valid signal to "get the ball rolling". The M87x Ethernet card can be manually
configured via jumpers for either "Force 10BASE-T half duplex" or "Force 10BASE-T full
duplex" which guarantees that the converter will see a valid 10 Mb copper link pulse. This
then causes it to output an optical idle which the hub/switch turns around to an output
optical idle which the converter then turns into a copper idle signal which then allows the
Ethernet card to link and everything works. See the above section for the proper jumper
settings. This method even works if a fiber-to-copper converter is also used at the hub end
(i.e., using copper Ethernet interfaces on both ends with a fiber-optic cable between them).
 Follow the suggestions for the all copper and all fiber system troubleshooting.

If both the LINK LED and the RX LED are both constantly on and the hub/switch indicates that it
is not transmitting, the system is in the "false link" state. One known cause is using a non-auto
negotiating 100BASE-TX hub/switch and setting the jumpers for "force 10BASE-T" mode.
Moving the jumpers back to the factory default locations will cure this problem.

8.13.3 PHYSTS Register Contents (P1x)

111
M87x/EN M/O

The Ethernet software driver supplies to the upper protocol layers a modified copy of the
PHYSTS register of the PHY controller chip at the time a link is established. Many of the bits in
the register are of no use to the M87x user. Bit 0 is the least significant bit.

BIT DESCRIPTION
9 1=Auto-negotiation enabled for the M87x
3 1=Link partner auto-negotiable, 0=network hub/switch does not support auto-negotiation
2 1=Full Duplex, 0=half duplex (differs from PHYTER register definition) (reflects duplex LED)
1 1=10 Mb speed in use, 0=100 Mb speed (if 100 LED on, then this bit is zero)
0 1=Link valid (follows Link LED).

112
M87x/EN M/O

8.13.4 Statistics Gathered by Ethernet Driver

The Ethernet driver gathers various statistics (stats) on transmit and receive activity. These can
be useful to diagnose network problems or to simply determine network loading. The stats are
gathered into a contiguous group of 4-byte unsigned integers. The first integer represents the
number of receive stats. The second integer is a constant representing the number of transmit
stats. This is followed by all receive stats, then all transmit stats. This format was chosen to
allow extending the number of stats without affecting software that read old stats. For
example, regardless of the number of receive stats, the first transmit stat will be offset by
2+number of receive stats. In the "C" programming language, this means the first receive stat
would be at array[2] and the first transmit stat would be at array[array[0]+2]. The array content
is:

ARRAY OFFSET DESCRIPTION


0 - Number of receive statistics (constant == 14)
1 - Number of transmit statistics (constant == 9)
2 0 Total received bytes (only multicast frames which pass logical address filter are counted)
3 1 Total received frames (multicast frames rejected by logical address filter are not counted)
4 2 Multicast bytes received (this is mainly OSI ES/IS Hello messages)
5 3 Multicast frames received
6 4 Broadcast bytes received (this is normally IP ARP messages)
7 5 Broadcast frames received
8 6 Broadcast frames accepted by hardware hash filter but rejected by software
9 7 Frames with CRC errors (does not included packets with non-integral number of bytes)
10 8 Frames with CRC errors and non-integral number of bytes
11 9 Frames with FIFO overflow (this are really bad errors indicating system malfunction)
12 10 Frames discarded because byte count exceeded Ethernet maximum of 1518
13 11 Frames with "BUFF" error (this is a really bad error indicating system malfunction)
14 12 Frames dropped because memory not available (this is a really bad error)
15 13 Frames dropped because infrequent interrupt response (this is a really bad error)
16 0 Total transmitted bytes
17 1 Total transmitted frames
18 2 Frames not sent on first try due to another device transmitting in half-duplex (deferred)
19 3 Frames never sent due to "excessive deferral" (this is a really bad network error)
20 4 Frames sent after one collision
21 5 Frames sent after between 1 and 16 collisions
22 6 Frames never sent due to more than 16 collisions ("excessive collisions").
23 7 Frames only partially sent due to transmit underflow (really bad system error)
24 8 Frames with late collisions (probably due to full-duplex network and we are half-duplex)

113
M87x/EN M/O

9.0 DIGITAL INPUT / OUTPUT MODULE P30A, P31, P33

9.1 Introduction

The high speed Digital I/O module features 8 (P30A) or 16 (P31) inputs that are fully isolated
from each other and the case. The terminals of 4 of these are shared with 4 output relays.
Other than the terminals themselves, the output relay circuits are completely independent of
the inputs. The P33 has no inputs and 8 output relays.

Because the output relay terminals are shared with inputs, they may be monitored to provide
feedback verifying proper operation of output commands. Protection and control industry
standard-type output relays ensure system reliability.

The inputs are jumper-selectable for input level and threshold (thresholds of 15Vdc or 70Vdc).
The outputs are jumper-selectable for "normal" output state (Normally Open or Normally
Closed) and for relay condition (energized or de-energized). The input LED indicator is green
when an input is driven high, and the output LED is amber when an output is activated (relay
activated).

The Digital I/O Module inputs can be read by the Host Processor Board and/or the Analog-
Digital Signal Processor Board. Input transition times are time-stamped. Outputs can be
turned on or off by the Host Processor based on commands received over communication links,
or by internal states generated by energy pulses, recorders, etc.

The Analog-Digital Signal Processor Board reads the state of the digital inputs every time it
samples the analog inputs, and the sample rate of the digital inputs is tied to the frequency of
the analog inputs. The Waveform and Disturbance Recorders may be configured to record the
status of the digital inputs.

Consult the appropriate Protocol manual for information on reading the digital inputs or setting
the digital outputs.

9.2 Features

 Two input ranges, for nominal system voltages of up to 100V or from 100 to 300V.
 Inputs protected against continuous overload to 300Vdc on low input range.
 All Input / Output terminals protected with internal transient limiting devices.
 Protection and control industry standard-type output relays and circuitry ensure system
reliability.
 Outputs on the P30A/P31 have "wrap-around" inputs to allow confirmation of circuit
operation.
 2000Vac, 1min isolation, I/O to Case; 1500Vdc, 1min isolation, I/O to I/O
 Removable terminal block for ease of installation

114
M87x/EN M/O

9.3 Specifications

Inputs: 8 (P30A) or 16 (P31) uni-directional, isolated inputs (4 are shared with output
relays ) jumper selectable for voltage range. Input terminals have internal 510V
clamp.

Low Input Voltage Range


Input Range: 0 to 100Vdc
Threshold Voltage: 15V dc +/-1V (at 25C)
Input Resistance: 33kΩ

High Input Voltage Range


Input Range: 0 to 300Vdc
Threshold Voltage: 70Vdc +/-3.5V (at 25C)
Input Resistance: 153kΩ

Input Channel-to-Channel Time Resolution: 200µs (maximum)

Outputs: 8 isolated outputs on P33; 4 isolated outputs, terminals shared with 4 inputs
(P30A, P31); jumper selectable for Normally Closed (NC) or Normally Open (NO)
operation and for energized or de-energized condition. Output terminals have
internal 510V clamp.

Output Maximum Switched Current (Resistive)

Tripping
(C37.90 Continuous Break
Voltage Resistive) Carry (Inductive)
24Vdc 30A 5A 8A
48Vdc 30A 5A 700mA
125Vdc 30A 5A 200mA
250Vdc 30A 5A 100mA

Input De-bounce Time: Selectable, from 60ns to 260s in 60 ns steps.

Output Operate Time (time from command by Host, does not include protocol delays)
Assert (Close time with "N.O." jumper): 8ms
Release (Open time with "N.O." jumper): 3ms

Input Delay Time (from terminals): <100µs

Indicator LEDs
Inputs: Green, on when input voltage exceeds threshold.
Outputs: Amber, on when relay coil is energized.

Isolation
I/O Terminals to Case: 2000Vac, 1min
I/O Channel to Channel: 1500Vdc, 1min

115
M87x/EN M/O

Input / Output Capacitance, any Terminal to Case: 1400pF

Power Supply Requirements:3.3Vdc, 5Vdc, +/-12Vdc (supplied from backplane)

Hot Swap: P30A, P31 complies with Hot Swap specification


PICMG 2.1 R1.0 for Basic Hot Swap (requires Host Processor re-
boot)

9.4 Environmental

Operating Temperature: -40C to 70C

Relative Humidity: 0-95% non-condensing

Installation Category: IC III (Distribution Level), Pollution Degree 2. Refer to definition on


page 9.

9.5 Physical

Connections: Removable Terminal Blocks, accepts #16-28AWG


(1,4-0,09mm) wire. Recommended Torque Rating is 2.2 In-Lbs, 0.25
N-m. Standard 0.150" (3,81mm) header socket accepts other
standard terminal types. Solid core wire is recommended, or
stranded wire with the use of “bootlace ferrules,” where these are
available.

Package: P30A: CompactPCITM (3U, 4HP) removable module


P31: CompactPCITM (3U, 8HP) removable module
P33: CompactPCITM (3U, 4HP) removable module

9.6 Hot Swap (HS) Compatibility

The blue Hot Swap LED located on the front panel is illuminated to indicate when it is
permissible to extract a board in systems that support the Full Hot Swap System Model. The
M87x currently supports the Basic Hot Swap System Model. The Basic Hot Swap System Model
does not illuminate the blue LED. The blue LED will turn on briefly when a card is inserted into
an energized device or when the device is reset. If the blue LED remains illuminated after
insertion into an M87x or remains illuminated after the Host module has booted, the associated
card is malfunctioning.

9.7 Description

9.7.1 P30A

The Digital I/O Module consists of two circuit boards, the CompactPCITM Interface Board (692),
and the I/O Board (693). The Interface Board contains the CompactPCITM backplane connector

116
M87x/EN M/O

and interface circuitry, front panel LEDs, and jumper blocks for output relay power-up
configuration.

The I/O Board contains the analog input and isolation circuitry, output relay and drive circuitry,
as well as input protection and EMI/RFI suppression.

9.7.2 P31

The P31 Digital I/O Module consists of four circuit boards, the CompactPCITM Interface Board
(692), the LED Daughterboard (717), and two I/O Boards (693 supports pins 1-16, and 716 for
pins 17-32). The Interface Board assembly contains the CompactPCITM backplane connector
and interface circuitry, front panel LEDs, and jumper blocks for output relay power-up
configuration.

The I/O Boards (693 and 716) contain the analog input and isolation circuitry, input protection
and EMI/RFI suppression, as well as output relay and drive circuitry (693 only).

9.7.3 P33

The P33 Digital Output Module consists of two circuit boards, the main board (803) contains the
CompactPCITM Interface and all of the output circuitry. Moveable jumpers are located on this
board that are used to set each relay output as either normally open (NO) or normally closed
(NC). Daughterboard (803A) consists of the LED’s used to indicate the relay status. An LED is
turned on when its respective relay coil is energized.

9.8 System Design Considerations

9.8.1 Input / Output Impedance

On the P30A and P31, all of the output relay terminals are shared with the circuitry for a digital
input. As a result, there is always an impedance across the output relay contacts, even when
the relay is not energized. The value of the impedance depends on the configuration of the
input, or more specifically, the setting for the input threshold. The input circuitry is shown in
Figure 11 (pg.112). THIS PARALLEL IMPEDANCE WILL CAUSE A CURRENT TO FLOW THROUGH
ANY LOADS THAT ARE CONTROLLED BY THE RELAY WHEN THE RELAY CONTACTS ARE OPEN.
IT IS IMPORTANT TO CONSIDER THIS CURRENT WHEN SELECTING THE INPUT THRESHOLD,
AND WHEN DESIGNING SYSTEMS USING THE OUTPUT RELAYS.

If the input is set for a low threshold (15V), then the impedance across the relay terminals is
33kΩ. On a 125Vdc system, this equates to a maximum of 3.8mA, depending on the
impedance of any loads in the loop. If the input is set for a high threshold (70V), then the
impedance across the relay terminals is 153kΩ. On a 125Vdc system, this equates to a
maximum of 817μA, depending on the impedance of any loads in the loop.

9.8.2 Input Assignments

Due to the shared nature of some of the I/O circuitry, careful planning should be used in
assigning the inputs and outputs of the P30A/P31 module. The user is reminded that the first
four inputs on either module are shared with the four outputs. SERIOUS SYSTEM AND/OR

117
M87x/EN M/O

PRODUCT DAMAGE COULD RESULT FROM HAVING AN OUTPUT RELAY OPERATE WHILE
CONNECTED TO AN INPUT. For this reason, it is recommended that the user assign inputs 5-8
(those not shared with inputs) prior to using the first four inputs. The output relays can be
completely disabled on a per-channel basis enabling the safe operation of the first four inputs if
desired. See section 9.10.4.

9.9 Debounce Time Setting

The Digital Input Module can filter the inputs to compensate for “chattering” relays, etc. The
debounce time may be set using the 70 Series Configurator software, via the various protocols.
An input transition is not recognized until the input remains in the new state for a time longer
than the debounce time. Values between 60 ns and 4 minutes are acceptable.

An event triggered from the digital inputs will be subject to the debounce time setting for the
digital input. Digital input traces in the Waveform and Disturbance files are the instantaneous
status of the inputs, and DO NOT reflect any debounce time settings. If a long debounce time is
set, it is possible to see an event on the digital input that does not cause a trigger.

118
M87x/EN M/O

Figure 11 - Simplified Input / Output Circuitry and Terminal Assignment P30A, P31

119
M87x/EN M/O

Figure 12 – Simplified Output Circuitry and Terminal Assignment P33

120
M87x/EN M/O

9.10 Setting Digital I/O Module Jumpers

9.10.1 Disassembly of the P30A Module

To set the jumpers on either board of the Digital I/O Module, the boards must first be separated:

1. Remove the three screws as shown:

Figure 13 - P30A Module Disassembly

2. Gently pull apart the boards by the inter-board connector near the back of the module.

Reassembly is performed in the reverse order.

9.10.2 Disassembly of the P31 Module

1. Remove the six screws (three per side) indicated in Figure 13, and set aside the shields
labeled PCB 712. Identify the main circuit boards that comprise the P31 assembly. They
are labeled 693, 692, and 716.
a. PCB 693 contains:
• Terminal block for I/O points 1-8 (pins labeled 1-16 in blue).
• Range jumpers for input points 1-8.
• Normally open/normally closed jumpers for output points 1-4.
b. PCB 692 contains:
• Power-up condition jumpers for output points 1-4.
c. PCB 716 contains:
• Terminal block for I/O points 9-16 (pins labeled 17-32 in red).
• Range jumpers for input points 9-16.

2. Note: If you only need access to the jumpers for configuring the digital output relays,
there is no need to remove PCB 716, and you may skip this step. Otherwise, (for access to
the range jumpers for input points 9-16) remove the two screws indicated in Figure 14.

121
M87x/EN M/O

Locate P8 (the 16 pin array connecting PCB 716 to PCB 692) and gently pry the pins from
the header.

3. For access to the range jumpers for input points 1-8, the normally open /
normally
closed jumpers for output points 1-4, and the power-up (energized / de-
energized)
condition jumpers, locate P1 (the 36 pin array connecting PCB 693 to PCB
692)
and gently pry the pins from the header.

Reassembly is performed in the reverse order.

Remove

Figure 14 - P31 Module Disassembly

9.10.3 CompactPCITM Interface Board (692) Jumper Settings

The CompactPCITM Interface Board (692) has jumper blocks (P7) to set the output relay power-up
configuration, which is the state (coil energized or de-energized) at which the relays go to when
power is first applied to the module. The actual contact state is determined by the relay Normally
Open (NO) or Normally Closed (NC) jumper (Section 9.10.4). By default, no P7 jumpers are installed
at the factory, which sets the output contact state to de-energized (open when configured for
NO), which should be sufficient for most applications. If it is necessary to change the power-up
configuration, jumpers may be installed on P7 as follows:

Power Up Configuration
Jumper Function ON OFF Output Relay NO Output Relay NC
P7 PUC1 X Output 1 set to OPEN Output 1 set to CLOSED
P7 PUC1 X Output 1 set to CLOSED Output 1 set to OPEN
P7 PUC2 X Output 2 set to OPEN Output 2 set to CLOSED
P7 PUC2 X Output 2 set to CLOSED Output 2 set to OPEN
P7 PUC3 X Output 3 set to OPEN Output 3 set to CLOSED
P7 PUC3 X Output 3 set to CLOSED Output 3 set to OPEN
P7 PUC4 X Output 4 set to OPEN Output 4 set to CLOSED
P7 PUC4 X Output 4 set to CLOSED Output 4 set to OPEN

122
M87x/EN M/O

P7

Figure 15 – P7 Jumper Location

9.10.4 I/O Board (693) Jumper Settings

There are several jumpers for setting the input range and threshold on the I/O board and for the
normal state of the output relay contacts. The board and jumper locations are shown in Figures
16 and 17. Range jumpers for Inputs 1-8 are located on PCB 693; inputs 9-16 (P31 only) are on
PCB 716. The jumpers are red in color for high visibility. Refer to the beginning of this section for
the procedure to access the jumpers.

When the input jumper is installed, the input is in LOW RANGE mode. Removing the jumper places
the input in HIGH RANGE mode. THE FACTORY SETTING IS HIGH RANGE (JUMPER IS PLACED IN
THE STORAGE POSITION). REFER TO SECTION 9.8.

The relay outputs can be set for Normally Open (NO) or Normally Closed (NC) operation. To enable
Normally Open operation, which is the factory setting, place the jumper from "C" (common) to
"NO". To enable Normally Closed operation, place the jumper from "C" to "NC".

The relay outputs can be disabled if desired by placing the jumper vertically, from the "NC" to the
"NO" contacts, or by removing the jumper entirely. This may be desirable if only the inputs are
going to be used on these terminals, and the user wishes to guarantee the outputs do not operate
(see figure 18).

123
M87x/EN M/O

Range Jumpers,
input points 1-4

Range Jumpers,
input points 5-8

Figure 16 - Jumper Locations for Digital Input / Output Module (693)

Range Jumpers,
input points 9-16

Figure 17 - Jumper Locations for Digital Input / Output Module (716)

124
M87x/EN M/O

A - Normally Open
B - Normally Closed
C- Relay Disconnected (Storage)

Figure 18 - Relay Output Configuration Jumper

9.10.5 Health Status Digital Output Setting (Optional assignment of Digital Output 1 of
Module 0)

Digital Output 1 of Module 0 may be assigned to operate when the value of the Health variable
is <1. To set up Digital Output 1 in this manner, it is necessary that the Relay Output 1
Connection Jumper be set for Normally Closed operation. Therefore, during normal operation,
the unit is actively holding the contacts of the output relay open (no alarm). If an erroneous
operation is detected, or there is a power supply failure, the contacts of the output relay will
close (alarm).

The function of this output may be assigned for Health status by using the 70
Series Configurator, along with the Normally Closed jumper connection installed for Relay
output 1.

9.10.6 Disassembly of the P33 Module

No additional disassembly is required, aside from removing the module from the chassis, to
access the relay jumpers.

9.10.7 Digital Output Board (803) Jumper Settings

There are several jumpers for setting the normal state of the output relay contacts. The board
and jumper locations are shown in Figure 19.

125
M87x/EN M/O

A - Normally Open - Default


B - Normally Closed

Figure 19 - Relay Output Configuration Jumper

126
M87x/EN M/O

10.0 TRANSDUCER INPUT MODULE P40

10.1 Introduction

The Transducer Input Module features 8 separate inputs each with two terminals, one which
provides a unique return path for each input. This permits the inputs configured as current inputs
to be series connected to multiple transducer input devices and inputs configured as voltage
inputs to be parallel connected to multiple transducer input devices. The input terminal
assignments are shown in figure 20.

The inputs are jumper-selectable for three different transducer input formats. The inputs can be
jumpered for either 0–1 mA or 4-20 mA current inputs or for 0–10V voltage inputs. Both the 0-1
mA and 0 -10 V formats are bipolar (bi-directional) such that they span (-)1mA to (+)1mA and (-
)10V to (+)10V respectively. Each format allows for input over-range such that inputs exceeding
the normal range can still be reported accurately. The reportable range for each input type is
approximately: (+/-) 2.5 mA for 0-1mA inputs; (+/-) 12.5V for the 0-10V inputs; and 0 to 25mA for
4-20mA inputs.

Each transducer input can be independently configured for any of the three input formats. This
permits one Transducer Input Module to be used to read eight analog inputs with any mix of the
three standard current and voltage formats. Transducer Input Modules can only be ordered pre-
configured for one standard input type (all inputs are pre-configured at the factory for one input
type), however, each input on every Transducer Input Module is calibrated to support all format
types. Changing an input’s type is easy and only requires changing that input’s jumper setting.
The jumper settings are documented in section 10.8.1, below.

Each transducer input is sampled by a 24-Bit delta sigma analog to digital converter, adjusted
by a factory set pre-stored gain and offset calibration constant, and then converted to a 16-Bit
integer value. The Host Processor Board updates the transducer input values in the floating point
database every 500msec by reading each input’s 16-Bit integer value and converting it to a
floating point value. By default the floating point value represents the actual current (in mA) or
voltage (in volts) present at the input. The Host Processor can be configured (via the Mx70 Series
Configurator software) to independently scale each transducer input’s floating point value. The
scaling is accomplished by assigning a floating point value to the extreme values of the
transducer input’s format. Input scaling is described in detail in section 10.8.2, below.

Consult the appropriate Protocol manual for information on reading the transducer inputs and
the available calculation types.

127
M87x/EN M/O

Figure 20 - Terminal Assignment

10.2 Features

 Each input has jumper selectable ranges for support of 0 to (+/-)10 volt, 0 to (+/-)1mA, and 4-
20mA transducer input formats.
 All input terminals protected with internal transient limiting devices and spark gap protection.
 Module meets CompactPCI Hardware Hot Swap specification.
 Design includes local microcontroller with 24-bit sigma delta analog-to-digital converter.
 Robust local microcontroller design incorporates local watchdog and continuously monitors
offset and gain calibration constants integrity via checksum calculation.
 Removable terminal block for ease of installation

128
M87x/EN M/O

10.3 Specifications

Inputs: 8 bi-directional, jumper selectable for voltage or current range. Input terminals
have internal transorb clamp and 90V spark gap protection.

0 – 10V Voltage Range


Overload Range: -12.5 V to +12.5 Vdc
Resolution: 0.381 mV
Input Resistance: 10KΩ

0 – 1mA Current Range


Overload Range: -2.5 mA to +2.5 mA
Resolution: 0.0763 μA
Input Resistance: 500Ω

4 – 20mA Current Range


Overload Range: 0 mA to +25 mA
Resolution: 0.381 μA
Input Resistance: 50Ω

Common Mode Input Range +/- 9V, Input to Chassis

Common Mode Error


Vcm DC: 0.3% of FS @ 9Vp Common Mode
Vcm 50/60Hz AC: 0.1% of FS @ 9Vp Common Mode

Accuracy 0.25% of Full Scale Input

Data Update Rate (poll rate): 100 ms minimum (single P40 Transducer input module)
500 ms minimum (multiple P40 Transducer input
modules)

Input Capacitance, any Terminal to Case: 470pF

Power Supply Requirements:3.3Vdc, 5Vdc, +/-12Vdc (supplied from backplane)

Hot Swap: Complies with Hot Swap specification


PICMG 2.1 R1.0 for Basic Hot Swap (requires Host Processor
re-boot)

10.4 Environmental

Operating Temperature: -40C to 70C

Relative Humidity: 0-95% non-condensing

Installation Category: IC III (Distribution Level), Pollution Degree 2. Refer to


definition on page 9.

129
M87x/EN M/O

10.5 Physical

Connections: Removable Terminal Blocks, accepts


#16-28AWG (1.4-0.09mm) wire. Recommended Torque
Rating is 2.2 In-Lbs, 0.25 N-m. Standard 0.150" (3.81mm)
header socket accepts other standard terminal types.

Recommended Wire: Twisted pair, solid core wire (preferred), or stranded


wire with the use of “bootlace ferrules,” where these are
available.

Package: CompactPCITM (3U, 4HP) removable module

10.6 Hot Swap (HS) Compatibility

The blue Hot Swap LED located on the front panel is illuminated to indicate when it is
permissible to extract a board in systems that support the Full Hot Swap System Model. The
M87x currently supports the Basic Hot Swap System Model. The Basic Hot Swap System Model
does not illuminate the blue LED. The blue LED will turn on briefly when a card is inserted into
an energized device or when the device is reset. If the blue LED remains illuminated after
insertion into an M87x or remains illuminated after the Host module has booted, the associated
card is malfunctioning.

10.7 Description

The Transducer Input Module is a one board design that contains the CompactPCITM backplane
connector and interface circuitry, jumper blocks for the input type selection, the input transient
protection circuitry, an analog-to-digital converter, a local microcontroller and the input
terminal block.

10.8 System Design Considerations

10.8.1 Input Type Jumper Settings

Transducer Input Modules are ordered by specifying an input type and the module is shipped
from the factory with all inputs configured for that specified transducer input type. The input
type configuration is determined by jumper settings and can easily be re-configured in the field.
Each input of the Transducer Input Module can be independently configured to support either
the 0 to 1mA, 4 to 20mA, or 0 to 10V transducer input formats.

130
M87x/EN M/O

Input # 8
Input # 7
Input # 6
Input # 5
Input # 4
Input # 3
Input # 2
Input # 1

Figure 21 – P40 Input Type Jumper Locations

Each input has two configurable jumper blocks. One jumper block configures the hardware (the
actual input circuitry), the other jumper control block configures the firmware and software driver
(informs drivers of the status of the hardware selection). It is extremely important that when
reconfiguring any input, that both the hardware jumper setting and firmware jumper setting for
that input match (select the same input type).

Figure 21 (P40 Input Type Jumper Locations) shows the location of each input’s jumper block pair.
Each jumper block pair consists of two three pin headers and each header is shipped with a
shorting block. The position of the shorting block on the header determines the input type
configuration. Figure 22 (P40 Input Type Jumper Configuration) demonstrates the shorting block
positions for the three valid input configuration options.

0 - 10V

0 - 1mA

4 - 20 mA

Figure 22 – P40 Input Type Jumper Configuration

131
M87x/EN M/O

10.8.2 Transducer Input Scaling Configuration

The floating point values for the Transducer Input points on all present Transducer Input Modules
will appear in the M87x floating point database. By default, values for Transducer Inputs
configured as voltage inputs will be in volts and values for Transducer Inputs configured as
currents will be in milliamps. Database points for which there are no corresponding Transducer
Input points will report as zero.

The 70 Series Configurator software provides for gain and offset scaling for each Transducer
Input. This permits transducer inputs to appear in primary units. The 70 Series Configurator
allows the user to enter two specific primary values for the associated transducer input values
and automatically calculates the correct offset and gain corrections. See Figure 23 (70 Series
Configurator Software Transducer I/O Configuration Screen).

In the screen snap shot shown in the Figure 23, the first Transducer Input card has the first three
inputs configured for type 0-1mA, inputs 4 through 6 configured for type 4-20mA inputs, and the
remaining two inputs configured as type 0-10V inputs. All inputs except for 5 and 6 will appear
in the database in default units (milliamps for inputs 1 through 4 and volts for inputs 7and 8).

10.8.3 Setting the Data Update Rate (Poll rate) for P40 Transducer Inputs

The poll rate is now settable through the Transducer Input page. Poll rate has been added as a
settable value starting with the release of Configurator v3.02. A poll rate as low as 100 ms can
now be set for certain applications. Refer to the specifications when setting the poll rate for
Transducer Inputs on M87x. See Figure 23, which shows an example of settings made using the
70 Series Configurator Software on the Transducer Input page.

132
M87x/EN M/O

Figure 23 – 70 Series Configurator Software Transducer Input Configuration Screen

Suppose the device connected to input 5 is a temperature transducer with an output range from
4 to 20mA that corresponds to a temperature of 0 to 100 degrees C. Configuring the 4mA setting
to report as 0 and the 20mA setting to report as 100 will scale the value in the M87x database to
the primary units of the transducer. If this same transducer is connected to input 6 and the
scalings are changed to -32 and 212 respectively, the value will appear in the M87x database in
degrees F.

133
M87x/EN M/O

APPENDIX A - CROSS TRIGGERING

Cross-Triggering

There are many possible uses for the Input / Output functions available from 70 Series
Recorders, but Cross-Triggering deserves special attention since it is prerequisite to the
application of distributed recording.

Intelligent Electronic Devices (IEDs) like microprocessor-based relays or 70 Series Recorders are
generally used to measure the electrical parameters associated with a particular load, such as
a feeder for example. In contrast, most dedicated Sequence-of-Events (SOE) Recorders or
Digital Fault Recorders (DFRs) collect measurements from all points of interest throughout an
entire substation or load center. Those devices generally produce recordings that include the
activity of all points in a single document facilitating analysis by showing everything on a
common time scale. A consolidated document like that can be produced by time-synchronized
distributed IEDs by combining files captured by each of the recorders.

In order to consolidate all the recordings from IEDs distributed throughout a substation, all the
IEDs must first be made to trigger simultaneously whenever an event of interest is sensed by
any one unit in the substation. That mechanism is referred to as Cross-Triggering. Recordings
are then downloaded and combined by software designed for that purpose (described
elsewhere). This appendix will concentrate on methods available for cross-triggering
distributed IEDs.

70 Series Recorders support two mechanisms for cross-triggering one another. These
mechanisms are vendor-independent so may be used in combination with protective relays
and other IEDs to the extent that status and control points are available or that protocols are
supported by the other devices.

1. Hard-wired, using discrete digital I/O. Contacts wired in parallel on a dedicated cable
pass a voltage signal to the status inputs on each IED when an event is sensed. The status
input on each device can then be configured to trigger a recording.

2. Ethernet:
a. using GOOSE. Status points are communicated across an Ethernet LAN using the IEC-
61850 standard. The principal advantage of GOOSE messaging is that it does not require
a separate dedicated control cable for physical contacts.
b. using GSSE. Status points are communicated across an Ethernet LAN. The principal
advantages of GSSE are interoperability with legacy equipment and simplicity of
configuration. All 70 Series firmware released from April 2004 to June 2008 supported
UCA. The term “GOOSE” when used in the UCA context is equivalent to GSSE as defined by
IEC-61850. GSSE messaging can be set up with the 70 Series Configurator alone. The IED
Configurator is not required for GSSE.

The 70 Series Recorder provides considerable flexibility in how a user could customize these
methods to fit the constraints of any particular application. An exhaustive description of all
possible variations is not practical, but it is useful to provide an example of each method in a
typical application.

134
M87x/EN M/O

Example 1. Discrete Digital I/O:

Please refer to Figure A1 for wiring, Figure A2 through A4 for configuration, and Figure 11,
section 9.9 for the pin-out of the Digital I/O cards and internal resistor values that are not
shown in Figure A1.

Note: Standard Digital I/O cards (P30A and P31) incorporate an internal parallel current path
on all digital outputs which conducts through a resistance even when the output contacts are
open. This is normally used as a parallel digital input circuit but it makes the standard card
unsuitable for cross-triggering because it tends to pull-up the switched conductor when
contacts are open. To use cross-triggering as shown in this example, be sure to specify
optional P30AW (8-point) and P31W (16-point) Digital I/O cards when ordering M87x models.

Unit Unit Unit

-P30 -P30 -P30

P30 Digital I/O Cards


from three different
M871 Units
IN IN IN

RP (optional)
IN IN IN

IN IN IN

IN IN IN

IN IN IN
O O O
U U U
T T T

IN IN IN
O O O
U U U
T T T

IN IN IN
O O O
U U U
T T T
IN IN IN
O O O
U U U
T T T

HS HS HS

Switched (+)

+
-

Figure A 1

Wiring:

Figure A1 illustrates one digital output (lower pair, pins 1 and 2 on a P30AW card) from each of
three M871 units wired in parallel. Closing the Output 1 contact on any M871 will energize the
switched conductor. The upper pair, pins 9 and 10, are digital inputs wired in parallel between
the switched and negative conductors. All three units will sense a status change on Input 5
whenever the switched conductor is energized or de-energized. All digital inputs on the M871
incorporate an internal current limiting resistor so no external resistor is required to prevent
shorting (+) to (-) when digital outputs operate. It may be advisable, however, to place one pull-

135
M87x/EN M/O

down resistor (RP, in Figure A1) between the switched and negative conductors to prevent
chatter on the inputs. Acceptable values for RP depend on the application, but something in the
100kΩ to 500kΩ range should generally be safe in most cases.

Configuration:

Figure A2 illustrates a typical configuration that will initiate an oscillography recording and an
SOE Log entry when the current exceeds a threshold on any of the three phases.

Figure A 2

Since a high current on one feeder would not normally be sensed by any other IEDs in a
substation, a cross-trigger is necessary to initiate the oscillography recorders on all other IEDs.
Figure A3 shows how any condition that triggers Waveform Recorder 1 also operates Digital
Output 1 which initiates the cross-trigger. In this example, the contact dwells in the closed
position for the length of time that Waveform Recorder 1 is running. (The characteristics of
WR1 are set on a different page of the 70 Series Configurator.)

136
M87x/EN M/O

Figure A 3

Figure A4 shows the action taken when a cross-trigger on Digital Input 5 is sensed. In general,
receiving a cross-trigger from another device should have the same effect as triggering on
something sensed directly by the IED.

Figure A 4

137
M87x/EN M/O

Example 2. Ethernet, using GOOSE:

GOOSE is a function defined within the context of the IEC-61850 standard but there is no
requirement to make use of any other aspect of 61850 just to use GOOSE for cross-triggering
70 Series IEDs. Due to the level of multi-vendor support for IEC-61850, cross-triggering between
70 Series IEDs, microprocessor based relays, and other devices may be an advantage of using
GOOSE for cross-triggering. If a broader use of IEC-61850 is not intended, however, the user
may find cross-triggering via GSSE (see Example 3) just as effective and somewhat simpler to
set up.

In a broader application of IEC-61850, GOOSE could be used for much more than what is
described in this example, but when applied simply for cross-triggering, it can be envisioned as
a method to communicate a binary status over an Ethernet medium, exactly analogous to
status and control performed by discrete I/O points (see Example 1). GOOSE messages are
reliable enough to be used for controlling interlocks and protective relay blocking schemes, and
can be propagated even faster than discrete digital contacts because of the time that it takes
for moving mechanical parts to operate.

GOOSE operates by means of publication and subscription to unsolicited, unacknowledged,


multicast (sometimes anycast) messages on an Ethernet LAN, so GOOSE messages can not
pass through a router into another network. In its simplest form, such a network could consist
of as little as an Ethernet switch and the inter-triggered IEDs connected via conventional Cat. 5
cables. There is no need to uplink into any wider LAN or to operate with any other clients or
servers on the network (except for the purpose of configuring the IEDs). So in a substation,
security could be accomplished easily just by restricting physical access to the network.

Otherwise, when used in a secure general purpose network, GOOSE messaging can coexist
unobtrusively with other network traffic including file transfer services useful for collecting the
recordings captured by the IEDs.

Connection:

The M87x must be fitted with one of the available Ethernet options and be connected to a Local
Area Network (LAN). The minimum hardware requirement for an M87x to support 61850 is
64MB SDRAM on the Host Processor. Older units built with 16MB SDRAM can either be
upgraded with a new Host Processor Card (H11 or H12), or else cross-triggering could be
accomplished via GSSE (see Example 3) instead of GOOSE.

Configuration:

As implemented on the 70 Series IED, IEC-61850 requires two separate software programs to
configure. These are the IED Configurator (used to set up functions specific to 61850, like
defining Datasets, GOOSE publication and subscription, etc.) and the 70 Series Configurator (for
trigger logic, recorder settings, and other legacy functions). Both programs are supplied at no
cost with the M87x and are also available for download from the company’s public FTP site.

138
M87x/EN M/O

The following steps illustrate a typical configuration:

1. In the 70 Series Configurator, Figure A5 shows how any event of interest measured directly
by an M871 is configured to initiate an oscillography recording and make an SOE Log entry.
(Only Phase-A Amps is shown, but the Trigger window scrolls vertically and can hold up to
120 separate independent events.)

Figure A 5

2. The condition “Waveform Recorder 1 Started” is represented by a soft bit which is an


element in the IEC-61850 Object Model (Records/WrxRDRE1.ST.RcdStr.stVal). Other soft bits
are available to represent recorders WR2, DR1 and DR2 as needed (see 70 Series IEC-61850
manual, MICS document). The IED Configurator will be used in steps 4 and 5 below to make
the M871 publish a GOOSE message when this bit changes status. The bit is set when WR1
begins recording. It remains set until it is re-initialized.

Note: No self-initializing bits are defined by the 61850 object model so an entry must be
made in the 70 Series Configurator to re-initialize the bit a short time after it is set. Event 2
in Figure A6 illustrates that instruction. The choice of a particular duration (Event 2, far right
column) as the dwell time before the bit is reset is more-or-less arbitrary, but should
generally be shorter than the run-time of the recorder. No new cross-trigger can be sent via
GOOSE until the bit is re-initialized and WR1 has completed recording.

139
M87x/EN M/O

Figure A 6

3. When a cross-trigger is received from another unit, it comes in the form of a GOOSE
subscription (set up in the IED Configurator in step 7, below). GOOSE subscriptions are
represented in the 70 Series Configurator by binary inputs that can be used to trigger WR1
and make an entry in the SOE Log. In this example, events 3, 4, and 5 shown in Figure A7
are the binary inputs received by subscribing to the GOOSE messages published by three
other M871s on the network. This completes the settings that are made in the 70 Series
Configurator.

Figure A 7

4. The following settings must be made in the IED Configurator: Configuring an M871 to publish a
GOOSE is a two step process. Figures A8 and A9 illustrate the first step, defining a Dataset that
includes the soft bit described in step 2, above (Records/WrxRDRE1.ST.RcdStr.stVal).

140
M87x/EN M/O

Figure A 8

Note: In order to be used for GOOSE publication, the Dataset must be defined under
System\LLN0 as shown in Figure A9.

Figure A 9

5. The second step in publication is defining a GOOSE message, Figure A10. Up to eight
independent GOOSE publications may be defined for each device. Only one is required for
cross-triggering any number of other devices. System\LLN0\gcb01 is used in this example.
All default entries shown in Figure A10 should generally be used in most cases, but the user
must select the dataset defined in step 4, above, from the pull-down menu in the box
Dataset Reference. Then the Configuration Revision must be incremented to at least 1
(usually incremented automatically by the IED Configurator). This Revision number must
match the corresponding GOOSE subscription settings on all the other inter-triggered IEDs
on the network (see step 7, below).

141
M87x/EN M/O

Figure A 10

6. Each IED only needs to publish one GOOSE to cross-trigger any number of other devices.
When setting up subscriptions, however, the device must subscribe to every other device
from which a cross-trigger may be expected. For example, in a substation with four inter-
triggered M871 units, each unit would publish one and subscribe to three GOOSE messages.
Up to thirty-two separate status points may be defined for each device. These status points
correspond to elements in the Dataset transmitted by the GOOSE message.

Refer to the points named System\GosGGIO1\Ind1.stVal through


System\GosGGIO1\Ind32.stVal in Figure A11. These are the points in the IED Configurator
that correspond to the points in the 70 Series Configurator which were described in step 3,
above. In the 70 Series Configurator these points are named GOOSE binary input Ind1
through GOOSE binary input Ind32. See Figure A7, Events 3, 4, 5, etc.

142
M87x/EN M/O

Figure A 11

7. The IED Configurator makes it relatively simple to configure subscriptions when the MCL files
for all devices are open at the same time and the GOOSE publications have already been
configured on each of the other devices. See Figure A12. By clicking on the Browse button,
a window appears allowing the user to select the status point (green dot shown in Figure
A12). Selecting the point (Records/WrxRDRE1.ST.RcdStr.stVal) causes a subscription to be
configured for the GOOSE message that contains that status point. After selecting that
point, next click on System\GosGGIO1\Ind2.stVal (see left side of Figure A11) and repeat
step 7 selecting the same status point from the second M871 for the second subscription,
and again with System\GosGGIO1\Ind3.stVal for the third subscription, etc. until a
subscription has been made to each of the other IEDs on the network.

Figure A 12

8. Under Destination Parameters (see Figure A11 near bottom) verify that the pull-down
menu labeled Evaluation Expression indicates Pass through. This completes the
configuration settings for GOOSE subscription.

143
M87x/EN M/O

Example 3. Ethernet, using GSSE:

The GSSE service, as defined by IEC-61850, is identical to what has been called GOOSE in
connection with UCA2.0 in past years. In order to reduce confusion as far as possible, all
previous references to GOOSE in the UCA context have been replaced by the expression GSSE in
70 Series documentation because IEC-61850 supersedes UCA as a communications standard.

The use of GSSE to perform cross-triggering carries all the practical advantages of GOOSE and
is simpler to set up, but has much narrower multi-vendor support. It is, however, available on
all 70 Series IED firmware versions released since April 2004, so GSSE may be a better choice
when it is either unnecessary to trigger other devices, or when triggering other vendors’ devices
might as easily be accomplished with discrete digital I/O while using GSSE among the 70 Series
IEDs installed.

As with GOOSE, there is no need to make use of any other aspect of 61850 or UCA protocols
just to use GSSE for cross-triggering.

GSSE can generally be envisioned as a way to communicate a binary status over an Ethernet
medium, exactly analogous to status and control performed by discrete I/O points (see Example
1). GSSE messages are reliable enough to be used for controlling interlocks and protective relay
blocking schemes, and can be propagated even faster than discrete digital contacts because of
the time that it takes for moving mechanical parts to operate.

GSSE operates by means of transmitting and receiving unsolicited, unacknowledged, multicast


messages on an Ethernet LAN, so GSSE messages can not pass through a router into another
network. In its simplest form, such a network could consist of as little as an Ethernet switch and
the inter-triggered IEDs connected via conventional Cat. 5 cables. There is no need to uplink
into any wider LAN or to operate with any other clients or servers on the network (except for the
purpose of configuring the IEDs). So in a substation, security could be accomplished easily just
by restricting physical access to the network.

Otherwise, when used in a secure general purpose network, GSSE messaging can coexist
unobtrusively with other network traffic including file transfer services useful for collecting the
recordings captured by the IEDs.

Connection:

The M87x must be fitted with one of the available Ethernet options and be connected to a Local
Area Network (LAN). There is no other minimum hardware requirement for an M87x to support
GSSE. Older units that support UCA but not 61850 can exchange cross-triggers via GSSE from
newer units that support 61850.

Configuration:

All settings required for cross-triggering with GSSE are made in the 70 Series Configurator. The
following steps illustrate a typical configuration:

1. In the 70 Series Configurator, Figure A13 shows how any event of interest measured directly
by an M871 is configured to initiate an oscillography recording and make an SOE Log entry.
(Only Phase-A Amps is shown, but the Trigger window scrolls vertically and can hold up to

144
M87x/EN M/O

120 separate independent events.)

Figure A 13

2. The condition “Waveform Recorder 1 Active” is used to drive a Virtual Output that is linked to
a GSSE message as illustrated in Figure A14. A Virtual Output can be driven by individual
conditions (like RMS Amps A1 > 2000, in this example) or it could be the result of a
combination of several conditions defined through rudimentary triggering logic.

Figure A 14

Note: “Waveform Recorder 1 Active” can be considered to be a self-initializing condition


since it transitions from 0 to 1 when the recorder starts then returns to 0 (its initialized state)
when the recording is completed. Therefore, no deliberate step is necessary to re-initialize a
soft bit, as was required for “Waveform Recorder 1 Started” in step 2 of Example 2.

145
M87x/EN M/O

3. On the GSSE (Virtual I/O) page, define a GSSE Tx Name (“Unit_1” in this example) which is
unique to the device sending the GSSE message as illustrated near the bottom of Figure
A15.

Figure A 15

4. When a cross-trigger is received from another unit, it comes in the form of a GSSE message.
Each unique GSSE message must be associated with specific numbered Virtual Input as
seen on top half of the GSSE (Virtual I/O) page of the 70 Series Configurator shown in Figure
A15. Each device only needs to transmit one GSSE to cross-trigger any number of other
devices. When setting up for receiving a cross-trigger, however, the device must be
configured to receive GSSE messages from every other device from which a cross-trigger
may be expected. For example, in a substation with four inter-triggered M871 units, each
unit would transmit one GSSE and be configured to receive GSSE messages from all three
other units. Up to thirty-two separate Virtual Inputs may be defined for each device.

5. On the Recorder Triggers page of the 70 Series Configurator, each of the Virtual Inputs
defined in step 4, above, is then used to initiate the oscillography recorder and make an
entry in the SOE Log. See Figure A16. This completes the configuration settings for cross-
triggering by means of GSSE.

146
M87x/EN M/O

Figure A 16

147
M87x/EN M/O

APPENDIX B - FIRMWARE VERSION HISTORY

v1.11 New feature additions include user selection of measurements for the
Trend Recorder, user selection of overwrite mode for file storage, and user
selection of binary or ASCII Comtrade formats.
Firmware changes have been made to correct a time set error encountered
during daylight savings time. The Select-Before-Operate (SBO) configuration in
UCA has also been changed to correct a problem discovered in earlier versions.

v1.12 Fixed update of digital outputs via DNP

v1.13 New product release adds event system, sequence of events, UCA GOOSE,
and support for the P31 Digital Input/Output module.

v1.14-1.17 Maintenance Upgrades.

v1.18 Initial Firmware release for H11 host module. Support added for DNP event
reporting.

v1.19 Maintenance Upgrades

v1.20 Add support for H11 host module and enable configurable measurement
names.

V1.21 Add auto-blanking for extremely low-level measurement readings

v1.22-1.23 Maintenance Upgrades.

v1.24 Added support for multiple Digital I/O cards. Supports Rate of change
Triggers.

v1.25-1.26 Maintenance upgrade

v1.27 Added Measurements – Real & Reactive & Impedance for each phase.
Added Telenet protocol. Added DNP analog events & DNP frozen counters.
State of Time sync is now in database, viewable from Modbus, DNP, and Display
protocols and can trigger recorders.
Various maintenance upgrades

v1.28-1.29 Maintenance upgrades.

148
M87x/EN M/O

APPENDIX B

Firmware Version History

v2.05 New features


- Support for new Mx72 hardware (dual bus signal inputs).
- Support for new P40 module (transducer inputs).
- Added the following new measurements: bus 2 currents, bus 2 power,
bus 2 energy, bus 2 demands, unbalanced, transducer inputs.
- Added voltage fluctuation table
- Improved SOE log including adding user’s message
- Support CT wiring of CBA.
- All Digital Inputs are now recorded in Waveform Recorders.
- Digital inputs can support resetting the demands
- Created counters for digital and virtual inputs
- Added Zmodem command “attrib” .
- Added Recorder Active Bits for DR1,DR2,WR1,WR2.
Maintenance upgrades

v2.06 Maintenance upgrade

v2.12 New Features


- AND/OR logic and timers for triggers for virtual outputs
- Added the derivative of any measurement that has a rate of change trigger
to the measurement database
- Auto Event Notification
Maintenance upgrade

v2.15 Maintenance upgrade

v2.17 New Features


- Fault location (distance-to-fault)
- Adjustable sampling rate on waveform capture
Maintenance upgrade

V2.18 New Product Release


Added per phase Watts ,VAr, & VA.
Configurator & Biview improvements w/ modems.
Change to Digital I/O default watchdog contact (Configurator (setup not firmware
dependent).
Support new version of hardware on P3x, P4x modules.

V3.01 New Product Release


Implementation of IEC 61850 protocol
Added Support of SNTP for time synchronization
Added average 3-phase Amps & average 3-phase Volts

V3.02 New Product Release

149
M87x/EN M/O

Simplified configuration for distance-to-fault measurement


Improved transducer input data update rate
Improved accuracy on frequency measurement to 1mHz
Increased waveform capture length of individual file

V3.03 Maintenance Upgrade

V3.04 New Product Release


Added Peak Fault Current Measurements
Added Virtual I/O into Disturbance Recorders
Added support of control characters for text/SMS messages
Improved password security

V3.05 New Product Release


Added support for dual peak current input range M872 (S16, S17),
Added IEEE C37.232 naming convention
Added periodic triggering
Increased to 4 IEC 61850 buffered reports

V3.06 Maintenance Upgrade

V3.07 New Product Release


Increased pre and post trigger times for DR recorders
Modified base memory to 1MB

V3.08 Maintenance Upgrade

V3.09 Support for split core CT in M571 only


Added maximum voltage difference as additional trigger value

V4.01 Support for H12 and H12 Ethernet (E1, E3) modules

V4.02 Support for IEC 61850 deadbands

V4.07 Support for IEC 61850 configuration option and DNP3 certification
Maintenance upgrade

V4.082 Support for S1C Split-Core Option

V4.084 Maintenance upgrade

V4.09 Support for P33 module

V4.10 Maintenance upgrade

V4.11 Add double point status object for input bit pairs, add IEC61850 support
for P33 module

150
M87x/EN M/O

V4.13 Added SER .csv file; maintenance upgrade

V4.15 Maintenance upgrade

151
M87x/EN M/O

Declaration of Conformity (for CE marked models of M87x)

The Declaration of Conformity, DOC B001 that appears in this manual is applicable for M87x
models that are CE marked. The CE mark, if applicable, will be located on the case label found
on the side of the product.

If the CE mark is not contained on the product, then the Declaration of Conformity,
DOC B001, is not applicable for those particular products that do not bear the CE mark.

152
M87x/EN M/O

Revision Date Changes


A/B 05/01/2009 Update Bitronics Name, Logo, cover page
C 9/25/2009 Updates per New Firmware release: Updated frequency accuracy specification
in 1.3 &, 7.3; Updated standards in 1.4.2; Updated P40 Transducer input
module poll rate specification in 10.3, 10.8.3, & Figure 21. Increased
waveform recorder limit in 5.4.1 from 999 to 2000 cycles (or from 16.7 to
33.3 seconds at 60Hz). Added several paragraphs to address processing
limits associated with generating long length waveform recorder COMTRADE
files and recommendations to alleviate loss of data in long WR files.
Removed paragraph entitled “5.4.2c Using the Disturbance Recorder for
Fault Distance” and in 4.13 removed the reference to 5.4.2c.
Moved Network Time Synchronization from Section 5.8 to 5.8.5. Moved SNTP
from section 5.8.1 to 5.8.6. Rewrote section 5.8 through 5.8.7 to summarize
Time sync methods. Added the ability for a DNP slave to solicit a request for
time sync from the DNP master in order to periodically set the DNP time.
Added SNTP Time Sync, DNP Time Sync and Best Clock to 4.14 List of
Available Measurements.
D 10/15/10 Updates per new firmware release: Modifications to add section 5.13.6 for SMS
control characters, modifications in fault analysis section 6.14 including
adding Peak Fault Measurement, updated Measurement table in 6.15

E 2/28/11 Updates per new firmware release: inserted new section 5.4.5 covering IEEE
long file naming convention, 5.3.8 Periodic Triggering and updated signal input
and accuracy and revenue accuracy sections for dual peak range current
options.
F 11/27/11 Updates per new firmware release: Note regarding reallocation of memory for
recording and change to length of pre- and post-trigger time in DR in section
5.4
G 12/12/12 Added/corrected burden information on signal input modules S11, S14, and S17
on pages 2 - 4 and in section 7.3. Updated standards in section 1.4.2
Environment. Added information for new H12 host module and H12E1 and
H12E3 Host/Ethernet options in sections 2, 3, and 8. Modified input range spec
for digital I/O in low input range.
H 3/14/13 Updated for change to lithium battery to capacitor backup.
I 4/25/13 Updated firmware version table in support of IEC 61850 deadband release

J 10/28/2013 Revised Section 1.4.3. UL/IEC 61010-1 ed. 2 is replaced by to UL/IEC 61010-1
(ed.3) and IEC 6101-2-030 (ed.1).
Updated Signal input requirements based on UL project evaluation to standards
IEC61010-1 (ed.3) & IEC61010-2-030 (ed.1). Overcurrent protection specified for
VTs. Current measurement inputs are intended for connections to isolated
grounded secondary CT circuits to comply to UL/IEC 61010-1. Revised
associated sub-sections 1.3, 7.3, 7.4, 7.5, 7.6, and added 7.5.1. New DoC.
K 11/7/2014 Added current input information for S1C split-core option
L 11/17/15 Added support for P33 eight output module
M 3/09/16 Maintenance Upgrade, new firmware version
N 2/10/17 Updated manual for new DoC, changes to 1.4.2, revised 9.3 for isolation
specification on I/O channel to channel from 2000 Vac to 1500 Vdc. Added
section 5.4.8 for SER recording.
O 5/22/17 Updated firmware version, corrected error in section 1.4.2

153
M87x/EN M/O

154
Imagination at work

Grid Solutions
St Leonards Building
Redhill Business Park
Stafford, ST16 1WT, UK
+44 (0) 1785 250 070
www.gegridsolutions.com/contact

© 2017 General Electric. All rights reserved. Information contained in this document is indicative only.
No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project.
This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice.
Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

M87x/EN M/O

You might also like