Ibpl ML-45 75
Ibpl ML-45 75
ML/MM/MH/MJ 55
ML/MM/MH/MJ 75
OPERATORS/INSTRUCTION MANUAL
AND PARTS BOOK
EFFECTIVE
Ingersoll Rand (I) Ltd.,
FROM 70715149IBPL
Peenya Industrial Area,
BANGALORE 560 058 New Release
TO
June, 2002
INDIA
1
2
ROTARY SCREW AIR COMPRESSOR
Serial Number:
Model Number:
TYPICAL UNIT
3
TABLE OF CONTENTS
0.0 SAFETY AND WARNINGS
0.1 safety instructions 6.0 TROUBLE SHOOTING
0.2 safety precautions
0.3 decals 7.0 REFERENCE DRAWINGS
7.1 electrical schematic - full voltage
1.0 RECEIPT OF EQUIPMENT 7.2 electrical schematic - star delta
1.1 inspection 7.3 foundation plan - air cooled
1.2 unpacking and handling 7.4 foundation plan - water cooled
1.3 tools 7.5 foundation plan - outdoor mod
7.6 basic flow schematic - air cooled
2.0 INSTALLATION 7.7 basic flow schematic - water cooled
2.1 ventilation 7.8 typical system flow diagrams
2.2 foundation requirements
2.3 piping 8.0 WATER QUALITY RECOMMENDATIONS
2.4 electrical installation
2.5 outdoor sheltered installation 9.0 MAINTENANCE RECORD
3.0 INTELLISYS
3.1 emergency stop switch GENERAL INFORMATION
3.2 power on light
3.3 power indicator light Weight: See foundation plan, Section 7.0
3.4 push buttons
Cooling Air Flow: See foundation plan, Section 7.0
3.5 set point procedure
3.6 warnings Ambient Temperature Limit: 2°C to 46°C (35°F to 115°F)
3.7 alarms
Coolant: Factory Filled SSR Ultra Coolant
4.0 SYSTEMS
4.1 general systems Coolant Change: 8000 hours or two years, whichever
comes first
4.2 aircooled compressors
4.3 coolant system Coolant Capacity: 18.9 liters
4.4 compressed air system
4.5 coolant/air separation system Discharge Temperature Limit: 109°C (228°F )
4.6 electrical system
4.7 compressor control system Power Inlet Wiring: Recommended conduit: metallic
4.8 options flexible Greenfield, or equivalent,
4
faced for emphasis. The signal words DANGER,
0.0 SAFETY AND WARNINGS WARNING and CAUTION are used to indicate hazard
0.1 SAFETY INSTRUCTIONS seriousness levels as follows:
Before you install this air compressor you should
take the time to carefully read all the instructions
contained in this manual. Danger is used to indicate the
Electricity and compressed air have the potential to presence of a hazard which will
! DANGER cause severe personal injury, death,
cause severe personal injury or property damage.
or substantial property damage if the
Before installing, wiring, starting, operating or warning is ignored.
making any adjustments, identify the components of
the air compressor using this manual as a guide. Warning is used to indicate the
The operator should use common sense and good presence of a hazard which can
working practices while operating and maintaining
! WARNING cause severe personal injury, death,
this unit. Follow all codes, pipe adequately, or substantial property damage if the
understand the starting and stopping sequence. warning is ignored.
Check the safety devices by following the procedure
contained in this manual. Caution is used to indicate the
presence of a hazard which will or
Maintenance should be done by qualified personnel, ! CAUTION can cause minor personal injury or
adequately equipped with proper tools. Follow the property damage if the warning is
maintenance schedules as outlined in the operators ignored.
manual to ensure problem free operation after start
up. Notice is used to notify people of
installation, operation, or
Safety instructions in the operators manual are bold- NOTICE maintenance information which is
important but not hazard-related.
0.2 SAFETY PRECAUTIONS
SAFETY PRECAUTIONS
BEFORE PROCEEDING, READ CAREFULLY BEFORE INSTALLING THE
COMPRESSOR OR PERFORMING ANY MAINTENANCE
WARNING
5. Install a manual shut off valve (isolation The use of plastic bowls on line
1. Do not remove the covers, loosen or
type) in the discharge line. When a safety filters without metal guards can
remove any fittings, connections or
valve is installed between the isolation be hazardous. From a safety
devices when this unit is in operation. Hot
valve and the compressor, it must have standpoint, metal bowls should
liquid and air under pressure that are
sufficient capacity to relieve the full be used on any pressurized
contained within this unit can cause
capacity of the compressor(s). system. Review of your plant air
severe injury or death.
line system is recommended.
2. The compressor has high and 6. Whenever pressure is released through
the pressure relief valve, it is due to 9. When a receiver is installed, it
dangerous voltage in the motor starter
excessive pressure in the system. The is recommended that
and control box. All installations must be
cause for the excessive pressure should occupational safety and health
in accordance with recognized electrical
be investigated immediately. standards be adhered to in the
codes. Before working on the electrical
installation and maintenance of
system, be sure to remove voltage from
7. Before doing any mechanical work on this receiver.
the system by use of a manual-
disconnect-switch. A circuit breaker or the compressor:
10. Before starting the
fuse safety switch must be provided in
a.) Shut the unit down. compressor, its maintenance
the electrical supply line leading to the
instructions should be
compressor.
b.) Electrically isolate the compressor by thoroughly read and understood.
Those responsible for installation of this use of the manual disconnect switch in the
power line to the unit. Lock and tag the 11. After maintenance functions
equipment must provide suitable
switch so that it cannot be operated. are completed, covers and
grounds, maintenance clearance and
guards must be replaced.
lightning arrestors for all electrical
components as stipulated in Indian c.) Vent pressure from the compressor and
Electricity Rules. isolate the unit from any other source of
air.
5
SAFETY SHUTDOWN
CHECK-HIGH-AIR-TEMPERATURE
There is a high discharge air temperature shutdown function built into the Intellisys on each compressor. It is factory pre-
set at 228°F (109°C). This function should be checked at regular intervals for proper operation, once a month is
recommended. The procedure is:
The actual temperature at which shutdown occurs should be recorded for comparison to the Intellisys set point and with
similar future test results.
WARNING
Failure to adhere to these recommendations can result in mechanical failure, property damage and serious injury or death.
All air and water inlet, and air and water discharge pipework to and from the inlet and discharge port connections must
take into account vibration, pulsations, temperature, maximum pressure applied, corrosion and chemical resistance. In
addition, it should be noted that lubricated compressors will discharge some oil into the air stream; therefore, compatibility
between discharge piping, system accessories and software must be assured.
For the foregoing reasons, the use of plastic piping, soldered copper fittings and rubber hose as discharge piping is not
recommended. In addition, flexible joints and/or flex lines can only be considered for such purposes if their specifications fit
the operating parameters of the system.
It is the responsibility of the installer and owner to provide the appropriate service pipework to and from the machine.
WARNING
“Ingersoll-Rand air compressors are not designed, intended, or approved for breathing air applications. Ingersoll-Rand
does not approve specialized equipment for breathing air application and assumes no responsibility or liability for
compressors used for breathing air services.”
0.3 DECALS
39879762
(3 REQUIRED)
39905443
70559018
39540257
39540273
(4) 2 EACH END
39541081
39540166
39905203
70559026
39540240
39541362
39540265
39541354
39540174 39899950
10
39543764
39543764
39868419
1.0 RECEIPT OF EQUIPMENT
1.1 INSPECTION
When you receive the compressor please inspect it
closely. Any indication of careless handling by the carrier
should be noted on the delivery receipt especially if the
compressor will not be immediately uncrated. Obtaining
the delivery man’s signed agreement to any noted
damages will facilitate any future insurance claims.
IMPORTANT
READ THIS
LOST OR DAMAGED GOODS
Ingersoll-Rand Company
Bangalore
1.3 TOOLS
Remove compressor unit from wooden skid. A crowbar
and hammer will be needed.
11
2.0 INSTALLATION
2.1 VENTILATION
Oil flooded rotary air compressors produce large
amounts of heat. Because of this large heat production,
the compressor must be placed in a room with
adequate ventilation.
DUST CHEMICALS
METAL PAINT
FILINGS SPRAY
OVERSPRAY
2.3 PIPING
2.2 FOUNDATION REQUIREMENTS The use of plastic bowls on line filters without metal
Refer to the foundation plan for the particular model guards can be hazardous. Their safety can be affected
compressor to be installed. See Section 7.0. by either synthetic lubricants or the additives used in
mineral oil. From a safety standpoint, metal bowls
The compressor can be installed on any level floor that should be used on any pressurized system. Review of
is capable of supporting it. Compressor weights are your plant air line system is recommended.
listed on the foundation plans.
12
2.3 PIPING (Continued)
A dripleg assembly and isolation valve should be
mounted near the compressor discharge. A drain line
should be connected to the condensate drain.
NOTICE
120
hours/1000 acfm
13
Two types of dryers, refrigerated or desiccant, are used
to correct moisture related problems in a compressed
air system. Refrigerated dryers are normally specified
where compressed air pressure dew points of 1°C
(33°F) to 4°C (39°F) are adequate. Desiccant dryers
are required where pressure dew points must be below
1°C (33°F).
2.4 ELECTRICAL-INSTALLATION
FUSE TABLE
Starter Size Control Transformer 1FU & 2FU 4FU & 5FU 3FU
(T1) Size Primary Fuse Secondary Fuse
( Amp ) ( Amp )
C70SD 350VA 6A 2A 6A
14
ELECTRICAL-INSTALLATION (Continued)
Inspect the motor and control wiring for tightness.
Rotation Check
Locate the rotation decal on each motor.
Drive Motor
The correct compressor drive motor rotation is
clockwise when viewed from the rear or non-drive
end of the motor. See Figure 2.4-2.
CAUTION
15
ELECTRICAL-INSTALLATION (Continued)
Open the starter box door.
The Intellisys will automatically shut the unit down if the
compressor rotation is incorrect, and “CHK MTR Interchange any two line connections (L1, L2 or L3) at
ROTATION” will appear in the display, also the alarm the starter. Close and fasten the starter box door.
light will be on. See Section 6. Recheck for correct rotation.
For the compressor motor rotation check, the motor Fan Motor
jogging time must be as short as possible. Observe the compressor cooling fan. The rotation
should be in accordance with the fan rotation decal
After depressing the start button, IMMEDIATELY affixed to the fan motor. Cooling air should exhaust
depress the “EMERGENCY STOP” button. Should through fan end of compressor enclosure.
the motor rotation be incorrect, put main
disconnect in the OFF position, lock and tag. See Should the motor rotation not be correct, put the main
Figure 2.4-3. disconnect in the OFF position, lock and tag.
NOTICE
Intellisys Operating Instructions
Before installing, operating, or performing any maintenance on this unit, read and understand the instructions in the Operators /
Instruction Manual
Before Starting
Stopping
1. Check coolant level. Add voltages are available for will stop immediately.
1. Push “UNLOADED STOP”.
coolant if necessary. starting.“UNLOAD” indicator 2. Open main disconnect switch.
Compressorwill immediately
2. Verify that main isolation light will be on. Stopping - Emergency
unload and continue to run
valve is open. Starting 1. If there is a need to stop the
unloaded roximately 7
3. If water-cooled, turn on 1. Push “START”. Compressor compressor immediately or if the
seconds.Compressor will then
water. will load automatically and the “UNLOADED STOP” does not stop
stop. If compressor is running
4. Close main disconnect air pressure will riseif there is the compressor after 7seconds,
unloaded when “UNLOADED
switch. The“POWER” light sufficient demand for air. push “EMERGENCY STOP”
STOP” is pushed, compressor
indicates that line and control 2. Open main disconnect switch.
16
2.5 OUTDOOR SHELTERED INSTALLATION
n Incoming power connections must use
Many times a compressor must be installed outside suitable connectors for outdoor weather
due to jobsite conditions or limited space within a tight service.
manufacturing facility. When this occurs there are
certain items that should be incorporated into the
n A minimum of 3 ft (.9 m) clearance must be
installation to help ensure trouble free operation. allowed on all four sides of the unit for
These items have been listed below plus Figure service access. If possible, access by a
2.5-1 has been included to show a typical outdoor forklift and/or an overhead beam hoist
sheltered installation.The unit must be purchased should be kept in mind (for eventual
with the Outdoor Modification Option to provide service to airend or motor).
NEMA 4 electrics and a cabinet exhaust on the end n If the area around the installation contains
of the unit rather than the top to prevent recir- fine airborne dust or lint and fibers etc.,
culation of cooling air. then the unit should be purchased with the
n The compressor should be on a concrete High Dust Filter Option and TEFC motors.
pad designed to drain water away. If the n If larger debris, such as leaves or trash,
concrete pad is sloped, then the compres- are blowing in the area, the Cabinet Pre-
sor must be leveled . In order to properly filter Accessory should be purchased and
pull cooling air through the aftercooler, the added to the unit (ship loose item).
base/skid must be sealed to the concrete
pad. n Some type of protection such as a fence or
security system, should be provided to
n The roof of the shelter should extend a prevent unauthorized access.
minimum of 4 ft (1.2 m) around all sides of
the compressor to prevent direct rain and
snow from falling on the unit.
n Air-cooled machines must be arranged
under the shelter in a way that prevents air
recirculation (i.e. hot exhaust back to the
package inlet).
n If the installation includes more than one
compressor, the hot air exhaust should not
be directed towards the fresh air intake of
the second unit or an Air Dryer.
n If a standard machine is to be installed
outside, the ambient temperature must
never drop below 35°F (1.7°C).
n Arrange the machine with the Intellisys
controller/starter enclosure facing away
from the sun as radiant heat can affect
starter/lntellisys performance. Also direct
sunlight and UV rays will degrade the
membrane touch panel.This is not a
warrantable situation.
n Power disconnect switch should be within
line of sight and in close proximity to the
unit. Local electrical codes must be fol-
lowed when installing the power disconnect
switch.
n Condensate drains must never be allowed
to dump on the ground. Run to a suitable
sump for future collection and disposal or
separation of lubricant and water mixture.
17
18
19
INTELLISYS CONTROLLER
3.0 INTELLISYS
3.0 INTELLISYS UNLOAD STOP
3.1 EMERGENCY STOP SWITCH Pressing this button will activate the unload stop. -If
the compressor is running loaded, it will unload.
Pressing this switch stops the compressor Seven seconds later it will stop. -if the compressor is
immediately. Compressor cannot be restarted until running unloaded, it will stop immediately. Pressing
switch is manually reset. Turn clockwise to reset. this button with the unit stopped will flash all L.E.D.’s
for a light check and flash the software version
number in the display.
START
20
3.4 PUSH BUTTONS (Continued)
PRESSURE SENSOR CALIBRATION (ZEROING)
DISPLAY SELECT ROUTINE
Pressing this button will change the information This routine is entered if the unit is not running and
selected for the display. The display table will be both the up and down arrows button are pressed at
incremented. If the button is held, this display table the same time. -Make sure all pressure is relieved
will scroll. This button can also be used to exit the from the compressor before calibration. The display
set point procedure. will flash the message “CALIBRATING”. After
calibration is completed the display will indicate
“READY TO START”. Zeroing should only be done
after a pressure sensor has been replaced or any
controller change.
SET
ARROWS
21
** The lead/lag feature allows the customer to choose
3.5 SET POINT PROCEDURE
one compressor as the “lead” compressor and any
others as the “lag” compressor (simulates the mode of a
This procedure allows the customer to modify 11
sequencer). The lag compressor’s on-line and off-line
variables in the controller logic.
pressures are determined by subtracting the lag offset
set-point from the on-line and off-line pressure set-
At this time, press the SET button to enter the set points of the lead compressor.
point routine. The SET OFFLINE AIR PRESSURE
indicator will light and the display will show:
OFFLINE AIR PRESSURE is the first set point and When a warning occurs, the alarm indicator will
XXXX stands for the value of the set point. Press flash and the display will alternate between the
the SET button to select the set point to be current message and the warning message. If
adjusted. Press the up or down arrow buttons to multiple warnings exist, the message
raise or lower the set point value. Press the SET
button to move to the next set point. If the set point SCROLL FOR WARN
value has been adjusted, press the SET button to
enter the new value. The display will flash to will be substituted for the warning messages. The up
acknowledge.The next set point will then be and down arrows can be used to obtain the
displayed. If the value of the set point was not warnings
changed, pressing the SET button will only step to
the next set point. When the SELECT OPTIONS set A warning needs to be reset by an operator. The
point is entered, the SELECT OPTIONS indicator warning will clear when the SET button is pressed
will light, and the setpoints for options Auto Start/ once. The following is a list of the warning
Stop or Remote Start/Stop will only be accessible messages.
and displayed if the option module is installed in the
unit. The Power Outage Restart setpoints will only 1) CHG SEPR ELEMENT
be accessible and displayed if the combination Auto/ This warning will occur if the pressure on the
Remote Start/Stop/Power Outage Restart option separator is 12 psig (.8 bar) greater than the
module is installed in the unit. The set point routine pressure at the package discharge and the unit is
can be exited by pressing the DISPLAY/SELECT fully loaded.
button or exit will be automatic after 30 sec.
2) HIGH AIREND TEMP
The following is a list of the set points. Also included This will occur if the airend discharge temperature
are maximum and minimum limits, step size, and (2ATT) exceeds 105°C(221°F ).
units of measure.
3) HIGH AIR PRESS
This will occur if the unit is connected to the ISC
MIN MAX STEP UNIT (sequencer), and the line pressure exceeds the
OFFLINE PRESSURE 75 RATED + 3 1 PSI max. offline pressure for 3 seconds.
ONLINE PRESSURE 65 OFFLINE - 10 1 PSI
CONTROL MODEMOD/ACS - MODULATION - ON/OFF LINE
DISPLAY TIME 10 600 10 SEC
4) T2 SENSOR FAILURE
AUTO RESTART OFF ON --- ---
This will occur when the low ambient option is
AUTO RESTART TIME 2 60 1 MIN turned on and either the low ambient sensor is not
SEQUENCER OFF ON --- --- installed or is broken.
REMOTE START/STOP * OFF ON --- ---
POWER OUT/RESTART* OFF ON --- ---
POWER OUT RESTART 10 120 1 SEC
TIME *
DELAY LOAD TIME 0 60 1 SEC
LEAD/LAG** --- --- --- ---
LAG OFFSET 0 45 1 PSI
*Optional
3.7 ALARMS 10) CK MTR ROTATION
When an alarm occurs, the alarm indicator will light This alarm will occur if a unit is started and
and display will show actual alarm message. If compressor has incorrect rotation.
alternately multiple alarms have occurred the display
will show SCROLL FOR ALARM. In this situation the 11) CALIBRATION FAIL
up and down arrows will be used to view the alarm This alarm will occur if the sensor calibration routine
messages. All alarms (with the exception of the is executed and the sensor reading exceeds 10% of
emergency stop) will be reset by twice pressing the scale.
SET button. Any exceptions to the above will be
explained in the alarm description. 12) NO CONTROL POWER
This alarm will occur when the controller senses a
The following is a list of the alarm messages. loss of control power.
Optional accessories can provide for such things as 4.3 COOLANT SYSTEM
remote starting or stopping and sequencer.
Coolant is forced by pressure from the receiver-
4.2 AIR COOLED COMPRESSORS separator sump to the inlet port of the coolant cooler
and the bypass port of the thermostatic control
Design Temperatures valve.
The standard compressor is designed for operation The thermostatic control valve controls the quantity
in an ambient range of 1.7°C to 46°C(35°F to 15°F of coolant necessary to provide a suitable
). When conditions other than design levels compressor injection temperature. When the
described are encountered, we recommend you compressor starts cold, part of the coolant will
contact your nearest Ingersoll-Rand representative bypass the cooler. As the system temperature rises
for additional information. above the valve setting, the coolant will be directed
to the cooler. During periods of operation in higher
The standard maximum temperature 46°C (115°F) is ambient temperatures, all the coolant flow will be
applicable up to an elevation of 3300 ft. (1000 directed through the cooler.
meters) above sea level. Above this altitude,
significant reductions in ambient temperature are The compressor injection minimum temperature is
required if a standard drive motor is to be used. controlled to preclude the possibility of water vapor
condensing in the receiver. By injecting coolant at a
Coolant Cooler sufficiently high temperature, temperature of the
discharge air and lubricant mixture will be kept
The cooler is an integral assembly of core, fan and above the dew point.
fan-motor, mounted in the compressor. The cooling
air flows in through the left side of the enclosure, The controlled temperature coolant passes through
through the vertically mounted cooler core, and a filter to the airend under constant pressure.
discharges upward through the top of the enclosure.
4.4 COMPRESSED AIR SYSTEM Operation
The air system is composed of: The coolant and air discharging from the
compressor flow into the separator tank through a
tangential inlet. This inlet directs the mixture along
1. Inlet air filter the inner circumference of the separator tank,
2. Inlet valve allowing the coolant stream to collect and drop to
3. Rotors the separator tank sump.
4. Coolant/air separator
5. Minimum pressure/check valve Internal baffles maintain the circumferential flow of
6. Aftercooler remaining coolant droplets and air. In an almost
7. Moisture separator/drain trap continuous change of direction of flow, more and
more droplets are removed from the air by inertial
action and then returned to the sump.
Air enters the compressor, passing through the inlet
air filter and inlet valve. The air stream, now essentially a very fine mist, is
directed to the separator element.
Compression in the screw-type air compressor is
created by the meshing of two helical rotors (male The separator element is constructed with two
and female) on parallel shafts, enclosed in a heavy- concentric, cylindrical sections of closely packed
duty cast iron housing, with air inlet and outlet ports fibers, each held in steel mesh. It is flange-mounted
at the receiver-outlet-cover.
located on opposite ends. The grooves of the female
rotor mesh with, and are driven by, the male rotor. The air stream enters the separator element radially
Tapered roller bearings at the discharge end prevent and the mist coalesces to form droplets. The
axial movement of the rotors. droplets collected on the outer first stage fall to the
receiver sump. Those collected on the inner second
The air-coolant mixture discharges from the stage collect near the outlet of the element, and are
compressor into the separation system. This system, drawn back to the compressor inlet through a filter-
self-contained in the receiver tank, removes all but a screen and orifice fitting installed in the separator
scavenge line.
few PPM of the coolant from the discharge air. The
coolant is returned to the system and the air passes The air stream, now essentially free of coolant,
to the aftercooler. The aftercooling system consists flows from the separator to the aftercooler, then to
of a heat exchanger, a condensate separator, and a the condensate separator, and on to the plant air
drain trap. By cooling the discharge air, much of the system.
water vapor naturally contained in the air is
condensed and eliminated from the downstream 4.6 ELECTRICAL SYSTEM
plant-piping and equipment.
The electrical system of each SSR compressor is
built around the microprocessor-based Intellisys
During unloaded operation, the inlet valve closes controller.
and the blowdown solenoid valve opens, expelling
any compressed air back to the compressor inlet. The standard electrical/electronic components,
enclosed in a readily accessible enclosure include:
4.5 COOLANT/AIR SEPARATION SYSTEM
1. SSR Intellisys controller
The coolant/air-separation-system is composed of a 2. Control transformers and fuses
3. Compressor motor starter, with auxiliary contacts
separator tank with specially designed internals, a
two-stage, coalescing-type separator-element, and and overload relays
provision for return of the coolant back to the 4. Cooling fan motor starter/overload
compressor.
4.7 COMPRESSOR CONTROL SYSTEM
Tools Required
The Intellisys® controls the various operating modes
of the compressor, monitors key compressor • 1/2" open end wrench.
operating parameters, and shuts the compressor • 9/16" open end wrench.
down in the case of an operating problem. The • Loctite® 242 or equivalent.
control system has customer adjustable inputs as
With the compressor shut down remove the nut that
described in the Intellisys® section 3.0. The
fastens the inlet valve pivot anchor to the bracket on
compressor control system has the following
the inlet valve. Apply Loctite® 242 or equivalent to
standard features.
threads on spacer and loosely install nut. Start
compressor and press the unload button so that the
• Automatic Unloaded Start. compressor will not load. Use the display select button
• On/Off Line Capacity Control. to indicate sump pressure on the display. Move the
• Unloaded Stop. position of the pivot anchor to alter the sump pressure
• Automatic Start/Stop. until the sump pressure is between 25-35 psig (1.7-2.4
• Compressor Fault Warning. bar). Moving the pivot towards the inlet valve will raise
• Compressor Fault Alarm Shutdown. the sump pressure. Moving the pivot away from the
inlet valve will lower the sump pressure. Once the
The following paragraphs provide a description of position is correct, fully tighten the nut.
the standard features. Please also refer to the flow
schematic in section 7.0. On/Off Line Control
Automatic Unloaded Start The standard control system provides for either full
compressor capacity flow or zero flow based on the
Pushing the start button signals the Intellisys® to system pressure. If the system pressure falls below
engage the starter coils and opens the oil stop valve the on line set point, the Intellisys® energizes the
(5SV). The compressor will always start in the load/unload solenoid (1SV) and the blowdown
unloaded mode, with the inlet valve in the closed solenoid (3SV). This causes the inlet valve to open
position and the blowdown valve open to vent the and the blowdown valve to close. Compressed air
pressure from the separator tank. The unloaded flows into the system.
start ensures that the compressor has a low starting
torque requirement and that proper oil flow is If system pressure reaches the off line setting, the
established before the compressor loads. compressor unloads to minimize power demands.
Compressors with full voltage starters will not load The Intellisys® de-energizes the load/unload
for seven seconds after the starter button is solenoid
pressed. Compressors with optional star-delta (1SV) and the blowdown solenoid (3SV). This
starters will not load until two seconds after star- causes the inlet valve to close and vents the
delta transition. If system pressure is below the on separator tank. The minimum pressure check valve
line set point pressure, the compressor will (MPCV) closes to prevent back flow from the
automatically load at this time. Press the load/unload compressed air system. The compressor operates at
button to prevent the compressor from loading. minimum power until the system pressure falls to the
on-line pressure setting.
Adjustment Of Unloaded Sump Pressure.
Delay Load Time
During unloaded operation, the inlet valve must allow
some air flow past it to maintain sump pressure for This is the amount of time the line pressure must
proper lubricant flow. This air is compressed by the remain below the on line set point before the
compression module and vented through the compressor will load or start (if the unit was stopped
blowdown valve (3SV). By adjusting the closed due to an auto start/stop situation). This timer will
position of the inlet valve plate, the unloaded sump not delay loading after a start or if the time is set to
pressure can be varied. The unloaded sump pressure
zero. The delay load time feature is useful if the
is set at the factory and should not need adjustment
compressor is operating as a backup to another
under most circumstances. If adjustment is required
compressor and is normally stopped in auto start/
use the following procedure.
stop mode. The delay load time prevents the
compressor from starting and loading if the system
air pressure momentarily drops below the on line
setting of the backup compressor. If no delay is
desired the delay load time setting should be set to
zero.
26
Unloaded Stop
Automatic Start/Stop Operation
If the compressor is running at full load and the
unloaded stop button is depressed, the compressor When in operation, the compressor must meet two
will unload and stop only after running unloaded for specific timing intervals before the Intellisys controller
seven seconds. If the compressor is already unloaded, will stop the unit in an Automatic Start/Stop situation.
the compressor will stop immediately. Use of the
unloaded stop button is the preferred method of For this discussion, the timers will be called timer "A"
stopping the compressor. If an immediate shutdown is and timer "B".
required the EMERGENCY STOP button should be
used. FIRST
Timer "A" prevents the compressor from automatically
Automatic Start/Stop Control starting more than 6 times an hour by requiring the
unit to run at least 10 minutes after each automatic
Many plant air systems have widely varying air start.
demands or large air storage capacity which allows for
automatic standby air capacity control. This 10 minute run period can be loaded, unloaded or
a combination of the two and allows dissipation of
The Intellisys system has been designed to carry out heat generated within the motor windings at start.
this function utilizing a software option module.
Automatic Start/Stop is available as a factory instailed SECOND
option or as a field installation kit. After the compressor has started and reached the off-
line setting and has unloaded, timer "B" requires the
During penods of low air demand, if the line pressure unit to run unloaded for a period of time that the
rises to the upper set point, the Intellisys begins to operator can adjust between 2 and 60 minutes.
time out. If the line pressure remains above the lower
set point for as long as the set time, the compressor The setting of timer "B" is part of the options setpoint
will stop. At the same time the display will indicate the routine and the timer cancels any accumulated time if
compressor has shut down automatically and will the compressor reloads before the timer cycle has
restart automatically. An automatic restart will occur finished.
when the line pressure drops to the lower set point.
An important point... This unloaded run time may, or
The upper and lower set points and shutdown delay may not, be included in the mandatory 10 minute run
time are set on the Intellisys control panel. There is a time used to cool the motor windings.
10 second delay after shutdown during which the
compressor will not restart even if line air pressure When the compressor has completed the settings of
drops below the lower set point. This is to allow the both timer "A" and timer "B", the Intellisys controller
motor to come to a complete stop and the Intellisys stops the compressor and displays "STOPPED IN
controller to collect current data of operating condition. AUTO RESTART."
If line air pressure is below the lower set point at the
end of 10 seconds, the unit will start unless the load Pressure sensor 3APT continues to monitor the
delay timer is set greater than 10 seconds. package discharge pressure and sends information to
the controller which automatically restarts the
Delay Load Time compressor when the pressure falls to the on-line
setting.
This is the amount of time the line pressure must
remain below the online set point before the An advantage to this method of automatic start/stop
compressor will load or start (if the unit was stopped control is allowing the compressor to stop much
due to an auto start/stop situation). This timer will not sooner in certain situations and timer settings,
delay loading after a start or if the time is set to 0. thereby reducing power costs.
When the delay load timer becomes active, the display
will show the delay load countdown. Once the
countdown reaches 0, the unit will load or start.
27
Some Examples of Operation 4.8 OPTIONS
EXAMPLE 2
The operator selects an unloaded run time of 3 4.8.2 Remote Start/Stop
minutes in the OPTION routine and starts the
compressor. The unit runs loaded for 10 minutes and The remote start/stop option allows the operator to
then unloads. control the compressor from a remote mounted start/
stop station. This option may be factory installed or a
At this point, timer “A” has been satisfied but timer “B” field installation kit is available. This feature requires a
still wants the compressor to run unloaded 3 more software option module.
minutes before allowing an automatic stop.
With the optional plug-in module installed, two different
The total run time for this example will be 13 minutes. switches can be wired to the controller for remote start/
stop. (Refer to Electrical Schematics 7.1 or 7.2 for
Remember.... If the unit reloads before timer “B” wiring locations). The switches are customer supplied
finishes the 3 minute setting, the partial time is and must be of momentary type. The stop switch
canceled and timer “B” must restart the 3 minute cycle contacts are normally closed and the start switch
when the compressor unloads again. contacts are normally open.
After 12 minutes of running, the 10 minute mandatory 4.8.3 Power Outage Restart
run-time for timer “A” has been met but the
compressor must continue to run unloaded an For customers that have interruption in their incoming
additional 10 minutes to satisfy timer “B”. power supply to the compressor and must maintain an
uninterrupted supply of compressor air, the Power
After 10 minutes of unloaded run time, the compressor Outage Restart Option allows an Intellisys®
is stopped automatically and the total run time was 22 compressor to automatically restart after incoming
minutes. power is restored.
Modulation Only
The Power Outage Restart Option is turned on by
plugging in the required option module and enabling it
The "MODULATlON" control mode can be selected
through the set point routine. The restart time delay, during the set point procedure on a compressor that
which is adjustable from 10-120 seconds, can also be has the modulation option installed. To load, the
adjusted while in the set point routine on the Intellisys® energizes the load solenoid (1SV) and
Intellisys® controller. Any time power is restored to the blowdown solenoid (3SV) as in on line/off line
compressor after a power interruption, a horn located control. The Intellisys® also energizes the
on the side of the starter box will sound during the modulation solenoids (2SV and 6SV). This connects
restart time delay (10-120 seconds) , after which the regulated pressure from the modulator valve (MV) to
compressor will automatically start. After starting, the the air cylinder. The regulated pressure decreases
compressor will return to the mode of operation that with increasing system pressure near the set point
the compressor was in prior to the power interruption. of the modulation valve. This causes the inlet valve
to throttle the compressor flow. The modulator valve
This option may be installed at the factory or in the is factory set such that the compressor will modulate
field by using an available kit. The remote start/stop to approximately 60% of rated capacity before the
option is included with this option. off line pressure is reached. If the system pressure
continues to increase, the compressor will unload at
4.8.4 Sequencer Control the off line pressure setting. If the system pressure
falls below the on line set point, the compressor will
Sequencer control capability can be added to the load in the modulation control mode.
Intellisys® system by using a sequencer interface.
This option is available as a field installation kit. Modulate/ACS Control
30
NOTES:
31
5.0 SCHEDULED PREVENTATIVE MAINTENANCE
5.1 MAINTENANCE SCHEDULE
THE MAINTENANCE SCHEDULE SPECIFIES ALL RECOMMENDED MAINTENANCE REQUIRED TO KEEP THE
COMPRESSOR IN GOOD OPERATING CONDITION. SERVICE AT THE INTERVAL LISTED OR AFTER THAT
NUMBER OF RUNNING HOURS, WHICHEVER OCCURS FIRST.
* In very clean operating environments and where inlet filter is changed at the above prescribed intervals.
In extremely dirty environments change coolant, filters, and separator elements more frequently.
** Clean cooler cores if discharge air temperature is excessive or if unit shutdown occurs on high air temperature.
SPECIAL-NOTE:
Replace separator element when the separator
differential pressure ( V P) reaches three times the
initial pressure drop or a maximum pressure
differential of 12 psi (.8 bar) at full load or if the
Intellisys warning CHANGE-SEPARATOR-ELEMENT is
displayed. See Section 3.6.
32
5.4 INLET AIR FILTER
Start unit and check for leaks. COOLANT FILTER (45-75 KW)
33
5.6 COOLANT
SSR Ultra Coolant is a polyglycol base coolant. Change 60 hp (45KW) .................. 19 liters (5 gallons)
Ultra Coolant after every 8000 hours or every two years,
75-100 hp (55-75KW)...... 34.2 liters (9 gallons)
whichever comes first.
Items Required
In addition to the tools normally found in any reasonably
equipped serviceman’s toolbox, the following items
should be available at the work site:
34
5.6 COOLANT (Continued)
Tools Required
Q Open end wrench
Q Pliers
Procedure
The screen/orifice assemblies are similar in appearance
to a straight tubing connector and will be located between
two pieces of 1/4 inch O.D. scavenge line tubing.
A removable screen and orifice is located in the exit end FIGURE 5.7-1 SEPARATOR TANK SCAVENGE
of the assembly (See Figure 5.7-1) and will require SCREEN/ORIFICE
cleaning as outlined in the Maintenance Schedule,
Section 5.1.
35
5.8 COOLANT SEPARATOR ELEMENT
36
5.9 COOLER CORES: CLEANING Coolant Coolers
Following are instructions for removal and internal
Ensure that the compressor is isolated from the cleaning of coolant/aftercooler.
compressed air system by closing the isolation
valve and venting pressure from the drip leg.
1) Remove right side panel.
Ensure that the main power disconnect switch is 2) Remove 6 screws in right side plenum wall and
locked open and tagged. (See Figure 5.9-1). remove plenum wall.
3) Remove 8 screws in left side plenum wall and
remove plenum wall.
4) Remove hose from aftercooler discharge (right side)
and plug hole.
5) Disconnect tube from aftercooler inlet (left side).
Loosen tube nut on opposite end of tube and rotate
tube away. Plug hole in aftercooler.
6) Loosen hose nuts 1/4 turn on oil cooler inlet and
outlet hoses. This will allow hose fittings to swivel
without causing kink in hose.
7) Remove 6 screws in cooler support panel to allow
cooler to swing out on hinges.
8) Cover opening that exposes fan and fan motor to
ensure water does not spray onto motors.
9) Before cleaning coolers, check to ensure all
connections are plugged to prevent contamination of
compressor system.
CAUTION
FIGURE 5.9-1 MAIN DISCONNECT
LOCKED AND TAGGED Strong cleaners can harm
Tools Required aluminum cooler parts. Follow cleaner
Q Screwdriver manufacturer’s instructions for use.
Q Wrench set Wear appropriate safety equipment.
Q Air hose equipped with approved local codes.
37
5.9-2 Water Cooled Coolers (Continued)
Precautions
CAUTION
5.10 MOTOR LUBRICATION
CAUTION
Relubrication amount Grease should be added when the motor
Lubricant Amount is stopped and power disconnected.
Motor Frame Size in3 cc oz. grams
38
5.10 MOTOR LUBRICATION (Continued)
Most motors require: 1) Prior to placing a unit in storage, rotate the motor
several revolutions by hand in the proper direction
Mobilith SHC 220.................................................Mobil of rotation.
Unrex N2........................................................... ESSO
2) Thereafter, rotate the motor as described in Step 1
Use the grease as indicated on a special grease at three month intervals until such time as the unit is
information nameplate on the motor. Use of alternative placed in service.
greases can result in shortened motor life due to
incompatibility of greases.
39
Follow these precautions to minimize damage from
5.11 INTELLISYS REMOVAL static electricity. Static can cause severe damage to
microcircuits.
Ensure that the compressor is isolated from the
compressed air system by closing the isolation 1) Make the least possible movement to avoid build-
valve and venting pressure from the drip leg. ing up static electricity from your clothing or tools.
Ensure that the main power disconnect switch is 2) Discharge potential static electricity by touching
locked open and tagged (See Figure 5.11-1). (grounding) yourself to the starter box.
Tools:
Screwdriver Size #1, flathead
3/8 inch hex driver
Controller Removal:
40
5.12 COOLANT HOSES
The flexible hoses that carry coolant to and from the oil
cooler may become brittle with age and will require
replacement. Have your local Ingersoll-Rand distributor
check them every 2 years.
Removal
Installation
Removal
41
6.0 TROUBLE SHOOTING CHART
TROUBLE CAUSE &/OR DISPLAY WHAT TO DO
Compressor fails to start. 110/120V control voltage not available. — Check fuses. Check transformers and
wiring connections.
Compressor shuts down. "HIGH AIREND TEMP." — Insure that installation area has
adequate ventilation.
— Insure that cooling fan is operating. If
not reset circuit breaker inside starter
box.
— Check coolant level. Add if required.
— Cooler cores dirty. Clean coolers.
NOTE: If a shutdown oc- "HIGH AIR PRESS." — Check for restricted or malfunctioning
curs, press the DISPLAY blowdown valve or minimum pressure
SELECT button once to check valve.
activate the L.E.D. display "LOW SUMP PRESS." — Check for air leak from tank or
table. Using the adjacent up blowdown piping.
and down arrows, the values — Adjust sump pressure.
displayed will be those im- "PRES SENSOR FAIL" or — Check for defective sensor, bad sensor
mediately preceding shut- "TEMP SENSOR FAIL" connection, or broken sensor wires.
down. Use these values
when trouble shooting a "CK MOTOR ROTATION." — Interchange any two line connections
problem. (L1,L2,L3) at the starter.
"MAIN MTR OVERLD" — Check for loose wires.
— Check supply voltage.
— Check heater size.
Low system air pressure Compressor running in "Unload" Mode. — Press "UNLOAD/LOAD" button.
Controller off-line set point too low. — Press "UNLOAD/STOP" button, set off-
line set point at a higher value.
Inlet valve not fully open. — Inspect and repair. Check control
system operation.
42
TROUBLE SHOOTING CHART (Continued)
Water in Air System Defective moisture separator/drain trap — Inspect and clean if required. Replace
separator/trap if defective.
Drain line/drip leg incorrectly installed. — Slope drain line away from trap. Install
drip leg.
Pressure relief valve opens Compressor operating over pressure. — Adjust Intellisys set points.
43
7.0 REFERENCE DRAWINGS
46
7.2 ELECTRICAL SCHEMATIC
(Air Cooled)
47
7.2 FOUNDATION PLAN (WATER COOLED)
48
7.3 ELECTRICAL SCHEMATIC
(Air Cooled)
49
7.4 BASIC FLOW SCHEMATIC - AIR COOLED
50
7.5 BASIC FLOW SCHEMATIC - WATER COOLED
51
TYPICAL SYSTEM FLOW
DIAGRAM
52
53
56
8.0 WATER QUALITY
RECOMMENDATIONS
Water quality is often overlooked when the cooling
system of a water cooled air compressor is examined. formation is the precipitation of calcium carbonate out
Water quality determines how effective the heat of the water. This is dependent on temperature and
transfer rate, as well as the flow rate will remain during pH. The higher the pH value, the greater the chance
the operation life of the unit. It should be noted that the of scale formation. Scale can be controlled with water
quality of water used in any cooling system does not treatment.
remain constant during the operation of the system.
The water makeup is affected by evaporation, CORROSION
corrosion, chemical and temperature changes, In contrast to scale formation is the problem of
aeration, scale, and biological formations. Most corrosion. Chlorides cause problems because of their
problems in a cooling system show up first in a size and conductivity. Low pH levels promote
reduction in the heat transfer rate, then in a reduced corrosion, as well as high levels of dissolved oxygen.
flow rate, and finally with damage to the system.
FOULING
There are many constituents in the water system that Biological and organic substances (slime) can also
must be balanced to have a good stable system. The cause problems, but in elevated temperature
following is a list of the major components that should environments such as cooling processes, they are not
be monitored: major concerns. If they create problems with clogging,
commercial shock treatments are available.
SCALE
Scale formation inhibits effective heat transfer, yet it To ensure good operation life and performance of the
does help prevent corrosion. Therefore, a thin uniform compressor cooling system, the recommended
coating of calcium carbonate is desired on the inner acceptable ranges for different water constituents are
surfaces. Perhaps the largest contributor to scale included below:
57
Recommended equipment for on-site analysis in-
cludes a thermometer, pH meter, and dissolved ox-
ygen meter. Dissolved oxygen and temperature must
be measured on-site and it is recommended that pH
be measured on-site. All other analyses should be
performed by a professional water quality analyst. The
Langelier Index (Ll) is calculated using the following
equation and the tables found on the following pages.
58
LANGELIER INDEX CHART VALUES
50 .07 0 2 4 6 8
TENS
100 1.74 1.72 1.71 1.09 1.67
400 .16 110 1.05 1.64 1.62 1.60 1.58
Hardness (ppm)
Alkalinity (ppm)
UNITS UNITS
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
0 0.08 0.20 0.30 0.38 0.43 0.51 0.56 0 0.00 0.30 0.48 0.60 0.70 0.78 0.85 0.90 0.93
10 0.60 0.64 0.68 0.72 0.73 0.78 0.81 0.83 0.86 0.88 10 1.00 1.04 1.08 1.11 1.15 1.18 1.20 1.23 1.26 1.29
20 0.90 0.92 0.94 0.96 0.98 1.00 1.02 1.03 1.05 1.06 20 1.30 1.32 1.34 1.36 1.38 1.40 1.42 1.43 1.45 1.46
30 1.08 1.09 1.11 1.12 1.13 1.15 1.16 1.17 1.18 1.19 30 1.48 1.49 1.51 1.52 1.53 1.54 1.56 1.67 1.58 1.59
40 1.20 1.21 1.23 1.24 1.25 1.26 1.26 1.27 1.28 1.29 40 1.60 1.61 1.62 1.63 1.64 1.65 1.66 1.67 1.68 1.69
50 1.30 1.31 1.32 1.33 1.34 1.34 1.35 1.36 1.37 1.37 50 1.70 1.71 1.72 1.72 1.73 1.74 1.75 1.76 1.76 1.77
60 1.38 1.39 1.39 1.40 1.41 1.42 1.42 1.43 1.43 1.44 60 1.78 1.79 1.79 1.80 1.81 1.81 1.82 1.83 1.83 1.84
70 1.45 1.45 1.46 1.47 1.47 1.48 1.48 1.49 1.49 1.50 70 1.85 1.85 1.86 1.86 1.87 1.88 1.88 1.89 1.89 1.90
80 1.51 1.51 1.52 1.52 1.53 1.53 1.54 1.54 1.55 1.55 80 1.90 1.91 1.91 1.92 1.92 1.93 1.93 1.94 1.94 1.95
90 1.95 1.96 1.96 1.97 1.97 1.98 1.98 1.99 1.99 2.00
TENS
90 1.56 1.56 1.57 1.57 1.58 1.58 1.58 1.59 1.59 1.60
TENS
100 1.60 1.61 1.61 1.61 1.62 1.62 1.63 1.63 1.64 1.64 100 2.00 2.00 2.01 2.01 2.02 2.02 2.03 2.03 2.03 2.04
110 1.64 1.65 1.65 1.66 1.66 1.66 1.67 1.67 1.67 1.68 110 2.04 2.05 2.05 2.05 2.06 2.06 2.06 2.07 2.07 2.08
120 1.68 1.68 1.69 1.69 1.70 1.70 1.70 1.71 1.71 1.71 120 2.08 2.08 2.09 2.09 2.09 2.10 2.10 2.10 2.11 2 11
130 1.72 1.72 1.72 1.73 1.73 1.73 1.74 1.74 1.74 1.75 130 2.11 2.12 2.12 2.12 2.13 2.13 2.13 2.14 2.14 2.14
140 1.75 1.75 1.75 1.76 1.76 1.76 1.77 1.77 1.77 1.78 140 2.15 2.15 2.15 2.16 2.16 2.16 2.16 2.17 2.17 2.17
150 1.78 1.78 1.78 1.79 1.79 1.79 1.80 1.80 1.80 1.80 150 2.18 2.18 2.18 2.18 2.19 2.19 2.19 2.20 2.20 2.20
160 1.81 1.81 1.81 1.81 1.82 1.82 1.82 1.82 1.83 1.83 160 2.20 2.21 2.21 2.21 2.21 2.22 2.22 2.23 2.23 2.23
170 1.83 1.84 1.84 1.84 1.84 1.85 1.85 1.85 1.85 1.85 170 2.23 2.23 2.23 2.24 2.24 2.24 2.24 2.25 2.25 2.25
180 1.86 1.86 1.86 1.86 1.87 1.87 1.87 1.87 1.88 1.88 180 2.26 2.26 2.26 2.26 2.26 2.27 2.27 2.27 2.27 2.28
190 1.88 1.88 1.89 1.89 1.89 1.89 1.89 1.90 1.90 1.90 190 2.28 2.28 2.28 2.29 2.29 2.29 2.29 2.29 2.30 2.30
200 1.90 1.91 1.91 1.91 1.91 1.91 1.92 1.92 1.92 1.92 200 2.30 2.30 2.30 2.31 2.31 2.31 2.31 2.32 2.32 2.32
TENS TENS
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90
200 1.92 1.94 1.96 1.98 2.00 2.02 2.03 2.03 2.06 200 2.32 2.34 2.36 2.38 2.40 2.42 2.43 2.43 2.46
300 2.08 2.09 2.11 2.12 2.13 2.13 2.16 2.17 2.18 2.19 300 2.48 2.49 2.51 2.52 2.53 2.54 2.56 2.57 2.58 2.59
400 2.20 2.21 2.23 2.24 2.23 2.26 2.26 2.27 2.28 2.29 400 2.60 2.61 2.62 2.63 2.64 2.65 2.66 2.67 2.68 2.69
HUNDREDS
HUNDREDS
500 2.30 2.31 2.32 2.33 2.34 2.34 2.35 2.36 2.37 2.37 500 2.70 2.71 2.72 2.72 2.73 2.74 2.75 2.76 2.76 2.77
600 2.38 2.39 2.39 2.40 2.41 2.42 2.42 2.43 2.43 2.44 600 2.78 2.79 2.79 2.80 2.81 2.81 2.82 2.83 2.83 2.84
700 2.45 2.45 2.46 2.47 2.47 2.48 2.48 2.49 2.49 2.50 700 2.85 2.85 2.86 2.86 2.87 2.88 2.88 2.89 2.89 2.90
800 2.51 2.51 2.52 2.52 2.53 2.53 2.54 2.54 2.55 2.55 800 2.90 2.91 2.91 2.92 2.92 2.93 2.93 2.94 2.94 2.95
900 2.56 2.56 2.57 2.57 2.58 2.58 2.58 2.59 2.60 2.60 900 2.95 2.96 2.96 2.97 2.97 2.98 2.98 2.99 2.99 3.00
59
60
61
MAINTENANCE RECORD
62
MAINTENANCE RECORD
63
MAINTENANCE RECORD
64
ML/MM/MH 45
ML/MM/MH/MJ 55
ML/MM/MH/MJ 75
PARTS BOOK
65
TABLE OF CONTENTS
ROTARY SCREW AIR COMPRESSOR
Serial Num-
ber:________________________________________
Model Num-
ber:_______________________________________
66
PARTS LIST
67
DRAWING NO. REV.
70570015 00
68
DRAWING NO. REV.
70570015 00
69
4 39256326 7 RETAINER, BOLT 0.25
5 70561840 1 BOX, STARTER
6 39589007 1 GASKET, CONDUIT PLATE
7 70561725 1 FACIA, CONTROL PANEL
8 70612791 4 GAUGE, PRESSURE 0-16 kg/cm2
9 70539333 4 ADAPTER
10 39155577 4 ELBOW, ADAPTER
11 94203288 8 PLUG
12 70097365 1 GAUGE, OIL TEMP
13 70140801 1 ADAPTER
70
DRAWING NO. REV.
39908439 02
71
6 39191648 1 PLUG 11 POSITION
7 39191655 1 PLUG 16 POSITION
8 39249875 1 GASKET SEALING EDGE 130” LONG
9 39256318 7 SCREW KNURL HD .25 X 1 LONG
10 39256326 7 RETAINER BOLT .25
11 39495874 1 GASKET INTELLYSIS STARTER BOX
12* 70195649 1 SWITCH EMERGENCY STOP
13 39589007 1 GASKET CONDUIT PLATE
14 39817655 1 CONTROLLER INTELLYSIS
15 85540144 1 BOX STARTER
16 85540169 2 ANGLE CONTROLLER
DRAWING NO. REV.
70570023 00
72
DRAWING NO. REV.
70570023 00
CONTROL PIPING NEMA 1 - NO MODULATION WITH INTELLISYS
73
** CONTROL PIPING NEMA 1 - NO MODULATION WITH RELAY PANEL
75
13 39181342 1 TEE, BRANCH
14 39418926 1 VALVE
15 39530852 1 VALVE, SOLENIOD 3WAY
16 39583943 2 VALVE, SOLENOID 3WAY (DC COIL)
17 39853809 1 TRANSDUCER, PRESSURE
18 39905542 1 VALVE, REGULATOR (XF & EP UNITS)
39905682 1 VALVE, REGULATOR (HP & XP UNITS)
19 95343679 1 NIPPLE
20 95837233 1 PLUG, SOCKET
21 95930301 1 BUSHING, REDUCER
22 95940672 1 TEE, BRANCH
77
13 39181342 1 TEE, BRANCH
14 39418926 1 VALVE
15 39530852 1 VALVE, SOLENIOD 3WAY
16 39583943 1 VALVE, SOLENOID 3WAY (DC COIL)
17 94417938 1 PRESSURE SWITCH
18 39905542 1 VALVE, REGULATOR (XF & EP UNITS)
39905682 1 VALVE, REGULATOR (HP & XP UNITS)
19 95343679 1 NIPPLE
20 95837233 1 PLUG, SOCKET
21 95930301 1 BUSHING, REDUCER
22 95940672 1 TEE, BRANCH
23 70543624 1 COUPLING
REF.
PART NO. QTY. DESCRIPTION
NO.
*1 70619325 1 ELBOW
2 39128483 8 SCREW, WHIZLOCK 0.38 X 1 LONG, ZINC PLATED
3 39454525 2 GASKET, FLANGE
4 95992632 2 ELBOW
5 39479845 2 FLANGE
*6 70615018 1 HOSE, HYDRAULIC
*7 70619341 1 HOSE, HYDRAULIC
8 39572276 1 HOSE, HYDRAULIC
9 39572375 1 HOSE, HYDRAULIC
10 39572433 1 HOSE, HYDRAULIC
113
*11 70619333 1 HOSE, HYDRAULIC
12 39577176 1 HOSE, HYDRAULIC
*13 70605530 1 COOLER, OIL
*14 70605548 1 AFTERCOOLER
15 95923355 8 NUT HEX. 0.63
*16 95952354 8 SCREW HEX. 0.63 X 2.75 LONG ZINC PLATED
17 95937645 1 ELBOW
18 95937678 1 ELBOW
19 95939336 2 CONNECTOR
20 95941043 2 BUSHING
21 95950002 1 ELBOW
*22 95376133 2 ELBOW
118
119
SSR 55/75 KW Recommended Spare Parts
Qty.
Part Per
Compressor Part No. Unit Location or Use