Ammodbus
Ammodbus
AM-MODBUS(-W)
Communication module for frequency inverters from the Basic series and fans from the
ECblue (D+G), AMblue and PMblue series
Operating Instructions
Content
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 FCC / IC Statements (for AM-MODBUS-W modules only) . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Connection terminal type A-G-247NW for service . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 RS-485 interface for MODBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4.1 Automatic addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.5 AM-MODBUS-W Wireless Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 A-G-247NW + PMblue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.1 Procedure for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.2 Menu group Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.3 Menu group Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.4 Menu group Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
13 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.2 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
13.3 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
13.4 Service information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
1 General notes
1.1 Structure of the operating instructions
These operating instructions only apply in conjunction with the mounting/operating instruc-
tions for the device in which this module is installed. The remarks concerning safety, installa-
tion and connection described there must be followed!
Before installation and start-up, read this manual carefully to ensure correct use!
Note: This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
FCC Warning
Changes or modifications not expressly approved by the party responsible for compliance could void
the user's authority to operate the equipment.
IC Compliance (Canada)
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions: (1) this device may not cause interference, and (2) this device must
accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio
exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit
pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique
subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
2 Safety instructions
Information
Mounting, electrical connection, and start-up operation may only be carried out by an electrical
specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)!
3 General description
3.1 Application
The add-on module can only be used together with compatible ZIEHL-ABEGG devices.
Note: The AM-MODBUS-W module is intended exclusively for integration and utilisation in host
devices (fans and converters) from ZIEHL-ABEGG.
3.2 Function
Access to the MODBUS register is possible via the RS-485 interface for MODBUS RTU.
Menu-guided programming is possible with the hand held terminal type A-G-247NW, the connection
can be made via the RS-485 interface (wired) or wirelessly by radio (AM-MODBUS- W).
Devices with integrated auxiliary module AM-MODBUS(-W) offer the following functions:
• The ECblue fan and the frequency inverter can be communicated with via the module. To program
desired functions during start-up or for diagnostics, the module can be inserted fort he required
period of time or can be left in the device.
• Devices can be integrated into existing MODBUS-RTU networks. A MODBUS network with several
members can be built up, communication is made via MODBUS-RTU.
• The members connected in a network can be addressed automatically. Manual addressing is not
necessary!
• Parameter sets can be saved by the module in the terminal type A-G-247NW and transferred to
other devices ( Operating Instructions Terminal Type A-G-247NW).
• It is possible to save and exchange parameters sets by PC via the USB interface of the terminal
type A-G-247NW ( Operating Instructions Terminal Type A-G-247NW).
• For ECblue fans tacho output with frequency signal, the evaluation of the signal shows the current
fan speed.
3.3 Transport
• The device is packed ex factory to suit the transport method previously agreed.
• Always use the original packaging materials when transporting the device.
• Avoid shocks and impacts to the device during the transport.
• During manual handling the human lifting and carrying restrictions must be observed and adhered
to.
3.4 Storage
• The device must be stored in its original packaging in a dry and weather-proof room.
• Avoid exposure to extreme heat and cold.
• Avoid over-long storage periods (we recommend a maximum of one year).
" ECblue: Mount the module in the housing with the two enclosed screws (permissible tightening
torque MA = 1.3 Nm).
" Fcontrol Basic, Icontrol Basic, PMcontrol: Press the module into the retaining clips.
" Permissible tightening torque of connection terminals MA = 0.24 Nm.
" When an AM-MODBUS-W module is installed in a fan or converter from ZIEHL-ABEGG, the
enclosed FCC/IC label “AM-MODBUS-W” inside must be stuck to the housing of the terminating
device.
5 Electrical installation
5.1 Safety precautions
Danger due to electric current
• Work on electric components may only be carried out by trained electricians or by persons
instructed in electricity under the supervision of an electrician in accordance with electrical
engineering regulations.
• It is forbidden to carry out work on electrically live parts.
IRDA-RXD
IRDA-TXD
IRDA-SD
A
(D+)
B
(D-)
GND
+5V
AM-MODBUS
A B A B
GND ID GND ID fout GND
(D+) (D-) (D+) (D-)
06.03.2014
v_modbus_link_terminal.vsd
The voltage supply of the terminal is made by the accumulators inserted there or the plug power
supply unit.
Addressing
Addressing
Addressing
11.03.2014
v_am_modbus_connect.vsd
The connections for MODBUS “A (D+)”, “B (D-)” are available double on the module and are connected with each other
internally.
Information
• You must ensure correct connection; i.e. “A (D+)” must also be connected on the following devices
to “A (D+)”. The same applies to “B (D-)”.
• addition, a "GND" connection must be established, as dissimilar potential (over 10 V!) will lead to
In
the destruction of the RS-485 interface (e.g. lightning).
• Except the data link “A (D+)”, “B (D-)” and “GND” (for automatic addressing additional “ID1” - “ID2”
following chapter) no further cable cores of the data line may be used.
• Do not use wire shield.
• Pay attention to sufficient distance from powerlines and motor wires (min. 20 cm).
• A maximum of 64 members can be directly connected to one another, and another 63 members via
a repeater (only for manual addressing i.e. no connection of the terminals “ID1”,“ID2”).
MODBUS
26.02.2007
v_modbus_verbindung.vsd
When using telephone flex with four cable cores, we recommend the following allocation:
• A (D+) = red
• B (D-) = black
• ID1 - ID2 = yellow (for automatic addressing)
• GND = white
MODBUS
(RS-485)
(D+)
B
(D-)
GND
A-G-247NW A-G-102ANE
UNIcon
MODBUS Master
Addressing
Addressing
Addressing
Addressing
MODBUS MODBUS MODBUS MODBUS
(RS-485) (RS-485) (RS-485) (RS-485)
A B A B A B A B
GND ID1 GND ID2 GND ID1 GND ID2
(D+) (D-) (D+) (D-) (D+) (D-) (D+) (D-)
10.03.2014
v_am_modbus_autoadr_A-G.vsd
Connection a MODBUS Master via the terminals: 1 A (1D+), B (1D-), ID and GND
Connection of the Slave members via the terminals: A (D+), B (D-), GND and ID1 / ID2
Information
• Except the data link “A (D+)”, “B (D-)” the “ID1 - ID2” and the “GND” connection may no further cable
cores of the data line be used.
• The connections for the automatic addressing “ID1” and “ID2” are not directly connected with each
other internally. These may not be bridged; any order of connection is possible.
• When using the automatic addressing, no repeaters can be used because these do not pass the
signal through to the addressing.
• Maximum number of members in automatic addressing:
– With hand held terminal type A-G-247 and control unit NETcon type A-G-102ANE max. 63
members.
– With control module UNIcon MODBUS Master max. 32 members.
On the first user that is connected directly to a terminal, MODBUS Master or PC, “GND” and “ID1” or
“ID2” must be bridged. This is recognised as a result and occupied by address 1.
For the following users the connection “ID1” or “ID2” of a user respectively is connected with
connection “ID1” or “ID2” of the next user.
The automatic addressing of other users is initiated by the previous user via this connection.
" Switch over between actual value* and “Start” with |Esc | arrow key.
" Switch over between “Start” and actual value* with |i | key.
* Actual value depending on device type: "Speed" / rpm,, "Frequency" / Hz, "Modulation" / %
" By pushing the P- key one reaches the menu item “Start”.
P↓
" Return to the menu group “Start” using arrow key |Esc | .
▲▼ " One moves up and down within the menu group using the arrow keys.
▲ ▲ ▲ ▲
▼ ▼ ▼ ▼
↑ ↑ ↑ ↑ ↑
|Esc | P |Esc | P |Esc | P |Esc | P |Esc | P
↓ ↓ ↓ ↓ ↓
▲▼ ▲▼ ▲▼ ▲▼
Selection of the menu group (e.g. “Setting”) to the right through the ▼-key, to the left through the ▲-key.
You can go to the menu items in the menu groups (e.g. “Set Intern1”) by using the P-key. Use the arrow keys to move up and
down within the menu group.
The menu groups consist of one area for the user (user menu) and one area for installation (service). The service area can be
protected against unauthorized access by using a PIN.
To make adjustments, press the P -key after selecting the menu item. If the previously set value starts to flash, it can be adjusted
with the ▼ + ▲ keys and then saved with the P -key. To exit the menu without making any changes, use the “Esc” key, i.e., the
originally set values remain.
Setting
Setting
Set Intern1
Setting only in Controlmode |4 | active ( Controller Setup).
Via the inputs “D1” / “E1” it is possible to switch to “Set Intern2” or “Set Intern3” ( IO
Setup).
Set Intern1
Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Set Intern2
Setting only in control mode |5 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern2 Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Set Intern3
Setting only in control mode |6 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern3 Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Min. Speed
The basic speed is active in every control mode.
Setting range: 0...100 % (Rated speed)
Min. Speed
Factory setting*: 0 %
Max. Speed
The speed limiting is active in every control mode.
Setting range: 100 % (Rated speed)... “Min.Speed”
Max. Speed
Factory setting*: 100 % (Rated speed)
* Specifications not binding, these values can differe depending on the software version and customer-specific pre-setting.
100 %
n-min 40 % n-max. = 100 %
90
n-min 40 % n-max. = 90 %
80
70
60
50
40
20
10
Analog In 1
0 1 2 3 4 5 6 7 8 9 10 0...10 V
0 10 20 30 40 50 60 70 80 90 100 0...100 % PWM
25.03.2014
v_ecblue_set_min_max.vsd
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN input
PIN 0010
Release of the service settings with programmed PIN-Accesslevel |0 | ( “Controller
Setup”).
Menu groups Service: “Controller Setup”, “IO Setup”, “Motor Setup”
PIN 1234
Opening “setting”.
Release of the menu group for the user “setting” with programmed PIN-Accesslevel |0 |
( “Controller Setup”).
PIN 3698
Communications parameters take-over.
PIN 9095
Load factory setting (exception, the menu language setting is retained).
Only the parameters which are released by the currently set PIN-Accesslevel are
loaded.
Reset
Complete re-start of the device
Reset
Software version
Firmware
Parameter sets can be saved by the module in the terminal type A-G-247NW and
transferred to other devices ( Operating Instructions Terminal Type A-G-247NW).
Name parameterset with the keys ▼, ▲ + P and load in the terminal with the P-key.
- - - - - - - - - -.CSV
Info
Speed
Motor speed
Speed
Motor current
Display of internal motor current (metering precision approx. +/-10 %)
Motor current
Modulation
Display of modulation 0...100 % (metering precision approx. +/- 10 %)
Modulation
Output power
Display of output power (metering precision approx. +/-10 %)
Output power
Controller Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
7.5.1 Controlmode
Controlmode
Factory setting
Control by external signal (0 - 10 V / PWM) at the input “E1”.
0
Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
1 no function
2 no function
3 no function
constant speed “Set Intern1”.
4 Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
5 Fixed speed “Default Internal2” (without switching possibility to other default).
6 Fixed speed “Default Internal3” (without switching possibility to other default).
7.5.2 Limit
Limit
“Limit value” = max. possible modulation (e.g. Limit (idealized principle diagram)
speed reduction during night operation by n [%]
e. no limit. L
50
Min.
Si [%]
0 50 100
07.10.2010
v_limit_101_rpm.vsd
LED Mode
Only for versions with integrated status LED!
LED Mode
Setting Function
Status LED in ECblue active i.e. operating conditions are indicated by flash code
ON (factory setting).
OFF Status LED not active, i.e. always OFF.
7.5.4 PIN-Accesslevel
PIN-Accesslevel
The PIN-Accesslevel determines for which setting ranges a PIN must be entered.
PIN-Accesslevel
Setting Function
Factory setting
2 All menu groups are visible, settings are possible without a PIN.
• The menu group “Setting” is free, i.e. changes are possible without a PIN.
1 • PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
All settings are only possible after entering a PIN.
0
• PIN 1234 for changes in the menu group: “Setting”
• PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
Information
Changes for the PIN protection which effect a reduced access right only become active after switching
off the device or executing the “Reset” ( Start menu group) function.
Wireless channel
Setting range: 0 - 15
Factory setting: 0
Wireless channel
Via the output “fout” the current motor speed can be 100 Ω
output.
Tacho out
With the voltage supply “10 V” / “24 V” (from the board of 24 V 10V GND fout
the basic unit) a frequency can be measured by a pull-
up resistor at the output “fout” which corresponds to the Pull Up Pull Up
10 kΩ 5 kΩ
speed of the motor (duty cycle 50 : 50). Hz
26.03.2014
i_ecblue_am_modbus_fout_tacho.eps
IO Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
Different functions can be assigned to the digital inputs “D1” and “E1”*.
Activation via floating contacts (a low voltage of approx. 24 V DC is connected).
“D1” is programmed for the “Enable” function at the factory.
D1 Function
* If the analogue input “E1” is not required for specifying the fan speed, this can be used as a digital input ( E1 function).
The same functions can be assigned for “E1” as for “D1”.
Attention!
Never apply line voltage to the digital input!
Function Description
OFF no function
1D Enable ON / OFF (factory setting)
Remote ON/OFF (electronic switch-off) by potential-free contact. The power unit is
switched off electronically, the device can still be operated in the switched-off state
after pressing the “Esc” key combination. Signal inputs and outputs remain active.
A programmed alarm relay (factory set “K1 function” = |2K | ) does not report the
switch-off.
Attention!
No disconnection (no potential isolation in accordance with VBG4 §6) in remote control
of the device!
3D Limit ON / OFF
Controller Setup / Limit
5D Set Intern2
Fixed speed “Default Internal2” active. Function with selected “Control mode”: 0 (
“Controller Setup”).
With simultaneous activation of “Default Internal3” with function |6D | , |5D | has prior-
ity).
6D Set Intern3
Constant speed “Set Intern3”, also with selected “Control mode”: 0 ( “Controller
Setup”).
13D Switch over direction of rotation
Switch over between direction of rotation “RIGHT” = |CW | and direction of rotation
“LEFT” |CCW | .
When“switching”over via a digital input, the device works with the opposite direction of
rotation than the one set in Motor Setup.
If the rotary direction is reversed with an available modulation, it is initially reduced to
“0” (disconnected) and subsequently increased back to the default value.
15D Smoke extraction: Switch off temperature management, operation at max. speed
To make the ECblue as durable as possible, the devices have active temperature
management. The modulation is reduced when internal temperature limits are ex-
ceeded.
In venting systems in which the fan must run at max. speed in the event of a fire, the
temperature management can be switched off by a digital input. At the same time, the
fan is operated independently of the speed default for regular operation at maximum
speed.
The function is activated at the digital input with the contact open (at factory setting
|D1/E1 Inverting | = OFF) so that the maximum speed of the fan is also possible with
the line to the digital input interrupted in case of fire.
Attention!
The device and its internal components are no longer protected against overtemper-
ature when this function is activated (this affects the life installation instructions ECbl-
ue).
Function Description
OFF no function
Relays remain always de-energized .
1K Operating indication
Operation without fault, reports enable “OFF”.
2K Fault indication (factory setting)
Pulled up in operation without fault, with release “OFF” not dropped out.
Drops out at: line fault, motor fault, etc. Events / Fault indications
4K Limit
Alarm when the speed exceeds the value set under “Default Internal3” ( menu group
“Setting”) (output power > 0 %).
The function is active in every Controlmode ( menu group: “Controller Setup”).
17K no function
20K Fault indication or message for active temperature management
In addition to the fault indication, a message will appear in the case of active temper-
ature management, i.e. if the specified temperature limits are exceeded resulting in a
reduction in modulation (function from software version 13.31 and upwards).
K1
1 = energized, terminals 11 - 14 bridged
0 = de-energized 11 - 14 not bridged
11 14
17.09.2009
v_relais_k1_11_14.vsd
K1
E1 Function
|1E | (factory setting) = speed setting by external signal (0 - 10 V / PWM).
For settings via |1E | “E1” operates like “D1” as a digital input ( Digital inputs /
E1 Function
function).
E1 Inverting
Factory setting inverting to “OFF”.
For control with inverted setting signal switch to “ON” (setting signal: 10 - 0 V).
E1 Inverting
E1 min.
Value of the input signal at which the controller starts at minimum modulation.
Setting range: 0 - 100 %
E1 min.
Factory setting: 5 %
E1 max
Value of the input signal at which the maximum modulation of the controller is reached.
Setting range: 0 - 100 %
E1 max
Factory setting: 100 %
nM
100 %
%
0
10
.=
ax
m
3
1
,E
%
0
.=
in
m
E1
%
2
50
x. =
ma
E1
50 % 1
%,
=0.
min
%
E1
0
10
.=
ax
m
1
,E
%
5
.=
in
m
E1
6%
4.5 %
0.5 V
Si
5 % PWM
0 1 2 3 4 5 6 7 8 9 10 0 – 10 V
0 10 20 30 40 50 60 70 80 90 100 0 – 100 % PWM
21.07.2015
v_ecblue_nmotor_at_0_10v_pwm.vsd
nM Motor speed
100 % Rated speed
6 % Height of start speed
4.5 % Height of stop speed
0.5 V / 5 % PWM Value start analog input (factory setting)
Si Speed setting signal 0...10 V / 0...100 % PWM
Watchdog Time
If the device receives no message in the time window, a definable function is executed.
Watchdog Time
Watchdog time in seconds.
Setting range: 0 - 255 sec.
Factory setting: 0 sec. = off
Watchdog Mode
Watchdog Mode:
0: No function (default) = OFF from FW 13
Watchdog Mode
1: Fault (K1 function, h15) in case of communication fault (WDT)
2: Constant speed 1 * in case of communication fault (WDT)
3: Fault + constant speed 1 * in case of communication fault (WDT)
4: Fault by E1 Fault ** (only ECblue)
5: Constant speed 1 by E1 Fault (only ECblue)
6: Fault constant speed 1 in case of E1 fault (only ECblue)
* in this condition it is possible by digital input function 5, 6 or digital control function to
change between the constant speeds (Holding register h4).
** E1 fault is triggered when E1 falls below E1 Min x 0.5. E1 fault is cancelled when E1
rises above E1 Min x 0.9.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
Bus Address
UART Baudrate
Setting transfer rate
Valid values: 4,800, 9,600, 19,200
Com. Baudrate
Factory setting: 19200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Com. Mode
Factory setting: 8E1
Information
Modified communication parameters are not taken over until the unit has been reset or until the PIN
input |3698 | !
Motor Setup
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Rampup time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Rampdown time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
0 .. 100 %
09.05.2007
2 v_hochlaufzeit_ruecklaufzeit.vsd
1 external Signal
2 Setting
3 Rampup time
4 Rampdown time
100 %
50 %
35 % max
Setting depending on device type
1 15 % min
in: %, Hz, rpm
09.05.2007
v_ausblendung_prz.vsd
0% 50 % 100 % D
I I
S R P
A Modulation
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
Suppression1 Suppression1
Suppression2
8 A-G-247NW + PMblue
8.1 Procedure for commissioning
Sequence Setting
Setting
Setting
Set Intern1
Setting only in Controlmode |4 | active ( Controller Setup).
Via the inputs “D1” / “E1” it is possible to switch to “Set Intern2” or “Set Intern3” ( IO
Setup).
Set Intern1
Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Set Intern2
Setting only in control mode |5 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern2 Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Set Intern3
Setting only in control mode |6 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern3 Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Min. Speed
The basic speed is active in every control mode.
Setting range: 0...100 % (Rated speed)
Min. Speed
Factory setting*: 0 %
Max. Speed
The speed limiting is active in every control mode.
Setting range: 100 % (Rated speed)... “Min.Speed”
Max. Speed
Factory setting*: 100 % (Rated speed)
* Specifications not binding, these values can differe depending on the software version and customer-specific pre-setting.
100 %
n-min 20 % n-max. = 100 %
90
n-min 40 % n-max. = 90 %
80
70
60
50
40
20
10
Analog In 1
0 1 2 3 4 5 6 7 8 9 10 0...10 V
0 10 20 30 40 50 60 70 80 90 100 0...100 % PWM
0 2 4 6 8 10 12 14 16 18 20 0...20 mA 24.08.2015
v_pmblue_set_min_max.vsd
nM Motor speed
100 % Rated speed
Analog In 1 Speed setting signal 0...10 V / 0...100 % PWM
The motor always starts with at least 10 % of the rated speed as soon as a speed setting signal above
0 % is applied (a lower speed is not possible in principle). The motor stops at 0 % setting signal.
Between 1 % and 10 % setting signal the speed stays at approx. 10 % rated speed providing that the
setting “Min. speed ”is “0” rpm (adjustable by auxiliary modules).
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN input
PIN 0010
Release of the service settings with programmed PIN-Accesslevel |0 | ( “Controller
Setup”).
Menu groups Service: “Controller Setup”, “IO Setup”, “Motor Setup”
PIN 1234
Opening “setting”.
Release of the menu group for the user “setting” with programmed PIN-Accesslevel |0 |
( “Controller Setup”).
PIN 3698
Communications parameters take-over.
PIN 9095
Load factory setting (exception, the menu language setting is retained).
Only the parameters which are released by the currently set PIN-Accesslevel are
loaded.
Reset
Complete re-start of the device
Reset
Software version
Firmware
Parameter sets can be saved by the module in the terminal type A-G-247NW and
transferred to other devices ( Operating Instructions Terminal Type A-G-247NW).
Name parameterset with the keys ▼, ▲ + P and load in the terminal with the P-key.
- - - - - - - - - -.CSV
Info
Speed
Motor speed
Speed
Motor current
Display of internal motor current (metering precision approx. +/-10 %)
Motor current
Modulation
Display of modulation 0...100 % (metering precision approx. +/- 10 %)
Modulation
Output power
Display of output power (metering precision approx. +/-10 %)
Output power
Controller Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
8.5.1 Controlmode
Controlmode
Factory setting
Control by external signal (0 - 10 V / PWM) at the input “E1”.
0
Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
1 no function
2 no function
3 no function
constant speed “Set Intern1”.
4 Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
5 Fixed speed “Default Internal2” (without switching possibility to other default).
6 Fixed speed “Default Internal3” (without switching possibility to other default).
8.5.2 Limit
Limit
“Limit value” = max. possible modulation (e.g. Limit (idealized principle diagram)
speed reduction during night operation by n [%]
e. no limit. L
50
Min.
Si [%]
0 50 100
07.10.2010
v_limit_101_rpm.vsd
LED Mode
Only for versions with integrated status LED!
LED Mode
Setting Function
Status LED in ECblue active i.e. operating conditions are indicated by flash code
ON (factory setting).
OFF Status LED not active, i.e. always OFF.
8.5.4 PIN-Accesslevel
PIN-Accesslevel
The PIN-Accesslevel determines for which setting ranges a PIN must be entered.
PIN-Accesslevel
Setting Function
Factory setting
2 All menu groups are visible, settings are possible without a PIN.
• The menu group “Setting” is free, i.e. changes are possible without a PIN.
1 • PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
All settings are only possible after entering a PIN.
0
• PIN 1234 for changes in the menu group: “Setting”
• PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
Information
Changes for the PIN protection which effect a reduced access right only become active after switching
off the device or executing the “Reset” ( Start menu group) function.
Wireless channel
Setting range: 0 - 15
Factory setting: 0
Wireless channel
Via the output “fout” the current motor speed can be 100 Ω
output.
Tacho out
With the voltage supply “10 V” / “24 V” (from the board of 24 V 10V GND fout
the basic unit) a frequency can be measured by a pull-
up resistor at the output “fout” which corresponds to the Pull Up Pull Up
10 kΩ 5 kΩ
speed of the motor (duty cycle 50 : 50). Hz
26.03.2014
i_ecblue_am_modbus_fout_tacho.eps
IO Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
Different functions can be assigned to the digital inputs “D1” and “E1”*.
Activation via floating contacts (a low voltage of approx. 24 V DC is connected).
“D1” is programmed for the “Enable” function at the factory.
D1 Function
* If the analogue input “E1” is not required for specifying the fan speed, this can be used as a digital input ( E1 function).
The same functions can be assigned for “E1” as for “D1”.
Attention!
Never apply line voltage to the digital input!
Function Description
OFF no function
1D Enable ON / OFF (factory setting)
Remote ON/OFF (electronic switch-off) by potential-free contact. The power unit is
switched off electronically, the device can still be operated in the switched-off state
after pressing the “Esc” key combination. Signal inputs and outputs remain active.
A programmed alarm relay (factory set “K1 function” = |2K | ) does not report the
switch-off.
Attention!
No disconnection (no potential isolation in accordance with VBG4 §6) in remote control
of the device!
3D Limit ON / OFF
Controller Setup / Limit
5D Set Intern2
Fixed speed “Default Internal2” active. Function with selected “Control mode”: 0 (
“Controller Setup”).
With simultaneous activation of “Default Internal3” with function |6D | , |5D | has prior-
ity).
6D Set Intern3
Constant speed “Set Intern3”, also with selected “Control mode”: 0 ( “Controller
Setup”).
13D Switch over direction of rotation
Switch over between direction of rotation “RIGHT” = |CW | and direction of rotation
“LEFT” |CCW | .
When“switching”over via a digital input, the device works with the opposite direction of
rotation than the one set in Motor Setup.
If the rotary direction is reversed with an available modulation, it is initially reduced to
“0” (disconnected) and subsequently increased back to the default value.
15D Smoke extraction: Switch off temperature management, operation at max. speed
To make the ECblue as durable as possible, the devices have active temperature
management. The modulation is reduced when internal temperature limits are ex-
ceeded.
In venting systems in which the fan must run at max. speed in the event of a fire, the
temperature management can be switched off by a digital input. At the same time, the
fan is operated independently of the speed default for regular operation at maximum
speed.
The function is activated at the digital input with the contact open (at factory setting
|D1/E1 Inverting | = OFF) so that the maximum speed of the fan is also possible with
the line to the digital input interrupted in case of fire.
Attention!
The device and its internal components are no longer protected against overtemper-
ature when this function is activated (this affects the life installation instructions ECbl-
ue).
Function Description
OFF no function
Relays remain always de-energized.
1K Operating indication
Operation without fault, reports enable “OFF”.
2K Fault indication (factory setting)
Pulled up in operation without fault, with release “OFF” not dropped out.
Drops out at: line fault, motor fault, etc. Events / Fault indications
4K Limit
Alarm when the speed exceeds the value set under “Default Internal3” ( menu group
“Setting”) (output power > 0 %).
The function is active in every control mode ( menu group: “Controller Setup”).
17K no function
K1
1 = energized, terminals 13 - 14 bridged
0 = de-energized 13-14 not bridged
13 14
10.11.2008
v_relais_k1_13_14.vsd
K1
E1 Function
|1E | (factory setting) = speed setting by external signal (0 - 10 V / PWM).
For settings via |1E | “E1” operates like “D1” as a digital input ( Digital inputs /
E1 Function
function).
E1 Inverting
Factory setting inverting to “OFF”.
For control with inverted setting signal switch to “ON” (setting signal: 10 - 0 V).
E1 Inverting
E1 min.
Value of the input signal at which the controller starts at minimum modulation.
Setting range: 0 - 100 %
E1 min.
Factory setting: 5 %
E1 max
Value of the input signal at which the maximum modulation of the controller is reached.
Setting range: 0 - 100 %
E1 max
Factory setting: 100 %
100 %
%
0
10
.=
ax
m
3
1
,E
%
0
.=
in
m
E1
%
2
50
x. =
ma
E1
50 % 1
%,
=0.
min
%
0
10
E1
.=
ax
m
1
,E
%
5
.=
in
m
E1
0.5 V
Si
5 % PWM
0 1 2 3 4 5 6 7 8 9 10 0 – 10 V
0 10 20 30 40 50 60 70 80 90 100 0 – 100 % PWM
17.12.2015
v_pmblue_nmotor_at_0_10v_pwm.vsd
nM Motor speed
100 % Rated speed
6 % Height of start speed
4.5 % Height of stop speed
0.5 V / 5 % PWM Value start analog input (factory setting)
Si Speed setting signal 0...10 V / 0...100 % PWM
Watchdog Time
If the device receives no message in the time window, a definable function is executed.
Watchdog Time
Watchdog time in seconds.
Setting range: 0 - 255 sec.
Factory setting: 0 sec. = off
Watchdog Mode
Watchdog Mode:
0: No function (default) = OFF from FW 13
Watchdog Mode
1: Fault (K1 function, h15) in case of communication fault (WDT)
2: Constant speed 1 * in case of communication fault (WDT)
3: Fault + constant speed 1 * in case of communication fault (WDT)
4: Fault by E1 Fault ** (only ECblue)
5: Constant speed 1 by E1 Fault (only ECblue)
6: Fault constant speed 1 in case of E1 fault (only ECblue)
* in this condition it is possible by digital input function 5, 6 or digital control function to
change between the constant speeds (Holding register h4).
** E1 fault is triggered when E1 falls below E1 Min x 0.5. E1 fault is cancelled when E1
rises above E1 Min x 0.9.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
Bus Address
UART Baudrate
Setting transfer rate
Valid values: 4,800, 9,600, 19,200
Com. Baudrate
Factory setting: 19200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Com. Mode
Factory setting: 8E1
Information
Modified communication parameters are not taken over until the unit has been reset or until the PIN
input |3698 | !
Motor Setup
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Rampup time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Rampdown time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
0 .. 100 %
09.05.2007
2 v_hochlaufzeit_ruecklaufzeit.vsd
1 external Signal
2 Setting
3 Rampup time
4 Rampdown time
100 %
50 %
35 % max
Setting depending on device type
1 15 % min
in: %, Hz, rpm
09.05.2007
v_ausblendung_prz.vsd
0% 50 % 100 % D
I I
S R P
A Modulation
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
Suppression1 Suppression1
Suppression2
Check if Thermostats or Thermistors of the motor are connected to input “TB/TP In”.
1 If the motor protection function of the device is not neccesary the both terminals “TB / TP” have to
be bridged.
The Motor Setup factory installed values are for variable voltage external rotor motors 400 V /
50 Hz. After checking of the motor data the setting are to be adapted if necessary.
Motor rated voltage Setting Setting
(see Rating plate) Edgefrequency Max. Frequency
5 3 ~ 400 V, 50 Hz 48.5 Hz 50 Hz
3 ~ 400 V, 50/60 Hz 48.5 Hz 60 Hz
3 ~ 400 V, 60 Hz 57 Hz 60 Hz
Additional settings Motor Setup.
Settings for U/f characteristic can only be made when no motor modulation is present!
" Switch off via a digital input for remote control (enable= OFF).
" Reduce speed setting signal or setting value to “0” with the display depending on the control mode.
Setting
Set Intern1
Setting only in Controlmode |4 | active ( Controller Setup).
Via the inputs “D1” / “E1” it is possible to switch to “Default Internal2” or “Default
Set Intern1
Internal3” ( IO Setup).
Setting range manual speed setting: “Min. Speed” - “Max. Speed”
Factory setting: 50.0 Hz ( Setting “Max. Speed”)
Set Intern2
Setting only in control mode |6 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern2
Setting range manual speed setting: “Min. Speed” - “Max. Speed”
Factory setting: 50.0 Hz ( Setting “Max. Speed”)
Set Intern3
Setting only in control mode |6 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern3
Setting range manual speed setting: “Min. Speed” - “Max. Speed”
Factory setting: 50.0 Hz ( Setting “Max. Speed”)
50
n-min 10 Hz n-max. = 50 Hz
45
n-min 20 Hz n-max. = 45 Hz
40
35
30
25
20
10
Foff = 5 Hz
5
Fon = 6 Hz
Analog In 1
0 1 2 3 4 5 6 7 8 9 10 0...10 V
0 2 4 6 8 10 12 14 16 18 20 0...20 mA
0 10 20 30 40 50 60 70 80 90 100 0...100 % PWM 08.05.2012
v_fxdm_setsig_min_max.vsd
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN input
PIN 0010
Release of the service settings with programmed PIN-Accesslevel |0 | ( “Controller
Setup”).
Menu groups Service: “Controller Setup”, “IO Setup”, “Motor Setup”
PIN 1234
Opening “setting”.
Release of the menu group for the user “setting” with programmed PIN-Accesslevel |0 |
( “Controller Setup”).
PIN 3698
Communications parameters take-over.
PIN 9095
Load factory setting (exception, the menu language setting is retained).
Only the parameters which are released by the currently set PIN-Accesslevel are
loaded.
Reset
Complete re-start of the device
Reset
Software version
Firmware
Parameter sets can be saved by the module in the terminal type A-G-247NW and
transferred to other devices ( Operating Instructions Terminal Type A-G-247NW).
Name parameterset with the keys ▼, ▲ + P and load in the terminal with the P-key.
- - - - - - - - - -.CSV
Info
Frequency
Motor current
Device modulation
Modulation
Controller Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
9.5.1 Controlmode
Controlmode
Factory setting
Control by external signal (0 - 10 V / PWM) at the input “E1”.
0
Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
1 no function
2 no function
3 no function
constant speed “Set Intern1”.
4 Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
5 Fixed speed “Default Internal2” (without switching possibility to other default).
6 Fixed speed “Default Internal3” (without switching possibility to other default).
9.5.2 Limit
Limit
“Limit value” = max. possible modulation (e.g. Limit (idealized principle diagram)
speed reduction during night operation by n [%]
e. no limit. L
50
Min.
Si [%]
0 50 100
07.10.2010
v_limit_101_rpm.vsd
LED Mode
Only for versions with integrated status LED!
LED Mode
Setting Function
Status LED in ECblue active i.e. operating conditions are indicated by flash code
ON (factory setting).
OFF Status LED not active, i.e. always OFF.
9.5.4 PIN-Accesslevel
PIN-Accesslevel
The PIN-Accesslevel determines for which setting ranges a PIN must be entered.
PIN-Accesslevel
Setting Function
Factory setting
2 All menu groups are visible, settings are possible without a PIN.
• The menu group “Setting” is free, i.e. changes are possible without a PIN.
1 • PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
All settings are only possible after entering a PIN.
0
• PIN 1234 for changes in the menu group: “Setting”
• PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
Information
Changes for the PIN protection which effect a reduced access right only become active after switching
off the device or executing the “Reset” ( Start menu group) function.
Wireless channel
Setting range: 0 - 15
Factory setting: 0
Wireless channel
IO Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
Different functions can be assigned to the digital inputs “D1” and “E1”*.
Activation via floating contacts (a low voltage of approx. 24 V DC is connected).
“D1” is programmed for the “Enable” function at the factory.
D1 Function
* If the analogue input “E1” is not required for specifying the fan speed, this can be used as a digital input ( E1 function).
The same functions can be assigned for “E1” as for “D1”.
Attention!
Never apply line voltage to the digital input!
Function Description
OFF no function
1D Enable ON / OFF (factory setting)
Remote ON/OFF (electronic disconnection) and Reset after a motor malfunction via
floating contact. The power section is electronically disconnected. Operation of the
device is still possible after pressing the “Esc” hotkey combination in switched-off
condition. Signal- in and outputs remain active.
A programmed alarm relay (factory set “K1 function” = |2K | ) does not report the
switch-off.
Attention!
No disconnection (no potential isolation in accordance with VBG4 §6) in remote control
of the device!
3D Limit ON / OFF
Controller Setup / Limit
5D Set Intern2
Fixed speed “Default Internal2” active. Function with selected “control mode”: 0, 1, 2 , 3
( “Controller Setup”).
With simultaneous activation of “Default Internal3” with function |6D | , |5D | has prior-
ity).
6D Set Intern3
Constant speed “Set Intern3”, also with selected “control mode”: 0 ( “Controller
Setup”).
13D Switch over direction of rotation
Switch over between direction of rotation “RIGHT” = |CW | and direction of rotation
“LEFT” |CCW | .
When“switching”over via a digital input, the device works with the opposite direction of
rotation than the one set in Motor Setup.
If the rotary direction is reversed with an available modulation, it is initially reduced to
“0” (disconnected) and subsequently increased back to the default value.
15D Smoke extraction: Switch off temperature management, operation at max. speed
To make the ECblue as durable as possible, the devices have active temperature
management. The modulation is reduced when internal temperature limits are ex-
ceeded.
In venting systems in which the fan must run at max. speed in the event of a fire, the
temperature management can be switched off by a digital input. At the same time, the
fan is operated independently of the speed default for regular operation at maximum
speed.
The function is activated at the digital input with the contact open (at factory setting
|D1/E1 Inverting | = OFF) so that the maximum speed of the fan is also possible with
the line to the digital input interrupted in case of fire.
Attention!
The device and its internal components are no longer protected against overtemper-
ature when this function is activated (this affects the life installation instructions ECbl-
ue).
The motor protection function by connected thermal protector is no longer effective!
Function Description
OFF no function
Relays remain always de-energized.
1K Operating indication
Operation without fault, reports enable “OFF”.
2K Fault indication (factory setting)
Pulled up in operation without fault, with release “OFF” not dropped out.
Drops out at: line fault, motor fault, etc. Events / Fault indications
4K Limit
Alarm when the speed exceeds the value set under “Default Internal3” ( menu group
“Setting”) (output power > 0 %).
The function is active in every control mode ( menu group: “Controller Setup”).
17K no function
K1
1 = energized, terminals 13 - 14 bridged
0 = de-energized 13-14 not bridged
13 14
10.11.2008
v_relais_k1_13_14.vsd
K1
E1 Function
|1E | (factory setting) = speed setting by external signal (0 - 10 V / PWM).
For settings via |1E | “E1” operates like “D1” as a digital input ( digital inputs /
E1 Function
function).
E1 Inverting
Factory setting inverting to “OFF”.
For control with inverted setting signal switch to “ON” (setting signal: 10 - 0 V).
E1 Inverting
E1 Min.
Value of the input signal at which the controller starts at minimum modulation.
Setting range: 0 - 100 %
E1 Min.
Factory setting: 5 %
E1 max
Value of the input signal at which the maximum modulation of the controller is reached.
Setting range: 0 - 100 %
E1 max
Factory setting: 100 %
Idealized principle diagrams for setting: “Min. Speed” = 0.0 Hz and “Max. Speed” = 50.0 Hz
Fout
[Hz]
50
Si E
0 1 2 3 4 5 6 7 8 9 10 0 – 10 V
15.02.2012
v_e1_adjust_i_basic.vsd
Watchdog Time
If the device receives no message in the time window, a definable function is executed.
Watchdog Time
Watchdog time in seconds.
Setting range: 0 - 255 sec.
Factory setting: 0 sec. = off
Watchdog Mode
Watchdog Mode:
0: No function (default) = OFF from FW 13
Watchdog Mode
1: Fault (K1 function, h15) in case of communication fault (WDT)
2: Constant speed 1 * in case of communication fault (WDT)
3: Fault + constant speed 1 * in case of communication fault (WDT)
4: Fault by E1 Fault ** (only ECblue)
5: Constant speed 1 by E1 Fault (only ECblue)
6: Fault constant speed 1 in case of E1 fault (only ECblue)
* in this condition it is possible by digital input function 5, 6 or digital control function to
change between the constant speeds (Holding register h4).
** E1 fault is triggered when E1 falls below E1 Min x 0.5. E1 fault is cancelled when E1
rises above E1 Min x 0.9.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
Bus Address
UART Baudrate
Setting transfer rate
Valid values: 4,800, 9,600, 19,200
Com. Baudrate
Factory setting: 19200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Com. Mode
Factory setting: 8E1
Information
Modified communication parameters are not taken over until the unit has been reset or until the PIN
input |3698 | !
Motor Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
Attention!
Settings for U/f characteristic may only be made when no motor modulation is present!
MotorRatedCurr.
Possible setting for the motor rated current.
The setting for the “DC brake level” ( setting brake behaviour) refers to this setting.
MotorRatedCurr.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
MotorRatedVolt.
When commissioning, you must set the motor to the rated voltage stated on the
rating plate.
MotorRatedVolt.
An adaptation can be made if the motor rated-voltage as the applied mains voltage is
lower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).
Verify the output voltage using suitable measuring instruments.
Setting range: 0...500 V
Factory setting: 400 V
Edgefrequency
The maximum output voltage is attained during break edge frequency.
Adjustment range: 1.0 - 120.0 Hz
Edgefrequency
Factory setting: 48.5 Hz
In the case of special settings with “Edge frequency” > “Max. frequency”, due to higher
power losses it is possible that automatic power reduction occurs ( Messages and
trouble shooting “Temp. Manager”).
Max. Frequency
Above the Edgefrequency, the frequency is merely increased up to the Maximum
frequency.
Max. Frequency
Adjustment range: 1.0 - 120 Hz
Factory setting: 50.0 Hz
Uout
Fmax = 50 Hz
100 %
Fedge = 48.5 Hz
Foff
Ustart = 10 %
Fon
Ustart = 0 % Fout [Hz]
0 5 10 15 20 25 30 35 40 45 50
Analog In 1
0.5 1 2 3 4 5 6 7 8 9 10 0...10 V
1 2 4 6 8 10 12 14 16 18 20 0...20 mA
5 10 20 30 40 50 60 70 80 90 100 0...100 % PWM 26.07.2012
v_u_f_dia_fcontr_d.vsd
Due to technical reasons the output voltage amounts to approx. max. 95 % of the applied mains
voltage.
In order to still be able to achieve the maximum airflow of the connected fans, an increase of the
maximum frequency is possible for our motors. For this, a current increase must be included in the
calculation. It is necessary to optimize monitoring of motor current, output voltage, and speed using
suitable measuring instruments.
The factory set values are for voltage controllable external rotor motors with 400 V / 50 Hz.
After verification of the motor specifications, adjustments are to be adapted, if applicable.
Startvoltage
The start voltage is used to apply enough torque to the motors to insure they will run at
low speed.
Startvoltage
Attention! In order to prevent over current and unnecessarily high thermal load of the
motor, do not select to high a setting.
Adjustment range: 0 - 15 % (percentage of the maximum output voltage)
Factory setting: 0 %
VF quadratic
U/f curve linear or square
Factory preprogrammed square characteristic curve “UF square” = “ON” for the
VF quadratic
operation of voltage controllable fans.
For operation with linear curve “UF quadratic” = “OFF ”
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Rampup time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Rampdown time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
0 .. 100 %
09.05.2007
2 v_hochlaufzeit_ruecklaufzeit.vsd
1 external Signal
2 Setting
3 Rampup time
4 Rampdown time
Attention!
It is essential to check the direction of rotation of the fan during the initial commissioning. To
do this, note the direction of the arrow on the fan housing. We will not be responsible under
any circumstances for warrantee for damage caused because the direction of rotation is
wrong!
When connected in accordance with the connection diagram, the standard rotary direction “RIGHT” =
|CW | results under factory settings. A change of direction is feasible by exchanging the phase
sequence in the motor connection or through reprogramming.
Pressing the P key causes the value that has been set to be
accepted.
If the rotary direction is reversed with an available modulation, it is initially reduced to “0” (discon-
nected) and subsequently increased back to the default value.
As an additional safety function the device has a current limit, this can be adapted if
necessary.
The setting refers to the motor rated current of the device (100 % = setting: MotorRa-
Current limit
tedCurr.).
On exceeding the percentage value set here, the modulation is reduced until the set
current is set again. This prevents overloading of the motor.
Setting range: 100...130 %
Factory setting: 120 %
Active current limit is signaled by a bright triangle in the display
E1 Actual
DC brake mode
Setting function of DC-brake for frequency inverters.
For units that come with a factory engaged DC brake mode (if extant, DC brake
DC brake mode
mode setting), simultaneously activating the “DC brake mode ” only makes sense in
exceptional cases.
DC brake level
Direct-current level, generated for braking. The higher this value, the greater the
braking effect.
DC brake level
The setting “DC brake level” refers in % to the value set in “MotorRated Curr.”.
The setting is dependent on the size of the fan/motor. Attention! Too high values can
lead to a considerable braking effect.
Same“setting”affects also the function Motorheating.
9.7.8 Motorheating
In order to avoid a sticking or a freezing of standing fans in cold environment, the “motor heating
system” can be switched on.
The motor heating function corresponds to the braking function in which a direct current
puts the motor into standstill. The height of the “brake level” is set in “Motor Setup”.
A current is impressed here, which does not permit any rotation of the fans. The value
Motorheating
required to prevent any freezing depends on the ambient conditions and the connected
motor’s technical data.
The setting effected is to be checked under real conditions. The higher the setting, the
greater the heating output generated in the motor (heat dissipation). The motor heating
or stationary heating can only become active, where there is no given modulation as a
result of regulation.
To prevent any overheating, motor protection in the form of thermal protection installed
in the motor is required ( motor protection). The heating function is switched off
when the motor protection function of the regulating unit responds.
OFF = motor heating switched off (at the factory)
ON = The motor heating becomes active automatically when there is no device
modulation.
100 %
50 %
35 % max
Setting depending on device type
1 15 % min
in: %, Hz, rpm
09.05.2007
v_ausblendung_prz.vsd
0% 50 % 100 % D
I I
S R P
A Modulation
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
Suppression1 Suppression1
Suppression2
Check if Thermostats or Thermistors of the motor are connected to input “TB/TP In”.
1 If the motor protection function of the device is not neccesary the both terminals “TB / TP” have to
be bridged.
The settings in the Motor Setup depend on the type of motor connected.
5.1: Setting motor rated current
5.2: Setting motor rated voltage
5*
5.3: Setting Edgefrequency
5.4: Setting maximum frequency
Additional settings as required Motor setup
Settings for U/f characteristic can only be made when no motor modulation is present!
" Switch off via a digital input for remote control (enable= OFF).
" Reduce speed setting signal or setting value to “0” with the display depending on the control mode.
* On units from the AMblue series which have been completed by ZIEHL-ABEGG, the Motor Setup settings are pre-configured
prior to delivery. These settings may only be modified after consultation with the manufacturer!
Setting
Set Intern1
Setting only in Controlmode |4 | active ( Controller Setup).
Via the inputs “D1” / “E1” it is possible to switch to “Default Internal2” or “Default
Set Intern1
Internal3” ( IO Setup).
Setting range manual speed setting: “Min. Speed” - “Max. Speed”
Factory setting: 50.0 Hz ( Setting “Max. Speed”)
Set Intern2
Setting only in control mode |6 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern2
Setting range manual speed setting: “Min. Speed” - “Max. Speed”
Factory setting: 50.0 Hz ( Setting “Max. Speed”)
Set Intern3
Setting only in control mode |6 | active only in control mode |4 | , if activated via inputs
“D1” / “E1” ( Controller Setup / IO Setup).
Set Intern3
Setting range manual speed setting: “Min. Speed” - “Max. Speed”
Factory setting: 50.0 Hz ( Setting “Max. Speed”)
50
n-min 10 Hz n-max. = 50 Hz
45
n-min 20 Hz n-max. = 45 Hz
40
35
30
25
20
10
Foff = 5 Hz
5
Fon = 6 Hz
Analog In 1
0 1 2 3 4 5 6 7 8 9 10 0...10 V
0 2 4 6 8 10 12 14 16 18 20 0...20 mA
0 10 20 30 40 50 60 70 80 90 100 0...100 % PWM 08.05.2012
v_fxdm_setsig_min_max.vsd
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN input
PIN 0010
Release of the service settings with programmed PIN-Accesslevel |0 | ( “Controller
Setup”).
Menu groups Service: “Controller Setup”, “IO Setup”, “Motor Setup”
PIN 1234
Opening “setting”.
Release of the menu group for the user “setting” with programmed PIN-Accesslevel |0 |
( “Controller Setup”).
PIN 3698
Communications parameters take-over.
PIN 9095
Load factory setting (exception, the menu language setting is retained).
Only the parameters which are released by the currently set PIN-Accesslevel are
loaded.
Reset
Complete re-start of the device
Reset
Software version
Firmware
Parameter sets can be saved by the module in the terminal type A-G-247NW and
transferred to other devices ( Operating Instructions Terminal Type A-G-247NW).
Name parameterset with the keys ▼, ▲ + P and load in the terminal with the P-key.
- - - - - - - - - -.CSV
Info
Frequency
Motor current
Device modulation
Modulation
Controller Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
10.5.1 Controlmode
Controlmode
Factory setting
Control by external signal (0 - 10 V / PWM) at the input “E1”.
0
Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
1 no function
2 no function
3 no function
constant speed “Set Intern1”.
4 Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible ( IO Setup).
5 Fixed speed “Default Internal2” (without switching possibility to other default).
6 Fixed speed “Default Internal3” (without switching possibility to other default).
10.5.2 Limit
Limit
“Limit value” = max. possible modulation (e.g. Limit (idealized principle diagram)
speed reduction during night operation by n [%]
e. no limit. L
50
Min.
Si [%]
0 50 100
07.10.2010
v_limit_101_rpm.vsd
LED Mode
Only for versions with integrated status LED!
LED Mode
Setting Function
Status LED in ECblue active i.e. operating conditions are indicated by flash code
ON (factory setting).
OFF Status LED not active, i.e. always OFF.
10.5.4 PIN-Accesslevel
PIN-Accesslevel
The PIN-Accesslevel determines for which setting ranges a PIN must be entered.
PIN-Accesslevel
Setting Function
Factory setting
2 All menu groups are visible, settings are possible without a PIN.
• The menu group “Setting” is free, i.e. changes are possible without a PIN.
1 • PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
All settings are only possible after entering a PIN.
0
• PIN 1234 for changes in the menu group: “Setting”
• PIN 0010: for changes in the menu groups: “Controller Setup”, “IO Setup” and
“Motor Setup” (these menu groups are not visible without a PIN).
Information
Changes for the PIN protection which effect a reduced access right only become active after switching
off the device or executing the “Reset” ( Start menu group) function.
Wireless channel
Setting range: 0 - 15
Factory setting: 0
Wireless channel
IO Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
Different functions can be assigned to the digital inputs “D1” and “E1”*.
Activation via floating contacts (a low voltage of approx. 24 V DC is connected).
“D1” is programmed for the “Enable” function at the factory.
D1 Function
* If the analogue input “E1” is not required for specifying the fan speed, this can be used as a digital input ( E1 function).
The same functions can be assigned for “E1” as for “D1”.
Attention!
Never apply line voltage to the digital input!
Function Description
OFF no function
1D Enable ON / OFF (factory setting)
Remote ON/OFF (electronic disconnection) and Reset after a motor malfunction via
floating contact. The power section is electronically disconnected. Operation of the
device is still possible after pressing the “Esc” hotkey combination in switched-off
condition. Signal- in and outputs remain active.
A programmed alarm relay (factory set “K1 function” = |2K | ) does not report the
switch-off.
Attention!
No disconnection (no potential isolation in accordance with VBG4 §6) in remote control
of the device!
3D Limit ON / OFF
Controller Setup / Limit
5D Set Intern2
Fixed speed “Default Internal2” active. Function with selected “control mode”: 0, 1, 2 , 3
( “Controller Setup”).
With simultaneous activation of “Default Internal3” with function |6D | , |5D | has prior-
ity).
6D Set Intern3
Constant speed “Set Intern3”, also with selected “control mode”: 0 ( “Controller
Setup”).
13D Switch over direction of rotation
Switch over between direction of rotation “RIGHT” = |CW | and direction of rotation
“LEFT” |CCW | .
When“switching”over via a digital input, the device works with the opposite direction of
rotation than the one set in Motor Setup.
If the rotary direction is reversed with an available modulation, it is initially reduced to
“0” (disconnected) and subsequently increased back to the default value.
15D Smoke extraction: Switch off temperature management, operation at max. speed
To make the ECblue as durable as possible, the devices have active temperature
management. The modulation is reduced when internal temperature limits are ex-
ceeded.
In venting systems in which the fan must run at max. speed in the event of a fire, the
temperature management can be switched off by a digital input. At the same time, the
fan is operated independently of the speed default for regular operation at maximum
speed.
The function is activated at the digital input with the contact open (at factory setting
|D1/E1 Inverting | = OFF) so that the maximum speed of the fan is also possible with
the line to the digital input interrupted in case of fire.
Attention!
The device and its internal components are no longer protected against overtemper-
ature when this function is activated (this affects the life installation instructions ECbl-
ue).
The motor protection function by connected thermal protector is no longer effective!
Function Description
OFF no function
Relays remain always de-energized.
1K Operating indication
Operation without fault, reports enable “OFF”.
2K Fault indication (factory setting)
Pulled up in operation without fault, with release “OFF” not dropped out.
Drops out at: line fault, motor fault, etc. Events / Fault indications
4K Limit
Alarm when the speed exceeds the value set under “Default Internal3” ( menu group
“Setting”) (output power > 0 %).
The function is active in every control mode ( menu group: “Controller Setup”).
17K no function
K1
1 = energized, terminals 13 - 14 bridged
0 = de-energized 13-14 not bridged
13 14
10.11.2008
v_relais_k1_13_14.vsd
K1
E1 Function
|1E | (factory setting) = speed setting by external signal (0 - 10 V / PWM).
For settings via |1E | “E1” operates like “D1” as a digital input ( digital inputs /
E1 Function
function).
E1 Inverting
Factory setting inverting to “OFF”.
For control with inverted setting signal switch to “ON” (setting signal: 10 - 0 V).
E1 Inverting
E1 Min.
Value of the input signal at which the controller starts at minimum modulation.
Setting range: 0 - 100 %
E1 Min.
Factory setting: 5 %
E1 max
Value of the input signal at which the maximum modulation of the controller is reached.
Setting range: 0 - 100 %
E1 max
Factory setting: 100 %
Idealized principle diagrams for setting: “Min. Speed” = 0.0 Hz and “Max. Speed” = 50.0 Hz
Fout
[Hz]
50
Si E
0 1 2 3 4 5 6 7 8 9 10 0 – 10 V
15.02.2012
v_e1_adjust_i_basic.vsd
Watchdog Time
If the device receives no message in the time window, a definable function is executed.
Watchdog Time
Watchdog time in seconds.
Setting range: 0 - 255 sec.
Factory setting: 0 sec. = off
Watchdog Mode
Watchdog Mode:
0: No function (default) = OFF from FW 13
Watchdog Mode
1: Fault (K1 function, h15) in case of communication fault (WDT)
2: Constant speed 1 * in case of communication fault (WDT)
3: Fault + constant speed 1 * in case of communication fault (WDT)
4: Fault by E1 Fault ** (only ECblue)
5: Constant speed 1 by E1 Fault (only ECblue)
6: Fault constant speed 1 in case of E1 fault (only ECblue)
* in this condition it is possible by digital input function 5, 6 or digital control function to
change between the constant speeds (Holding register h4).
** E1 fault is triggered when E1 falls below E1 Min x 0.5. E1 fault is cancelled when E1
rises above E1 Min x 0.9.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
Bus Address
UART Baudrate
Setting transfer rate
Valid values: 4,800, 9,600, 19,200
Com. Baudrate
Factory setting: 19200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Com. Mode
Factory setting: 8E1
Information
Modified communication parameters are not taken over until the unit has been reset or until the PIN
input |3698 | !
Motor Setup
Information
• The following factory settings specifications are not binding, these values can differ depending on
the software version and customer-specific pre-setting.
• On units from the AMblue series which have been completed by ZIEHL-ABEGG, the Motor Setup
settings are pre-configured prior to delivery. These settings may only be modified after consultation
with the manufacturer!
Attention!
Settings for U/f characteristic may only be made when no motor modulation is present!
MotorRatedCurr.
When commissioning, you must set the motor to the rated current stated on the
rating plate.
MotorRatedCurr.
The setting for the “DC brake level” ( setting brake behaviour) refers to this setting.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
MotorRatedVolt.
When commissioning, you must set the motor to the rated voltage stated on the
rating plate.
MotorRatedVolt.
An adaptation can be made if the motor rated-voltage as the applied mains voltage is
lower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).
Verify the output voltage using suitable measuring instruments.
Setting range: 0...500 V
Factory setting: 400 V
Attention!
Settings for U/f characteristic may only be made when no motor modulation is present!
Edgefrequency
The maximum output voltage is attained during break edge frequency.
Adjustment range: 1.0 - 120.0 Hz
Edgefrequency
Factory setting: 50.0 Hz
In the case of special settings with “Edge frequency” > “Max. frequency”, due to higher
power losses it is possible that automatic power reduction occurs ( Messages and
trouble shooting “Temp. Manager”).
Max. Frequency
Above the Edgefrequency, the frequency is merely increased up to the Maximum
frequency.
Max. Frequency
Adjustment range: 1.0 - 120.0 Hz
Factory setting: 50.0 Hz
Uout
Fedge = Fmax
100 %
L
Q
Foff
Ustart = 10 %
Fon
Ustart = 0 % Fout [Hz]
5 10 15 20 25 30 35 40 45 50
Analog In 1
0.5 2 3 4 5 6 7 8 9 10 0...10 V
1 2 4 6 8 10 12 14 16 18 20 0...20 mA
5 10 20 30 40 50 60 70 80 90 100 0...100 % PWM
26.07.2012
v_u_f_dia_icontr_d.vsd
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Rampup time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Rampdown time
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
0 .. 100 %
09.05.2007
2 v_hochlaufzeit_ruecklaufzeit.vsd
1 external Signal
2 Setting
3 Rampup time
4 Rampdown time
Switching frequency
Possible motor noises can be reduced by adjusting the clock frequency (16 kHz =
upper limit of the human acoustic range).
Switching frequency
Information
• This fixed switching frequency setting is only effective if the automatic switching frequency
changeover is not activated (see “Auto. Switchfreq”).
• Increasing of clock frequency only possible by reducing maximal load. ( Maximum load
depending on clock frequency and ambient temperature).
Attention!
It is essential to check the direction of rotation of the fan during the initial commissioning. To
do this, note the direction of the arrow on the fan housing. We will not be responsible under
any circumstances for warrantee for damage caused because the direction of rotation is
wrong!
When connected in accordance with the connection diagram, the standard rotary direction “RIGHT” =
|CW | results under factory settings. A change of direction is feasible by exchanging the phase
sequence in the motor connection or through reprogramming.
By selection of the parameter “Direction of rotation” and
following pressing the P key, the direction of rotation can
changed to |CCW | for anti-“clockwise” = |CCW | direction of
Rotat. Direction rotation. Rotat. Direction
Pressing the P key causes the value that has been set to be
accepted.
If the rotary direction is reversed with an available modulation, it is initially reduced to “0” (discon-
nected) and subsequently increased back to the default value.
As an additional safety function the device has a current limit, this can be adapted if
necessary.
The setting refers to the motor rated current of the device (100 % = setting: MotorRa-
Current limit
tedCurr.).
On exceeding the percentage value set here, the modulation is reduced until the set
current is set again. This prevents overloading of the motor.
Setting range: 100...130 %
Factory setting: 120 %
Active current limit is signaled by a bright triangle in the display
E1 Actual
DC brake mode
Setting function of DC-brake for frequency inverters.
For units that come with a factory engaged DC brake mode (if extant, DC brake
DC brake mode
mode setting), simultaneously activating the “DC brake mode ” only makes sense in
exceptional cases.
The setting is dependent on the size of the fan/motor. Attention! Too high values can
lead to a considerable braking effect.
Same“setting”affects also the function Motorheating.
Attention!
Due to the transient motor triggering with maximum frequency at reduced output voltage necessary for
the quench mode, short-term start-up can occur in a stationary motor with low centrifugal force.
The quench function can be combined with motor braking (DC brake mode). However, running both
functions successively increases the time span until the motor is reaccelerated. For normal use, it is
recommended to use only the quench mode.
Attention!
• In operation with overmodulation, you must make sure that resonance vibrations cannot
increase. Speed ranges (frequencies) can be faded out in the following settings.
• The notes on mechanical vibrations and operation with overmodulation in the assembly and
operating manual of the drive must be observed!
10.7.11 Motorheating
In order to avoid a sticking or a freezing of standing fans in cold environment, the “motor heating
system” can be switched on.
The motor heating function corresponds to the braking function in which a direct current
puts the motor into standstill. The height of the “brake level” is set in “Motor Setup”.
A current is impressed here, which does not permit any rotation of the fans. The value
Motorheating
required to prevent any freezing depends on the ambient conditions and the connected
motor’s technical data.
The setting effected is to be checked under real conditions. The higher the setting, the
greater the heating output generated in the motor (heat dissipation). The motor heating
or stationary heating can only become active, where there is no given modulation as a
result of regulation.
To prevent any overheating, motor protection in the form of thermal protection installed
in the motor is required ( motor protection). The heating function is switched off
when the motor protection function of the regulating unit responds.
OFF = motor heating switched off (at the factory)
ON = The motor heating becomes active automatically when there is no device
modulation.
100 %
50 %
35 % max
Setting depending on device type
1 15 % min
in: %, Hz, rpm
09.05.2007
v_ausblendung_prz.vsd
0% 50 % 100 % D
I I
S R P
A Modulation
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
Suppression1 Suppression1
Suppression2
Diagnostic
32.0 °C Display of the internal temperature of the power semiconductor.
IGBT Temp.
32.0 °C Display of electronics internal temperature.
Inside Temp.
32.0 °C Display of the internal temperature of the microcontroller.
MCU Temp.
0% Signal height at analog input1“E1”.
E1 Input
565 V For 1 ~ types: DC-link voltage constantly approx. 400 V.
DC-Voltage For 3 ~ types DC-link voltage without load = peak value oft the input voltage.
In a three-phase supply network with 400 V, an intermediate circuit voltage of ca. 565 V
results. This voltage sinks slightly under load.
330 V Line voltage
Line voltage
0 Stateflags
Stateflags
0 Faultflags
Faultflags
2 Momentarily adjusted PIN-Accesslevel ( Controller Setup).
PIN-Accesslevel
Diagnostic
32.0 °C Display of the internal temperature of the power semiconductor.
IGBT Temp.
32.0 °C Display of electronics internal temperature.
Capacitor
32.0 °C Display of the internal temperature of the microcontroller.
MCU Temp.
32.0 °C Only in version with integrated sine filter.
Output filter
0% Signal height at analog input1“E1”.
E1 Input
565 V The intermediate circuit voltage without load is the peak value of the input voltage.
DC-Voltage In a three-phase supply network with 400 V, an intermediate circuit voltage of ca. 565 V
results. This voltage sinks slightly under load.
330 V Line voltage peak value.
Line voltage
0 Not active in devices with integrated display.
Stateflags
0 Not active in devices with integrated display.
Faultflags
2 Momentarily adjusted PIN-Accesslevel ( Controller Setup).
PIN-Accesslevel
An error message appears alternately with the actual value display ( Diagnostic faults).
ON
1x
2x
3x
4x
5x
6x
23.04.2012
v_flash_explain_1_x.VSD
ON
1x
2x
3x
Status LED integrated in the cover
4x
5x
6x
22.06.2012
v_flash_expl_red_1_x.VSD
13 Enclosure
13.1 Connection diagram
AM-MODBUS(-W)
A B A B
GND (D+) (D-) ID1 GND (D+) (D-) ID2 fout GND
n = f x 60
2
Information
The full connection diagram for the terminating device is a combination of the connection diagram of
the module plus the connection diagram of the device in which the module is installed ( appropriate
operating instructions).
13.2 Index
B start voltage 43, 56
startup attempt 65
Baudrate 10
Suppression 4, 22, 32, 46, 59
C
T
characteristic curve 43
temperature management62, 65, 67
clock frequency 57
terminal 8
current increase 43
torque 43, 56
D
U
DC-brake 45, 58
U/f curve 42, 55
diagnostics menu 60-61
direction of rotation 44, 57
E
Earth fault 65
edge frequency 42, 56
F
flashing code 64
I
interface parameter 10
L
linear characteristic 42
linear curve 56
M
mains interruption 65
Maximum frequency 42, 56
MODBUS 9
modulation 65
motor noises 57
motor speed 17, 28
O
output voltage 42, 56
overload 65-66
P
pin code 15, 25, 35, 48
PIN input 15, 25, 35, 48
R
Rampdown time 22, 32, 44, 56
Rampup time 22, 32, 44, 56
Reset 38, 52, 65
resonances 22, 32, 46, 60
RS-485 9
S
setting signal 20, 24, 30
short-circuit 65
ZIEHL-ABEGG SE
Heinz-Ziehl-Straße
74653 Künzelsau
Telephone: +49 (0) 7940 16-0
Telefax: +49 (0) 7940 16-504
[email protected]
http://www.ziehl-abegg.de
Our worldwide contacts are available in our subsidiaries for deliveries outside of Germany.
www.ziehl-abegg.com.
If you make returns for inspections or repairs we need certain information in order to facilitate focused
trouble shooting and fast repair. Please use our repair ticket for this. It is provided to you after you
have consulted our support department.
In addition, you can download it from our homepage. Download - Ventilation Technology - Topic:
Control Engineering - Document type: General documents.