Daikin Field Settings

This document contains a field settings table for applicable indoor units of a heat pump system. It includes default values and configurable ranges for various installer and user settings related to temperature setpoints, weather dependent curves, system layout and more. Notes indicate the quiet level and compressor type settings for different indoor unit models.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views

Daikin Field Settings

This document contains a field settings table for applicable indoor units of a heat pump system. It includes default values and configurable ranges for various installer and user settings related to temperature setpoints, weather dependent curves, system layout and more. Notes indicate the quiet level and compressor type settings for different indoor unit models.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

1/8

Field settings table

Applicable indoor units

EHVH04SU18CB6W
EHVH08SU18CB6W
EHVH08SU26CB6W
EHVH11SU26CB6W
EHVH16SU26CB6W

Notes

(*1) *04/08*
(*2) *11/16*

4P449983-1 - 2016.06
2/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
User settings
└─ Preset values
└─ Room temperature
7.4.1.1 Comfort (heating) R/W [3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2 Eco (heating) R/W [3-07]~[3-06], step: A.3.2.4
19°C
└─ LWT main
7.4.2.1 [8-09] Comfort (heating) R/W [9-01]~[9-00], step: 1°C
35°C
7.4.2.2 [8-0A] Eco (heating) R/W [9-01]~[9-00], step: 1°C
33°C
7.4.2.5 Comfort (heating) R/W -10~10°C, step: 1°C
0°C
7.4.2.6 Eco (heating) R/W -10~10°C, step: 1°C
-2°C
└─ Tank temperature
7.4.3.1 [6-0A] Storage comfort R/W 30~[6-0E]°C, step: 1°C
60°C
7.4.3.2 [6-0B] Storage eco R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
7.4.3.3 [6-0C] Reheat R/W 30~min(50, [6-0E])°C, step: 1°C
48°C
└─ Quiet level
7.4.4 R/W 0: Level 1 (*2)
1: Level 2 (*1)
2: Level 3
└─ Electricity price
7.4.5.1 [C-0C] High R/W 0,00~990/kWh
[D-0C] 0/kWh
7.4.5.2 [C-0D] Medium R/W 0,00~990/kWh
[D-0D] 0/kWh
7.4.5.3 [C-0E] Low R/W 0,00~990/kWh
[D-0E] 0/kWh
└─ Fuel price
7.4.6 R/W 0,00~990/kWh
0,00~290/MBtu
8,0/kWh
└─ Set weather dependent
└─ Main
7.7.1.1 [1-00] Set weather-dependent heating Low ambient temp. for LWT main zone heating R/W -40~5°C, step: 1°C
WD curve. -10°C
7.7.1.1 [1-01] Set weather-dependent heating High ambient temp. for LWT main zone heating R/W 10~25°C, step: 1°C
WD curve. 15°C
7.7.1.1 [1-02] Set weather-dependent heating Leaving water value for low ambient temp. for R/W [9-01]~[9-00], step: 1°C
LWT main zone heating WD curve. 40°C
7.7.1.1 [1-03] Set weather-dependent heating Leaving water value for high ambient temp. for R/W [9-01]~min(45, [9-00])°C , step: 1°C
LWT main zone heating WD curve. 25°C
└─ Additional
7.7.2.1 [0-00] Set weather-dependent heating Leaving water value for high ambient temp. for R/W [9-05]~min(45,[9-06])°C, step: 1°C
LWT add zone heating WD curve. 35°C
7.7.2.1 [0-01] Set weather-dependent heating Leaving water value for low ambient temp. for R/W [9-05]~[9-06]°C, step: 1°C
LWT add zone heating WD curve. 45°C
7.7.2.1 [0-02] Set weather-dependent heating High ambient temp. for LWT add zone heating R/W 10~25°C, step: 1°C
WD curve. 15°C
7.7.2.1 [0-03] Set weather-dependent heating Low ambient temp. for LWT add zone heating R/W -40~5°C, step: 1°C
WD curve. -10°C
Installer settings
└─ System layout
└─ Standard
A.2.1.1 [E-00] Unit type R/O 0~5
0: LT split
A.2.1.2 [E-01] Compressor type R/O 0: 8
1: 16
A.2.1.3 [E-02] Indoor software type R/O 0~1
1: Type 2
A.2.1.4 [E-03] Backup heater steps R/O 0: No BUH
1: 1 step
2: 2 steps
A.2.1.5 [5-0D] BUH type R/W 0~5
1: 1P,(1/1+2)
3: 3P,(1/1+2)
4: 3PN,(1/2)
A.2.1.6 [D-01] Forced off contact R/W 0: No
1: Open tariff
2: Closed tariff
3: Thermostat
A.2.1.7 [C-07] Unit control method R/W 0: LWT control
1: Ext RT control
2: RT control
A.2.1.8 [7-02] Number of LWT zones R/W 0: 1 LWT zone
1: 2 LWT zones
A.2.1.9 [F-0D] Pump operation mode R/W 0: Continuous
1: Sample
2: Request
A.2.1.A [E-04] Power saving possible R/O 0: No
1: Yes
A.2.1.B User interface location R/W 0: At unit
1: In room
└─ Options
A.2.2.1 [E-05] DHW operation R/W 0: No
1: Yes
A.2.2.3 [E-07] DHW tank type R/O 2: Type 3
A.2.2.4 [C-05] Contact type main R/W 1: Thermo ON/OFF
2: C/H request
A.2.2.5 [C-06] Contact type add. R/W 1: Thermo ON/OFF
2: C/H request
A.2.2.6.1 [C-02] Digital I/O PCB Ext. backup heat src R/W 0: No
1: Bivalent
2: -
3: -
A.2.2.6.2 [D-07] Digital I/O PCB Solar kit R/W 0: No
1: Yes

4P449983-1 - 2016.06 (*1) *04/08*_(*2) *11/16*


3/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
A.2.2.6.3 [C-09] Digital I/O PCB Alarm output R/W 0: Normally open
1: Normally closed
A.2.2.6.4 [F-04] Digital I/O PCB Bottom plate heater R/W 0: No
1: Yes
A.2.2.7 [D-04] Demand PCB R/W 0: No
1: Pwr consmp ctrl
A.2.2.8 [D-08] External kWh meter 1 R/W 0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.9 [D-09] External kWh meter 2 R/W 0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.A [D-02] DHW pump R/W 0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
A.2.2.B [C-08] External sensor R/W 0: No
1: Outdoor sensor
2: Room sensor
└─ Capacities
A.2.3.1 [6-02] Booster heater R/W 0~10 kW, step: 0,2 kW
2,4 kW
A.2.3.2 [6-03] BUH: step 1 R/W 0~10 kW, step: 0,2 kW
3 kW
A.2.3.3 [6-04] BUH: step 2 R/W 0~10 kW, step: 0,2 kW
3 kW
A.2.3.6 [6-07] Bottom plate heater R/W 0~200W, step: 10W
0W
Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1 LWT setpoint mode R/W 0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.1.2.1 [9-01] Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.1.2.2 [9-00] Temperature range Maximum temp (heating) R/W 37~depending on outdoor unit, step: 1°C
55°C

A.3.1.1.5 [8-05] Modulated LWT R/W 0: No


1: Yes
A.3.1.1.6.1 [F-0B] Shut-off valve Thermo On/OFF R/W 0: No
1: Yes
A.3.1.1.7 [9-0B] Emitter type R/W 0: Quick
1: Slow
└────────────────── Additional
A.3.1.2.1 LWT setpoint mode R/W 0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.2.2.1 [9-05] Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.2.2.2 [9-06] Temperature range Maximum temp (heating) R/W 37~depending on outdoor unit, step: 1°C
55°C

└────────────────── Delta T source


A.3.1.3.1 [9-09] Heating R/W 3~10°C, step: 1°C
5°C
└─ Room thermostat
A.3.2.1.1 [3-07] Room temp. range Minimum temp (heating) R/W 12~18°C, step: A.3.2.4
12°C
A.3.2.1.2 [3-06] Room temp. range Maximum temp (heating) R/W 18~30°C, step: A.3.2.4
30°C
A.3.2.2 [2-0A] Room temp. offset R/W -5~5°C, step: 0,5°C
0°C
A.3.2.3 [2-09] Ext. room sensor offset R/W -5~5°C, step: 0,5°C
0°C
A.3.2.4 Room temp. step R/W 0: 0,5 °C
1: 1 °C
└─ Operation range
A.3.3.1 [4-02] Space heating OFF temp R/W 14~35°C, step: 1°C
25°C (*1)
14~35°C, step: 1°C
35°C (*2)
└─ Domestic hot water (DHW)
└─ Type
A.4.1 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled only
└─ Disinfection
A.4.4.1 [2-01] Disinfection R/W 0: No
1: Yes
A.4.4.2 [2-00] Operation day R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3 [2-02] Start time R/W 0~23 hour, step: 1 hour
23
A.4.4.4 [2-03] Temperature target R/O 60°C
A.4.4.5 [2-04] Duration R/W 40~60 min, step: 5 min
40 min

(*1) *04/08*_(*2) *11/16* 4P449983-1 - 2016.06


4/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
└─ Maximum setpoint
A.4.5 [6-0E] R/W 40~65°C, step: 1°C
65°C
└─ SP mode
A.4.6 R/W 0: Fixed
1: Weather dep.
└─ Weather dependent curve
A.4.7 [0-0B] Weather-dependent curve Leaving water value for high ambient temp. for R/W 35~[6-0E]°C, step: 1°C
DHW WD curve. 55°C
A.4.7 [0-0C] Weather-dependent curve Leaving water value for low ambient temp. for R/W 45~[6-0E]°C, step: 1°C
DHW WD curve. 65°C
A.4.7 [0-0D] Weather-dependent curve High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.4.7 [0-0E] Weather-dependent curve Low ambient temp. for DHW WD curve. R/W -40~5°C, step: 1°C
-10°C
└─ Heat sources
└─ Backup heater
A.5.1.1 [4-00] Operation mode R/W 0~2
0: Disabled
1: Enabled
A.5.1.3 [4-07] Enable BUH step 2 R/W 0: No
1: Yes
A.5.1.4 [5-01] Equilibrium temp. R/W -15~35°C, step: 1°C
0°C
└─ System operation
└─ Auto restart
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Preferential kWh rate
A.6.2.1 [D-00] Allowed heaters R/W 0: None
1: BSH only
2: BUH only
3: All heaters
A.6.2.2 [D-05] Forced pump OFF R/W 0: Forced off
1: As normal
└─ Pwr consumpt. Control
A.6.3.1 [4-08] Mode R/W 0: No limitation
1: Continuous
2: Digital inputs
A.6.3.2 [4-09] Type R/W 0: Current
1: Power
A.6.3.3 [5-05] Amp. value R/W 0~50 A, step: 1 A
50 A
A.6.3.4 [5-09] kW value R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1 [5-05] Amp. limits for DI Limit DI1 R/W 0~50 A, step: 1 A
50 A
A.6.3.5.2 [5-06] Amp. limits for DI Limit DI2 R/W 0~50 A, step: 1 A
50 A
A.6.3.5.3 [5-07] Amp. limits for DI Limit DI3 R/W 0~50 A, step: 1 A
50 A
A.6.3.5.4 [5-08] Amp. limits for DI Limit DI4 R/W 0~50 A, step: 1 A
50 A
A.6.3.6.1 [5-09] kW limits for DI Limit DI1 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2 [5-0A] kW limits for DI Limit DI2 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3 [5-0B] kW limits for DI Limit DI3 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4 [5-0C] kW limits for DI Limit DI4 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.7 [4-01] Priority R/W 0: None
1: BSH
2: BUH
└─ Averaging time
A.6.4 [1-0A] R/W 0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Ext amb. sensor offset
A.6.5 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
└─ Boiler efficiency
A.6.A [7-05] R/W 0: Very high
1: High
2: Medium
3: Low
4: Very low
└─ Emergency
A.6.C R/W 0: Manual
1: Automatic
└─ Overview settings
A.8 [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8 [0-01] Leaving water value for low ambient temp. for LWT add zone heating WD curve. R/W [9-05]~[9-06]°C, step: 1°C
45°C
A.8 [0-02] High ambient temp. for LWT add zone heating WD curve. R/W 10~25°C, step: 1°C
15°C
A.8 [0-03] Low ambient temp. for LWT add zone heating WD curve. R/W -40~5°C, step: 1°C
-10°C
A.8 [0-04] -- 8
A.8 [0-05] -- 12
A.8 [0-06] -- 35
A.8 [0-07] -- 20
A.8 [0-0B] Leaving water value for high ambient temp. for DHW WD curve. R/W 35~[6-0E]°C, step: 1°C
55°C
A.8 [0-0C] Leaving water value for low ambient temp. for DHW WD curve. R/W 45~[6-0E]°C, step: 1°C
65°C
A.8 [0-0D] High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.8 [0-0E] Low ambient temp. for DHW WD curve. R/W -40~5°C, step: 1°C
-10°C

4P449983-1 - 2016.06 (*1) *04/08*_(*2) *11/16*


5/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
A.8 [1-00] Low ambient temp. for LWT main zone heating WD curve. R/W -40~5°C, step: 1°C
-10°C
A.8 [1-01] High ambient temp. for LWT main zone heating WD curve. R/W 10~25°C, step: 1°C
15°C
A.8 [1-02] Leaving water value for low ambient temp. for LWT main zone heating WD curve. R/W [9-01]~[9-00], step: 1°C
40°C
A.8 [1-03] Leaving water value for high ambient temp. for LWT main zone heating WD curve. R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
A.8 [1-04] -- 1
A.8 [1-05] -- 1
A.8 [1-06] -- 20
A.8 [1-07] -- 35
A.8 [1-08] -- 22
A.8 [1-09] -- 18
A.8 [1-0A] What is the averaging time for the outdoor temp? R/W 0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8 [2-00] When should the disinfection function be executed? R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.8 [2-01] Should the disinfection function be executed? R/W 0: No
1: Yes
A.8 [2-02] When should the disinfection function start? R/W 0~23 hour, step: 1 hour
23 hours
A.8 [2-03] What is the disinfection target temperature? R/O 60°C
A.8 [2-04] How long must the tank temperature be maintained? R/W 40~60 min, step: 5 min
40 min
A.8 [2-05] Room antifrost temperature R/W 4~16°C, step: 1°C
12°C
A.8 [2-06] Room frost protection R/W 0: Disabled
1: Enabled
A.8 [2-09] Adjust the offset on the measured room temperature R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0A] Adjust the offset on the measured room temperature R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0B] What is the required offset on the measured outdoor temp.? R/W -5~5°C, step: 0,5°C
0°C
A.8 [3-00] Is auto restart of the unit allowed? R/W 0: No
1: Yes
A.8 [3-01] -- 0
A.8 [3-02] -- 1
A.8 [3-03] -- 4
A.8 [3-04] -- 2
A.8 [3-05] -- 1
A.8 [3-06] What is the maximum desired room temperature in heating? R/W 18~30°C, step: A.3.2.4
30°C
A.8 [3-07] What is the mimimum desired room temperature in heating? R/W 12~18°C, step: A.3.2.4
12°C
A.8 [3-08] -- 35
A.8 [3-09] -- 15
A.8 [4-00] What is the BUH operation mode? R/W 0~2
0: Disabled
1: Enabled
A.8 [4-01] Which electric heater has priority? R/W 0: None
1: BSH
2: BUH
A.8 [4-02] Below which outdoor temperature is heating allowed? R/W 14~35°C, step: 1°C
25°C (*1)
14~35°C, step: 1°C
35°C (*2)
A.8 [4-03] Operation permission of the booster heater. R/W 0: Limited
1: No limit
2: Most optimum
3: Optimum
4: Only legionella
A.8 [4-04] -- 2
A.8 [4-05] -- 0
A.8 [4-06] -- (Do not change this value) 0/1
A.8 [4-07] Enable the second step of the backup heater? R/W 0: No
1: Yes
A.8 [4-08] Which power limitation mode is required on the system? R/W 0: No limitation
1: Continuous
2: Digital inputs
A.8 [4-09] Which power limitation type is required? R/W 0: Current
1: Power
A.8 [4-0A] -- 0
A.8 [4-0B] Automatic cooling/heating changeover hysteresis. R/W 1~10°C, step: 0,5°C
1°C
A.8 [4-0D] Automatic cooling/heating changeover offset. R/W 1~10°C, step: 0,5°C
3°C
A.8 [4-0E] Is the installer on site? R/W 0: No
1: Yes
A.8 [5-00] Is backup heater operation allowed above equilibrium temperature during space R/W 0: Allowed
heating operation? 1: Not allowed
A.8 [5-01] What is the equilibrium temperature for the building? R/W -15~35°C, step: 1°C
0°C
A.8 [5-02] Space heating priority. R/W 0: Disabled
1: Enabled
A.8 [5-03] Space heating priority temperature. R/W -15~35°C, step: 1°C
0°C
A.8 [5-04] Set point correction for domestic hot water temperature. R/W 0~20°C, step: 1°C
10°C
A.8 [5-05] What is the requested limit for DI1? R/W 0~50 A, step: 1 A
50 A
A.8 [5-06] What is the requested limit for DI2? R/W 0~50 A, step: 1 A
50 A

(*1) *04/08*_(*2) *11/16* 4P449983-1 - 2016.06


6/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
A.8 [5-07] What is the requested limit for DI3? R/W 0~50 A, step: 1 A
50 A
A.8 [5-08] What is the requested limit for DI4? R/W 0~50 A, step: 1 A
50 A
A.8 [5-09] What is the requested limit for DI1? R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0A] What is the requested limit for DI2? R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0B] What is the requested limit for DI3? R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0C] What is the requested limit for DI4? R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0D] What type of backup heater installation is used? R/W 0~5
1: 1P,(1/1+2)
3: 3P,(1/1+2)
4: 3PN,(1/2)
A.8 [5-0E] -- 1
A.8 [6-00] The temperature difference determining the heat pump ON temperature. R/W 2~20°C, step: 1°C
2°C
A.8 [6-01] The temperature difference determining the heat pump OFF temperature. R/W 0~10°C, step: 1°C
2°C
A.8 [6-02] What is the capacity of the booster heater? R/W 0~10 kW, step: 0,2 kW
2,4 kW
A.8 [6-03] What is the capacity of the backup heater step 1? R/W 0~10 kW, step: 0,2 kW
3kW
A.8 [6-04] What is the capacity of the backup heater step 2? R/W 0~10 kW, step: 0,2 kW
3 kW
A.8 [6-05] -- 0
A.8 [6-06] -- 0
A.8 [6-07] What is the capacity of the bottom plate heater? R/W 0~200 W, step: 10 W
0W
A.8 [6-08] What is the hysteresis to be used in reheat mode? R/W 2~20°C, step: 1°C
8°C
A.8 [6-09] -- 0
A.8 [6-0A] What is the desired comfort storage temperature? R/W 30~[6-0E]°C, step: 1°C
60°C
A.8 [6-0B] What is the desired eco storage temperature? R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
A.8 [6-0C] What is the desired reheat temperature? R/W 30~min(50, [6-0E])°C, step: 1°C
48°C
A.8 [6-0D] What is the desired DHW production type? R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled only
A.8 [6-0E] What is the maximum temperature setpoint? R/W 40~65°C, step: 1°C
65°C
A.8 [7-00] Domestic hot water booster heater overshoot temperature. R/W 0~4°C, step: 1°C
0°C
A.8 [7-01] Domestic hot water booster heater hysteresis. R/W 2~40°C, step: 1°C
2°C
A.8 [7-02] How many leaving water temperature zones are there? R/W 0: 1 LWT zone
1: 2 LWT zones
A.8 [7-03] -- 2,5
A.8 [7-04] -- 0
A.8 [7-05] Boiler efficiency R/W 0: Very high
1: High
2: Medium
3: Low
4: Very low
A.8 [8-00] -- 1 min
A.8 [8-01] Maximum running time for domestic hot water operation. R/W 5~95 min, step: 5 min
30 min
A.8 [8-02] Anti-recycling time. R/W 0~10 hour, step: 0,5 hour
3 hours
A.8 [8-03] Booster heater delay timer. R/W 20~95 min, step: 5 min
50 min
A.8 [8-04] Additional running time for the maximum running time. R/W 0~95 min, step: 5 min
95 min
A.8 [8-05] Allow modulation of the LWT to control the room temp? R/W 0: No
1: Yes
A.8 [8-06] Leaving water temperature maximum modulation. R/W 0~10°C, step: 1°C
3°C
A.8 [8-07] -- 18
A.8 [8-08] -- 20
A.8 [8-09] What is the desired comfort main LWT in heating? R/W [9-01]~[9-00], step: 1°C
35°C
A.8 [8-0A] What is the desired eco main LWT in heating? R/W [9-01]~[9-00], step: 1°C
33°C
A.8 [8-0B] -- 13
A.8 [8-0C] -- 10
A.8 [8-0D] -- 16
A.8 [9-00] What is the maximum desired LWT for main zone in heating? R/W 37~depending on outdoor unit, step: 1°C
55°C

A.8 [9-01] What is the mimimum desired LWT for main zone in heating? R/W 15~37°C, step: 1°C
25°C
A.8 [9-02] -- 22
A.8 [9-03] -- 5
A.8 [9-04] Leaving water temperature overshoot temperature. R/W 1~4°C, step: 1°C
1°C
A.8 [9-05] What is the mimimum desired LWT for add. zone in heating? R/W 15~37°C, step: 1°C
25°C
A.8 [9-06] What is the maximum desired LWT for add. zone in heating? R/W 37~depending on outdoor unit, step: 1°C
55°C

A.8 [9-07] -- 5
A.8 [9-08] -- 22
A.8 [9-09] What is the desired delta T in heating? R/W 3~10°C, step: 1°C
5°C
A.8 [9-0A] -- 5
A.8 [9-0B] What emitter type is connected to the main LWT zone? R/W 0: Quick
1: Slow
A.8 [9-0C] Room temperature hysteresis. R/W 1~6°C, step: 0,5°C
1 °C

4P449983-1 - 2016.06 (*1) *04/08*_(*2) *11/16*


7/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
A.8 [9-0D] Pump speed limitation R/W 0~8, step:1
0 : 100%
1~4 : 80~50%
5~8 : 80~50%
6
A.8 [9-0E] -- 6
A.8 [A-00] -- 0
A.8 [A-01] -- 0 (*1)
3 (*2)
A.8 [A-02] -- 0 (*1)
1 (*2)
A.8 [A-03] -- 0
A.8 [A-04] -- 0
A.8 [B-00] -- 0
A.8 [B-01] -- 0
A.8 [B-02] -- 0
A.8 [B-03] -- 0
A.8 [B-04] -- 0
A.8 [C-00] Domestic heating water priority. R/W 0: Solar priority
1: Heat pump priority
A.8 [C-01] -- 0
A.8 [C-02] Is an external backup heat source connected? R/W 0: No
1: Bivalent
2: -
3: -
A.8 [C-03] Bivalent activation temperature. R/W -25~25°C, step: 1°C
0°C
A.8 [C-04] Bivalent hysteresis temperature. R/W 2~10°C, step: 1°C
3°C
A.8 [C-05] What is the thermo request contact type for the main zone? R/W 1: Thermo ON/OFF
2: C/H request
A.8 [C-06] What is the thermo request contact type for the add. zone? R/W 0: -
1: Thermo ON/OFF
2: C/H request
A.8 [C-07] What is the unit control method in space operation? R/W 0: LWT control
1: Ext RT control
2: RT control
A.8 [C-08] Which type of external sensor is installed? R/W 0: No
1: Outdoor sensor
2: Room sensor
A.8 [C-09] What is the required alarm output contact type? R/W 0: Normally open
1: Normally closed
A.8 [C-0A] -- 0
A.8 [C-0C] High electricity price decimal (Do not use) R/W 0~7
0
A.8 [C-0D] Medium electricity price decimal (Do not use) R/W 0~7
0
A.8 [C-0E] Low electricity price decimal (Do not use) R/W 0~7
0
A.8 [D-00] Which heaters are permitted if prefer. kWh rate PS is cut? R/W 0: None
1: BSH only
2: BUH only
3: All heaters
A.8 [D-01] Forced off contact type R/W 0: No
1: Open tariff
2: Closed tariff
3: Thermostat
A.8 [D-02] Which type of DHW pump is installed? R/W 0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
A.8 [D-03] Leaving water temperature compensation around 0°C. R/W 0: Disabled
1: Enabled, shift 2°C (from -2 to 2°C)
2: Enabled, shift 4°C (from -2 to 2°C)
3: Enabled, shift 2°C (from -4 to 4°C)
4: Enabled, shift 4°C (from -4 to 4°C)
A.8 [D-04] Is a demand PCB connected? R/W 0: No
1: Pwr consmp ctrl
A.8 [D-05] Is the pump allowed to run if prefer. kWh rate PS is cut? R/W 0: Forced off
1: As normal
A.8 [D-07] Is a solar kit connected? R/W 0: No
1: Yes
A.8 [D-08] Is an external kWh meter used for power measurement? R/W 0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.8 [D-09] Is an external kWh meter used for power measurement? R/W 0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.8 [D-0A] -- 0
A.8 [D-0B] -- 2
A.8 [D-0C] What is the high electricity price (Do not use) R/W 0~49
0
A.8 [D-0D] What is the medium electricity price (Do not use) R/W 0~49
0
A.8 [D-0E] What is the low electricity price (Do not use) R/W 0~49
0
A.8 [E-00] Which type of unit is installed? R/O 0~5
0: LT split
A.8 [E-01] Which type of compressor is installed? R/O 0: 8
1: 16
A.8 [E-02] What is the indoor unit software type? R/O 0~1
1: Type 2
A.8 [E-03] What is the number of backup heater steps? R/O 0: No BUH
1: 1 step
2: 2 steps

(*1) *04/08*_(*2) *11/16* 4P449983-1 - 2016.06


8/8

Field settings table Installer setting at variance with


default value
Breadcrumb Field code Setting name Range, step Date Value
Default value
A.8 [E-04] Is the power saving function available on the outdoor unit? R/O 0: No
1: Yes
A.8 [E-05] Can the system prepare domestic hot water? R/W 0: No
1: Yes
A.8 [E-06] Is a DHW tank installed in the system? R/O 0: No
1: Yes
A.8 [E-07] What kind of DHW tank is installed? R/O 2: Type 3
A.8 [E-08] Power saving function for outdoor unit. R/W 0: Disabled (*2)
1: Enabled (*1)
A.8 [E-09] -- 0
A.8 [E-0A] -- 0
A.8 [E-0B] -- 0
A.8 [E-0C] -- 0
A.8 [E-0D] -- 0
A.8 [F-00] Pump operation allowed outside range. R/W 0: Disabled
1: Enabled
A.8 [F-01] -- 20°C
A.8 [F-02] Bottom plate heater ON temperature. R/W 3~10°C, step: 1°C
3°C
A.8 [F-03] Bottom plate heater hysteresis. R/W 2~5°C, step: 1°C
5°C
A.8 [F-04] Is a bottom plate heater connected? R/W 0: No
1: Yes
A.8 [F-05] -- 0
A.8 [F-06] -- 0
A.8 [F-09] Pump operation during flow abnormality. R/W 0: Disabled
1: Enabled
A.8 [F-0A] -- 0
A.8 [F-0B] Close shut-off valve during thermo OFF? R/W 0: No
1: Yes
A.8 [F-0C] -- 1
A.8 [F-0D] What is the pump operation mode? R/W 0: Continuous
1: Sample
2: Request

4P449983-1 - 2016.06 (*1) *04/08*_(*2) *11/16*