Equal Friction Method
Equal Friction Method
2
DUCTWORK IN PRACTICE
3
Ductwork in Practice
4
Ductwork in Practice
5
Ductwork in Practice
• The ratio of the rectangular ductwork is very important
since the average velocity is different:
6
Ductwork in Practice
• The air distribution includes various components:
7
https://www.nrel.gov/docs/fy03osti/29166.pdf
Ductwork in Practice
• Use separate design for return and supply
8
Ductwork in Practice
• Change of diameter
9
Ductwork in Practice
• Outdoor air intake
10
Ductwork in Practice
• Installation of supply and return outlets
11
DUCT DESIGN METHODS
13
Duct Design Methods
• Codes & standards
• Airflow rates
• Single line ductwork
• Size ductwork
• Calculate pressure drop
• Establish system total pressure
14
Duct Design Methods
• There are different duct design methods:
q Equal friction: Size based on chosen friction loss rate (per
100 ft) for each duct section to balance the pressure gradient
(commonly used)
16
Duct Design Methods
• When do we use high velocity design?
17
Duct Design Methods
• When do we use low velocity design?
18
EQUAL FRICTION METHOD
19
Equal Friction Method
• The design friction rate per unit length (in. w.c per 100 ft)
is maintained
21
Equal Friction Method
• Example:
q Loss for each outlet is 0.05 in. w.c.
q Maximum velocity mains = 1,300 fpm, branches = 900 fpm
q Uniform pressure loss/100 ft and for elbows r/W = 1.0
1000 cfm
50 ft
40 ft 30 ft 80 ft
Plenum
Balancing Damper
40 ft 40 ft
22
1500 cfm 500 cfm
Equal Friction Method
• Solution:
q Add labels for different branches and fittings
2
1000 cfm
F9
50 ft
A B C F8
40 ft F1 30 ft 80 ft F4
Plenum
F6 Balancing Damper F2 F3
40 ft 40 ft
F7 F5
𝑄!"#$ = 500 𝑐𝑓𝑚 + 1500 𝑐𝑓𝑚 + 1000 𝑐𝑓𝑚 = 3000 𝑐𝑓𝑚 𝑉!"% = 1300 𝑓𝑝𝑚
24
Equal Friction Method
• Solution:
q Construct a tabular air flow
Section Air Flow Rate Duct Size (in) Duct (in Velocity (fpm)
(cfm) Rectangular)
AB 3,000
BC 1,500
B1 1,500
C2 1,000
C3 500
25
Equal Friction Method
• Solution:
q Find round diameters and velocities
26
Equal Friction Method
• Solution:
q Add the duct sizes and velocity rates
Section Air Flow Duct Size Duct (in Area (ft2) Velocity
Rate (cfm) (in) Rectangular) (fpm)
AB 3,000 21 1,059
BC 1,500 16 1,000
B1 1,500 16 1,000
C2 1,000 14.5 750
C3 500 11 600
27
Equal Friction Method
• Solution:
q Find square duct sizes
C-3
C-2
B-C
A-B 28
Equal Friction Method
• Solution:
q Add the rectangular values to the table
Section Air Flow Duct Size Duct (in Area (ft2) Velocity
Rate (cfm) (in) Rectangular) (fpm)
AB 3,000 21 34 / 12 2.83 1,059
BC 1,500 16 18 /12 1.50 1,000
B1 1,500 16 18 / 12 1.50 1,000
C2 1,000 14.5 16 / 12 1.33 750
C3 500 11 10 / 12 0.83 600
29
Equal Friction Method
• Solution:
q Add the calculated ductwork sizes to the diagram
2
1000 cfm
F9
50 ft 16’’x12’’
40 ft 18’’x12’’ 40 ft
F7 F5
Section Air Flow Duct (in De Friction Loss Length Section Loss
Rate (cfm) Rectangular) (in) (in/100 ft) (ft) (in. w.c.)
31
Equal Friction Method
• Solution:
q Friction losses (in/100 ft)
32
Equal Friction Method
• Solution:
q Find the friction losses (in/100 ft)
Section Air Flow Duct (in De Friction Length Section Loss (in. w.c.)
Rate Rectangular) (in) Loss (ft)
(cfm) (in/100 ft)
AB 3,000 34 / 12 21.4 0.088 40 40
0.088× = 0.035
100
BC 1,500 18 /12 16 0.1 30 30
0.1× = 0.03
100
B1 1,500 18 / 12 16 0.1 40 40
0.1× = 0.04
100
C2 1,000 16 / 12 15.1 0.065 50 50
0.065× = 0.0325
100
C3 500 10 / 12 12 0.056 120 120
0.056× = 0.067
100
33
Equal Friction Method
• Solution: Compute fittings
Section Fitting Fitting ASHRAE Parameters Loss Velocity Pv (in. Pt (in.
No Type Fitting Coefficient (fpm) w.c.) w.c.)
No.
AB F1b Tee SR5-13 𝐴! 1.5 𝑄! 1500 0.82 1,000 0.062 0.051
= = 0.53 = = 0.5
Branch 𝐴" 2.83 𝑄" 3000
F1s Tee SR5-13 𝐴! 1.5 𝑄! 1500 0.06 1,000 0.062 0.004
= = 0.53 = = 0.5
Straight 𝐴" 2.83 𝑄" 3000
BC F2 Tee SR5-13 𝐴! 1.33 𝑄! 1000 1.33 752 0.035 0.047
= = 0.9 = = 0.67
Branch 𝐴" 1.50 𝑄" 1500
F2 Tee SR5-13 𝐴! 0.83 𝑄! 500 0.58 602 0.023 0.013
= = 0.55 = = 0.3
Straight 𝐴" 1.5 𝑄" 1500
B1 F3 Damper CR9-1 𝑞 = 0# 0.19 600 0.022 0.004
𝚫𝐏 (in. w.c.)
Path Note Duct Tee Duct T𝐞𝐞 Damper Duct Outlet Total Differe
ntial
35
Equal Friction Method
• Solution (summary):
2
1000 cfm
F9
50 ft 16’’x12’’
40 ft 18’’x12’’ 40 ft
37
Equal Friction Method
• See Chapter 21 – Page 21.24 of the Fundamentals for
another example:
38
BALANCED CAPACITY METHOD
39
Balanced Capacity Method
• The balanced design method uses the duct network
principle
40
Balanced Capacity Method
• Based on the continuity equation, the summation of air
flow rate into any junction is zero
Σ±𝑄 =0
Σ±𝑃 =0
41
Balanced Capacity Method
• Satisfy all the possible pressure drops
2
1000 cfm
F9
𝑄% = 1500 𝑐𝑓𝑚
50 ft
B C F8 𝑄- = 1000 𝑐𝑓𝑚
A
40 ft F1 30 ft 80 ft F4 𝑄& = 500 𝑐𝑓𝑚
Plenum
F2
Balancing Damper F3
F6 Σ𝑄 = 3000 𝑐𝑓𝑚
40 ft 40 ft
F7 F5
43
SYSTEM CHARACTERISTICS CURVE
44
System Characteristics Curve
• There are a couple of components required for the design
of an air distribution
Load Calc
Thermal
Comfort
Determine air Deliver air to Control air speed Direct air to the Move air through
flow rate the space and temperature terminal units or the duct system
diffusers 45
System Characteristics Curve
• Overall system resistance can be written as:
> ?@ ! ?@ !
= ∑𝑓 +∑𝐾
3 A<" A<"
46
System Characteristics Curve
• Flow through any resistance (i.e., duct and fittings) is
proportional to the square root of the pressure causing the
flow
47
System Characteristics Curve
• This relationship defines the flow versus pressure
characteristics of a system
48
https://www.nrel.gov/docs/fy03osti/29166.pdf
FAN PERFORMANCE CURVE
49
Fan Performance Curve
• An example of a fan curve:
50
https://content.greenheck.com/public/DAMProd/Original/10002/CentrifugalDWPerfSuppl_catalog.pdf
Fan Performance Curve
• An example of a fan curve:
51
https://content.greenheck.com/public/DAMProd/Original/10002/CentrifugalDWPerfSuppl_catalog.pdf
Fan Performance Curve
• An example of a fan curve:
52
https://content.greenheck.com/public/DAMProd/Original/10002/CentrifugalDWPerfSuppl_catalog.pdf
HALLWAY VENTILATION
53
Hallway Ventilation
54
https://www.energyvanguard.com/blog/ventilating-high-rise-multifamily-buildings-a-first-look
Hallway Ventilation
55
https://www.nrel.gov/docs/fy14osti/62313.pdf
Hallway Ventilation
40% x 20% = 8%
56
https://www.energyvanguard.com/blog/ventilating-high-rise-multifamily-buildings-a-first-look
Hallway Ventilation
57
https://www.nrel.gov/docs/fy14osti/62313.pdf