Simplex MAPNET II Control ZAMs Installation Instructions
Simplex MAPNET II Control ZAMs Installation Instructions
Control ZAMs
Installation Instructions
DIP SWITCHES
Introduction
Use the procedure below to install the following Control Zone
Adapter Modules (ZAMs):
1 10
2 9
Unsupervised Control ZAM 3 8
4 7
Control ZAMs receive data over this wire pair; a separate pair is
required for 24 VDC power, and in the case of signal ZAMs with
speakers another pair is required for audio power. All circuits are
-
power limited only if operating power and MAPNET II communi-
+
cations are provided by a 4002 Control Unit or by a system with
the 4100/4120-6050 power limited option. If other power supplies
or systems are used, no circuits are power limited.
+28V 0V
Installation +28V 0V
FROM
POWER SUPPLY
TO
Part A — Setting the Control ZAM’s Address and Labeling OTHER ZAMs
the ZAM
Figure 2. Class A Power / MAPNET II
Control ZAM installation consists of three parts: Connections for Control ZAMs
firealarmresources.com
CONTROL ZAM CONTROL ZAM
1 10
2 9
3 8
4 2A 7
REFER TO UNSUPERVISED 6
5
841-804 OR CONTRACTOR 6 K1B
5
841-996 FOR WIRING TO 7 2A 4
3
DETAILS RELAY 8
2
9 K1A
CONTACTS 10 1
TB2 TB1
EOL RESISTOR
(10K, 1/4W), NUMBER
378-156
Figure 4. Class B Signal ZAM, Figure 5. Connections for Control
NAC Connection ZAM Contacts
Each control ZAM has a unique address. This address is associated with a custom label which identifies its physical
location within a building. The ZAM’s address and location must match up with the address listed in the specification
sheets of the 4020 Programmer’s Report, the 4100+ Programmer’s Report, or the 4120 Programmer’s Report. The
address of the ZAM is set via an eight position DIP switch (Figure 1), DIP switch Position 1 being the least significant bit
(LSB) and Position 8 being the most significant bit (MSB). Set the ZAM’s address using Figure 6 as reference. Use a
small screwdriver or pen to set the switches.
Note: DIP switch in “1” position is “ON” while DIP switch in “0” position is “OFF.”
LSB MSB DIPSWITCH IS SHOWN SET AT ADDRESS 7
1 2 3 4 5 6 7 8
ON
OFF 1 = ON 0 = OFF
firealarmresources.com
Part B — Making Electrical Connections to the ZAM
CAUTION: Ensure that cable shields will not ground when closing the box. Use shrink tubing or high
grade electrical tape to cover bare shield.
Control and Signal ZAMs are connected to the 4020, 4100+, or 4120 Panel by a single wire pair. Connect the Control or
Signal ZAM to the MAPNET II wire pair and power supply using Figure 2 as a reference. (Refer to the appropriate
4020, 4100+, 4120 Panel cabinet drawing for MAPNET II panel connections.) Connect the Style Z (formerly Class A)
or Style Y (formerly Class B) Signal ZAM to its signal power or audio source using Figure 7 and 8. Refer to wiring
diagrams in MAPNET II Devices (841-804 or 841-996) to determine peripheral device connections to the ZAM you are
installing.
SHIELD IF REQUIRED
(REFER TO DRAWINGS IN
841-804 OR 841-996
TB2
FOR DETAILS) 1
3
INCOMING AUDIO
OR SIGNAL 4
OUTGOING AUDIO
POWER LINES
5 OR SIGNAL
POWER LINES
6
10
11
12
8
INCOMING AUDIO OUTGOING AUDIO
OR SIGNAL 9 OR SIGNAL
POWER LINES POWER LINES
10
firealarmresources.com
Part C — Mechanically Installing the ZAM
SIMPLEX
SURFACE COVER
SIMPLEX
FLUSH COVER
CONTROL ZAM
ASSEMBLY
Note: Attach extension ring to the front of square back box, making the total box depth 3 5/8” inches deep for either
flush or surface mounting.
575-279
Rev. B
firealarmresources.com