0% found this document useful (0 votes)
218 views14 pages

BOQVIEWONLY

The document is a bill of quantities for electrical work at a hospital in Pithoragarh, Uttarakhand. It includes specifications for a 4 breaker panel in the substation, 2 oil cooled transformers, 2 diesel generator sets, laying of 500 meters of HT cable, and a main LT panel. The main LT panel will have microprocessor based circuit breakers and equipment for monitoring loads and energy usage.

Uploaded by

Vinay Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
218 views14 pages

BOQVIEWONLY

The document is a bill of quantities for electrical work at a hospital in Pithoragarh, Uttarakhand. It includes specifications for a 4 breaker panel in the substation, 2 oil cooled transformers, 2 diesel generator sets, laying of 500 meters of HT cable, and a main LT panel. The main LT panel will have microprocessor based circuit breakers and equipment for monitoring loads and energy usage.

Uploaded by

Vinay Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

BASE HOSIPTAL AT LINTHURA, PITHORAGARH, UTTARAKHAND

BILL OF QUANTITIES
SUB STATION/ DG SET/ EXTERNAL LIGHTING (3rd Call)

Name of the Bidder's Firm:

S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT


QTY GST (in Rs)
(in Rs)

1 FOUR BREAKER PANEL (IN THE SUBSTAION )


Supplying, installation, connecting, testing & Commissioning of one incoming, three
outgoing 11KV, 3 Phase, 3Wire, 50 Hz, effectively earthed, 350 MVA fault level
Vacuum Circuit Breaker as per IS: 13118, IEC-56, all steel totally enclosed, fully
Interlocked, Indoor industrial pattern, Metal clad, Horizontal drawout, floor mounting,
main Burbar & Earth Busbar shall be EC Grade Aluminium. The details are following.

INCOMER
1no.-Incoming each equipped with the following:
Vacuum Circuit Breaker-800Amp Three Phase
Current Transfomer-
Ratio: 70/1+1A
CL:1& 5P10, 15VA
Potential Transformer-
Ratio: 11KV/110V
CL:1/100VA
Relays-
IDMT 2 O/C+1 E/F RELAY
PT Transfer Scheme
METERS-
Digital Ammeter With selector switch
Digital Voltmeter With selector switch
PF meter
Set of indication Lamp-
Red-ON
Green-OFF
White-Trip Circuit Healthy
Amber-Trip Condition
Set of fine wiring, Ferrules & Fuses Power-Pack 110/24v DC Supply for simltaneous
tripping of three breakers.
BUSBAR-
A set of 800A copper bus bar with heat Shrink Sleeve.
OUTGOING-
3 nos-Outgoing Panels on 11KV BUS each equipped with the following:
Vacuum Circuit Breaker-630 Amp Three Phase
Current Transfomer-
Ratio: 70/1+1A
CL:1& 5P10, 15VA
Potential Transformer-
Ratio: 11KV/110V
CL:1/100VA
Relays-
IDMT 2 O/C+1 E/F RELAY
METERS-
Digital Ammeter With selector switch
Digital Entergy meter
Set of indication Lamp-
Red-ON
Green-OFF
White-Trip Circuit Healthy
Amber-Trip Condition
Set of fine wiring, Ferrules & Fuses.
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
TOTAL 4 PANEL BAORD COMPLETE 1.00 Sets 0.00
2 OIL COOLED TRANSFORMERS:
Supply, Installation & Testing Commissioning of INDOOR Oil cooled ONAN, 1000
KVA 11/0.433 KV, 3 Phase, 50Hz, Dyn11 vector group, copper wound, Transformer
with ON LOAD Tap Changer ,with RTCC Panel and with Tap Range + 5 to - 10 in
steps of 2.5 % having cable end box on HV side suitable of 3C x240 sq. mm. XLPE
cable of 11 KV grade and 5 nos 3-1/2 core 300 sq mm on LV side complete with all
accessaries. The insulation class A class and temp rise shall be limited to 50 in Oil 55 in
winding OTI, WTI with trip alarm contact .Transformer Impedance 5%, No Load
Losses - 1000 Watts, Load Losses 11.0 KW tolerance as per IS 2026

All instruments Contact wiring to be done up to Marshalling box.


Installation & testing shall be done by the electrical contractor in the presence of
engineer in charge .
The supplier shall certify that the Transformer has installed as per norms. 2.00 Sets. 0.00
3 DIESEL GENERATOR SETS:
D.G. SETS:
Supply, intastallation, testing & commissioning of 750 KVA Capacity water cooled DG
Set with suitable capacity Cummins make engine directly coupled with alternator for
415 volt, 3 phase, 50 Hz, 4 wire, generation system complete with accessories, fuel oil
tank & control panel etc as required and sound proof acquastic enclosure for the DG
SET, includind supply, fixing of antivibration pads suitable for 750KVA DG Set
dunlop make or make as per standards of Engine manufecture, provision of conrol cable
from engine to control panel to engine. Provision of pipe fuel pipe line of suitable size
fron fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and
fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as
recommended by manufecture heavey duty complete as required at site complete with
stand and battery charger residentials sylensor suotabe for diesel engine exhaust pipe line
complete complete flange, bend, flexible pipe all as required and as directed by engineer
incharge.

Gerb make or Resistoflex antivibration pads.


Day tank for fuel with markings
ECP Panel mounted on a separate frame.
Suitable space heater for alternators.
Lub oil drain arrangement.
Suitable amended arrangement for bus duct and arrangement for mounting differential
/REF CTs.
Suitable self priming pump with engine (if inbuilt in this model).
DG shall be completely filled with luboil & HSD 990 ltr day tank shall be completely
2.00 Nos 0.00
filled.
4 HT CABLE SUPPLY , LAYING & TERMINATIONS:
Supply of H.T. Cable
Supply of following 11 KV( UE) grade multicore Aluminium conductor XLPE insulated
cable, insulation screening with extruded semi conducting compound in combination
with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat
strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and
complete with all latest amendments etc. complete as required.
3 C x 240 Sq. mm 11 KV (UE) 500.00 Meter 0.00
PANELS :-
5 Main L.T. Panel
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Suppy , installation, testing, Design, manufacture, supply inspection, handling,
assembling, affecting proper connections, testing and commissioning of 14 SWG
CRCA sheet steel fabricated cubical type Main L.T. Panel with PLC based load
manager, floor mounting, dust & vermin proof, front operated construction, enclosure
class - IP 52, powder coated after proper treatment with 9 tank process with top/bottom
removable gland plates, as required, double compression type cable glands, earth bus,
hinged and lockable doors to achieve dust and vermin proof complete with all inter
connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The
Aluminium Bus Bar shall be of suitable length, 500 volts, 3 phase 50 Hz TPN,
electrolytic aluminium as per IS 8623 . The panel feeders shall be suitable for
terminating suitable nos. 3.5 / 4 core armoured aluminium cable or Aluminium Bus
Duct as required.
All incoming & outgoing MCCB's shall be microprocessor based with O/L & S/C and
E/F protection.
All MCCB's shall be Ics = 100% Icu, with rotary handle & pad locking arrangement,
with adjustable O/L & S/C trip setting as per load requirement. All TP MCCB shall be
with heavy duty solid isolable neutral link.
The breaking capacity specified for all MCCB's breakers is Ics value (service rating).

The instrument chamber shall be separate and shall comprise of flush type ammeter,
voltmeter, selector switches, cast resin type CT's & PT's, etc. Separate CT's shall be
provided for protective and measuring system and for APFCR of capacitor bank with
suitable VA.
All Energy Analyser / TVM Shall have RS 485 Modbus RTU on board Communication
protocol for SCADA communication.
The fault withstanding capacity of panel & its control gear shall be min. 35 KA rms for
1 sec.
GA drawings shall be got approved from Owners / Architects / Consultants before
fabrication.The panel has to be specifically fabricated as per the space available at
site. The existing column positions will also be considered.
INCOMERS from 2 Nos. 1000 KVA Transformers
The incoming ACB shall be micropocessor based with inbuilt O/L & S/C release with
E/F protection and all Outgoings MCCB's up to 250 amp shall be thermal-magnetic
based with inbuilt O/L & S/C release and MCCB's more than 250 amp to 800 amp shall
have microprocessor baed with in built O/L, S/C AND E/F Protection
All MCCB's shall have rotary handle & pad locking arrangement, with adjustable O/L
& S/C trip setting as per load requirement. All TP MCCB shall be with solid isolable
neutral link. The breaking capacity specified is Ics value. All outgoing MCB's shall be
C type with 10 KA breaking capacity.
All incoming ACB's shall be electrically interlocked with the bus coupler, DG incomers
and other transformer incomers.
All Incomers shall be of 4P, EDO with EN 6400 multifunction meters
All Outgoings shall be of 4P MDO type only but with ON and OFF indication lamps
TRANSFORMER INCOMERS : 1600 AMP FP EDO ACB - 2 SETS
All incoming ACB's shall be electrically interlocked with the bus coupler, DG incomers
and other transformer incomers.
Over Voltage / Under Voltage relay / release with timer.
Backup earth fault relay.
Master trip relay.
Trip Circuit Supervison relay.
TNC switch.
Auto manual selector switch.
1 nos. 0-500 volt range digital type voltmeter with selector switch
1 set of 3 CT's of ratio 1600/5A, Class 1.0 accuracy 15 VA burden for metering.
1 set of 3 CT's of ratio 1600/5A, Class 1.0 accuracy 15 VA burden for APFCR.
1 set of 3 CT's of ratio 1600/5A, Class 5P20, accuracy 15 VA burden for
PROTECTION .
1 no. 0-1600 Amp range digital type ammeter with selector switch.
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Energy analyser (digital type) consisting of I, V, KW, KWH, KVA, PF, HZ, MDI (EM
6400 of Conzerve or equi.) with RS 485 communication port for communication /
report generation.
Power factor meter.
Frequency meter.
3 Nos. LED type phase indicating lamps, each lamp shall be with bakup MCB along
with hooter, auxillary relay, 2 sets of push buttons.
5 Nos. LED type indicating lamp for indicating the status of feeder - ON / OFF / TRIP /
Trip circuit healthy / DC supply healthy. Each lamp shall be with bakup MCB.
DG INCOMERS : 1250 AMP FP EDO ACB - 2 SETS
All incoming ACB's shall be electrically interlocked with the bus coupler, DG incomers
and other transformer incomers.
Over Voltage / Under Voltage relay / release with timer.
Backup earth fault relay.
Master trip relay.
Trip Circuit Supervison relay.
TNC switch.
Auto manual selector switch.
1 nos. 0-500 volt range digital type voltmeter with selector switch
1 set of 3 CT's of ratio 1250/5A, Class 1.0 accuracy 15 VA burden for metering.
1 set of 3 CT's of ratio 1250/5A, Class 5P20, accuracy 15 VA burden for
PROTECTION .
1 no. 0-1600 Amp range digital type ammeter with selector switch.
Energy analyser (digital type) consisting of I, V, KW, KWH, KVA, PF, HZ, MDI (EM
6400 of Conzerve or equi.) with RS 485 communication port for communication /
report generation.
Power factor meter.
Frequency meter.
3 Nos. LED type phase indicating lamps, each lamp shall be with bakup MCB along
with hooter, auxillary relay, 2 sets of push buttons.
5 Nos. LED type indicating lamp for indicating the status of feeder - ON / OFF / TRIP /
Trip circuit healthy / DC supply healthy. Each lamp shall be with bakup MCB.
BUS COUPLERS
BUS COUPLER : 1600 AMP FP EDO ACB- 1 SETS
Protection releases / relays, Metering & Accessories for Bus Coupler (s)
Trip circuit supervision relay
TNC switch.
Auto / manual selector switch
5 Nos. LED type indicating lamp for indicating the status of feeder - ON / OFF / TRIP /
Trip circuit healthy / DC supply healthy. Each lamp shall be with bakup HRC
The bus coupler shall be electrically interlocked with all incoming ACB's in such a way
that at any one time two supply should not get mixed up.
BUS BARS
1 No of 2000 AMP , 415 Volts, 3 phase 50 HZ TPN high conductivity electrolytic
Aluminium bus bar of suitable length, SMC / DMC supports, with colour coading and
insulated by heat shrinkable sleeves and clip on shrouds for joints. The current density
of bus bar shall be minimum 1.00 sq mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 85 deg C. The
temperature rise should be restricted to 35 deg C above design ambient temperature of
50 deg C.
PLC for load management / automation
Design, manufacturing, testing at works, supply of PLC BASED , AUTOLOAD
TRANSFER,AUTO START AND AUTO STOP AUTOLOAD BALANCING
PANEL FOR 2 nos. 750 KVA D.G. sets AND AUTO ON OF TRASNFORMER
FEEDERS ONCE THE SUPPLY IS RESTORED, complete as required to acheive
the desired functions.
PLC shall be provided in main LT panel for interlocking between different incomers and
bus couplers to avoid unintentional paralleling of different supplies.
PLC is not envisazed for D G synchronization
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
In addition to required hardware and software following components shall also be
provided.
Based on the load requirement only required no. of DG sets shall be operated.
Monitoring of DG set safeties (mechanical as well as electrical).
PLC Hardware as required
Auxiliary relays/contactor/metering/protection etc as required
230 V AC, UPS of suitable rating
Annunciators as required
One no. Battery charger set consisting of Transformer / Rectifier, DC ammeter, DC
voltmeter, Charging rate selector switch, Off/Trickle/boost.
All control wiring from PLC to various feeders with min. of 2.5 sq mm copper FRLS
cable.
The PLC provided for Load Management & for interlocking of Breakers shall
perform to achieve the system as described in given Main Schemetic Diagram.
OUTGOINGS -
All outgoing feeders shall be provided with one set of phase indication lamps and trip
indication lamps with protection fuses/MCB and ammeter with selector switch with
suitable ratio CT's of accuracy class 1.0
ALL outgoing feeders shall be provided with electronic dual reading KWHR meter with
RS 485 communication port, CT's with accuracy class 1, control circuits and wiring as
per SLD.
2 nos. 800 AMPS TP MCCB (CAPACITOR PANEL)
2 nos. 630 AMPS FP MCCB (FOR EPD AND OPD BLOCK)
1 nos. 400 AMPS FP MCCB ( FOR ADMIN BLOCK )
2 nos. 400 AMPS FP MCCB ( FOR IPD BLOCK)
1 nos. 630 AMPS FP MCCB ( FOR MAIN HVAC FEEDER- AC MACHINES)
1 nos. 250 AMPS FP MCCB ( FOR SPLIT AC MACHINE PANEL)
2 nos. 200 AMPS FP MCCB (FOR VENTILATION AND PRESSIRISATION
PANELS)
1 nos. 400 AMPS FP MCCB ( FOR MAIN FIRE FIGHTING PANEL)
1 nos. 250 AMPS FP MCCB ( FOR MAIN PLUMBING PANEL PANEL)
2 nos. 160 AMPS FP MCCB ( FOR 2 NOS OF EXTERNAL LIGHTING PANELS )

1 nos. 160 AMPS FP MCCB ( FOR 1 NOS LIFT PANEL )


3 nos 630 amp FP MCCB's - spare
3 nos 400 amp FP MCCB'S -SPARE
SWITH BOARD COMPLETE WITH ALL INTERNAL WIRING, NAME PLATES
1.00 SET 0.00
AND COMPLETE IN ALL RESPECTS
6 External Lighting Panel
INCOMER:
1 Nos. 160 A TPN feeder each having one no. 160A TPN MCCB's with microprocessor
based releases with isolable neutral ,ON indication1 no. multifunction meter (showing
all power parameters), with selector switch, matching cast resin CT's.
BUS BAR
A set of TPN Aluminium bus bar with heat Shrink Sleeve rated for 200A (after
considering all necessary deratings) 3 phase 4wire, 50Hz.
A suitable minimum derating factor must be taken for calculation of bus bar sizes. The
bus bar size after derating shall be equal to the ampere given in the BOQ
Maximum current density of 1 Amp per sq.mm is suitable for the busbar.
OUTGOINGS
8 nos 32 A DP MCB's with ON indicationlamps
2 nos 25 A TPN MCB's with ON indicationlamps
Other items such as
1 Lot of control wiring
1 Set of designation plates 2.00 No 0.00
7 CAPACITOR PANEL- 350 KVAR
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Supply , Installation, Testing commissioning, Design, manufacture, supply, inspection,
handling, assembling, affecting proper connections, testing and commissioning of 14
SWG CRCA sheet steel fabricated cubical type 350 KVAR APFC Panel consisting
of 100 / 50 / 25 KVAR capacitor units in tier formation, housed in an integrated
cubicle type automatic switching ON and OFF control panel, floor mounting,
dust & vermin proof, front operated construction, enclosure class - IP 52,
powder coated after proper treatment with 9 tank process with top/bottom
removable gland plates, as required, double compression type cable glands,
earth bus, hinged and lockable doors to achieve dust and vermin proof
complete with all inter connections small wiring by min. 2.5 sq. mm. copper
wires, ckt labels etc. The Aluminium Bus Bar shall be of suitable length, 500
volts, 3 phase 50 Hz TPN, electrolytic aluminium as per IS 8623 .

All outgoings MCCB's shall be thermal-magnetic based with inbuilt O/L & S/C release.
All MCCB's shall be Ics = 100% Icu, with rotary handle & pad locking arrangement,
with adjustable O/L & S/C trip setting as per load requirement. All TP MCCB shall be
with heavy duty solid isolable neutral link. The breaking capacity specified is Ics value.
The instrument chamber shall be separate and shall comprise of flush type ammeter,
voltmeter, selector switches, CT's, PT's, etc
Capacitor duty contactors should be used for switching individual capacitor banks.
The fault withstanding capacity of panel & its control gear shall be min. 35 KA rms for
1 sec.
The capacitor panel shall be integrated with the main L T Panel as per schematic
diagram.
INCOMING
Incomer circuit breaker has been included in the main panel.
1 set- 3 CTs , ratio 100/5A Class 1.0 accuracy 15 VA burden for metering.
1Nos- (0-100A) digital Ameter with selector switch
Micro processor based automatic power factor control relay (including power
factor meter) in 8 steps for automatic cut off or add on capacitor units to keep
the power factor at 0.95 with variation of loads. All associated auxiliary
contactors / relays shall be provided with in the scope of work.
Phase indicating lamps with HRC fuses, and indicating in each capacitor chamber unit
to indicate On/Off status of capacitor unit.
BUS BARS
800 AMP, 500 Volts, 3 phase 50 HZ TPN high conductivity electrolytic Aluminium
bus bar of suitable length, SMC / DMC supports, with colour coding and insulated by
heat shrinkable sleeves and clips on shrouds for joints. The current density of bus bar
shall be minimum 1.00 sq mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 85 deg C. The
temperature rise should be restricted to 35 deg C above ambient temperature.
OUTGOINGS -
1 no. of 250 AMPS TPN 25 KA MCCB and 300 amps AC3 duty contactor
with 100 KVAR gas filled 415 V capacitor bank, auto-manual selector switch,
start stop push button for manual operation including on/off indicating lamps
and delay timer complete.
4 no. of 125 AMPS TPN 25 KA MCCB and 150 amps AC3 duty contactor
with 50 KVAR gas filled 415 V capacitor bank, auto-manual selector switch,
start stop push button for manual operation including on/off indicating lamps
and delay timer complete.
2 no. of 63 AMPS TPN 25 KA MCCB and 80 amps AC3 duty contactor with
25 KVAR gas filled 415 V capacitor bank, auto-manual selector switch, start
2.00 SET 0.00
stop push button for manual operation including on/off indicating lamps and
delay timer complete.
8 LIFT PANEL
INCOMER:
1 Nos. 160A TPN feeder each having one no. 160A TPN MCCB's with microprocessor
based releases with isolable neutral ,ON indication1 no. multifunction meter (showing
all power parameters), with selector switch, matching cast resin CT's.
BUS BAR
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
A set of TPN Aluminium bus bar with heat Shrink Sleeve rated for 200A (after
considering all necessary deratings) 3 phase 4wire, 50Hz.
A suitable minimum derating factor must be taken for calculation of bus bar sizes. The
bus bar size after derating shall be equal to the ampere given in the BOQ
Maximum current density of 1 Amp per sq.mm is suitable for the busbar.
OUTGOING
4 nos 63 A 4P 10 KA MCB's with indication lamps
Other items such as
1 Lot of control wiring
1 Set of designation plates 1.00 No 0.00
9 ADMIN MAIN PANEL TO BE LCOATED AT GROUND LEVEL
INCOMER:
1 Nos. 400 A 4P MCCB, 35 KA with microprocessor based releases ,ON indication1
no. multifunction meter (showing all power parameters), with selector switch, matching
cast resin CT's.
BUS BAR
A set of TPN Aluminium bus bar with heat Shrink Sleeve rated for 500A (after
considering all necessary deratings) 3 phase 4wire, 50Hz.
A suitable minimum derating factor must be taken for calculation of bus bar sizes. The
bus bar size after derating shall be equal to the ampere given in the BOQ
Maximum current density of 1 Amp per sq.mm is suitable for the busbar.
OUTGOING
5 nos 63 A TPN MCB's with indication lamps
3 nos 160 A 4P 25 kA MCCB's for abvoe floors with indication lamps
2 nos 160 A 4P 25 kA MCCB's for AC provisions with indication lamps
Other items such as
1 Lot of control wiring
1 Set of designation plates 1.00 No 0.00
10 MAIN PANEL OPD BLOCK AND EMERGENCY BLOCK
INCOMER:
1 Nos. 630A 4P MCCB's with microprocessor based releases ,ON indication1 no.
multifunction meter (showing all power parameters), with selector switch, matching cast
resin CT's.
BUS BAR
A set of TPN Aluminium bus bar with heat Shrink Sleeve rated for 800A (after
considering all necessary deratings) 3 phase 4wire, 50Hz.
A suitable minimum derating factor must be taken for calculation of bus bar sizes. The
bus bar size after derating shall be equal to the ampere given in the BOQ
Maximum current density of 1 Amp per sq.mm is suitable for the busbar.
OUTGOING
9 nos 63 A TPN MCB's with indication lamps
4 nos 200 amp 25 kA 4 P MCCB's with On indication lamp, multifunction meters with
selector switches and suitable CT's- casst resin type
Other items such as
1 Lot of control wiring
1 Set of designation plates 2.00 Nos 0.00
11 MAIN PANEL IPD BLOCK- 2 NOS
INCOMER:
1 Nos. 400A 4P MCCB's with microprocessor based releases ,ON indication1 no.
multifunction meter (showing all power parameters), with selector switch, matching cast
resin CT's.
BUS BAR
A set of TPN Aluminium bus bar with heat Shrink Sleeve rated for 400A (after
considering all necessary deratings) 3 phase 4wire, 50Hz.
A suitable minimum derating factor must be taken for calculation of bus bar sizes. The
bus bar size after derating shall be equal to the ampere given in the BOQ
Maximum current density of 1 Amp per sq.mm is suitable for the busbar.
OUTGOING
6 nos 63 A TPN MCB's with indication lamps
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
4 nos 125 amp 25 kA 4 P MCCB's with On indication lamp, multifunction meters with
selector switches and suitable CT's- casst resin type
Other items such as
1 Lot of control wiring
1 Set of designation plates 2.00 Nos 0.00
12 FLOOR DISTRIBUTION BOARDS :-
Design, manufacture, supply, installation, testing and commissioning of FLOOR
DISTRIBUTION PANELS fabricated out of 14 SWG CRCA sheet steel, wall / floor
mounting type. The sheet steel shall undergo minimum seven tank treatment followed by
finishing powder coating of min 60 micron thickness. the board includes 415 V
electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including
connection with outgoing feeders complete in all respect.
The MCCB's shall be with rotary handle & pad locking arrangement, with trip setting as
per load requirement. TP MCCB shall be with solid isolable neutral link. The breaking
capacity specified is Ics value. All incoming MCCB's shall be microprocessor based.
All outgoing MCCB's shall be thermomagnetic type. All outgoing MCB's shall be C type
with 10 KA breaking capacity.
The above board shall be complete with 3 nos. phase indicating lights, flush mounted
Ammeter, Voltmeter, CT's, PT's, selector switches, protective fuses etc. at Incomer with
all inter connections by min. 2.5 sq.mm. Copper wires. A MULTI FUNCTION METER
whic can read all the paramerters on iinput side
INCOMER : 200 AMP FP MCCB (35 KA) (OPD)
BUS BAR : 250 AMP FP Aluminium
OUT GOINGS : 8 nos. 63 AMP TPN MCB AND 2 NOS 100 AMO 16 KA MCCB

OUT GOINGS : 1 nos. 63 AMP TPN MCB AND 1 NO 100 AMP (SPARE) 2.00 SET 0.00
INCOMER : 160 AMP FP MCCB (35 KA) (EMERGENCY )
BUS BAR : 200 AMP FP Aluminium
OUT GOINGS : 8 nos. 63 AMP TPN MCB and 2 nos 100 amp 16kA MCCB
OUT GOINGS : 1 nos. 63 AMP TPN MCB and 1 no 100 amp MCCB 2.00 SET 0.00
INCOMER : 125 AMP FP MCCB (35 KA) (IPD-01 and IPD-02)
BUS BAR : 150 AMP FP Aluminium
OUT GOINGS : 6 nos. 63 AMP TPN MCB
OUT GOINGS : 3 nos. 63 AMP TPN MCB (SPARE) 5.00 SET 0.00
INCOMER : 125 AMP FP MCCB (35 KA) (service block)
BUS BAR : 150 AMP FP Aluminium
OUT GOINGS : 6 nos. 63 AMP TPN MCB
OUT GOINGS : 1 nos. 63 AMP TPN MCB (SPARE) 3.00 SET 0.00
UPS :-
13 UNINTERRUPTED POWER SUPPLY (UPS) for ADMIN BLOCK
Supply, installation, testing and commissioning of 30 KVA UPS along with lead acid
batteries, 6 Pulse rectifier + Filter + SNMP & IGBT Inverter based,complete as required.
30 KVA 3 phase input (415 V + 15% / - 25%), three phase output (415 V + 0.05%) 1.00 SET 0.00
with 20 minutes battery backup of each UPS complete with battery rack and
connecting wires.
Supply , installation , testing and commissioning 100A FP MCCB of 35KA breaking
Capacity in metal sheet enclosure with ON/OFF, TYB Indication lamps for Incoming of 2.00 Nos 0.00
30KVA UPS complete in all respect as required.
14 UNINTERRUPTED POWER SUPPLY (UPS) for OPD BLOCK
Supply, installation, testing and commissioning of 50 KVA UPS along with lead acid
batteries, 6 Pulse rectifier + Filter + SNMP & IGBT Inverter based,complete as required.
100 KVA 3 phase input (415 V + 15% / - 25%), three phase output (415 V + 0.05%) 2.00 SET 0.00
with 20 minutes battery backup of each UPS complete with battery rack and
connecting wires.
Supply , installation , testing and commissioning 160A FP MCCB of 35KA breaking
Capacity in metal sheet enclosure with ON/OFF, TYB Indication lamps for Incoming of 4.00 Nos 0.00
160KVA UPS complete in all respect as required.
15 UNINTERRUPTED POWER SUPPLY (UPS) for EMERGENCY BLOCK
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Supply, installation, testing and commissioning of 50 KVA UPS along with lead acid
batteries, 6 Pulse rectifier + Filter + SNMP & IGBT Inverter based,complete as required.
100 KVA 3 phase input (415 V + 15% / - 25%), three phase output (415 V + 0.05%) 2.00 SET 0.00
with 20 minutes battery backup of each UPS complete with battery rack and
connecting wires.
Supply , installation , testing and commissioning 160A FP MCCB of 35KA breaking
Capacity in metal sheet enclosure with ON/OFF, TYB Indication lamps for Incoming of 4.00 Nos 0.00
160KVA UPS complete in all respect as required.
16 UNINTERRUPTED POWER SUPPLY (UPS) for IPD BLOCK
Supply, installation, testing and commissioning of 50 KVA UPS along with lead acid
batteries, 6 Pulse rectifier + Filter + SNMP & IGBT Inverter based,complete as required.
100 KVA 3 phase input (415 V + 15% / - 25%), three phase output (415 V + 0.05%) 2.00 SET 0.00
with 20 minutes battery backup of each UPS complete with battery rack and
connecting wires.
Supply , installation , testing and commissioning 160A FP MCCB of 35KA breaking
Capacity in metal sheet enclosure with ON/OFF, TYB Indication lamps for Incoming of 4.00 Nos 0.00
50 KVA UPS complete in all respect as required.
UPS PANELS :-
17 UPS Panel (ADMIN BLOCK )
Incoming
1 Nos. 100 Amp FP MCCB of 35 kA Breaking capacity from outgoings of 30 KVA
UPS.
Indication/metering for each incoming
1 set of RYB phase Indication lamps with suitable rating MCB
1 set of ON/OFF indicating lamps along with 2A SP MCB backup protection.
1 set Digital Ampere meter with suitable rating CT and selector switch
1 set Digital Volt meter with suitable rating MCBs and selector switch
Busbar
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 415V,
125 amps, 35 kA, insulated with heat shrinkable coloured PVC sleeves & clip on
shrouds for joints. The busbar sizing calculations shall be submitted for approval,
considering all derating factors.
Outgoings
12 No.63 amp TPN MCB of 10 kA breaking capacity. 1.00 SET 0.00
18 UPS Panel (OPD AND EMERGECNY BLOCK)
Incoming
1 Nos. 160 Amp FP MCCB of 35 kA Breaking capacity from outgoings of 100 KVA
UPS.
Indication/metering for each incoming
1 set of RYB phase Indication lamps with suitable rating MCB
1 set of ON/OFF indicating lamps along with 2A SP MCB backup protection.
1 set Digital Ampere meter with suitable rating CT and selector switch
1 set Digital Volt meter with suitable rating MCBs and selector switch
Busbar
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 415V,
200 amps, 35 kA, insulated with heat shrinkable coloured PVC sleeves & clip on
shrouds for joints. The busbar sizing calculations shall be submitted for approval,
considering all derating factors.
Outgoings
18 No.63 amp TPN MCB of 10 kA breaking capacity. 2.00 set 0.00
19 UPS Panel (IPD BLOCK )
Incoming
1 Nos. 160 Amp FP MCCB of 35 kA Breaking capacity from outgoings of 100 KVA
UPS.
Indication/metering for each incoming
1 set of RYB phase Indication lamps with suitable rating MCB
1 set of ON/OFF indicating lamps along with 2A SP MCB backup protection.
1 set Digital Ampere meter with suitable rating CT and selector switch
1 set Digital Volt meter with suitable rating MCBs and selector switch
Busbar
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 415V,
200 amps, 35 kA, insulated with heat shrinkable coloured PVC sleeves & clip on
shrouds for joints. The busbar sizing calculations shall be submitted for approval,
considering all derating factors.
Outgoings
12 No.63 amp TPN MCB of 10 kA breaking capacity. 2.00 set 0.00
20 UPS Panel (SERVICE BLOCK )
Incoming
1 Nos. 125 Amp FP MCCB of 35 kA Breaking capacity from outgoings of 20 KVA
UPS.
Indication/metering for each incoming
1 set of RYB phase Indication lamps with suitable rating MCB
1 set of ON/OFF indicating lamps along with 2A SP MCB backup protection.
1 set Digital Ampere meter with suitable rating CT and selector switch
1 set Digital Volt meter with suitable rating MCBs and selector switch
Busbar
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 415V,
160 amps, 35 kA, insulated with heat shrinkable coloured PVC sleeves & clip on
shrouds for joints. The busbar sizing calculations shall be submitted for approval,
considering all derating factors.
Outgoings
8 No.63 amp TPN MCB of 10 kA breaking capacity. 1.00 set 0.00
21 SERVO STABLIZERs
Supply Installation 60 KVA of static electronic Automatic Voltage Stablizer
(unbalanced supply and un balanced loadl) frequency 50 HZ +/-3 HZ Three Phase 6.00 Nos 0.00
Onam type Cooling .
BY PASS PANEL FOR VOLTAGE STABLIZER 6.00 Nos 0.00

Supply Installation 30 KVA of static electronic Automatic Voltage Stablizer


(unbalanced supply and un balanced loadl) frequency 50 HZ +/-3 HZ Three Phase 2.00 Nos 0.00
Onam type Cooling .
BY PASS PANEL FOR VOLTAGE STABLIZER 2.00 Nos 0.00
22 ISOLATION PANEL
SYSTEM :- 230V AC 50Hz Single Phase
LOCATION & TYPE :- Indoor, cubical, wall mounted.
ENCLOUSRE :- IP42
ISOLATION PANEL
a) Isolation transformer capacity :- 10 KVA-PIECO MAKE.
b) Ratio :- 0.0423
c) Primary Voltage (Volts) :- 230V
d) Secondary Voltage (Volts) :- 230V
e) Cooling :- Air Cooled
f) Winding & type :- Cooper winding Double wound with shield grounded to isolated
ground bus.
OVERALL DIMENSION :- 1150mm H X 650mm W X 250mm D
INCOMER
ELCB HI TYPE :- 63A 30 mA. DP –HAGGER MAKE
MCB D CURVE :- 63A DP – HAGGER MAKE
OUTGOING
MCB D CURVE :- 12 Nos. 20A DP – HAGGER MAKE
LINE ISOLATION MONITOR :- Hazard Index 0-10MA. - PIECO MAKE
INDICATION
a) Meter :- Digital – PIECO MAKE
b) Indicating Lamp :- Red & Green for Zones
COOLING FAN :- 230V 4 inches
TOTAL 1 PANEL COMPLETE 1.00 Nos 0.00
23 LT CABLE AND ACCESSRIES
SUPPLY OF L.T. CABLE:
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Supplying of following sizes of 1.1 KV grade multicore aluminium conductor XLPE
insulated armoured cable conforming to IS:7098 (Part - I) complete with all amendments
etc. as required
3.5 C X 300 Sq.mm Al. XLPE arm. 480.00 Mtrs. 0.00
3.5 C X 240 Sq.mm Al. XLPE arm. 975.00 Mtrs. 0.00
3.5 C X 185 Sq.mm Al. XLPE arm. 340.00 Mtrs. 0.00
3.5 C X 150 Sq.mm Al. XLPE arm. 250.00 Mtrs. 0.00
3.5 C X 120 Sq.mm Al. XLPE arm. 190.00 Mtrs. 0.00
3.5 C X 95 Sq.mm Al. XLPE arm. 150.00 Mtrs. 0.00
3.5 C X 70 Sq.mm Al. XLPE arm. 135.00 Mtrs. 0.00
3.5 C X 50 Sq.mm Al. XLPE arm. 100.00 Mtrs. 0.00
3.5 C X 35 Sq.mm Al. XLPE arm. 120.00 Mtrs. 0.00
3.5 C X 25 Sq.mm Al. XLPE arm. 80.00 Mtrs. 0.00
24 SAFETY EQUIPMENT
Supply, installation and fixing of the following equipment at suitable place in the sub-
station building as required:-
M.S bucket of 9 liters capacity painted with red oxide paint & lettered as 'Fire' with
White and red mounted on freestanding stand, as required including filling with dry 4.00 Sets. 0.00
sand.
First aid box as approved by St.John Ambulance Brigade /Indian Red Cross society
6.00 Nos. 0.00
conforming to IS : 2217 - 1963.
Shock treatment chart duly mounted on a wooden frame with glass on, as required in 2
6.00 Nos. 0.00
languages (Hindi & English).
Rubber Mat 914.4 mm wide and 12 mm thick checkered rubber mat to withstand 11
KV dielectric strength confirming to IS : 5424 -1969 complete as required. 20.00 Mtr. 0.00

Supply and fixing of Carbon Dioxide fire extinguishers of 4.5 Kg each mounted on
6.00 Nos 0.00
wall hooks as per IS 2878-1976.
25 EXTERNAL LIGHTING
SUPPLY OF EXTERNAL LIGHTING SYSTEM
Supply of Ring shape LED post top ,Class I with ingress protection(IP) 65 W.
Housing made of Die cast Magnesium alloy and Diffuser board made of Poly
carbonate weight of 6.3 Kg and should be CCC, CE and RoHS compliant, wattage
should be 60 W, lumen out put should be 1500 and 2100 lumens for WW and NW 6.00 Nos 0.00
respectively, should contain 24 high power LEDs for better distribution,Such as
Philips BGP150 LED PSU 220-240V 7043 + 4 mt GI Tubular pole painted with PU
of RAL 7043 similar to Luminaire(Dark Gray)
ERECTION OF EXTERNAL LIGHTING FIXTURES
Installation, testing and commissioning of CFL / HPSV / MH / CDMT type post top
lantern with required lamps complete with, control gears, ballast, capacitor etc.
6.00 Nos 0.00
including connection with 3x1.5 sqmm flexible fire retardant copper connecting wire of
required length complete as required.
LED & SOLAR LIGHTING
Supply of LED Lights
Supply, installation, testing and commissiong of Street light luminaire having with
minimum 3350 lumens(system level), Housing made of Pressure Die-cast LM6
Aluminum, Lumen output minimum 3350lm,Color:Cool white,Voltage 220V-240V AC
50 Hz, Driver integral type,inuilt surge protection of minimum 4KV,Ip protection IP
65,class I,system Efficiency >75 lm/W,power factor>0.97, life class of minimum
50,000 burning hours @ L70,each led should have a penut lens to ensure proper lighting 10.00 Nos 0.00
distribution, should have inbult Hilo protection,Supply voltage range of 140-270V, , In
luminare the LED, driver, should be of same make.LM 79 and LM80 Reports to be
submitted from NABL accredited Lab to ensure above parameters,Such as Philips
BRP320 LED CW 034 NR S2 PSU GR
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Supply, installation, testing and commissiong of Solar street light with IP 65 LED
fixture having a system wattage of 43W of Philips BRP 403 make with 3500 lumen
system output, 2X100Wp high efficiency crystalline solar panel certified IEC 61215
and 2x100Ah tubular lead-acid battery with BIS approval. The LED driver should have
> 92% efficiency. The battery shall not be discharged beyond 75% of capacity. The solar
charge controller should be of Microprocessor Based MPPT make with 96% efficiency
and enclosed in IP 65 box. The charge controller shall provide all safety protections and
temperature compensated charging of the batter. The battery should be housed in a box
made from galvanized steel and powder coated so that it withstands corrosion. The solar
system should be mounted on a 7.0 Mtrs Octagonal Pole above ground. The solar
street light shall comply with standards such as IEC 61215,IEC 61730, IEC 62124, IEC 10.00 Nos 0.00
61347-2-13, IEC 62384, CISPR 15, IEC 61547, IEC 60598. Type test certificate with
compliance to EN 50530 should be provided . The solar panel and battery shall be of
reputed make and manufactured in India. The approved makes of LEDs are CREE,
Nichia and Philips Lumileds and LM80, LM 79 report to be submitted. The Panel
sizing and battery sizing need to be provided using insolation of 5kwh/sqm/day ,
efficiency factor from provided test certificate, dust factor of 0.75 , panel ageing of
10%, battery efficiency of 90%. The calculation should be for backup for 36 hours
such as Philips BRP 403 43W solar

Supply, installation, testing and commissiong of Street light luminaire having with
minimum 5600 lumens(system level), Housing made of Pressure Die-cast LM6
Aluminum,Color:Cool white,Voltage 220V-240V AC 50 Hz, Driver integral
type,inbuilt surge protection of minimum 4KV,Ip protection IP 65,class I,system
Efficiency >75 lm/W,power factor>0.97, life class of minimum 50,000 burning hours 0.00 Nos 0.00
@ L70,each led should have a penut lens to ensure proper lighting distribution, should
have inbult Hilo protection,Supply voltage range of 140-270V, , In luminare the LED,
driver, should be of same make.LM 79 and LM80 Reports to be submitted from NABL
accredited Lab to ensure above parameters ,Such as Philips BRP320 LED CW 034 NR
S2 PSU GR
Supply, installation, testing and commissiong of Solar street light with IP 65 LED
fixture having a system wattage of 28W(including driver lossses) of Philips BRP
402 make with 2300 lumen system output, 120Wp high efficiency crystalline solar
panel certified IEC 61215 and 12V 100Ah tubular lead-acid battery with BIS approval.
The LED driver should have > 92% efficiency. The driver loss should not be more than
10 % of system wattage. The battery shall not be discharged beyond 75% of capacity.
The solar charge controller should be of Microprocessor Based MPPT make with 94%
efficiency and enclosed in IP 65 box. The charge controller shall provide all safety 0.00 Nos 0.00
protections and temperature compensated charging of the battery. The battery should be
housed in a box made from galvanized steel and powder coated so that it withstands
corrosion. The solar system should be mounted on a 6.0 Mtrs Octagonal Pole(with
4mm thickness) above ground. The solar street light shall comply with standards
such as IEC 61215,IEC 61730, IEC 62124, IEC 61347-2-13, IEC 62384, CISPR 15,
IEC 61547, IEC 60598. Type test certificate with compliance to EN 50530 should be
provided . The solar panel and battery shall be of reputed make and manufactured in
Supply of Poles
Supply, installation, testing and commission of The pole shaft shall be made single piece
MS structure continuously tapered having polygonal (8/12 sides) cross section and a
single longitudinal welding.Top dia 70mm and bottom dia 130 mm, thickness 3mm ,
height 6m. The welding will be done as per BS 5135 / IS 9595. No circumferential
welding shall be allowed in the pole shaft. The MS shall conform to BSEN
100025/100027. The structure shall be single hot dip galvanized as per BS 729 / IS
2629. A suitably designed door shall be provided at approximate 700mm height from 0.00 Nos 0.00
the pole base. The door opening will be suitably reinforced for structural strength. The
door shall be flushed with pole external surface and shall provide easy access for
electrical connections at a maintainable height. A Suitable base flange will be welded
and plate reinforcements will be provided between base flange & pole. Base Plate
220x 220 x 16mm Foundation accessories will be as per IS 1367 of Philips make
SP6M0
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
Supply, installation, testing and commission of The pole shaft shall be made single piece
MS structure continuously tapered having polygonal (8/12 sides) cross section and a
single longitudinal welding.Top dia 70mm and bottom dia 130 mm, thickness 3mm ,
height 7m. The welding will be done as per BS 5135 / IS 9595. No circumferential
welding shall be allowed in the pole shaft. The MS shall conform to BSEN
100025/100027. The structure shall be single hot dip galvanized as per BS 729 / IS
2629. A suitably designed door shall be provided at approximate 700mm height from 20.00 Nos 0.00
the pole base. The door opening will be suitably reinforced for structural strength. The
door shall be flushed with pole external surface and shall provide easy access for
electrical connections at a maintainable height. A Suitable base flange will be welded
and plate reinforcements will be provided between base flange & pole. Base Plate
220x 220 x 16mm Foundation accessories will be as per IS 1367 of Philips make
SP7M0
Erection of Poles
Erection of 6/7 meter high street light GI pole including providing and casting in
position 'M20' grade reinforced cement concrete pole foundation i/c excavation of earth 20.00 Nos 0.00
in all kind of soils including foundation.
Supplying, drawing, connecting and testing of following size of PVC insulated FRLS
copper conductor (as per IS : 694) flexible multicore wire in the existing poles and
bracket from cable termination connector / MCB to the fitting i/c providing suitable
connectors
3 core 2.5 sq.mm (for 6/7 Mtr Poles) 200.00 M 0.00
26 BUS DUCTS - SANDWICH TYPE :
Supply ,Installation , Including Suspention, Testing and Commisioning of Following
Capacity Bus Trunking with Aluminium Bus Bar in 1.6mm Thick Sheet Steel Enclosed
in convenient sections for use on 3 phase, 4 wire, 415 volts 50 HZ AC Supply including
jointing of section flexible joints, expention joint, bends & earthing with 2 runs of
galvanised iron strips, suspenders, angle iron bracket steel fastner, connecting to the
earth system etc as required

1600 A 20.00 RM 0.00


1250 A 35.00 RM 0.00
27 H.T. Cable Laying-DSR ITEM
H V CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV
grade of following size direct in ground including excavation, sand cushioning,
protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm 500.00 Meter 0.00
28 H.T Termination: DSR ITEM
Supply and making Indoor cable end jointing with cast resin compund, including lugs
and other jointing materials for following size of 3 core, XLPE aluminium conductor
cable of 11KV ( UE )grade as required.
3 C x 240 Sq.mm ( 11KV UE ) 6.00 Sets 0.00
Supply and making Outdoor cable end jointing with cast resin compund, including lugs
and other jointing materials for following size of 3 core, XLPE aluminium conductor
cable of 11KV ( UE )grade as required.
3 C x 240 Sq.mm ( 11KV UE ) 2.00 Sets 0.00
29 EARTHING STATION : DSR ITEM
EARTHING
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories,
and providing masonry enclosure with cover plate having locking arrangement and 24.00 Set 0.00
watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including
accessories, and providing masonry enclosure with cover plate having locking
22.00 Set 0.00
arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as
required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections
800.00 Meter 0.00
etc. as required.
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for
450.00 Meter 0.00
connections etc. as required.
S.No DESCRIPTION TOTAL UNIT RATE Excluding AMOUNT
QTY GST (in Rs)
(in Rs)
30 MV CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV
grade of following size direct in ground including excavation, sand cushioning,
protective covering and refilling the trench etc as required.
Upto 35 sq. mm 200.00 Mtrs 0.00
Above 35 sq. mm and upto 95 sq. mm 385.00 Mtrs 0.00
Above 95 sq. mm and upto 185 sq. mm 780.00 Mtrs 0.00
Above 185 sq. mm and upto 400 sq. mm 1455.00 Mtrs 0.00
31 MV CABLE JOINTING & END TERMINATION
Supplying and making end termination with brass compression gland and aluminium
lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium
conductor cable of 1.1 KV grade as required.
3½ X 25 sq. mm (28mm) 4.00 Each 0.00
3½ X 35 sq. mm (32mm) 6.00 Each 0.00
3½ X 50 sq. mm (35mm) 6.00 Each 0.00
3½ X 70 sq. mm (38mm) 12.00 Each 0.00
3½ X 95 sq. mm (45mm) 12.00 Each 0.00
3½ X 120 sq. mm (45mm) 8.00 Each 0.00
3½ X 150 sq. mm (50mm) 6.00 Each 0.00
3½ X 185 sq. mm (57mm) 4.00 Each 0.00
3½ X 240 sq. mm (62mm) 12.00 Each 0.00
3½ X 300 sq. mm (70mm) 8.00 Each 0.00
32 CABLE TRAY
Supplying and installing following size of perforated pre-painted M.S. cable trays with
perforation not more than 17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts & nuts, painting
suspenders etc as required.
100 mm width X 50 mm depth X 1.6 mm thickness 100.00 Metre 0.00
150 mm width X 50 mm depth X 1.6 mm thickness 75.00 Metre 0.00
300 mm width X 50 mm depth X 1.6 mm thickness 125.00 Metre 0.00
450 mm width X 50 mm depth X 2.0 mm thickness 100.00 Metre 0.00
33 Providing and fixing MV danger notice plate of 200 mm x 150 mm made of mild
steel at least 2mm thick & vitreous enamelled white on both sides and with 18.00 Nos. 0.00
inscription in signal red colour on front side as required.
34 Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel
at least 2mm thick & vitreous enamelled white on both sides and with inscription in 2.00 Nos. 0.00
signal red colour on front side as required.
GRAND TOTAL 0.00