Load Calculation

This document calculates load and sizing requirements for a building with 8 flats. It summarizes: 1) The total building load is 164.4KW when all loads are running, but typically only 70% of loads run at a time, giving a total load of 115.08KW. 2) The recommended transformer rating is 150KVA to supply this typical load while allowing for 20% overload. 3) The emergency generator rating is 40KVA to supply the 30.6KW emergency load from flats, common areas, lift and water pump. 4) A 90KVR power factor improvement plant is recommended to correct the power factor of 0.8 used in the calculations.

Uploaded by

Abdul Alim
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views

Load Calculation

This document calculates load and sizing requirements for a building with 8 flats. It summarizes: 1) The total building load is 164.4KW when all loads are running, but typically only 70% of loads run at a time, giving a total load of 115.08KW. 2) The recommended transformer rating is 150KVA to supply this typical load while allowing for 20% overload. 3) The emergency generator rating is 40KVA to supply the 30.6KW emergency load from flats, common areas, lift and water pump. 4) A 90KVR power factor improvement plant is recommended to correct the power factor of 0.8 used in the calculations.

Uploaded by

Abdul Alim
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Load Calculation [ Ground Floor + Stair + Roof]

Load Description Quantity Total Watt Total Watt


Number per
of Loads Load
Light Items :

Tube Light(TL) 5+0+2 7 100 700

Wall Light(WL) 6+10+2 18 25 450

Celling Light(CEL) 5+0+2 7 25 175


1325
Fan Items :

Celling Fan (FA) 2+0+1 3 75 225

Exhaust Fan(EXF) 2+0+0 2 25 50


275
Power Outlets

P ( 3 pin,5A,240V,1 2+0+2 4 300 1200


phase)
2+0+2 4 100 400
R ( 2 pin,5A) 1600

3200

Load Calculation [A single Flat ]


Load Description Quantity Watt per Total Watt
Load
Light Items :

Tube Light(TL) 8 100 800

Wall Light(WL) 10 25 250

Candlelight(CL) 1 200 200 1250

Fan Items :

Celling Fan (FA) 6 75 450

Exhaust Fan(EXF) 1 25 25
475
Power Outlets :

P ( 3 pin,5A,240V,1 6 300 1800


phase)
7 100 700
R ( 2 pin,5A)
4 2000 8000
Q ( 3pin,15A,2000W)
3 1500 4500 15000
G ( 3 pin , 15A,1500W)
Emergency Load :

Emergency wall Light(EL) 2 100 200

Emergency Celling Fan 1 75 75


(EFA)
1 25 25 300
Calling bell (CB)
17025

Find out transformer rating :


Our designed building 4 floor each floor having 2 flat.so total number of flat 8.
So
1) 8 flat total load = 17025*8= 136200 watt =136.2 KW
2) (Ground Floor + Stair + Roof ) load =3200W=3.2KW
3) Lift Load =20KW
4) Water Pump =5KW

Total load our designed building = 164.4KW

We know at a time all load doesn’t running .so we assume 70% of load running at
a time.
So now total number of load =70% of 164.4=115.08 KW

Transformer rating= 115.08/0.8=143.85≅ 150 KVA


[ here, let power factor 0.8 ]

Find out Generator rating :

1) 8 flat total Emergency Load =300*8=2400W=2.4KW


2) (Ground Floor + Stair + Roof ) load =3200W=3.2KW
3) Lift Load =20KW
4) Water Pump =5KW

Generator supply emergency case Total load our


designed building = 30.6 KW

Generator rating= 30.6/0.8=38.25≅ 40 KVA


Find PFI(power factor Improvement) Plant rating :

PFI Plant rating = 150*0.6=90KVR