Simplex 4010-0004
Simplex 4010-0004
Features
Compatible with Simplex ES Net and 4120 fire alarm networks
*This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0369 for allowable
values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. NYC Fire Dept COA #6095. Additional listings may be
applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Introduction
4010ES series fire detection and control units provide leading edge installation, operator, and service features for customer applications in the mid-
range addressable fire alarm systems market. An onboard Ethernet port provides fast external system communications to expedite installation and
service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files.
Modular design: A variety of functional modules are available to meet specific system requirements. With these selections, you can configure control
units for either stand-alone or networked fire control operation.
InfoAlarm Command Center options provide convenient expanded display content. Refer to data sheet InfoAlarm Command Center for the 4010ES Fire
Alarm Control Unit S4010-0009 for more information.
Mechanical description
• Mounting box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting
• Includes smooth box surfaces for precise local cutting of conduit entrance holes
• The hinged user interface panel easily opens for internal access
• NACs mount directly on power supply assemblies providing minimized wiring loss, compact size, and readily accessible terminations
• Modules are power-limited except where noted, such as relay modules
• Doors include tempered glass inserts; boxes and doors are available in platinum or red
• Box and door or retainer assemblies are included with basic control unit assemblies
• Cabinet assembly is rated NEMA 1 and IP 30
• Cabinet assembly design is seismic tested and is certified to IBC and CBC standards and to ASCE 7 categories A through F; requires battery brackets
as detailed on data sheet Battery Brackets for Seismic Activity Applications S2081-0019
Addressable operation
Each addressable device on the communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm,
supervisory, or trouble. Both Class B and Class A pathway operation is available. Sophisticated poll and response communication techniques ensure
supervision integrity and allow you to T-tap the circuit for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications
poll, and you can change them to steady from the control unit.
IDNet addressable channel capacity
The Main System Supply 2 provides an electrically isolated IDNet2 signaling line circuit (SLC) that supports up to 250 addressable monitor and control
points intermixed on the same pair of wires. Additional 250 address IDNet 2+2 Modules with four short circuit isolating output loops are available.
IDNet 2+2 Module SLCs are isolated from other system reference voltages to reduce common mode noise interaction with adjacent system wiring.
Table 1: IDNet 2 and IDNet 2+2 SLC wiring specifications
Specification Rating
Maximum distance from control unit for each 0 to 125 4000 ft (1219 m); 50 ohms
device load 126 to 250 2500 ft (762 m); 35 ohms
Total wire length allowed with T-taps for Class B wiring Up to 12,500 ft (3.8 km); 0.60 µF
Maximum capacitance between IDNet channels 1 µF
Wire type and connections Shielded or unshielded, twisted or untwisted wire. See note.
2 2
Connections Terminals for 18 AWG to 12 AWG (0.82 mm to 3.31 mm )
Installation instructions 579-989
Compatibility includes: IDNet communicating devices and TrueAlarm sensors including QuickConnect2 sensors. See data sheet S4090-0011 for
additional reference.
Note: Some applications may require shielded wiring. Review your system with your local Simplex product supplier.
Programmable sensitivity
You can select the programmable sensitivity of each sensor at the control unit for different levels of smoke obscuration, shown directly in percent, or
for specific heat detection levels. To evaluate whether to revise the sensitivity, read the peak value, which is stored in memory, and compare the value
to the alarm threshold directly in percent.
CO sensor bases
CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one
system address. You can enable or disable the CO sensor for use in LED or Switch modes and custom control, and you can make the CO sensor public
for communication across a fire alarm network. Refer to data sheet TrueAlarm CO Sensor Bases for Smoke, Heat, and Photo/Heat Sensors using IDNet
Communications S4098-0052 for details.
• Select as IDC or Relay. Configure up to eight Class B IDCs, or up to four Class A IDCs; or up to eight Relay outputs rated 2 A resistive at 30 VDC (N.O.
or N.C.); or a combinations of IDCs and Relays; each zone is separately configurable as an IDC or Relay output.
• IDC Support. Each IDC supports up to 30, 2-wire devices. Zone relay modules may be powered directly from the control unit power supply or through
the optional 25 VDC regulator module where required for 2-wire detector compatibility. Refer to 2-Wire Detector Compatibility Chart (579-832) for
additional details.
• You can select the following IDC EOL resistor values as: 3.3 kohms, 2 kohms, 2.2 kohms, 3.4 kohms, 3.9 kohms, 4.7 kohms, 5.1 kohms, 5.6 kohms,
6.34/6.8 kohms, and 3.6 kohms + 1.1 kohms. Refer to Zone/Relay Module Installation Instructions (579-1236) for more details.
Features
The ES Touch Screen Displays provide customized operating experience with the following features
• Event activity display choices include: First 8 Events; or First 7 Events with emphasis on Most Recent; or First 6 Events with emphasis on First and
Most Recent, individually selectable for each event type
• System reports are easily viewable; you can read logs with minimal scrolling
• Up to two languages are available for each system, easily selected by programmable key press
• You can vector information sent to Remote ES Touch Screen Displays by point or zone
• Both Hard and Soft keys are available for critical functions: Event Acknowledge, Alarm Silence, and Reset Functions
• Resistive touchscreen technology allows operation with or without gloves
• Seven programmable RGY LEDs are available for user-defined display status, up to 2 status conditions for each LED
• Seven programmable Soft keys are available for user-defined control or maintenance functions
• PRI2 Soft key label which you change to CO to annunciate Carbon Monoxide detection status
• ES Touch Screen Display which you can program to report individual points or groups of points as a single zone
• Supports ability to display a custom watermark background file of a company logo or other desired display content
• Seismically compliant under the State of California Statewide Office of Housing and Development (OSHPD) Special Seismic Certification (SSC) program
guidelines. Refer to Simplex Seismic Application Guide (579-1213) and Battery Brackets for Seismic Activity Applications (S2081-0019) for details.
Display properties
• 8 inch (203 mm) diagonal, 800 x 600 resolution color touch screen display capable of annunciating up to 8 active events without scrolling
• Bright white LED backlighting provides efficient and long lasting illumination. The backlight is dim in a quiescent state and automatically switches to
full power on touch or on event activity in system.
Description
ES Touch Screen Displays for 4010ES fire alarm systems provide a large display with extended information content, dual language support including
UTF-8 character languages, and an intuitive control key interface with the following features:
• Each 4010ES control panel supports up to 8 ES Touch Screen Displays, one main and seven remote. It can enable one ES Touch Screen Display to
take-control and to designate access levels for interfaces not in-control. You can assign programmable LEDs to, in-control status indications.
• Menu-driven format conveniently prompts operators for the next action required
• Direct point callup displays individual points alphabetically and then homes in on the logical choice as more point information is entered
• Event categories are color coded for quick visual representation; Red for Alarm and Priority 2 Events; Yellow for Supervisory and Trouble events
• Date formats are either MM/DD/YY or DD/MM/YY
• Time formats are either 24 hour or 12 hour with AM/PM
• System Normal screen supports a color background (watermark) for company name, company logo, or other desired display content
Figure 5: First Eight Active Trouble Events List Figure 6: Direct Point Callup
Figure 7: Alarm History Log Figure 8: Detailed Point Status Screen for TrueAlert ES Appliance
Specifications
Table 2: General ES Touch Screen Display Specifications
Specification Rating
Resolution 800 x 600 Pixels (RGB)
Size / Type 8 inch (203 mm) Diagonal / Color Touch Screen
Touch Screen Technology Resistive
Event Display Up to 8 Events without scrolling
Normal Screen Custom Watermark File Format 680 x 484 Pixels: BMP, JPG, TIFF, GIF or PNG file format
Environmental Operating Temperature: 32°F to 120°F (0°C to 49°C)
Operating Humidity: Up to 93% RH, non-condensing at 90°F (32°C)
maximum
Miscellaneous accessories
Table 5: LED kits
Model Description
4010-9831 French Applique Kit for ES Touch Screen Display Panels, order separately as required for Canadian French
panels
4100-9843 8 Yellow LED Kit
4100-9844 8 Green LED Kit
4100-9845 8 Red LED Kit
4100-9855 8 Blue LED Kit
4100-0650 Battery shelf, required for 50 Ah batteries, in two-bay cabinets only
Note: LEDs are pluggable. Use LEDs to change color for local application requirements
Table 6: Factory Programming Tools
Model Description
4010-0831 Custom labels and programming, requires 4010-8810
4010-8810 Factory programming (select)
General specifications
Table 7: General specifications
Specification Rating
AC input current 120 VAC models 4 A maximum, 120 VAC at 60 Hz nominal
Including module currents and auxiliary power outputs; Output switches to
Power supply output ratings Total power supply output
8 A total for Special Application appliances; 4 A total for battery backup during
(nominal 28 VDC on AC, 24 rating
Regulated 24 DC power, see below for details mains AC failure or
VDC on battery backup)
Auxiliary power tap 2 A maximum, rated 19.1 VDC to 31.1 VDC brownout conditions
Special application
Simplex 4901, 4903, 4904, and 4906 series horns, strobes, and combination horn or strobes and speaker or
appliances, maximum of 70
strobes. Contact your Simplex product representative for compatible appliances.
appliances for each NAC
Regulated 24 DC appliances Power for other UL listed appliances; use associated external synchronization modules where required
See data sheet Batteries and Battery Cabinets; 110 Ah Sealed Lead-Acid Batteries and
Battery capacity range
Battery charger rating (sealed Compatible Battery Cabinet (without charger) (S2081-0012) for further details.
lead acid batteries) Charger characteristics and Temperature compensated, dual rate, recharges depleted batteries within 48 hours
performance per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Battery Current 9 A maximum at 24 VDC (during battery operation)
Operating temperature 32°F to 120°F (0°C to 49°C)
Environmental
Operating humidity Up to 93% RH, non-condensing at 90°F (32°C) maximum
Additional technical Installation instructions 4010ES Fire Alarm System Installation Guide ( 579-989)
reference Operating instructions 4010ES Fire Alarm Operator's Manual (579-969)
Note:
1. UL,ULC, and CSFM Listed.
2. For details on other dual vertical block network options refer to data sheets S4100-0029, S4100-0056, S4100-0057, ES Net Network Applications,
Communications, Options and Specifications (S4100-0076), and Building Network Interface Card (BNIC) (S4100-0061).
Note: Side view dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 in. stud construction with minimum
protrusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall must
be a minimum of 3 in. (76 mm) for both 4 in. and 6 in. stud construction.
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice.
Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex,
and the product names listed in this material are marks or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered
trademarks of the National Fire Protection Association (NFPA).
S4010-0004 Rev. 26 06/2022