Parameter
Parameter
When the fixed speed is selected, the additional setpoint channel from the analog is
disabled. If there is no fixed speed setpoint, the setpoint channel connects to the analog
input.
If a negative setpoint for the PID control is desired, change the setpoint and feedback wiring
as needed.
When you switch to Hand mode from PID control mode, P2200 becomes 0 to disable the
PID control. When you switch it back to Auto mode, P2200 becomes 1 to enable the PID
control again.
When commissioning the converter, the application macro setting is a one-off setting. Make
sure that you proceed as follows before you change the application macro setting to a value
different from your last setting:
1. Do a factory reset (P0010 = 30, P0970 = 1)
2. Repeat the quick commissioning and change the application macro
Failure to observe may cause the converter to accept the parameter settings from both the
currently and the previously selected macros, which may lead to undefined and
unexplainable operation.
This menu defines certain common applications. Each application macro provides a set of
parameter settings for a specific application. After you select an application macro, the
corresponding settings are applied to the converter to simplify the commissioning process.
The default application macro is "AP000" for application macro 0. If none of the application
macros fits your application, select the one that is the closest to your application and make
further parameter changes as desired.
This menu provides some common parameters for converter performance optimization.
If you set P8553 to 1, parameter numbers in this menu are replaced with short text.
The "Index" chapter at the end of this manual provides complete lists of CDS/DDS
parameters.
In the converter, the parameters which are used to define the sources for commands and
setpoints are combined in the (CDS), while the parameters for the open
and closed-loop control of the motor are combined in the (DDS).
The converter can be operated from different signal sources by switching over the command
data sets. When switching over the drive data sets, it is possible to switch between different
converter configurations (control type, motor).
Three independent settings are possible for each data set. These settings can be made
using the index [0...2] of the particular parameter.
SINAMICS V20 has an integrated copy function which is used to transfer data sets. This can
be used to copy CDS/DDS parameters corresponding to the particular application.
For example, copying of all values from CDS0 to CDS2 can be accomplished by the
following procedure:
1. Set P0809[0] = 0: copy from CDS0
2. Set P0809[1] = 2: copy to CDS2
3. Set P0809[2] = 1: start copy
The command data sets are changed over using the BICO parameters P0810 and P0811,
whereby the active command data set is displayed in parameter r0050. Changeover is
possible in both the "Ready" and the "Run" states.
P0810 = 0 CDS0
P0811 = 0
P0810 = 1 CDS1
P0811 = 0
P0810 = 0 or 1 CDS2
P0811 = 1
The drive data sets are changed over using the BICO parameters P0820 and P0821,
whereby the active drive data set is displayed in parameter r0051. Drive data sets can only
be changed over in the "Ready" state.
P0820 = 0 DDS0
P0821 = 0
P0820 = 1 DDS1
P0821 = 0
P0820 = 0 or 1 DDS2
P0821 = 1
The "Index" chapter at the end of this manual provides groups of the BICO parameters.
Certain parameter names include the following abbreviated prefixes: BI, BO, CI, CO and
CO/BO followed by a colon. These abbreviations have the following meanings:
BICO or the binary interconnection technology can help the user to connect internal function
and values to realize more customized features.
BICO functionality is a different, more flexible way of setting and combining input and output
functions. It can be used in most cases in conjunction with the simple, access level 2
settings.
The BICO system allows complex functions to be programmed. Boolean and mathematical
relationships can be set up between inputs (digital, analog, serial etc.) and outputs
(converter current, frequency, analog output, digital outputs, etc.).
The default parameter that a BI or CI parameter is connected to is shown in the Factory
default column of the parameter list.
0 User-defined parameter list Defines a limited set of parameters to which the end
user has access. See P0013 for details on use.
1 Standard Allows access into most frequently used parameters.
2 Extended Allows extended access to more parameters.
3 Expert For expert use only.
4 Service Only for use by authorized service personnel, password
protected.
U8 8-bit unsigned
U16 16-bit unsigned
U32 32-bit unsigned
I16 16-bit integer
I32 32-bit integer
Float 32-bit floating point number
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source) the following combinations are possible when creating BICO
interconnections:
CO: U8 - -
CO: U16 - -
CO: U32 - -
CO: I16 - -
CO: I32 - -
CO: Float -
BO: U8 - - -
BO: U16 - - -
BO: U32 - - -
BO: I16 - - -
BO: I32 - - -
BO: Float - - - -
Legend:
: BICO interconnection permitted
-: BICO interconnection not permitted
Specification of the reference quantity with which the signal value will be converted
automatically.
Reference quantities, corresponding to 100 %, are required for the statement of physical
units as percentages. These reference quantities are entered in P2000 to P2004.
In addition to P2000 to P2004 the following normalizations are used:
TEMP: 100 °C = 100 %
PERCENT: 1.0 = 100 %
4000H: 4000 hex = 100 %
Converter state in which the parameter is changeable. Three states are possible:
Commissioning: C, C(1) or C(30)
Run: U
Ready to run: T
This indicates when the parameter can be changed. One, two or all three states may be
specified. If all three states are specified, this means that it is possible to change this
parameter setting in all three converter states. C shows the parameter is changeable
whatever P0010 equals; C(1) shows that the parameter is changeable only when P0010 = 1;
C(30) shows that the parameter is changeable only when P0010 = 30.
r0002 - - - - - U16 2
Displays actual converter state.
0 Commissioning mode (P0010 0)
1 Converter ready
2 Converter fault active
3 Converter starting (visible only while pre-charging DC link)
4 Converter running
5 Stopping (ramping down)
6 Converter inhibited
P0003 0-4 1 U, T - - U16 1
Defines user access level to parameter sets.
0 User defined parameter list - see P0013 for details on use
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access, for example, to converter I/O functions
3 Expert: For expert use only
4 Service: Only for use by authorized service, password protected
P0004 0 - 24 0 U, T - - U16 1
Filters parameters according to functionality to enable a more focused approach to commissioning.
0 All parameters
2 Converter
3 Motor
5 Technology application/units
7 Commands, binary I/O
8 Analog input and analog output
10 Setpoint channel/RFG
12 Converter features
13 Motor control
19 Motor identification
20 Communication
21 Warnings/faults/monitoring
22 Technology controller
24 List of modified parameters
P0005 0 - 9580 0 C, U, T - - U16 2
Filters parameters so that only those related to a particular functional group are selected.
0 Ready
1 Quick commissioning
2 Converter
29 Download
30 Factory setting
Reset to 0 for converter to run.
P0003 (user access level) also determines access to parameters.
• P0010 = 1
The converter can be commissioned very quickly and easily by setting P0010 = 1. After that only the
important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be en-
tered one after the other. The end of quick commissioning and the start of internal calculation will be
done by setting P3900 = 1 - 3. Afterwards parameter P0010 and P3900 will be reset to zero automati-
cally.
• P0010 = 2
For service purposes only.
• P0010 = 30
When resetting the parameters or user default values of converter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1. The converter will automat-
ically reset all its parameters to their default settings. This can prove beneficial if you experience prob-
lems during parameter setup and wish to start again.
Resetting of the user default values will be started by setting parameter P0970 = 21. The converter will
automatically reset all its parameters to the factory default settings. Duration of factory setting will take
about 60 seconds.
P0011 0 - 65535 0 U, T - - U16 3
See P0013
P0012 0 - 65535 0 U, T - - U16 3
See P0013
Displays status of operator panel commands. The settings below are used as the "source" codes for key-
pad control when connecting to BICO input parameters.
00 ON/OFF1 Yes No
01 OFF2: Electrical stop No Yes
08 JOG right Yes No
11 Reverse (setpoint inversion) Yes No
13 Motor potentiometer MOP up Yes No
14 Motor potentiometer MOP down Yes No
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
r0020 - - - - - Float 3
Displays actual frequency setpoint (input of ramp function generator). This value is available filtered
(r0020) and unfiltered (r1119). The actual frequency setpoint after RFG is displayed in r1170.
r0021 - - - - - Float 2
Displays actual converter output frequency (r0024) excluding slip compensation (and resonance damping,
frequency limitation in V/f mode).
r0022 - - - - - Float 3
Displays calculated rotor speed based on r0021 (filtered output frequency [Hz] x 120/number of poles). The
value is updated every 128 ms.
This calculation makes no allowance for load-dependent slip.
r0024 - - - - - Float 3
Displays actual filtered output frequency (slip compensation, resonance damping and frequency limitation
are included). See also r0021. This value is available filtered (r0024) and unfiltered (r0066).
r0025 - - - - - Float 2
Displays filtered [rms] voltage applied to motor. This value is available filtered (r0025) and unfiltered
(r0072).
r0026[0] - - - - - Float 2
Displays filtered DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
[0] Compensation DC voltage channel
r0026[0] = Main DC-link voltage
r0027 - - - P2002 - Float 2
Displays rms value of motor current. This value is available filtered (r0027) and unfiltered (r0068).
r0028 - - - P2002 - Float 3
Displays estimated rms value of motor current calculated from dclink current.
r0031 - - - - - Float 2
Displays electrical torque. This value is available filtered (r0031) and unfiltered (r0080).
The electrical torque is not the same as the mechanical torque, which can be measured on the shaft. Due
to windage and friction a part of the electrical torque is lost in the motor.
r0032 - - - r2004 - Float 2
Displays (mechanical) shaft power. Value is displayed in [kW] or [hp] depending on setting for P0100 (op-
eration for Europe/North America).
P_mech = 2 * Pi * f * M -->
r0032[kW] = (2 * Pi/1000) * (r0022/60)[1/min] * r0031[Nm]
r0032[hp] = r0032[kW]/0.75
r0035[0...2] - - - - DDS Float 2
r0037[0...1] - - - - - Float 3
Displays measured heat sink temperature and calculated junction temperature of IGBTs based on thermal
model.
[0] Measured heat sink temperature
[1] Total Chip Junction Temperature
The values are updated every 128 ms.
r0038 - - - - - Float 3
Displays electrical energy used by converter since display was last reset (see P0040 - reset energy con-
sumption meter).
Value is reset when P0040 = 1 (reset energy consumption meter).
P0040 0-1 0 T - - U16 2
Resets value of r0039 (energy consumption meter) and r0043 (energy saved meter) to zero.
0 No reset
1 Reset r0039 to 0
P0042[0...1] 0.000 - 100.00 0.000 T - - Float 2
Scales the calculated energy saved value
[0] Factor for kWh to currency conversion
[1] Factor for kWh to CO2 conversion
r0043[0...2] - - - - - Float 2
Displays calculated energy saved
[0] Energy saving in kWh
[1] Energy saving in currency
[2] Energy saving in CO2
r0050 - - - - - U16 2
r0052.0...15 - - - - - U16 2
Displays first active status word of converter (bit format) and can be used to diagnose converter status.
r0054.0...15 - - - - - U16 3
Displays first control word of converter (in bit format) and can be used to diagnose which commands are
active.
00 ON/OFF1 Yes No
01 OFF2: electrical stop No Yes
02 OFF3: fast stop No Yes
03 Pulse enable Yes No
04 RFG enable Yes No
05 RFG start Yes No
06 Setpoint enable Yes No
07 Fault acknowledge Yes No
08 JOG right Yes No
09 JOG left Yes No
10 Control from PLC Yes No
11 Reverse (setpoint inversion) Yes No
13 Motor potentiometer MOP up Yes No
14 Motor potentiometer MOP down Yes No
15 CDS Bit 0 (Hand/Auto) Yes No
r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
r0055.0...15 - - - - - U16 3
Displays additional control word of converter (in bit format) and can be used to diagnose which commands
are active.
r0056.0...15 - - - - - U16 3
Displays status of motor control (in bit format), which can be used to diagnose converter status.
Displays actual output frequency in Hz. This value is available filtered (r0024) and unfiltered (r0066).
The output frequency is limited by the values entered in P1080 (minimum frequency) and P1082 (maxi-
mum frequency).
r0067 - - - P2002 - Float 3
Displays DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered).
r0071 - - - - - Float 3
Displays output voltage. This value is available filtered (r0025) and unfiltered (r0072).
r0074 - - - PERCE - Float 4
NT
Displays actual modulation index. The modulation index is defined as ratio between the magnitude of the
fundamental component in the converter phase output voltage and half of the DC-link voltage.
r0078 - - - P2002 - Float 3
Displays the transformation angle (flux angle in VC mode or angle from frequency in Vf mode).
P0095[0...9] 0 - 4294967295 0 T 4000H - U32 3
Selects source of display for PZD signals.
[0] 1st PZD signal
[1] 2nd PZD signal
... ...
[9] 10th PZD signal
r0096[0...9] - - - - - Float 3
Displays PZD signals.
[0] 1st PZD signal
[1] 2nd PZD signal
... ...
[9] 10th PZD signal
r0096 = 100 % corresponds to 4000 hex.
P0100 0-2 0 C(1) - - U16 1
Determines whether the power settings are expressed in [kW] or [hp] (e.g. Rated motor power P0307).
The default settings for the rated motor frequency P0310 and maximum frequency P1082 are set automat-
ically here, in addition to reference frequency P2000.
0 Europe [kW], motor base frequency is 50 Hz
1 North America [hp], motor base frequency is 60 Hz
2 North America [kW], motor base frequency is 60 Hz
Where:
• Stop converter first (i.e. disable all pulses) before you change this parameter.
• P0100 can only be changed with P0010 = 1 (Commissioning mode) via the respective interface (for
example, USS).
• Changing P0100 resets all rated motor parameters as well as other parameters that depend on the
rated motor parameters (see P0340 - calculation of motor parameters).
r0191[0...2] - 0 - - - U32 4
Displays the actual hardware configuration (SZL vector) of the converter.
[0] SZL vector of converter and power module
[1] SZL vector of converter
[2] SZL vector of power module
Use setting 1 (low overload) only for low-overload applications (for example, pumps and fans).
If it is used for high-overload applications, I2t warning will be produced too late, causing overheating in the
motor.
This parameter selects converter application for FSE only. The parameter value is not reset by the factory
setting (see P0970).
r0206 - - - - - Float 2
r0208 - - - - - U32 2
r0209 - - - - - Float 2
Following physical values influence the converter overload protection (see diagram):
• Heat sink temperature (r0037[0]); causes A504 and F4.
• IGBT Junction temperature (r0037[1]); causes F4 or F6.
• Delta temperature between heat sink and junction temperature; causes A504 and F6.
• Converter I2t (r0036); causes A505 and F5.
P0290 = 0, 2:
• Reduction of output frequency is only effective if the load is also reduced.
This is for example valid for light overload applications with a quadratic torque characteristic as pumps or fans.
• For settings P0290 = 0 or 2, the I-max controller will act upon the output current limit (r0067) in case of overtemper-
ature.
P0290 = 0:
• With pulse frequencies above nominal, pulse frequency will be reduced to nominal immediately in the event of
r0027 greater than r0067 (current limit).
P0290 = 2, 3:
• The pulse frequency P1800 is reduced only if higher than 2 kHz and if the operating frequency is below 2 Hz.
• The actual pulse frequency is displayed in r1801[0] and the minimal pulse frequency for reduction is displayed in
r1801[1].
• Converter I2t acts upon output current and output frequency, but not on pulse frequency.
A trip will always result, if the action taken does not sufficiently reduce internal temperatures.
P0291[0...2] 0-7 1 U, T - DDS U16 4
Bit 00 for enabling/disabling automatic pulse frequency reduction at output frequencies below 2 Hz. The
benefit is to reduce the noises at frequencies below 2 Hz.
P0292 0 - 25 5 U, T - - U16 3
Defines the temperature difference (in °C) between the overtemperature trip threshold (F4) and the warn-
ing threshold (A504) of the converter. The trip threshold is stored internally by the converter and cannot be
changed by the user.
P0294 2 10.0 - 95.0 U, T - - Float 3
100.0
Defines the [%] value at which warning A505 (converter I2t) is generated.
Converter I2t calculation is used to determine a maximum tolerable period for converter overload.
The I2t calculation value is deemed = 100 % when this maximum tolerable period is reached.
• The output current of the converter has been reduced.
• The value of I2t does not exceed 100 %.
P0294 = 100 % corresponds to stationary nominal load.
P0295 0 - 3600 0 U, T - - U16 3
Defines converter fan switch-off delay time in seconds after converter has stopped.
Setting to 0, converter fan will switch off when the converter stops, that means no delay.
P0296 0-2 0 T - - U16 3
Defines the converter response with increased ripple in the output current.
0 No response
1 Alarm produced (A523)
2 Fault produced (F23)
P0301[0...2] 0 - 2000 0 C(1) - DDS Float 1
Rated motor power from the rating plate. No other data is necessary. If this parameter is used, the rest of
the motor data are then estimated by the firmware.
Changeable only when P0010 = 1 (quick commissioning).
This functionality is only valid with 50 Hz supply, star configuration on 4-pole motors. You must set this
parameter to zero if you desire to set the other motor data.
Following diagram shows a typical rating plate with the locations of the relevant motor data.
Displays standardized total leakage reactance of the motor equivalent circuit (phase value).
r0382[0...2] - - - PERCENT DDS Float 4
Displays standardized main reactance of the motor equivalent circuit (phase value).
r0384[0...2] - - - - DDS Float 3
Displays calculated rotor time constant.
r0386[0...2] - - - - DDS Float 4
Enables keep-running operation. This attempts to prevent the converter from tripping by enabling all pos-
sible existing de-rating features, and the automatic restart function. May be used with P2113 = 1 (convert-
er warnings disabled) to mask resulting warnings from the user.
0 Keep-running mode disabled
1 Keep-running mode enabled
[0] Drive data set 0 (DDS0)
[1] Drive data set 1 (DDS1)
[2] Drive data set 2 (DDS2)
P0503 = 1
Sets the following parameter values to minimize likelihood of a trip:
• P0290 = 2 (converter overload reaction: reduce pulse frequency, output current and output frequency)
• P1210 = 7 (automatic restart function: restart after mains brown- /blackout or fault, trip when P1211
expires)
• P1211 = 10 (number of times converter will attempt to restart)
• P1240 = 3 (configuration of Vdc controller: Vdc_max controller and kinetic buffering (KIB) enabled)
P0503 = 0
Resets the parameters to their default values:
• P0290 = 2 (converter overload reaction: reduce pulse frequency, output current and output frequency)
• P1210 = 1 (automatic restart function: trip reset after power on, P1211 disabled)
• P1211 = 3 (number of times converter will attempt to restart)
• P1240 = 1(configuration of Vdc controller: Vdc_max controller enabled)
See also P0290, P1210, P1211, P1240, and P2113
Displays actual converter output frequency (r0024) excluding slip compensation (and resonance damping,
frequency limitation in V/f mode).
P0604[0...2] 0.0 - 200.0 130.0 U, T - DDS Float 2
Enters warning threshold for motor temperature protection. The trip temperature defined is always 10 %
higher than the warning threshold P0604. When actual motor temperature exceeds warning temperature
then converter reacts as defined in P0610.
This value should be at least 40°C higher than the motor surrounding temperature P0625.
P0610[0...2] 2 0-6 6 T - DDS U16 3
Surrounding temperature of motor at time of motor data identification. It is only allowed to change the
value when the motor is cold. A motor identification has to be made after changing the value.
This parameter is influenced by automatic calculations defined by P0340.
Overtemperature of the stator winding. It is only allowed to change the value when the motor is cold. A
motor identification has to be made after changing the value.
See P0626
P0628[0...2] 20.0 - 200.0 100.0 U, T - DDS Float 4
RS485 also supports MODBUS protocol as well as USS. All USS options on RS485 are also applicable to
MODBUS.
If P0700 = 0, the values of the following parameters relevant to the digital input function will be restricted
to their defaults: P0701, P0702, P0703, P0704, P0712 and P0713.
Central switch to select control command source for converter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command/setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
0 Cmd = BICO parameter, Setpoint = BICO parameter
1 Cmd = BICO parameter, Setpoint = MOP setpoint
2 Cmd = BICO parameter, Setpoint = Analog setpoint
3 Cmd = BICO parameter, Setpoint = Fixed frequency
4 Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
5 Cmd = BICO parameter, Setpoint = USS/MODBUS on RS485
7 Cmd = BICO parameter, Setpoint = Analog setpoint 2
40 Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
41 Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
Determines the control method using the terminals. This parameter allows the selection of the control
philosophy. The control philosophies exclude each other.
2/3-wire control allows to start, stop and reverse the converter in one of the following ways:
• 2-wire control with Siemens standard control
using ON/OFF1 and REV as permanent signals
• 2-wire control
using ON_FWD and ON_REV as permanent signals
• 3-wire control
using STOP as permanent signal, FWD and REVP as pulses
• 3 wire control
using OFF1/HOLD and REV as permanent signal, ON as pulse signal
0 Siemens (start/dir)
1 2-wire (fwd/rev)
2 3-wire (fwd/rev)
3 3-wire (start/dir)
Where:
• P denotes Pulse
• FWD denotes FORWARD
• REV denotes REVERSE
When any of the control functions are selected using P0727, the setting for the digital inputs (P0701 -
P0704) are redefined as follows:
Settings of P0701 P0727 = 0 (Siemens P0727 = 1 (2-wire P0727 = 2 (3- P0727 = 3 (3-wire
- P0706 Standard Control) Control) wire Control) Control)
= 1 (P0840) ON/OFF1 ON_FWD STOP ON_PULSE
= 2 (P0842) ON_REV/OFF1 ON_REV FWDP OFF1/HOLD
= 12 (P1113) REV REV REVP REV
To use the 2/3-wire control, the sources for ON/OFF1 (P0840), ON_REV/OFF1 (P0842) and REV (P1113)
corresponding to the redefined values have to be set accordingly.
The ON/OFF2 functionality is not supported in 2/3 wire modes. Do not select ON/OFF2 unless P0727 = 0.
Regarding the use of fixed frequencies see P1000 and P1001.
r0730 - - - - - U16 3
Displays number of digital outputs.
P0731[0...2] 0 - 4294967295 52.3 U, T - CDS U32/Bi 2
n
Defines source of digital output 1.
An inverse logic can be realized by inverting the digital outputs in P0748.
Output of fault bit 52.3 is inverted on digital output. Therefore, with P0748 = 0, the digital output is set to
low when a fault is triggered, and when there is no fault, it is set to high.
Monitor functions ==> see r0052, r0053
Motor holding brake ==> see P1215
DC-Brake ==> see P1232, P1233
P0732[0...2] 0 - 4294967295 52.7 U, T - CDS U32/Bi 2
n
Defines source of digital output 2.
P0733[0...2] 0 - 4294967295 0 U, T - CDS U32/Bi 2
n
Defines source of digital output 3.
This digital output is provided by the optional I/O Extension Module.
P0734[0...2] 0 - 4294967295 0 U, T - CDS U32/Bi 2
n
Defines source of digital output 4.
This digital output is provided by the optional I/O Extension Module.
r0747.0...1 - - - - - U16 3
Displays status of digital outputs (also includes inversion of digital outputs via P0748).
r0751.0...9 - - - - - U16 3
Displays smoothed analog input value in volts or milliamps before the scaling block.
[0] Analog input 1 (AI1)
[1] Analog input 2 (AI2)
P0753[0...1] 0 - 10000 3 U, T - - U16 3
Displays analog input, scaled using ASPmin and ASPmax (ASP = analog setpoint).
Analog setpoint (ASP) from the analog scaling block can vary from minimum analog setpoint (ASPmin) to
a maximum analog setpoint (ASPmax).
The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384.
By associating r0755 with an internal value (e.g. frequency setpoint), a scaled value is calculated internally
by the converter.
The frequency value is calculated using the following equation:
r0755 [Hz] = (r0755 [hex]/4000 [hex]) * P2000 * (max (|ASP_max|, |ASP_min|)/100%)
Case a:
ASPmin = 300 %, ASPmax = 100 % then 16384 represents 300 %.
This parameter will vary from 5461 to 16384.
Case b:
ASPmin = -200 %, ASPmax = 100 % then 16384 represents 200 %.
This parameter will vary from -16384 to +8192.
See r0752
This value is used as an input to analog BICO connectors. ASPmax represents the highest analog set-
point (this may be at 10 V). ASPmin represents the lowest analog setpoint (this may be at 0 V). See
P0757 to P0760 (analog input scaling).
P0756[0...1] 0-4 0 T - - U16 2
Defines type of analog input and also enables analog input monitoring.
0 Unipolar voltage input (0 to 10 V)
1 Unipolar voltage input with monitoring (0 to 10 V)
2 Unipolar current input (0 to 20 mA)
3 Unipolar current input with monitoring (0 to 20 mA)
4 Bipolar voltage input (-10 V to 10 V)
See r0752
The monitoring function is disabled if the analog scaling block is programmed to output negative setpoints
(see P0757 to P0760).
When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F80) if
the analog input voltage falls below 50 % of the deadband voltage. It is not possible to select the bipolar
voltage for analog input 2.
For P0756 = 4, you need to ensure the analog input scaling, for example, if you desire to obtain an output
frequency within the range of -50 Hz to 50 Hz, you can set parameters P0757 to P0760 within their nega-
tive ranges (examples: P0757 = -10 V, P0758 = -100%).
See P0757 to P0760 (analog input scaling).
In current mode, if the input exceeds 24mA, the converter will trip F80/11 for analog input 1 and F80/12 for
analog input 2. This will result in channel switching back to voltage mode. Analog input parameter read-
ings for the channel concerned will no longer be updated until the fault (F80) has been reset. Once the
fault has been reset then the input will switch back to current mode and normal readings will resume.
P0757 - P0760 configure the input scaling. x1 is the first value of the two pairs of variants x1/y1 and x2/y2
which determine the straight line. The value x2 of analog input scaling P0759 must be greater than the
value x1 of analog input scaling P0757.
See r0752
• Analog setpoints represent a [%] of the normalized frequency in P2000.
• Analog setpoints may be larger than 100 %.
• ASPmax represents highest analog setpoint (this may be at 10 V or 20 mA).
• ASPmin represents lowest analog setpoint (this may be at 0 V or 20 mA).
• Default values provide a scaling of 0 V or 0 mA = 0 %, and 10 V or 20 mA = 100 %.
P0758[0...1] -99999.9 - 0.0 U, T - - Float 2
99999.9
Sets value of y1 as described in P0757 (analog input scaling)
See r0752
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is
to be generated.
P0759[0...1] -20 - 20 10 U, T - - Float 2
P0761[0...1] 0 - 20 0 U, T - - Float 2
Defines time delay between loss of analog setpoint and appearance of fault code F80.
See r0752
Expert users can choose the desired reaction to F80 (default is OFF2).
r0770 - - - - - U16 3
Displays number of analog outputs available.
P0771[0] 0 - 4294967295 21[0] U, T - - U32 2
Defines function of the analog output.
[0] Analog output 1 (AO1)
21 CO: Actual frequency (scaled to P2000)
24 CO: Actual output frequency (scaled to P2000)
25 CO: Actual output voltage (scaled to P2001)
26 CO: Actual DC-link voltage (scaled to P2001)
27 CO: Actual output current (scaled to P2002)
P0773[0] 0 - 1000 2 U, T - - U16 2
Defines smoothing time for analog output signal. This parameter enables smoothing for analog output
using a PT1 filter.
See P0771
P0773 = 0: Deactivates filter.
r0774[0] - - - - - Float 2
Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute
value to be outputted. If the value was originally negative then the corresponding bit in r0785 is set, oth-
erwise it is cleared.
See P0771
P0777[0] -99999 - 99999 0.0 U, T - - Float 2
Defines x1 output characteristic. Scaling block is responsible for adjustment of output value defined in
P0771 (analog output connector input). x1 is the first value of the two pairs of variants x1/y1 and x2/y2
which determine the straight line. The two points P1 (x1, y1) and P2 (x2, y2) can be chosen freely.
See P0771
See P0758
P0778[0] 0 - 20 0 U, T - - Float 2
Displays status of analog output. Bit 0 indicates that the value of analog output 1 is negative.
Transfers values from the converter to external device when P0802 0. P0010 must be set to 30 for this
to be possible.
0 Disabled
2 Start data transfer to the SD card
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
Ensure that enough space exists on the SD card before transferring data (8 KB).
P0803 0-3 0 C(30) - - U16 3
0 Disabled
2 Start data transfer from the SD card
3 Start data transfer from the SD card (except the motor data)
Transfers parameter values from the SD clone file to the converter when P0803 0. P0010 must be set to
30 to activate this parameter. See P0802 for parameter values.
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
P0804 0 - 99 0 C(30) - - U16 3
Select clone file to upload/download.
if P0804 = 0, then the file name is clone00.bin
if P0804 = 1, then the file name is clone01.bin
etc.
P0806 0 - 4294967295 0 U, T - - U32 3
Binector input to lock control panel access through external client.
r0807.0 - - - - - U16 3
Binector output to display whether command and setpoint source is connected to an external client.
Selects command source from which to read Bit 0 for selecting a command data set (CDS). The actual
selected CDS is displayed in r0054.15 (CDS bit 0) and r0055.15 (CDS bit 1). The actual active CDS is
displayed in r0050.
722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
P0811 is also relevant for command data set (CDS) selection.
P0811 0 - 4294967295 0 U, T - - U32 2
Selects command source from which to read Bit 1 for selecting a command data set (see P0810).
See P0810.
P0810 is also relevant for command data set (CDS) selection.
P0819[0...2] 0-2 [0] 0 [1] 1 T - - U16 2
[2] 0
Calls 'Copy drive data set (DDS)' function. The list of all drive data set (DDS) parameters is shown in
"Index" at the end of the manual.
Copying of all values from DDS0 to DDS2 can be accomplished by the following procedure:
P0819[0] = 0 Copy from DDS0
P0819[1] = 2 Copy to DDS2
P0819[2] = 1 Start copy
[0] Copy from DDS
[1] Copy to DDS
[2] Start copy
See P0809
P0820 0 - 4294967295 0 T - - U32 3
Selects command source from which to read Bit 0 for selecting a drive data set (DDS). The actual select-
ed drive data set (DDS) is displayed in parameter r0051[0]. The actual active drive data set (DDS) is dis-
played in parameter r0051[1].
See P0810
P0821 is also relevant for drive data set (DDS) selection.
P0821 0 - 4294967295 0 T - - U32 3
Selects command source from which Bit 1 for selecting a drive data set is to be read in (see P0820).
See P0810
P0820 is also relevant for drive data set (DDS) selection.
P0840[0...2] 0 - 4294967295 19.0 T - CDS U32 3
Allows ON/OFF1 command source to be selected using BICO. The digits in front of the colon show the
parameter number of the command source; the digits following the colon denote the bit setting for that
parameter.
See P0810
For digital inputs as command source BICO requires P0700 set to 2 (enable BICO). The default setting
(ON right) is digital input 1 (722.0). Alternative source possible only when function of digital input 1 is
changed (via P0701) before changing value of P0840.
Specifies the interfaces which can be used to change parameters. This parameter allows the user to easi-
ly protect the converter from unauthorized modification of parameters.
Annotation: P0927 is not password protected.
r0947[0...63] - - - - - U16 2
Displays fault history.
r0948[0...63] - - - - - U32 3
Time stamp to indicate when a fault has occurred.
P0969 (system run time counter) is the possible source of the time stamp.
[0] Recent fault trip --, fault time 1
... ...
[7] Recent fault trip --, fault time 8
[8] Recent fault trip -1, fault time 1
... ...
[15] Recent fault trip -1, fault time 8
[16] Recent fault trip -2, fault time 1
... ...
[23] Recent fault trip -2, fault time 8
... ...
[63] Recent fault trip -7, fault time 8
r0949[0...63] - - - - - U32 3
Displays converter fault values. It is for service purposes and indicates the type of fault reported.
The values are not documented. They are listed in the code where faults are reported.
[0] Recent fault trip --, fault value 1
... ...
[7] Recent fault trip --, fault value 8
[8] Recent fault trip -1, fault value 1
... ...
[15] Recent fault trip -1, fault value 8
[16] Recent fault trip -2, fault value 1
... ...
[23] Recent fault trip -2, fault value 8
... ...
[63] Recent fault trip -7, fault value 8
P0952 0 - 65535 0 T - - U16 3
Displays number of trips stored in r0947 (last fault code).
Setting 0 resets fault history (changing to 0 also resets r0948 - fault time).
If the source of a non-momentary fault remains active before a factory reset, the converter removes the
source first and then places the fault into the fault history during a factory reset. That means P0952 still
has a non-zero value after the factory reset. If you want to clear the fault history, you need to perform a
second factory reset or set P0952 = 0.
r0954[0...2] - - - - - Float 3
Displays the setpoint after RFG when the first instantaneous fault occurs (see r1170).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0954[0] corresponds to
r0947[0...7], r0954[1] corresponds to r0947[8...15] and r0954[2] corresponds to r0947[16...23].
r0955[0...2] - - - - - U16 3
Displays status word 2 when the first instantaneous fault occurs (see r0053).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0955[0] corresponds to
r0947[0...7], r0955[1] corresponds to r0947[8...15] and r0955[2] corresponds to r0947[16...23].
r0956[0...2] - - - - - Float 3
Displays the DC link voltage when the first instantaneous fault occurs (see r0026).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0956[0] corresponds to
r0947[0...7], r0956[1] corresponds to r0947[8...15] and r0956[2] corresponds to r0947[16...23].
r0957[0...2] - - - - - Float 3
Displays the output current RMS when the first instantaneous fault occurs (see r0027).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0957[0] corresponds to
r0947[0...7], r0957[1] corresponds to r0947[8...15] and r0957[2] corresponds to r0947[16...23].
r0958[0...2] - - - - - Float 3
Displays the output voltage when the first instantaneous fault occurs (see r0025).
[0] Recent trip - Fault information
[1] Recent trip - 1 Fault information
[2] Recent trip - 2 Fault information
Only one set of fault information is stored per block of instantaneous faults. r0958[0] corresponds to
r0947[0...7], r0958[1] corresponds to r0947[8...15] and r0958[2] corresponds to r0947[16...23].
r0964[0...6] - - - - - U16 3
Firmware version data.
[0] Company (Siemens = 42)
[1] Product type (V20 = 8001)
[2] Firmware version
[3] Firmware date (year)
[4] Firmware date (day/month)
[5] Number of converter objects
[6] Firmware version
r0967 - - - - - U16 3
Displays control word 1. See r0054 for the bit field description.
r0968 - - - - - U16 3
Displays active status word of converter (in binary) and can be used to diagnose which commands are
active. See r0052 for the bit field description.
P0969 0 - 4294967295 0 T - - U32 3
Selects frequency setpoint source. The main setpoint is given by the least significant digit (right-hand
position) and the additional setpoint is given by the most significant digit (left-hand position). Single digits
denote main setpoints that have no additional setpoint.
0 No main setpoint
1 MOP setpoint
2 Analog setpoint 1
3 Fixed frequency
5 USS/MODBUS on RS485
7 Analog setpoint 2
10 No main setpoint + MOP setpoint
11 MOP setpoint + MOP setpoint
12 Analog setpoint 1 + MOP setpoint
13 Fixed frequency + MOP setpoint
15 USS/MODBUS on RS485 + MOP setpoint
17 Analog setpoint 2 + MOP setpoint
20 No main setpoint + Analog setpoint 1
21 MOP setpoint + Analog setpoint 1
22 Analog setpoint 1 + Analog setpoint 1
23 Fixed frequency + Analog setpoint 1
25 USS/MODBUS on RS485 + Analog setpoint 1
27 Analog setpoint 2 + Analog setpoint 1
30 No main setpoint + Fixed frequency
31 MOP setpoint + Fixed frequency
32 Analog setpoint 1 + Fixed frequency
33 Fixed frequency + Fixed frequency
35 USS/MODBUS on RS485 + Fixed frequency
37 Analog setpoint 2 + Fixed frequency
50 No main setpoint + USS/MODBUS on RS485
51 MOP setpoint + USS/MODBUS on RS485
52 Analog setpoint 1 + USS/MODBUS on RS485
53 Fixed frequency + USS/MODBUS on RS485
55 USS/MODBUS on RS485 + USS/MODBUS on RS485
57 Analog setpoint 2 + USS/MODBUS on RS485
70 No main setpoint + Analog setpoint 2
71 MOP setpoint + Analog setpoint 2
72 Analog setpoint 1 + Analog setpoint 2
73 Fixed frequency + Analog setpoint 2
75 USS/MODBUS on RS485 + Analog setpoint 2
77 Analog setpoint 2 + Analog setpoint 2
Related parameter: P1074 (BI: Disable additional setpoint)
Changing this parameter sets (to default) all settings on item selected. These are the following parame-
ters: P1070, P1071, P1075, P1076
If P1000 = 1 or 1X, and P1032 (inhibit reverse direction of MOP) = 1, then reverse motor direction will be
inhibited.
RS485 also supports MODBUS protocol as well as USS. All USS options on RS485 are also applicable to
MODBUS. To alter the setpoint using the BOP when the command source P0700 is not set to 1, you must
check that P1035 is set to r0019 bit 13 and P1036 is set to r0019 bit 14.
See P1020 to P1023 for assigning desired digital inputs to the fixed frequency bits.
Select fixed frequency operation (using P1000).
Converter requires ON command to start in the case of direct selection. Therefore r1025 must be con-
nected to P0840 to start.
Fixed frequencies can be selected using the digital inputs.
P1002[0...2] -550.00 - 550.00 15.00 U, T - DDS Float 2
Defines fixed frequency setpoint 2.
See P1001
See P1020
P1022[0...2] 0 - 4294967295 722.5 T - CDS U32 3
See P1020
P1023[0...2] 0 - 4294967295 722.6 T - CDS U32 3
See P1020
r1024 - - - - - Float 3
00 Status of FF Yes No
P1031[0...2] 0-3 1 U, T - DDS U16 2
MOP mode specification.
If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse direc-
tion will be inhibited by default of P1032 (inhibit reverse direction of MOP). To re-enable reverse direction,
set P1032 = 0.
A short press of the 'up' or 'down' keys (e.g.: operator panel) will change the frequency setpoint in steps of
0.1 Hz. A longer press will cause an accelerated frequency setpoint change.
The start value gets active (for the MOP output) only at the start of the MOP. P1031 influences the start
value behavior as follows:
• P1031 = 0: Last MOP setpoint not saved in P1040
MOP UP/DOWN requires an ON command to become active.
• P1031 = 1: Last MOP setpoint saved in P1040 on every OFF
MOP UP/DOWN requires an ON command to become active (default).
• P1031 = 2: Last MOP setpoint not saved in P1040
MOP UP/DOWN active without additional ON command.
• P1031 = 3: Last MOP setpoint saved in P1040 on powering up
MOP UP/DOWN active without additional ON command.
P1041[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source to change over from manual to automatic mode. If using the motorized potentiome-
ter in the manual mode the setpoint is changed using two signals for up and down e.g. P1035 and P1036.
If using the automatic mode the setpoint must be interconnected via the connector input (P1042).
0: manually
1: automatically
Refer to: P1035, P1036, P1042
P1042[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setpoint of the motorized potentiometer if automatic mode P1041 is select-
ed.
Refer to: P1041
P1043[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setting command to accept the setting value for the motorized potentiome-
ter. The value becomes effective for a 0/1 edge of the setting command.
Refer to: P1044
P1044[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0/1 edge of
the setting command.
Refer to: P1043
r1045 - - - - - Float 3
Displays the motorized potentiometer setpoint before it passed the MOP RFG.
P1047[0...2] 0.00 - 1000.00 10.00 U, T - DDS Float 2
Sets the ramp-up time for the internal MOP ramp-function generator. The setpoint is changed from zero
up to limit defined in P1082 within this time.
Refer to: P1048, P1082
Sets the ramp-down time for the internal MOP ramp-function generator. The setpoint is changed from limit
defined in P1082 down to zero within this time.
Refer to: P1047, P1082
r1050 - - - - - Float 2
The maximum value of P1082 also depends on the nominal frequency: Max. P1082 = min (15*P0310,
550.0 Hz). As consequence P1082 can be affected if P0310 is changed to a smaller value. The maximum
frequency and the pulse frequency depending on each other. The maximum frequency affects the pulse
frequency according to the following table.
P1800
2 kHz 4 kHz 6 kHz 8 - 16 kHz
fmax P1082 0 - 133.3 Hz 0 - 266.6 Hz 0 - 400 Hz 0 - 550.0 Hz
Example:
If P1082 is set to 350 Hz a pulse frequency from at least 6 kHz is necessary. If P1800 is smaller than 6
kHz the parameter is changed P1800 = 6 kHz.
The maximum output frequency of converter can be exceeded if one of the following is active:
r1084 - - - - - Float 3
This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited
to the set-point channel. If a minimum frequency (P1080) and a negative setpoint are given, the motor is
accelerated by a positive value in relationship to the minimum frequency.
0 Disabled
1 Enabled
P1113[0...2] 0 - 4294967295 19.11 T - CDS U32 3
Defines source of reverse command used when P0719 = 0 (Auto selection of command/setpoint source).
722.0 Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 Digital input 3 (requires P0703 to be set to 99, BICO)
r1114 - - - - - Float 3
r1119 - - - - - Float 3
Displays frequency setpoint at the input to the ramp function generator after modification by other func-
tions, e.g.:
• P1110 BI: Inhibit neg. freq. setpoint,
• P1091 - P1094 skip frequencies,
• P1080 min. frequency,
• P1082 max. frequency,
This value is available filtered (r0020) and unfiltered (r1119).
P1120[0...2] 0.00 - 650.00 10.00 C, U, T - DDS Float 1
Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no
rounding is used. Setting the ramp-up time too short can cause the converter to trip (overcurrent F1).
Rounding times (P1130 - P1133), rounding type (P1134), and ramp-up time scaling factor (P1138) will
also have influence on the ramp.
See also P3350, P3353.
Ramp times will be used as follows:
• P1060/P1061 : JOG mode is active
• P1120/P1121 : Normal mode (ON/OFF) is active
• P1060/P1061 : Normal mode (ON/OFF) and P1124 is active
Set ramp-up time = ramp-up time scaling factor (P1138) x ramp-up time (P1120).
If an external frequency setpoint with set ramp rates is used (e.g. from a PLC), the best way to achieve
optimum converter performance is to set ramp times in P1120 and P1121 slightly shorter than those of the
PLC. Changes to P1120 will be immediately effective. If the SuperTorque function is enabled, the con-
verter will initially ramp using the value in P3353.
P1121[0...2] 0.00 - 650.00 10.00 C, U, T - DDS Float 1
Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no
rounding is used.
Ramp-down time scaling factor (P1139) will also have influence on the ramp.
See also P3350, P3353.
Setting the ramp-down time too short can cause the converter to trip (overcurrent F1/overvoltage F2).
Ramp times will be used as follows:
• P1060/P1061 : JOG mode is active
• P1120/P1121 : Normal mode (ON/OFF) is active
• P1060/P1061 : Normal mode (ON/OFF) and P1124 is active
Set ramp-down time = ramp-down time scaling factor (P1139) x ramp-down time (P1121).
Changes to P1121 will be immediately effective.
See P1120
P1124[0...2] 0 - 4294967295 0 T - CDS U32 3
Defines source for switching between jog ramp times (P1060, P1061) and normal ramp times (P1120,
P1121) as applied to the RFG. This parameter is valid for normal mode (ON/OFF) only.
See also P1175.
P1124 does not have any impact when JOG mode is selected. In this case, jog ramp times (P1060,
P1061) will be used all the time. If the Dual Ramp function is selected using P1175, ramp times will switch
between normal (P1120, P1121) and JOG (P1060, P1061) ramp times, depending on the settings of
P2150, P2157 and P2159. Therefore, it is not recommended that JOG ramp is selected at the same time
as Dual Ramp.
See P1120.
P1130[0...2] 0.00 - 40.00 0.00 U, T - DDS Float 2
Defines ramp-down time from maximum frequency to standstill for OFF3 command. Settings in P1130 and
P1134 will have no effect on OFF3 ramp-down characteristic. An initial ramp-down rounding time of ap-
proximately 10% of P1135 is however included. For the total OFF3 ramp-down time: t_down,OFF3 =
f(P1134) = 1.1 * P1135 * (|f_2|/P1082)
This time may be exceeded if the Vdc_max level is reached.
P1138[0...2] 1.00 - 10.00 1.00 C, U, T - DDS Float 1
Defines the scaling factor for the ramp-up time. This is a ramp-up time multiplier, extending the maximum
ramp-up time to 6500 s. Set ramp-up time = ramp-up time scaling factor (P1138) x ramp-up time (P1120).
This time may be exceeded if the Vdc_max level is reached.
P1139[0...2] 1.00 - 10.00 1.00 C, U, T - DDS Float 1
Defines the scaling factor for the ramp-down time.This is a ramp-down time multiplier, extending the max-
imum ramp-down time to 6500 s. Set ramp-down time = ramp-down time scaling factor (P1139) x ramp-
down time (P1121).
This time may be exceeded if the VDC_max level is reached.
P1140[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines command source of RFG enable command (RFG: ramp function generator). If binary input is
equal to zero then the RFG output will be set immediately to 0.
P1141[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal
to zero then the RFG output is held at its present value.
P1142[0...2] 0 - 4294967295 1 T - CDS U32 3
Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary
input is equal to zero, the RFG input will be set to zero and the RFG output will ramp-down to zero.
r1170 - - - - - Float 3
r1199.7...12 - - - - - U16 3
Defines search current used for flying start. Value is in [%] based on rated motor current (P0305).
Reducing the search current may improve performance for flying start if the inertia of the system is not
very high. However, search current settings in P1202 that are below 30% (and sometimes other settings
in P1202 and P1203) may cause motor speed to be found prematurely or too late, which can result in F1
or F2 trips.
P1203[0...2] 10 - 500 100 U, T - DDS U16 3
Sets factor (in V/f mode only) by which the output frequency changes during flying start to synchronize
with turning motor. This value is entered in [%]. It defines the reciprocal initial gradient in the search se-
quence. P1203 influences the time taken to search for the motor frequency.
For a motor with 50 Hz, 1350 rpm, 100 % would produce a maximum search time of 600 ms.
A higher value produces a flatter gradient and thus a longer search time. A lower value has the opposite
effect.
r1204 - - - - - U16 4
P1210 = 6:
The converter will acknowledge the faults (F3 etc.) at power on after blackout or brownout and restarts the
converter. It is necessary that the ON command is wired via a digital input (digital input). Setting 6 causes
the motor to restart immediately.
P1210 = 7:
The converter will acknowledge the faults (F3 etc.) at power on after blackout or brownout and restarts the
converter. It is necessary that the ON command is wired via a digital input (digital input). Setting 7 causes
the motor to restart immediately.
The difference between this mode and Mode 6 is that the fault status bit (r0052.3) is not set until the num-
ber of restarts defined by P1211 have been exhausted.
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load (P1200).
P1210 = 8:
The converter will acknowledge the fault (F3) at power on after blackout or brownout and restarts. It is
necessary that the ON command is wired via a digital input (DI). Setting 8 causes the motor to restart im-
mediately. The interval between restarts is determined by P1214.
P1210 = 9:
The converter will acknowledge the fault (F3) at power on after blackout or brownout and restarts. It is
necessary that the ON command is wired via a digital input (DI). The interval between restarts is fixed at
0.5 s. P1214 sets the total restart attempt time. If an F3 occurs and cannot be acknowledged within the
time set in P1214, the F3 will go permanent and must be acknowledged manually to restart the converter.
P1210 = 10:
• The converter will acknowledge the fault (F3) at power on after blackout or brownout and restarts. It is
necessary that the ON command is wired via a digital input (DI). The interval between restarts is fixed
at 1.0 s. P1214 sets the total restart attempt time, but it must be equal to or less than 8 s. If an F3 oc-
curs and cannot be acknowledged within the time set in P1214, the F3 will go permanent and must be
acknowledged manually to restart the converter.
• If a fault (the converter cannot recover from F6, F51, F52, F85, F100, and F101) occurs, the fault must
be acknowledged manually at power on after blackout or brownout and the converter restarts. It is nec-
essary that the ON command is wired via a digital input (DI).
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load (P1200).
P1211 0 - 10 3 U, T - - U16 3
Specifies number of times converter will attempt to restart if automatic restart P1210 is activated.
P1214 0 - 1000 30 - - - U16 3
This parameter has either of the following functions:
• Specifying the restart interval when P1210 = 8
• Specifying the total restart attempt time when P1210 = 9 or P1210 = 10
P1215 0-1 0 C, T - - U16 2
Enables/disables holding brake function. The motor holding brake (MHB) is controlled via status word 1
r0052 bit 12. This signal can be issued via:
• status word of the serial interface (e.g. USS)
• digital outputs (e.g. DO1: ==> P0731 = 52.C (r0052 bit 12))
0 Motor holding brake disabled
1 Motor holding brake enabled
If the converter controls the motor holding brake, then a commissioning may not be carried out for poten-
tially hazardous loads (e.g. suspended loads for crane applications) unless the load has been secured.
It is not permissible to use the motor holding brake as working brake, as it is generally only designed for a
limited number of emergency braking operations.
Defines period during which converter runs at minimum frequency P1080 before ramping up.
P1217 0.0 - 20.0 1.0 C, T - - Float 2
Defines time for which converter runs at minimum frequency (P1080) after ramping down.
If P1217 > P1227, P1227 will take precedence.
P1218[0...2] 0 - 4294967295 0 U, T - CDS U32 3
Enables the motor holding brake output to be overridden, allowing the brake to be opened under separate
control.
P1227[0...2] 0.0 - 300.0 4.0 U, T - DDS Float 2
Defines DC level superimposed on AC waveform after exceeding DC-link voltage threshold of compound
braking. The value is entered in [%] relative to rated motor current (P0305). Compound braking switch-on
level (V_DC,Comp):
If P1254 = 0 --> V_DC,Comp = 1.13 * sqrt(2) * V_mains = 1.13 * sqrt(2) * P0210
otherwise V_DC,Comp = 0.98 * r1242
The Compound Brake is an overlay of the DC brake function with regenerative braking (effective braking at
the ramp) after OFF1 or OFF3. This enables braking with controlled motor frequency and a minimum of
energy returned to the motor. Through optimization of the ramp-down time and the compound braking an
efficient braking without additional HW components is possible.
Compound braking depends on the DC link voltage only (see threshold above). This will happen on OFF1,
OFF3 and any regenerative condition. It is disabled, when:
• DC braking is active
• Flying start is active
Increasing the value will generally improve braking performance; however, if you set the value too high, an
overcurrent trip may result.
If used with dynamic braking enabled as well compound braking will take priority.
If used with the Vdc_max controller enabled the converter behavior when braking may be worsened partic-
ularly with high values of compound braking.
P1236 = 0 means that compound braking is not activated.
P1237 0-5 0 U, T - - U16 2
Dynamic braking absorbs the braking energy in a braking resistor.
This parameter defines the rated duty cycle of the braking resistor.
Dynamic braking is active when the function is enabled and DC-link voltage exceeds the dynamic braking
switch-on level.
Dynamic braking switch-on level (V_DC,Chopper) :
If P1254 = 0 --> V_DC,Chopper = 1.13 * sqrt(2) * V_mains = 1.13 * sqrt(2) * P0210
otherwise V_DC,Chopper = 0.98 * r1242
0 Disabled
1 5 % duty cycle
2 10 % duty cycle
3 20 % duty cycle
4 50 % duty cycle
5 100 % duty cycle
This parameter is only applicable for converters of frame size D and E. For frame sizes AA to C, the duty
cycle of the braking resistor can be selected with the dynamic braking module (see Appendix "Dynamic
braking module (Page 375)").
If dynamic braking is used with DC braking enabled as well as compound braking, DC braking and com-
pound braking will take priority.
Initially the brake will operate at a high duty cycle dependent on the DC link level until the thermal limit is
approached. The duty cycle specified by this parameter will then be imposed. The resistor should be able
to operate at this level indefinitely without overheating.
The threshold for the warning A535 is equivalent to 10 seconds running at 95 % duty cycle. The duty cycle
will be limited when it was running 12 seconds at 95 % duty cycle.
P1240[0...2] 0-3 1 C, T - DDS U16 3
Enables/disables Vdc controller. The Vdc controller dynamically controls the DC link voltage to prevent
overvoltage trips on high inertia systems.
0 Vdc controller disabled
1 Vdc_max controller enabled
2 Kinetic buffering (Vdc_min controller) enabled
3 Vdc_max controller and kinetic buffering (KIB) enabled
If P1245 increased too much, it may interfere with the converter normal operation.
• Vdc_max controller:
Vdc_max controller automatically increases ramp-down times to keep the DC-link voltage (r0026) with-
in limits (r1242).
• Vdc_min controller:
Vdc_min is activated if DC-link voltage falls below the switch on level P1245. The kinetic energy of the
motor is then used to buffer the DC-link voltage, thus causing deceleration of the converter. If the con-
verter trips with F3 immediately, try increasing the dynamic factor P1247 first. If still tripping with F3 try
then increasing the switch on level P1245.
r1242 - - - - - Float 3
Enter switch-on level for kinetic buffering (KIB) in [%] relative to supply voltage (P0210).
r1246[V] = (P1245[%]/100) * sqrt(2) * P0210
Increasing the value too much, may interfere with the converter normal operation.
P1254 has no effect on the switch-on-level for kinetic buffering.
P1245 default for the single phase variants is 74%.
r1246[0...2] - - - - DDS Float 3
Displays switch-on level of kinetic buffering (KIB, Vdc_min controller). If the dc-link voltage drops below the
value in r1246, kinetic buffering will be activated. That means the motor frequency will be reduced in order
to keep Vdc within the valid range. If there is not enough regenerative energy, the converter trips with
undervoltage.
P1247[0...2] 10 - 200 100 U, T - DDS U16 3
Enters dynamic factor for kinetic buffering (KIB, Vdc_min controller). P1247 = 100 % means P1250, P1251
and P1252 (gain, integration time and differential time) are used as set. Otherwise, these are multiplied by
P1247 (dynamic factor of Vdc_min).
Vdc controller adjustment is calculated automatically from motor and converter data.
P1250[0...2] 0.00 - 10.00 1.00 U, T - DDS Float 3
Enters gain for Vdc controller.
P1251[0...2] 0.1 - 1000.0 40.0 U, T - DDS Float 3
Enables/disables auto-detection of switch-on levels for Vdc_max controller. For best results, it is recom-
mended to set P1254 = 1 (auto-detection of Vdc switch-on levels enabled). Setting P1254 = 0 is only rec-
ommended when there is a high degree of fluctuation of the DC-link when the motor is being driven. Note
that the auto detection only works when the converter has been in standby for over 20s.
0 Disabled
1 Enabled
See P0210
P1256[0...2] 0-2 0 C, T - DDS U16 3
Enters reaction for kinetic buffering controller (Vdc_min controller). Depending on the setting selected, the
frequency limit defined in P1257 is used to either hold the speed or disable pulses. If not enough regenera-
tion is produced, converter may trip with undervoltage.
0 Maintain DC-link until trip
1 Maintain DC-link until trip/stop
2 Control stop
P1256 = 0:
Maintain DC-link voltage until mains is returned or converter is tripped with undervoltage. The frequency is
kept above the frequency limit provided in P1257.
P1256 = 1:
Maintain DC-link voltage until mains is returned or converter is tripped with undervoltage or pulses are
disabled when frequency falls below the limit in P1257.
P1256 = 2:
This option ramps down the frequency to standstill even when mains return.
If mains do not return, frequency brought down under the control of Vdc_min controller until P1257 limit.
Then pulses are disabled or undervoltage has occurred. If mains return, then an OFF1 is active until
P1257 limit. Then pulses are disabled.
P1257[0...2] 0.00 - 550.00 2.50 U, T - DDS Float 3
Frequency which kinetic buffering (KIB) either hold speed or disable pulses depending on P1256.
P1300[0...2] 0 - 19 0 C, T - DDS U16 2
Parameter to select the control method. Controls relationship between speed of motor and voltage sup-
plied by converter.
0 V/f with linear characteristic
1 V/f with FCC
2 V/f with quadratic characteristic
3 V/f with programmable characteristic
4 V/f with linear eco
5 V/f for textile applications
6 V/f with FCC for textile applications
7 V/f with quadratic eco
19 V/f control with independent voltage setpoint
The following table presents an overview of control parameters (V/f) that can be modified in relationship to
P1300 dependencies:
Sets the frequency of the first point of V/f coordinates (P1320/1321 to P1324/1325) to define V/f character-
istic. These parameter pairs can be used to provide correct torque at correct frequency.
To set parameter, select P1300 = 3 (V/f with programmable characteristic). The acceleration boost and
starting boost defined in P1311 and P1312 are applied to V/f with programmable characteristic.
Linear interpolation will be applied between the individual data points.
V/f with programmable characteristic (P1300 = 3) has 3 programmable points and 2 non-programmable
points. The 2 non-programmable points are:
• Continuous boost P1310 at 0 Hz
• Rated motor voltage P0304 at rated motor frequency P0310
P1321[0...2] 0.0 - 3000.0 0.0 U, T - DDS Float 3
See P1320
P1322[0...2] 0.00 - 550.00 0.00 T - DDS Float 3
See P1320
P1323[0...2] 0.0 - 3000.0 0.0 U, T - DDS Float 3
See P1320
P1324[0...2] 0.00 - 550.00 0.00 T - DDS Float 3
See P1320
P1325[0...2] 0.0 - 3000.0 0.0 U, T - DDS Float 3
See P1320
P1330[0...2] 0 - 4294967295 0 T - CDS U32 3
BICO parameter for selecting source of voltage setpoint for independent V/f control (P1300 = 19).
P1333[0...2] 0.0 - 100.0 10.0 U, T PERC DDS Float 3
ENT
Defines start frequency at which FCC (flux current control) is enabled as [%] of rated motor frequency
(P0310).
If this value is too low, the system may become unstable.
Defines resonance damping gain for V/f. The di/dt of the active current will be scaled by P1338. If di/dt
increases the resonance damping circuit decreases the converter output frequency.
This parameter is influenced by automatic calculations defined by P0340.
The resonance circuit damps oscillations of the active current which frequently occur during no-load opera-
tion. In V/ f modes (see P1300), the resonance damping circuit is active in a range from approx. 6 % to 80
% of rated motor frequency (P0310). If the value of P1338 is too high, this will cause instability (forward
control effect).
P1340[0...2] 0.000 - 0.499 0.030 U, T - DDS Float 3
r1343 - - - - - Float 3
Displays amount by which the I_max controller is reducing the converter output voltage.
P1345[0...2] 0.000 - 0.250 U, T - DDS Float 3
5.499
If the output current (r0068) exceeds the maximum current (r0067), the converter is dynamically controlled
by reducing the output voltage. This parameter sets the proportional gain of this controller.
This parameter is influenced by automatic calculations defined by P0340.
See P1340 for further information. The Factory setting depends on converter power.
P1346[0...2] 0.000 - 0.300 U, T - DDS Float 3
50.000
Integral time constant of the I_max voltage controller.
• P1341 = 0: I_max controller disabled
• P1345 = 0 and P1346 > 0: I_max voltage controller enhanced integral
• P1345 > 0 and P1346 > 0: I_max voltage controller normal PI control
This parameter is influenced by automatic calculations defined by P0340.
See P1340 for further information. The Factory setting depends on converter power.
r1348 - - - PERCENT - Float 2
Displays the calculated economy mode factor (range 80%-120%) applied to the demanded output volts.
Economy mode is used to find the most efficient operating point for a given load. It does this by a continu-
ous method of hill climbing optimization. Hill climbing optimization works by slightly changing the output
volts either up or down and monitoring the change in input power. If the input power has decreased, the
algorithm changes the output volts in the same direction. If the input power has increased then the algo-
rithm adjusts the output volts in the other direction. Using this algorithm, the software should be able to
find the minimum point on the graph between input power and output volts.
If this value is too low, the system may become unstable.
Enables thermal adaptation of stator and rotor resistance to reduce torque errors in speed/torque regula-
tion with speed sensor, or speed errors in speed/torque regulation without speed sensor.
Adjusts the phase angle at the point where the output frequency crosses zero. The angle is only used if
the output frequency changes direction.
00 Estimation of Xs Yes No
01 Motor ID at 2 kHz Yes No
02 Estimation of Tr Yes No
03 Estimation of Lsigma Yes No
05 Det. Tr meas. with 2 freq. Yes No
06 Measurement of on voltage Yes No
07 Deadtime detection from Rs measurement Yes No
08 MotID with hw deadtime comp activ Yes No
09 No deadtime detection with 2 freq Yes No
10 Detect Ls with LsBlock method Yes No
11 MotID adaption of magnetizing current Yes No
12 MotID adaption of main reactance Yes No
13 MotID switch off saturation curve optim. Yes No
14 MotID saturation curve optim. all framesizes Yes No
15 MotID saturation curve optim. big framesizes Yes No
P1910 0 - 23 0 T - - U16 4
Displays measured stator resistance value (line-to-line). This value also includes the cable resistances.
[0] U_phase
If the value identified (Rs = stator resistance) does not lie within the range 0.1 % < Rs [p. u.] < 100 % fault
message 41 (motor data identification failure) is issued. P0949 provides further information (fault value = 2
in this case).
This value is measured using P1900 = 2.
r1920[0] - - - - - Float 4
r1925[0] - - - - - Float 4
When Quick Commissioning is carried out, P2000 is changed as follows: P2000 = P1082.
P2000 represents the reference frequency of the above mentioned interfaces.
A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface.
Unlike P1082 (Maximum Frequency) this limits the converter frequency internally independent of the ref-
erence frequency.
By modification of P2000 it will also adapt the parameter to the new settings.
Reference parameters are intended as an aid to presenting setpoint and actual value signals in a uniform
manner.
This also applies to fixed settings entered as a percentage.
A value of 100 % corresponds to a process data value of 4000H, or 4000 0000H in the case of double
values.
In this respect, the following parameters are available:
P2010[0...1] 6 - 12 6 U, T - - U16 2
Sets baud rate for USS/MODBUS communication.
6 9600 bps
7 19200 bps
8 38400 bps
9 57600 bps
10 76800 bps
11 93750 bps
12 115200 bps
[0] USS/MODBUS on RS485
[1] USS on RS232 (reserved)
Before fitting SINAMICS V20 Smart Access to V20, if RS485 communication is present, then you must set
P2010[1] = 12 via the BOP.
This parameter, index 0, will alter the baudrate on RS485 regardless of the protocol selected in P2023.
P2011[0...1] 0 - 31 0 U, T - - U16 2
Sets unique address for converter.
[0] USS on RS485
[1] USS on RS232 (reserved)
You can connect up to a further 30 converters via the serial link (i.e. 31 converters in total) and control
them with the USS serial bus protocol.
P2012[0...1] 0-8 2 U, T - - U16 3
Defines the number of 16-bit words in PZD part of USS telegram. In this area, process data (PZD) are
continually exchanged between the master and slaves. The PZD part of the USS telegram is used for the
main setpoint, and to control the converter.
[0] USS on RS485
[1] USS on RS232 (reserved)
USS protocol consists of PZD and PKW which can be changed by the user via P2012 and P2013 respectively.
PZD transmits a control word and setpoint or status word and actual values.
The number of PZD-words in a USS-telegram are determined by P2012, where the first two words are
either:
a) control word and main setpoint or
b) status word and actual value.
When P2012 is greater or equal to 4 the additional control word is transferred as the 4th PZD-word (de-
fault setting).
USS protocol consists of PZD and PKW which can be changed by the user via P2012 and P2013 respec-
tively. P2013 determines the number of PKW-words in a USS-telegram. Setting P2013 to 3 or 4 deter-
mines the length of the PKW words (3 = three words and 4 = four words). When P2013 set to 127
automatically adjusts the length of the PKW words are required.
If a fixed PKW length is selected only one parameter value can be transferred.
In the case of indexed parameter, you must use the variable PKW length if you wish to have the values of
all indices transferred in a single telegram.
In selecting the fixed PKW length, it is important to ensure the value in question can be transferred using
this PKW length.
P2013 = 3, fixes PKW length, but does not allow access to many parameter values.
A parameter fault is generated when an out-of-range value is used. The value will not be accepted but the
converter state will not be affected.
Useful for applications where parameters are not changed, but MM3s are also used.
Broadcast mode is not possible with this setting.
P2013 = 4, fixes PKW length.
Allows access to all parameters, but indexed parameters can only be read one index at a time.
Word order for single word values are different to setting 3 or 127, see example below.
P2013 = 127, most useful setting.
PKW reply length varies depending on the amount of information needed.
Can read fault information and all indices of a parameter with a single telegram with this setting.
Example:
Set P0700 to value 5 (P0700 = 2BC (hex))
P2013 = 3 P2013 = 4 P2013 = 127
Master SINAMICS 22BC 0000 0006 22BC 0000 0000 0006 22BC 0000 0006 0000
SINAMICS Master 12BC 0000 0006 12BC 0000 0000 0006 12BC 0000 0006
P2014[0...1] 0 - 65535 2000 T - - U16 3
Index 0 defines a time T_off after which a fault will be generated (F72) if no telegram is received via the
USS/MODBUS channel RS485.
Index 1 defines a time T_off after which a fault will be generated (F71) if no telegram is received via the
USS channel RS232 (reserved).
[0] USS/MODBUS on RS485
[1] USS on RS232 (reserved)
If time set to 0, no fault is generated (i.e. watchdog disabled).
The telegram off time will function on RS485 regardless of the protocol set in P2023.
MODBUS on RS485:
MODBUS on RS485:
The time in which the converter is allowed to respond to the Modbus master. If the forming of a response
needs more time than specified in this parameter, the processing is done, but no response is sent.
P2023 0-3 1 T - - U16 1
Select the protocol which runs on the RS485 link.
0 None
1 USS
2 Modbus
3 Script terminal
After changing P2023, powercycle the converter. During the powercycle, wait until LED has gone off or
the display has gone blank (may take a few seconds) before re-applying power. If P2023 has been
changed via a PLC, make sure the change has been saved to EEPROM via P0971.
r2024[0...1] - - - - - U16 3
r2029[0...1] - - - - - U16 3
Displays number of USS telegrams with unidentified start.
See r2024
Not used on MODBUS.
r2030[0...1] - - - - - U16 3
Displays control word 1 from USS/MODBUS on RS485 (i.e. word 1 within USS/MODBUS = PZD1). See
r0054 for the bit field description.
See P2012
r2037.0...15 - - - - - U16 3
Displays control word 2 from USS on RS485 (i.e. word 4 within USS = PZD4). See r0055 for the bit field
description.
See P2012
To enable the external fault (r2037 bit 13) facility via USS, the following parameters must be set:
• P2012 = 4
• P2106 = 1
r2053[0...7] - 0 - - - U16 3
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
Switches off reporting of converter warnings. Can be used in conjunction with P0503 as an adjunct to
keep-running operation.
1 Converter warnings disabled
0 Converter warnings enabled
[0] Drive data set 0 (DDS0)
[1] Drive data set 1 (DDS1)
[2] Drive data set 2 (DDS2)
See also P0503
r2114[0...1] - - - - - U16 3
Displays run time counter.
It is the total time the converter has been powered up. When power is switched off, the value is saved,
and then restored on powerup. The run time counter will be calculate as followed:
Multiply the value in r2114[0] by 65536 and then add it to the value in r2114[1]. The resultant answer will
be in seconds. This means that r2114[0] is not days. Total powerup time = 65536 * r2114[0] + r2114[1]
seconds.
If r2114[0] = 1 and r2114[1] = 20864
We get 1 * 65536 + 20864 = 86400 seconds which equals 1 day.
[0] System Time, Seconds, Upper Word
[1] System Time, Seconds, Lower Word
P2115[0...2] 0 - 65535 257 T - - U16 4
Displays real time.
All converters require an on-board clock function with which fault conditions may be time-stamped and
logged. However, they have no battery backed Real Time Clock (RTC). Converters may support a soft-
ware driven RTC which requires synchronization with the RTC supplied via a serial interface.
The time is stored in a word array parameter P2115. The time will be set by USS Protocol standard "word
array parameter write" telegrams. Once the last word is received in index 2, the software will start running
the timer itself using internal running 1 millisecond tic. Hence becoming like RTC.
If power-cycle takes place, then the real time must be sent again to the converter.
Time is maintained in a word array parameter and encoded as follows - the same format will be used in
fault report logs.
Index High Byte (MSB) Low Byte (LSB)
0 Seconds (0 - 59) Minutes (0 - 59)
1 Hours (0 - 23) Days (1 - 31)
2 Month (1 - 12) Years (00 - 250)
The values are in binary form.
[0] Real Time, Seconds + Minutes
[1] Real Time, Hours + Days
[2] Real Time, Month + Year
P2120 0 - 65535 0 U, T - - U16 4
Indicates total number of fault/warning events. This parameter is incremented whenever a fault/warning
event occurs.
Defines hysteresis level applied for comparing frequency and speed to threshold.
See P1175.
If P1175 is set, P2150 is also used to control the Dual Ramp function.
P2151[0...2] 0 - 4294967295 1170[0] U, T - DDS U32 3
Selects the source of setpoint frequency, actual frequency is compared with this frequency to detect fre-
quency deviation (see monitoring bit r2197.7).
P2155[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 3
Sets a threshold for comparing actual speed or frequency to threshold values f_1. This threshold controls
status bits 4 and 5 in status word 2 (r0053).
P2156[0...2] 0 - 10000 10 U, T - DDS U16 3
When comparing speed or frequency to threshold f_2 (P2157) this is the time delay before status bits are
cleared.
P2159[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 2
When comparing speed or frequency to threshold f_3 (P2159) this is the time delay before status bits are
set.
P2162[0...2] 0.00 - 25.00 3.00 U, T - DDS Float 3
Hysteresis speed (frequency) for overspeed detection. For V/f control modes the hysteresis acts below the
maximum frequency.
P2164[0...2] 0.00 - 10.00 3.00 U, T - DDS Float 3
Hysteresis frequency for detecting permitted deviation (from setpoint) or frequency or speed. This fre-
quency controls bit 8 in status word 1 (r0052).
P2166[0...2] 0 - 10000 10 U, T - DDS U16 3
Defines the threshold of the monitoring function |f_act| > P2167 (f_off). P2167 influences following func-
tions:
• If the actual frequency falls below this threshold and the time delay has expired, bit 1 in status word 2
(r0053) is reset.
• If an OFF1 or OFF3 was applied and bit 1 is reset the converter will disable the pulse (OFF2).
P2168[0...2] 0 - 10000 0 U, T - DDS U16 3
Defines time for which the converter may operate below switch-off frequency (P2167) before switch off
occurs.
Active if holding brake (P1215) not parameterized.
P2170[0...2] 0.00 - 400.0 100.0 U, T - DDS Float 3
Defines threshold current relative to P0305 (rated motor current) to be used in comparisons of I_act and
I_Thresh. This threshold controls bit 3 in status word 3 (r0053).
P2171[0...2] 0 - 10000 10 U, T - DDS U16 3
Defines delay time prior to activation of current comparison.
P2172[0...2] 0 - 2000 800 U, T - DDS U16 3
Defines DC link voltage to be compared to actual voltage. This voltage controls bits 7 and 8 in status word
3 (r0053).
P2173[0...2] 0 - 10000 10 U, T - DDS U16 3
Threshold current for A922 (no load applied to converter) relative to P0305 (rated motor current).
If a motor setpoint cannot be entered and the current limit (P2179) is not exceeded, warning A922 (no
load applied) is issued when delay time (P2180) expires.
It may be that the motor is not connected or a phase could be missing.
P2180 0 - 10000 2000 U, T - - U16 3
Sets the lower frequency threshold f_1 for defining the area where the load monitoring is effective. The
frequency torque envelope is defined by 9 parameters - 3 are frequency parameters (P2182 - P2184), and
the other 6 define the low and high torque limits (P2185 - P2190) for each frequency.
See P2181 for calculated default value.
Below the threshold in P2182 and above the threshold in P2184, the load monitoring mode is not active.
In this case the values for normal operation with the torque limits given in P1521 and P1520 are valid.
P2183[0...2] 0.00 - 550.00 30.00 U, T - DDS Float 3
Sets the frequency threshold f_2 for defining the envelope in which the torque values are valid. See
P2182.
See P2181 for calculated default value.
P2184[0...2] 0.00 - 550.00 50.00 U, T - DDS Float 3
Sets the upper frequency threshold f_3 for defining the area where the load monitoring is effective. See
P2182.
See P2181 for calculated default value.
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function.
Monitoring word 2 which indicates the state of monitor functions. Each bit represents one monitor function.
00 Status of FF Yes No
P2231[0...2] 0-3 0 U, T - DDS U16 2
PID-MOP mode specification
Sets the signal source to change over from manual to automatic mode. If using the motorized potentiome-
ter in the manual mode the setpoint is changed using two signals for up and down, e.g. P2235 and P2236.
If using the automatic mode the setpoint must be interconnected via the connector input (P2242).
0: manually
1: automatically
Refer to: P2235, P1036, P2242
P2242[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setpoint of the motorized potentiometer if automatic mode P2241 is select-
ed.
Refer to: P2241
P2243[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setting command to accept the setting value for the motorized potentiome-
ter. The value becomes effective for a 0/1 edge of the setting command.
Refer to: P2244
P2244[0...2] 0 - 4294967295 0 T - CDS U32 3
Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0/1 edge of
the setting command.
Refer to: P2243
r2245 - - - - - Float 3
Displays the motorized potentiometer setpoint before it passed the PID-MOP RFG.
P2247[0...2] 0.00 - 1000.0 10.00 U, T - DDS Float 2
Sets the ramp-up time for the internal PID-MOP ramp-function generator. The setpoint is changed from
zero up to limit defined in P1082 within this time.
Refer to: P2248, P1082
P2248[0...2] 0.00 - 1000.0 10.00 U, T - DDS Float 2
Sets the ramp-down time for the internal PID-MOP ramp-function generator. The setpoint is changed from
limit defined in P1082 down to zero within this time.
Refer to: P2247, P1082
r2250 - - - PERCE - Float 2
NT
Displays output setpoint of motor potentiometer.
P2251 0-1 0 T - - U16 3
Enables function of PID controller.
0 PID as setpoint
1 PID as trim
Active when PID loop is enabled (see P2200).
r2262 - - - - - Float 3
Displays filtered PID setpoint after PID-RFG. r2262 is the result of the value in r2260, filtered with PT1-
Filter and the time constant given in P2261.
r2262 = 100 % corresponds to 4000 hex.
P2263 0-1 0 T - - U16 3
Sets the PID controller type.
0 D component on feedback signal
1 D component on error signal
P2264[0...2] 0 - 4294967295 0 U, T 4000H CDS U32 2
Selects the source of the PID feedback signal.
See P2254
When analog input is selected, offset and gain can be implemented using P0756 to P0760 (analog input
scaling).
P2265 0.00 - 60.00 0.00 U, T - - Float 2
Sets the upper limit for the value of the feedback signal.
When PID is enabled (P2200 = 1) and the signal rises above this value, the converter will trip with F222.
P2267 = 100 % corresponds to 4000 hex.
Allows the user to scale the PID feedback as a percentage value. A gain of 100.0 % means that feedback
signal has not changed from its default value.
P2270 0-3 0 U, T - - U16 3
Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269.
0 Disabled
1 Square root (root(x))
2 Square (x*x)
3 Cube (x*x*x)
P2271 0-1 0 U, T - - U16 2
Allows the user to select the transducer type for the PID feedback signal.
0 Disabled
1 Inversion of PID feedback signal
It is essential that you select the correct transducer type. If you are unsure whether 0 or 1 is applicable,
you can determine the correct type as follows:
1. Disable the PID function (P2200 = 0).
2. Increase the motor frequency while measuring the feedback signal.
3. If the feedback signal increases with an increase in motor frequency, the PID transducer type should be 0.
4. If the feedback signal decreases with an increase in motor frequency the PID transducer type should
be set to 1.
r2272 - - - - - Float 2
This parameter determines the time that the autotuning code will wait before aborting a tuning run if no
oscillation has been obtained.
P2355 0.00 - 20.00 5.00 U, T - - Float 3
Sets applied offset and deviation for PID autotuning.
This can be varied depending on plant conditions e.g. a very long system time constant might require a
larger value.
0 Disable
1 Fault
2 Warn
The time for which cavitation conditions have to be present before a fault/warning is triggered.
P2365[0...2] 0-2 0 U, T - DDS U16 2
With hibernation enabled. If the frequency demand drops below the threshold there is a delay of P2366
seconds before the converter is stopped.
P2367[0...2] 0 - 254 2 U, T - DDS U16 3
With hibernation enabled. If pulses have been disabled by the unit going into hibernation, and the fre-
quency demand has increased to above the hibernation threshold, there will be a delay of P2367 seconds
before the converter restarts.
P2370[0...2] 0-1 0 T - DDS U16 3
Selects stop mode for external motors when motor staging is in use.
0 Normal stop
1 Sequence stop
P2371[0...2] 0-3 0 T - DDS U16 3
Selects configuration of external motors (M1, M2) used for motor staging feature.
0 Motor staging disabled
1 M1 = 1 x MV, M2 = Not fitted
2 M1 = 1 x MV, M2 = 1 x MV
3 M1 = 1 x MV, M2 = 2 x MV
For this kind of motor application it is mandatory to disable negative frequency setpoint!
Motor staging allows the control of up to 2 additional staged pumps or fans, based on a PID control sys-
tem.
The complete system consists of one pump controlled by the converter with up to 2 further pumps/fans
controlled from contactors or motor starters.
The contactors or motor starter are controlled by outputs from the converter.
The diagram below shows a typical pumping system.
A similar system could be set up using fans and air ducts, instead of pumps and pipes.
When the converter is running at minimum frequency, and the PID feedback indicates that a lower speed
is required, the converter switches off (de-stages) one of the digital output controlled motors M1 and M2.
In this case, the converter must ramp from minimum frequency to maximum frequency outside of PID
control (see P2378 and diagram below).
P2373 as a percentage of PID setpoint that PID error r2273 must be exceeded before staging delay
starts.
The value of this parameter must always be smaller than delay override lockout timer P2377.
P2374[0...2] 0 - 650 30 U, T - DDS U16 3
Time that PID error r2273 must exceed motor staging hysteresis P2373 before staging occurs.
P2375[0...2] 0 - 650 30 U, T - DDS U16 3
Time that PID error r2273 must exceed motor staging hysteresis P2373 before destaging occurs.
P2376[0...2] 0.0 - 200.0 25.0 U, T PERCENT DDS Float 3
P2376 as a percentage of PID setpoint. When the PID error r2273 exceeds this value, a motor is
staged/destaged irrespective of the delay timers.
The value of this parameter must always be larger than staging hysteresis P2373.
P2377[0...2] 0 - 650 30 U, T - DDS U16 3
Time for which delay override is prevented after a motor has been staged or destaged.
This prevents a second staging event immediately after a first, being caused by the transient conditions
after the first staging event.
The frequency as a percentage of maximum frequency. During a (de) staging event, as the converter
ramps from maximum to minimum frequency (or vice versa) this is the frequency at which the digital out-
put is switched.
This is illustrated by the following diagrams.
r2379.0...1 - - - - - U16 3
Output word from the motor staging feature that allows external connections to be made.
0 Not Active
1 Level 1
2 Level 2
... ...
6 Level 6
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2
FFBs will be calculated in following order: P2802[3], P2801[3] , P2801[4], P2802[4]
[0] Enable AND 1
[1] Enable AND 2
[2] Enable AND 3
[3] Enable OR 1
[4] Enable OR 2
[5] Enable OR 3
[6] Enable XOR 1
[7] Enable XOR 2
[8] Enable XOR 3
[9] Enable NOT 1
[10] Enable NOT 2
[11] Enable NOT 3
[12] Enable D-FF 1
[13] Enable D-FF 2
[14] Enable RS-FF 1
[15] Enable RS-FF 2
[16] Enable RS-FF 3
Set P2800 to 1 to enable function blocks.
All active function blocks will be calculated in every 128 ms, if set to level 1 to 3. Fast free function blocks
(level 4 to 6) will be calculated in every 8 ms.
P2810[0...1] 0- 0 U, T - - U32 3
4294967295
P2810[0], P2810[1] define inputs of AND 1 element, output is r2811.
00 Output of BO Yes No
See P2810
P2812[0...1] 0 - 4294967295 0 U, T - - U32 3
P2812[0], 2812[1] define inputs of AND 2 element, output is r2813.
See P2810
P2801[1] assigns the AND element to the processing sequence.
r2813.0 - - - - - U16 3
Output of AND 2 element. Displays and logic of bits defined in P2812[0], P2812[1]. See r2811 for the bit
field description.
See P2812
P2814[0...1] 0 - 4294967295 0 U, T - - U32 3
P2814[0], P2814[1] define inputs of AND 3 element, output is r2815.
See P2810
P2801[2] assigns the AND element to the processing sequence.
r2815.0 - - - - - U16 3
Output of AND 3 element. Displays and logic of bits defined in P2814[0], P2814[1]. See r2811 for the bit
field description.
See P2814
P2816[0...1] 0 - 4294967295 0 U, T - - U32 3
P2816[0], P2816[1] define inputs of OR 1 element, output is r2817.
See P2810
P2801[3] assigns the OR element to the processing sequence.
r2817.0 - - - - - U16 3
Output of OR 1 element. Displays or logic of bits defined in P2816[0], P2816[1]. See r2811 for the bit field
description.
See P2816
P2818[0...1] 0 - 4294967295 0 U, T - - U32 3
P2818[0], P2818[1] define inputs of OR 2 element, output is r2819.
See P2810
P2801[4] assigns the OR element to the processing sequence.
r2819.0 - - - - - U16 3
Output of OR 2 element. Displays or logic of bits defined in P2818[0], P2818[1]. See r2811 for the bit field
description.
See P2818
P2820[0...1] 0 - 4294967295 0 U, T - - U32 3
P2820[0], P2820[1] define inputs of OR 3 element, output is r2821.
See P2810
P2801[5] assigns the OR element to the processing sequence.
r2821.0 - - - - - U16 3
Output of OR 3 element. Displays or logic of bits defined in P2820[0], P2820[1]. See r2811 for the bit field
description.
See P2820
P2822[0...1] 0 - 4294967295 0 U, T - - U32 3
P2822[0], P2822[1] define inputs of XOR 1 element, output is r2823.
See P2810
P2801[6] assigns the XOR element to the processing sequence.
r2823.0 - - - - - U16 3
Output of XOR 1 element. Displays exclusive-or logic of bits defined in P2822[0], P2822[1]. See r2811 for
the bit field description.
See P2822
P2824[0...1] 0 - 4294967295 0 U, T - - U32 3
P2824[0], P2824[1] define inputs of XOR 2 element, output is r2825.
See P2810
P2801[7] assigns the XOR element to the processing sequence.
r2825.0 - - - - - U16 3
Output of XOR 2 element. Displays exclusive-or logic of bits defined in P2824[0], P2824[1]. See r2811 for
the bit field description.
See P2824
P2826[0...1] 0 - 4294967295 0 U, T - - U32 3
P2826[0], P2826[1] define inputs of XOR 3 element, output is r2827.
See P2810
P2801[8] assigns the XOR element to the processing sequence.
r2827.0 - - - - - U16 3
Output of XOR 3 element. Displays exclusive-or logic of bits defined in P2826[0], P2826[1]. See r2811 for
the bit field description.
See P2826
P2828 0- 0 U, T - - U32 3
4294967295
P2828 defines input of NOT 1 element, output is r2829.
r2848.0 - - - - - U16 3
Displays Not-output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1]. See r2811 for the bit field description.
See P2846
P2849 0 - 4294967295 0 U, T - - U32 3
Define input signal of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
r2870 - - - - - Float 3
Result of Adder 1.
See P2869
P2871[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Adder 2, result is in r2872.
See P2869
P2802[5] assigns the Adder to the processing sequence.
r2872 - - - - - Float 3
Result of Adder 2.
See P2871
P2873[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Subtractor 1, result is in r2874.
See P2869
P2802[6] assigns the Subtractor to the processing sequence.
r2874 - - - - - Float 3
Result of Subtractor 1.
See P2873
P2875[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Subtractor 2, result is in r2876.
See P2869
P2802[7] assigns the Subtractor to the processing sequence.
r2876 - - - - - Float 3
Result of Subtractor 2.
See P2875
P2877[0...1] 0 - 4294967295 0 U, T 4000H - U32 3
Define inputs of Multiplier 1, result is in r2878.
See P2869
P2802[8] assigns the Multiplier to the processing sequence.
r2878 - - - - - Float 3
Result of Multiplier 1.
See P2877
See P2869
P2802[10] assigns the Divider to the processing sequence.
r2882 - - - - - Float 3
Result of Divider 1.
See P2881
P2883[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Define inputs of Divider 2, result is in r2884.
See P2869
P2802[11] assigns the Divider to the processing sequence.
r2884 - - - - - Float 3
Result of Divider 2.
See P2883
P2885[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Defines inputs of Comparator 1, output is r2886.
See P2869
P2802[12] assigns the Comparator to the processing sequence.
r2886.0 - - - - - Float 3
Displays result bit of Comparator 1. See r2811 for the bit field description.
See P2885
P2887[0...1] 0- 0 U, T 4000H - U32 3
4294967295
Defines inputs of Comparator 2, output is r2888.
See P2869
P2802[13] assigns the Comparator to the processing sequence.
r2888.0 - - - - - U16 3
Displays result bit of Comparator 2. See r2811 for the bit field description.
See P2887
P2889 -200.00 - 0.00 U, T - - Float 3
200.00
Fixed percent setting 1.
Sets the value for the amplitude of the wobble-signal as a proportion of the present ramp function genera-
tor (RFG) output. The value of P2946 is multiplied by the output value of the RFG then added to RFG out-
put.
For example, if the RFG output is 10 Hz, and P2946 has a value of 0.100, the wobble signal amplitude will
be 0.100 * 10 = 1 Hz. This means that the RFG output will therefore wobble between 9 Hz and 11 Hz.
P2947 0.000 - 1.000 0.000 T - - Float 2
Sets the value for decrement step at the end of the positive signal period. The amplitude of the step is
dependent upon the signal amplitude as follows:
Amplitude of signal decrement step = P2947 * P2946
P2948 0.000 - 1.000 0.000 T - - Float 2
Sets the value for the increment step at the end of the negative signal period. The amplitude of the incre-
ment step is dependent upon the signal amplitude as follows:
Amplitude of signal increment step = P2948 * P2946
P2949 0 - 100 50 T - - U16 2
Sets the relative widths of the rising and falling pulses. The value in P2949 sets the proportion of the wob-
ble period (determined by P2945) allocated to the rising pulse, the remainder of the time is allocation to the
falling pulse.
A value of 60% in P2949 means that 60% of the wobble period the wobble output will be rising. For the
remaining 40% of the wobble period the wobble output will be falling.
r2955 - - - - - Float 2
r3237[0...1] - 0 - - - Float 4
Defines the frequency at which the additional boost is applied for super torque and hammer start modes.
See P3350
P3355[0...2] 0.0 - 200.0 150.0 T PERCE - Float 2
NT
The magnitude of the Super Torque boost is calculated as follows:
V_ST = P0305 * Rsadj * (P3355/100)
Note:
Rsadj = stator resistance adjusted for temperature
Rsadj = (r0395/100) * (P0304/(sqrt(3) * P0305)) * P0305 * sqrt(3)
See P3350
Up to 200% of rated motor current (P0305) or limit of converter.
The Super Torque boost is calculated in the same way as Continuous Boost (P1310). As the stator resistance is used,
the calculated voltage is only accurate at 0 Hz. Thereafter, it will vary in the same way as Continuous Boost.
Setting in P0640 (motor overload factor [%]) limits the boost.
Defines the frequency at which the converter runs in the opposite direction to the setpoint during the block-
age clearing reverse sequence.
See P3350
P3362[0...2] 0.0 - 20.0 5.0 T - - Float 2
Sets the time for which the converter runs in the opposite direction to the setpoint during the reverse se-
quence.
See P3350
P3363[0...2] 0-1 0 T - - U16 2
Selects whether the converter ramps to, or starts directly from, the blockage clearing frequency (P3361).
0 Disable rapid ramp for blockage clearing
1 Enable rapid ramp for blockage clearing
See P3350
If P3363 = 1, the output jumps to the reverse frequency - this introduces a "kicking" effect which helps to
clear the blockage.
P3364[0...2] 1 - 10 1 T - - U16 2
Shows the operational status of the Super Torque function, while active.
Defines command source of protection enable command. If binary input is equal to one, then protection will
be initiated. If converter is stopped and protection signal becomes active, protection measure is applied as
follows:
• If P3853 0, frost protection is applied by applying the given frequency to the motor
• If P3853 = 0, and P3854 0, condensation protection is applied by applying the given current to the
motor
The protection function may be overridden under the following circumstances:
• If converter is running and protection signal becomes active, signal is ignored
• If converter is turning motor due to active protection signal and a RUN command is received, RUN
command overrides frost signal
• Issuing an OFF command while protection is active will stop the motor
P3853[0...2] 0.00 - 550.00 5.00 U, T - DDS Float 2
The DC current (as a percentage of nominal current) which is applied to the motor when condensation
protection is active.
See also P3852.
Performs calculations necessary for optimized motor operation. After completion of calculation, P3900 and
P0010 (parameter groups for commissioning) are automatically reset to their original value 0.
0 No quick commissioning
1 End quick commissioning with factory reset
2 End quick commissioning
3 End quick commissioning and initiate motor data calculation
Changeable only when P0010 = 1 (quick commissioning).
P3900 = 1:
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick
commissioning" are retained; all other parameter changes, including the I/O settings, are lost. Motor calcu-
lations are also performed.
P3900 = 2:
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning
menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the
motor calculations performed.
P3900 = 3:
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commis-
sioning with this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (motor
weight), P0350 (stator resistance), P2000 (reference frequency), P2002 (reference current).
When transferring P3900, the converter uses its processor to carry out internal calculations.
Communications - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to
make these calculations. This can result in the following error messages at the connected SIMATIC S7
control (communications via Fieldbus):
• Parameter fault 30
• Converter fault 70
• Converter fault 75
r3930[0...4] - - - - - U16 3
Displays the A5E number and the converter data versions.
[0] A5E 1st 4 digits
[1] A5E 2nd 4 digits
[2] Logistic Version
[3] Fixed Data Version
[4] Calib Data Version
P3950 0 - 255 0 U, T - - U16 4
Accesses special parameters for development (expert only) and factory functionality (calibration parame-
ter).
r3954[0...12] - - - - - U16 4
Used to classify firmware (only for SIEMENS internal purposes).
[0] CM label (increment/branch)
[1] CM label (counter)
[2] CM label
[3...10] GUI ID
[11] GUI ID major release
[12] GUI ID minor release
r3978 - - - - - U32 4
Counts the number of changed BICO links.
P3981 0-1 0 T - - U16 4
Resets active faults when changed from 0 to 1.
0 No fault reset
1 Reset fault
See P0947 (last fault code)
Automatically reset to 0.
P3984 100 - 10000 1000 T - - U16 3
Defines time after which a fault will be generated (F73) if no telegram is received from the client.
Setting 0 = watchdog disabled
r3986[0...1] - - - - - U16 4
Number of parameters on the converter.
[0] Read only
[1] Read & write
r4000 - r4064
P7844 0-2 0 T - - U16 3
After an automatic download from the SD card at startup, this parameter will be automatically set to 1. Also
a fault F395 will be set.
With setting to P7844 = 0 you quit F395 and confirm the parameter settings. Setting this parameter to 2 is
only possible if an automatic download has been performed at startup. In this case the download will be
undone and the previously stored parameters will be enabled.
0 Acceptance test/confirmation OK
1 Acceptance test/confirmation is pending
2 Undo clone
If no automatic download from the SD card has been performed during startup the setting 2 is not possible.
If the clone file contains user defaults and the cloning at startup is rejected with P7844 = 2, parameters are
set to the user defaults in the clone file instead of the previously saved values.
P8458 0-4 2 C, T - - U16 3
This parameter specifies whether a cloning at startup will be performed. The File clone00.bin will be used.
If no SD card is inserted there will be a normal startup.
0 No startup cloning
1 Clone at startup once
2 Clone at startup always
3 Clone at startup once, except the motor data
4 Clone at startup always, except the motor data
Default value is 2. After first cloning the parameter is set to 0. If an SD card is inserted without a valid file
the converter will set a fault F61/F63/F64 which can only be cleared by a power-cycle. The fault is signaled
by a flashing RUN LED (Commissioning). The SF LED is not activated. P8458 will not be changed by per-
forming a factory reset.
P8553 0-1 0 U, T - - U16 1
Selects whether to have menus with no text or menus with some text on the BOP.
0 Menus with no text
1 Menus with some text
Immediately when a fault occurs the fault icon shows and the display transitions to the
faults screen. The faults screen displays the fault number proceeded by "F".
To view the converter status at fault, press (> 2 s); to return to the fault code display,
press (< 2 s).
To clear/acknowledge the fault, press or acknowledge externally if the converter has
been set up so; to ignore the fault, press .
After you acknowledge or ignore the fault, the screen returns to the previous display. The
fault icon remains active until the fault is cleared/acknowledged.
You can use P2100 to select up to 3 faults for non-default stop reaction and use P2101 to
specify the reaction. For more information, see the description of P2100 and P2101 in
Section "Parameter list (Page 197)".
The calculated output ripple level has • Check the output wiring.
Output current exceeded the safe threshold. Common
• Check the mechanical vibration of the motor.
ripple too high causes are as follows:
• Check whether the setting of converter response to high
• Output phase missing
output current ripple (P0296) is correct.
• High motor vibration
Parameter cloning failed. • r0949 = 0: Use an SD card with FAT16 or FAT32 format
SD card pa- • r0949 = 0: The SD card is not con- , or fit an SD card to the converter.
rameter cloning nected or the card type is incorrect or • r0949 = 1: Check the SD card (for example, is the card
failed the card failed to initialize for automatic memory full?) - format the card again to FAT16 or
cloning. FAT32.
• r0949 = 1: Converter data cannot be • r0949 = 2: Put the correct named file in the correct direc-
written to the card. tory /USER/SINAMICS/DATA.
• r0949 = 2: Parameter cloning file is • r0949 = 3: Make sure file is accessible - recreate file if
unavailable. possible.
• r0949 = 3: The SD card cannot read • r0949 = 4: File has been changed - recreate file.
the file.
• r0949 = 4: Reading data from the
clone file failed (e.g., reading failed,
data or checksum wrong).
File exists but the contents are not valid Recopy and ensure operation completes.
Parameter control word corruption.
cloning con-
tents invalid
File exists but was not the correct con- Ensure clone from compatible converter type.
Parameter verter type.
cloning con-
tents incompat-
ible
No Clone00.bin file in the correct directory If an automatic clone is required:
Converter at- /USER/SINAMICS/DATA. • Insert the SD card with correct file and power-cycle.
tempted to do If no automatic clone is required:
an automatic
clone during • Remove the card if not needed and power-cycle.
startup • Reset P8458 = 0 and power-cycle.
This fault occurs after a startup clone. It The current parameter set needs to be checked and con-
Acceptance can also be caused by a faulty read from firmed by clearing the fault.
test/confirmatio the EEPROM, see F51 for more details.
n pending A startup clone could have changed and
might not match the application.
This parameter set needs to be checked
before the converter can start a motor.
• r0949 = 3/4: Converter data change
• r0949 = 5: Startup clone via an SD
card has been performed
• r0949 = 10: Previous startup clone was
aborted
Conditions exist for cavitation damage. If cavitation is not occurring, reduce the cavitation threshold
Cavitation pro- Cavitation damage is damage caused to a P2361, or increase the cavitation protection delay. Ensure
tection failure pump in pumping systems when the fluid sensor feedback is working.
is not flowing sufficiently. This can lead to
heat build up and subsequent damage to
the pump.
Load conditions on motor indicate belt Check the following:
Load monitor- failure or mechanical fault.
• No breakage, seizure or obstruction of converter train.
ing trip • r0949 = 0: trip low torque/speed • Apply lubrication if required.
• r0949 = 1: trip high torque/speed If using an external speed sensor, check the following pa-
rameters for correct function:
- P2192 (delay time for permitted deviation)
- P2182 (threshold frequency f1)
- P2183 (threshold frequency f2)
- P2184 (threshold frequency f3)
If using a specific torque/speed range, check parameters:
- P2182 (threshold frequency 1)
- P2183 (threshold frequency 2)
- P2184 (threshold frequency 3)
- P2185 (upper torque threshold 1)
- P2186 (lower torque threshold 1)
- P2187 (upper torque threshold 2)
- P2188 (lower torque threshold 2)
- P2189 (upper torque threshold 3)
- P2190 (lower torque threshold 3)
- P2192 (delay time for permitted deviation)
If an alarm is activated the alarm icon shows immediately and then the display shows the
alarm code proceeded by "A".
Note that alarms cannot be acknowledged. They are cleared automatically once the warning
has been rectified.
You can disable stop reaction for three selected alarms or all alarms:
Use P2100 to select up to 3 alarms and use P2101 to disable stop reaction for the
selected alarms.
Use P2113 to disable stop reaction for all alarms.
For more information, see the description of P2100, P2101, and P2113 in Section
"Parameter list (Page 202)".
• Small motors (120 W) under FCC and light load Use V/f operation for very small motors
may cause a high current
Overvoltage limit is reached. This warning can occur If this warning is displayed permanently,
Overvoltage limit during ramp down, if the Vdc controller is disabled check converter input voltage.
(P1240 = 0).
• Main supply failed. Check main supply voltage.
Undervoltage • Main supply and consequently DC-link voltage
limit (r0026) below specified limit.
Warning level of converter heat sink temperature,
Converter over- warning level of chip junction temperature, or allowed r0037[0]: Heat sink temperature
temperature change in temperature on chip junction is exceeded,
r0037[1]: Chip junction temperature (includes
resulting in pulse frequency reduction and / or output
heat sink)
frequency reduction (depending on parameterization in
P0290). Check the following:
• Surrounding temperature must lie within
specified limits
• Load conditions and load steps must be
appropriate
• Fan must turn when converter is running
Warning level exceeded, current will be reduced if Check that load cycle lies within specified
Converter I2t parameterized (P0610 = 1). limits.
Overload warning. Difference between heat sink and Check that load steps and shock loads lie
IGBT junction IGBT junction temperature exceeds warning limits. within specified limits.
temperature rise
warning
Converter heat sink temperature signal loss. Possible Contact service department or change con-
Converter tem- sensor fallen off. verter.
perature signal
lost
• Motor overloaded. Independently of the kind of temperature
Motor over- determination check:
• Load cycles or load steps too high.
temperature I2t • P0604 motor temperature warning thresh-
old
• P0625 motor surrounding temperature
• Check if name plate data is correct. If not,
perform quick commissioning. Accurate
equivalent circuit data can be found by
performing motor identification (P1900 =
2).
• Check if motor weight (P0344) is reasona-
ble. Change if necessary.
• With P0626, P0627, and P0628 the
standard overtemperature can be
changed, If the motor is not a SIEMENS
standard motor.
The calculated output ripple level has exceeded the • Check the output wiring.
Output current safe threshold. Common causes are as follows:
• Check the mechanical vibration of the
ripple too high • Loss of one of the output phases motor.
• High motor vibration
The braking energy is too large. Reduce the braking energy.
Braking resistor The braking resistor is not suited for the application. Use a braking resistor with a higher rating.
overload
Motor data identification (P1900) selected or running.
Motor data identi-
fication active
Internal time slice overrun Contact service department.
RTOS overrun
warning