Product data sheet 6EP1334-3BA00

SITOP PSU200M 10 A STABILIZED POWER SUPPLY


INPUT: 120/230-500 V AC OUTPUT: 24 V DC/10 A

Technical specifications

Product SITOP modular

Power supply, type 24 V/10 A

Input

Input 1-phase and 2-phase AC

Supply voltage / 1 / with AC 120 … 230 V

Supply voltage / 2 / with AC 230 … 500 V

Voltage range

• Note Set by means of selector switch on the device

Input voltage / 1 / at AC 85 … 264 V

Input voltage / 2 / at AC 176 … 550 V

Wide-range input Yes

Overvoltage resistance 1300 Vpeak, 1.3 ms

Mains buffering at Iout rated, min. 25 ms

Mains buffering at Vin = 120/230 V, typ. 150 ms at Vin = 400 V

Rated line frequency 50 / 60 Hz

Rated line range 47 ... 63 Hz

Input current / at nominal level of the input voltage 120 V 4.4 A

Input current / at nominal level of the input voltage 230 V 2.4 A

Input current / at nominal level of the input voltage 500 V 1.1 A

Switch-on current limiting (+25 °C), max. 35 A

6EP1334-3BA00 subject to modifications


Page 1/ 4 05/02/2014 © Copyright Siemens AG 2014
I²t, max. 4 A²·s

Built-in incoming fuse T 6.3 A (not accessible)

Protection in the mains power input (IEC 898) Recommended miniature circuit breaker at 1-phase operation: from
6 A (10 A) characteristic C (B); required at 2-phase operation: circuit
breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10
(setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V

Output

Output Controlled, isolated DC voltage

Rated voltage Vout DC 24 V

Total tolerance, static ± 3%

Static mains compensation, approx. 0.1 %

Static load balancing, approx. 0.1 %

Residual ripple peak-peak, max. 50 mV

Spikes peak-peak, max. (bandwidth: 20 MHz) 200 mV

Adjustment range 24 … 28.8 V

Product feature / output voltage adjustable Yes

Output voltage setting via potentiometer

Status display Green LED for 24 V OK

Signaling via signaling module (6EP1961-3BA10)

On/off behavior Overshoot of Vout approx. 3 %

Startup delay, max. 1s

Voltage rise, typ. 50 ms

Rated current value Iout rated 10 A

Current range 0 … 10 A

• Note +60 ... +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V)

delivered active power / typ. 240 W

Constant overload current / in the event of a short circuit during 12 A


startup /typical

short-term overload current / at short-circuit during operation / typical 30 A

Duration of overloading ability for excess current / on short-circuiting 25 ms


during the operational phase

Parallel switching for enhanced performance Yes

• Note switchable characteristic

Numbers of parallel switchable units for enhanced performance 2

Efficiency

Efficiency at Vout rated, Iout rated, approx. 87 %

Power loss at Vout rated, Iout rated, approx. 36 W

Closed-loop control

Dynamic mains compensation (Vin rated ±15 %), max. 0.1 %

Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 3%

6EP1334-3BA00 subject to modifications


Page 2/ 4 05/02/2014 © Copyright Siemens AG 2014
Load step setting time 50 to 100%, typ. 2 ms

Load step setting time 100 to 50%, typ. 2 ms

Setting time / maximum 5 ms

Protection and monitoring

Output overvoltage protection < 35 V

Current limitation, typ. 12 A

Characteristic feature of the output / short-circuit protected Yes

Short-circuit protection Alternatively, constant current characteristic approx. 12 A or latching


shutdown

Enduring short circuit current / Effective level / typical 12 A

Overload/short-circuit indicator LED yellow for "overload", LED red for "latching shutdown"

Safety

Primary/secondary isolation Yes

Potential separation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178

Protection class Class I

stray current / maximum 3.5 mA

stray current / typical 0.32 mA

CE mark Yes

UL/CSA approval Yes

UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259

Explosion protection ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cCSAus (CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3

FM approval -

CB approval No

Marine approval GL, ABS

Degree of protection (EN 60529) IP20

EMC

Emitted interference EN 55022 Class B

Supply harmonics limitation EN 61000-3-2

Noise immunity EN 61000-6-2

Operating data

Ambient temperature / in operation -25 … +70 °C

• Note with natural convection

Ambient temperature / on transport -40 … +85 °C

Ambient temperature / in storage -40 … +85 °C

Humidity class according to EN 60721 Climate class 3K3, no condensation

Mechanics

Connection technology screw-type terminals

6EP1334-3BA00 subject to modifications


Page 3/ 4 05/02/2014 © Copyright Siemens AG 2014
Connections / Supply input L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely
stranded

Connections / Output +, -: 2 screw terminals each for 0.2 ... 2.5 mm²

Connections / Auxiliary -

Width / of the housing 90 mm

Height / of the housing 125 mm

Depth / of the housing 125 mm

Installation width 90 mm

Mounting height 225 mm

Weight, approx. 1.4 kg

Product feature / of the housing / housing for side-by-side mounting Yes

Mounting type / wall mounting No

Type of mounting / standard rail mounting Yes

Mounting type / S7-300 rail mounting No

Installation Snaps onto DIN rail EN 60715 35x7.5/15

Electrical accessories Buffer module, signaling module

Other information Specifications at rated input voltage and ambient temperature +25