The HYBRICOOL is an outdoor compact cooler suitable for harsh climatic conditions designed for direct heat transfer to passive cooling systems. It operates on compressed refrigeration with four main components: compressor, condenser, expansion valve, and evaporator heat exchanger. The unit is fully isolated with an IP65 rating and filter-free for low maintenance operation in desert environments. Technical data includes operating temperatures from -20°C to 55°C and housing from corrosion-resistant GRP.

Uploaded by

Ambresh C
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views

CD HYBRICOOL General REV2

The HYBRICOOL is an outdoor compact cooler suitable for harsh climatic conditions designed for direct heat transfer to passive cooling systems. It operates on compressed refrigeration with four main components: compressor, condenser, expansion valve, and evaporator heat exchanger. The unit is fully isolated with an IP65 rating and filter-free for low maintenance operation in desert environments. Technical data includes operating temperatures from -20°C to 55°C and housing from corrosion-resistant GRP.

Uploaded by

Ambresh C
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

HYBRICOOL

1 Application
HYBRICOOL is an outdoor compact cooler suitable for
industrial harsh climatic conditions.

2 Description
Very efficient and reliable active cooling unit. Designed
for direct heat transfer to the buffer of a passive cooling
system.

4 Technical Data
The HYBRICOOL is usually mounted on the outside wall General
of the protective cabinet or shelter. The housing is a Ingress Protection
corrosion-resistant INTERTEC MULTIBOX GRP between outside and IP65
enclosure. inside
Fully designed, developed und assembled by INTERTEC 24V DC / 48V DC
HYBRICOOL is suitable for application in desert with
Nominal Voltage 230V AC 1Ph
sand condition and water spraying…
400V AC 3Ph
Refrigerant R-134a
3 Principle Operating temperature
-20°C … +55°C
range
The unit operates on the basis of compressed
refrigeration consisting of the four main components, Heat exchanger stainless steel coil
compressor, condenser, expansion valve and evaporator Glass fibre reinforced
Housing Material
(heat exchanger). polyester GRP (RAL7032)
The interior and exterior components are completly
isolated to maintain the cabinet/shelter IP class and
ensured that no harmful and corrosive substances can Heat exchanger: Evaporator coil
enter.
Filter-free operation: The air intake is equipped with a
centrifugal sediment separator to remove dust and sand.
The condenser within the external circuit is coated with a
corrosion protection system against aggressive media.
The air outlet is equipped with flaps so no dust can enter
if the cooler is not in operation.
The HYBRICOOL is designed for low maintenance and
constant power, no power drop due to blocked filter mats.
There is no condensate and no possible icing due to the
direct heat transfer to the water buffer.

CD_HYBRICOOL_General_REV2.docx Page 1/3


HYBRICOOL

Hybricool 48V DC 4800


HYBRICOOL DC

HYBRICOOL 24V HYBRICOOL 48V


Masterflux Sierra
Compressor Brushless

3000 W 5400 W
Cooling power @
35°C/ 35°C*

3,12 3,27
COP maximal*

2400 W 4800 W
Cooling power @
35°C/ 50°C*

2,18 2
COP maximal*
* Values based on manufacturer data (subject to change)

HYBRICOOL AC

AC
HYBRICOOL 230V HYBRICOOL 400V
Copeland Copeland Copeland Copeland Copeland Copeland Copeland
ZR18 ZR22 ZR28 ZR34 ZR18 ZR22 ZR28
Compressor Scroll

7000 W 8000 W 10500 W 12000 W 8000 W 10000 W 12000 W


Cooling power
@ 35°C/ 35°C*

5,61 5,73 6,45 6,57 5,77 6,11 6,57


COP maximal*

5600 W 6700 W 8500 W 10000 W 6500 W 8000 W 10000 W


Cooling power
@ 35°C/ 50°C*

3,2 3,33 3,55 3,64 3,32 3,36 3,69


COP maximal*
* Values based on manufacturer data (subject to change)

CD_HYBRICOOL_General_REV2.docx Page 2/3


HYBRICOOL

5 Options

- Available for hazardous area EX (only for


HYBRICOOL AC)
- Global coating of refrigerant's circuit
- Redundant installation with operating time
management unit, automatic switching in case
of failure
- Possibility to adapt a ventilated evaporator to
use the HYBRICOOL as an air cooler (split
system principle)
- All other specific requests can be considered.

Redundant HYBRICOOLs

CD_HYBRICOOL_General_REV2.docx Page 3/3