0% found this document useful (0 votes)
90 views

Ge Frame 6

Uploaded by

Ali Sadiq
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views

Ge Frame 6

Uploaded by

Ali Sadiq
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PRODUCT BULLETIN: 00004

GE FRAME 6® GAS TURBINE GENERATOR DRIVE


APPLICATION CONTROL PACKAGE
MAY 2012

THERMOCOUPLES

NHP
1

NHP
2

NHP
3 GENERATOR

NST STARTER

PCD

AUTO
F WT
E SYNC
IGV RAM E
D
B
HYDRAULIC A
POWER C
UNIT SERVO K
VALVE
SERVO
CONTROLLER

I/E

BYPASS
VALVE

GAS LIQUID
FUEL FUEL
SPEED STOP GAS FUEL STOP
FUEL
RATIO VALVE CONTROL VALVE
PUMP
VALVE FUEL VALVE
FLOW
DIVIDER

4-20 mA 4-20 mA
FUEL PRESSURE INPUT LIQUID FUEL FLOW INPUT
4-20 mA 4-20 mA
SRV OUTPUT LCV VALVE OUTPUT
4-20 mA
GCV OUTPUT RAISE
4-20 mA SYNCHRONIZING INPUT
INLET GUIDE VANE OUTPUT
4-20 mA LOWER
PCD INPUT
FREQUENCY 4-20 mA
NST INPUT WATTS INPUT
FREQUENCY
THERMOCOUPLE mV
FREQUENCY SPEED INPUTS INPUTS TC01 - TC18
2oo3 VOTE
FREQUENCY

OPTIONAL
APPLICATION CONTROL PACKAGE 9500-FR6-GEN MMI

COMM PORT

TO PLANT INFORMATION SYSTEM DCS/SCADA

PLC INTEGRATED CONTROL SYSTEM

Simplified schematic showing a Petrotech GE Frame 6® gas turbine generator drive application control
package integrated into an advanced PLC-based control system. Shown with dual fuel system.
PRODUCT BULLETIN 00004 - GE FRAME 6® GAS TURBINE GENERATOR DRIVE APPLICATION CONTROL PACKAGE- Page 2

APPLICATION SCOPE OF SUPPLY


The GE Frame 6 gas turbine gen set application control package
®
The application control package for GE Frame 6® gas turbine
replaces older mechanical/hydraulic/electronic/pneumatic gas generator drive system, includes:
turbine fuel regulators with a modern, reliable application control
Analog inputs, 4-20 mA:
package which runs on an open architecture advanced PLC-based
• Watts (load control)
system. The control package for the gas turbine provides on-line
dual fuel control, speed ratio control, and inlet guide vane control • Compressor discharge pressure (PCD)
based on temperature. • Fuel interstage pressure
Analog inputs, frequency:
ADVANTAGES • Three (3) redundant NHP
• Hardware independent system: • One (1) starter speed
Application control package’s portability allows customer choice
Analog inputs, mV:
of platform, reducing need for additional spare parts and training
• EGT (up to 18 thermocouples)
expenses. Available PLCs include General Electric, Siemens/TI, Allen-
Bradley, and Modicon. Analog outputs, 4-20 mA:
• Speed ratio valve position setpoint
• Fault tolerant:
• Fuel control valve position setpoint
Control package is available on fault tolerant controllers for critical
control applications. • Inlet guide vane position setpoint (if applicable)

• Simplified interface to DCS or SCADA: Operating states:


Communication tasks are handled with a separate, dedicated module • Firing
in the PLC, increasing data rate and simplifying network installation. • Warm-up
• Improved fuel regulation: • Accelerate
Fast loop sampling rate, combined with modern digital control • Load
techniques, improves steady-state setpoint control, and reduces • Upset
overshoot during transients, allowing full load rejection without
Status, alarms, and shutdowns:
driving the unit into overspeed.
• Fault
• Improved start-up reliability: • NHP overspeed alarm
Special “lean lightoff” procedure ignites all burners with essentially
• NHP underspeed alarm
100% reliability, and with greatly reduced thermal stress.
• NHP overspeed shutdown
• Improved exhaust temperature monitoring and control:
• Redundant NHP overspeed shutdown
Advanced statistical algorithms detect turbine hot/cold spots and
• rNHP alarm
automatically reject failed thermocouples.
• High EGT alarm
• Fail-safe features:
• High EGT shutdown
Redundant overspeeds; open/short monitoring of mA and
thermocouples; readback monitoring of outputs, and special self- • Low EGT shutdown
check features improve safety. • Rejected thermocouple
• Non-proprietary interfaces: • Too few thermocouples shutdown
Simple 4-20 mA, RTD, thermocouple, and dry contact I/O allow • rT alarm
simple interface to existing sequence/protection logic unit, making • rT shutdown
low-cost partial upgrades practical, and system troubleshooting • Thermocouple spread alarm
simple.
• Thermocouple spread shutdown
• Improved operator information with optional MMI: • Turbine maximum limit
Optional Man-Machine Interface MS Windows-based graphic
• Turbine minimum limit
operator interface displays system status, trending and data logging,
which can be used as part of a preventive maintenance program. • NHP speed #1
• NHP speed #2
• NHP speed #3
• NHP speed #4
• NHP speed #5
• EGT switch #1
• Bolt test
• Manual
• Starter overspeed
• Starter zero speed
• High firing fuel pressure shutdown
PRODUCT BULLETIN 00004 - GE FRAME 6® GAS TURBINE GENERATOR DRIVE APPLICATION CONTROL PACKAGE- Page 3

SCOPE OF SUPPLY-Continued OPTIONS FOR COMPLETE CONTROL SYSTEM


• PCD bias active UPGRADE
• Flow following error • Gas turbine sequencing and protection discrete logic
• Transmitter failure alarms • Generator sequencing and protection discrete logic
• Transmitter failure shutdowns • Communication interface to DCS or SCAD
• Output failure shutdowns • PLC hardware
• Control mode • Man machine interface unit with WonderWare InTouch®
licensed software package
Controllers/special features:
• Start-up controller for fuel valve • Complete custom engineered control panel, factory tested
and ready to install
• NHP controller for fuel valve
• Fuel valve system upgrade
• NHP acceleration controller for fuel valve
• Inlet guide vanes actuator system upgrade or retrofit
• EGT controller for fuel valve
• Thermocouple upgrade
• EGT rate of rise controller for fuel valve
• Flame sensor upgrade
• EGT controller for inlet guide vanes (if applicable)
• Vibration system upgrade
• Combustion monitoring system
• Installation and commissioning
• Dual fuel capability with on-line transfer
• Training
Ramps:
• Firing (lean lightoff) ramp
• Start-up ramp
• Loading ramp
• Cooldown ramp
Does not include:
• PLC hardware
• Gas turbine sequencing and protection discrete logic
• Generator sequencing and protection discrete logic
• Synchronizing and regulation equipment
• End elements

Petrotech, Inc. Phone: (504) 620-6600


151 Brookhollow Esplanade Fax: (504) 620-6601
New Orleans, Louisiana 70123 Email: [email protected]
USA Website: www.petrotechinc.com

This document is a Petrotech, Inc. copyrighted intellectual property and may be changed at any time without notice.