Datasheet

4010ES Fire Control Units


UL, ULC, CSFM Listed; FM, NYC Fire 4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories
Dept Approved*

Features
Compatible with Simplex ES Net and 4120 fire alarm networks

Basic system features:

• Models available with Color ES Touch Screen Display or Monochrome 2


line x 40 Character Display
• Capacity for up to 1000 addressable IDNet points, up to 127 VESDA
Air Aspiration points, up to 2000 points of annunciation, and up to 20
internal and external card addresses
• CPU assembly includes dedicated compact flash memory for on-site
system information storage and convenient Ethernet service port
access
• 8 A power supply with up to 2 A of auxiliary power and battery charger
capacity for up to 110 Ah batteries (UL) or up to 50 Ah batteries
(ULC), 33 Ah max in single bay control cabinet 50 Ah maximum with
4100-0650 battery shelf in two-bay control cabinet
• Four onboard Class A or B, 3 A notification appliance circuits (NACs)
and one programmable auxiliary relay output rated for 2 A at 32 VDC
• IDNet addressable device communications that support TrueAlarm
analog sensors and IDNet communications monitoring and control
devices with an electrically isolated output channel allowing use with
either shielded or unshielded, twisted or untwisted single pair wiring;
and providing dual short circuit isolating output loops
• Remote annunciator module support with remote unit interface (RUI)
communications port, either Class B or Class A operation
Figure 1: 2-Bay 4010ES Fire Alarm Control
• 48 LED panel mount annunciation provides 40 red and 8 yellow Unit with 2x40 Monochrome LCD Display
pluggable LEDs (select models), optional LED kits are available for
custom LED configurations 4010ES Agency Listing*:
Optional Main System Supply 2 and door mounted modules, and • UL 864 - Control Units, System (UOJZ); Control Unit Accessories,
other options include the following: System, Fire Alarm (UOXX); Control Units, Releasing Device Service
(SYZV); Smoke Control System Equipment (UUKL)
• City Connect Module
• UL 1076 - Proprietary Alarm Units (APOU)
• Alarm relay module
• UL 1730 - Smoke Detector Monitors and Accessories (UULH)
• Battery brackets for seismic area protection
• UL 2017 - Emergency Alarm System Control Units, CO detection (FSZI);
Optional block space modules include the following: Process Equipment Management (QVAX)
• ULC-S527 - Control Units, System, Fire Alarm (UOJZ7); Control Unit
• Fire alarm network interface card (NIC) for ES Net or 4120 network
Accessories, System, Fire Alarm (UOXX7); Control Units, Releasing
• Peer-to-peer network communications, supports either Class B or Device Service (SYZV7)
Class X operation
• ULC-S559 - Central Station Fire Alarm System Units (DAYR7)
• Ethernet connectivity options include ES Net NIC , Building Network
• ULC/ORD-C1076 - Proprietary Burglar Alarm System Units (APOU7)
Interface card (BNIC), and BACpac Ethernet portal
• ULC/ORD-C100 - Smoke Control System Equipment, (UUKL7)
• Dual RS-232 Module for printer or third party interface
• VESDA Air Aspiration High Level Interface
• Serial DACT
• 8-Point Zone/Relay Module
• 4-Point Auxiliary Relay Module with Feedback
• 8 Zone IDC Modules Class A or Class B
• Four point Auxiliary Relay module
• Modem or TCP/IP Physical Bridge Network Modules, Class B or Class X
• Additional IDNet addressable channels
• Connected Services Gateway

*This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0369 for allowable
values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. NYC Fire Dept COA #6095. Additional listings may be
applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Introduction
4010ES series fire detection and control units provide leading edge installation, operator, and service features for customer applications in the mid-
range addressable fire alarm systems market. An onboard Ethernet port provides fast external system communications to expedite installation and
service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files.
Modular design: A variety of functional modules are available to meet specific system requirements. With these selections, you can configure control
units for either stand-alone or networked fire control operation.
InfoAlarm Command Center options provide convenient expanded display content. Refer to data sheet InfoAlarm Command Center for the 4010ES Fire
Alarm Control Unit S4010-0009 for more information.

Compatible with the following Simplex remotely located modules:

• 4098-9757 QuickConnect2 and legacy 4098-9757 QuickConnect TrueAlarm smoke sensors


• 4003EC Small Voice Control Units
• 4009 IDNet NAC Extenders (4009A)
• 4081 Series, 110 Ah Battery Chargers
• 4100-7400 Series Graphic Annunciators
• 4190 Series Fiber Modems and Physical Bridges
• 4606-9102 Remote LCD Annunciator and 4100-9400 Series Remote ES Touch Screen Displays, and 4100-9400 Series Remote InfoAlarm Command
Centers, and 4602 Series Status Command Units (SCU) and Remote Command Units (RCU) Annunciators

Mechanical description
• Mounting box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting
• Includes smooth box surfaces for precise local cutting of conduit entrance holes
• The hinged user interface panel easily opens for internal access
• NACs mount directly on power supply assemblies providing minimized wiring loss, compact size, and readily accessible terminations
• Modules are power-limited except where noted, such as relay modules
• Doors include tempered glass inserts; boxes and doors are available in platinum or red
• Box and door or retainer assemblies are included with basic control unit assemblies
• Cabinet assembly is rated NEMA 1 and IP 30
• Cabinet assembly design is seismic tested and is certified to IBC and CBC standards and to ASCE 7 categories A through F; requires battery brackets
as detailed on data sheet Battery Brackets for Seismic Activity Applications S2081-0019

Control unit hardware


The Master Controller and Main System Supply 2
Mount the Master Controller and Main System Supply 2 in the upper section of the 4010ES cabinet. See Figure 10 for more information.

4010ES Block Space Option Cards


Mount the 4010ES Block Space Option Cards to the left of the 4010ES Main System Supply 2. In two-bay cabinets, mount the block space option cards
below the 4010ES ESS.

Other 4010ES options


Mount the 4010ES City Connect module or the optional Alarm Relay module directly to the Main System Supply 2. These options are mutually
exclusive.
The battery compartment located in the bottom of the 4010ES cabinet accepts two batteries without interfering with expansion module space.

Software feature summary


• TrueAlarm individual analog sensing with front panel information and selection access
• Dirty TrueAlarm sensor maintenance alerts, service and status reports including almost dirty
• TrueAlarm magnet test indication appears as a distinct test abnormal message on display when in test mode
• TrueAlarm sensor peak value performance report
• Install Mode allows grouping of multiple troubles for uninstalled modules and devices into a single trouble condition
• Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring
• Recurring Trouble Filtering allows the control unit to recognize, process, and log recurring intermittent troubles such as external wiring ground faults,
but only sends a single outbound system trouble to avoid nuisance communications
• WALKTEST silent or audible system test performs an automatic self-resetting test cycle

Compatible peripheral devices


The 4010ES is compatible with an extensive list of remote peripheral devices including printers and both conventional and addressable devices
including TrueAlarm analog sensors.

Page 2 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Addressable device control


The 4010ES provides standard addressable device communications for IDNet compatible devices. Using a two-wire communications circuit, individual
devices such as manual fire alarm stations, TrueAlarm sensors, conventional IDC zones, and sprinkler waterflow switches interface to the addressable
controller to communicate their identity and status.
Addressability allows the location and condition of the connected device to display on the operator interface LCD and on remote system annunciators.
Additionally, control circuits such as fans or dampers may be individually controlled and monitored with addressable devices.

Addressable operation
Each addressable device on the communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm,
supervisory, or trouble. Both Class B and Class A pathway operation is available. Sophisticated poll and response communication techniques ensure
supervision integrity and allow you to T-tap the circuit for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications
poll, and you can change them to steady from the control unit.
IDNet addressable channel capacity
The Main System Supply 2 provides an electrically isolated IDNet2 signaling line circuit (SLC) that supports up to 250 addressable monitor and control
points intermixed on the same pair of wires. Additional 250 address IDNet 2+2 Modules with four short circuit isolating output loops are available.
IDNet 2+2 Module SLCs are isolated from other system reference voltages to reduce common mode noise interaction with adjacent system wiring.
Table 1: IDNet 2 and IDNet 2+2 SLC wiring specifications
Specification Rating
Maximum distance from control unit for each 0 to 125 4000 ft (1219 m); 50 ohms
device load 126 to 250 2500 ft (762 m); 35 ohms
Total wire length allowed with T-taps for Class B wiring Up to 12,500 ft (3.8 km); 0.60 µF
Maximum capacitance between IDNet channels 1 µF
Wire type and connections Shielded or unshielded, twisted or untwisted wire. See note.
2 2
Connections Terminals for 18 AWG to 12 AWG (0.82 mm to 3.31 mm )
Installation instructions 579-989
Compatibility includes: IDNet communicating devices and TrueAlarm sensors including QuickConnect2 sensors. See data sheet S4090-0011 for
additional reference.
Note: Some applications may require shielded wiring. Review your system with your local Simplex product supplier.

TrueAlarm system operation


Addressable device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based
on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor.
To determine status, compare the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters
out environmental factors that cause shifts in sensitivity.

Programmable sensitivity
You can select the programmable sensitivity of each sensor at the control unit for different levels of smoke obscuration, shown directly in percent, or
for specific heat detection levels. To evaluate whether to revise the sensitivity, read the peak value, which is stored in memory, and compare the value
to the alarm threshold directly in percent.

CO sensor bases
CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one
system address. You can enable or disable the CO sensor for use in LED or Switch modes and custom control, and you can make the CO sensor public
for communication across a fire alarm network. Refer to data sheet TrueAlarm CO Sensor Bases for Smoke, Heat, and Photo/Heat Sensors using IDNet
Communications S4098-0052 for details.

TrueAlarm heat sensors


You can select TrueAlarm heat sensors for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also
available, typically to provide freeze warnings or alert to HVAC system problems. Readings are selectable as either Fahrenheit or Celsius.

TrueSense early fire detection


The Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4010ES IDNet address. The control unit evaluates smoke
activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet TrueAlarm
Multi-Sensor Model A4098-9754 Providing TrueSense Early Fire Detection (S4098-0024).

Page 3 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Diagnostics and default device type


Sensor status
TrueAlarm operation allows the control unit to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72
requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each
sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at one year, six months,
and when end of life is reached.

Modular TrueAlarm sensors


Modular TrueAlarm sensors use the same base and either smoke or heat sensor types. You can easily interchange the sensors to meet specific
location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of
covering smoke sensors and causing them to be disabled, you can install heat sensors without reprogramming the control unit. The control unit will
indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that
location.

Master Controller (CPU)


• The 4010ES Master Controller includes dedicated compact flash Mass Storage memory for on-site system information storage and convenient
Ethernet service port access
• For quick and easy download of site-specific programming and firmware enhancements, the Ethernet port is conveniently accessed from the front
panel. You can make firmware enhancements through software downloads to the onboard flash memory.
• Every downloaded job is automatically stored to compact flash without overwriting earlier versions providing a means for recovering previous
configurations
• Downtime is reduced because the system stays running during download
• You can upload and download modifications for greater service flexibility
• You can store job specific files in the control unit such as test and inspection reports, record drawings, specifications, and more using mass storage.
• RUI communications port supports either Class B or Class A operation for remote annunciation equipment

Basic control unit description


4010ES control units include the following features:
• An Operator Interface, Master Controller with Compact Flash, IDNet addressable device SLCs with short circuit isolating loops configurable for Class B
or Class A operation
• 8 A power supply with up to 2 A of auxiliary power, 110 Ah (UL) or 50 Ah (ULC) battery charger (33 Ah max in one bay cabinet, 50 Ah max with
4100-0650 battery shelf in two bay control cabinet); four Class A or Class B NACs rated at 3 A each for Special Application Appliances, selectable for
synchronized strobe, or SmartSync horn or strobe operation over two wires; and 2 A for regulated 24 DC operation; one programmable auxiliary
relay rated for 2 A at 32 VDC
• One RUI Class B or Class A communications port for remote annunciation devices, cabinet and door
• Support for up to 20 internal and external card addresses. Other standard options may be provided depending on model; see and for additional
details on specific models.

8-point zone / relay module details:

• Select as IDC or Relay. Configure up to eight Class B IDCs, or up to four Class A IDCs; or up to eight Relay outputs rated 2 A resistive at 30 VDC (N.O.
or N.C.); or a combinations of IDCs and Relays; each zone is separately configurable as an IDC or Relay output.
• IDC Support. Each IDC supports up to 30, 2-wire devices. Zone relay modules may be powered directly from the control unit power supply or through
the optional 25 VDC regulator module where required for 2-wire detector compatibility. Refer to 2-Wire Detector Compatibility Chart (579-832) for
additional details.
• You can select the following IDC EOL resistor values as: 3.3 kohms, 2 kohms, 2.2 kohms, 3.4 kohms, 3.9 kohms, 4.7 kohms, 5.1 kohms, 5.6 kohms,
6.34/6.8 kohms, and 3.6 kohms + 1.1 kohms. Refer to Zone/Relay Module Installation Instructions (579-1236) for more details.

Main System Supply 2


The Main System Supply 2 provides the power source and the input or output connections for the basic 4010ES control unit. The main features are
listed in Basic control unit description.

Page 4 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Color ES Touch Screen Display


The Color ES Touch Screen Display interface offers intuitive operation similar to a tablet or smart phone. With a larger area format compared to an
individual text line display, more information is available at a glance, and minimal key presses are needed to access detailed information.

Figure 2: ES Touch Screen Display Operator Interface

Features
The ES Touch Screen Displays provide customized operating experience with the following features

• Event activity display choices include: First 8 Events; or First 7 Events with emphasis on Most Recent; or First 6 Events with emphasis on First and
Most Recent, individually selectable for each event type
• System reports are easily viewable; you can read logs with minimal scrolling
• Up to two languages are available for each system, easily selected by programmable key press
• You can vector information sent to Remote ES Touch Screen Displays by point or zone
• Both Hard and Soft keys are available for critical functions: Event Acknowledge, Alarm Silence, and Reset Functions
• Resistive touchscreen technology allows operation with or without gloves
• Seven programmable RGY LEDs are available for user-defined display status, up to 2 status conditions for each LED
• Seven programmable Soft keys are available for user-defined control or maintenance functions
• PRI2 Soft key label which you change to CO to annunciate Carbon Monoxide detection status
• ES Touch Screen Display which you can program to report individual points or groups of points as a single zone
• Supports ability to display a custom watermark background file of a company logo or other desired display content
• Seismically compliant under the State of California Statewide Office of Housing and Development (OSHPD) Special Seismic Certification (SSC) program
guidelines. Refer to Simplex Seismic Application Guide (579-1213) and Battery Brackets for Seismic Activity Applications (S2081-0019) for details.

Page 5 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Display properties
• 8 inch (203 mm) diagonal, 800 x 600 resolution color touch screen display capable of annunciating up to 8 active events without scrolling
• Bright white LED backlighting provides efficient and long lasting illumination. The backlight is dim in a quiescent state and automatically switches to
full power on touch or on event activity in system.

Description
ES Touch Screen Displays for 4010ES fire alarm systems provide a large display with extended information content, dual language support including
UTF-8 character languages, and an intuitive control key interface with the following features:
• Each 4010ES control panel supports up to 8 ES Touch Screen Displays, one main and seven remote. It can enable one ES Touch Screen Display to
take-control and to designate access levels for interfaces not in-control. You can assign programmable LEDs to, in-control status indications.
• Menu-driven format conveniently prompts operators for the next action required
• Direct point callup displays individual points alphabetically and then homes in on the logical choice as more point information is entered
• Event categories are color coded for quick visual representation; Red for Alarm and Priority 2 Events; Yellow for Supervisory and Trouble events
• Date formats are either MM/DD/YY or DD/MM/YY
• Time formats are either 24 hour or 12 hour with AM/PM
• System Normal screen supports a color background (watermark) for company name, company logo, or other desired display content

Page 6 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Example display screens

Figure 4: Main Menu


Figure 3: First and Most Recent Alarm Display

Figure 5: First Eight Active Trouble Events List Figure 6: Direct Point Callup

Figure 7: Alarm History Log Figure 8: Detailed Point Status Screen for TrueAlert ES Appliance

Page 7 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Specifications
Table 2: General ES Touch Screen Display Specifications
Specification Rating
Resolution 800 x 600 Pixels (RGB)
Size / Type 8 inch (203 mm) Diagonal / Color Touch Screen
Touch Screen Technology Resistive
Event Display Up to 8 Events without scrolling
Normal Screen Custom Watermark File Format 680 x 484 Pixels: BMP, JPG, TIFF, GIF or PNG file format
Environmental Operating Temperature: 32°F to 120°F (0°C to 49°C)
Operating Humidity: Up to 93% RH, non-condensing at 90°F (32°C)
maximum

Operator Interface with Monochrome 2 x 40 LCD


• Provides convenient and extensive operator information using a logical, menu-driven display
• Multiple automatic and manual diagnostics for maintenance reduction
• Alarm and Trouble History Logs of up to 1250 entries for each, 2500 total events, are available for viewing on the LCD screen, printing on a connected
printer, or downloading to a service computer
• Convenient PC programmer label editing
• Password access control

Figure 9: Operator interface features

Page 8 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Basic control unit model selection, one-bay units


Supervisory and alarm current specifications are for determining battery standby requirements. Current specifications include an active RUI channel.
Models with an IDNet channel include 20 IDNet device LEDs activated in alarm. Actual IDNet device current is not included. For models with 48 LED
annunciation, alarm also includes 24 LEDs activated.
Table 3: Basic Control Unit Model Selection - 1 Bay Units
Language and Supv. Alarm Available
Model Panel color Listings Features
voltage current current option blocks
4010-9401 Basic control unit with 2x40
Red
4010-9401BA LCD Operator Interface and
UL, one two-loop isolated IDNet2
English 120 VAC CSFM, FM, Communications Channel, Class A 316 mA 430 mA
4010-9402
Platinum NYC Fire Dept or Class B operation, with support
4010-9402BA for up to 250 addressable analog Three 4 in. x 5 in.
devices blocks
4010-9403 Red UL, ULC,
English 120 VAC CSFM, FM,
4010-9404 Platinum Same features as above with 48 LED
NYC Fire Dept 336 mA 495 mA
annunciation
4010-9405 Red
French 120 VAC ULC, CSFM FM
4010-9406 Platinum
Note: Model numbers ending in BA are assembled in the USA.

Basic control unit model selection, two-bay units


Supervisory and alarm current specifications are for determining battery standby requirements. Current specifications include an active RUI channel.
Models with IDNet channels include 20 IDNet device LEDs activated in alarm for each channel. Actual IDNet current is not included. See Addressable
device load specifications for battery standby for details.
Table 4: Basic Control Unit Model Selection - 2 Bay Units
Language & Available Supv. Alarm
Model Panel Color Listings Features
Voltage Option Blocks Current Current
4010-9421 Basic control unit with 2x40
Red English 120 VAC
4010-9421BA Operator Interface, one two-loop
isolated IDNet2 Communications
Channel and one four-loop
UL, FM 391 mA 545 mA
4010-9422 Isolated IDNet 2+2 Communications
Platinum English 120 VAC
4010-9422BA Channel Module, Class A or Class B
operation, with support for up to 500
addressable IDNet points
Same features as above with 48 LED
4010-9423 Red English 120 VAC
annunciation
Same features as above with 48 LED 10 4 in. x 5 in.
4010-9428 Platinum English 120 VAC UL, ULC, FM 411 mA 610 mA
annunciation blocks
Same features as above with 48 LED
4010-9430 Platinum French 120 VAC
annunciation
Basic control unit with ES Touch
120 VAC.
Screen Operator Interface and
Multiple
one two-loop Isolated IDNet2
languages
Communications Channel, one
are available, UL/ULC,
4010-9435 Red four-loop Isolated IDNet 2+2 486 mA 661 mA
contact your CSFM
Communications Channel Module,
local Simplex
Class A or Class B operation, with
product supplier
support for up to 500 addressable
for details.
IDNet points
Note: Model numbers ending in BA are assembled in the USA.

Page 9 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Miscellaneous accessories
Table 5: LED kits
Model Description
4010-9831 French Applique Kit for ES Touch Screen Display Panels, order separately as required for Canadian French
panels
4100-9843 8 Yellow LED Kit
4100-9844 8 Green LED Kit
4100-9845 8 Red LED Kit
4100-9855 8 Blue LED Kit
4100-0650 Battery shelf, required for 50 Ah batteries, in two-bay cabinets only

Note: LEDs are pluggable. Use LEDs to change color for local application requirements
Table 6: Factory Programming Tools
Model Description
4010-0831 Custom labels and programming, requires 4010-8810
4010-8810 Factory programming (select)

General specifications
Table 7: General specifications
Specification Rating
AC input current 120 VAC models 4 A maximum, 120 VAC at 60 Hz nominal
Including module currents and auxiliary power outputs; Output switches to
Power supply output ratings Total power supply output
8 A total for Special Application appliances; 4 A total for battery backup during
(nominal 28 VDC on AC, 24 rating
Regulated 24 DC power, see below for details mains AC failure or
VDC on battery backup)
Auxiliary power tap 2 A maximum, rated 19.1 VDC to 31.1 VDC brownout conditions
Special application
Simplex 4901, 4903, 4904, and 4906 series horns, strobes, and combination horn or strobes and speaker or
appliances, maximum of 70
strobes. Contact your Simplex product representative for compatible appliances.
appliances for each NAC
Regulated 24 DC appliances Power for other UL listed appliances; use associated external synchronization modules where required
See data sheet Batteries and Battery Cabinets; 110 Ah Sealed Lead-Acid Batteries and
Battery capacity range
Battery charger rating (sealed Compatible Battery Cabinet (without charger) (S2081-0012) for further details.
lead acid batteries) Charger characteristics and Temperature compensated, dual rate, recharges depleted batteries within 48 hours
performance per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Battery Current 9 A maximum at 24 VDC (during battery operation)
Operating temperature 32°F to 120°F (0°C to 49°C)
Environmental
Operating humidity Up to 93% RH, non-condensing at 90°F (32°C) maximum
Additional technical Installation instructions 4010ES Fire Alarm System Installation Guide ( 579-989)
reference Operating instructions 4010ES Fire Alarm Operator's Manual (579-969)

Addressable device load specifications for battery standby


Table 8: Addressable device load specifications for battery standby
Addressable channel Load Supervisory current Alarm current
IDNet2 and IDNet 2+2 Channel Device With 250 devices add 200 mA 250 mA
Currents. 20 device LEDs in alarm are included With 125 devices add 100 mA 125 mA
with control unit and module currents With 50 devices add 40 mA 50 mA
Table 9: Current draw for each IDNet device
Condition Current
Standby 0.8 mA
Alarm, with LED off 1.0 mA
Alarm, with LED on 3.0 mA
Note: A maximum of 20 devices with LED on is supported for each channel. Additional device LEDs do not turn on.

Page 10 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Block space option card selection


Note: Maximum block option module quantities may require 2 bay cabinets, 1 bay cabinets are limited to 3 option block spaces total. See Figure 10
for option module space availability. Supervisory and alarm current specifications for determining battery standby requirement consider no load on
addressable channels except as noted, see Addressable device load specifications for battery standby.
Table 10: Single block option modules
Supervisory Alarm Option block
Model Features
current current usage
4010-2504 Connected Services Gateway with IP communicator 125 mA 125 mA 1 block
Serial DACT 1 block
4010-9912 30 mA 40 mA (must mount in
Note: Must mount in Block D under Main System Supply 2 top bay, block D)
1 block
4010-9908 4-Point Aux Relay Module 15 mA 60 mA
(3 max)
Voltage Regulator Module, 22.8 VDC to 26.4 VDC (25 VDC nominal); isolated
4.9 A
and resettable output; includes earth detection circuit and trouble relay for 3 A maximum with 1 block
4010-9916 maximum
status monitoring. One 4010-6305 harness (see below) is required for each 2.5 A load (1 max)
with 4 A load
4010-9935 or 4010-9936 module powered from the 4010-9916.
1 block
4010-9918 Dual RS-232 Module 60 mA 60 mA
(3 max)
BACpac Ethernet Portal Module; requires 4010-9918 RS-232 Module (no 1 block
4010-9915 123 mA 123 mA
address required) (3 max)
1 block
4010-9901 VESDA HLI 60 mA 60 mA
(1 max)
8-point z1/relay 4 in. x 5 in. flat module. Supports eight Class B or four Class
A IDCs. Mounts in any open block in a master controller or expansion bay.
Alarm current shown is for eight Class B IDCs using 3.3 K end-of-line-resistors One block (11
4010-9935 83 mA 295 mA
with four IDCs in alarm and four IDCs in standby. Standby current shown is maximum)
for all eight IDCs in standby. Detector current is added separately. Refer to
Z1/Relay Module Installation Instructions 579-1236 for more information.
4010-9936 4 DPDT Relays with feedback, 2A 18 mA 65 mA 1 Block (11
maximum)
25 V regulator harness for 8 point z1/relay module. 1 required for each
8 point z1/relay module to be powered by the 4010-9916 25 V regulator
4010-6305 N/A N/A N/A
module. A maximum quantity of five 8 point z1/relay modules can be
powered from the 4010-9916 25 V regulator module.
IDNet 2+2 Module, 250 point capacity; electrically isolated No device 50 mA 60 mA
output with four short circuit isolating Class B or Class 50 devices 90 mA 150 mA 1 block
4010-9929 A output loops; alarm currents for 50 and above devices 125 devices 150 mA 225 mA (3 max)
includes 20 device LEDs in alarm; see control unit model
selection for individual device currents 250 devices 250 mA 350 mA

Table 11: Dual vertical block (flat) modules, see note 2


Model Features Option block usage Supervisory Alarm current
current
4010-9928 For 1 bay control units only: Dual Vertical Block Two vertical blocks (mounts in top bay, N/A N/A
Card Mounting Kit, allows selecting two, dual block space A and B only)
Vertical Block (flat) modules from the list below;
mounts at right angle to chassis (note the block
usage details)
4010-9923 See note SafeLINC Internet Interface 2 Vertical Blocks 115 mA 115 mA
1.

Note:
1. UL,ULC, and CSFM Listed.
2. For details on other dual vertical block network options refer to data sheets S4100-0029, S4100-0056, S4100-0057, ES Net Network Applications,
Communications, Options and Specifications (S4100-0076), and Building Network Interface Card (BNIC) (S4100-0061).

Page 11 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Additional control unit feature selection - block space is not used


Table 12: Additional control unit feature selection - block space is not used
Model Features Supervisory current Alarm current Mounting requirements
4010-9909 City Connect Module w/ 20 mA 36 mA Mounts on Main System
disconnect switches Supply (1 max)
4010-9910 City Connect Module 20 mA 36 mA
4010-9911 Alarm Relay Module 15 mA 37 mA
4100-5128 Battery Distribution Terminal Block, mounts to side of box. Required when battery connection leaves the 4010ES box.
Also used in the 4100ES fire alarm control unit.
Refer to data sheet TrueInsight Remote Service Overview and Hardware Reference (S4100-0063) and contact your local Simplex product representative
for more details.

Network interface and network media card product selection


4010ES fire alarm control units are compatible with Simplex ES Net network or 4120 network fire alarm products.
• Refer to datasheet ES Net Network Applications, Communications, Options and Specifications (S4100-0076) for additional information on compatible
ES Net fire alarm products.
• Refer to datasheet 4120 Network Applications, Communications, Options and Specifications (S4100-0056) for additional information on compatible
4120 network fire alarm products.
• Refer to datasheet Building Network Interface Card (BNIC) Models 4100-6047 and 4010-9914 (S4100-0061) for additional information on the BNIC.
• Refer to datasheet Connected Services Gateway - Central Station Communication and SafeLINC Cloud Services (S2080-0091) for additional information
on the Connected Services Gateway.

Additional 4010ES and network product reference data sheets


Table 13: Additional 4010ES and network product reference data sheets
Title Doc. number
Serial DACT (SDACT) for 4100ES, 4010ES, 4007ES S2080-0009
Connected Services Gateway - Central Station Communication and SafeLINC Cloud S2080-0091
Services
Seismic Battery Brackets Reference S2081-0019
4003EC Voice Control Unit S4003-0002
4009 IDNet NAC Extender S4009-0002
4009 IDNAC Repeater S4009-0004
4010ES Extinguishing Release Applications S4010-0005
4010ES Panels with Conventional Notification (INTL) S4010-0006
4010ES Extinguishing Release Applications (INTL) S4010-0007
InfoAlarm Command Center for the 4010ES Panels S4010-0008
InfoAlarm Command Center for the 4010ES Panels (INTL) S4010-0009
4010ES Panels with Addressable Notification S4010-0011
4010ES Panels with Addressable Notification (INTL) S4010-0012
External 110 Ah Battery Charger for 4100ES, 4010ES S4081-0002
Graphic I/O Modules for 4100ES, 4010ES, 4007ES S4100-0005
Interface to VESDA Air Aspiration Detection Systems S4100-0026
NDU with SPS Power Supplies for 4120 Network S4100-0036
InfoAlarm Command Center with SPS Power Supplies S4100-0045
Multiple Signal Fiber Optic Modems for 4120 Networks S4100-0049
BACpac Ethernet Module S4100-0051
4120 Network Products and Specifications S4100-0056
Building Network Interface Card (BNIC) S4100-0061
SafeLINC Internet Interface S4100-0062
ES Net Network Products and Specifications S4100-0076
NDU with EPS Power Supplies for 4120 Network S4100-0102
NDU with EPS Power Supplies for ES Net S4100-0104
NDU with ES-PS Power Supplies for 4120 Network S4100-1036
Remote ES Touch Screen Displays for 4100ES and 4010ES Panels S4100-1070
NDU with ES-PS Power Supplies for ES Net S4100-1077
TrueSite Workstation S4190-0016
TrueSite Incident Commander S4190-0020
24-Pin Dot Matrix Fire Alarm System Remote Printer S4190-0027
SCU/RCU Annunciators S4602-0001
4606-9102 Remote LCD Annunciator S4606-0002

Page 12 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

4010ES card address allocation


The 4010ES has a maximum internal and external card address limit of 20 card addresses. Use Table 14 to calculate 4010ES card address allocation.
1. For the applicable control unit, write in the Card Address Consumption value in the Card Address Allocation column. Select one control unit only.
2. For the option cards to be installed on the 4010ES, write in the Card Address Consumption value in the Card Address Allocation column.
3. Add together the numbers in the Card Address Allocation column. The total must not exceed 20.
Table 14: 4010ES card address allocation
Card Address Card Address
Model Description
Consumption Allocation
Control units (select one)
4010-9401
4010-9401BA
4010-9402
2x40 display, (1) IDNet 2 Communications Channel, 1-Bay box 2
4010-9402BA
4010-9405
4010-9406
4010-9403 2x40 Display, (1) IDNet 2 Communications Channel, 48 Pluggable LED Module, 1-Bay
3
4010-9404 Box
4010-9421
4010-9421BA 2x40 Display, (1) IDNet 2 Communications Channels and one IDNet 2+2
3
4010-9422 Communications Channel, 2-Bay box
4010-9422BA
4010-9423
2x40 Display, (1) IDNet2 Communications Channels and (1) IDNet 2+2 Communications
4010-9428 4
Channel, 48 Pluggable LED Module, 2-Bay Box
4010-9430
4010-9425
4010-9425BA InfoAlarm display, one IDNet+ Communications Channel and one IDNet 2+2
4
4010-9426 Communications Channel, 2-Bay box
4010-9426BA
ES Color Touch Screen Display, (1) IDNet 2 Communications Channel and (1) IDNet 2+2
4010-9435 4
Communications Channel, 2-Bay Box
Control unit option cards (select as required)
4010-2504 Connected Services Gateway with IP communicator 1
4010-9901 Flat VESDA HLI Card 1
4010-9922 Flat 4120 Network Card 1
4010-6310 Flat ES Net Network Interface Card 1
4010-9908 4 Point Flat Aux Relay Module 1
4010-9912 Serial DACT 1
4010-9923 SafeLINC Internet Interface Card 1
4010-9914 Building Network Interface Card 1
4010-9918 Dual RS-232 Module 1
4010-9935 8 point zone/relay 4 in. x 5 in. flat module 1
4010-9929 IDNet 2+2 Communications Module 1
4010-9936 4-Point Auxiliary Relay Module with Feedback 1
Remote Annunciation (Select As Required)
4100-9401 Red Cabinet, English 2
4100-9403 Platinum Cabinet, English 2
Remote
4100-9421 InfoAlarm Red Cabinet, French 2
4100-9423 Command Platinum Cabinet, French 2
Center
4100-9441 Red Cabinet, with blank inserts for key labels 2
4100-9443 Platinum Cabinet, with blank inserts for key labels 2
4100-9404 Remote Red Cabinet 1
ES Touch
4100-9405 Screen Platinum Cabinet 1
Display
4606-9102 4010ES RUI LCD Annunciator, English 1
4606-9102BA 4010ES RUI LCD Annunciator, English 1

Page 13 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Table 14: 4010ES card address allocation


Card Address Card Address
Model Description
Consumption Allocation
4606-9102CF 4010ES RUI LCD Annunciator, French 1
4602-9101 Status Command Unit (SCU) LED Annunciator 1
4602-9102 Remote Command Unit (RCU) LED Annunciator w/control 1
4602-9150 Graphic I/O RCU/SCU Assembly for custom annunciator 1
4602-7101 Graphic I/O RCU/SCU Assembly for custom annunciator 1
4602-7001 RCU for cabinet mount 1
4602-6001 SCU for cabinet mount 1
4100-7401 24 Point I/O Graphic Module (requires mounting cabinet) 1
4100-7402 64/64 LED Switch Controller for custom annunciator 1
4100-7403 32 Point LED Driver Module for custom annunciator 1
4100-7404 32 Point Switch Input Module for custom annunciator 1
Total Card Addresses (not to exceed 20) TOTAL

Note: Products ending with BA are assembled in the USA.

One-bay and two-bay cabinet loading reference

Figure 10: Loading reference

Note: Some spaces may be used by basic control unit features.

Page 14 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

Cabinet dimension reference

Figure 11: Cabinet dimension reference

Note: Side view dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 in. stud construction with minimum
protrusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall must
be a minimum of 3 in. (76 mm) for both 4 in. and 6 in. stud construction.

Page 15 S4010-0004 Rev. 26 06/2022


4010ES Basic Addressable Fire Detection and Control Unit Modules and Accessories

© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice.
Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex,
and the product names listed in this material are marks or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered
trademarks of the National Fire Protection Association (NFPA).
S4010-0004 Rev. 26 06/2022