0% found this document useful (0 votes)
110 views

Parameter

This document provides instructions for quickly commissioning a SINAMICS V20 converter via its built-in BOP (Basic Operator Panel). It describes three methods for setting fixed speeds using digital inputs: 1) three fixed speeds with ON/OFF commands, 2) up to 16 fixed speeds selected via binary inputs, and 3) two fixed speeds that can be summed if two inputs are active together. Connection macro settings are provided for each method. The document also notes that the analog input can serve as an additional setpoint and describes using digital inputs for pulse commands to control motor operation via a MOP (Motorized Potentiometer).

Uploaded by

PhúcMập
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views

Parameter

This document provides instructions for quickly commissioning a SINAMICS V20 converter via its built-in BOP (Basic Operator Panel). It describes three methods for setting fixed speeds using digital inputs: 1) three fixed speeds with ON/OFF commands, 2) up to 16 fixed speeds selected via binary inputs, and 3) two fixed speeds that can be summed if two inputs are active together. Connection macro settings are provided for each method. The document also notes that the analog input can serve as an additional setpoint and describes using digital inputs for pulse commands to control motor operation via a MOP (Motorized Potentiometer).

Uploaded by

PhúcMập
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 166

Commissioning via the built-in BOP

5.5 Quick commissioning

Three fixed speeds with ON/OFF1


If more than one fixed frequency is selected at the same time, the selected frequencies are
summed, that is, FF1 + FF2 + FF3.

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminal as command source


P1000[0] Selection of frequency 1 3 Fixed frequency
P0701[0] Function of digital input 1 0 1 ON/OFF
P0702[0] Function of digital input 2 0 15 Fixed speed bit 0
P0703[0] Function of digital input 3 9 16 Fixed speed bit 1
P0704[0] Function of digital input 4 15 17 Fixed speed bit 2
P1016[0] Fixed frequency mode 1 1 Direct selection mode
P1020[0] BI: Fixed frequency selection bit 0 722.3 722.1 DI2
P1021[0] BI: Fixed frequency selection bit 1 722.4 722.2 DI3
P1022[0] BI: Fixed frequency selection bit 2 722.5 722.3 DI4
P1001[0] Fixed frequency 1 10 10 Speed low
P1002[0] Fixed frequency 2 15 15 Speed middle
P1003[0] Fixed frequency 3 25 25 Speed high
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 73
Commissioning via the built-in BOP
5.5 Quick commissioning

Fixed speeds with ON command in binary mode


Up to 16 different fixed frequency values (0 Hz, P1001 to P1015) can be selected by the
fixed frequency selectors (P1020 to P1023). For more information about the fixed
frequencies in binary mode, see the parameter descriptions of P1001 to P1016 in Section
"Parameter list (Page 202)".

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminals as command source


P1000[0] Selection of frequency 1 3 Fixed frequency
P0701[0] Function of digital input 1 0 15 Fixed speed bit 0
P0702[0] Function of digital input 2 0 16 Fixed speed bit 1
P0703[0] Function of digital input 3 9 17 Fixed speed bit 2
P0704[0] Function of digital input 4 15 18 Fixed speed bit 3
P1001[0] Fixed frequency 1 10 10 Fixed speed 1
P1002[0] Fixed frequency 2 15 15 Fixed speed 2
P1003[0] Fixed frequency 3 25 25 Fixed speed 3
P1004[0] Fixed frequency 4 50 50 Fixed speed 4
P1016[0] Fixed frequency mode 1 2 Binary mode
P0840[0] BI: ON/OFF1 19.0 1025.0 Converter starts at the fixed
speed selected
P1020[0] BI: Fixed frequency selection bit 0 722.3 722.0 DI1
P1021[0] BI: Fixed frequency selection bit 1 722.4 722.1 DI2
P1022[0] BI: Fixed frequency selection bit 2 722.5 722.2 DI3
P1023[0] BI: Fixed frequency selection bit 3 722.6 722.3 DI4
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active

SINAMICS V20 Converter


74 Operating Instructions, 05/2020, A5E34559884-013
Commissioning via the built-in BOP
5.5 Quick commissioning

The analog input works as an additional setpoint.


If digital input 2 and digital input 3 are active together, the selected frequencies are summed,
that is, FF1 + FF2.

When the fixed speed is selected, the additional setpoint channel from the analog is
disabled. If there is no fixed speed setpoint, the setpoint channel connects to the analog
input.

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminals as command source


P1000[0] Selection of frequency 1 23 Fixed frequency + analog setpoint 1
P0701[0] Function of digital input 1 0 1 ON/OFF
P0702[0] Function of digital input 2 0 15 Fixed speed bit 0
P0703[0] Function of digital input 3 9 16 Fixed speed bit 1
P0704[0] Function of digital input 4 15 9 Fault acknowledgement
P1016[0] Fixed frequency mode 1 1 Direct selection mode
P1020[0] BI: Fixed frequency selection bit 0 722.3 722.1 DI2

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 75
Commissioning via the built-in BOP
5.5 Quick commissioning

P1021[0] BI: Fixed frequency selection bit 1 722.4 722.2 DI3


P1001[0] Fixed frequency 1 10 10 Fixed speed 1
P1002[0] Fixed frequency 2 15 15 Fixed speed 2
P1074[0] BI: Disable additional setpoint 0 1025.0 FF disables the additional setpoint
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active

Note that the command sources are pulse signals.

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminals as command source


P1000[0] Selection of frequency 1 1 MOP as setpoint
P0701[0] Function of digital input 1 0 2 OFF1/hold
P0702[0] Function of digital input 2 0 1 ON pulse
P0703[0] Function of digital input 3 9 13 MOP up pulse
P0704[0] Function of digital input 4 15 14 MOP down pulse
P0727[0] Selection of 2/3-wire method 0 3 3-wire
ON pulse + OFF1/hold + Reverse
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active
P1040[0] Setpoint of the MOP 5 0 Initial frequency
P1047[0] MOP ramp-up time of the RFG 10 10 Ramp-up time from zero to maxi-
mum frequency
P1048[0] MOP ramp-down time of the RFG 10 10 Ramp-down time from maximum
frequency to zero

SINAMICS V20 Converter


76 Operating Instructions, 05/2020, A5E34559884-013
Commissioning via the built-in BOP
5.5 Quick commissioning

Note that the command sources are pulse signals.

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminals as command source


P1000[0] Selection of frequency 1 2 Analog setpoint 1
P0701[0] Function of digital input 1 0 1 OFF hold
P0702[0] Function of digital input 2 0 2 Forward pulse + ON
P0703[0] Function of digital input 3 9 12 Reverse pulse + ON
P0704[0] Function of digital input 4 15 9 Fault acknowledgement
P0727[0] Selection of 2/3-wire method 0 2 3-wire
STOP + Forward pulse + Reverse
pulse
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 77
Commissioning via the built-in BOP
5.5 Quick commissioning

If a negative setpoint for the PID control is desired, change the setpoint and feedback wiring
as needed.
When you switch to Hand mode from PID control mode, P2200 becomes 0 to disable the
PID control. When you switch it back to Auto mode, P2200 becomes 1 to enable the PID
control again.

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminals as command source


P0701[0] Function of digital input 1 0 1 ON/OFF
P0703[0] Function of digital input 3 9 9 Fault acknowledgement
P2200[0] BI: Enable PID controller 0 1 Enable PID
P2253[0] CI: PID setpoint 0 755.0 PID setpoint = AI1
P2264[0] CI: PID feedback 755.0 755.1 PID feedback = AI2
P0756[1] Type of analog input 0 2 AI2, 0 mA to 20 mA
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active

SINAMICS V20 Converter


78 Operating Instructions, 05/2020, A5E34559884-013
Commissioning via the built-in BOP
5.5 Quick commissioning

Connection macro settings:

P0700[0] Selection of command source 1 2 Terminals as command source


P0701[0] Function of digital input 1 0 1 ON/OFF
P0702[0] Function of digital input 2 0 15 DI2 = PID fixed value 1
P0703[0] Function of digital input 3 9 16 DI3 = PID fixed value 2
P0704[0] Function of digital input 4 15 17 DI4 = PID fixed value 3
P2200[0] BI: Enable PID controller 0 1 Enable PID
P2201[0] Fixed PID setpoint 1 [%] 10 10 -
P2202[0] Fixed PID setpoint 2 [%] 20 20 -
P2203[0] Fixed PID setpoint 3 [%] 50 50 -
P2216[0] Fixed PID setpoint mode 1 1 Direct selection
P2220[0] BI: Fixed PID setpoint select bit 0 722.3 722.1 BICO connection DI2
P2221[0] BI: Fixed PID setpoint select bit 1 722.4 722.2 BICO connection DI3
P2222[0] BI: Fixed PID setpoint select bit 2 722.5 722.3 BICO connection DI4
P2253[0] CI: PID setpoint 0 2224 PID setpoint = fixed value
P2264[0] CI: PID feedback 755.0 755.1 PID feedback = AI2

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 79
Commissioning via the built-in BOP
5.5 Quick commissioning

Connection macro settings:

P0700[0] Selection of command source 1 5 RS485 as the command source


P1000[0] Selection of frequency 1 5 RS485 as the speed setpoint
P2023[0] RS485 protocol selection 1 1 USS protocol
P2010[0] USS/MODBUS baudrate 6 8 Baudrate 38400 bps
P2011[0] USS address 0 1 USS address for converter
P2012[0] USS PZD length 2 2 Number of PZD words
P2013[0] USS PKW length 127 127 Variable PKW words
P2014[0] USS/MODBUS telegram off time 2000 500 Time to receive data

Connection macro settings:

P0700[0] Selection of command source 1 5 RS485 as the command source


P1000[0] Selection of frequency 1 5 RS485 as the speed setpoint
P2023[0] RS485 protocol selection 1 2 MODBUS RTU protocol

SINAMICS V20 Converter


80 Operating Instructions, 05/2020, A5E34559884-013
Commissioning via the built-in BOP
5.5 Quick commissioning

P2010[0] USS/MODBUS baudrate 6 6 Baudrate 9600 bps


P2021[0] MODBUS address 1 1 MODBUS address for converter
P2022[0] MODBUS reply timeout 1000 1000 Maximum time to send reply back
to the master
P2014[0] USS/MODBUS telegram off time 2000 100 Time to receive data
P2034 MODBUS parity on RS485 2 2 Parity of MODBUS telegrams on
RS485
P2035 MODBUS stop bits on RS485 1 1 Number of stop bits in MODBUS
telegrams on RS485

When commissioning the converter, the application macro setting is a one-off setting. Make
sure that you proceed as follows before you change the application macro setting to a value
different from your last setting:
1. Do a factory reset (P0010 = 30, P0970 = 1)
2. Repeat the quick commissioning and change the application macro
Failure to observe may cause the converter to accept the parameter settings from both the
currently and the previously selected macros, which may lead to undefined and
unexplainable operation.

This menu defines certain common applications. Each application macro provides a set of
parameter settings for a specific application. After you select an application macro, the
corresponding settings are applied to the converter to simplify the commissioning process.
The default application macro is "AP000" for application macro 0. If none of the application
macros fits your application, select the one that is the closest to your application and make
further parameter changes as desired.

AP000 Factory default setting. Makes no parameter changes.


AP010 Simple pump applications
AP020 Simple fan applications
AP021 Compressor applications
AP030 Conveyor applications
The minus sign indicates that this macro is
the currently selected macro.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 81
Commissioning via the built-in BOP
5.5 Quick commissioning

P1080[0] Minimum frequency 0 15 Converter running at a lower speed inhibited


P1300[0] Control mode 0 7 Quadratic V/f
P1110[0] BI: Inhibit negative 0 1 Reverse pump rotation inhibited
frequency setpoint
P1210[0] Automatic restart 1 2 Restart after mains blackout
P1120[0] Ramp-up time 10 10 Ramp-up time from zero to maximum frequency
P1121[0] Ramp-down time 10 10 Ramp-down time from maximum frequency to
zero

P1110[0] BI: Inhibit negative 0 1 Reverse fan rotation inhibited


frequency setpoint
P1300[0] Control mode 0 7 Quadratic V/f
P1200[0] Flying start 0 2 Search for the speed of the running motor with
a heavy inertia load so that the motor runs up to
the setpoint
P1210[0] Automatic restart 1 2 Restart after mains blackout
P1080[0] Minimum frequency 0 20 Converter running at a lower speed inhibited
P1120[0] Ramp-up time 10 10 Ramp-up time from zero to maximum frequency
P1121[0] Ramp-down time 10 20 Ramp-down time from maximum frequency to
zero

SINAMICS V20 Converter


82 Operating Instructions, 05/2020, A5E34559884-013
Commissioning via the built-in BOP
5.5 Quick commissioning

P1300[0] Control mode 0 0 Linear V/f


P1080[0] Minimum frequency 0 10 Converter running at a lower speed inhibited
P1312[0] Starting boost 0 30 Boost only effective when accelerating for the first time
(standstill)
P1311[0] Acceleration boost 0 0 Boost only effective when accelerating or braking
P1310[0] Continuous boost 50 50 Additional boost over the complete frequency range
P1120[0] Ramp-up time 10 10 Ramp-up time from zero to maximum frequency
P1121[0] Ramp-down time 10 10 Ramp-down time from maximum frequency to zero

P1300[0] Control mode 0 1 V/f with FCC


P1312[0] Starting boost 0 30 Boost only effective when accelerating for the first time (standstill)
P1120[0] Ramp-up time 10 5 Ramp-up time from zero to maximum frequency
P1121[0] Ramp-down time 10 5 Ramp-down time from maximum frequency to zero

This menu provides some common parameters for converter performance optimization.

If you set P8553 to 1, parameter numbers in this menu are replaced with short text.

P1080[0] 1 Minimum motor P1001[0] 2 Fixed frequency


frequency setpoint 1

(MIN F) (FIX F1)


P1082[0] 1 Maximum motor P1002[0] 2 Fixed frequency
frequency setpoint 2

(MAX F) (FIX F2)

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 83
Numbers prefixed with an "r" indicate that the parameter is a "read-only" parameter.
Numbers prefixed with a "P" indicate that the parameter is a "writable" parameter.
indicates that the parameter is an indexed parameter and specifies the range of
indices available. If the index is [0...2] and the meaning is not listed, then see "Data set".
indicates that the parameter has several bits, which can be evaluated or connected
individually.

The "Index" chapter at the end of this manual provides complete lists of CDS/DDS
parameters.

In the converter, the parameters which are used to define the sources for commands and
setpoints are combined in the (CDS), while the parameters for the open
and closed-loop control of the motor are combined in the (DDS).
The converter can be operated from different signal sources by switching over the command
data sets. When switching over the drive data sets, it is possible to switch between different
converter configurations (control type, motor).
Three independent settings are possible for each data set. These settings can be made
using the index [0...2] of the particular parameter.

[0] Command data set 0 Drive data set 0


[1] Command data set 1 Drive data set 1
[2] Command data set 2 Drive data set 2

SINAMICS V20 has an integrated copy function which is used to transfer data sets. This can
be used to copy CDS/DDS parameters corresponding to the particular application.

P0809[0] P0819[0] The data set which is to be copied (source)


P0809[1] P0819[1] The data set into which data is to be copied (target)
P0809[2] P0819[2] = 1: Start copying
= 0: Copying completed

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 197
Parameter list
8.1 Introduction to parameters

For example, copying of all values from CDS0 to CDS2 can be accomplished by the
following procedure:
1. Set P0809[0] = 0: copy from CDS0
2. Set P0809[1] = 2: copy to CDS2
3. Set P0809[2] = 1: start copy

The command data sets are changed over using the BICO parameters P0810 and P0811,
whereby the active command data set is displayed in parameter r0050. Changeover is
possible in both the "Ready" and the "Run" states.

P0810 = 0 CDS0
P0811 = 0
P0810 = 1 CDS1
P0811 = 0
P0810 = 0 or 1 CDS2
P0811 = 1

The drive data sets are changed over using the BICO parameters P0820 and P0821,
whereby the active drive data set is displayed in parameter r0051. Drive data sets can only
be changed over in the "Ready" state.

P0820 = 0 DDS0
P0821 = 0
P0820 = 1 DDS1
P0821 = 0
P0820 = 0 or 1 DDS2
P0821 = 1

The "Index" chapter at the end of this manual provides groups of the BICO parameters.

Certain parameter names include the following abbreviated prefixes: BI, BO, CI, CO and
CO/BO followed by a colon. These abbreviations have the following meanings:

BI = Binector input: Parameter selects the source of a binary signal


Each BI parameter can connect as the input to any BO or CO/BO parameter.
BO = Binector output: Parameter connects as a binary signal
Each BO parameter can connect as the output to any BI parameter.
CI = Connector input: Parameter selects the source of an analog signal
Each CI parameter can connect as the input to any CO or CO/BO parameter.
CO = Connector output: Parameter connects as an analog signal
Each CO parameter can connect as the output to any CI parameter.
CO/ = Connector/binector output: Parameter connects as an analog signal and/or as a binary signal
BO Each CO/BO parameter can connect as the output to any BI or CI parameter.

SINAMICS V20 Converter


198 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.1 Introduction to parameters

BICO or the binary interconnection technology can help the user to connect internal function
and values to realize more customized features.
BICO functionality is a different, more flexible way of setting and combining input and output
functions. It can be used in most cases in conjunction with the simple, access level 2
settings.
The BICO system allows complex functions to be programmed. Boolean and mathematical
relationships can be set up between inputs (digital, analog, serial etc.) and outputs
(converter current, frequency, analog output, digital outputs, etc.).
The default parameter that a BI or CI parameter is connected to is shown in the Factory
default column of the parameter list.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 199
Parameter list
8.1 Introduction to parameters

Defines the level of user access to parameter sets.

0 User-defined parameter list Defines a limited set of parameters to which the end
user has access. See P0013 for details on use.
1 Standard Allows access into most frequently used parameters.
2 Extended Allows extended access to more parameters.
3 Expert For expert use only.
4 Service Only for use by authorized service personnel, password
protected.

The data types available are shown in the table below.

U8 8-bit unsigned
U16 16-bit unsigned
U32 32-bit unsigned
I16 16-bit integer
I32 32-bit integer
Float 32-bit floating point number

Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source) the following combinations are possible when creating BICO
interconnections:

CO: U8 - -
CO: U16 - -
CO: U32 - -
CO: I16 - -
CO: I32 - -
CO: Float -
BO: U8 - - -
BO: U16 - - -
BO: U32 - - -
BO: I16 - - -
BO: I32 - - -
BO: Float - - - -
Legend:
: BICO interconnection permitted
-: BICO interconnection not permitted

SINAMICS V20 Converter


200 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.1 Introduction to parameters

Specification of the reference quantity with which the signal value will be converted
automatically.
Reference quantities, corresponding to 100 %, are required for the statement of physical
units as percentages. These reference quantities are entered in P2000 to P2004.
In addition to P2000 to P2004 the following normalizations are used:
TEMP: 100 °C = 100 %
PERCENT: 1.0 = 100 %
4000H: 4000 hex = 100 %

Converter state in which the parameter is changeable. Three states are possible:
Commissioning: C, C(1) or C(30)
Run: U
Ready to run: T
This indicates when the parameter can be changed. One, two or all three states may be
specified. If all three states are specified, this means that it is possible to change this
parameter setting in all three converter states. C shows the parameter is changeable
whatever P0010 equals; C(1) shows that the parameter is changeable only when P0010 = 1;
C(30) shows that the parameter is changeable only when P0010 = 30.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 201
Parameter list
8.2 Parameter list

r0002 - - - - - U16 2
Displays actual converter state.
0 Commissioning mode (P0010 0)
1 Converter ready
2 Converter fault active
3 Converter starting (visible only while pre-charging DC link)
4 Converter running
5 Stopping (ramping down)
6 Converter inhibited
P0003 0-4 1 U, T - - U16 1
Defines user access level to parameter sets.
0 User defined parameter list - see P0013 for details on use
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access, for example, to converter I/O functions
3 Expert: For expert use only
4 Service: Only for use by authorized service, password protected
P0004 0 - 24 0 U, T - - U16 1
Filters parameters according to functionality to enable a more focused approach to commissioning.
0 All parameters
2 Converter
3 Motor
5 Technology application/units
7 Commands, binary I/O
8 Analog input and analog output
10 Setpoint channel/RFG
12 Converter features
13 Motor control
19 Motor identification
20 Communication
21 Warnings/faults/monitoring
22 Technology controller
24 List of modified parameters
P0005 0 - 9580 0 C, U, T - - U16 2

Selects default display parameter (converter display).


The converter displays the value of the parameter selected here by default.
If you have set P0005 to a non-zero value which represents an actual parameter number, then the con-
verter displays the value of the selected parameter as the default display value; if you have set P0005 to 0
or a non-zero value which does not represent an actual parameter number, then the default display re-
mains unchanged.

SINAMICS V20 Converter


202 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0007 0 - 2000 0 U, T - - U16 3


Defines time period after which the backlight of the operator panel display turns off if no buttons have been
pressed.
0 Backlight always on
1 - 2000 Number of seconds after which the backlight turns off.
P0010 0 - 30 0 T - - U16 1

Filters parameters so that only those related to a particular functional group are selected.
0 Ready
1 Quick commissioning
2 Converter
29 Download
30 Factory setting
Reset to 0 for converter to run.
P0003 (user access level) also determines access to parameters.
• P0010 = 1
The converter can be commissioned very quickly and easily by setting P0010 = 1. After that only the
important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be en-
tered one after the other. The end of quick commissioning and the start of internal calculation will be
done by setting P3900 = 1 - 3. Afterwards parameter P0010 and P3900 will be reset to zero automati-
cally.
• P0010 = 2
For service purposes only.
• P0010 = 30
When resetting the parameters or user default values of converter P0010 must be set to 30.

Resetting of the parameters will be started by setting parameter P0970 = 1. The converter will automat-
ically reset all its parameters to their default settings. This can prove beneficial if you experience prob-
lems during parameter setup and wish to start again.

Resetting of the user default values will be started by setting parameter P0970 = 21. The converter will
automatically reset all its parameters to the factory default settings. Duration of factory setting will take
about 60 seconds.
P0011 0 - 65535 0 U, T - - U16 3

See P0013
P0012 0 - 65535 0 U, T - - U16 3

See P0013

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 203
Parameter list
8.2 Parameter list

P0013[0...19] 0 - 65535 [0...16] 0 U, T - - U16 3


[17] 3
[18] 10
[19] 12
Defines a limited set of parameters to which the end user has access.

1. Set P0003 = 3 (expert user).


2. Go to P0013 indices 0 to 16 (user list)
3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list.
The following values are fixed and cannot be changed:
- P0013 index 17 = 3 (user access level)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 19 = 12 (key for user defined parameter)
4. Set P0003 = 0 to activate the user defined parameter.
[0] 1st user parameter
[1] 2nd user parameter
... ...
[19] 20th user parameter
First, set P0011 ("lock") to a different value then P0012 ("key") to prevent changes to user-defined parame-
ter.
Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
P0014[0...2] 0-1 0 U, T - - U16 3
Sets the store mode for parameters. The store mode can be configured for all interfaces under "Index".
0 Volatile ( RAM)
1 Non-volatile (EEPROM)
[0] USS/Modbus on RS485
[1] USS on RS232 (reserved)
[2] Reserved
An independent store request may be part of the serial communications (for example, PKE bits 15-12 of
USS protocol). See the table below for an influence on the settings of P0014.

RAM EEPROM EEPROM


EEPROM EEPROM EEPROM
RAM RAM RAM
EEPROM RAM EEPROM
1. P0014 itself will always be stored in the EEPROM.
2. P0014 will not be changed by performing a factory reset.
When transferring parameter P0014, the converter uses its processor to carry-out internal calculations.
Communications - both via USS as well as Modbus - are interrupted for the time that it takes to make
these calculations.

SINAMICS V20 Converter


204 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0016 0-1 0 C, U, T - - U16 3

Prevents parameter editing on the BOP.


0 Enable parameter editing on BOP (immediately effective)
1 Disable parameter editing on BOP (effective only after converter power-cycle)
In addition to enabling parameter editing with P0016=0, you can alternatively use the BOP buttons to ena-
ble the editing. Long-press (> 2 s), wait until "ULOC?" appears on the BOP display, and then press
. The unlocking becomes effective immediately.
r0017 - - - - - U16 3

Shows the immediate status of the BOP buttons.

00 Run button Yes No


01 Stop button Yes No
02 HAND/AUTO button combination (OK + M) Yes No
03 OK button Yes No
05 Up button Yes No
06 Down button Yes No
07 Run/stop latch Yes No
Bit 07 (ON/OFF), will remain high if the run button has been pressed and released. It will only be reset
once the stop button has been pressed.
r0018 - - - - - Float 1
Displays version number of installed firmware.
r0019.0...14 - - - - - U16 3

Displays status of operator panel commands. The settings below are used as the "source" codes for key-
pad control when connecting to BICO input parameters.

00 ON/OFF1 Yes No
01 OFF2: Electrical stop No Yes
08 JOG right Yes No
11 Reverse (setpoint inversion) Yes No
13 Motor potentiometer MOP up Yes No
14 Motor potentiometer MOP down Yes No
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
r0020 - - - - - Float 3

Displays actual frequency setpoint (input of ramp function generator). This value is available filtered
(r0020) and unfiltered (r1119). The actual frequency setpoint after RFG is displayed in r1170.
r0021 - - - - - Float 2

Displays actual converter output frequency (r0024) excluding slip compensation (and resonance damping,
frequency limitation in V/f mode).

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 205
Parameter list
8.2 Parameter list

r0022 - - - - - Float 3

Displays calculated rotor speed based on r0021 (filtered output frequency [Hz] x 120/number of poles). The
value is updated every 128 ms.
This calculation makes no allowance for load-dependent slip.
r0024 - - - - - Float 3

Displays actual filtered output frequency (slip compensation, resonance damping and frequency limitation
are included). See also r0021. This value is available filtered (r0024) and unfiltered (r0066).
r0025 - - - - - Float 2

Displays filtered [rms] voltage applied to motor. This value is available filtered (r0025) and unfiltered
(r0072).
r0026[0] - - - - - Float 2

Displays filtered DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
[0] Compensation DC voltage channel
r0026[0] = Main DC-link voltage
r0027 - - - P2002 - Float 2

Displays rms value of motor current. This value is available filtered (r0027) and unfiltered (r0068).
r0028 - - - P2002 - Float 3

Displays estimated rms value of motor current calculated from dclink current.
r0031 - - - - - Float 2

Displays electrical torque. This value is available filtered (r0031) and unfiltered (r0080).
The electrical torque is not the same as the mechanical torque, which can be measured on the shaft. Due
to windage and friction a part of the electrical torque is lost in the motor.
r0032 - - - r2004 - Float 2
Displays (mechanical) shaft power. Value is displayed in [kW] or [hp] depending on setting for P0100 (op-
eration for Europe/North America).
P_mech = 2 * Pi * f * M -->
r0032[kW] = (2 * Pi/1000) * (r0022/60)[1/min] * r0031[Nm]
r0032[hp] = r0032[kW]/0.75
r0035[0...2] - - - - DDS Float 2

Displays calculated motor temperature.


r0036 - - - PERCE - Float 3
NT
Displays converter overload utilization calculated via the I 2t model.
The actual I2t value relative to the maximum possible I2t value supplies utilization in [%].
If the current exceeds the threshold for P0294 (converter I2t overload warning), warning A505 (converter
I2t) is generated and the output current of the converter reduced via P0290 (converter overload reaction).
If 100 % utilization is exceeded, fault F5 (converter I2t) is tripped.

SINAMICS V20 Converter


206 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0037[0...1] - - - - - Float 3

Displays measured heat sink temperature and calculated junction temperature of IGBTs based on thermal
model.
[0] Measured heat sink temperature
[1] Total Chip Junction Temperature
The values are updated every 128 ms.
r0038 - - - - - Float 3

Displays the filtered power factor.


r0039 - - - - - Float 2

Displays electrical energy used by converter since display was last reset (see P0040 - reset energy con-
sumption meter).
Value is reset when P0040 = 1 (reset energy consumption meter).
P0040 0-1 0 T - - U16 2

Resets value of r0039 (energy consumption meter) and r0043 (energy saved meter) to zero.
0 No reset
1 Reset r0039 to 0
P0042[0...1] 0.000 - 100.00 0.000 T - - Float 2
Scales the calculated energy saved value
[0] Factor for kWh to currency conversion
[1] Factor for kWh to CO2 conversion
r0043[0...2] - - - - - Float 2
Displays calculated energy saved
[0] Energy saving in kWh
[1] Energy saving in currency
[2] Energy saving in CO2
r0050 - - - - - U16 2

Displays currently active command data set.


0 Command data set 0 (CDS)
1 Command data set 1 (CDS)
2 Command data set 2 (CDS)
See P0810
r0051[0...1] - - - - - U16 2

Displays currently selected and active drive data set (DDS).


0 Drive data set 0 (DDS0)
1 Drive data set 1 (DDS1)
2 Drive data set 2 (DDS2)
[0] Selected drive data set
[1] Active drive data set
See P0820

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 207
Parameter list
8.2 Parameter list

r0052.0...15 - - - - - U16 2

Displays first active status word of converter (bit format) and can be used to diagnose converter status.

00 Converter ready Yes No


01 Converter ready to run Yes No
02 Converter running Yes No
03 Converter fault active Yes No
04 OFF2 active No Yes
05 OFF3 active No Yes
06 ON inhibit active Yes No
07 Converter warning active Yes No
08 Deviation setpoint/act. value No Yes
09 PZD control Yes No
10 |f_act| >= P1082 (f_max) Yes No
11 Warning: Motor current/torque limit No Yes
12 Brake open Yes No
13 Motor overload No Yes
14 Motor runs right Yes No
15 Converter overload No Yes
r0052 bit 03 "Converter fault active": Output of bit 3 (Fault) will be inverted on digital output (Low = Fault,
High = No Fault);
r0052 bit 06 "On inhibit" is active with OFF2 or OFF3 and becomes disabled with OFF1, NOT OFF2 and
NOT OFF3.
See r2197 and r2198.
r0053.0...11 - - - - - U16 2

Displays second status word of converter (in bit format).

00 DC brake active Yes No


01 |f_act| > P2167 (f_off) Yes No
02 |f_act| > P1080 (f_min) Yes No
03 Act. current |r0068| >= P2170 Yes No
04 |f_act| > P2155 (f_1) Yes No
05 |f_act| <= P2155 (f_1) Yes No
06 f_act >= setpoint (f_set) Yes No
07 Act. unfilt. Vdc < P2172 Yes No
08 Act. unfilt. Vdc > P2172 Yes No
09 Ramping finished Yes No
10 PID output r2294 == P2292 (PID_min) Yes No
11 PID output r2294 == P2291 (PID_max) Yes No
r0053 bit 00 "DC brake active" ==> see P1233
See r2197 and r2198.

SINAMICS V20 Converter


208 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0054.0...15 - - - - - U16 3

Displays first control word of converter (in bit format) and can be used to diagnose which commands are
active.

00 ON/OFF1 Yes No
01 OFF2: electrical stop No Yes
02 OFF3: fast stop No Yes
03 Pulse enable Yes No
04 RFG enable Yes No
05 RFG start Yes No
06 Setpoint enable Yes No
07 Fault acknowledge Yes No
08 JOG right Yes No
09 JOG left Yes No
10 Control from PLC Yes No
11 Reverse (setpoint inversion) Yes No
13 Motor potentiometer MOP up Yes No
14 Motor potentiometer MOP down Yes No
15 CDS Bit 0 (Hand/Auto) Yes No
r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
r0055.0...15 - - - - - U16 3

Displays additional control word of converter (in bit format) and can be used to diagnose which commands
are active.

00 Fixed frequency Bit 0 Yes No


01 Fixed frequency Bit 1 Yes No
02 Fixed frequency Bit 2 Yes No
03 Fixed frequency Bit 3 Yes No
04 Drive data set (DDS) Bit 0 Yes No
05 Drive data set (DDS) Bit 1 Yes No
06 Quick stop disable Yes No
08 Enable PID Yes No
09 Enable DC brake Yes No
13 External fault 1 No Yes
15 Command data set (CDS) Bit 1 Yes No
r0055 is identical to r2037 if USS is selected as command source via P0700 or P0719.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 209
Parameter list
8.2 Parameter list

r0056.0...15 - - - - - U16 3

Displays status of motor control (in bit format), which can be used to diagnose converter status.

00 Init. control finished Yes No


01 Motor demagnetizing finished Yes No
02 Pulses enabled Yes No
03 Voltage soft start select Yes No
04 Motor excitation finished Yes No
05 Starting boost active Yes No
06 Acceleration boost active Yes No
07 Frequency is negative Yes No
08 Field weakening active Yes No
09 Volts setpoint limited Yes No
10 Slip frequency limited Yes No
11 f_out > f_max Freq. limited Yes No
12 Phase reversal selected Yes No
13 Imax controller active/torque limit reached Yes No
14 Vdc_max controller active Yes No
15 KIB (Vdc_min control) active Yes No
The I-max controller (r0056 bit 13) will be activated when the actual output current (r0027) exceeds the
current limit in r0067.
r0066 - - - - - Float 3

Displays actual output frequency in Hz. This value is available filtered (r0024) and unfiltered (r0066).
The output frequency is limited by the values entered in P1080 (minimum frequency) and P1082 (maxi-
mum frequency).
r0067 - - - P2002 - Float 3

Displays valid maximum output current of converter.


r0067 is influenced/determined by the following factors:
• Converter application P0205
• Rated motor current P0305
• Motor overload factor P0640
• Motor protection in dependency of P0610
• r0067 is less than or equal to maximum converter current r0209
• Converter protection in dependency of P0290
A reduction of r0067 may indicate a converter overload or a motor overload.
r0068 - - - P2002 - Float 3
Displays unfiltered [rms] value of motor current. This value is available filtered (r0027) and unfiltered (r0068).
Used for process control purposes (in contrast to r0027, which is filtered and is used to display the value
through USS).

SINAMICS V20 Converter


210 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0069[0...5] - - - P2002 - Float 4

Displays measured phase currents.


[0] U_Phase/ Emitter1/
[1] Dclink/Emitter2
[2] Dclink
[3] Offset U_phase/Emitter
[4] Offset dclink
[5] Not used
r0070 - - - - - Float 3

Displays DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered).
r0071 - - - - - Float 3

Displays maximum output voltage.


Actual maximum output voltage depends on the actual input supply voltage.
r0072 - - - - - Float 3

Displays output voltage. This value is available filtered (r0025) and unfiltered (r0072).
r0074 - - - PERCE - Float 4
NT
Displays actual modulation index. The modulation index is defined as ratio between the magnitude of the
fundamental component in the converter phase output voltage and half of the DC-link voltage.
r0078 - - - P2002 - Float 3

Displays component of torque generating current.


r0080 - - - - - Float 4
Displays actual torque. This value is available filtered (r0031) and unfiltered (r0080).
r0084 - - - PERCE - Float 4
NT
Displays air gap flux relative to the rated motor flux.
r0085 - - - P2002 - Float 3

Displays re-active (imaginary part) of motor current.


Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0086 - - - P2002 - Float 3

Displays active (real part) of motor current.


See r0085
r0087 - - - - - Float 3
Displays the actual power factor.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 211
Parameter list
8.2 Parameter list

r0094 - 0.0 - 4000H - Float 3

Displays the transformation angle (flux angle in VC mode or angle from frequency in Vf mode).
P0095[0...9] 0 - 4294967295 0 T 4000H - U32 3
Selects source of display for PZD signals.
[0] 1st PZD signal
[1] 2nd PZD signal
... ...
[9] 10th PZD signal
r0096[0...9] - - - - - Float 3
Displays PZD signals.
[0] 1st PZD signal
[1] 2nd PZD signal
... ...
[9] 10th PZD signal
r0096 = 100 % corresponds to 4000 hex.
P0100 0-2 0 C(1) - - U16 1
Determines whether the power settings are expressed in [kW] or [hp] (e.g. Rated motor power P0307).
The default settings for the rated motor frequency P0310 and maximum frequency P1082 are set automat-
ically here, in addition to reference frequency P2000.
0 Europe [kW], motor base frequency is 50 Hz
1 North America [hp], motor base frequency is 60 Hz
2 North America [kW], motor base frequency is 60 Hz
Where:
• Stop converter first (i.e. disable all pulses) before you change this parameter.
• P0100 can only be changed with P0010 = 1 (Commissioning mode) via the respective interface (for
example, USS).
• Changing P0100 resets all rated motor parameters as well as other parameters that depend on the
rated motor parameters (see P0340 - calculation of motor parameters).
r0191[0...2] - 0 - - - U32 4
Displays the actual hardware configuration (SZL vector) of the converter.
[0] SZL vector of converter and power module
[1] SZL vector of converter
[2] SZL vector of power module

SINAMICS V20 Converter


212 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0199 0 - 65535 0 U, T - - U16 2

Specifies the unique equipment system number for the converter.


P0201[0...2] 0 - 65535 0 T - - U16 3

Identifies hardware variant.


[0] Converter code
[1] Functionality version - last digit of the article number
[2] Last used converter ID
Parameter P0201 = 0 indicates that no power module has been identified.
r0204 - 0 - - - U32 3
Displays hardware features of power module.

00 DC input voltage Yes No


01 RFI filter Yes No
02 Active line module Yes No
03 SLM Yes No
04 BLM with thryistor Yes No
05 BLM with diode Yes No
06 Water cooled Yes No
07 F3E converter Yes No
12 Safe brake Yes No
13 Safety enabled Yes No
14 Integrated output filter Yes No
Parameter r0204 = 0 indicates that no power module has been identified.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 213
Parameter list
8.2 Parameter list

P0205 0-1 0 C1 - - U16 3


Selects a converter application.
The converter and motor requirements are determined by the speed range and torque requirements of the
load. The relationship between speed and torque for different loads (high overloads or low overloads) is
shown in the following figure:

• High overload (HO):


HO mode is used if the application needs a high overload on the whole frequency range. Many loads
can be considered to be high overloads. Typical high overloads are conveyors, compressors and posi-
tive displacement pumps.
• Low overload (LO):
LO mode is used if the application has a parabolic frequency/torque characteristic like many fans and
pumps. Low overload offers the following possibilities with the same converter:
– Higher rated converter current r0207
– Higher rated converter power r0206
– Higher threshold for I2t protection
If P0205 is modified in quick commissioning it immediately calculates various motor parameters:
– P0305 Rated motor current
– P0307 Rated motor power
– P0640 Motor overload factor
It is recommended to modify P0205 first. Afterwards motor parameter may be adapted.
Motor parameter will be overridden by changing this sequence.
0 High overload
1 Low overload

SINAMICS V20 Converter


214 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

Use setting 1 (low overload) only for low-overload applications (for example, pumps and fans).
If it is used for high-overload applications, I2t warning will be produced too late, causing overheating in the
motor.
This parameter selects converter application for FSE only. The parameter value is not reset by the factory
setting (see P0970).
r0206 - - - - - Float 2

Displays nominal rated motor power from converter.


Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe/North America).
r0207[0...2] - - - - - Float 2

Displays rated converter current.


[0] Rated converter current
[1] Rated LO current
[2] Rated HO current
The rated high overload (HO) current r0207[2] values correspond to suitable 4-pole Siemens standard
motors (IEC) for the selected load cycle (see diagram). r0207[2] is the default value of P0305 in associa-
tion with the HO application (load cycle).

r0208 - - - - - U32 2

Displays nominal AC supply voltage of converter.


r0208 = 230: 200 V to 240 V (tolerance: -10% to +10%)
r0208 = 400: 380 V to 480 V (tolerance: -15% to +10%)

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 215
Parameter list
8.2 Parameter list

r0209 - - - - - Float 2

Display the maximum allowable output current of converter.


In actual applications, Siemens recommends that you consider the output current derating affected by
pulse frequency P1800, surrounding temperature and altitude. The data of derating is given in the Operat-
ing Instructions.
P0210 380 - 480 400 T - - U16 3
P0210 defines the supply voltage. Its default value depends upon the type of converter. If P0210 does not
correspond to the supply voltage, then it must be modified.
Optimizes Vdc controller, which extends the ramp-down time if regenerative energy from motor would
otherwise cause DC-link overvoltage trips.
Reducing the value enables controller to cut in earlier and reduce the risk of overvoltage.
Set P1254 ("Auto detect Vdc switch-on levels") = 0. Cut-in levels for Vdc controller and compound braking
are then derived directly from P0210 (supply voltage):
• Vdc_min switch-on level (r1246) = P1245 * sqrt(2) * P0210
• Vdc_max switch-on level (r1242) = 1.15 * sqrt(2) * P0210
• Dynamic braking switch-on level = 1.13 * sqrt(2) * P0210
• Compound braking switch-on level = 1.13 * sqrt(2) * P0210
Set P1254 ("Auto detect Vdc switch-on levels") = 1. Cut-in levels for Vdc controller and compound braking
are then derived from r0070 (DC-link voltage):
• Vdc_min switch-on level (r1246) = P1245 * r0070
• Vdc_max switch-on level (r1242) = 1.15 * r0070
• Dynamic braking switch-on level = 0.98 * r1242
• Compound braking switch-on level = 0.98 * r1242
Auto-detection calculations are only performed when the converter has been in standby for over 20s.
When pulses are enabled, the calculated values are frozen after pulses are ceased for 20s.
For best results, it is recommended that auto-detection of Vdc switch-on levels (P1254 = 1) is used. Set-
ting P1254 = 0 is only recommended when there is a high degree of fluctuation of the DC-link when the
motor is being driven. In this case, ensure the setting of P0210 is correct.
If mains voltage is higher than value entered, automatic deactivation of the Vdc controller may occur to
avoid acceleration of the motor. A warning will be issued in this case (A910).
Default value is depending on converter type and its rating data.
r0231[0...1] - - - - - U16 3
Indexed parameter to display maximum allowable cable length between converter and motor.
[0] Maximum allowed unscreened cable length
[1] Maximum allowed screened cable length
For full EMC compliance, the screened cable must not exceed 25 m in length when an EMC filter is fitted.
P0290 0-3 2 T - - U16 3
Selects reaction of converter to an internal thermal overload condition.
0 Reduce output frequency and output current
1 No reduction, trip (F4/5/6) when thermal limits reached
2 Reduce pulse frequency, output current and output frequency
3 Reduce pulse frequency only and trip (F6) when overload too high

SINAMICS V20 Converter


216 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

Following physical values influence the converter overload protection (see diagram):
• Heat sink temperature (r0037[0]); causes A504 and F4.
• IGBT Junction temperature (r0037[1]); causes F4 or F6.
• Delta temperature between heat sink and junction temperature; causes A504 and F6.
• Converter I2t (r0036); causes A505 and F5.

P0290 = 0, 2:
• Reduction of output frequency is only effective if the load is also reduced.

This is for example valid for light overload applications with a quadratic torque characteristic as pumps or fans.
• For settings P0290 = 0 or 2, the I-max controller will act upon the output current limit (r0067) in case of overtemper-
ature.
P0290 = 0:
• With pulse frequencies above nominal, pulse frequency will be reduced to nominal immediately in the event of
r0027 greater than r0067 (current limit).
P0290 = 2, 3:
• The pulse frequency P1800 is reduced only if higher than 2 kHz and if the operating frequency is below 2 Hz.
• The actual pulse frequency is displayed in r1801[0] and the minimal pulse frequency for reduction is displayed in
r1801[1].
• Converter I2t acts upon output current and output frequency, but not on pulse frequency.
A trip will always result, if the action taken does not sufficiently reduce internal temperatures.
P0291[0...2] 0-7 1 U, T - DDS U16 4
Bit 00 for enabling/disabling automatic pulse frequency reduction at output frequencies below 2 Hz. The
benefit is to reduce the noises at frequencies below 2 Hz.

00 Pulse frequency reduced below 2 Hz Yes No


01 Reserved Yes No
02 Phase loss detection enable No Yes
03 Reserved Yes No
04 Output current ripple detection enable No Yes
05 Enhanced dead-time compensation enable No Yes
See P0290

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 217
Parameter list
8.2 Parameter list

P0292 0 - 25 5 U, T - - U16 3

Defines the temperature difference (in °C) between the overtemperature trip threshold (F4) and the warn-
ing threshold (A504) of the converter. The trip threshold is stored internally by the converter and cannot be
changed by the user.
P0294 2 10.0 - 95.0 U, T - - Float 3
100.0
Defines the [%] value at which warning A505 (converter I2t) is generated.
Converter I2t calculation is used to determine a maximum tolerable period for converter overload.
The I2t calculation value is deemed = 100 % when this maximum tolerable period is reached.
• The output current of the converter has been reduced.
• The value of I2t does not exceed 100 %.
P0294 = 100 % corresponds to stationary nominal load.
P0295 0 - 3600 0 U, T - - U16 3

Defines converter fan switch-off delay time in seconds after converter has stopped.
Setting to 0, converter fan will switch off when the converter stops, that means no delay.
P0296 0-2 0 T - - U16 3

Defines the converter response with increased ripple in the output current.
0 No response
1 Alarm produced (A523)
2 Fault produced (F23)
P0301[0...2] 0 - 2000 0 C(1) - DDS Float 1

Rated motor power from the rating plate. No other data is necessary. If this parameter is used, the rest of
the motor data are then estimated by the firmware.
Changeable only when P0010 = 1 (quick commissioning).
This functionality is only valid with 50 Hz supply, star configuration on 4-pole motors. You must set this
parameter to zero if you desire to set the other motor data.

SINAMICS V20 Converter


218 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0304[0...2] 10 - 2000 400 C(1) - DDS U16 1


Nominal motor voltage from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Default value is depending on converter type and its rating data.
The input of rating plate data must correspond with the wiring of the motor (star/delta). This means, if delta
wiring is used for the motor, delta rating plate data has to be entered.

Following diagram shows a typical rating plate with the locations of the relevant motor data.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 219
Parameter list
8.2 Parameter list

P0305[0...2] 0.01 - 1.86 C(1) - DDS Float 1


10000.00
Nominal motor current from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Depends also on P0320 (motor magnetization current).
The maximum value of P0305 depends on the maximum converter current r0209 and the motor type:
Asynchronous motor : P0305_max = P0209
It is recommended that the ratio of P0305 (rated motor current) and r0207 (rated converter current) should
not be lower than: (1/8) <= (P0305/r0207)
When the relation of the nominal motor current P0305 and half of the maximal converter current (r0209)
exceeds 1.5 an additional current derating is applied. This is necessary to protect the converter from har-
monic current waves.

Default value is depending on converter type and its rating data.


P0307[0...2] 0.01 - 0.75 C(1) - DDS Float 1
2000.00
Nominal motor power [kW/hp] from rating plate.
If P0100 = 1, values will be in [hp].
Changeable only when P0010 = 1 (quick commissioning).
Default value is depending on converter type and its rating data.
P0308[0...2] 0.000 - 0.000 C(1) - DDS Float 1
1.000
Nominal motor power factor (cos ) from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Visible only when P0100 = 0 or 2, (motor power entered in [kW]).
Setting 0 causes internal calculation of value. The value is displayed in r0332.
P0309[0...2] 0.0 - 99.9 0.0 C(1) - DDS Float 1
Nominal motor efficiency from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Visible only when P0100 = 1, (i.e. motor power entered in [hp]).
Setting 0 causes internal calculation of value. The value is displayed in r0332.
P0310[0...2] 12.00 - 50.00 C(1) - DDS Float 1
550.00
Nominal motor frequency from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Pole pair number recalculated automatically if parameter is changed.
Changes to P0310 can influence the maximum motor frequency. For further information see P1082.

SINAMICS V20 Converter


220 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0311[0...2] 0 - 40000 1395 C(1) - DDS U16 1


Nominal motor speed from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Setting 0 causes internal calculation of value.
Slip compensation in V/f control requires rated motor speed for correct operation.
Pole pair number recalculated automatically if parameter is changed.
Default value is depending on converter type and its rating data.
r0313[0...2] - - - - DDS U16 3
Displays number of motor pole pairs that the converter is currently using for internal calculations.
Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is
changed.
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor
...
P0314[0...2] 0 - 99 0 C(1) - DDS U16 3
Specifies number of pole pairs of motor.
Changeable only when P0010 = 1 (quick commissioning).
Setting 0 causes r0313 (calculated motor pole pairs) to be used during operation. Setting to > 0 overrides
r0313.
P0314 = 1: 2-pole motor
P0314 = 2: 4-pole motor
...
P0320[0...2] 0.0 - 99.0 0.0 C, T - DDS Float 3

Defines motor magnetization current relative to P0305 (rated motor current).


Setting 0 causes calculation by P0340 = 1 (data entered from rating plate) or by P3900 = 1 - 3 (end of
quick commissioning). The calculated value is displayed in r0331.
r0330[0...2] - - - PERCENT DDS Float 3
Displays nominal motor slip relative to P0310 (rated motor frequency) and P0311 (rated motor speed).
r0330[%] = ((P0310 - r0313 * (P0311/60))/P0310) * 100%
r0331[0...2] - - - - DDS Float 3

Displays calculated magnetizing current of motor.


r0332[0...2] - - - - DDS Float 3
Displays power factor for motor.
Value is calculated internally if P0308 (rated motor cos ) set to 0; otherwise, value entered in P0308 is
displayed.
r0333[0...2] - - - - DDS Float 3
Displays rated motor torque.
Value is calculated from P0307 (rated motor power) and P0311 (rated motor speed). r0333[Nm] =
(P0307[kW] * 1000)/((P0311[1/min]/60) * 2 * Pi)

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 221
Parameter list
8.2 Parameter list

P0335[0...2] 0-3 0 C, T - DDS U16 2


Selects motor cooling system used.
0 Self-cooled: Shaft mounted fan attached motor
1 Force-cooled: Separately powered cooling fan
2 Self-cooled and internal fan
3 Force-cooled and internal fan
P0340[0...2] 0-4 0 T - DDS U16 2

Calculates various motor parameters.


P0340 = 1 P0340 = 2 P0340 = 3 P0340 = 4
P0341[0...2] Motor inertia [kg*m^2] x
P0342[0...2] Total/motor inertia ratio x
P0344[0...2] Motor weight x
P0346[0...2] Magnetization time x x
P0347[0...2] Demagnetization time x x
P0350[0...2] Stator resistance (line-to-line) x x
P0352[0...2] Cable resistance x x
P0354[0...2] Rotor resistance x x
P0356[0...2] Stator leakage inductance x x
P0358[0...2] Rotor leakage inductance x x
P0360[0...2] Main inductance x x
P0625[0...2] Surrounding motor temperature x x
P1253[0...2] Controller output limitation x x
P1316[0...2] Boost end frequency x x
P1338[0...2] Resonance damping gain V/f x x x
P1341[0...2] Imax controller integral time x x x
P1345[0...2] Imax voltage ctrl. prop. gain x x x
P1346[0...2] Imax voltage ctrl. integral time x x x
P2002[0...2] Reference current x
P2003[0...2] Reference torque x
P2185[0...2] Upper torque threshold 1 x
P2187[0...2] Upper torque threshold 2 x
P2189[0...2] Upper torque threshold 3 x
0 No calculation
1 Complete parameterization
2 Calculation of equivalent circuit data
3 Calculation of V/f control data
4 Calculation of controller settings only
This parameter is required during commissioning to optimize converter performance. If there is a large
mismatch in Power ratings of converter to Motor it is possible that r0384 and r0386 may not be calculated
correctly. In these cases use P1900.
When transferring P0340, the converter uses its processor to carry out internal calculations. Communica-
tions to the converter may be interrupted.
The faults can be acknowledged as soon as the calculations have been completed in the converter. These
calculations can take approximately 10s to complete.

SINAMICS V20 Converter


222 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0341[0...2] 0.0001 - 0.0018 U, T - DDS Float 3


1000.0
Sets no-load inertia of motor.
Together with P0342 (inertia ratio total/motor) and P1496 (scaling factor acceleration), this value produces
the acceleration torque (r1518), which can be added to any additional torque produced from a BICO
source (P1511), and incorporated in the torque control function.
This parameter is influenced by automatic calculations defined by P0340.
The result of P0341 * P0342 is included in the speed controller calculation.
P0341 * P0342 = total motor inertia
P1496 = 100 % activates acceleration pre-control for the speed controller and calculates the torque from
P0341 and P0342.
P0342[0...2] 1.000 - 1.000 U, T - DDS Float 3
400.00
Specifies ratio between total inertia (load + motor) and motor inertia.
See P0341
P0344[0...2] 1.0 - 9.4 U, T - DDS Float 3
6500.0
Specifies motor weight [kg].
See P0341
This value is used in the motor thermal model. It is normally calculated automatically from P0340 (motor
parameters) but can also be entered manually. Default value is depending on converter type and its rating
data.
r0345[0...2] - - - - DDS Float 3
Displays motor start-up time. This time corresponds to the standardized motor inertia. The start-up time is
the time taken to reach rated motor speed from standstill at acceleration with rated motor torque (r0333).
P0346[0...2] 0.000 - 1.000 U, T - DDS Float 3
20.000
Sets magnetization time [s], i.e. waiting time between pulse enable and start of ramp-up. Motor magneti-
zation builds up during this time. Magnetization time is normally calculated automatically from the motor
data and corresponds to the rotor time constant.
See P0341
An excessive reduction of this time can result in insufficient motor magnetization.
If boost settings are higher than 100 %, magnetization time may be reduced. Default value is depending
on converter type and its rating data.
P0347[0...2] 0.000 - 1.000 U, T - DDS Float 3
20.000
Changes time allowed after OFF2/fault condition, before pulses can be re-enabled.
See P0341
Not active following a normally completed ramp-down, e.g. after OFF1, OFF3 or JOG. Overcurrent trips
will occur if the time is decreased excessively.
The demagnetization time is approximately 2.5 x rotor time constant in seconds. Default value is depend-
ing on converter type and its rating data.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 223
Parameter list
8.2 Parameter list

P0350[0...2] 0.00001 - 2.0000 U, T - DDS Float 3


2000.0
Stator resistance value for connected motor (line value). The parameter value doesn't include the cable
resistance.
See P0341
There are three ways to determine the value for this parameter:
• Calculate using
– P0340 = 1 (data entered from rating plate) or
– P0010 = 1, P3900 = 1, 2 or 3 (end of quick commissioning).
• Measure using P1900 = 2 (standard motor data identification - value for stator resistance is overwrit-
ten).
• Measure manually using an Ohmmeter.
Since the manually measured resistor is a line-to-line value, which includes the cable resistors, the meas-
ured value has to be divided by two and the cable resistor of a line has to be subtracted from that value.
The value entered in P0350 is the one obtained by the method last used. Default value is depending on
converter type and its rating data.
P0352[0...2] 0.0 - 120.0 0.0 U, T - DDS Float 3
Cable resistance value between converter and motor for one phase.
See P0341
P0354[0...2] 0.0 - 300.0 10.0 U, T - DDS Float 3
Sets rotor resistance of motor equivalent circuit (phase value).
Calculated automatically using the motor model or determined using P1900 (motor identification). This
parameter is influenced by automatic calculations defined by P0340.
P0356[0...2] 0.00001 - 10.000 U, T - DDS Float 3
1000.0
Sets stator leakage inductance of motor equivalent circuit (phase value).
See P0354
P0358[0...2] 0.0 - 10.0 U, T - DDS Float 3
1000.0
Sets rotor leakage inductance of motor equivalent circuit (phase value).
See P0354
P0360[0...2] 0.0 - 10.0 U, T - DDS Float 3
10000.0
Sets main inductance of the motor equivalent circuit (phase value).
See P0354
The data of equivalent circuit relates to the star equivalent circuit. Any data of the delta equivalent circuit
available therefore must be transformed to the star equivalent circuit before entering into the converter.
r0370[0...2] - - - PERCENT DDS Float 4
Displays standardized stator resistance of motor equivalent circuit (phase value).
r0372[0...2] - - - PERCENT DDS Float 4
Displays standardized cable resistance of motor equivalent circuit (phase value). It is estimated to be 20
% of the stator resistance.
r0373[0...2] - - - PERCENT DDS Float 4
Displays rated stator resistance of the motor equivalent circuit (phase value).

SINAMICS V20 Converter


224 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0374[0...2] - - - PERCENT DDS Float 4


Displays standardized rotor resistance of the motor equivalent circuit (phase value).
r0376[0...2] - - - PERCENT DDS Float 4
Displays rated rotor resistance of the motor equivalent circuit (phase value).
r0377[0...2] - - - PERCENT DDS Float 4

Displays standardized total leakage reactance of the motor equivalent circuit (phase value).
r0382[0...2] - - - PERCENT DDS Float 4
Displays standardized main reactance of the motor equivalent circuit (phase value).
r0384[0...2] - - - - DDS Float 3
Displays calculated rotor time constant.
r0386[0...2] - - - - DDS Float 4

Displays total leakage time constant of motor.


r0395 - - - PERCENT - Float 3

Displays stator resistance of motor of combined stator/cable resistance.


P0503[0...2] 0-1 0 T - - U16 3

Enables keep-running operation. This attempts to prevent the converter from tripping by enabling all pos-
sible existing de-rating features, and the automatic restart function. May be used with P2113 = 1 (convert-
er warnings disabled) to mask resulting warnings from the user.
0 Keep-running mode disabled
1 Keep-running mode enabled
[0] Drive data set 0 (DDS0)
[1] Drive data set 1 (DDS1)
[2] Drive data set 2 (DDS2)
P0503 = 1
Sets the following parameter values to minimize likelihood of a trip:
• P0290 = 2 (converter overload reaction: reduce pulse frequency, output current and output frequency)
• P1210 = 7 (automatic restart function: restart after mains brown- /blackout or fault, trip when P1211
expires)
• P1211 = 10 (number of times converter will attempt to restart)
• P1240 = 3 (configuration of Vdc controller: Vdc_max controller and kinetic buffering (KIB) enabled)
P0503 = 0
Resets the parameters to their default values:
• P0290 = 2 (converter overload reaction: reduce pulse frequency, output current and output frequency)
• P1210 = 1 (automatic restart function: trip reset after power on, P1211 disabled)
• P1211 = 3 (number of times converter will attempt to restart)
• P1240 = 1(configuration of Vdc controller: Vdc_max controller enabled)
See also P0290, P1210, P1211, P1240, and P2113

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 225
Parameter list
8.2 Parameter list

P0507 0 - 255 0 C(1) - - U16 1


Selects a given Application macro, which is a set of parameter values for a given application. There are a
number of application macros covering a set of basic applications such as simple pump, conveyor, com-
pressor etc.
Please note that to guarantee correct setting of the Application macro, the Application macro number
should only be changed during Setup directly after a parameter reset.
P0511[0...2] 0.00 - [0] 1.00 U, T - - Float 3
100.00 [1] 1.00
[2] 0.00
Allows operator to enter the scaling factors for the display of motor frequency.
Index 0 = value of multiplier (a)
Index 1 = value of divisor (b)
Index 2 = value of constant (c)
With the parameter set to a non-default value the displayed value for frequency and setpoint on internal
and external BOPs is scaled accordingly. Note - the units "Hz" is no longer displayed if the value is scaled.
The formula used to scale the display is: (a/b)*N + c.
[0] Multiplier for Scaling for display
[1] Divider for Scaling for display
[2] Constant for Scaling for display
r0512 - - - - - Float 2

Displays actual converter output frequency (r0024) excluding slip compensation (and resonance damping,
frequency limitation in V/f mode).
P0604[0...2] 0.0 - 200.0 130.0 U, T - DDS Float 2

Enters warning threshold for motor temperature protection. The trip temperature defined is always 10 %
higher than the warning threshold P0604. When actual motor temperature exceeds warning temperature
then converter reacts as defined in P0610.
This value should be at least 40°C higher than the motor surrounding temperature P0625.
P0610[0...2] 2 0-6 6 T - DDS U16 3

Defines reaction when motor temperature reaches warning threshold.


0 Warning only. Does not recall the motor temperature (stored at power down)
on power up
1 Warning with Imax control (motor current reduced) and trip (F11). Does not
recall the motor temperature (stored at power down) on power up
2 Warning and trip (F11). Does not recall the motor temperature (stored at
power down) on power up
4 Warning only. Recalls the motor temperature (stored at power down) on
power up
5 Warning with Imax control (motor current reduced) and trip (F11). Recalls
the motor temperature (stored at power down) on power up
6 Warning and trip (F11). Recalls the motor temperature (stored at power
down) on power up
Trip level = P0604 (motor temperature threshold) * 110 %

SINAMICS V20 Converter


226 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

• P0610 = 0 (No reaction, warning only)


When temperature reaches warning level defined in P0604, the converter displays warning A511, no reac-
tion is done.
• P0610 = 1 (Warning, Imax reduction and Trip)
When temperature reaches warning level defined in P0604, the converter displays warning A511, reduce
frequency and trips F11, when temperature exceeds the trip level.
• P0610 = 2 (Warning and trip F11)
When temperature reaches warning level defined in P0604, the converter displays warning A511 and trips
F11, when temperature exceeds the trip level.
The purpose of motor I2t is to calculate the motor temperature and disable the converter if the motor is in
danger of overheating.
I2t operation:
The measured motor current is displayed in r0027. The motor temperature in °C is displayed in r0035.
This temperature is derived from a calculated value using motor thermal model.
The reaction to the warning can be changed from this default using P0610.
r0035 is particularly useful to monitor if the calculated motor temperature is rising excessively.
P0622[0...2] 0.000 - 0.000 U, T - DDS Float 3
20000
Specifies the magnetization time for stator resistance identification.
r0623[0...2] - - - - DDS Float 4

Display of the actual identified stator resistance after temperature identification.


P0625[0...2] -40.0 - 80.0 20.0 C, U, T - DDS Float 3

Surrounding temperature of motor at time of motor data identification. It is only allowed to change the
value when the motor is cold. A motor identification has to be made after changing the value.
This parameter is influenced by automatic calculations defined by P0340.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 227
Parameter list
8.2 Parameter list

P0626[0...2] 20.0 - 200.0 50.0 U, T - DDS Float 4

Overtemperature of stator iron.


Temperature rises are valid for sinusoidal operations (line supply temperature rises). Temperature rises
due to converter operation (modulation losses) and output filter are also considered.
P0627[0...2] 20.0 - 200.0 80.0 U, T - DDS Float 4

Overtemperature of the stator winding. It is only allowed to change the value when the motor is cold. A
motor identification has to be made after changing the value.
See P0626
P0628[0...2] 20.0 - 200.0 100.0 U, T - DDS Float 4

Overtemperature of the rotor winding.


See P0626
r0630[0...2] - - - - DDS Float 4

Displays the surrounding temperature of the motor mass model.


r0631[0...2] - - - - DDS Float 4

Displays the iron temperature of the motor mass model.


r0632[0...2] - - - - DDS Float 4

Displays the stator winding temperature of the motor mass model.


r0633[0...2] - - - - DDS Float 4

Displays the rotor winding temperature of the motor mass model.


P0640[0...2] 10.0 - 400.0 150.0 C, U, T - DDS Float 2
Defines motor overload current limit relative to P0305 (rated motor current).
Limited to maximum converter current or to 400 % of rated motor current (P0305), whichever is the lower.
P0640_max = (min(r0209, 4 * P0305)/P0305) * 100
Changes to P0640 will be effective only after the next off state.
P0700[0...2] 0-5 1 C, T - CDS U16 1

Selects digital command source.


0 Factory default setting
1 Operator panel (keypad)
2 Terminal
5 USS/MODBUS on RS485
Changing this parameter sets (to default) all settings on item selected. These are the following parame-
ters: P0701, ... (function of digital input), P0840, P0842, P0844, P0845, P0848, P0849, P0852, P1020,
P1021, P1022, P1023, P1035, P1036, P1055, P1056, P1074, P1110, P1113, P1124, P1140, P1141,
P1142, P1230, P2103, P2104, P2106, P2200, P2220, P2221, P2222, P2223, P2235, P2236
Be aware, by changing of P0700 all BI parameters are reset to the default value.

SINAMICS V20 Converter


228 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

RS485 also supports MODBUS protocol as well as USS. All USS options on RS485 are also applicable to
MODBUS.
If P0700 = 0, the values of the following parameters relevant to the digital input function will be restricted
to their defaults: P0701, P0702, P0703, P0704, P0712 and P0713.

P0701[0...2] 0 - 99 0 T - CDS U16 2


Selects function of digital input 1.
0 Digital input disabled
1 ON/OFF1
2 ON reverse/OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp-down
5 ON/OFF2
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed frequency selector bit0
16 Fixed frequency selector bit1
17 Fixed frequency selector bit2
18 Fixed frequency selector bit3
22 QuickStop Source 1
23 QuickStop Source 2
24 QuickStop Override
25 DC brake enable
27 Enable PID
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Resetting 99 (enable BICO parameterization) requires:
• P0700 command source or
• P0010 = 1, P3900 = 1, 2 or 3 (quick commissioning) or
• P0010 = 30, P0970 = 1 factory reset in order to reset
"ON/OFF1" can only be selected for one digital input (e.g. P0700 = 2 and P0701 = 1). Configuring DI2 with
P0702 = 1 will disable digital input 1 by setting P0701 = 0. Only the last activated digital input serves as a
command source. "ON/OFF1" on a digital input can be combined with "ON reverse/OFF1" on another
digital input.
P0702[0...2] 0 - 99 0 T - CDS U16 2
Selects function of digital input 2.
See P0701.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 229
Parameter list
8.2 Parameter list

P0703[0...2] 0 - 99 9 T - CDS U16 2


Selects function of digital input 3.
See P0701.
P0704[0...2] 0 - 99 15 T - CDS U16 2
Selects function of digital input 4.
See P0701.
P0705[0...2] 0 - 99 16 T - CDS U16 2
Selects function of digital input 5.
See P0701.
This digital input is provided by the optional I/O Extension Module.
P0706[0...2] 0 - 99 17 T - CDS U16 2
Selects function of digital input 6.
See P0701.
This digital input is provided by the optional I/O Extension Module.
P0712[0...2] 0 - 99 0 T - CDS U16 2
Selects function of digital input AI1 (via analog input).
See P0701.
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0713[0...2] 0 - 99 0 T - CDS U16 2
Selects function of digital input AI2 (via analog input).
See P0701.
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0717 0 - 255 0 C(1) - - U16 1
Selects a given connection macro, which is a set of parameter values for a given set of control connec-
tions. There are a number of connection macros which define basic control connection settings such as
Terminals, BOP, PID with analog setpoint etc.
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2] 0 - 57 0 T - CDS U16 4

Central switch to select control command source for converter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command/setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
0 Cmd = BICO parameter, Setpoint = BICO parameter
1 Cmd = BICO parameter, Setpoint = MOP setpoint
2 Cmd = BICO parameter, Setpoint = Analog setpoint
3 Cmd = BICO parameter, Setpoint = Fixed frequency
4 Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
5 Cmd = BICO parameter, Setpoint = USS/MODBUS on RS485
7 Cmd = BICO parameter, Setpoint = Analog setpoint 2
40 Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
41 Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint

SINAMICS V20 Converter


230 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

42 Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint


43 Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
44 Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)
45 Cmd = USS on RS232 (reserved), Setpoint = USS/MODBUS on RS485
47 Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
50 Cmd = USS/MODBUS on RS485, Setpoint = BICO parameter
51 Cmd = USS/MODBUS on RS485, Setpoint = MOP setpoint
52 Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint
53 Cmd = USS/MODBUS on RS485, Setpoint = Fixed frequency
54 Cmd = USS/MODBUS on RS485, Setpoint = USS on RS232 (reserved)
55 Cmd = USS/MODBUS on RS485, Setpoint = USS/MODBUS on RS485
57 Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint 2
P0719 has higher priority than P0700 and P1000. If set to a value other than 0 (i.e. BICO parameter is not
the setpoint source), P0844/P0848 (first source of OFF2/OFF3) are not effective; instead, P0845/P0849
(second source of OFF2/OFF3) apply and the OFF commands are obtained via the particular source de-
fined. BICO connections made previously remain unchanged.
Particularly useful when e.g. changing command source temporarily from P0700 = 2. Settings in P0719
(contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
r0720 - - - - - U16 3
Displays number of digital inputs.
r0722.0...12 - - - - - U16 2
Displays status of digital inputs.

00 Digital input 1 Yes No


01 Digital input 2 Yes No
02 Digital input 3 Yes No
03 Digital input 4 Yes No
04 Digital input 5 Yes No
05 Digital input 6 Yes No
11 Analog input 1 Yes No
12 Analog input 2 Yes No
Segment is lit when signal is active.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
P0724 0-3 3 T - - U16 3

Defines debounce time (filtering time) used for digital inputs.


0 No debounce time
1 2.5 ms debounce time
2 8.2 ms debounce time
3 12.3 ms debounce time

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 231
Parameter list
8.2 Parameter list

P0727[0...2] 0-3 0 C, T - CDS U16 2

Determines the control method using the terminals. This parameter allows the selection of the control
philosophy. The control philosophies exclude each other.
2/3-wire control allows to start, stop and reverse the converter in one of the following ways:
• 2-wire control with Siemens standard control
using ON/OFF1 and REV as permanent signals

• 2-wire control with Siemens standard control


using ON/OFF1 and ON_REV/OFF1 as permanent signals

• 2-wire control
using ON_FWD and ON_REV as permanent signals

SINAMICS V20 Converter


232 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

• 3-wire control
using STOP as permanent signal, FWD and REVP as pulses

• 3 wire control
using OFF1/HOLD and REV as permanent signal, ON as pulse signal

0 Siemens (start/dir)
1 2-wire (fwd/rev)
2 3-wire (fwd/rev)
3 3-wire (start/dir)
Where:
• P denotes Pulse
• FWD denotes FORWARD
• REV denotes REVERSE
When any of the control functions are selected using P0727, the setting for the digital inputs (P0701 -
P0704) are redefined as follows:
Settings of P0701 P0727 = 0 (Siemens P0727 = 1 (2-wire P0727 = 2 (3- P0727 = 3 (3-wire
- P0706 Standard Control) Control) wire Control) Control)
= 1 (P0840) ON/OFF1 ON_FWD STOP ON_PULSE
= 2 (P0842) ON_REV/OFF1 ON_REV FWDP OFF1/HOLD
= 12 (P1113) REV REV REVP REV
To use the 2/3-wire control, the sources for ON/OFF1 (P0840), ON_REV/OFF1 (P0842) and REV (P1113)
corresponding to the redefined values have to be set accordingly.
The ON/OFF2 functionality is not supported in 2/3 wire modes. Do not select ON/OFF2 unless P0727 = 0.
Regarding the use of fixed frequencies see P1000 and P1001.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 233
Parameter list
8.2 Parameter list

r0730 - - - - - U16 3
Displays number of digital outputs.
P0731[0...2] 0 - 4294967295 52.3 U, T - CDS U32/Bi 2
n
Defines source of digital output 1.
An inverse logic can be realized by inverting the digital outputs in P0748.
Output of fault bit 52.3 is inverted on digital output. Therefore, with P0748 = 0, the digital output is set to
low when a fault is triggered, and when there is no fault, it is set to high.
Monitor functions ==> see r0052, r0053
Motor holding brake ==> see P1215
DC-Brake ==> see P1232, P1233
P0732[0...2] 0 - 4294967295 52.7 U, T - CDS U32/Bi 2
n
Defines source of digital output 2.
P0733[0...2] 0 - 4294967295 0 U, T - CDS U32/Bi 2
n
Defines source of digital output 3.
This digital output is provided by the optional I/O Extension Module.
P0734[0...2] 0 - 4294967295 0 U, T - CDS U32/Bi 2
n
Defines source of digital output 4.
This digital output is provided by the optional I/O Extension Module.
r0747.0...1 - - - - - U16 3

Displays status of digital outputs (also includes inversion of digital outputs via P0748).

00 Digital output 1 energized Yes No


01 Digital output 2 energized Yes No
02 Digital output 3 energized Yes No
03 Digital output 4 energized Yes No
Bit = 0 signal: Contacts open
Bit = 1 signal: Contacts closed
The digital output 3 and 4 are provided by the optional I/O Extension Module.
P0748 - 0000 bin U, T - - U16 3
Defines high and low states of digital output for a given function.

00 Invert digital output 1 Yes No


01 Invert digital output 2 Yes No
02 Invert digital output 3 Yes No
03 Invert digital output 4 Yes No
The digital output 3 and 4 are provided by the optional I/O Extension Module.
r0750 - - - - - U16 3
Displays number of analog inputs available.

SINAMICS V20 Converter


234 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0751.0...9 - - - - - U16 3

Displays status of analog input.

00 Signal lost on analog input 1 Yes No


01 Signal lost on analog input 2 Yes No
08 No signal lost on analog input 1 Yes No
09 No signal lost on analog input 2 Yes No
r0752[0...1] - - - - - Float 2

Displays smoothed analog input value in volts or milliamps before the scaling block.
[0] Analog input 1 (AI1)
[1] Analog input 2 (AI2)
P0753[0...1] 0 - 10000 3 U, T - - U16 3

Defines filter time (PT1 filter) for analog input.


See r0752
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
P0753 = 0: No filtering
r0754[0...1] - - - - - Float 2

Shows smoothed value of analog input after scaling block.


See r0752
P0757 to P0760 define range (analog input scaling).
r0755[0...1] - - - 4000H - I16 2

Displays analog input, scaled using ASPmin and ASPmax (ASP = analog setpoint).
Analog setpoint (ASP) from the analog scaling block can vary from minimum analog setpoint (ASPmin) to
a maximum analog setpoint (ASPmax).
The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384.
By associating r0755 with an internal value (e.g. frequency setpoint), a scaled value is calculated internally
by the converter.
The frequency value is calculated using the following equation:
r0755 [Hz] = (r0755 [hex]/4000 [hex]) * P2000 * (max (|ASP_max|, |ASP_min|)/100%)

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 235
Parameter list
8.2 Parameter list

Case a:
ASPmin = 300 %, ASPmax = 100 % then 16384 represents 300 %.
This parameter will vary from 5461 to 16384.
Case b:
ASPmin = -200 %, ASPmax = 100 % then 16384 represents 200 %.
This parameter will vary from -16384 to +8192.

See r0752
This value is used as an input to analog BICO connectors. ASPmax represents the highest analog set-
point (this may be at 10 V). ASPmin represents the lowest analog setpoint (this may be at 0 V). See
P0757 to P0760 (analog input scaling).
P0756[0...1] 0-4 0 T - - U16 2
Defines type of analog input and also enables analog input monitoring.
0 Unipolar voltage input (0 to 10 V)
1 Unipolar voltage input with monitoring (0 to 10 V)
2 Unipolar current input (0 to 20 mA)
3 Unipolar current input with monitoring (0 to 20 mA)
4 Bipolar voltage input (-10 V to 10 V)
See r0752
The monitoring function is disabled if the analog scaling block is programmed to output negative setpoints
(see P0757 to P0760).
When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F80) if
the analog input voltage falls below 50 % of the deadband voltage. It is not possible to select the bipolar
voltage for analog input 2.
For P0756 = 4, you need to ensure the analog input scaling, for example, if you desire to obtain an output
frequency within the range of -50 Hz to 50 Hz, you can set parameters P0757 to P0760 within their nega-
tive ranges (examples: P0757 = -10 V, P0758 = -100%).
See P0757 to P0760 (analog input scaling).
In current mode, if the input exceeds 24mA, the converter will trip F80/11 for analog input 1 and F80/12 for
analog input 2. This will result in channel switching back to voltage mode. Analog input parameter read-
ings for the channel concerned will no longer be updated until the fault (F80) has been reset. Once the
fault has been reset then the input will switch back to current mode and normal readings will resume.

SINAMICS V20 Converter


236 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0757[0...1] -20 - 20 0 U, T - - Float 2

P0757 - P0760 configure the input scaling. x1 is the first value of the two pairs of variants x1/y1 and x2/y2
which determine the straight line. The value x2 of analog input scaling P0759 must be greater than the
value x1 of analog input scaling P0757.
See r0752
• Analog setpoints represent a [%] of the normalized frequency in P2000.
• Analog setpoints may be larger than 100 %.
• ASPmax represents highest analog setpoint (this may be at 10 V or 20 mA).
• ASPmin represents lowest analog setpoint (this may be at 0 V or 20 mA).
• Default values provide a scaling of 0 V or 0 mA = 0 %, and 10 V or 20 mA = 100 %.
P0758[0...1] -99999.9 - 0.0 U, T - - Float 2
99999.9
Sets value of y1 as described in P0757 (analog input scaling)
See r0752
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is
to be generated.
P0759[0...1] -20 - 20 10 U, T - - Float 2

Sets value of x2 as described in P0757 (analog input scaling).


See r0752
The value x2 of analog input scaling P0759 must be greater than the value x1 of analog input scaling
P0757.
P0760[0...1] -99999.9 - 100.0 U, T - - Float 2
99999.9
Sets value of y2 as described in P0757 (analog input scaling).
See r0752
See P0758

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 237
Parameter list
8.2 Parameter list

P0761[0...1] 0 - 20 0 U, T - - Float 2

Defines width of deadband on analog input.


The following example produces a 2 V to 10 V, 0 Hz to 50 Hz analog input (analog input value 2 V to 10 V,
0 Hz to 50 Hz):
• P2000 = 50 Hz
• P0759 = 8 V P0760 = 75 %
• P0757 = 2 V P0758 = 0 %
• P0761 = 2 V
• P0756 = 0 or 1
The following example produces a 0 V to 10 V analog input (-50 Hz to +50 Hz) with center zero and a
"holding point" 0.2 V wide (0.1 V to each side of center, analog input value 0 V to 10 V, -50 Hz to +50 Hz):
• P2000 = 50 Hz
• P0759 = 8.75 V P0760 = 75 %
• P0757 = 1.25 V P0758 = -75 %
• P0761 = 0.1 V
• P0756 = 0 or 1
See r0752
Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of analog
input scaling) are positive or negative respectively. However, deadband is active in both directions from
point of intersection (x axis with analog input scaling curve), if sign of P0758 and P0760 are opposite.
P0761[x] = 0: No deadband active.
Minimum frequency P1080 should be zero when using center zero setup.
There is no hysteresis at the end of the deadband.
P0762[0...1] 0 - 10000 10 U, T - - U16 3

Defines time delay between loss of analog setpoint and appearance of fault code F80.
See r0752
Expert users can choose the desired reaction to F80 (default is OFF2).
r0770 - - - - - U16 3
Displays number of analog outputs available.
P0771[0] 0 - 4294967295 21[0] U, T - - U32 2
Defines function of the analog output.
[0] Analog output 1 (AO1)
21 CO: Actual frequency (scaled to P2000)
24 CO: Actual output frequency (scaled to P2000)
25 CO: Actual output voltage (scaled to P2001)
26 CO: Actual DC-link voltage (scaled to P2001)
27 CO: Actual output current (scaled to P2002)
P0773[0] 0 - 1000 2 U, T - - U16 2

Defines smoothing time for analog output signal. This parameter enables smoothing for analog output
using a PT1 filter.
See P0771
P0773 = 0: Deactivates filter.

SINAMICS V20 Converter


238 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0774[0] - - - - - Float 2

Shows value of analog output after filtering and scaling.


See P0771
The analog output is only a current output. By connecting an external resistor of 500 to the terminals
(4/5) a voltage output with a range of 0 V to 10 V can be created.
P0775[0] 0-1 0 T - - U16 2

Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute
value to be outputted. If the value was originally negative then the corresponding bit in r0785 is set, oth-
erwise it is cleared.
See P0771
P0777[0] -99999 - 99999 0.0 U, T - - Float 2

Defines x1 output characteristic. Scaling block is responsible for adjustment of output value defined in
P0771 (analog output connector input). x1 is the first value of the two pairs of variants x1/y1 and x2/y2
which determine the straight line. The two points P1 (x1, y1) and P2 (x2, y2) can be chosen freely.
See P0771
See P0758
P0778[0] 0 - 20 0 U, T - - Float 2

Defines y1 of output characteristic.


See P0771
P0779[0] -99999 - 99999 100.0 U, T - - Float 2

Defines x2 of output characteristic.


See P0771
See P0758
P0780[0] 0 - 20 20 U, T - - Float 2

Defines y2 of output characteristic.


See P0771
P0781[0] 0 - 20 0 U, T - - Float 2

Sets width of dead-band for analog output.


See P0771
r0785.0 - - - - - U16 2

Displays status of analog output. Bit 0 indicates that the value of analog output 1 is negative.

00 Analog output 1 negative Yes No

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 239
Parameter list
8.2 Parameter list

P0802 0-2 0 C(30) - - U16 3

Transfers values from the converter to external device when P0802 0. P0010 must be set to 30 for this
to be possible.
0 Disabled
2 Start data transfer to the SD card
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
Ensure that enough space exists on the SD card before transferring data (8 KB).
P0803 0-3 0 C(30) - - U16 3

0 Disabled
2 Start data transfer from the SD card
3 Start data transfer from the SD card (except the motor data)
Transfers parameter values from the SD clone file to the converter when P0803 0. P0010 must be set to
30 to activate this parameter. See P0802 for parameter values.
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
P0804 0 - 99 0 C(30) - - U16 3
Select clone file to upload/download.
if P0804 = 0, then the file name is clone00.bin
if P0804 = 1, then the file name is clone01.bin
etc.
P0806 0 - 4294967295 0 U, T - - U32 3
Binector input to lock control panel access through external client.
r0807.0 - - - - - U16 3

Binector output to display whether command and setpoint source is connected to an external client.

00 Master control active Yes No


P0809[0...2] 0-2 [0] 0 [1] 1 T - - U16 2
[2] 0
Calls 'Copy command data set (CDS)' function. The list of all command data sets (CDS) parameters is
shown in "Index" at the end of the manual.
Copying of all values from CDS0 to CDS2 can be accomplished by the following procedure:
P0809[0] = 0 Copy from CDS0
P0809[1] = 2 Copy to CDS2
P0809[2] = 1 Start copy
[0] Copy from CDS
[1] Copy to CDS
[2] Start copy
Start value in index 2 is automatically reset to '0' after execution of function.

SINAMICS V20 Converter


240 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0810 0 - 4294967295 0 U, T - - U32 2

Selects command source from which to read Bit 0 for selecting a command data set (CDS). The actual
selected CDS is displayed in r0054.15 (CDS bit 0) and r0055.15 (CDS bit 1). The actual active CDS is
displayed in r0050.
722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
P0811 is also relevant for command data set (CDS) selection.
P0811 0 - 4294967295 0 U, T - - U32 2

Selects command source from which to read Bit 1 for selecting a command data set (see P0810).
See P0810.
P0810 is also relevant for command data set (CDS) selection.
P0819[0...2] 0-2 [0] 0 [1] 1 T - - U16 2
[2] 0
Calls 'Copy drive data set (DDS)' function. The list of all drive data set (DDS) parameters is shown in
"Index" at the end of the manual.
Copying of all values from DDS0 to DDS2 can be accomplished by the following procedure:
P0819[0] = 0 Copy from DDS0
P0819[1] = 2 Copy to DDS2
P0819[2] = 1 Start copy
[0] Copy from DDS
[1] Copy to DDS
[2] Start copy
See P0809
P0820 0 - 4294967295 0 T - - U32 3
Selects command source from which to read Bit 0 for selecting a drive data set (DDS). The actual select-
ed drive data set (DDS) is displayed in parameter r0051[0]. The actual active drive data set (DDS) is dis-
played in parameter r0051[1].
See P0810
P0821 is also relevant for drive data set (DDS) selection.
P0821 0 - 4294967295 0 T - - U32 3
Selects command source from which Bit 1 for selecting a drive data set is to be read in (see P0820).
See P0810
P0820 is also relevant for drive data set (DDS) selection.
P0840[0...2] 0 - 4294967295 19.0 T - CDS U32 3
Allows ON/OFF1 command source to be selected using BICO. The digits in front of the colon show the
parameter number of the command source; the digits following the colon denote the bit setting for that
parameter.
See P0810
For digital inputs as command source BICO requires P0700 set to 2 (enable BICO). The default setting
(ON right) is digital input 1 (722.0). Alternative source possible only when function of digital input 1 is
changed (via P0701) before changing value of P0840.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 241
Parameter list
8.2 Parameter list

P0842[0...2] 0 - 4294967295 0 T - CDS U32 3


Allows ON/OFF1 reverse command source to be selected using BICO. In general a positive frequency
setpoint is run up counterclockwise (negative frequency).
See P0810
P0843[0...2] BI: ON/OFF2 0 - 4294967295 1 T - CDS U32/B 3
in
Allows ON/OFF2 command source to be selected using BICO. The default setting 1.0 will disable this parameter.
See P0810
For digital inputs as command source BICO requires P0700 set to 2 (enable BICO). If one of the digital
inputs is selected for ON/OFF2, the converter will not run unless the digital input is active. OFF2 means
immediate pulse-disabling; the motor is coasting. OFF2 is low-active, i.e. :0 = Pulse disabling. 1 = Pulses
enabled. (As long as there are no other OFF conditions active).
The ON/OFF2 functionality is not supported in 2/3 wire modes. Do not select ON/OFF2 unless P0727 = 0.
P0844[0...2] 0 - 4294967295 19.1 T - CDS U32 3
Defines first source of OFF2 when P0719 = 0 (BICO).
See P0810
If one of the digital inputs is selected for OFF2, the converter will not run unless the digital input is active.
OFF2 means immediate pulse-disabling; the motor is coasting. OFF2 is low-active, i.e.:
0 = Pulse disabling.
1 = Operating condition.
P0845[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines second source of OFF2.
See P0810
In contrast to P0844 (first source of OFF2), this parameter is always active, independent of P0719 (selec-
tion of command and frequency setpoint). See P0844.
See P0844
P0848[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines first source of OFF3 when P0719 = 0 (BICO).
See P0810
If one of the digital inputs is selected for OFF3, the converter will not run unless the digital input is active.
OFF3 means quick ramp-down to 0.
OFF3 is low-active, i.e.
0 = Quick ramp-down.
1 = Operating condition.
P0849[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines second source of OFF3.
See P0810
In contrast to P0848 (first source of OFF3), this parameter is always active, independent of P0719 (selec-
tion of command and frequency setpoint). See P0848.
See P0848
P0852[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines source of pulse enable/disable signal.
See P0810
Active only when P0719 = 0 (Auto selection of command/setpoint source).

SINAMICS V20 Converter


242 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P0881[0...2] 0 - 4294967295 1 T - CDS U32 3


Allows quick stop source 1 command to be selected using BICO. The signal is expected to be active low
(default setting P0886 = 2).
See P0810
P0882[0...2] 0 - 4294967295 1 T - CDS U32 3
Allows quick stop source 2 command to be selected using BICO. The signal is expected to be active low
(default setting P0886 = 2).
See P0810
P0883[0...2] 0 - 4294967295 0 T - CDS U32 3
Allows quick stop override command source to be selected using BICO. The signal is expected to be
active high.
See P0810
P0886[0...2] 0-4 2 T - CDS U16 3
Control Word for selecting the quick stop input type.
0 Quick stop not selected
1 Quick stop input active high
2 Quick stop input active low
3 Quick stop input positive edge triggered
4 Quick stop input negative edge triggered
P0927 0 - 31 31 U, T - - U16 2

Specifies the interfaces which can be used to change parameters. This parameter allows the user to easi-
ly protect the converter from unauthorized modification of parameters.
Annotation: P0927 is not password protected.

00 Not used Yes No


01 BOP (including built-in BOP and external BOP) Yes No
02 USS on RS232 Yes No
03 USS on RS485 Yes No
04 Script terminal on RS485 Yes No
Default: All bits are set.
The default setting allows parameters to be changed via any interface.
r0944 - - - - - U16 3

Displays the total number of messages available.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 243
Parameter list
8.2 Parameter list

r0947[0...63] - - - - - U16 2
Displays fault history.

[0] Recent fault trip --, fault 1


... ...
[7] Recent fault trip --, fault 8
[8] Recent fault trip -1, fault 1
... ...
[15] Recent fault trip -1, fault 8
[16] Recent fault trip -2, fault 1
... ...
[23] Recent fault trip -2, fault 8
... ...
[63] Recent fault trip -7, fault 8
It is possible that this parameter is empty but a fault is still indicated by the converter. The reason for this
is most likely due to a SAFE condition still existing in the system. In this situation the fault is cleared from
this parameter and it makes no sense to go back to a READY state. First remove the reason for the SAFE
condition and then the converter will be able to change to a READY state (SAFE condition example is
"safety function is activated").
The function "converter status at fault" (Page 341) serves as a snapshot record in time of the relative
parameters being monitored at the point of a fault occurring. Some recorded parameters are filtered val-
ues. Therefore if a hardware trip occurs, (r0949 = 0), some filtered values may not appear to reflect those
values which caused the trip.
If a hardware overvoltage trip occurs, (r0947 = 2 and r0949 = 0), the value of the filtered DC link voltage in
r0956 may appear to be under the trip limit. In this case, the filtered DC link value had not had enough
time to rise to the trip level; however, the actual limit had been exceeded and hence the hardware had
tripped to protect itself.

SINAMICS V20 Converter


244 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0948[0...63] - - - - - U32 3
Time stamp to indicate when a fault has occurred.
P0969 (system run time counter) is the possible source of the time stamp.
[0] Recent fault trip --, fault time 1
... ...
[7] Recent fault trip --, fault time 8
[8] Recent fault trip -1, fault time 1
... ...
[15] Recent fault trip -1, fault time 8
[16] Recent fault trip -2, fault time 1
... ...
[23] Recent fault trip -2, fault time 8
... ...
[63] Recent fault trip -7, fault time 8
r0949[0...63] - - - - - U32 3
Displays converter fault values. It is for service purposes and indicates the type of fault reported.
The values are not documented. They are listed in the code where faults are reported.
[0] Recent fault trip --, fault value 1
... ...
[7] Recent fault trip --, fault value 8
[8] Recent fault trip -1, fault value 1
... ...
[15] Recent fault trip -1, fault value 8
[16] Recent fault trip -2, fault value 1
... ...
[23] Recent fault trip -2, fault value 8
... ...
[63] Recent fault trip -7, fault value 8
P0952 0 - 65535 0 T - - U16 3
Displays number of trips stored in r0947 (last fault code).
Setting 0 resets fault history (changing to 0 also resets r0948 - fault time).
If the source of a non-momentary fault remains active before a factory reset, the converter removes the
source first and then places the fault into the fault history during a factory reset. That means P0952 still
has a non-zero value after the factory reset. If you want to clear the fault history, you need to perform a
second factory reset or set P0952 = 0.
r0954[0...2] - - - - - Float 3

Displays the setpoint after RFG when the first instantaneous fault occurs (see r1170).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0954[0] corresponds to
r0947[0...7], r0954[1] corresponds to r0947[8...15] and r0954[2] corresponds to r0947[16...23].

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 245
Parameter list
8.2 Parameter list

r0955[0...2] - - - - - U16 3

Displays status word 2 when the first instantaneous fault occurs (see r0053).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0955[0] corresponds to
r0947[0...7], r0955[1] corresponds to r0947[8...15] and r0955[2] corresponds to r0947[16...23].
r0956[0...2] - - - - - Float 3

Displays the DC link voltage when the first instantaneous fault occurs (see r0026).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0956[0] corresponds to
r0947[0...7], r0956[1] corresponds to r0947[8...15] and r0956[2] corresponds to r0947[16...23].
r0957[0...2] - - - - - Float 3

Displays the output current RMS when the first instantaneous fault occurs (see r0027).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0957[0] corresponds to
r0947[0...7], r0957[1] corresponds to r0947[8...15] and r0957[2] corresponds to r0947[16...23].
r0958[0...2] - - - - - Float 3

Displays the output voltage when the first instantaneous fault occurs (see r0025).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0958[0] corresponds to
r0947[0...7], r0958[1] corresponds to r0947[8...15] and r0958[2] corresponds to r0947[16...23].
r0964[0...6] - - - - - U16 3
Firmware version data.
[0] Company (Siemens = 42)
[1] Product type (V20 = 8001)
[2] Firmware version
[3] Firmware date (year)
[4] Firmware date (day/month)
[5] Number of converter objects
[6] Firmware version
r0967 - - - - - U16 3
Displays control word 1. See r0054 for the bit field description.

SINAMICS V20 Converter


246 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0968 - - - - - U16 3
Displays active status word of converter (in binary) and can be used to diagnose which commands are
active. See r0052 for the bit field description.
P0969 0 - 4294967295 0 T - - U32 3

Resettable system run time counter.


P0970 0 - 21 0 C(30) - - U16 1
P0970 = 1 resets all parameters (not user defaults) to their default values.
P0970 = 21 resets all parameters and all user defaults to Factory Reset state.
When resetting all parameters by setting P0970 = 1 or P0970 = 21, please note the following aspects:
• When you reset parameters through the BOP, parameters in both RAM and EEPROM are reset.
• When you select USS/MODBUS communication on RS485 and the volatile storage mode (P0014[0] =
0), only parameters in RAM are reset.
• When you select USS/MODBUS communication on RS485 and the non-volatile storage mode
(P0014[0] =1), parameters in both RAM and EEPROM are reset.
0 Disabled
1 Parameter reset
21 User Default Parameter Reset
First set P0010 = 30 (factory settings).
Stop converter (i.e. disable all pulses) before you can reset parameters to default values.
The following parameters retain their values after a factory reset:
• r0039 CO: Energy consumption meter [kWh]
• P0014 Store mode
• P0100 Europe/North America
• P0205 Converter application
• P2010 USS/MODBUS baudrate
• P2011 USS address
• P2021 MODBUS address
• P2023 RS485 protocol selection
• P8458 Clone control
When transferring P0970, the converter uses its processor to carry out internal calculations. Communica-
tions are interrupted for the time that it takes to make these calculations.
P0971 0 - 21 0 U, T - - U16 3

Transfers values from RAM to EEPROM when set to 1.


Transfers new user default values from RAM to EEPROM when set to 21.
0 Disabled
1 Start transfer
21 Start User Defaults transfer

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 247
Parameter list
8.2 Parameter list

All values in RAM are transferred to EEPROM.


Parameter is automatically reset to 0 (default) after successful transfer.
The storage from RAM to EEPROM is accomplished via P0971. The communications are reset, if the
transfer was successful. During the reset process communications will be interrupted.
• BOP displays 88888
After completion of the transfer process, the communication between the converter and external periph-
erals (BOP, USS or Modbus Master) is automatically re-established.
r0980[0...99] 0 - 65535 981 - - - U16 4

Contains 100 parameter numbers index 0 - 99.


[0] Parameter 1
[1] Parameter 2
... ...
[98] Parameter 99
[99] Next parameter list
The parameter list array has 2 elements to reduce memory consumption. On each access to an element
index 0 - 99, the individual result is determined dynamically by the 'BeforeAccess' function. The last ele-
ment contains the number of the following parameter array, 0 indicates end of list.
r0981[0...99] 0 - 65535 982 - - - U16 4

Contains 100 parameter numbers index 100 - 199.


See r0980
See r0980
r0982[0...99] 0 - 65535 983 - - - U16 4

Contains 100 parameter numbers index 200 - 299.


See r0980
See r0980
r0983[0...99] 0 - 65535 984 - - - U16 4

Contains 100 parameter numbers index 300 - 399.


See r0980
See r0980
r0984[0...99] 0 - 65535 985 - - - U16 4

Contains 100 parameter numbers index 400 - 499.


See r0980
See r0980
r0985[0...99] 0 - 65535 986 - - - U16 4

Contains 100 parameter numbers index 500 - 599.


See r0980
See r0980

SINAMICS V20 Converter


248 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r0986[0...99] 0 - 65535 987 - - - U16 4

Contains 100 parameter numbers index 600 - 699.


See r0980
See r0980
r0987[0...99] 0 - 65535 988 - - - U16 4

Contains 100 parameter numbers index 700 - 799.


See r0980
See r0980
r0988[0...99] 0 - 65535 989 - - - U16 4

Contains 100 parameter numbers index 800 - 899.


See r0980
See r0980
r0989[0...99] 0 - 65535 0 - - - U16 4

Contains 100 parameter numbers index 900 - 999.


See r0980
See r0980
P1000[0...2] 0 - 77 1 C, T - CDS U16 1

Selects frequency setpoint source. The main setpoint is given by the least significant digit (right-hand
position) and the additional setpoint is given by the most significant digit (left-hand position). Single digits
denote main setpoints that have no additional setpoint.

0 No main setpoint
1 MOP setpoint
2 Analog setpoint 1

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 249
Parameter list
8.2 Parameter list

3 Fixed frequency
5 USS/MODBUS on RS485
7 Analog setpoint 2
10 No main setpoint + MOP setpoint
11 MOP setpoint + MOP setpoint
12 Analog setpoint 1 + MOP setpoint
13 Fixed frequency + MOP setpoint
15 USS/MODBUS on RS485 + MOP setpoint
17 Analog setpoint 2 + MOP setpoint
20 No main setpoint + Analog setpoint 1
21 MOP setpoint + Analog setpoint 1
22 Analog setpoint 1 + Analog setpoint 1
23 Fixed frequency + Analog setpoint 1
25 USS/MODBUS on RS485 + Analog setpoint 1
27 Analog setpoint 2 + Analog setpoint 1
30 No main setpoint + Fixed frequency
31 MOP setpoint + Fixed frequency
32 Analog setpoint 1 + Fixed frequency
33 Fixed frequency + Fixed frequency
35 USS/MODBUS on RS485 + Fixed frequency
37 Analog setpoint 2 + Fixed frequency
50 No main setpoint + USS/MODBUS on RS485
51 MOP setpoint + USS/MODBUS on RS485
52 Analog setpoint 1 + USS/MODBUS on RS485
53 Fixed frequency + USS/MODBUS on RS485
55 USS/MODBUS on RS485 + USS/MODBUS on RS485
57 Analog setpoint 2 + USS/MODBUS on RS485
70 No main setpoint + Analog setpoint 2
71 MOP setpoint + Analog setpoint 2
72 Analog setpoint 1 + Analog setpoint 2
73 Fixed frequency + Analog setpoint 2
75 USS/MODBUS on RS485 + Analog setpoint 2
77 Analog setpoint 2 + Analog setpoint 2
Related parameter: P1074 (BI: Disable additional setpoint)
Changing this parameter sets (to default) all settings on item selected. These are the following parame-
ters: P1070, P1071, P1075, P1076
If P1000 = 1 or 1X, and P1032 (inhibit reverse direction of MOP) = 1, then reverse motor direction will be
inhibited.
RS485 also supports MODBUS protocol as well as USS. All USS options on RS485 are also applicable to
MODBUS. To alter the setpoint using the BOP when the command source P0700 is not set to 1, you must
check that P1035 is set to r0019 bit 13 and P1036 is set to r0019 bit 14.

SINAMICS V20 Converter


250 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1001[0...2] -550.00 - 550.00 10.00 U, T - DDS Float 2


Defines fixed frequency setpoint 1. There are 2 types of fixed frequencies:
• Direct selection (P1016 = 1):
– In this mode, 1 fixed frequency selector (P1020 to P1023) selects 1 fixed frequency (P1001 to
P1004).
– If several inputs are active together, the selected frequencies are summed.
Example: fixed frequency 1 (P1001) + fixed frequency 2 (P1002) + fixed frequency 3 (P1003) +
fixed frequency 4 (P1004).
• Binary coded selection (P1016 = 2):
– Up to 16 different fixed frequency values can be selected using this method.

See P1020 to P1023 for assigning desired digital inputs to the fixed frequency bits.
Select fixed frequency operation (using P1000).
Converter requires ON command to start in the case of direct selection. Therefore r1025 must be con-
nected to P0840 to start.
Fixed frequencies can be selected using the digital inputs.
P1002[0...2] -550.00 - 550.00 15.00 U, T - DDS Float 2
Defines fixed frequency setpoint 2.
See P1001

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 251
Parameter list
8.2 Parameter list

P1003[0...2] -550.00 - 550.00 25.00 U, T - DDS Float 2


Defines fixed frequency setpoint 3.
See P1001
P1004[0...2] -550.00 - 550.00 50.00 U, T - DDS Float 2
Defines fixed frequency setpoint 4.
See P1001
P1005[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 5.
See P1001
P1006[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 6.
See P1001
P1007[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 7.
See P1001
P1008[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 8.
See P1001
P1009[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 9.
See P1001

SINAMICS V20 Converter


252 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1010[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2


Defines fixed frequency setpoint 10.
See P1001
P1011[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 11.
See P1001
P1012[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 12.
See P1001
P1013[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 13.
See P1001
P1014[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 14.
See P1001
P1015[0...2] -550.00 - 550.00 0.00 U, T - DDS Float 2
Defines fixed frequency setpoint 15.
See P1001
P1016[0...2] 1-2 1 T - DDS U16 2
Fixed frequencies can be selected in two different modes. P1016 defines the mode.
1 Direct selection
2 Binary selection
See P1001 for description of how to use fixed frequencies.
P1020[0...2] 0 - 4294967295 722.3 T - CDS U32 3

Defines origin of fixed frequency selection.


= 722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
= 722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
= 722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
= 722.3 Digital input 4 (requires P0704 to be set to 99, BICO)
Accessible only if P0701 - P070x = 99 (function of digital inputs = BICO)
P1021[0...2] 0 - 4294967295 722.4 T - CDS U32 3

See P1020
P1022[0...2] 0 - 4294967295 722.5 T - CDS U32 3

See P1020
P1023[0...2] 0 - 4294967295 722.6 T - CDS U32 3

See P1020

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 253
Parameter list
8.2 Parameter list

r1024 - - - - - Float 3

Displays sum total of selected fixed frequencies.


r1025.0 - - - - - U16 3

Displays the status of fixed frequencies.

00 Status of FF Yes No
P1031[0...2] 0-3 1 U, T - DDS U16 2
MOP mode specification.

00 Setpoint store active Yes No


01 No On-state for MOP necessary Yes No
Defines the operation mode of the motorized potentiometer. See P1040.
P1032 0-1 1 T - - U16 2

Inhibits reverse setpoint selection of the MOP.


0 Reverse direction is allowed
1 Reverse direction inhibited
It is possible to change motor direction using the motor potentiometer setpoint (increase/decrease fre-
quency).
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
frequency).
If P1032 = 1 and P1000 = 1 or 1X, then reverse motor direction will be inhibited.
P1035[0...2] 0 - 4294967295 19.13 T - CDS U32 3

Defines source for motor potentiometer setpoint increase frequency.


722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator accelerates with the rate of
P1047.
P1036[0...2] 0 - 4294967295 19.14 T - CDS U32 3

Defines source for motor potentiometer setpoint decrease frequency.


See P1035
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator decelerates with the rate of
P1048.
P1040[0...2] -550.00 - 550.00 5.00 U, T - DDS Float 2
Determines setpoint for motor potentiometer control (P1000 = 1).
Motor potentiometer (P1040) must be chosen as main setpoint or additional setpoint (using P1000).

SINAMICS V20 Converter


254 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse direc-
tion will be inhibited by default of P1032 (inhibit reverse direction of MOP). To re-enable reverse direction,
set P1032 = 0.
A short press of the 'up' or 'down' keys (e.g.: operator panel) will change the frequency setpoint in steps of
0.1 Hz. A longer press will cause an accelerated frequency setpoint change.
The start value gets active (for the MOP output) only at the start of the MOP. P1031 influences the start
value behavior as follows:
• P1031 = 0: Last MOP setpoint not saved in P1040
MOP UP/DOWN requires an ON command to become active.
• P1031 = 1: Last MOP setpoint saved in P1040 on every OFF
MOP UP/DOWN requires an ON command to become active (default).
• P1031 = 2: Last MOP setpoint not saved in P1040
MOP UP/DOWN active without additional ON command.
• P1031 = 3: Last MOP setpoint saved in P1040 on powering up
MOP UP/DOWN active without additional ON command.
P1041[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source to change over from manual to automatic mode. If using the motorized potentiome-
ter in the manual mode the setpoint is changed using two signals for up and down e.g. P1035 and P1036.
If using the automatic mode the setpoint must be interconnected via the connector input (P1042).
0: manually
1: automatically
Refer to: P1035, P1036, P1042
P1042[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setpoint of the motorized potentiometer if automatic mode P1041 is select-
ed.
Refer to: P1041
P1043[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source for the setting command to accept the setting value for the motorized potentiome-
ter. The value becomes effective for a 0/1 edge of the setting command.
Refer to: P1044
P1044[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0/1 edge of
the setting command.
Refer to: P1043
r1045 - - - - - Float 3

Displays the motorized potentiometer setpoint before it passed the MOP RFG.
P1047[0...2] 0.00 - 1000.00 10.00 U, T - DDS Float 2

Sets the ramp-up time for the internal MOP ramp-function generator. The setpoint is changed from zero
up to limit defined in P1082 within this time.
Refer to: P1048, P1082

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 255
Parameter list
8.2 Parameter list

P1048[0...2] 0.00 - 1000.0 10.00 U, T - DDS Float 2

Sets the ramp-down time for the internal MOP ramp-function generator. The setpoint is changed from limit
defined in P1082 down to zero within this time.
Refer to: P1047, P1082
r1050 - - - - - Float 2

Displays output frequency of motor potentiometer setpoint.


P1055[0...2] 0 - 4294967295 19.8 T - CDS U32 3
Defines source of JOG right when P0719 = 0 (Auto selection of command/setpoint source).
P1056[0...2] 0 - 4294967295 0 T - CDS U32 3
Defines source of JOG left when P0719 = 0 (Auto selection of command/setpoint source).
P1057 0-1 1 T - - U16 3
While JOG enable is '0' Jogging (P1056 and P1055) is disabled. When '1' Jogging is enabled.
P1058[0...2] 0.00 - 550.00 5.00 U, T - DDS Float 2
Jogging increases the motor speed by small amounts. The JOG mode allows the operator to perform a
specific number of revolutions and position the rotor manually. In JOG mode, the RUN button on the op-
erator panel for jogging uses a non-latching switch on one of the digital inputs to control the motor speed.
While jogging, P1058 determines the frequency at which the converter will run. The motor speed is in-
creased as long as 'JOG left' or 'JOG right' are selected and until the left or right JOG frequency is
reached.
P1060 and P1061 set up and down ramp times respectively for jogging. Rounding times (P1130 - P1133),
rounding type (P1134) and P2167 will also have influence on the JOG ramp.
P1059[0...2] 0.00 - 550.00 5.00 U, T - DDS Float 2
While JOG left is selected, this parameter determines the frequency at which the converter will run.
P1060 and P1061 set up and down ramp times respectively for jogging.
P1060[0...2] 0.00 - 650.00 10.00 U, T - DDS Float 2
Sets jog ramp-up time. This is the time used while jogging is active.
See also P3350, P3353.
Ramp times will be used as follows:
• P1060/P1061 : JOG mode is active
• P1120/P1121 : Normal mode (ON/OFF) is active
• P1060/P1061 : Normal mode (ON/OFF) and P1124 is active
The rounding of P1130 - P1133 also applies to the JOG ramping.
If the SuperTorque function is enabled, the converter will initially ramp using the value in P3353.
P1061[0...2] 0.00 - 650.00 10.00 U, T - DDS Float 2
Sets ramp-down time. This is the time used while jogging is active.
See also P3350, P3353.
See P1060
P1070[0...2] 0 - 4294967295 1050[0] T - CDS U32 3
Defines source of main setpoint.
755 Analog input 1 setpoint
1024 Fixed frequency setpoint
1050 Motor potentiometer (MOP) setpoint

SINAMICS V20 Converter


256 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1071[0...2] 0 - 4294967295 1 T 4000H CDS U32 3


Defines source of the main setpoint scaling.
See P1070
P1074[0...2] 0 - 4294967295 0 U, T - CDS U32 3

Disables additional setpoint.


See P1070
P1075[0...2] 0 - 4294967295 0 T - CDS U32 3
Defines source of the additional setpoint (to be added to main setpoint).
See P1070
P1076[0...2] 0 - 4294967295 [0] 1 T 4000H CDS U32 3
[1] 0
[2] 1
Defines source of scaling for additional setpoint (to be added to main setpoint).
1 Scaling of 1.0 (100%)
755 Analog input 1 setpoint
1024 Fixed frequency setpoint
1050 MOP setpoint
r1078 - - - - - Float 3

Displays sum of main and additional setpoints.


r1079 - - - - - Float 3

Displays selected frequency setpoint. Following frequency setpoints are displayed:


• r1078 Total frequency setpoint
• P1058 JOG frequency right
• P1059 JOG frequency left
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
left respectively.
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
P1080[0...2] 0.00 - 550.00 0.00 C, U, T - DDS Float 1
Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The minimum
frequency P1080 represents a masking frequency of 0 Hz for all frequency target value sources e.g. ana-
log input, MOP, FF, USS with the exception of the JOG target value source (analogous to P1091). Thus
the frequency band +/-P1080 is run through in optimum time by means of the acceleration/deceleration
ramps. Dwelling in the frequency band is not possible. Furthermore, an overshoot of the actual frequency
f_act upper minimum frequency P1080 is output by the signal function |f_act| > f_min.
Value set here is valid both for clockwise and for counterclockwise rotation.
Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 257
Parameter list
8.2 Parameter list

P1082[0...2] 0.00 - 550.00 50.00 C, T - DDS Float 1


Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value
set here is valid for both clockwise and counterclockwise rotation.
Furthermore, the monitoring function |f_act| >= P1082 (r0052 bit 10, see example below) is affected by
this parameter.

The maximum value of P1082 also depends on the nominal frequency: Max. P1082 = min (15*P0310,
550.0 Hz). As consequence P1082 can be affected if P0310 is changed to a smaller value. The maximum
frequency and the pulse frequency depending on each other. The maximum frequency affects the pulse
frequency according to the following table.
P1800
2 kHz 4 kHz 6 kHz 8 - 16 kHz
fmax P1082 0 - 133.3 Hz 0 - 266.6 Hz 0 - 400 Hz 0 - 550.0 Hz
Example:
If P1082 is set to 350 Hz a pulse frequency from at least 6 kHz is necessary. If P1800 is smaller than 6
kHz the parameter is changed P1800 = 6 kHz.
The maximum output frequency of converter can be exceeded if one of the following is active:

When using the setpoint source


• Analog Input
• USS
the setpoint frequency (in Hz) is cyclically calculated using
• a percentage value(e.g. for the analog input r0754)
• a hexadecimal value (e.g. for the USS r2018[1])
• and the reference frequency P2000.
If for example P1082 = 80 Hz, P2000 = 50 Hz and the analog input is parameterized with P0757 = 0 V,
P0758 = 0 %, P0759 = 10 V, P0760 = 100 %, a setpoint frequency of 50 Hz will be applied at 10 V of the
analog input. When Quick Commissioning is carried out P2000 is changed as follows: P2000 = P1082.

SINAMICS V20 Converter


258 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r1084 - - - - - Float 3

Displays resultant maximum frequency.


P1091[0...2] 0.00 - 550.00 0.00 U, T - DDS Float 3
Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies with-
in +/-P1101 (skip frequency bandwidth).
Stationary operation is not possible within the suppressed frequency range; the range is merely passed
through (on the ramp). For example, if P1091 = 10 Hz and P1101 = 2 Hz, it is not possible to operate
continuously between 10 Hz +/- 2 Hz (i.e. between 8 and 12 Hz).
The function is disabled if P1091 = 0.
P1092[0...2] 0.00 - 550.00 0.00 U, T - DDS Float 3
Defines skip frequency 2 which avoids effects of mechanical resonance and suppresses frequencies with-
in +/-P1101 (skip frequency bandwidth).
See P1091
P1093[0...2] 0.00 - 550.00 0.00 U, T - DDS Float 3
Defines skip frequency 3 which avoids effects of mechanical resonance and suppresses frequencies with-
in +/-P1101 (skip frequency bandwidth).
See P1091
P1094[0...2] 0.00 - 550.00 0.00 U, T - DDS Float 3
Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies with-
in +/-P1101 (skip frequency bandwidth).
See P1091
P1101[0...2] 0.00 - 10.00 2.00 U, T - DDS Float 3

Delivers frequency bandwidth to be applied to skip frequencies.


See P1091
P1110[0...2] 0 - 4294967295 0 T - CDS U32 3

This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited
to the set-point channel. If a minimum frequency (P1080) and a negative setpoint are given, the motor is
accelerated by a positive value in relationship to the minimum frequency.
0 Disabled
1 Enabled
P1113[0...2] 0 - 4294967295 19.11 T - CDS U32 3
Defines source of reverse command used when P0719 = 0 (Auto selection of command/setpoint source).
722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
r1114 - - - - - Float 3

Displays setpoint frequency after change of direction.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 259
Parameter list
8.2 Parameter list

r1119 - - - - - Float 3

Displays frequency setpoint at the input to the ramp function generator after modification by other func-
tions, e.g.:
• P1110 BI: Inhibit neg. freq. setpoint,
• P1091 - P1094 skip frequencies,
• P1080 min. frequency,
• P1082 max. frequency,
This value is available filtered (r0020) and unfiltered (r1119).
P1120[0...2] 0.00 - 650.00 10.00 C, U, T - DDS Float 1
Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no
rounding is used. Setting the ramp-up time too short can cause the converter to trip (overcurrent F1).
Rounding times (P1130 - P1133), rounding type (P1134), and ramp-up time scaling factor (P1138) will
also have influence on the ramp.
See also P3350, P3353.
Ramp times will be used as follows:
• P1060/P1061 : JOG mode is active
• P1120/P1121 : Normal mode (ON/OFF) is active
• P1060/P1061 : Normal mode (ON/OFF) and P1124 is active
Set ramp-up time = ramp-up time scaling factor (P1138) x ramp-up time (P1120).
If an external frequency setpoint with set ramp rates is used (e.g. from a PLC), the best way to achieve
optimum converter performance is to set ramp times in P1120 and P1121 slightly shorter than those of the
PLC. Changes to P1120 will be immediately effective. If the SuperTorque function is enabled, the con-
verter will initially ramp using the value in P3353.
P1121[0...2] 0.00 - 650.00 10.00 C, U, T - DDS Float 1
Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no
rounding is used.
Ramp-down time scaling factor (P1139) will also have influence on the ramp.
See also P3350, P3353.
Setting the ramp-down time too short can cause the converter to trip (overcurrent F1/overvoltage F2).
Ramp times will be used as follows:
• P1060/P1061 : JOG mode is active
• P1120/P1121 : Normal mode (ON/OFF) is active
• P1060/P1061 : Normal mode (ON/OFF) and P1124 is active
Set ramp-down time = ramp-down time scaling factor (P1139) x ramp-down time (P1121).
Changes to P1121 will be immediately effective.
See P1120
P1124[0...2] 0 - 4294967295 0 T - CDS U32 3

Defines source for switching between jog ramp times (P1060, P1061) and normal ramp times (P1120,
P1121) as applied to the RFG. This parameter is valid for normal mode (ON/OFF) only.
See also P1175.

SINAMICS V20 Converter


260 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1124 does not have any impact when JOG mode is selected. In this case, jog ramp times (P1060,
P1061) will be used all the time. If the Dual Ramp function is selected using P1175, ramp times will switch
between normal (P1120, P1121) and JOG (P1060, P1061) ramp times, depending on the settings of
P2150, P2157 and P2159. Therefore, it is not recommended that JOG ramp is selected at the same time
as Dual Ramp.
See P1120.
P1130[0...2] 0.00 - 40.00 0.00 U, T - DDS Float 2

Defines rounding time in seconds at start of ramp-up.


Rounding times are recommended, since they prevent an abrupt response, thus avoiding detrimental
effects on the mechanics.
Rounding times are not recommended when analog inputs are used, since they would result in over-
shoot/undershoot in the converter response.
If short or zero ramp times (P1120, P1121 < P1130, P1131, P1132, P1133) are set, the total ramp up time
(t_up) or ramp down time (t_down) will not depend on P1130.
P1131[0...2] 0.00 - 40.00 0.00 U, T - DDS Float 2

Defines rounding time at end of ramp-up.


See P1130
P1132[0...2] 0.00 - 40.00 0.00 U, T - DDS Float 2

Defines rounding time at start of ramp-down.


See P1130
P1133[0...2] 0.00 - 40.00 0.00 U, T - DDS Float 2

Defines rounding time at end of ramp-down.


See P1130
P1134[0...2] 0-1 0 U, T - DDS U16 2
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g.
new setpoint, OFF1, OFF3, REV). This smoothing is applied, if the motor is ramped-up or ramped-down
and
• P1134 = 0,
• P1132 > 0, P1133 > 0 and
• the setpoint is not yet reached.
0 Continuous smoothing
1 Discontinuous smoothing
Effect only when P1130 (Ramp-up initial rounding time) or P1131 (Ramp-up final rounding time) or P1132
(Ramp-down initial rounding time) or P1133 (Ramp-down final rounding time) > 0 s.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 261
Parameter list
8.2 Parameter list

P1135[0...2] 0.00 - 650.00 5.00 C, U, T - DDS Float 2

Defines ramp-down time from maximum frequency to standstill for OFF3 command. Settings in P1130 and
P1134 will have no effect on OFF3 ramp-down characteristic. An initial ramp-down rounding time of ap-
proximately 10% of P1135 is however included. For the total OFF3 ramp-down time: t_down,OFF3 =
f(P1134) = 1.1 * P1135 * (|f_2|/P1082)
This time may be exceeded if the Vdc_max level is reached.
P1138[0...2] 1.00 - 10.00 1.00 C, U, T - DDS Float 1

Defines the scaling factor for the ramp-up time. This is a ramp-up time multiplier, extending the maximum
ramp-up time to 6500 s. Set ramp-up time = ramp-up time scaling factor (P1138) x ramp-up time (P1120).
This time may be exceeded if the Vdc_max level is reached.
P1139[0...2] 1.00 - 10.00 1.00 C, U, T - DDS Float 1

Defines the scaling factor for the ramp-down time.This is a ramp-down time multiplier, extending the max-
imum ramp-down time to 6500 s. Set ramp-down time = ramp-down time scaling factor (P1139) x ramp-
down time (P1121).
This time may be exceeded if the VDC_max level is reached.
P1140[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines command source of RFG enable command (RFG: ramp function generator). If binary input is
equal to zero then the RFG output will be set immediately to 0.
P1141[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal
to zero then the RFG output is held at its present value.
P1142[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary
input is equal to zero, the RFG input will be set to zero and the RFG output will ramp-down to zero.
r1170 - - - - - Float 3

Displays overall frequency setpoint after ramp generator.

SINAMICS V20 Converter


262 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1175[0...2] 0 - 4294967295 0 T - CDS U32 3


Defines command source of dual ramp enable command. If binary input is equal to one, then the dual
ramp will be applied. This works as follows:
• Ramp-up:
– Converter starts ramp-up using ramp time from P1120
– When f_act > P2157, switch to ramp time from P1060
• Ramp-down:
– Converter starts ramp-down using ramp time from P1061
– When f_act < P2159, switch to ramp time from P1121

See P2150, P2157, P2159, r2198.


The dual ramp algorithm uses r2198 bits 1 and 2 to determine (f_act > P2157) and (f_act < P2159). P2150
is used to apply hysteresis to these settings, so the user may wish to change the value of this parameter
to make the dual ramp function more responsive. It is not recommended that the dual ramp function is
used in conjunction with JOG ramp.
See P1124.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 263
Parameter list
8.2 Parameter list

r1199.7...12 - - - - - U16 3

Displays status of ramp function generator (RFG).

07 Ramp #0 active Yes No


08 Ramp #1 active Yes No
09 Ramping finished Yes No
10 Direction right/left Yes No
11 f_act > P2157(f_2) Yes No
12 f_act < P2159(f_3) Yes No
See P2157 and P2159.
P1200 0-6 0 U, T - - U16 2
Starts converter onto a rotating motor by rapidly changing the output frequency of the converter until the
actual motor speed has been found. Then, the motor runs up to setpoint using the normal ramp time.
0 Flying start disabled
1 Flying start always active; searches in both directions
2 Flying start active after power on, fault, OFF2; searches in both directions
3 Flying start active after fault, OFF2; searches in both directions
4 Flying start always active; searches in direction of setpoint only
5 Flying start active after power on, fault, OFF2; searches in direction of setpoint
only
6 Flying start active after fault, OFF2; searches in direction of setpoint only
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load. Otherwise, overcurrent trips will occur.
Useful for motors with high inertia loads. Settings 1 to 3 search in both directions. Settings 4 to 6 search
only in direction of setpoint.

SINAMICS V20 Converter


264 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1202[0...2] 10 - 200 100 U, T - DDS U16 3

Defines search current used for flying start. Value is in [%] based on rated motor current (P0305).
Reducing the search current may improve performance for flying start if the inertia of the system is not
very high. However, search current settings in P1202 that are below 30% (and sometimes other settings
in P1202 and P1203) may cause motor speed to be found prematurely or too late, which can result in F1
or F2 trips.
P1203[0...2] 10 - 500 100 U, T - DDS U16 3

Sets factor (in V/f mode only) by which the output frequency changes during flying start to synchronize
with turning motor. This value is entered in [%]. It defines the reciprocal initial gradient in the search se-
quence. P1203 influences the time taken to search for the motor frequency.
For a motor with 50 Hz, 1350 rpm, 100 % would produce a maximum search time of 600 ms.
A higher value produces a flatter gradient and thus a longer search time. A lower value has the opposite
effect.
r1204 - - - - - U16 4

Bit parameter for checking and monitoring states during search.

00 Current applied Yes No


01 Current could not be applied Yes No
02 Voltage reduced Yes No
03 Slope-filter started Yes No
04 Current less threshold Yes No
05 Current-minimum Yes No
07 Speed could not be found Yes No

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 265
Parameter list
8.2 Parameter list

P1210 0-8 1 U, T - - U16 2


Configures automatic restart function.
0 Disabled
1 Trip reset after power on, P1211 disabled
2 Restart after mains blackout, P1211 disabled
3 Restart after mains brownout or fault, P1211 enabled
4 Restart after mains brownout, P1211 enabled
5 Restart after mains blackout and fault, P1211 disabled
6 Restart after mains brown- /blackout or fault, P1211 enabled
7 Restart after mains brown- /blackout or fault, trip when P1211 expires
8 Restart after mains brown- /blackout with F3 and leave an interval in seconds determined by P1214,
P1211 disabled
9 Restart after mains brown- /blackout with F3 during the attempt time determined by P1214, P1211
disabled
10 Restart after mains brown- /blackout with F3 during the attempt time determined by P1214 or manual
fault acknowledgment, P1211 disabled
Automatic restart requires constant ON command via a digital input wire link.
P1210 > 2 can cause the motor to restart automatically without toggling the ON command!
A "mains brownout" is a very short mains break, where the DC link has not fully collapsed before the pow-
er is reapplied.
A "mains blackout" is a long mains break, where the DC link has fully collapsed before the power is re-
applied.
"Delay Time" is the time between attempts of quitting fault. The "Delay Time" of first attempt is 1 second,
then it will be doubled every next attempt.
The "Number of Restart Attempts" can be set in P1211. This is the number of restarts the converter will try
to quit fault.
When faults are quit and after 4 seconds of no fault condition, "Number of Restart Attempts" will be reset to
P1211 and "Delay Time" will be reset to 1 second.
P1210 = 0:
Automatic restart is disabled.
P1210 = 1:
The converter will acknowledge (reset) faults i.e. it will reset a fault when the power is re-applied. This
means the converter must be fully powered down, a brownout is not sufficed. The converter will not run
until the ON command has been toggled.
P1210 = 2:
The converter will acknowledge the fault F3 at power on after blackout and restarts the converter. It is
necessary that the ON command is wired via a digital input (digital input).
P1210 = 3:
For these settings it is fundamental that the converter only restarts if it has been in a RUN state at the time
of the faults (F3, etc.). The converter will acknowledge the fault and restarts the converter after a brownout.
It is necessary that the ON command is wired via a digital input (digital input).
P1210 = 4:
For these settings it is fundamental that the converter only restarts if it has been in a RUN state at the time
of the fault (F3). The converter will acknowledge the fault and restarts the converter after a brownout. It is
necessary that the ON command is wired via a digital input (digital input).
P1210 = 5:
The converter will acknowledge the faults F3 etc. at power on after blackout and restarts the converter. It is
necessary that the ON command is wired via a digital input (digital input).

SINAMICS V20 Converter


266 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1210 = 6:
The converter will acknowledge the faults (F3 etc.) at power on after blackout or brownout and restarts the
converter. It is necessary that the ON command is wired via a digital input (digital input). Setting 6 causes
the motor to restart immediately.
P1210 = 7:
The converter will acknowledge the faults (F3 etc.) at power on after blackout or brownout and restarts the
converter. It is necessary that the ON command is wired via a digital input (digital input). Setting 7 causes
the motor to restart immediately.
The difference between this mode and Mode 6 is that the fault status bit (r0052.3) is not set until the num-
ber of restarts defined by P1211 have been exhausted.
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load (P1200).
P1210 = 8:
The converter will acknowledge the fault (F3) at power on after blackout or brownout and restarts. It is
necessary that the ON command is wired via a digital input (DI). Setting 8 causes the motor to restart im-
mediately. The interval between restarts is determined by P1214.
P1210 = 9:
The converter will acknowledge the fault (F3) at power on after blackout or brownout and restarts. It is
necessary that the ON command is wired via a digital input (DI). The interval between restarts is fixed at
0.5 s. P1214 sets the total restart attempt time. If an F3 occurs and cannot be acknowledged within the
time set in P1214, the F3 will go permanent and must be acknowledged manually to restart the converter.
P1210 = 10:
• The converter will acknowledge the fault (F3) at power on after blackout or brownout and restarts. It is
necessary that the ON command is wired via a digital input (DI). The interval between restarts is fixed
at 1.0 s. P1214 sets the total restart attempt time, but it must be equal to or less than 8 s. If an F3 oc-
curs and cannot be acknowledged within the time set in P1214, the F3 will go permanent and must be
acknowledged manually to restart the converter.
• If a fault (the converter cannot recover from F6, F51, F52, F85, F100, and F101) occurs, the fault must
be acknowledged manually at power on after blackout or brownout and the converter restarts. It is nec-
essary that the ON command is wired via a digital input (DI).
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load (P1200).
P1211 0 - 10 3 U, T - - U16 3

Specifies number of times converter will attempt to restart if automatic restart P1210 is activated.
P1214 0 - 1000 30 - - - U16 3
This parameter has either of the following functions:
• Specifying the restart interval when P1210 = 8
• Specifying the total restart attempt time when P1210 = 9 or P1210 = 10
P1215 0-1 0 C, T - - U16 2
Enables/disables holding brake function. The motor holding brake (MHB) is controlled via status word 1
r0052 bit 12. This signal can be issued via:
• status word of the serial interface (e.g. USS)
• digital outputs (e.g. DO1: ==> P0731 = 52.C (r0052 bit 12))
0 Motor holding brake disabled
1 Motor holding brake enabled
If the converter controls the motor holding brake, then a commissioning may not be carried out for poten-
tially hazardous loads (e.g. suspended loads for crane applications) unless the load has been secured.
It is not permissible to use the motor holding brake as working brake, as it is generally only designed for a
limited number of emergency braking operations.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 267
Parameter list
8.2 Parameter list

P1216 0.0 - 20.0 1.0 C, T - - Float 2

Defines period during which converter runs at minimum frequency P1080 before ramping up.
P1217 0.0 - 20.0 1.0 C, T - - Float 2

Defines time for which converter runs at minimum frequency (P1080) after ramping down.
If P1217 > P1227, P1227 will take precedence.
P1218[0...2] 0 - 4294967295 0 U, T - CDS U32 3

Enables the motor holding brake output to be overridden, allowing the brake to be opened under separate
control.
P1227[0...2] 0.0 - 300.0 4.0 U, T - DDS Float 2

Sets the monitoring time for the standstill identification.


When braking with OFF1 or OFF3, standstill is identified after this time has expired, after the setpoint
speed has fallen below P2167. After this, the braking signal is started, the system waits for the closing time
and then the pulses are cancelled.
P1227 = 300.0: function is deactivated
P1227 = 0.0: pulses are locked immediately
If P1217 > P1227, P1227 will take precedence.
P1230[0...2] 0 - 4294967295 0 U, T - CDS U32 3
Enables DC braking via a signal applied from an external source. Function remains active while external
input signal is active. DC braking causes the motor to stop rapidly by applying a DC braking current (cur-
rent applied also holds shaft stationary).
When the DC braking signal is applied, the converter output pulses are blocked and the DC current is not
applied until the motor has been sufficiently demagnetized. This delay time is set in P0347 (demagnetiza-
tion time). If this delay is too short, overcurrent trips can occur. The level of DC braking is set in P1232 (DC
braking current - relative to the rated motor current) which is set to 100 % by default.
With the DC braking, the kinetic energy of the motor is converted into heat in the motor. The converter
could overheat if it remains in this status for an excessive period of time!
P1232[0...2] 0 - 250 100 U, T - DDS U16 2
Defines level of DC current relative to rated motor current (P0305). The DC braking can be issued observ-
ing the following dependencies:
• OFF1/OFF3 ==> see P1233
• BICO ==> see P1230
P1233[0...2] 0.00 - 250.00 0.00 U, T - DDS Float 2
Defines duration for which DC braking is active following an OFF1 or OFF3 command.
When an OFF1 or OFF3 command is received by the converter, the output frequency starts to ramp to 0 Hz.
When the output frequency reaches the value set in P1234, the converter injects a DC braking current
P1232 for the time duration set in P1233.
See P1230
The DC braking function causes the motor to stop rapidly by applying a DC braking current.
When the DC braking signal is applied, the converter output pulses are blocked and the DC current not
applied until the motor has been sufficiently demagnetized (demagnetization time is calculated automati-
cally from motor data).
P1233 = 0 means that DC braking is not activated.

SINAMICS V20 Converter


268 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1234[0...2] 0.00 - 550.00 550.00 U, T - DDS Float 2

Sets start frequency for DC braking.


When an OFF1 or OFF3 command is received by the converter, the output frequency starts to ramp to 0 Hz.
When the output frequency reaches the value set in start frequency of DC braking P1234, the converter
injects a DC braking current P1232 for the time duration set in P1233.
P1236[0...2] 0 - 250 0 U, T - DDS U16 2

Defines DC level superimposed on AC waveform after exceeding DC-link voltage threshold of compound
braking. The value is entered in [%] relative to rated motor current (P0305). Compound braking switch-on
level (V_DC,Comp):
If P1254 = 0 --> V_DC,Comp = 1.13 * sqrt(2) * V_mains = 1.13 * sqrt(2) * P0210
otherwise V_DC,Comp = 0.98 * r1242
The Compound Brake is an overlay of the DC brake function with regenerative braking (effective braking at
the ramp) after OFF1 or OFF3. This enables braking with controlled motor frequency and a minimum of
energy returned to the motor. Through optimization of the ramp-down time and the compound braking an
efficient braking without additional HW components is possible.
Compound braking depends on the DC link voltage only (see threshold above). This will happen on OFF1,
OFF3 and any regenerative condition. It is disabled, when:
• DC braking is active
• Flying start is active
Increasing the value will generally improve braking performance; however, if you set the value too high, an
overcurrent trip may result.
If used with dynamic braking enabled as well compound braking will take priority.
If used with the Vdc_max controller enabled the converter behavior when braking may be worsened partic-
ularly with high values of compound braking.
P1236 = 0 means that compound braking is not activated.
P1237 0-5 0 U, T - - U16 2
Dynamic braking absorbs the braking energy in a braking resistor.
This parameter defines the rated duty cycle of the braking resistor.
Dynamic braking is active when the function is enabled and DC-link voltage exceeds the dynamic braking
switch-on level.
Dynamic braking switch-on level (V_DC,Chopper) :
If P1254 = 0 --> V_DC,Chopper = 1.13 * sqrt(2) * V_mains = 1.13 * sqrt(2) * P0210
otherwise V_DC,Chopper = 0.98 * r1242
0 Disabled
1 5 % duty cycle
2 10 % duty cycle
3 20 % duty cycle
4 50 % duty cycle
5 100 % duty cycle
This parameter is only applicable for converters of frame size D and E. For frame sizes AA to C, the duty
cycle of the braking resistor can be selected with the dynamic braking module (see Appendix "Dynamic
braking module (Page 375)").

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 269
Parameter list
8.2 Parameter list

If dynamic braking is used with DC braking enabled as well as compound braking, DC braking and com-
pound braking will take priority.

Initially the brake will operate at a high duty cycle dependent on the DC link level until the thermal limit is
approached. The duty cycle specified by this parameter will then be imposed. The resistor should be able
to operate at this level indefinitely without overheating.

The threshold for the warning A535 is equivalent to 10 seconds running at 95 % duty cycle. The duty cycle
will be limited when it was running 12 seconds at 95 % duty cycle.
P1240[0...2] 0-3 1 C, T - DDS U16 3

Enables/disables Vdc controller. The Vdc controller dynamically controls the DC link voltage to prevent
overvoltage trips on high inertia systems.
0 Vdc controller disabled
1 Vdc_max controller enabled
2 Kinetic buffering (Vdc_min controller) enabled
3 Vdc_max controller and kinetic buffering (KIB) enabled
If P1245 increased too much, it may interfere with the converter normal operation.
• Vdc_max controller:
Vdc_max controller automatically increases ramp-down times to keep the DC-link voltage (r0026) with-
in limits (r1242).
• Vdc_min controller:
Vdc_min is activated if DC-link voltage falls below the switch on level P1245. The kinetic energy of the
motor is then used to buffer the DC-link voltage, thus causing deceleration of the converter. If the con-
verter trips with F3 immediately, try increasing the dynamic factor P1247 first. If still tripping with F3 try
then increasing the switch on level P1245.

SINAMICS V20 Converter


270 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r1242 - - - - - Float 3

Displays switch-on level of Vdc_max controller.


Following equation is only valid, if P1254 = 0:
r1242 = 1.15 * sqrt(2) * V_mains = 1.15 * sqrt(2) * P0210
otherwise r1242 is internally calculated.
P1243[0...2] 10 - 200 100 U, T - DDS U16 3

Defines dynamic factor for DC link controller.


P1243 = 100 % means P1250, P1251 and P1252 (gain, integration time and differential time) are used as
set. Otherwise, these are multiplied by P1243 (dynamic factor of Vdc_max).
Vdc controller adjustment is calculated automatically from motor and converter data.
P1245[0...2] 65 - 95 76 U, T - DDS U16 3

Enter switch-on level for kinetic buffering (KIB) in [%] relative to supply voltage (P0210).
r1246[V] = (P1245[%]/100) * sqrt(2) * P0210
Increasing the value too much, may interfere with the converter normal operation.
P1254 has no effect on the switch-on-level for kinetic buffering.
P1245 default for the single phase variants is 74%.
r1246[0...2] - - - - DDS Float 3

Displays switch-on level of kinetic buffering (KIB, Vdc_min controller). If the dc-link voltage drops below the
value in r1246, kinetic buffering will be activated. That means the motor frequency will be reduced in order
to keep Vdc within the valid range. If there is not enough regenerative energy, the converter trips with
undervoltage.
P1247[0...2] 10 - 200 100 U, T - DDS U16 3

Enters dynamic factor for kinetic buffering (KIB, Vdc_min controller). P1247 = 100 % means P1250, P1251
and P1252 (gain, integration time and differential time) are used as set. Otherwise, these are multiplied by
P1247 (dynamic factor of Vdc_min).
Vdc controller adjustment is calculated automatically from motor and converter data.
P1250[0...2] 0.00 - 10.00 1.00 U, T - DDS Float 3
Enters gain for Vdc controller.
P1251[0...2] 0.1 - 1000.0 40.0 U, T - DDS Float 3

Enters integral time constant for Vdc controller.


P1252[0...2] 0.0 - 1000.0 1.0 U, T - DDS Float 3

Enters differential time constant for Vdc controller.


P1253[0...2] 0.00 - 550.00 10.00 U, T - DDS Float 3

Limits maximum effect of Vdc_max controller.


This parameter is influenced by automatic calculations defined by P0340.
The Factory setting depends on converter power.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 271
Parameter list
8.2 Parameter list

P1254 0-1 1 C, T - - U16 3

Enables/disables auto-detection of switch-on levels for Vdc_max controller. For best results, it is recom-
mended to set P1254 = 1 (auto-detection of Vdc switch-on levels enabled). Setting P1254 = 0 is only rec-
ommended when there is a high degree of fluctuation of the DC-link when the motor is being driven. Note
that the auto detection only works when the converter has been in standby for over 20s.
0 Disabled
1 Enabled
See P0210
P1256[0...2] 0-2 0 C, T - DDS U16 3

Enters reaction for kinetic buffering controller (Vdc_min controller). Depending on the setting selected, the
frequency limit defined in P1257 is used to either hold the speed or disable pulses. If not enough regenera-
tion is produced, converter may trip with undervoltage.
0 Maintain DC-link until trip
1 Maintain DC-link until trip/stop
2 Control stop
P1256 = 0:
Maintain DC-link voltage until mains is returned or converter is tripped with undervoltage. The frequency is
kept above the frequency limit provided in P1257.
P1256 = 1:
Maintain DC-link voltage until mains is returned or converter is tripped with undervoltage or pulses are
disabled when frequency falls below the limit in P1257.
P1256 = 2:
This option ramps down the frequency to standstill even when mains return.
If mains do not return, frequency brought down under the control of Vdc_min controller until P1257 limit.
Then pulses are disabled or undervoltage has occurred. If mains return, then an OFF1 is active until
P1257 limit. Then pulses are disabled.
P1257[0...2] 0.00 - 550.00 2.50 U, T - DDS Float 3

Frequency which kinetic buffering (KIB) either hold speed or disable pulses depending on P1256.
P1300[0...2] 0 - 19 0 C, T - DDS U16 2
Parameter to select the control method. Controls relationship between speed of motor and voltage sup-
plied by converter.
0 V/f with linear characteristic
1 V/f with FCC
2 V/f with quadratic characteristic
3 V/f with programmable characteristic
4 V/f with linear eco
5 V/f for textile applications
6 V/f with FCC for textile applications
7 V/f with quadratic eco
19 V/f control with independent voltage setpoint

SINAMICS V20 Converter


272 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1300 = 1: V/f with FCC (flux current control)


• Maintains motor flux current for improved efficiency
• If FCC is chosen, linear V/f is active at low frequencies
P1300 = 2: V/f with a quadratic characteristic
• Suitable for centrifugal fans/pumps
P1300 = 3: V/f with a programmable characteristic
• User defined characteristic (see P1320)
P1300 = 4: V/f with linear characteristic and Economy Mode
• Linear characteristic with Economy Mode
• Modifies the output voltage to reduce power consumption
P1300 = 5,6: V/f for textile applications
• Slip compensation disabled.
• Imax controller modifies the output voltage only.
• Imax controller does not influence the output frequency.
P1300 = 7: V/f with quadratic characteristic and Economy Mode
• Quadratic characteristic with Economy Mode
• Modifies the output voltage to reduce power consumption
P1300 = 19: V/f control with independent voltage setpoint

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 273
Parameter list
8.2 Parameter list

The following table presents an overview of control parameters (V/f) that can be modified in relationship to
P1300 dependencies:

P1310[0...2] 0.0 - 250.0 50.0 U, T PERC DDS Float 2


ENT
Defines boost level in [%] relative to P0305 (rated motor current) applicable to both linear and quadratic V/f
curves.
At low output frequencies the output voltage is low to keep the flux level constant. However, the output
voltage may be too low for the following:
• magnetization the asynchronous motor
• hold the load
• overcome losses in the system.
The converter output voltage can be increased via P1310 for the compensation of losses, holding loads at
0 Hz, or maintaining the magnetization.
The magnitude of the boost in Volt at a frequency of zero is defined as follows:
V_ConBoost,100 = P0305 * Rsadj * (P1310/100)
Where:
Rsadj = stator resistance adjusted for temperature
Rsadj = (r0395/100) * (P0304/(sqrt(3) * P0305)) * P0305 * sqrt(3)

SINAMICS V20 Converter


274 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

Increasing the boost levels increases motor heating (especially at standstill).


Setting in P0640 (motor overload factor [%]) limits the boost:
sum(V_Boost)/(P0305 * Rsadj) <= P1310/100
The boost values are combined when continuous boost (P1310) used in conjunction with other boost pa-
rameters (acceleration boost P1311 and starting boost P1312). However priorities are allocated to these
parameters as follows:
P1310 > P1311 > P1312
The total boost is limited by following equation:
sum(V_Boost) <= 3 * R_S * I_Mot = 3 * P0305 * Rsadj
P1311[0...2] 0.0 - 250.0 0.0 U, T PERC DDS Float 2
ENT
Applies boost in [%] relative to P0305 (rated motor current) following a positive setpoint change and drops
back out once the setpoint is reached.
P1311 will only produce boost during ramping, and is therefore useful for additional torque during accelera-
tion and deceleration.
As opposed to P1312, which is only active on the first acceleration issued after the ON command, P1311
is always effect during an acceleration and deceleration when issued.
The magnitude of the boost in volt at a frequency of zero is defined as follows:
V_AccBoost,100 = P0305 * Rsadj * (P1311/100)
Where:
Rsadj = stator resistance adjusted for temperature
Rsadj = (r0395/100) * (P0304/(sqrt(3) * P0305)) * P0305 * sqrt(3)
See P1310
P1312[0...2] 0.0 - 250.0 0.0 U, T PERC DDS Float 2
ENT
Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either
linear or quadratic) after an ON command and is active until:
1. ramp output reaches setpoint for the first time respectively
2. setpoint is reduced to less than present ramp output
This is useful for starting loads with high inertia. Setting the starting boost (P1312) too high will cause the
converter to limit the current, which will in turn restrict the output frequency to below the setpoint frequen-
cy.
The magnitude of the boost in volt at a frequency of zero is defined as follows:
V_StartBoost,100 = P0305 * Rsadj * (P1312/100)
Where:
Rsadj = stator resistance adjusted for temperature
Rsadj = (r0395/100) * (P0304/(sqrt(3) * P0305)) * P0305 * sqrt(3)
See P1310
r1315 - - - - - Float 4

Displays total value of voltage boost.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 275
Parameter list
8.2 Parameter list

P1316[0...2] 0.0 - 100.0 20.0 U, T PERC DDS Float 3


ENT
Defines point at which programmed boost reaches 50 % of its value. This value is expressed in [%] relative
to P0310 (rated motor frequency). The default frequency is defined as follows:
V_Boost,min = 2 * (3 + (153/sqrt(P_Motor))
This parameter is influenced by automatic calculations defined by P0340.
The expert user may change this value to alter the shape of the curve, e.g. to increase torque at a particu-
lar frequency.
Default value is depending on converter type and its rating data.
P1320[0...2] 0.00 - 550.00 0.00 T - DDS Float 3

Sets the frequency of the first point of V/f coordinates (P1320/1321 to P1324/1325) to define V/f character-
istic. These parameter pairs can be used to provide correct torque at correct frequency.
To set parameter, select P1300 = 3 (V/f with programmable characteristic). The acceleration boost and
starting boost defined in P1311 and P1312 are applied to V/f with programmable characteristic.
Linear interpolation will be applied between the individual data points.
V/f with programmable characteristic (P1300 = 3) has 3 programmable points and 2 non-programmable
points. The 2 non-programmable points are:
• Continuous boost P1310 at 0 Hz
• Rated motor voltage P0304 at rated motor frequency P0310
P1321[0...2] 0.0 - 3000.0 0.0 U, T - DDS Float 3

See P1320
P1322[0...2] 0.00 - 550.00 0.00 T - DDS Float 3

See P1320
P1323[0...2] 0.0 - 3000.0 0.0 U, T - DDS Float 3

See P1320
P1324[0...2] 0.00 - 550.00 0.00 T - DDS Float 3

See P1320
P1325[0...2] 0.0 - 3000.0 0.0 U, T - DDS Float 3

See P1320
P1330[0...2] 0 - 4294967295 0 T - CDS U32 3
BICO parameter for selecting source of voltage setpoint for independent V/f control (P1300 = 19).
P1333[0...2] 0.0 - 100.0 10.0 U, T PERC DDS Float 3
ENT
Defines start frequency at which FCC (flux current control) is enabled as [%] of rated motor frequency
(P0310).
If this value is too low, the system may become unstable.

SINAMICS V20 Converter


276 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1334[0...2] 1.0 - 20.0 6.0 U, T PERC DDS Float 3


ENT
To set the frequency activation range for slip compensation. The percentage value of P1334 refers to the
motor rated frequency P0310.
The upper threshold will always stay 4 % above P1334.

Slip compensation (P1335) active.


See P1335.
The starting frequency of the slip compensation is P1334 * P0310.
P1335[0...2] 0.0 - 600.0 0.0 U, T PERC DDS Float 2
ENT
Parameter dynamically adjusts converter output frequency so that motor speed is kept constant independ-
ent of motor load.
In the V/f-control, the motor frequency will always be less than the converter output frequency due to the
slip frequency. For a given output frequency, the motor frequency will drop as load is increased. This be-
havior, typical for induction motors, can be compensated using slip compensation. P1335 can be used to
enable and fine-tune the slip compensation.
Gain adjustment enables fine-tuning of the actual motor speed.
P1335 > 0, P1336 > 0, P1337 = 0 if P1300 = 5, 6.
The applied value of the slip compensation (scaled by P1335) is limited by following equation:
f_Slip_comp,max = r0330 * (P1336/100)
P1335 = 0 %:
Slip compensation disabled.
P1335 = 50 % - 70 %:
Full slip compensation at cold motor (partial load).
P1335 = 100 % (standard setting for warm stator):
Full slip compensation at warm motor (full load).
P1336[0...2] 0 - 600 250 U, T - DDS U16 2
Compensation slip limit in [%] relative to r0330 (rated motor slip), which is added to frequency setpoint.
Slip compensation (P1335) active.
r1337 - - - PERC - Float 3
ENT
Displays actual compensated motor slip as [%]. f_slip [Hz] = r1337 [%] * P0310/100
Slip compensation (P1335) active.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 277
Parameter list
8.2 Parameter list

P1338[0...2] 0.00 - 10.00 0.00 U, T - DDS Float 3

Defines resonance damping gain for V/f. The di/dt of the active current will be scaled by P1338. If di/dt
increases the resonance damping circuit decreases the converter output frequency.
This parameter is influenced by automatic calculations defined by P0340.
The resonance circuit damps oscillations of the active current which frequently occur during no-load opera-
tion. In V/ f modes (see P1300), the resonance damping circuit is active in a range from approx. 6 % to 80
% of rated motor frequency (P0310). If the value of P1338 is too high, this will cause instability (forward
control effect).
P1340[0...2] 0.000 - 0.499 0.030 U, T - DDS Float 3

Proportional gain of the I_max controller.


The Imax controller reduces converter current if the output current exceeds the maximum motor current
(r0067).
In linear V/f, parabolic V/f, FCC, and programmable V/f modes the I_max controller uses both a frequency
controller (see P1340 and P1341) and a voltage controller (see P1345 and P1346).
The frequency controller seeks to reduce current by limiting the converter output frequency (to a minimum
of the two times nominal slip frequency).
If this action does not successfully remove the overcurrent condition, the converter output voltage is re-
duced using the I_max voltage controller.
When the overcurrent condition has been removed successfully, frequency limiting is removed using the
ramp-up time set in P1120.
In linear V/f for textiles, FCC for textiles, or external V/f modes only the I_max voltage controller is used to
reduce current (see P1345 and P1346).
The I_max controller can be disabled by setting the frequency controller integral time P1341 to zero. This
disables both the frequency and voltage controllers.
Note that when disabled, the I_max controller will take no action to reduce current but overcurrent warn-
ings will still be generated, and the converter will trip in excessive overcurrent or overload conditions.
P1341[0...2] 0.000 - 50.000 0.300 U, T - DDS Float 3

Integral time constant of the I_max controller.


• P1341 = 0: I_max controller disabled
• P1340 = 0 and P1341 > 0: frequency controller enhanced integral
• P1340 > 0 and P1341 > 0: frequency controller normal PI control
This parameter is influenced by automatic calculations defined by P0340.
See P1340 for further information. The Factory setting depends on converter power.

SINAMICS V20 Converter


278 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r1343 - - - - - Float 3

Displays effective frequency limitation.


If I_max controller not in operation, parameter normally shows maximum frequency P1082.
r1344 - - - - - Float 3

Displays amount by which the I_max controller is reducing the converter output voltage.
P1345[0...2] 0.000 - 0.250 U, T - DDS Float 3
5.499
If the output current (r0068) exceeds the maximum current (r0067), the converter is dynamically controlled
by reducing the output voltage. This parameter sets the proportional gain of this controller.
This parameter is influenced by automatic calculations defined by P0340.
See P1340 for further information. The Factory setting depends on converter power.
P1346[0...2] 0.000 - 0.300 U, T - DDS Float 3
50.000
Integral time constant of the I_max voltage controller.
• P1341 = 0: I_max controller disabled
• P1345 = 0 and P1346 > 0: I_max voltage controller enhanced integral
• P1345 > 0 and P1346 > 0: I_max voltage controller normal PI control
This parameter is influenced by automatic calculations defined by P0340.
See P1340 for further information. The Factory setting depends on converter power.
r1348 - - - PERCENT - Float 2

Displays the calculated economy mode factor (range 80%-120%) applied to the demanded output volts.
Economy mode is used to find the most efficient operating point for a given load. It does this by a continu-
ous method of hill climbing optimization. Hill climbing optimization works by slightly changing the output
volts either up or down and monitoring the change in input power. If the input power has decreased, the
algorithm changes the output volts in the same direction. If the input power has increased then the algo-
rithm adjusts the output volts in the other direction. Using this algorithm, the software should be able to
find the minimum point on the graph between input power and output volts.
If this value is too low, the system may become unstable.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 279
Parameter list
8.2 Parameter list

P1350[0...2] 0-1 0 U, T - DDS U16 3


Sets whether voltage is built up smoothly during magnetization time (ON) or whether it simply jumps to
boost voltage (OFF).
0 OFF
1 ON
The settings for this parameter bring benefits and drawbacks:
• P1350 = 0: OFF (jump to boost voltage)
Benefit: flux is built up quickly
Drawback: motor may move
• P1350 = 1: ON (smooth voltage build-up)

Benefit: motor less likely to move


Drawback: flux build-up takes longer
P1780[0...2] 0-1 1 U, T - DDS U16 3

Enables thermal adaptation of stator and rotor resistance to reduce torque errors in speed/torque regula-
tion with speed sensor, or speed errors in speed/torque regulation without speed sensor.

00 Enable thermal Rs/Rr-adapt. Yes No


P1800[0...2] 2 - 16 4 U, T - DDS U16 2
Sets pulse frequency of power switches in converter. The frequency can be changed in steps of 2 kHz.
The minimum/maximum/default values of the pulse frequency are determined by the used power module.
Furthermore the minimum pulse frequency depends on the parameterization of P1082 (maximum fre-
quency) and P0310 (rated motor frequency).
If the pulse frequency is increased, maximum converter current r0209 can be reduced (derating). The
derating characteristic depends on the type and power of the converter.
If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce con-
verter losses and radio-frequency emissions.
Under certain circumstances, the converter may reduce the pulse frequency to provide protection against
overtemperature (see P0290 and P0291 bit 00).
r1801[0...1] - - - - - U16 3

Displays information about pulse frequency of power switches in converter.


r1801[0] displays the actual converter pulse frequency.
r1801[1] displays the minimum converter pulse frequency which can be reached when the functions "mo-
tor identification" or "converter overload reaction" are active. If no PM is plugged this parameter is set to 0
kHz.
[0] Actual pulse frequency
[1] Minimum pulse frequency
Under certain conditions (converter overtemperature, see P0290), this can differ from the values selected
in P1800 (pulse frequency).

SINAMICS V20 Converter


280 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1802 1-3 3 U, T - - U16 3


Selects converter modulator mode.
1 Asymmetric SVM
2 Space vector modulation
3 SVM/ASVM controlled mode
• Asymmetric space vector modulation (ASVM) produces lower switching losses than space vector
modulation (SVM), but may cause irregular rotation at very low speeds.
• Space vector modulation (SVM) with over-modulation may produce current waveform distortion at high
output voltages.
• Space vector modulation (SVM) without over-modulation will reduce maximum output voltage available
to motor.
P1803[0...2] 20.0 - 150.0 106.0 U, T - DDS Float 3

Sets maximum modulation index.


P1803 = 100 %: Limit for over-control (for ideal converter without switching delay).
P1810 0-3 3 U, T - - U16 3
Configures Vdc filtering and compensation.

00 Enable Vdc average filter Yes No


01 Enable Vdc compensation Yes No
P1810 default for the single phase variants is 2.
P1820[0...2] 0-1 0 T - DDS U16 2

Changes sequence of phases without changing setpoint polarity.


0 Forward
1 Reverse the Motor
See P1000
P1825 0.0 - 20.0 0.9 U, T - - Float 4

Corrects on-state voltage of the IGBTs.


P1828 0.00 - 3.98 0.01 U, T - - Float 4

Sets compensation time of gating unit interlock.


P1829 0.0 – 180.0 0.0 U, T - - Float 4

Adjusts the phase angle at the point where the output frequency crosses zero. The angle is only used if
the output frequency changes direction.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 281
Parameter list
8.2 Parameter list

P1900 0-2 0 C, T - - U16 2

Performs motor data identification.


0 Disabled
2 Identification of all parameters in standstill
No measurement if motor data incorrect.
P1900 = 2: Calculated value for stator resistance (see P0350) is overwritten.
When the identification is finished P1900 is set to 0. When choosing the setting for measurement, observe
the following:
The value is actually adopted as P0350 parameter setting and applied to the control as well as being
shown in the read-only parameters below. Ensure that the motor holding brake is not active when per-
forming the motor identification.
Before selecting motor data identification, "Quick commissioning" has to be performed in advance.
Since the cable length of the applications differs in a wide range, the preset resistor P0352 is only a rough
estimation. Better results of the motor identification can be achieved by specifying the cable resistor be-
fore the start of the motor identification by measuring/calculating.
Once enabled (P1900 > 0), A541 generates a warning that the next ON command will initiate measure-
ment of motor parameters.
Communications - both via USS as well as via the Modbus - are interrupted for the time that it takes to
make internal calculations. These calculations can take up to one minute to complete.
P1909[0...2] 0 - 65519 23552 U, T - DDS U16 4

Control word of motor data identification.

00 Estimation of Xs Yes No
01 Motor ID at 2 kHz Yes No
02 Estimation of Tr Yes No
03 Estimation of Lsigma Yes No
05 Det. Tr meas. with 2 freq. Yes No
06 Measurement of on voltage Yes No
07 Deadtime detection from Rs measurement Yes No
08 MotID with hw deadtime comp activ Yes No
09 No deadtime detection with 2 freq Yes No
10 Detect Ls with LsBlock method Yes No
11 MotID adaption of magnetizing current Yes No
12 MotID adaption of main reactance Yes No
13 MotID switch off saturation curve optim. Yes No
14 MotID saturation curve optim. all framesizes Yes No
15 MotID saturation curve optim. big framesizes Yes No

SINAMICS V20 Converter


282 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P1910 0 - 23 0 T - - U16 4

Performs a motor data identification with extended figures.


Performs stator resistance measuring.
0 Disabled
1 Identification of all parameters with parameter change
2 Identification of all parameters without parameter change
3 Identification of saturation curve with parameter change
4 Identification of saturation curve without parameter change
5 Identification of XsigDyn without parameter change
6 Identification of Tdead without parameter change
7 Identification of Rs without parameter change
8 Identification of Xs without parameter change
9 Identification of Tr without parameter change
10 Identification of Xsigma without parameter change
20 Set voltage vector
21 Set voltage vector without filtering in r0069
22 Set voltage vector rectangle signal
23 Set voltage vector triangle signal
Ensure that the motor holding brake is not active when performing the motor identification. P1910 can't be
changed while the motor identification with P1900 is active (P1900 = 2 or 3). When the identification is
finished P1910 is set to 0. When choosing the setting for measurement, observe the following:
• "with parameter change"
means that the value is actually adopted as P0350 parameter setting and applied to the control as well
as being shown in the read-only parameters below.
• "without parameter change"
means that the value is only displayed, i.e. shown for checking purposes in the read-only parameter
r1912 (identified stator resistance).
The value is not applied to the control.
No measurement if motor data incorrect.
P1910 = 1: Calculated value for stator resistance (see P0350) is overwritten.
See P1900
r1912[0] - - - - - Float 4

Displays measured stator resistance value (line-to-line). This value also includes the cable resistances.
[0] U_phase
If the value identified (Rs = stator resistance) does not lie within the range 0.1 % < Rs [p. u.] < 100 % fault
message 41 (motor data identification failure) is issued. P0949 provides further information (fault value = 2
in this case).
This value is measured using P1900 = 2.
r1920[0] - - - - - Float 4

Displays identified total dynamic leakage inductance.


[0] U_phase

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 283
Parameter list
8.2 Parameter list

r1925[0] - - - - - Float 4

Displays identified on-state voltage of IGBT.


[0] U_phase
If the identified on-state voltage does not lie within the range 0.0V < 10V fault message 41 (motor data
identification failure) is issued. P0949 provides further information (fault value = 20 in this case).
r1926 - - - - - Float 2

Displays identified dead time of gating unit interlock.


P2000[0...2] 1.00 - 50.00 T - DDS Float 2
550.00
P2000 represents the reference frequency for frequency values which are displayed/transferred as a per-
centage or a hexadecimal value.
Where:
• hexadecimal 4000 H ==> P2000 (e.g.: USS-PZD)
• percentage 100 % ==> P2000 (e.g.: analog input)
If a BICO connection is made between two parameters or alternatively using P0719 or P1000, the 'unit' of
the parameters (standardized (Hex) or physical (i.e. Hz) values) may differ. SINAMICS implicitly makes an
automatic conversion to the target value.

When Quick Commissioning is carried out, P2000 is changed as follows: P2000 = P1082.
P2000 represents the reference frequency of the above mentioned interfaces.
A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface.
Unlike P1082 (Maximum Frequency) this limits the converter frequency internally independent of the ref-
erence frequency.
By modification of P2000 it will also adapt the parameter to the new settings.

SINAMICS V20 Converter


284 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

Reference parameters are intended as an aid to presenting setpoint and actual value signals in a uniform
manner.
This also applies to fixed settings entered as a percentage.
A value of 100 % corresponds to a process data value of 4000H, or 4000 0000H in the case of double
values.
In this respect, the following parameters are available:

Changes to P2000 result in a new calculation of P2004.


P2001[0...2] 10 - 2000 1000 T - DDS U16 3
Full-scale output voltage (i.e. 100 %) used over serial link (corresponds to 4000H).

Changes to P2001 result in a new calculation of P2004.


P2002[0...2] 0.10 - 0.10 T - DDS Float 3
10000.0
Full-scale output current used over serial link (corresponds to 4000H).
If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. A) values) may differ. In this case an automatic conversion to the target value is made.

This parameter is influenced by automatic calculations defined by P0340.


Changes to P2002 result in a new calculation of P2004.
P2003[0...2] 0.10 - 0.75 T - DDS Float 3
99999.0
Full-scale reference torque used over the serial link (corresponds to 4000H).
If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. Nm) values) may differ. In this case an automatic conversion to the target value is made.

This parameter is influenced by automatic calculations defined by P0340.


Changes to P2003 result in a new calculation of P2004.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 285
Parameter list
8.2 Parameter list

P2004[0...2] 0.01 - 0.75 T - DDS Float 3


2000.0
Full-scale reference power used over the serial link (corresponds to 4000H).
If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. kW/hp) values) may differ. In this case an automatic conversion to the target value is made.

P2010[0...1] 6 - 12 6 U, T - - U16 2
Sets baud rate for USS/MODBUS communication.
6 9600 bps
7 19200 bps
8 38400 bps
9 57600 bps
10 76800 bps
11 93750 bps
12 115200 bps
[0] USS/MODBUS on RS485
[1] USS on RS232 (reserved)
Before fitting SINAMICS V20 Smart Access to V20, if RS485 communication is present, then you must set
P2010[1] = 12 via the BOP.
This parameter, index 0, will alter the baudrate on RS485 regardless of the protocol selected in P2023.
P2011[0...1] 0 - 31 0 U, T - - U16 2
Sets unique address for converter.
[0] USS on RS485
[1] USS on RS232 (reserved)
You can connect up to a further 30 converters via the serial link (i.e. 31 converters in total) and control
them with the USS serial bus protocol.
P2012[0...1] 0-8 2 U, T - - U16 3
Defines the number of 16-bit words in PZD part of USS telegram. In this area, process data (PZD) are
continually exchanged between the master and slaves. The PZD part of the USS telegram is used for the
main setpoint, and to control the converter.
[0] USS on RS485
[1] USS on RS232 (reserved)

SINAMICS V20 Converter


286 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

USS protocol consists of PZD and PKW which can be changed by the user via P2012 and P2013 respectively.

PZD transmits a control word and setpoint or status word and actual values.
The number of PZD-words in a USS-telegram are determined by P2012, where the first two words are
either:
a) control word and main setpoint or
b) status word and actual value.
When P2012 is greater or equal to 4 the additional control word is transferred as the 4th PZD-word (de-
fault setting).

P2013[0...1] 0 - 127 127 U, T - - U16 3


Defines the number of 16-bit words in PKW part of USS telegram. The PKW area can be varied. Depend-
ing on the particular requirement, 3-word, 4-word or variable word lengths can be parameterized. The
PKW part of the USS telegram is used to read and write individual parameter values.
0 No words
3 3 words
4 4 words
127 Variable
Data type
U16 (16 Bit) U32 (32 Bit) Float (32 Bit)
P2013 = 3 X Parameter access fault Parameter access fault
P2013 = 4 X X X
P2013 = 127 X X X
[0] USS on RS485
[1] USS on RS232 (reserved)

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 287
Parameter list
8.2 Parameter list

USS protocol consists of PZD and PKW which can be changed by the user via P2012 and P2013 respec-
tively. P2013 determines the number of PKW-words in a USS-telegram. Setting P2013 to 3 or 4 deter-
mines the length of the PKW words (3 = three words and 4 = four words). When P2013 set to 127
automatically adjusts the length of the PKW words are required.

If a fixed PKW length is selected only one parameter value can be transferred.
In the case of indexed parameter, you must use the variable PKW length if you wish to have the values of
all indices transferred in a single telegram.
In selecting the fixed PKW length, it is important to ensure the value in question can be transferred using
this PKW length.
P2013 = 3, fixes PKW length, but does not allow access to many parameter values.
A parameter fault is generated when an out-of-range value is used. The value will not be accepted but the
converter state will not be affected.
Useful for applications where parameters are not changed, but MM3s are also used.
Broadcast mode is not possible with this setting.
P2013 = 4, fixes PKW length.
Allows access to all parameters, but indexed parameters can only be read one index at a time.
Word order for single word values are different to setting 3 or 127, see example below.
P2013 = 127, most useful setting.
PKW reply length varies depending on the amount of information needed.
Can read fault information and all indices of a parameter with a single telegram with this setting.
Example:
Set P0700 to value 5 (P0700 = 2BC (hex))
P2013 = 3 P2013 = 4 P2013 = 127
Master SINAMICS 22BC 0000 0006 22BC 0000 0000 0006 22BC 0000 0006 0000
SINAMICS Master 12BC 0000 0006 12BC 0000 0000 0006 12BC 0000 0006
P2014[0...1] 0 - 65535 2000 T - - U16 3

Index 0 defines a time T_off after which a fault will be generated (F72) if no telegram is received via the
USS/MODBUS channel RS485.
Index 1 defines a time T_off after which a fault will be generated (F71) if no telegram is received via the
USS channel RS232 (reserved).
[0] USS/MODBUS on RS485
[1] USS on RS232 (reserved)
If time set to 0, no fault is generated (i.e. watchdog disabled).
The telegram off time will function on RS485 regardless of the protocol set in P2023.

SINAMICS V20 Converter


288 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r2018[0...7] - - - 4000H - U16 3

Displays process data received via USS/MODBUS on RS485.


USS on RS485:

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 289
Parameter list
8.2 Parameter list

MODBUS on RS485:

[0] Received word 0


[1] Received word 1
... ...
[7] Received word 7
Restrictions:
• If the above serial interface controls the converter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.
• If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transferred in the
2nd PZD-word.
• When P2012 is greater than or equal to 4 the additional control word (2nd control word) must trans-
ferred in the 4th PZD-word, if the above serial interface controls the converter (P0700 or P0719).

SINAMICS V20 Converter


290 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2019[0...7] - 52[0] T 4000H - U32/I 3


16

Displays process data transmitted via USS/MODBUS on RS485.


USS on RS485:

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 291
Parameter list
8.2 Parameter list

MODBUS on RS485:

[0] Transmitted word 0


[1] Transmitted word 1
... ...
[7] Transmitted word 7
If r0052 not indexed, display does not show an index (".0").

SINAMICS V20 Converter


292 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2021 1 - 247 1 T - - U16 2


Sets unique address for converter.
P2022 0 - 10000 1000 U, T - - U16 3

The time in which the converter is allowed to respond to the Modbus master. If the forming of a response
needs more time than specified in this parameter, the processing is done, but no response is sent.
P2023 0-3 1 T - - U16 1
Select the protocol which runs on the RS485 link.
0 None
1 USS
2 Modbus
3 Script terminal
After changing P2023, powercycle the converter. During the powercycle, wait until LED has gone off or
the display has gone blank (may take a few seconds) before re-applying power. If P2023 has been
changed via a PLC, make sure the change has been saved to EEPROM via P0971.
r2024[0...1] - - - - - U16 3

Displays number of error-free USS/MODBUS telegrams received.


[0] USS/MODBUS on RS485
[1] USS on RS232 (reserved)
The state of the telegram information on RS485 is reported regardless of the protocol set in P2023.
r2025[0...1] - - - - - U16 3

Displays number of USS/MODBUS telegrams rejected.


See r2024
See r2024
r2026[0...1] - - - - - U16 3

Displays number of USS/MODBUS character frame errors.


See r2024
See r2024
r2027[0...1] - - - - - U16 3

Displays number of USS/MODBUS with overrun error.


See r2024
See r2024
r2028[0...1] - - - - - U16 3

Displays number of USS/MODBUS telegrams with parity error.


See r2024
See r2024

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 293
Parameter list
8.2 Parameter list

r2029[0...1] - - - - - U16 3
Displays number of USS telegrams with unidentified start.
See r2024
Not used on MODBUS.
r2030[0...1] - - - - - U16 3

Displays number of USS/MODBUS telegrams with BCC/CRC error.


See r2024
See r2024
r2031[0...1] - - - - - U16 3

Displays number of USS/MODBUS telegrams with incorrect length.


See r2024
See r2024
P2034 0-2 2 U, T - - U16 2

Parity of MODBUS telegrams on RS485.


0 No parity
1 Odd parity
2 Even parity
Also see P2010 for baudrate and P2035 for stop bit settings. You must set P2034 to 0 if P2035=2.
P2035 1-2 1 U, T - - U16 2

Number of stop bits in MODBUS telegrams on RS485.


1 1 stop bit
2 2 stop bits
Also see P2010 for baudrate and P2034 for parity settings. You must set P2035 to 2 if P2034=0.
r2036.0...15 - - - - - U16 3

Displays control word 1 from USS/MODBUS on RS485 (i.e. word 1 within USS/MODBUS = PZD1). See
r0054 for the bit field description.
See P2012
r2037.0...15 - - - - - U16 3

Displays control word 2 from USS on RS485 (i.e. word 4 within USS = PZD4). See r0055 for the bit field
description.
See P2012
To enable the external fault (r2037 bit 13) facility via USS, the following parameters must be set:
• P2012 = 4
• P2106 = 1

SINAMICS V20 Converter


294 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r2053[0...7] - 0 - - - U16 3

Displays identification data of the I/O Extension Module.


[0] I/O Extension Module ID number
[1] I/O Extension Module firmware version number (major)
[2] I/O Extension Module firmware version number (minor)
[3] I/O Extension Module firmware version number (hot fix)
[4] I/O Extension Module firmware version number (internal)
[5] Not used
[6] Not used
[7] Company ID (Siemens = 42)
r2067.0...12 - - - - - U16 3

Displays status of digital inputs.

00 Digital input 1 Yes No


01 Digital input 2 Yes No
02 Digital input 3 Yes No
03 Digital input 4 Yes No
04 Digital input 5 Yes No
05 Digital input 6 Yes No
11 Digital input AI1 Yes No
12 Digital input AI2 Yes No
This is used for BICO connection without software intervention.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
P2100[0...2] 0 - 65535 0 T - - U16 3
Selects up to 3 faults or alarms for non-default reactions.
If, for example, an OFF3 is to be carried out instead of an OFF2 for a fault, the fault number has to be
entered in P2100 and the desired reaction selected in P2101 (in this case (OFF3) P2101 = 3).
[0] Fault Number 1
[1] Fault Number 2
[2] Fault Number 3
All fault codes have a default reaction to OFF2.
Only the following faults (F11,F12,F20,F35,F71,F72,F85,F200,F221,F222, and F452) can be changed
from the default reactions.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 295
Parameter list
8.2 Parameter list

P2101[0...2] 0-4 0 T - - U16 3


Sets converter stop reaction values for faults selected by P2100 (alarm number selection). This indexed
parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
0 No reaction, no display
1 OFF1 stop reaction
2 OFF2 stop reaction
3 OFF3 stop reaction
4 No reaction, warning only
[0] Stop reaction value 1
[1] Stop reaction value 2
[2] Stop reaction value 3
Settings 1 - 3 are only available for fault codes.
Setting 4 is only available for warnings.
Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103[0...2] 0 - 4294967295 722.2 T - CDS U32 3

Defines first source of fault acknowledgement.


722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
P2104[0...2] 0 - 4294967295 0 T - CDS U32 3

Selects second source of fault acknowledgement.


See P2103
P2106[0...2] 0 - 4294967295 1 T - CDS U32 3
Selects source of external faults.
See P2103
r2110[0...3] - - - - - U16 2
Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be
viewed.
[0] Recent Warnings --, warning 1
[1] Recent Warnings --, warning 2
[2] Recent Warnings -1, warning 3
[3] Recent Warnings -1, warning 4
Indices 0 and 1 are not stored.
The LED indicates the warning status in this case. The keypad will flash while a warning is active.
P2111 0-4 0 T - - U16 3

Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.

SINAMICS V20 Converter


296 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2113[0...2] 0-1 0 T - - U16 3

Switches off reporting of converter warnings. Can be used in conjunction with P0503 as an adjunct to
keep-running operation.
1 Converter warnings disabled
0 Converter warnings enabled
[0] Drive data set 0 (DDS0)
[1] Drive data set 1 (DDS1)
[2] Drive data set 2 (DDS2)
See also P0503
r2114[0...1] - - - - - U16 3
Displays run time counter.
It is the total time the converter has been powered up. When power is switched off, the value is saved,
and then restored on powerup. The run time counter will be calculate as followed:
Multiply the value in r2114[0] by 65536 and then add it to the value in r2114[1]. The resultant answer will
be in seconds. This means that r2114[0] is not days. Total powerup time = 65536 * r2114[0] + r2114[1]
seconds.
If r2114[0] = 1 and r2114[1] = 20864
We get 1 * 65536 + 20864 = 86400 seconds which equals 1 day.
[0] System Time, Seconds, Upper Word
[1] System Time, Seconds, Lower Word
P2115[0...2] 0 - 65535 257 T - - U16 4
Displays real time.
All converters require an on-board clock function with which fault conditions may be time-stamped and
logged. However, they have no battery backed Real Time Clock (RTC). Converters may support a soft-
ware driven RTC which requires synchronization with the RTC supplied via a serial interface.
The time is stored in a word array parameter P2115. The time will be set by USS Protocol standard "word
array parameter write" telegrams. Once the last word is received in index 2, the software will start running
the timer itself using internal running 1 millisecond tic. Hence becoming like RTC.
If power-cycle takes place, then the real time must be sent again to the converter.
Time is maintained in a word array parameter and encoded as follows - the same format will be used in
fault report logs.
Index High Byte (MSB) Low Byte (LSB)
0 Seconds (0 - 59) Minutes (0 - 59)
1 Hours (0 - 23) Days (1 - 31)
2 Month (1 - 12) Years (00 - 250)
The values are in binary form.
[0] Real Time, Seconds + Minutes
[1] Real Time, Hours + Days
[2] Real Time, Month + Year
P2120 0 - 65535 0 U, T - - U16 4
Indicates total number of fault/warning events. This parameter is incremented whenever a fault/warning
event occurs.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 297
Parameter list
8.2 Parameter list

P2150[0...2] 0.00 - 10.00 3.00 U, T - DDS Float 3

Defines hysteresis level applied for comparing frequency and speed to threshold.
See P1175.
If P1175 is set, P2150 is also used to control the Dual Ramp function.
P2151[0...2] 0 - 4294967295 1170[0] U, T - DDS U32 3

Selects the source of setpoint frequency, actual frequency is compared with this frequency to detect fre-
quency deviation (see monitoring bit r2197.7).
P2155[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 3

Sets a threshold for comparing actual speed or frequency to threshold values f_1. This threshold controls
status bits 4 and 5 in status word 2 (r0053).
P2156[0...2] 0 - 10000 10 U, T - DDS U16 3

Sets delay time prior to threshold frequency f_1 comparison (P2155).


P2157[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 2

Threshold_2 for comparing speed or frequency to thresholds.


See P1175.
If P1175 is set, P2157 is also used to control the Dual Ramp function.
P2158[0...2] 0 - 10000 10 U, T - DDS U16 2

When comparing speed or frequency to threshold f_2 (P2157) this is the time delay before status bits are
cleared.
P2159[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 2

Threshold_3 for comparing speed or frequency to thresholds.


See P1175.
If P1175 is set, P2159 is also used to control the Dual Ramp function.
P2160[0...2] 0 - 10000 10 U, T - DDS U16 2

When comparing speed or frequency to threshold f_3 (P2159) this is the time delay before status bits are
set.
P2162[0...2] 0.00 - 25.00 3.00 U, T - DDS Float 3

Hysteresis speed (frequency) for overspeed detection. For V/f control modes the hysteresis acts below the
maximum frequency.
P2164[0...2] 0.00 - 10.00 3.00 U, T - DDS Float 3

Hysteresis frequency for detecting permitted deviation (from setpoint) or frequency or speed. This fre-
quency controls bit 8 in status word 1 (r0052).
P2166[0...2] 0 - 10000 10 U, T - DDS U16 3

Delay time for signal that indicates completion of ramp-up.

SINAMICS V20 Converter


298 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2167[0...2] 0.00 - 10.00 1.00 U, T - DDS Float 3

Defines the threshold of the monitoring function |f_act| > P2167 (f_off). P2167 influences following func-
tions:
• If the actual frequency falls below this threshold and the time delay has expired, bit 1 in status word 2
(r0053) is reset.
• If an OFF1 or OFF3 was applied and bit 1 is reset the converter will disable the pulse (OFF2).
P2168[0...2] 0 - 10000 0 U, T - DDS U16 3
Defines time for which the converter may operate below switch-off frequency (P2167) before switch off
occurs.
Active if holding brake (P1215) not parameterized.
P2170[0...2] 0.00 - 400.0 100.0 U, T - DDS Float 3

Defines threshold current relative to P0305 (rated motor current) to be used in comparisons of I_act and
I_Thresh. This threshold controls bit 3 in status word 3 (r0053).
P2171[0...2] 0 - 10000 10 U, T - DDS U16 3
Defines delay time prior to activation of current comparison.
P2172[0...2] 0 - 2000 800 U, T - DDS U16 3

Defines DC link voltage to be compared to actual voltage. This voltage controls bits 7 and 8 in status word
3 (r0053).
P2173[0...2] 0 - 10000 10 U, T - DDS U16 3

Defines delay time prior to activation of threshold comparison.


P2177[0...2] 0 - 10000 10 U, T - DDS U16 3

Delay time for identifying that the motor is blocked.


P2179 0.00 - 10.0 3.0 U, T - - Float 3

Threshold current for A922 (no load applied to converter) relative to P0305 (rated motor current).
If a motor setpoint cannot be entered and the current limit (P2179) is not exceeded, warning A922 (no
load applied) is issued when delay time (P2180) expires.
It may be that the motor is not connected or a phase could be missing.
P2180 0 - 10000 2000 U, T - - U16 3

Delay time for detecting a missing output load.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 299
Parameter list
8.2 Parameter list

P2181[0...2] 0-6 0 T - DDS U16 3


Sets load monitoring mode.
This function allows monitoring of mechanical failure of the converter train, e.g. a broken converter belt. It
can also detect conditions which cause an overload, such as a jam. P2182 -P2190 are set to the following
values when this parameter is changed from 0.
P2182 = P1080 (Fmin)
P2183 = P1082 (Fmax) * 0.8
P2184 = P1082 (Fmax)
P2185 = r0333 (rated motor torque) * 1.1
P2186 = 0
P2187 = r0333 (rated motor torque) * 1.1
P2188 = 0
P2189 = r0333 (rated motor torque) * 1.1
P2190 = r0333 (rated motor torque)/2
This is achieved by comparing the actual frequency/torque curve with a programmed envelope (see
P2182 - P2190). If the curve falls outside the envelope, a warning A952 or trip F452 is generated.
0 Load monitoring disabled
1 Warning: Low torque/frequency
2 Warning: High torque/frequency
3 Warning: High/low torque/frequency
4 Trip: Low torque/frequency
5 Trip: High torque/frequency
6 Trip: High/low torque/frequency
P2182[0...2] 0.00 - 550.00 5.00 U, T - DDS Float 3

Sets the lower frequency threshold f_1 for defining the area where the load monitoring is effective. The
frequency torque envelope is defined by 9 parameters - 3 are frequency parameters (P2182 - P2184), and
the other 6 define the low and high torque limits (P2185 - P2190) for each frequency.
See P2181 for calculated default value.
Below the threshold in P2182 and above the threshold in P2184, the load monitoring mode is not active.
In this case the values for normal operation with the torque limits given in P1521 and P1520 are valid.
P2183[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 3

Sets the frequency threshold f_2 for defining the envelope in which the torque values are valid. See
P2182.
See P2181 for calculated default value.
P2184[0...2] 0.00 - 550.00 50.00 U, T - DDS Float 3

Sets the upper frequency threshold f_3 for defining the area where the load monitoring is effective. See
P2182.
See P2181 for calculated default value.

SINAMICS V20 Converter


300 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2185[0...2] 0.0 - 99999.0 Value in U, T - DDS Float 3


r0333
Upper limit threshold value 1 for comparing actual torque.
This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
The factory setting depends on rating data of Power Module and Motor.
P2186[0...2] 0.0 - 99999.0 0.0 U, T - DDS Float 3

Lower limit threshold value 1 for comparing actual torque.


See P2181 for calculated default value.
P2187[0...2] 0.0 - 99999.0 Value in U, T - DDS Float 3
r0333
Upper limit threshold value 2 for comparing actual torque.
This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
See P2185
P2188[0...2] 0.0 - 99999.0 0.0 U, T - DDS Float 3

Lower limit threshold value 2 for comparing actual torque.


See P2181 for calculated default value.
P2189[0...2] 0.0 - 99999.0 Value in U, T - DDS Float 3
r0333
Upper limit threshold value 3 for comparing actual torque.
This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
See P2185
P2190[0...2] 0.0 - 99999.0 0.0 U, T - DDS Float 3

Lower limit threshold value 3 for comparing actual torque.


See P2181 for calculated default value.
P2192[0...2] 0 - 65 10 U, T - DDS U16 3

P2192 defines a delay before warning/trip becomes active.


- It is used to eliminate events caused by transient conditions.
- It is used for both methods of fault detection.
r2197.0...12 - - - - - U16 3

Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function.

00 |f_act| <= P1080 (f_min) Yes No


01 |f_act| <= P2155 (f_1) Yes No
02 |f_act| > P2155 (f_1) Yes No
03 f_act >= zero Yes No

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 301
Parameter list
8.2 Parameter list

04 f_act >= setp. (f_set) Yes No


05 |f_act| <= P2167 (f_off) Yes No
06 |f_act| >= P1082 (f_max) Yes No
07 f_act == setp. (f_set) Yes No
08 Act. current |r0027| >= P2170 Yes No
09 Act. unfilt. Vdc < P2172 Yes No
10 Act. unfilt. Vdc > P2172 Yes No
11 Output load is not present Yes No
12 |f_act| > P1082 with delay Yes No
r2198.0...12 - - - - - U16 3

Monitoring word 2 which indicates the state of monitor functions. Each bit represents one monitor function.

00 |f_act| <= P2157 (f_2) Yes No


01 |f_act| > P2157 (f_2) Yes No
02 |f_act| <= P2159 (f_3) Yes No
03 |f_act| > P2159 (f_3) Yes No
04 Unused Yes No
05 Reserved Yes No
06 Reserved Yes No
07 Reserved Yes No
08 Reserved Yes No
09 Reserved Yes No
10 Reserved Yes No
11 Load monitoring signals an alarm Yes No
12 Load monitoring signals a fault Yes No
P2200[0...2] 0 - 4294967295 0 U, T - CDS U32 2
Allows user to enable/disable the PID controller. Setting to 1 enables the PID closed-loop controller.
Setting 1 automatically disables normal ramp times set in P1120 and P1121 and the normal frequency
setpoints.
Following an OFF1 or OFF3 command, however, the converter frequency will ramp down to zero using
the ramp time set in P1121 (P1135 for OFF3).
The minimum and maximum motor frequencies (P1080 and P1082) as well as the skip frequencies
(P1091 to P1094) remain active on the converter output.
However, enabling skip frequencies with PID control can produce instabilities.
The PID setpoint source is selected using P2253.
The PID setpoint and the PID feedback signal are interpreted as [%] values (not [Hz]).
The output of the PID controller is displayed as [%] and then normalized into [Hz] through P2000 (refer-
ence frequency) when PID is enabled.
The reverse command is not active when PID is active.
Attention: P2200 and P2803 are locked parameter against each other. PID and FFB of the same data set
cannot be active at same time.

SINAMICS V20 Converter


302 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2201[0...2] -200.00 - 200.00 10.00 U, T - DDS Float 2


Defines fixed PID setpoint 1. There are 2 types of fixed frequencies:
1. Direct selection (P2216 = 1):
– In this mode of operation 1 Fixed Frequency selector (P2220 to P2223) selects 1 fixed frequency.
– If several inputs are active together, the selected frequencies are summed. E.g.: PID-FF1 + PID-
FF2 + PID-FF3 + PID-FF4.
2. Binary coded selection (P2216 = 2):
– Up to 16 different fixed frequency values can be selected using this method.
P2200 = 1 required in user access level 2 to enable setpoint source.
You may mix different types of frequencies; however, remember that they will be summed if selected
together.
P2201 = 100 % corresponds to 4000 hex.
P2202[0...2] -200.00 - 200.00 20.00 U, T - DDS Float 2
Defines fixed PID setpoint 2.
See P2201
P2203[0...2] -200.00 - 200.00 50.00 U, T - DDS Float 2
Defines fixed PID setpoint 3.
See P2201
P2204[0...2] -200.00 - 200.00 100.00 U, T - DDS Float 2
Defines fixed PID setpoint 4.
See P2201
P2205[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 5.
See P2201
P2206[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 6.
See P2201
P2207[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 7.
See P2201
P2208[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 8.
See P2201
P2209[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 9.
See P2201
P2210[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 10.
See P2201
P2211[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 11.
See P2201

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 303
Parameter list
8.2 Parameter list

P2212[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2


Defines fixed PID setpoint 12.
See P2201
P2213[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 13.
See P2201
P2214[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 14.
See P2201
P2215[0...2] -200.00 - 200.00 0.00 U, T - DDS Float 2
Defines fixed PID setpoint 15.
See P2201
P2216[0...2] 1-2 1 T - DDS U16 2
Fixed frequencies for PID setpoint can be selected in two different modes. P2216 defines the mode.
1 Direct selection
2 Binary selection
P2220[0...2] 0 - 4294967295 722.3 T - CDS U32 3

Defines command source of fixed PID setpoint selection bit 0.


P2221[0...2] 0 - 4294967295 722.4 T - CDS U32 3

Defines command source of fixed PID setpoint selection bit 1.


P2222[0...2] 0 - 4294967295 722.5 T - CDS U32 3

Defines command source of fixed PID setpoint selection bit 2.


P2223[0...2] 0 - 4294967295 722.6 T - CDS U32 3

Defines command source of fixed PID setpoint selection bit 3.


r2224 - - - - - Float 2

Displays total output of PID fixed setpoint selection.


r2224 = 100 % corresponds to 4000 hex.
r2225.0 - - - - - U16 3

Displays the status of PID fixed frequencies.

00 Status of FF Yes No
P2231[0...2] 0-3 0 U, T - DDS U16 2
PID-MOP mode specification

00 Setpoint store active Yes No


01 No On-state for MOP necessary Yes No
Defines the operation mode of the motorized potentiometer. See P2240.

SINAMICS V20 Converter


304 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2232 0-1 1 T - - U16 2

Inhibits reverse setpoint selection of the PID-MOP.


0 Reverse direction is allowed
1 Reverse direction inhibited
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
frequency).
P2235[0...2] 0 - 4294967295 0 T - CDS U32 3

Defines source of UP command.


To change setpoint:
- Configure a digital input as source
- Use UP/DOWN key on operator panel.
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.2
% (P0310). When the signal is enabled longer than 1 second the ramp generator accelerates with the rate
of P2247.
P2236[0...2] 0 - 4294967295 0 T - CDS U32 3

Defines source of DOWN command.


See P2235
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.2
% (P0310). When the signal is enabled longer than 1 second the ramp generator decelerates with the rate
of P2248.
P2240[0...2] -200.00 - 200.00 10.00 U, T - DDS Float 2
Setpoint of the motor potentiometer. Allows user to set a digital PID setpoint in [%].
P2240 = 100 % corresponds to 4000 hex.
The start value gets active (for the MOP output) only at the start of the MOP. P2231 influences the start
value behavior as follows:
• P2231 = 0:
P2240 gets immediately active in the OFF-state and when changed in the ON-state, it gets active after
the next OFF and ON cycle.
• P2231 = 1:
The last MOP output before stop is stored as starting value, since storing is selected, so a change of
P2240 while in ON-state has no effect. In OFF-state P2240 can be changed.
• P2231 = 2:
The MOP is active every time, so the change of P2240 affects after the next power-cycle or a change
of P2231 to 0.
• P2231 = 3:
The last MOP output before power down is stored as starting value, since the MOP is active inde-
pendent from the ON-command, a change of P2240 has only effect in the case of a change of P2231.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 305
Parameter list
8.2 Parameter list

P2241[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source to change over from manual to automatic mode. If using the motorized potentiome-
ter in the manual mode the setpoint is changed using two signals for up and down, e.g. P2235 and P2236.
If using the automatic mode the setpoint must be interconnected via the connector input (P2242).
0: manually
1: automatically
Refer to: P2235, P1036, P2242
P2242[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source for the setpoint of the motorized potentiometer if automatic mode P2241 is select-
ed.
Refer to: P2241
P2243[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source for the setting command to accept the setting value for the motorized potentiome-
ter. The value becomes effective for a 0/1 edge of the setting command.
Refer to: P2244
P2244[0...2] 0 - 4294967295 0 T - CDS U32 3

Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0/1 edge of
the setting command.
Refer to: P2243
r2245 - - - - - Float 3

Displays the motorized potentiometer setpoint before it passed the PID-MOP RFG.
P2247[0...2] 0.00 - 1000.0 10.00 U, T - DDS Float 2

Sets the ramp-up time for the internal PID-MOP ramp-function generator. The setpoint is changed from
zero up to limit defined in P1082 within this time.
Refer to: P2248, P1082
P2248[0...2] 0.00 - 1000.0 10.00 U, T - DDS Float 2

Sets the ramp-down time for the internal PID-MOP ramp-function generator. The setpoint is changed from
limit defined in P1082 down to zero within this time.
Refer to: P2247, P1082
r2250 - - - PERCE - Float 2
NT
Displays output setpoint of motor potentiometer.
P2251 0-1 0 T - - U16 3
Enables function of PID controller.
0 PID as setpoint
1 PID as trim
Active when PID loop is enabled (see P2200).

SINAMICS V20 Converter


306 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2253[0...2] 0 - 4294967295 0 U, T 4000H CDS U32 2


Defines setpoint source for PID setpoint input. This parameter allows the user to select the source of the
PID setpoint. Normally, a digital setpoint is selected either using a fixed PID setpoint or an active setpoint.
P2254[0...2] 0 - 4294967295 0 U, T 4000H CDS U32 3
Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to the PID set-
point.
755 Analog input 1
2224 Fixed PI setpoint (see P2201 to P2207)
2250 Active PI setpoint (see P2240)
P2255 0.00 - 100.00 100.00 U, T - - Float 3
Gain factor for PID setpoint. The PID setpoint input is multiplied by this gain factor to produce a suitable
ratio between setpoint and trim.
P2256 0.00 - 100.00 100.00 U, T - - Float 3
Gain factor for PID trim. This gain factor scales the trim signal, which is added to the main PID setpoint.
P2257 0.00 - 650.00 1.00 U, T - - Float 2

Sets the ramp-up time for the PID setpoint.


P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120). PID ramp time is effective only
on PID setpoint and active only when PID setpoint is changed or when RUN command is given (when PID
setpoint uses this ramp to reach its value from 0%).
Setting the ramp-up time too short may cause the converter to trip, on overcurrent for example.
P2258 0.00 - 650.00 1.00 U, T - - Float 2

Sets ramp-down time for PID setpoint.


P2200 = 1 (PID control is enabled) disables normal ramp-down time (P1121). PID setpoint ramp effective
only on PID setpoint changes. P1121 (ramp-down time) and P1135 (OFF3 ramp-down time) define the
ramp times used after OFF1 and OFF3 respectively.
Setting the ramp-down time too short can cause the converter to trip on overvoltage F2/overcurrent F1.
r2260 - - - - - Float 2

Displays total active PID setpoint after PID-RFG.


r2260 = 100 % corresponds to 4000 hex.
P2261 0.00 - 60.00 0.00 U, T - - Float 3

Sets a time constant for smoothing the PID setpoint.


P2261 = 0 = no smoothing.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 307
Parameter list
8.2 Parameter list

r2262 - - - - - Float 3

Displays filtered PID setpoint after PID-RFG. r2262 is the result of the value in r2260, filtered with PT1-
Filter and the time constant given in P2261.
r2262 = 100 % corresponds to 4000 hex.
P2263 0-1 0 T - - U16 3
Sets the PID controller type.
0 D component on feedback signal
1 D component on error signal
P2264[0...2] 0 - 4294967295 0 U, T 4000H CDS U32 2
Selects the source of the PID feedback signal.
See P2254
When analog input is selected, offset and gain can be implemented using P0756 to P0760 (analog input
scaling).
P2265 0.00 - 60.00 0.00 U, T - - Float 2

Defines time constant for PID feedback filter.


r2266 - - - - - Float 2

Displays PID feedback signal.


r2266 = 100 % corresponds to 4000 hex.
P2267 -200.00 - 200.00 100.00 U, T - - Float 3

Sets the upper limit for the value of the feedback signal.
When PID is enabled (P2200 = 1) and the signal rises above this value, the converter will trip with F222.
P2267 = 100 % corresponds to 4000 hex.

SINAMICS V20 Converter


308 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2268 -200.00 - 0.00 U, T - - Float 3


200.00
Sets lower limit for value of feedback signal.
When PID is enabled (P2200 = 1) and the signal drops below this value, the converter will trip with F221.
P2268 = 100 % corresponds to 4000 hex.
P2269 0.00 - 500.00 100.00 U, T - - Float 3

Allows the user to scale the PID feedback as a percentage value. A gain of 100.0 % means that feedback
signal has not changed from its default value.
P2270 0-3 0 U, T - - U16 3

Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269.
0 Disabled
1 Square root (root(x))
2 Square (x*x)
3 Cube (x*x*x)
P2271 0-1 0 U, T - - U16 2
Allows the user to select the transducer type for the PID feedback signal.
0 Disabled
1 Inversion of PID feedback signal
It is essential that you select the correct transducer type. If you are unsure whether 0 or 1 is applicable,
you can determine the correct type as follows:
1. Disable the PID function (P2200 = 0).
2. Increase the motor frequency while measuring the feedback signal.
3. If the feedback signal increases with an increase in motor frequency, the PID transducer type should be 0.
4. If the feedback signal decreases with an increase in motor frequency the PID transducer type should
be set to 1.
r2272 - - - - - Float 2

Displays PID scaled feedback signal.


r2272 = 100 % corresponds to 4000 hex.
r2273 - - - - - Float 2
Displays PID error (difference) signal between setpoint and feedback signals.
r2273 = 100 % corresponds to 4000 hex.
P2274 0.000 - 60.000 0.000 U, T - - Float 2
Sets PID derivative time.
P2274 = 0: The derivative term does not have any effect (it applies a gain of 1).
P2280 0.000 - 65.000 3.000 U, T - - Float 2
Allows user to set proportional gain for PID controller. The PID controller is implemented using the stand-
ard model. For best results, enable both P and I terms.
P2280 = 0 (P term of PID = 0): The I term acts on the square of the error signal.
P2285 = 0 (I term of PID = 0): PID controller acts as a P or PD controller respectively.
If the system is prone to sudden step changes in the feedback signal, P term should normally be set to a
small value (0.5) with a faster I term for optimum performance.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 309
Parameter list
8.2 Parameter list

P2285 0.000 - 60.000 0.000 U, T - - Float 2


Sets integral time constant for PID controller.
See P2280
P2291 -200.00 - 100.00 U, T - - Float 2
200.00
Sets upper limit for PID controller output
If f_max (P1082) is greater than P2000 (reference frequency), either P2000 or P2291 (PID output upper
limit) must be changed to achieve f_max.
P2291 = 100 % corresponds to 4000 hex (as defined by P2000 (reference frequency)).
P2292 -200.00 - 0.00 U, T - - Float 2
200.00
Sets lower limit for the PID controller output.
A negative value allows bipolar operation of PID controller.
P2292 = 100 % corresponds to 4000 hex.
P2293 0.00 - 100.00 1.00 U, T - - Float 3

Sets maximum ramp rate on output of PID.


When PI is enabled, the output limits are ramped up from 0 to the limits set in P2291 (PID output upper
limit) and P2292 (PID output lower limit). Limits prevent large step changes appearing on the output of the
PID when the converter is started. Once the limits have been reached, the PID controller output is instan-
taneous. These ramp times are used whenever a RUN command is issued.
If an OFF1 or OFF 3 are issued, the converter output frequency ramps down as set in P1121 (ramp-down
time) or P1135 (OFF3 ramp-down time).
r2294 - - - - - Float 2

Displays PID output.


r2294 = 100 % corresponds to 4000 hex.
P2295 -100.00 - 100.00 U, T - - Float 3
100.00
Allows the user to scale the PID output as a percentage value. A gain of 100.0 % means that output signal
has not changed from its default value.
The ramp rate applied by the PID controller is clamped to a rate of 0.1s/100% to protect the converter.
r2349 - 0 - - - U16 3
Displays PID status word.

00 PID disabled Yes No


01 PID limit reached Yes No

SINAMICS V20 Converter


310 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2350 0-4 0 U, T - - U16 2


Enables autotune function of PID controller.
0 PID autotuning disabled
1 PID autotuning via Ziegler Nichols (ZN) standard
2 PID autotuning as 1 plus some overshoot (O/S)
3 PID autotuning as 2 little or no overshoot (O/S)
4 PID autotuning PI only, quarter damped response
Active when PID loop is enabled (see P2200).
• P2350 = 1
This is the standard Ziegler Nichols (ZN) tuning which should be a quarter damped response to a step.
• P2350 = 2
This tuning will give some overshoot (O/S) but should be faster than option 1.
• P2350 = 3
This tuning should give little or no overshoot but will not be as fast as option 2.
• P2350 = 4
This tuning only changes values of P and I and should be a quarter damped response.
The option to be selected depends on the application but broadly speaking option 1 will give a good re-
sponse, whereas if a faster response is desired option 2 should be selected.
If no overshoot is desired then option 3 is the choice. For cases where no D term is wanted then option 4
can be selected.
The tuning procedure is the same for all options. It is just the calculation of P, I, and D values that are
different.
After autotune this parameter is set to zero (autotune completed).
P2354 60 - 65000 240 U, T - - U16 3

This parameter determines the time that the autotuning code will wait before aborting a tuning run if no
oscillation has been obtained.
P2355 0.00 - 20.00 5.00 U, T - - Float 3
Sets applied offset and deviation for PID autotuning.
This can be varied depending on plant conditions e.g. a very long system time constant might require a
larger value.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 311
Parameter list
8.2 Parameter list

P2360[0...2] 0-2 0 U, T - DDS U16 2

Cavitation protection enabled.


Will generate a fault/warning when cavitation conditions are deemed to be present.

0 Disable
1 Fault
2 Warn

SINAMICS V20 Converter


312 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2361[0...2] 0.00 - 200.00 40.00 U, T - DDS Float 2


Feedback threshold over which a fault/warning is triggered, as a percentage (%).
P2362[0...2] 0 - 65000 30 U, T - DDS U16 2

The time for which cavitation conditions have to be present before a fault/warning is triggered.
P2365[0...2] 0-2 0 U, T - DDS U16 2

Select or disable the hibernation functionality.


0 Disabled
1 Frequency hibernation (The converter uses the frequency setpoint as the
wakeup trigger. You can use P2366 and P2367 to configure this function.)
2 PID hibernation (The converter uses the PID error as the wakeup trigger. You
can use P2390, P2391, and P2392 to configure this function.)
P2366[0...2] 0 - 254 5 U, T - DDS U16 3

With hibernation enabled. If the frequency demand drops below the threshold there is a delay of P2366
seconds before the converter is stopped.
P2367[0...2] 0 - 254 2 U, T - DDS U16 3

With hibernation enabled. If pulses have been disabled by the unit going into hibernation, and the fre-
quency demand has increased to above the hibernation threshold, there will be a delay of P2367 seconds
before the converter restarts.
P2370[0...2] 0-1 0 T - DDS U16 3
Selects stop mode for external motors when motor staging is in use.
0 Normal stop
1 Sequence stop
P2371[0...2] 0-3 0 T - DDS U16 3

Selects configuration of external motors (M1, M2) used for motor staging feature.
0 Motor staging disabled
1 M1 = 1 x MV, M2 = Not fitted
2 M1 = 1 x MV, M2 = 1 x MV
3 M1 = 1 x MV, M2 = 2 x MV
For this kind of motor application it is mandatory to disable negative frequency setpoint!

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 313
Parameter list
8.2 Parameter list

Motor staging allows the control of up to 2 additional staged pumps or fans, based on a PID control sys-
tem.
The complete system consists of one pump controlled by the converter with up to 2 further pumps/fans
controlled from contactors or motor starters.
The contactors or motor starter are controlled by outputs from the converter.
The diagram below shows a typical pumping system.
A similar system could be set up using fans and air ducts, instead of pumps and pipes.

By default the motor states are controlled from digital outputs.


In the text below, the following terminology will be used:
MV - Variable speed (Converter controlled motor)
M1 - Motor switched with digital output 1
M2 - Motor switched with digital output 2
Staging: The process of starting one of the fixed speed motors.
De-staging: The process of stopping one of the fixed speed motors.
When the converter is running at maximum frequency, and the PID feedback indicates that a higher speed
is required, the converter switches on (stages) one of the digital output controlled motors M1 and M2.
At the same time, to keep the controlled variable as constant as possible, the converter must ramp down
to minimum frequency.
Therefore, during the staging process, PID control must be suspended (see P2378 and diagram below)

SINAMICS V20 Converter


314 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

When the converter is running at minimum frequency, and the PID feedback indicates that a lower speed
is required, the converter switches off (de-stages) one of the digital output controlled motors M1 and M2.
In this case, the converter must ramp from minimum frequency to maximum frequency outside of PID
control (see P2378 and diagram below).

P2372[0...2] 0-1 0 T - DDS U16 3


Enables motor cycling for the motor staging feature.
When enabled, the motor selected for staging/destaging is based on the hours run counter P2380. When
staging, the motor with the least hours is switched on. When destaging, the motor with most hours is
switched off.
If staged motors are different sizes the choice of motor is first based on required motor size, and then if
there is still a choice, on hours run.
0 Disabled
1 Enabled
P2373[0...2] 0.0 - 200.0 20.0 U, T PERCENT DDS Float 3

P2373 as a percentage of PID setpoint that PID error r2273 must be exceeded before staging delay
starts.
The value of this parameter must always be smaller than delay override lockout timer P2377.
P2374[0...2] 0 - 650 30 U, T - DDS U16 3
Time that PID error r2273 must exceed motor staging hysteresis P2373 before staging occurs.
P2375[0...2] 0 - 650 30 U, T - DDS U16 3
Time that PID error r2273 must exceed motor staging hysteresis P2373 before destaging occurs.
P2376[0...2] 0.0 - 200.0 25.0 U, T PERCENT DDS Float 3

P2376 as a percentage of PID setpoint. When the PID error r2273 exceeds this value, a motor is
staged/destaged irrespective of the delay timers.
The value of this parameter must always be larger than staging hysteresis P2373.
P2377[0...2] 0 - 650 30 U, T - DDS U16 3

Time for which delay override is prevented after a motor has been staged or destaged.
This prevents a second staging event immediately after a first, being caused by the transient conditions
after the first staging event.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 315
Parameter list
8.2 Parameter list

P2378[0...2] 0.0 - 120.0 50.0 U, T PERCENT DDS Float 3

The frequency as a percentage of maximum frequency. During a (de) staging event, as the converter
ramps from maximum to minimum frequency (or vice versa) this is the frequency at which the digital out-
put is switched.
This is illustrated by the following diagrams.

SINAMICS V20 Converter


316 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r2379.0...1 - - - - - U16 3

Output word from the motor staging feature that allows external connections to be made.

00 Start motor 1 Yes No


01 Start motor 2 Yes No
P2380[0...2] 0.0 - 0.0 U, T - - Float 3
429496720.0
Displays hours run for external motors. To reset the running hours, set the value to zero, any other value
is ignored.
P2380 = 0.1 ==> 6 min
60 min = 1 h
[0] Motor 1 hrs run
[1] Motor 2 hrs run
[2] Not used

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 317
Parameter list
8.2 Parameter list

P2390 -200.00 - 0 U, T - - Float 3


% 200.00
The PID hibernation setpoint P2390 is a percentage of the rated motor frequency P0310.
When the value of P2365 is set to 2 and the converter under PID control drops below the PID hibernation
setpoint P2390, the PID hibernation timer P2391 is started. When the PID hibernation timer has expired,
the converter is ramped down to stop and enters the PID hibernation mode.
PID hibernation is an added feature to enhance PID functionality, and switches off the motor when the
converter is running at low setpoint. Note that this is an independent function from staging, although it can
be used together with staging.
If PID hibernation setpoint is 0, the PID hibernation function is disabled. The PID hibernation setpoint
should be greater than the minimum frequency (P1080). Reverse operation is not allowed with the PID
hibernation mode.
P2391 0 - 254 0 T - - U16 3
When the PID hibernation timer P2391 has expired, the converter is ramped down to stop and enters the
PID hibernation mode.
P2392 -200.00 - 0 T - - Float 3
% 200.00
While in PID hibernation mode, the PID controller continues to generate the error r2273. Once this reach-
es the restart point P2392, the converter immediately ramps to the setpoint calculated by the PID control-
ler.
r2399 - 0 - - - U16 3

Displays PID hibernation status word.

Bit 00 Not used Yes No


Bit 01 PID hibernation enabled (PID hibernation is ena- Yes No
bled and the converter is not in PID hibernation.)
Bit 02 Hibernation active (PID hibernation is enabled and Yes No
the converter is in PID hibernation.)
P2800 0-1 0 U, T - - U16 3
Free function blocks (FFB) are enabled in two steps:
1. P2800 enables all free function blocks (P2800 = 1).
2. P2801 and P2802 respectively, enable each free function block individually. Additionally fast free func-
tion blocks can be enabled via P2803 = 1.
0 Disable
1 Enable
All active function blocks will be calculated in every 128 ms, fast free function blocks in every 8 ms.

SINAMICS V20 Converter


318 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2801[0...16] 0-6 0 U, T - - U16 3


P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0 or P2802[x] >
0). In addition, P2801 and P2802 determine the chronological order of each function block by setting the
level in which the free function block will work.
The following table shows that the priority decreases from right to left and from top to bottom.

0 Not Active
1 Level 1
2 Level 2
... ...
6 Level 6
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2
FFBs will be calculated in following order: P2802[3], P2801[3] , P2801[4], P2802[4]
[0] Enable AND 1
[1] Enable AND 2
[2] Enable AND 3
[3] Enable OR 1
[4] Enable OR 2
[5] Enable OR 3
[6] Enable XOR 1
[7] Enable XOR 2
[8] Enable XOR 3
[9] Enable NOT 1
[10] Enable NOT 2
[11] Enable NOT 3
[12] Enable D-FF 1
[13] Enable D-FF 2
[14] Enable RS-FF 1
[15] Enable RS-FF 2
[16] Enable RS-FF 3
Set P2800 to 1 to enable function blocks.
All active function blocks will be calculated in every 128 ms, if set to level 1 to 3. Fast free function blocks
(level 4 to 6) will be calculated in every 8 ms.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 319
Parameter list
8.2 Parameter list

P2802[0...13] 0-3 0 U, T - - U16 3


Enables free function blocks (FFB) and determines the chronological order of each function block. See
P2801.
0 Not Active
1 Level 1
2 Level 2
3 Level 3
[0] Enable timer 1
[1] Enable timer 2
[2] Enable timer 3
[3] Enable timer 4
[4] Enable ADD 1
[5] Enable ADD 2
[6] Enable SUB 1
[7] Enable SUB 2
[8] Enable MUL 1
[9] Enable MUL 2
[10] Enable DIV 1
[11] Enable DIV 2
[12] Enable CMP 1
[13] Enable CMP 2
Set P2800 to 1 to enable function blocks.
All active function blocks, enabled with P2802, will be calculated in every 128 ms.
P2803[0...2] 0-1 0 U, T - CDS U16 3
Fast free function blocks (FFB) are enabled in two steps:
1. P2803 enables the use of fast free function blocks (P2803 = 1).
2. P2801 enables each fast free function block individually and determines the chronological order
(P2801[x] = 4 to 6).
0 Disable
1 Enable
All active fast function blocks will be calculated in every 8 ms.
Attention: P2200 and P2803 are locked parameter against each other. PID and FFB of the same data set
cannot be active at same time.

SINAMICS V20 Converter


320 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2810[0...1] 0- 0 U, T - - U32 3
4294967295
P2810[0], P2810[1] define inputs of AND 1 element, output is r2811.

[0] Binector input 0 (BI 0)


[1] Binector input 1 (BI 1)
P2801[0] assigns the AND element to the processing sequence.
r2811.0 - - - - - U16 3
Output of AND 1 element. Displays and logic of bits defined in P2810[0], P2810[1].

00 Output of BO Yes No
See P2810
P2812[0...1] 0 - 4294967295 0 U, T - - U32 3
P2812[0], 2812[1] define inputs of AND 2 element, output is r2813.
See P2810
P2801[1] assigns the AND element to the processing sequence.
r2813.0 - - - - - U16 3
Output of AND 2 element. Displays and logic of bits defined in P2812[0], P2812[1]. See r2811 for the bit
field description.
See P2812
P2814[0...1] 0 - 4294967295 0 U, T - - U32 3
P2814[0], P2814[1] define inputs of AND 3 element, output is r2815.
See P2810
P2801[2] assigns the AND element to the processing sequence.
r2815.0 - - - - - U16 3
Output of AND 3 element. Displays and logic of bits defined in P2814[0], P2814[1]. See r2811 for the bit
field description.
See P2814
P2816[0...1] 0 - 4294967295 0 U, T - - U32 3
P2816[0], P2816[1] define inputs of OR 1 element, output is r2817.

See P2810
P2801[3] assigns the OR element to the processing sequence.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 321
Parameter list
8.2 Parameter list

r2817.0 - - - - - U16 3
Output of OR 1 element. Displays or logic of bits defined in P2816[0], P2816[1]. See r2811 for the bit field
description.
See P2816
P2818[0...1] 0 - 4294967295 0 U, T - - U32 3
P2818[0], P2818[1] define inputs of OR 2 element, output is r2819.
See P2810
P2801[4] assigns the OR element to the processing sequence.
r2819.0 - - - - - U16 3
Output of OR 2 element. Displays or logic of bits defined in P2818[0], P2818[1]. See r2811 for the bit field
description.
See P2818
P2820[0...1] 0 - 4294967295 0 U, T - - U32 3
P2820[0], P2820[1] define inputs of OR 3 element, output is r2821.
See P2810
P2801[5] assigns the OR element to the processing sequence.
r2821.0 - - - - - U16 3
Output of OR 3 element. Displays or logic of bits defined in P2820[0], P2820[1]. See r2811 for the bit field
description.
See P2820
P2822[0...1] 0 - 4294967295 0 U, T - - U32 3
P2822[0], P2822[1] define inputs of XOR 1 element, output is r2823.

See P2810
P2801[6] assigns the XOR element to the processing sequence.
r2823.0 - - - - - U16 3
Output of XOR 1 element. Displays exclusive-or logic of bits defined in P2822[0], P2822[1]. See r2811 for
the bit field description.
See P2822
P2824[0...1] 0 - 4294967295 0 U, T - - U32 3
P2824[0], P2824[1] define inputs of XOR 2 element, output is r2825.
See P2810
P2801[7] assigns the XOR element to the processing sequence.
r2825.0 - - - - - U16 3
Output of XOR 2 element. Displays exclusive-or logic of bits defined in P2824[0], P2824[1]. See r2811 for
the bit field description.
See P2824
P2826[0...1] 0 - 4294967295 0 U, T - - U32 3
P2826[0], P2826[1] define inputs of XOR 3 element, output is r2827.
See P2810
P2801[8] assigns the XOR element to the processing sequence.

SINAMICS V20 Converter


322 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r2827.0 - - - - - U16 3
Output of XOR 3 element. Displays exclusive-or logic of bits defined in P2826[0], P2826[1]. See r2811 for
the bit field description.
See P2826
P2828 0- 0 U, T - - U32 3
4294967295
P2828 defines input of NOT 1 element, output is r2829.

P2801[9] assigns the NOT element to the processing sequence.


r2829.0 - - - - - U16 3
Output of NOT 1 element. Displays not logic of bit defined in P2828. See r2811 for the bit field descrip-
tion.
See P2828
P2830 0- 0 U, T - - U32 3
4294967295
P2830 defines input of NOT 2 element, output is r2831.
P2801[10] assigns the NOT element to the processing sequence.
r2831.0 - - - - - U16 3
Output of NOT 2 element. Displays not logic of bit defined in P2830. See r2811 for the bit field descrip-
tion.
See P2830
P2832 0- 0 U, T - - U32 3
4294967295
P2832 defines input of NOT 3 element, output is r2833.
P2801[11] assigns the NOT element to the processing sequence.
r2833.0 - - - - - U16 3
Output of NOT 3 element. Displays not logic of bit defined in P2832. See r2811 for the bit field descrip-
tion.
See P2832

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 323
Parameter list
8.2 Parameter list

P2834[0...3] 0 - 4294967295 0 U, T - - U32 3


P2834[0], P2834[1], P2834[2], P2834[3] define inputs of D-FlipFlop 1, outputs are r2835, r2836.

[0] Binector input: Set


[1] Binector input: D input
[2] Binector input: Store pulse
[3] Binector input: Reset
P2801[12] assigns the D-FlipFlop to the processing sequence.
r2835.0 - - - - - U16 3
Displays output of D-FlipFlop 1, inputs are defined in P2834[0], P2834[1], P2834[2], P2834[3]. See r2811
for the bit field description.
See P2834
r2836.0 - - - - - U16 3
Displays Not-output of D-FlipFlop 1, inputs are defined in P2834[0], P2834[1], P2834[2], P2834[3]. See
r2811 for the bit field description.
See P2834
P2837[0...3] 0 - 4294967295 0 U, T - - U32 3
P2837[0], P2837[1], P2837[2], P2837[3] define inputs of D-FlipFlop 2, outputs are r2838, r2839.
See P2834
P2801[13] assigns the D-FlipFlop to the processing sequence.
r2838.0 - - - - - U16 3
Displays output of D-FlipFlop 2, inputs are defined in P2837[0], P2837[1], P2837[2], P2837[3]. See r2811
for the bit field description.
See P2837
r2839.0 - - - - - U16 3
Displays Not-output of D-FlipFlop 2, inputs are defined in P2837[0], P2837[1], P2837[2], P2837[3]. See
r2811 for the bit field description.
See P2837

SINAMICS V20 Converter


324 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2840[0...1] 0 - 4294967295 0 U, T - - U32 3


P2840[0], P2840[1] define inputs of RS-FlipFlop 1, outputs are r2841, r2842.

[0] Binector input: Set


[1] Binector input: Reset
P2801[14] assigns the RS-FlipFlop to the processing sequence.
r2841.0 - - - - - U16 3
Displays output of RS-FlipFlop 1, inputs are defined in P2840[0], P2840[1]. See r2811 for the bit field
description.
See P2840
r2842.0 - - - - - U16 3
Displays Not-output of RS-FlipFlop 1, inputs are defined in P2840[0], P2840[1]. See r2811 for the bit field
description.
See P2840
P2843[0...1] 0- 0 U, T - - U32 3
4294967295
P2843[0], P2843[1] define inputs of RS-FlipFlop 2, outputs are r2844, r2845.
See P2840
P2801[15] assigns the RS-FlipFlop to the processing sequence.
r2844.0 - - - - - U16 3
Displays output of RS-FlipFlop 2, inputs are defined in P2843[0], P2843[1]. See r2811 for the bit field
description.
See P2843
r2845.0 - - - - - U16 3
Displays Not-output of RS-FlipFlop 2, inputs are defined in P2843[0], P2843[1]. See r2811 for the bit field
description.
See P2843
P2846[0...1] 0- 0 U, T - - U32 3
4294967295
P2846[0], P2846[1] define inputs of RS-FlipFlop 3, outputs are r2847, r2848.
See P2840
P2801[16] assigns the RS-FlipFlop to the processing sequence.
r2847.0 - - - - - U16 3
Displays output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1]. See r2811 for the bit field
description.
See P2846

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 325
Parameter list
8.2 Parameter list

r2848.0 - - - - - U16 3
Displays Not-output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1]. See r2811 for the bit field description.
See P2846
P2849 0 - 4294967295 0 U, T - - U32 3
Define input signal of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.

P2802[0] assigns the timer to the processing sequence.

SINAMICS V20 Converter


326 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P2850 0.0 - 9999.9 0.0 U, T - - Float 3


Defines delay time of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
See P2849
P2851 0 - 13 0 U, T - - U16 3
Selects mode of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
0 ON delay (seconds)
1 OFF delay (seconds)
2 ON/OFF delay (seconds)
3 Pulse generator (seconds)
10 ON delay (minutes)
11 OFF delay (minutes)
12 ON/OFF delay (minutes)
13 Pulse generator (minutes)
See P2849
r2852.0 - - - - - U16 3
Displays output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
See r2811 for the bit field description.
See P2849
r2853.0 - - - - - U16 3
Displays Not-output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852,
r2853. See r2811 for the bit field description.
See P2849
P2854 0 - 4294967295 0 U, T - - U32 3
Define input signal of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
P2802[1] assigns the timer to the processing sequence.
P2855 0.0 - 9999.9 0.0 U, T - - Float 3
Defines delay time of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
See P2854
P2856 0 - 13 0 U, T - - U16 3
Selects mode of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
See P2851 for value description.
See P2854
r2857.0 - - - - - U16 3
Displays output of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
See r2811 for the bit field description.
See P2854
r2858.0 - - - - - U16 3
Displays Not-output of timer 2 P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
See r2811 for the bit field description.
See P2854
P2859 0 - 4294967295 0 U, T - - U32 3
Define input signal of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are r2862, r2863.
P2802[2] assigns the timer to the processing sequence.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 327
Parameter list
8.2 Parameter list

P2860 0.0 - 9999.9 0.0 U, T - - Float 3


Defines delay time of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are r2862, r2863.
See P2859
P2861 0 - 13 0 U, T - - U16 3
Selects mode of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are r2862, r2863. See
P2851 for value description.
See P2859
r2862.0 - - - - - U16 3
Displays output of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are r2862, r2863.
See r2811 for the bit field description.
See P2859
r2863.0 - - - - - U16 3
Displays Not-output of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are r2862,
r2863. See r2811 for the bit field description.
See P2859
P2864 0 - 4294967295 0 U, T - - U32 3
Define input signal of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.
P2802[3] assigns the timer to the processing sequence.
P2865 0.0 - 9999.9 0.0 U, T - - Float 3
Defines delay time of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are r2867, r2868.
See P2864
P2866 0 - 13 0 U, T - - U16 3
Selects mode of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are r2867, r2868. See
P2851 for value description.
See P2864
r2867.0 - - - - - U16 3
Displays output of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are r2867, r2868.
See r2811 for the bit field description.
See P2864
r2868.0 - - - - - U16 3
Displays Not-output of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are r2867,
r2868. See r2811 for the bit field description.
See P2864
P2869[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Adder 1, result is in r2870.

[0] Connector input 0 (CI 0)


[1] Connector input 1 (CI 1)
P2802[4] assigns the Adder to the processing sequence.

SINAMICS V20 Converter


328 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r2870 - - - - - Float 3
Result of Adder 1.
See P2869
P2871[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Adder 2, result is in r2872.
See P2869
P2802[5] assigns the Adder to the processing sequence.
r2872 - - - - - Float 3
Result of Adder 2.
See P2871
P2873[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Subtractor 1, result is in r2874.

See P2869
P2802[6] assigns the Subtractor to the processing sequence.
r2874 - - - - - Float 3
Result of Subtractor 1.
See P2873
P2875[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Subtractor 2, result is in r2876.
See P2869
P2802[7] assigns the Subtractor to the processing sequence.
r2876 - - - - - Float 3
Result of Subtractor 2.
See P2875
P2877[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Multiplier 1, result is in r2878.

See P2869
P2802[8] assigns the Multiplier to the processing sequence.
r2878 - - - - - Float 3
Result of Multiplier 1.
See P2877

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 329
Parameter list
8.2 Parameter list

P2879[0...1] 0- 0 U, T 4000H - U32 3


4294967295
Define inputs of Multiplier 2, result is in r2880.
See P2869
P2802[9] assigns the Multiplier to the processing sequence.
r2880 - - - - - Float 3
Result of Multiplier 2.
See P2879
P2881[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Define inputs of Divider 1, result is in r2882.

See P2869
P2802[10] assigns the Divider to the processing sequence.
r2882 - - - - - Float 3
Result of Divider 1.
See P2881
P2883[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Define inputs of Divider 2, result is in r2884.
See P2869
P2802[11] assigns the Divider to the processing sequence.
r2884 - - - - - Float 3
Result of Divider 2.
See P2883
P2885[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Defines inputs of Comparator 1, output is r2886.

See P2869
P2802[12] assigns the Comparator to the processing sequence.

SINAMICS V20 Converter


330 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r2886.0 - - - - - Float 3
Displays result bit of Comparator 1. See r2811 for the bit field description.
See P2885
P2887[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Defines inputs of Comparator 2, output is r2888.
See P2869
P2802[13] assigns the Comparator to the processing sequence.
r2888.0 - - - - - U16 3
Displays result bit of Comparator 2. See r2811 for the bit field description.
See P2887
P2889 -200.00 - 0.00 U, T - - Float 3
200.00
Fixed percent setting 1.

P2890 -200.00 - 0.00 U, T - - Float 3


200.00
Fixed percent setting 2.
P2940 0- 0.0 T - - U32 2
4294967295
Defines the source to release the wobble function.
P2945 0.001 - 1.000 T - - Float 2
10.000
Sets the frequency of the wobble signal.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 331
Parameter list
8.2 Parameter list

P2946 0.000 - 0.200 0.000 T - - Float 2

Sets the value for the amplitude of the wobble-signal as a proportion of the present ramp function genera-
tor (RFG) output. The value of P2946 is multiplied by the output value of the RFG then added to RFG out-
put.
For example, if the RFG output is 10 Hz, and P2946 has a value of 0.100, the wobble signal amplitude will
be 0.100 * 10 = 1 Hz. This means that the RFG output will therefore wobble between 9 Hz and 11 Hz.
P2947 0.000 - 1.000 0.000 T - - Float 2

Sets the value for decrement step at the end of the positive signal period. The amplitude of the step is
dependent upon the signal amplitude as follows:
Amplitude of signal decrement step = P2947 * P2946
P2948 0.000 - 1.000 0.000 T - - Float 2

Sets the value for the increment step at the end of the negative signal period. The amplitude of the incre-
ment step is dependent upon the signal amplitude as follows:
Amplitude of signal increment step = P2948 * P2946
P2949 0 - 100 50 T - - U16 2

Sets the relative widths of the rising and falling pulses. The value in P2949 sets the proportion of the wob-
ble period (determined by P2945) allocated to the rising pulse, the remainder of the time is allocation to the
falling pulse.
A value of 60% in P2949 means that 60% of the wobble period the wobble output will be rising. For the
remaining 40% of the wobble period the wobble output will be falling.
r2955 - - - - - Float 2

Displays the output of the wobble function.


r3113.0...15 - - - - - U16 1
Gives information about actual fault.

00 Converter error Yes No


01 Power line failure Yes No
02 Intermediate circuit power voltage Yes No
03 Error power electronics Yes No
04 Converter overtemperature Yes No
05 Earth leakage Yes No
06 Motor overload Yes No
07 Bus fault Yes No
09 Reserved Yes No
10 Fault internal communication Yes No
11 Motor current limit Yes No
12 Supply failure Yes No
13 Reserved Yes No
14 Reserved Yes No
15 Other error Yes No

SINAMICS V20 Converter


332 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r3237[0...1] - 0 - - - Float 4

Displays calculated rms dc-link ripple voltage.


[0] Ripple Volts
[1] Unfiltered Volts
P3350[0...2] 0-3 0 T - - U16 2
Selects the super torque function. Three different super torque modes are available:
• Super Torque - applies a pulse of torque for a given time to help start the motor
• Hammer Start - applies a sequence of torque pulses to help start the motor
• Blockage Clearing - performs a reverse-forward operation to clear a pump blockage

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 333
Parameter list
8.2 Parameter list

SINAMICS V20 Converter


334 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

0 Super torque modes disabled


1 Super torque enabled
2 Hammer start enabled
3 Blockage clearing enabled
[0] Drive data set 0 (DDS0)
[1] Drive data set 1 (DDS1)
[2] Drive data set 2 (DDS2)
When the value of P3350 is changed, the value of P3353 is changed as follows:
• P3350 = 2: P3353 = 0.0s
• P3350 2: P3353 = default
The ramp time of 0s gives an additional 'kicking' effect when hammer start is in use.
This setting can be overridden by the operator.
If blockage clearing mode is enabled (P3350 = 3), make sure that reverse direction is not inhibited, i.e.
P1032 = P1110 = 0.
P3351[0...2] 0 - 4294967295 0 T - CDS U32 2
Defines source of the super torque enable when P3352 = 2.
Applies only when P3352 = 2.
P3352[0...2] 0-2 1 T - - U16 2

Defines when the super torque function becomes active.


0 Enabled on first run after power-up
1 Enabled on every run
2 Enabled by digital input
See P3350
If P3352 = 2, enable source is defined by P3351
P3353[0...2] 0.0 - 650.0 5.0 T - - Float 2
Defines the ramp time to be used for all super torque functions. Overrides the P1120/P1060 when convert-
er is ramping to super torque/hammer start frequency (P3354) or the blockage clearing frequency (P3361).
See P3350
The value of this parameter is changed by the setting of P3350.
See the description of P3350.
P3354[0...2] 0.0 - 550.0 5.0 T - - Float 2

Defines the frequency at which the additional boost is applied for super torque and hammer start modes.
See P3350
P3355[0...2] 0.0 - 200.0 150.0 T PERCE - Float 2
NT
The magnitude of the Super Torque boost is calculated as follows:
V_ST = P0305 * Rsadj * (P3355/100)
Note:
Rsadj = stator resistance adjusted for temperature
Rsadj = (r0395/100) * (P0304/(sqrt(3) * P0305)) * P0305 * sqrt(3)
See P3350
Up to 200% of rated motor current (P0305) or limit of converter.
The Super Torque boost is calculated in the same way as Continuous Boost (P1310). As the stator resistance is used,
the calculated voltage is only accurate at 0 Hz. Thereafter, it will vary in the same way as Continuous Boost.
Setting in P0640 (motor overload factor [%]) limits the boost.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 335
Parameter list
8.2 Parameter list

P3356[0...2] 0.0 - 20.0 5.0 T - - Float 2


Sets the time for which the additional boost will be applied, when the output frequency is held at P3354 Hz.
See P3350
P3357[0...2] 0.0 - 200.0 150.0 T PERCE - Float 2
NT
The magnitude of the Hammer Start boost is calculated as follows:
V_HS = P0305 * Rsadj * (P3357/100)
Note:
Rsadj = stator resistance adjusted for temperature
Rsadj = (r0395/100) * (P0304/(sqrt(3) * P0305)) * P0305 * sqrt(3)
See P3350
Up to 200% of rated motor current (P0305) or limit of converter.
The Hammer Start boost is calculated in the same way as Continuous Boost (P1310). As the stator re-
sistance is used, the calculated voltage is only accurate at 0Hz. Thereafter, it will vary in the same way as
Continuous Boost.
Setting in P0640 (motor overload factor [%]) limits the boost.
P3358[0...2] 1 - 10 5 C, T - - U16 2
The number of times the hammer start boost level (P3357) is applied.
See P3350
P3359[0...2] 0 - 1000 300 T - - U16 2
Time for which the additional boost is applied for each repetition.
See P3350
The time must be at least 3 x motor magnetization time (P0346).
P3360[0...2] 0 - 1000 100 T - - U16 2
Time for which the additional boost is removed for each repetition.
See P3350
During this time, the boost level drops to the level defined by P1310 (continuous boost).
P3361[0...2] 0.0 - 550.0 5.0 T - - Float 2

Defines the frequency at which the converter runs in the opposite direction to the setpoint during the block-
age clearing reverse sequence.
See P3350
P3362[0...2] 0.0 - 20.0 5.0 T - - Float 2

Sets the time for which the converter runs in the opposite direction to the setpoint during the reverse se-
quence.
See P3350
P3363[0...2] 0-1 0 T - - U16 2
Selects whether the converter ramps to, or starts directly from, the blockage clearing frequency (P3361).
0 Disable rapid ramp for blockage clearing
1 Enable rapid ramp for blockage clearing
See P3350
If P3363 = 1, the output jumps to the reverse frequency - this introduces a "kicking" effect which helps to
clear the blockage.

SINAMICS V20 Converter


336 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

P3364[0...2] 1 - 10 1 T - - U16 2

The number of times the blockage clearing reversing cycle is repeated.


See P3350
r3365 - - - - - U16 2

Shows the operational status of the Super Torque function, while active.

00 Super Torque Active Yes No


01 Super Torque Ramping Yes No
02 Super Torque Boost On Yes No
03 Super Torque Boost Off Yes No
04 Blockage Clearing Reverse On Yes No
05 Blockage Clearing Reverse Off Yes No
P3852[0...2] 0 - 4294967295 0 U, T - CDS U32 2

Defines command source of protection enable command. If binary input is equal to one, then protection will
be initiated. If converter is stopped and protection signal becomes active, protection measure is applied as
follows:
• If P3853 0, frost protection is applied by applying the given frequency to the motor
• If P3853 = 0, and P3854 0, condensation protection is applied by applying the given current to the
motor
The protection function may be overridden under the following circumstances:
• If converter is running and protection signal becomes active, signal is ignored
• If converter is turning motor due to active protection signal and a RUN command is received, RUN
command overrides frost signal
• Issuing an OFF command while protection is active will stop the motor
P3853[0...2] 0.00 - 550.00 5.00 U, T - DDS Float 2

The frequency applied to the motor when frost protection is active.


See also P3852.
P3854[0...2] 0 - 250 100 U, T - DDS U16 2

The DC current (as a percentage of nominal current) which is applied to the motor when condensation
protection is active.
See also P3852.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 337
Parameter list
8.2 Parameter list

P3900 0-3 0 C(1) - - U16 1

Performs calculations necessary for optimized motor operation. After completion of calculation, P3900 and
P0010 (parameter groups for commissioning) are automatically reset to their original value 0.
0 No quick commissioning
1 End quick commissioning with factory reset
2 End quick commissioning
3 End quick commissioning and initiate motor data calculation
Changeable only when P0010 = 1 (quick commissioning).
P3900 = 1:
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick
commissioning" are retained; all other parameter changes, including the I/O settings, are lost. Motor calcu-
lations are also performed.
P3900 = 2:
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning
menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the
motor calculations performed.
P3900 = 3:
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commis-
sioning with this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (motor
weight), P0350 (stator resistance), P2000 (reference frequency), P2002 (reference current).
When transferring P3900, the converter uses its processor to carry out internal calculations.
Communications - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to
make these calculations. This can result in the following error messages at the connected SIMATIC S7
control (communications via Fieldbus):
• Parameter fault 30
• Converter fault 70
• Converter fault 75
r3930[0...4] - - - - - U16 3
Displays the A5E number and the converter data versions.
[0] A5E 1st 4 digits
[1] A5E 2nd 4 digits
[2] Logistic Version
[3] Fixed Data Version
[4] Calib Data Version
P3950 0 - 255 0 U, T - - U16 4

Accesses special parameters for development (expert only) and factory functionality (calibration parame-
ter).
r3954[0...12] - - - - - U16 4
Used to classify firmware (only for SIEMENS internal purposes).
[0] CM label (increment/branch)
[1] CM label (counter)
[2] CM label
[3...10] GUI ID
[11] GUI ID major release
[12] GUI ID minor release

SINAMICS V20 Converter


338 Operating Instructions, 05/2020, A5E34559884-013
Parameter list
8.2 Parameter list

r3978 - - - - - U32 4
Counts the number of changed BICO links.
P3981 0-1 0 T - - U16 4
Resets active faults when changed from 0 to 1.
0 No fault reset
1 Reset fault
See P0947 (last fault code)
Automatically reset to 0.
P3984 100 - 10000 1000 T - - U16 3

Defines time after which a fault will be generated (F73) if no telegram is received from the client.
Setting 0 = watchdog disabled
r3986[0...1] - - - - - U16 4
Number of parameters on the converter.
[0] Read only
[1] Read & write
r4000 - r4064
P7844 0-2 0 T - - U16 3

After an automatic download from the SD card at startup, this parameter will be automatically set to 1. Also
a fault F395 will be set.
With setting to P7844 = 0 you quit F395 and confirm the parameter settings. Setting this parameter to 2 is
only possible if an automatic download has been performed at startup. In this case the download will be
undone and the previously stored parameters will be enabled.
0 Acceptance test/confirmation OK
1 Acceptance test/confirmation is pending
2 Undo clone
If no automatic download from the SD card has been performed during startup the setting 2 is not possible.
If the clone file contains user defaults and the cloning at startup is rejected with P7844 = 2, parameters are
set to the user defaults in the clone file instead of the previously saved values.
P8458 0-4 2 C, T - - U16 3
This parameter specifies whether a cloning at startup will be performed. The File clone00.bin will be used.
If no SD card is inserted there will be a normal startup.
0 No startup cloning
1 Clone at startup once
2 Clone at startup always
3 Clone at startup once, except the motor data
4 Clone at startup always, except the motor data
Default value is 2. After first cloning the parameter is set to 0. If an SD card is inserted without a valid file
the converter will set a fault F61/F63/F64 which can only be cleared by a power-cycle. The fault is signaled
by a flashing RUN LED (Commissioning). The SF LED is not activated. P8458 will not be changed by per-
forming a factory reset.
P8553 0-1 0 U, T - - U16 1
Selects whether to have menus with no text or menus with some text on the BOP.
0 Menus with no text
1 Menus with some text

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 339
Parameter list
8.2 Parameter list

SINAMICS V20 Converter


340 Operating Instructions, 05/2020, A5E34559884-013
If there are multiple active faults and alarms, the BOP first displays all faults one after
another. Once all faults are displayed, it displays all alarms in succession.

Immediately when a fault occurs the fault icon shows and the display transitions to the
faults screen. The faults screen displays the fault number proceeded by "F".

To navigate through the current list of faults, press or .

To view the converter status at fault, press (> 2 s); to return to the fault code display,
press (< 2 s).
To clear/acknowledge the fault, press or acknowledge externally if the converter has
been set up so; to ignore the fault, press .
After you acknowledge or ignore the fault, the screen returns to the previous display. The
fault icon remains active until the fault is cleared/acknowledged.

Under the following circumstances, the faults screen displays again:


• If the fault has not been cleared and the button is pressed, the faults screen displays
again.
• If there is no key press for 60 seconds.
If a fault is active and there has been no key press for 60 seconds, the backlight (P0070)
flashes.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 341
Faults and alarms
9.1 Faults

You can use P2100 to select up to 3 faults for non-default stop reaction and use P2101 to
specify the reaction. For more information, see the description of P2100 and P2101 in
Section "Parameter list (Page 197)".

• Motor power (P0307) does not corre- Check the following:


Overcurrent spond to the converter power (r0206). • Motor power (P0307) must correspond to converter
• Motor lead short circuit power (r0206).
• Earth faults • Cable length limits must not be exceeded.
r0949 = 0: Hardware reported • Motor cable and motor must have no short-circuits or
r0949 = 1: Software reported earth faults.
r0949 = 22: Hardware reported • Motor parameters must match the motor in use.
• Value of stator resistance (P0350) must be correct.
• Motor must not be obstructed or overloaded.
• Increase ramp-up time (P1120)
• Reduce starting boost level (P1312)
• Main supply voltage too high Check the following:
Overvoltage • Motor is in regenerative mode • Supply voltage (P0210) must lie within limits indicated on
r0949 = 0: Hardware reported rating plate.
r0949 = 1 or 2: Software reported • Ramp-down time (P1121) must match inertia of load.
• Required braking power must lie within specified limits.
• Vdc controller must be enabled (P1240) and parameter-
ized properly.

Regenerative mode can be caused by fast ramp downs or if


the motor is driven by an active load.
Higher inertia requires longer ramp times; otherwise, apply
braking resistor.

SINAMICS V20 Converter


342 Operating Instructions, 05/2020, A5E34559884-013
Faults and alarms
9.1 Faults

• Main supply failed. Check supply voltage.


Undervoltage • Shock load outside specified limits.
r0949 = 0: Hardware reported
r0949 = 1 or 2: Software reported
• Converter overloaded Check the following:
Converter over- • Ventilation inadequate • Load or load cycle too high?
temperature
• Pulse frequency too high • Motor power (P0307) must match converter power
• Surrounding temperature too high (r0206)

• Fan inoperative • Pulse frequency must be set to default value


• Surrounding temperature too high?
• Fan must turn when converter is running

• Converter overloaded. Check the following:


Converter I2t • Load cycle too demanding. • Load cycle must lie within specified limits.
• Motor power (P0307) exceeds con- • Motor power (P0307) must match converter power
verter power capability (r0206). (r0206)
F5 cannot be cleared until the converter overload
utilization (r0036) is lower than the converter I2t warning
(P0294).
• Load at start-up is too high Check the following:
Chip tempera- • Load step is too high • Load or load step too high?
ture rise ex-
• Ramp-up rate is too fast • Increase ramp-up time (P1120).
ceeds critical
levels • Motor power (P0307) must match converter power
(r0206).
• Use setting P0290 = 0 or 2 for preventing F6.

• Motor overloaded Check the following:


Motor over- • Load or load step too high?
temperature
• Motor nominal overtemperatures (P0626 - P0628) must
be correct
• Motor temperature warning level (P0604) must match

• This fault may occur if small motors Check the following:


are used and run at a frequency below • Motor current is not in excess of the motor nominal cur-
15 Hz, even though the motor temper- rent as indicated by the motor rating plate
ature is within limits.
• Physical temperature of the motor lies within limits
If these two conditions are satisfied, then set parameter
P0335 = 1.
Wire breakage of converter temperature
Converter tem- (heat sink) sensor.
perature signal
lost
The calculated DC ripple level has ex- Check the mains supply wiring.
DC ripple too ceeded the safe threshold. This is com-
high monly caused by loss of one of the mains
input phases.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 343
Faults and alarms
9.1 Faults

The calculated output ripple level has • Check the output wiring.
Output current exceeded the safe threshold. Common
• Check the mechanical vibration of the motor.
ripple too high causes are as follows:
• Check whether the setting of converter response to high
• Output phase missing
output current ripple (P0296) is correct.
• High motor vibration

Auto restart attempts exceed value of


Maximum P1211.
number of auto
restart attempts
exceeded
Motor data identification failed. Check the following:
Motor data • r0949 = 0: No load applied • r0949 = 0: is the motor connected to the converter?
identification
• r0949 = 1: Current limit level reached • r0949 = 1 - 49: are the motor data in P0304 - P0311
failure
during identification. correct?
• r0949 = 2: Identified stator resistance • Check what type of motor wiring is required (star, delta).
less than 0.1% or greater than 100%.
• r0949 = 30: Current controller at volt-
age limit
• r0949 = 40: Inconsistency of identified
dataset, at least one identification
failed
Percentage values based on the imped-
ance Zb = Vmot,nom/sqrt(3)/Imot,nom
Read or write failure while access to • Must be power-cycled to cancel this bug as some pa-
Parameter EEPROM. This can also be caused by the rameters may not be read correctly.
EEPROM fault EEPROM being full, too many parameters
have been changed. • Factory reset and new parameterization, if power-cycle
does not remove fault.
• Change some parameters back to default values if the
EEPROM is full, then power-cycle.
• Change converter.

• r0949 = 1: EEPROM full


• r0949 = 1000 + block No: reading data block failed
• r0949 = 2000 + block No: reading data block timeout
• r0949 = 3000 + block No: reading data block CRC failed
• r0949 = 4000 + block No: writing data block failed
• r0949 = 5000 + block No: writing data block timeout
• r0949 = 6000 + block No: writing data block verify failed
• r0949 = 7000 + block No: reading data block at wrong time
• r0949 = 8000 + block No: writing data block at wrong time
• r0949 = 9000 + block No: factory reset did not work because
restart or power failure

SINAMICS V20 Converter


344 Operating Instructions, 05/2020, A5E34559884-013
Faults and alarms
9.1 Faults

Read failure for converter information or


Converter soft- invalid data. • r0949 = 1: Failed reading converter identity
ware fault • r0949 = 2: Converter identity wrong
• r0949 = 3: Failed reading converter version
• r0949 = 4: Converter version wrong
• r0949 = 5: Start of Part 1 converter data wrong
• r0949 = 6: Converter number of temperature sensor wrong
• r0949 = 7: Converter number of application wrong
• r0949 = 8: Start of Part 3 converter data wrong
• r0949 = 9: Reading converter data string wrong
• r0949 = 10: Converter CRC failed
• r0949 = 11: Converter is blank
• r0949 = 15: Failed CRC of converter block 0
• r0949 = 16: Failed CRC of converter block 1
• r0949 = 17: Failed CRC of converter block 2
• r0949 = 20: Converter invalid
• r0949 = 30: Directory size wrong
• r0949 = 31: Directory ID wrong
• r0949 = 32: Invalid block
• r0949 = 33: File size wrong
• r0949 = 34: Data section size wrong

• r0949 = 35: Block section size wrong


• r0949 = 36: RAM size exceeded
• r0949 = 37: Parameter size wrong
• r0949 = 38: Device header wrong
• r0949 = 39: Invalid file pointer
• r0949 = 40: Scaling block version wrong
• r0949 = 41: Calibration block version wrong
• r0949 = 50: Wrong serial number format
• r0949 = 51: Wrong serial number format start
• r0949 = 52: Wrong serial number format end
• r0949 = 53: Wrong serial number format month
• r0949 = 54: Wrong serial number format day
• r0949 = 1000 + addr: Converter read data failed
• r0949 = 2000 + addr: Converter write data failed
• r0949 = 3000 + addr: Converter read data wrong time
• r0949 = 4000 + addr: Converter write data wrong time
• r0949 = 5000 + addr: Converter read data invalid
• r0949 = 6000 + addr: Converter write data invalid
• Power-cycle converter
• Contact service department or change converter

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 345
Faults and alarms
9.1 Faults

Internal communications failure. Check converter.


Asic timeout Fault appears sporadically:

• r0949 = 0: Hardware reported link fail


• r0949 = 1: Software reported link fail
• r0949 = 6: Feedback is not disabled for reading converter data
• r0949 = 7: During converter download, message didn't transmit
to disable feedback
• Communication failure due to EMC problems
• Check - and if necessary - improve EMC
• Use EMC filter

Parameter cloning failed. • r0949 = 0: Use an SD card with FAT16 or FAT32 format
SD card pa- • r0949 = 0: The SD card is not con- , or fit an SD card to the converter.
rameter cloning nected or the card type is incorrect or • r0949 = 1: Check the SD card (for example, is the card
failed the card failed to initialize for automatic memory full?) - format the card again to FAT16 or
cloning. FAT32.
• r0949 = 1: Converter data cannot be • r0949 = 2: Put the correct named file in the correct direc-
written to the card. tory /USER/SINAMICS/DATA.
• r0949 = 2: Parameter cloning file is • r0949 = 3: Make sure file is accessible - recreate file if
unavailable. possible.
• r0949 = 3: The SD card cannot read • r0949 = 4: File has been changed - recreate file.
the file.
• r0949 = 4: Reading data from the
clone file failed (e.g., reading failed,
data or checksum wrong).
File exists but the contents are not valid Recopy and ensure operation completes.
Parameter control word corruption.
cloning con-
tents invalid
File exists but was not the correct con- Ensure clone from compatible converter type.
Parameter verter type.
cloning con-
tents incompat-
ible
No Clone00.bin file in the correct directory If an automatic clone is required:
Converter at- /USER/SINAMICS/DATA. • Insert the SD card with correct file and power-cycle.
tempted to do If no automatic clone is required:
an automatic
clone during • Remove the card if not needed and power-cycle.
startup • Reset P8458 = 0 and power-cycle.

Fault can only be cleared by a power-cycle.


Communication is no longer established Reconnect the module and check whether it is operating
I/O Extension with the I/O Extension Module. correctly. Acknowledge the fault. If the fault persists, replace
Module com- the module.
munication fault
No setpoint values from USS (on RS232) Check USS master on RS232.
USS setpoint during telegram off time.
fault (on
RS232)

SINAMICS V20 Converter


346 Operating Instructions, 05/2020, A5E34559884-013
Faults and alarms
9.1 Faults

No setpoint values from USS/MODBUS Check USS/MODBUS master on RS485.


USS/MODBUS (on RS485) during telegram off time.
setpoint fault
(on RS485)
• Broken wire
Signal lost on • Signal out of limits
analog input
External fault triggered via command input • Check P2106.
External fault via control word 2, bit 13. • Disable control word 2 bit 13 as command source.
• Disable terminal input for fault trigger.
Software error Contact service department or change converter.
Watchdog reset
Software error or processor failure. Contact service department or change converter.
Stack overflow
Script of the internal converter program Check the script and make necessary corrections.
Script error has stopped running due to script errors
except for forced exit.
PID feedback below minimum value • Change value of P2268.
PID feedback P2268. • Adjust feedback gain.
below minimum
value
PID feedback above maximum value • Change value of P2267.
PID feedback P2267. • Adjust feedback gain.
above maxi-
mum value
During startup the converter checks if the Internal failures cannot be fixed.
Configuration configuration vector (SZL vector) has been r0949 = 13 - Make sure the right power module is fitted.
vector for the programmed correctly and if hardware
converter failed matches the programmed vector. If not the
converter will trip. Fault needs power-cycle to be acknowledged.
• r0949 = 1: Internal failure - no hard-
ware configuration vector available.
• r0949 = 2: Internal failure - no software
configuration vector available.
• r0949 = 11: Internal failure - converter
code not supported.
• r0949 = 12: Internal failure - software
vector not possible.
• r0949 = 13: Wrong power module
fitted.
• r0949 > 1000: Internal failure - wrong
I/O board fitted.

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 347
Faults and alarms
9.1 Faults

This fault occurs after a startup clone. It The current parameter set needs to be checked and con-
Acceptance can also be caused by a faulty read from firmed by clearing the fault.
test/confirmatio the EEPROM, see F51 for more details.
n pending A startup clone could have changed and
might not match the application.
This parameter set needs to be checked
before the converter can start a motor.
• r0949 = 3/4: Converter data change
• r0949 = 5: Startup clone via an SD
card has been performed
• r0949 = 10: Previous startup clone was
aborted
Conditions exist for cavitation damage. If cavitation is not occurring, reduce the cavitation threshold
Cavitation pro- Cavitation damage is damage caused to a P2361, or increase the cavitation protection delay. Ensure
tection failure pump in pumping systems when the fluid sensor feedback is working.
is not flowing sufficiently. This can lead to
heat build up and subsequent damage to
the pump.
Load conditions on motor indicate belt Check the following:
Load monitor- failure or mechanical fault.
• No breakage, seizure or obstruction of converter train.
ing trip • r0949 = 0: trip low torque/speed • Apply lubrication if required.
• r0949 = 1: trip high torque/speed If using an external speed sensor, check the following pa-
rameters for correct function:
- P2192 (delay time for permitted deviation)
- P2182 (threshold frequency f1)
- P2183 (threshold frequency f2)
- P2184 (threshold frequency f3)
If using a specific torque/speed range, check parameters:
- P2182 (threshold frequency 1)
- P2183 (threshold frequency 2)
- P2184 (threshold frequency 3)
- P2185 (upper torque threshold 1)
- P2186 (lower torque threshold 1)
- P2187 (upper torque threshold 2)
- P2188 (lower torque threshold 2)
- P2189 (upper torque threshold 3)
- P2190 (lower torque threshold 3)
- P2192 (delay time for permitted deviation)

SINAMICS V20 Converter


348 Operating Instructions, 05/2020, A5E34559884-013
Faults and alarms
9.2 Alarms

If an alarm is activated the alarm icon shows immediately and then the display shows the
alarm code proceeded by "A".

Note that alarms cannot be acknowledged. They are cleared automatically once the warning
has been rectified.

You can disable stop reaction for three selected alarms or all alarms:
Use P2100 to select up to 3 alarms and use P2101 to disable stop reaction for the
selected alarms.
Use P2113 to disable stop reaction for all alarms.
For more information, see the description of P2100, P2101, and P2113 in Section
"Parameter list (Page 202)".

• Motor power does not correspond to the converter See F1.


Current limit power
• Motor leads are too long
• Earth faults

• Small motors (120 W) under FCC and light load Use V/f operation for very small motors
may cause a high current
Overvoltage limit is reached. This warning can occur If this warning is displayed permanently,
Overvoltage limit during ramp down, if the Vdc controller is disabled check converter input voltage.
(P1240 = 0).
• Main supply failed. Check main supply voltage.
Undervoltage • Main supply and consequently DC-link voltage
limit (r0026) below specified limit.
Warning level of converter heat sink temperature,
Converter over- warning level of chip junction temperature, or allowed r0037[0]: Heat sink temperature
temperature change in temperature on chip junction is exceeded,
r0037[1]: Chip junction temperature (includes
resulting in pulse frequency reduction and / or output
heat sink)
frequency reduction (depending on parameterization in
P0290). Check the following:
• Surrounding temperature must lie within
specified limits
• Load conditions and load steps must be
appropriate
• Fan must turn when converter is running

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 349
Faults and alarms
9.2 Alarms

Warning level exceeded, current will be reduced if Check that load cycle lies within specified
Converter I2t parameterized (P0610 = 1). limits.
Overload warning. Difference between heat sink and Check that load steps and shock loads lie
IGBT junction IGBT junction temperature exceeds warning limits. within specified limits.
temperature rise
warning
Converter heat sink temperature signal loss. Possible Contact service department or change con-
Converter tem- sensor fallen off. verter.
perature signal
lost
• Motor overloaded. Independently of the kind of temperature
Motor over- determination check:
• Load cycles or load steps too high.
temperature I2t • P0604 motor temperature warning thresh-
old
• P0625 motor surrounding temperature
• Check if name plate data is correct. If not,
perform quick commissioning. Accurate
equivalent circuit data can be found by
performing motor identification (P1900 =
2).
• Check if motor weight (P0344) is reasona-
ble. Change if necessary.
• With P0626, P0627, and P0628 the
standard overtemperature can be
changed, If the motor is not a SIEMENS
standard motor.
The calculated output ripple level has exceeded the • Check the output wiring.
Output current safe threshold. Common causes are as follows:
• Check the mechanical vibration of the
ripple too high • Loss of one of the output phases motor.
• High motor vibration
The braking energy is too large. Reduce the braking energy.
Braking resistor The braking resistor is not suited for the application. Use a braking resistor with a higher rating.
overload
Motor data identification (P1900) selected or running.
Motor data identi-
fication active
Internal time slice overrun Contact service department.
RTOS overrun
warning

SINAMICS V20 Converter


350 Operating Instructions, 05/2020, A5E34559884-013
Faults and alarms
9.2 Alarms

Occurs Check the following:


Vdc_max control- • if main supply voltage (P0210) is permanently too high. • Input voltage must lie within range.
ler de-activated
• if motor is driven by an active load, causing motor to go • Load must be match.
into regenerative mode. • In certain cases apply braking resistor.
• at very high load inertias, when ramping down.
If warning A910 occurs while the converter is in
standby (output pulses disabled) and an ON command
is subsequently given, the Vdc_max controller (A911)
will not be activated unless warning A910 is rectified.
The Vdc_max controller works to keep the DC-link Check the following:
Vdc_max control- voltage (r0026) below the level specified in r1242. • Supply voltage must lie within limits indi-
ler active cated on rating plate.
• Ramp-down time (P1121) must match
inertia of load.

Higher inertia requires longer ramp times;


otherwise, apply braking resistor.
The Vdc_min controller will be activated if the DC-link
Vdc_min control- voltage (r0026) falls below the level specified in r1246.
ler active The kinetic energy of the motor is used to buffer the
DC-link voltage, thus causing deceleration of the con-
verter! So short mains failures do not necessarily lead
to an undervoltage trip.
Note that this warning may also occur on fast ramp-
ups.
Analog output parameters (P0777 and P0779) should Check the following:
Analog output not be set to identical values, since this would produce • Parameter settings for output identical
parameters not illogical results.
• Parameter settings for input identical
set properly
• Parameter settings for output do not cor-
respond to analog output type
Set P0777 and P0779 to different values.
No Load is applied to the converter. Check that motor is connected to converter.
No load applied As a result, some functions may not work as under
to converter normal load conditions.
Both JOG right and JOG left (P1055/P1056) have Do not press JOG right and left simultaneous-
Both JOG left been requested. This freezes the RFG output frequen- ly.
and JOG right cy at its current value.
are requested
Conditions exist for possible cavitation damage. See F410.
Cavitation protec-
tion warn
PID autotuning (P2350) selected or running Warning disappears when PID autotuning has
PID autotuning finished.
active
Load conditions on motor indicate belt failure or me- See F452.
Load monitoring chanical fault.
warning

SINAMICS V20 Converter


Operating Instructions, 05/2020, A5E34559884-013 351

You might also like