Final Design
Final Design
Design of Column:
Effective Length, Le = 1.0L = 4.5312 m Both ends Hinged
Design Strength, Py = fy/ϒs = 260.87 N/mm 2
Design of Column:
Effective Length, Le = 1.0L = 0.5 m Both ends Hinged
Design Strength, Py = fy/ϒs = 260.87 N/mm2
Second moment of area of the cross section
Ixx = 165900 mm4
Iyy = 22600 mm4
Design of Column:
Effective Length, Le = 1.0L = 0.367 m Both ends Hinged
Design Strength, Py = fy/ϒs = 430.43 N/mm 2
7.5
0.75
s Hinged
Cold Formed Steel Section Design (Single Channel Section): (Longitudinal wall members)
Grade = 550 Mpa
Yield Stress,fy = 495 Mpa 37
Compressive force = 0.129 kN
Length of member,L = 1.981 m
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.75 mm
No. of channel section = 1
Internal Radius,R = 1.5t = 1.13 mm 90
B1 = 86.25 mm
B2 = 33.25 mm
h=B2/B1 = 0.39
i) Effective width of Web
Buckling Coefficient,
K1 = 7-1.8h/(0.15+h)-1.43h3 = 5.62 (= K)
Design of Column:
Effective Length, Le = 1.0L = 1.981 m Both ends Hinged
Design Strength, Py = fy/ϒs = 478.26 N/mm 2
7.5
0.75
s Hinged
Cold Formed Steel Section Design (Single Channel Section): (Longitudinal wall members)
First Floor
Yield Stress,fy = 495 Mpa 37
Compressive force = 3.687 kN
Length of member,L = 2.999 m
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.75 mm
No. of channel section = 1
Internal Radius,R = 1.5t = 1.13 mm 90
B1 = 86.25 mm
B2 = 33.25 mm
h=B2/B1 = 0.39
i) Effective width of Web
Buckling Coefficient,
K1 = 7-1.8h/(0.15+h)-1.43h3 = 5.62 (= K)
Design of Column:
Effective Length, Le = 1.0L = 2.999 m Both ends Hinged
Design Strength, Py = fy/ϒs = 430.43 N/mm 2
7.5
0.75
s Hinged
Cold Formed Steel Section Design (Double Channel Section): (Longitudinal wall members)
Grade
Yield Stress,fy = 495 Mpa
Compressive force = - kN
Length of member,L = 2.999 m
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.75 mm
No. of channel section = 2
Internal Radius,R = 1.5t = 1.13 mm
B1 = 86.25 mm
B2 = 33.25 mm
h=B2/B1 = 0.39
i) Effective width of Web
Buckling Coefficient,
K1 = 7-1.8h/(0.15+h)-1.43h3 = 5.62 (= K)
Design of Column:
Effective Length, Le = 1.0L = 2.999 m Both ends Hinged
Design Strength, Py = fy/ϒs = 430.43 N/mm 2
Design of Column:
Effective Length, Le = 0.358 m Both ends Hinged
Design Strength, Py = fy/ϒs = 430.43 N/mm 2
7.5
0.75
s Hinged
Cold Formed Steel Section Design (Single Channel Section): (Transverse wall members)
First Floor
Yield Stress,fy = 495 Mpa 37
Compressive force = 0.139 kN
Length of member,L = 1.981 m
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.75 mm
No. of channel section = 1
Internal Radius,R = 1.5t = 1.13 mm 90
B1 = 86.25 mm
B2 = 33.25 mm
h=B2/B1 = 0.39
i) Effective width of Web
Buckling Coefficient,
K1 = 7-1.8h/(0.15+h)-1.43h3 = 5.62 (= K)
Design of Column:
Effective Length, Le = 1.0L = 0.9905 m Both ends Hinged
Design Strength, Py = fy/ϒs = 430.43 N/mm 2
7.5
0.75
s Hinged
Design of Cold formed steel Beam (First Floor)
Grade = 550 Mpa
Span, l = 0.4 m
Modulus of Elasticity,E = 205000 Mpa 37
Yield Stress, fy = 495 Mpa
Maximum Moment in Beam,M = 0.18 kN-m
Maximum Shear Force, V = 1.094 kN
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.75 mm
No. of channel section = 1 90
Internal Radius,R = 1.5t = 1.13 mm
Radius of gyration, ryy = 13.21 mm
Second moment of area, Ixx = 165900 mm4
Section modulus, Zxx=Ixx/(D/2) = 3686.67 mm3
Assume only compression flange is subjected to local buckling.
Buckling Coefficient,
K1=5.4-(1.4h/0.6+h)-0.02h3 = 3.91 or 4 whichever is greater
or, k = 4.00
Critical Buckling Stress,
Pcr = ((kπ2E)/12(1-μ2))*(t/b)2 = 376.69 N/mm2
fc/Pcr = 0.94 > 0.123
beff/b = 1 when (fc/Pcr) ≤ 0.123
beff/b = (1+14((fc/Pcr)^0.5- 0.35)^4)^-0.2 when (fc/Pcr) > 0.123
Here,
beff/b = (1+14((fc/Pcr)^0.5- 0.35)^4)^-0.2 = 0.80
beff = 26.52 mm
This means the full section is not effective in bending.
Ixr=Ixx = 165900 mm4
Zxr=Zxx = 3686.67 mm3
ver is greater
kN-m
N/mm2 Ok
Design of Cold formed steel Beam (Ground Floor)
Span, l = 1.958 m
Modulus of Elasticity,E = 205000 Mpa 37
Yield Stress, fy = 495 Mpa
Maximum Moment in Beam,M = 0.618 kN-m
Maximum Shear Force, V = 0.872 kN
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.75 mm
No. of channel section = 1 90
Internal Radius,R = 1.5t = 1.13 mm
Radius of gyration, ryy = 13.21 mm
Second moment of area, Ixx = 165900 mm4
Section modulus, Zxx=Ixx/(D/2) = 3686.67 mm3
Assume only compression flange is subjected to local buckling.
Buckling Coefficient,
K1=5.4-(1.4h/0.6+h)-0.02h3 = 3.91 or 4 whichever is greater
or, k = 4.00
Critical Buckling Stress,
Pcr = ((kπ2E)/12(1-μ2))*(t/b)2 = 376.69 N/mm2
fc/Pcr = 0.94 > 0.123
beff/b = 1 when (fc/Pcr) ≤ 0.123
beff/b = (1+14((fc/Pcr)^0.5- 0.35)^4)^-0.2 when (fc/Pcr) > 0.123
Here,
beff/b = (1+14((fc/Pcr)^0.5- 0.35)^4)^-0.2 = 0.80
beff = 26.52 mm
This means the full section is not effective in bending.
Ixr=Ixx = 165900 mm4
Zxr=Zxx = 3686.67 mm3
ver is greater
kN-m
N/mm2 Ok
Design of Cold formed steel Purlin
Span, l = 1.958 m
Modulus of Elasticity,E = 205000 Mpa 37
Yield Stress, fy = 495 Mpa
Maximum Moment in Purlin,M = 0.618 kN-m
Maximum Shear Force, V = 0.872 kN
Depth of web = 90 mm
Width of flange = 37 mm
Length of lips = 7.5 mm
Thickness of Member,t = 0.55 mm
No. of channel section = 1 90
Internal Radius,R = 1.5t = 0.83 mm
Radius of gyration, ryy = 13.27 mm
Second moment of area, Ixx = 122100 mm4
Section modulus, Zxx=Ixx/(D/2) = 2713.33 mm3
Assume only compression flange is subjected to local buckling.
Buckling Coefficient,
K1=5.4-(1.4h/0.6+h)-0.02h3 = 3.94 or 4 whichever is greater
or, k = 4.00
Critical Buckling Stress,
Pcr = ((kπ2E)/12(1-μ2))*(t/b)2 = 190.92 N/mm2
fc/Pcr = 1.62 > 0.123
beff/b = 1 when (fc/Pcr) ≤ 0.123
beff/b = (1+14((fc/Pcr)^0.5- 0.35)^4)^-0.2 when (fc/Pcr) > 0.123
Here,
beff/b = (1+14((fc/Pcr)^0.5- 0.35)^4)^-0.2 = 0.62
beff = 21.17 mm
This means the full section is not effective in bending.
Ixr=Ixx = 122100 mm4
Zxr=Zxx = 2713.33 mm3
ver is greater
kN-m Ok
N/mm2 Ok
DESIGN OF COLD FORMED STEEL ROOF TRUSS
Material Properties
Grade of steel, fy = 495 Mpa
i) Structural Model
Span of truss = 1.958 m
Maximum Spacing of truss = 1.958 m
Height of truss = 0.793 m
Number of truss = 6
Spacing of Purlin = 0.392 m
Maximum length of rafter = 0.392 m
Maximum length of bottom chord = 1.958 m
Maximum length of the vertical member = 0.493 m
Maximum length of inclined member = 0.358 m
ii) Loading
calculation for dead load
CCGI Sheet = 0.055 kN/m2
Fixings = 0.025 kN/m2
Services = 0.1 kN/m2
Total Load = 0.18 kN/m2
Load Calculations:
Live load on sloping roof = 0.49 kN/m2 As per IS 875 Part 2
Total dead Load on Purlin = 0.18 kN/m 2
Load combinations:
1. DL +WL
Normal to slope = -1.662 kN/m2
parallel to slope = 0.06 kN/m2
Due to continuity of purlins, factored bending moments and shear force are as follows:
Load combination (Max Response)
Mz = 0.29 kN-m
My = 0.21 kN-m
SFz = 0.33 kN
Grade of steel = 550 Mpa
Factor of safety = 1.1
DESIGN OF MASONRY STRIP FOOTING
Axial Load, P = 2.765 kN/m
Size of wall = 90 mm
Unit weight of soil, ϒ = 20 kN/m3
Angle of repose for the soil,ɸ = 30 Degree
Allowable bearing capacity of soil,qo = 50 kN/m2
Depth of Foundation
Df=(P/ϒ)(1-sinɸ/1+sinɸ)2 = 0.28 m
Provided depth of footing = 0.9 m Ok
Safe
Design of Rivet Connection
Diameter of rivet,d = 4 mm
i. Shear capacity Ps of a rivet in tilting and bearing
For t4/t3 = 1.0
Ps = 3.2(t33d)0.5Py
whichever is smaller
or Ps = 2.1t3dPy
Where,
t3 = the thickness of the member in contact with the screw
head or the preformed rivet head
t4 = the thickness of the member remote from the screw head
or the preformed rivet head
d = Diameter of the fastener
Py = Design strength of member material
Here,
Yield strength, fy = 495 Mpa
ϒs = 1.15
Therefore, Py=fy/ϒs = 430.43 N/mm2
t3=t4 = 0.75 mm
Ps = 1.79 kN
or Ps = 2.71 kN
Here,
Yield strength, fy = 495 Mpa
ϒs = 1.15
Therefore, Py=fy/ϒs = 430.43 N/mm2
t3=t4 = 0.75 mm
Ps = 1.79 kN
or Ps = 2.71 kN
Here,
Yield strength, fy = 495 Mpa
ϒs = 1.15
Therefore, Py=fy/ϒs = 430.43 N/mm2
t3=t4 = 0.75 mm
Ps = 1.74 kN
or Ps = 2.58 kN
Along Y-Direction
Anchor bolt diameter = 12 mm
Length of bolt = 100 mm
Max. tension in the structural member = 103.80 kN
Base Shear along Y-direction (Wind Governing) = 67.771 kN
Total length of the wall along Y- direction = 13.706 m
Providing 3 numbers of anchor bolts at each of the seven walls along Y-direction of length 1.958 m.
Total No. of Bolts used = 21
Using hex high carbon steel,
Max. tensile capacity of each bolt = 14.4 kN
Max. shear capacity of each bolt = 16.7 kN
Hence, Total Shear capacity of Bolts = 350.7 kN > 67.771 kN
Hence, Total tensile capacity of Bolts = 302.4 kN > 103.80 kN
Along X-Direction
Anchor bolt diameter = 12 mm
Length of bolt = 100 mm
Max. tension in the structural member = 2.71 kN
Base Shear along X-direction (EQx Governing) = 10.71 kN
Total length of the wall along X- direction = 23.68 m
Total No. of Bolts used = 36
Using hex high carbon steel,
Max. tensile capacity of each bolt = 14.4 kN
Max. shear capacity of each bolt = 16.7 kN
Hence, Total Shear capacity of Bolts = 601.2 kN > 10.71 kN
Hence, Total tensile capacity of Bolts = 518.4 kN > 2.71 kN
Ok
Ok
Ok
Ok