Draft Specification No - RDSOPESPECAC0200 - 2020 (Rev - 1)
Draft Specification No - RDSOPESPECAC0200 - 2020 (Rev - 1)
RDSO/PE/SPEC/AC/0200-2020(Rev-1)
GOVERNMENT OF INDIA
MINISTRY OFRAILWAYS
APPROVED
Prepared By Checked by
INDEX
Sr Clause no Description Page
No. No.
1 1.0 -4.0 Foreword, Scope of supply, Operating and service conditions & 3-4
Governing specifications
2 5.0 Technical requirements of SBC 5-8
3 6.0 Constructional Features 8-10
4 7.0 - 8.0 Inspection and testing, Type Test, Routine test, Acceptance test, 10-12
Tests on SBC complete Unit.
5 9.0 Description of Tests; 12-16
Visual inspection and inspection of cabinet structure before
wiring, Visual inspection of complete SBC after wiring and
electrical operation test, Check for BOM and proof of material as
per specification with proof of invoices, Test for verification of di-
electric properties, Test for verification of insulation resistance,
Mechanical operation and sequence test, Test for verification of
clearance and creepage distances, Checking of electrical
continuity, Verification for effectiveness of protective circuits,
Temperature rise test, Shock and Vibration test, Tests on Fire
suppression system and cable fire barrier.
6 10.0 Technical Data to be submitted 16-17
7 11.0 Commissioning 17
8 12.0 Supplier’s Responsibility 17
9 13.0 Marking and packing 17-18
10 14.0 Guarantee/Warrantee 18
11 15.0 Training 18
12 16.0 Infringement of patent right 18-19
13 17.0 Cartel Formation 19
14 18.0 Annexure 19
Annexure A Undertaking against Cartel Formation. 20
Annexure B List of layout drawings 21
Annexure C List of wiring diagrams 22
Annexure D Bill of Material 23-45
Annexure E Particulars of connectors 46-47
Annexure F Schedule of cable sizes 48
Annexure G Technical requirements of aerosol fire detection and suppression 49
system.
Annexure H Technical requirements of hinges/locks/Accessories 50-57
Annexure I Temperature rise Scheme for guidance 58-59
Annexure J Modifications in Bill of Material of Annexure D with suitable 61-60
Switchgears (MPCB/MCB/Contactors) for LHB GS AC Coaches
Annexure K Format for feedback given by user railways regarding 62
performance of set of electrical panels for LHB EOG/HOG 3-tier
economy class type and general type AC coaches of Indian
Railways
Prepared By Checked by
1.0 FOREWORD
With the introduction of LHB GaribRath 3-Tier Economy Class type AC Coaches with
increased number of berths (83 nos.), the on-board space for installation of Switch Board
Cabinet has reduced drastically. In view of this, the on-board Switch Board Cabinet has
been split into two parts i.e. Under-slung Cubicle and On Board Cubicle. However, the
existing Switch Board Cabinet to RDSO specification no. RDSO/PE/SPEC/AC/0184-2015,
Rev.0 or latest shall be the most relevant specification for functional requirements of
scheme.
2.0 SCOPE
This specification covers general guidelines for design, manufacture, testing and supply of
Set of Electrical Panels for LHB EOG/HOG 3-Tier Economy Class Type and General Type
AC Coaches of Indian Railways.
A Manufacturer shall supply Set of Panels for 3-Tier Economy Class Type AC Coaches which
comprises of various cubicles along with Bill of material attached as Annexure D and wired
according to electrical wiring scheme as per Annexure –C of this specification as following:
-
B Manufacturer shall supply Set of Panels for General Type AC Coaches which comprises of
various cubicles along with Bill of material attached as Annexure D along with Annexure J
and wired according to electrical wiring scheme as per Annexure –C of this specification as
following: -
The equipment shall be sturdy and suitable for the following service conditions normally to
be met in Railway rolling stock service:
Prepared By Checked by
Referenced
Description
specification/Document
RDSO specification no. Specification of microprocessor based microcontroller of
RDSO/PE/SPEC/AC/0139- 2009. Roof Mounted Package Unit for AC LHB EOG coaches.
RDSO SPEC. NO.
Reliability of electronics used in rolling stock application.
ELRS/SPEC/SI/0015.
Code of practice for selection, installation and
IS:10118
maintenance of the switchgear and the control gear.
Specification for low voltage fuses for voltages not
IS:13703
exceeding 1000 volts or 1500 volts dc.
Direct acting indicating analog electrical measuring
IS: 1248 PT.II instruments and their accessories (ammeter and
voltmeters).
Hexagon head bolts, screws and nuts of product grades
IS:1364
a & b.
IS : 2500 Sampling procedure for inspection.
Specification for low voltage switchgear and control gear
IS : 8623
assemblies.
IS : 6911 Stainless steel plate, sheet and strip
EN : 45545 European railway standard for fire safety
IEC : 60529 Degrees of protection provided by enclosures (IP code).
IEC : 60947 Specification for low voltage switchgear and control gear.
Railway applications - electronic equipment used on
IEC : 60571
rolling stock
Electromagnetic compatibility (EMC/EMI compatibility
IEC : 61000 test)
Prepared By Checked by
Note: Latest editions/versions of the above specifications/ standards shall be applicable and
shall be available with the firm before commencement of the prototype testing.
Set of panel shall consist of Under slung cubicle and On Board cubicle.
Under slung cubicle shall consist of Disconnecting & Earthing Device & Feeder contactors
working on 750 V AC supply, High Voltage Fuse, Local main supply Contactors working on
415 V AC supply, Current transformers 750 VAC and control transformers750 VAC/415 V
AC etc. as mentioned in this specification.
On Board cubicle shall consist of 415 V AC/230 V AC/110 V AC power circuits and control
circuits like RMPU contactors, relay, Power supply On /off Switch, Feeder selection switch,
Low voltage fuses, RC filters, Measuring & Monitoring relay for 750 V AC supply 415 V AC
power supply Insulation Monitoring Relay for 415 V AC and 110 V AC power supply, PIS
controller, RMPU controller, Pump controller, Digital voltmeters and current meter, Charge
discharge meters, terminal Board, Push buttons , Indication etc. as mentioned in this
specification.
i. A disconnecting and earthing device along with high voltage fuses shall be located as
indicated in the drawing. The main function of this device is to isolate the two feeders (input
supply) and simultaneously earthing 750 volts ac network of the coach in OFF condition.
The connections to this device shall be made by removing the top cover on the front of the
device as per RDSO/PE/SK/AC/0220-2020(Rev-1) Sheet1 to Sheet 3.
ii. Wheel slide protection device (not in scope of supply). Clear space to be maintained for
Anti-skid device.
iii. Suitable mounting plate shall be provided on the back of the panel to house the switchgear
for main contactors and cage clamp terminals.
Iv Under-slung cubicle shall be IP-65 protected.
i. The On Board Cubicle shall house power and control switchgear, Measuring/Indicating
instruments, MMR & IMR, protection devices, light, fan, sanitary/pump control, controller of
the air conditioning unit, switchgear for the pantry equipment, DC-DC converters, PIS/PA
system, Fire detection & suppression system etc. duly wired. PIS/PA system, RMPU
controller, Pump controller are not in the scope of supply of SBC manufacturers.
ii. Depth wise, the cubicle contains contactors, relays, low voltage fuses, insulation monitoring
and terminal blocks for the incoming and outgoing 415 V /230 V AC,110V AC circuits, cable
alleys/trays and terminals for other layers as per sheet 2 of 5 of RDSO Drawing no.
RDSO/PE/SK/AC/0219-2020(Rev-1).
iv. MCBs/MPCBs shall be arranged in two rows with a voltage level of 415V/240 V AC for
feeding the RMPU load and part of the pantry load. MCBs/MPCBs shall not be accessible
without opening the Set of Panel front door.
Prepared By Checked by
v. PIS controller (not in scope of supply) mounting to be provided as per sheet 2 of 4 to RDSO
Drawing no. RDSO/PE/SK/AC/0219-2020(REV-0).
vi. Voltmeter, Ammeter and supply network selector switch shall be provided on the right door.
The voltmeter shall be connected directly to 750V ac network. Therefore, backside of the
voltmeter shall be covered with a polycarbonate sheet to prevent direct contact.
vii. Devices such as meters for battery voltage, charging and discharging current along with
various push buttons for faults of important devices (bus-bar network, local network, 415V
network, battery charger) etc. with a voltage level under or equal to 110V shall be arranged
on the right door as shown in the sheet number 3 of 5 to RDSO Drawing no.
RDSO/PE/SK/AC/0219-2020(Rev-1).
viii. Cut out for the RMPU display unit (S1U4) of size mentioned in RDSO drawing enclosed shall
also be provided for their mounting on the left door as show in the sheet number 4 of 5 to
RDSO Drawing no. RDSO/PE/SK/AC/0219-2020(Rev-1). Switch plate for mounting LCD
display & LP/HP Gauge etc. for RMPU AC Controller shall be supplied by SBC
manufacturer duly providing cut-outs as per RDSO drawing no. RDSO/PE/SK/AC/0219
(Sheet 5 of 5) -2020 (Rev-1).
Switch plate supplied by RMPU manufacturer to PUs shall be retained by PUs and
components viz. LCD display Unit, LP Gauge, HP Gauge & its selection switch etc.
supplied on Switch plate by RMPU manufacturer shall be retrofitted on switch plate supplied
by SBC manufacturer by PU during installation and commissioning.
Cut out for the Pump controller mentioned in RDSO drawing enclosed shall also be
provided for their mounting.
Suitable mounting plate shall be provided to house the measuring and monitoring relays.
ix. The connectors for the mobile charging socket shall be provided in the panel as indicated in
the drawing.
x. Space for RMPU AC controller (cut out size 420mm X 360 330mm(min.)) shall be provided
on left door as indicated in the sheet number 4 of 5 to RDSO Drawing no.
RDSO/PE/SK/AC/0219-2020(Rev-1).
5.3 Space for RC Filter shall be provided on right door as indicated in the sheet number 3 of 5
to RDSO Drawing no. RDSO/PE/SK/AC/0219-2020(Rev-1).
5.4 All crimping of cable/connector pins shall be done with suitable crimping tools to avoid any
crimping failure in service.
5.5 All wiring shall be secured with fire retardant cable ties and provided with cable protection
sleeves made up of polyamide. Wherever required, cable stiffener shall be provided for
proper cable routing.
5.6 The internal wiring shall be done with Halogen free electron beam irradiated cables voltage
grade 1.8 kV /3 kV for 750 V circuit and 750 V for 415/230/110 V Circuit conforming to
RDSO specification No. ELRS/SPEC/ELEC/0019 latest revision. The sizes/type of cables
shall be as indicated in harness chart given in Annexure F. All cables/wiring shall be color
coded according to phases for easy identification. Control wiring and power cables shall be
segregated according to the voltages and adequately secured with cable ties. Wherever
required, cable stiffener shall be provided for proper cable routing.
Prepared By Checked by
5.8 Two earthing terminals shall be provided on top and bottom of the panel on diagonally
opposite ends. For earthing Set of Panel with coach body two braided copper cable of 70 sq
mm and 300 mm in length each, duly crimped at both ends shall be supplied with the panel.
Earthing of the metal parts/sub-assemblies inside the panel shall be done with suitable size
braided copper cable as determined in accordance with 7.4.3.1.7 (a) of IS: 8623 (Pt-I) –
latest.
5.9 Screen printed component code list shall be provided at backside of left front door at
suitable place, which should be visible after opening of front door. Laminated copy
Schematic power and control circuit printed on A0 size paper after suitable fold shall be
placed in pocket provided at inner side of left lower front door.
5.10 Suitable zero halogen polyamide alleys/ABS alley with snap-in element of approved make
shall be provided for cable transverse as indicated in the drawings. Whenever the cables
shall cross the door/passage area, the cables shall be covered by self-extinguishing and
halogen free braided cable jacket (material-polyamide 6.6) of approved make.
5.11 All the switchgear devices fitted in the Set of Panel shall be easily accessible for
maintenance from the front of the panel.
5.12 HT fuses and 750 V & 415 V MMRs (Measuring & monitoring Relay i.e. phase control relay)
shall be mounted on minimum 3 mm epoxy/ Bakelite/SMC (FRP) sheet in “On Board
Panel”. There shall be minimum 100 mm gap between two MMR’s.
5.13 The Power/Control wiring of the Set of Panel shall be as per wiring diagram given in
Annexure-C.
5.15 Only approved make of components mentioned in the bill of material as per Annexure-D for
Set of Panels for 3 Tier Economy type AC coaches and Annexure-D along with Annexure-J
for General Type AC Coaches shall be used. For any deviation prior approval from RDSO
shall be taken.
5.16 All rotary switches shall conform to IEC 60947 and shall be suitable for universal mounting.
5.17 General and safety requirements shall be governed by IEC 60947 and IS:8623-latest.
5.18 Door stopper arrangement for retaining the door of under slung cubicle shall be provide for
maintenance purpose.
6.1 The Set of Panel shall be fabricated from standard of welded stainless steel SS304L for On
Board Panel and SS304 grade S2 as per IS 6911 for Underslung Panel. Only TIG
(Tungsten Inert Gas) welding shall be used for fabrication of frames. Overall dimensions
shall not exceed the following dimension:
i) ON BOARD PANEL
Height 1850 mm
Width 850mm
Depth 300mm including door
Height 550 mm
Width 2300mm
Depth 600mm including door
6.2 The Stainless steel sheet used for all the front doors shall be 1.6 mm thick.
6.3 The dimensions/switchgear mounting/general layout of the Set of Panel shall be as per
RDSO Drawing no. RDSO/PE/SK/AC/0219-2020(Rev-1) sheet 1 to sheet 5 for On Board
Panel and RDSO Drawing no. RDSO/PE/SK/AC/0220-2020 (Rev-1) sheet 1 to sheet 3 for
Under-slung Panel.
6.4 All internal partition frames, plate, swivelling frames and complete Set of Panel including
bottom doors and top sheet shall be as in Para 6.1.
Prepared By Checked by
6.5 All Fasteners used in the construction of overall structure shall be of stainless steel to
IS:1364 Part 2.
6.6 On Board Panel shall be covered on left & right and back side with 1.0 mm thick fixed with
SS fasteners. Under door closed condition of Set of Panel no possibility should remain to
enter any rodent to avoid short circuit.
6.7 The general construction of the Set of Panel shall be such as to keep the various voltage
levels segregated against each other as far as possible. There shall be no crisscrossing of
cables/wires within same voltage or different voltage levels.
6.8 Suitable 4 nos. SS 304 M12 eye bolts shall be provided at the top four corners of On
Board panel for lifting panel during mounting/dismounting from the coach.
6.9 Each door leaf of On board panel shall be provided with non lockable snap lock of
approved make.
6.10 The doors shall be fixed to the main frame by means of heavy duty hinges duly fixed on
appropriate size back piece to provide adequate strength sustaining vibrations in door
open conditions and of approved make as shown in drawings/BOM.
6.11 For fixing DIN rails and other switchgear viz. Power contactors, power fuses etc., minimum
3 mm back-piece with tapped hole or nut shall be provided behind mounting plate/sheet.
Mounting screw for DIN rails shall not be less than M6. Suitable Mounting screw for body
mounted switch gear shall be as per OEMs stipulation. Interspacing
between two fixing screws for DIN rails should not be more than 200 mm. Good
engineering practices shall be adopted. The depth of the tapped hole shall be more than
the diameter of the screw.
6.12 Metallic end locking plates shall be used for securing of switch gears on DIN rail &
minimum 35mm free length of DIN rail should be available on ends, unless not feasible due
to space constraints.
6.13 All switch gear component used in Set of Panel shall be conforming to following criteria:
(i) Components material provided in Set of Panel shall conform to EN 45545 with hazard level
HL-2, pollution category 3, vibration shock to IEC 61373 and suitable to work in
temperature range -5 Deg C to 70 Deg C & relative humidity up to 98 % and suitable for
rolling stock application.
(ii) Stipulated current rating for all switch gears items shall be at rated voltage, specified
utilization category and at 700C.
(iii) Rated voltage for components used on 750 Volts AC & 415 Volts AC side shall be 1000
volts AC & 690 Volts AC respectively.
(iv) Surface mounted switchgear such as Feeder selection contactor K01 & K02, K44 shall be
fitted on unified mounting plate of adequate thickness & strength so as to ensure full
interchangeability amongst at least four approved make i.e. ABB, Siemens, Schneider,
L&T. Firm shall submit details and shall have RDSO’s prior approval before type test.
6.14 Fire standard- IEC EN 45545 HL-2 shall be followed for all materials used in Set of Panel.
6.15 Complete stainless steel SS -304 structure and partition etc. Are not required to be painted
but outer sheets & doors shall be finished for proper appearance and aesthetics. Finishes
of SS-304 L sheet shall be scotch brite/No. 4 i.e. smooth, polished with finish grit/fine line
finish, as per IS 6911.
Prepared By Checked by
6.16 For fire detection & suppression system, condensed aerosol fire extinguishers conforming
to technical requirements given in Annexure G shall be installed with the suitable anti-
pilferage arrangements. Tentative numbers & Weights shall be as under: -
6.17 110 V DC, compact LED “D” type Light fitting conforming to RDSO specification no.
RDSO/PE/SPEC/AC TL/0091-(Rev-2 1) and ICF RCF Drawing no. ICF/STD-7-6-050
LW76092 along with switch and socket and procured form approved source shall be
provided inside onboard panel along with switch and socket point for the ease of
maintenance staff. Light fitting shall be mounted /screwed suitably to avoid damage due to
vibration in service.
6.18 Two nos. RC filters (RC1 and RC2) consisting of 1 ohm, 6 W resistor connected in series
with parallel connected 1.5 Micro Farad, 850 V capacitor of Vishay or Epcos make in each
arm of 415 V circuit between phase to neutral and phase to earth circuit. The RC filter to be
tested on incoming supply of > 20% THD before introducing RC Filter in the circuit and the
same to be smoothened to <5% THD on introduction of RC Filter. The test to be carried out
inhouse or by NABL/NABCB accredited Lab.
Firm manufacturing SBC for the first time shall get test plan/protocol approved from RDSO.
7 1.1 Only after the detail drawings and the design have been approved and the clearance given
to this effect, the manufacturer shall take up the manufacture of the prototype. It is to be
clearly understood that any changes, required to be done in the prototype or any additional
tests other than specified herein are required to be conducted on the prototype unit or its
components, they shall be done expeditiously at the expense of firm.
7.1.2 If so desired, RDSO shall repeat some or all type tests once in three years on sample
basis, so as to confirm the quality of the product to meet the specified requirements.
7.1.3 The type tests shall be carried out by RDSO on prototype unit either totally or in part under
the following conditions without any additional cost:
7.1.4 Investigation tests are intended to obtain additional information regarding the performance
of the product. They shall be specially requested either by the RDSO or Purchaser or by
the manufacturer.
Prepared By Checked by
7.1.5 RDSO may conduct surprise checks on manufacturing process and quality control along
with any of the tests to ensure consistent quality of product and its conformance to RDSO
specification.
7.1.6 The tests shall be carried out at the works of the manufacturer in presence of Indian
Railway representative on the prototype unit as per the relevant governing specifications
modified or amplified. The manufacture shall have all possible necessary arrangement for
testing. Unless otherwise stated, tests specified in RDSO specification and for which
facilities are not available with the firm shall be conducted at NABL/NABCB accredited lab.
7.1.7 The Test Protocol indicating relevant clause of the test, condition of the test, specified
value and observed value of the parameter shall be submitted by the firm before offering
the prototype for type testing.
7.1.8 The SBC shall successfully pass all the type tests for proving conformity with this
document. If any one of the equipment fails in any of the type tests, the inspecting agency
at his discretion, may call for another equipment of the same type and subject it to all tests
or the test(s) in which failure occurred. No failure shall be permitted in the repeat test.
Routine tests are to be carried out on each unit by firm to verify that properties & design of
the product correspond to those measured during type test. Proper documentation of
routine test results should be available with the firm and should be produced before
inspecting official on demand. Tests shall be conducted as per test schedule given.
Each offered lot of supply shall be subjected to acceptance tests as per RDSO approved
sampling plan or as per sampling plan specified in IS 2500 GIS S-2 GIL Level II, at
manufacturer’s works. Acceptance test shall be witnessed by inspecting official nominated
by purchaser/RDSO. Manufacturer, on demand by inspecting official shall produce the
internal/routine test report carried out by him.
8.0 TESTS
8.1 Tests as mentioned in table below shall be carried out as per respective clause of this
specification indicated against each.
Prepared By Checked by
age distances
8. 9.8 Checking of electrical continuity Yes 9.8(g vii) Yes (vii)
only only
9. 9.9 Verification for effectiveness of protective Yes Yes Yes
Circuits
10. 9.10 Temperature rise test Yes No No
11 9.11 Shock &Vibration test from NABL/NABCB Yes No No
accredited Lab
12 9.12 Test on fire suppression system Yes* No No
13 9.13 Test on cable fire barrier Yes* No No
14 9.14 Test of degree of protection Yes No No
IP – 65 as per IEC-60529 (latest Edition)
from NABL/NABCB Accredited Lab for
Under slung cubicle only.
The accuracy of measuring instruments used for all type of tests shall be of class 0.5.
* Tests at SN 12 & 13 above are not required if RDSO approved Fire Suppression System
Cartridges and Fire Barriers are used whose prototype has already been carried out before in
similar type of Switch Board Cabinets.
Prototype structure of Set of Panel shall be checked as per RDSO drawing no.
RDSO/PE/SK/AC/0219-2020(Rev-1) for On Board Panel and RDSO/PE/SK/AC/0220-
2020 (Rev-1) for Under-slung Panel Annexure B of this specification or with latest
drawings.
9.2 Visual inspection of complete SBC after wiring and electrical operation test:
a) General workmanship of Switch Board Cabinet and its accessories such as MPCB,
MCB, fuse, relay, contactor, connector, cable etc.
b) Name plate
c) Codification chart
d) Interface dimensions with coach and overall and mounting dimension of cabinet.
e) Provision of Earthing cables
f) Sticker /Marking plate of components
g) Marking and general layout of housing,
h) Color coding of cables as mentioned in the specification & drawings.
i) Detailed dimensions
j) Electrical operations as per applicable drawings and prepared test protocol.
Sr. No (a) to (h) shall be checked during acceptance test & routine test also.
(i) Firm shall submit BOM with clear details of actual part number and make used in the
SBC. Firm shall bring out clearly the variations in actual part number and that
approved by RDSO during type test.
Prepared By Checked by
(ii) Firm shall have to provide switchgears as per catalog no. Mentioned in the BOM. For
those items where catalog no. Is not mentioned, firm shall obtain RDSO prior
approval.
(iv) The test shall include visual inspection of component and material of SBC as per Bill
of material.
(v) Invoice, test certificates and data sheets of the following shall be checked:
a) MCBs/MPCBs
b) Contactors
c) Rotary switches & Overload relays
d) Insulation Monitoring Relay & Phase control relay(MMR)
e) RC filter
f) Control transformer
g) Earthing& disconnecting device
h) HT fuses
i) Cables
j) Cable alley
k) Polycarbonate sheet
l) Door hinges & locks
m) Fire detection & suppression system
n) Cable fire barrier.
9.4 Test for verification of di-electric properties:
The SBC shall be tested with 3 kV test set between live parts and earthed body.
The HV test shall be done with AC (50 Hz) which shall be gradually increased (applied
for one minute). The test is considered pass, if no electric breakdown or flashover
occurs.
Prepared By Checked by
Satisfactory mechanical operation shall be verified after installation. The number of the
operating cycles shall be 20 on all rotary switches, disconnecting & earthing switch,
sliding tray, rotating frame & all doors. The operation of the mechanical interlocks
associated with these movements shall be checked.
The test is considered to have been passed, if the operating conditions of the apparatus,
interlocks etc. Have not been impaired and if the effort required for operation is
practically the same as before the test.
In the case of withdraw-able functional units, the cycle shall be from the connected to the
disconnected position and back to the connected position.
(ii) Electrical switchgears/cable alley shall be mounted keeping in mind the clearance
given in drawings mentioned in Annexure B for maintaining clearance and
creepage distance.
Prepared By Checked by
(ii) When a part of Switch Board Cabinet is removed from the enclosure, for routine
maintenance, the protective circuits for the remainder of the Switch Board Cabinet
shall not get interrupted.
(iii) Means used for assembling the various metal parts of Switch Board Cabinet shall
be sufficient for ensuring the following: -
(iv) For lids, doors, cover plates etc. The usual metal screwed connections and metal
hinges are considered sufficient to ensure continuity provided that no electrical
equipment is attached to them.
(v) All parts of protective circuit within the Switch Board Cabinet shall be so designed
that they are capable of withstanding the highest thermal and dynamic stresses
that may occur at the place of installation in Switch Board Cabinet.
(vi) During prototype test continuity of all live components shall be checked as per
wiring diagram attached with specification.
During acceptance test inspecting agency shall examine the testing of pervious lot of
the SBC and it shall be ensured that the above 5 tests are not repeated with previous
lot.
Prepared By Checked by
a) D& ED.
b) Single phasing, Phase sequence reversal, Unbalancing of phase voltages, under
voltage, Overvoltage of Phase control relay (MMR).
c) Contactors K1, K2, K43, K44 pick up and drop out voltage.
d) All MPCBs/ and minimum 3 MCBs of each rating for different voltage grades.
e) IMR A6 & A7
f) DC-DC converter
These tests shall be carried out during type test and routine test. In acceptance test any
2 of the above randomly picked up shall be tested on test bench.
(iii) Tripping of relevant MCB/MPCB of different circuit of after creating fault at the output
terminal of SBC shall be carried out during type test and routine test. In acceptance test
any 5 MPCB/MCB randomly picked up shall be tested for tripping.
(iv) It shall be verified that the different exposed conductive parts of the assembly are
effectively connected to the protective circuit in accordance with safety requirements. A
protective circuit in an assembly consists of either a separate protective conductor or the
conductive structural parts or both. It provides the following-
Temperature rise test of the Switch Board Cabinet shall be carried out as per clause no.
8.2.1 of IS 8623 Pt -1. The reading at various points of switchgears conductors &
insulators, HT fuses, bus bar, SBC body, doors, handles etc. Shall be measured at an
interval of 30 minutes till the temperature gets stabilized. The firm shall follow the
temperature rise scheme as per Annexure I submit the test scheme for temperature rise
test in advance to RDSO as per schematic given with this specification and get it
approved before type test.
Shock & vibration test of complete SBC shall be conducted as per category 1, class B
given in Annexure B of IEC 61373 – 2010 from any NABL/NABCB accredited agency.
Performance tests shall be carried out after shock & vibration tests and firm shall submit
internal performance test results after vibration and shock test to RDSO.
One unit of each size randomly picked up from offered lot of SBC shall be tested for its
triggering at stipulated temperature.
Test on one randomly picked up sample along with cable shall be conducted by putting
one side of cable on fire. Fire shall not propagate on other side of cable end fitting.
Test on prototype unit of Under-slung Panel for degree of protection class IP –65 as per
IEC-60529 (latest Edition) shall be conducted by NABL/NABCB Accredited Lab.
Prepared By Checked by
10.1 The firm manufacturing switch board cabinet for first time shall submit the mechanical & GA
drawings of SBC for approval to RDSO before starting production as per RDSO drawing
no. RDSO/PE/SK/AC/0219-2020(Rev-1) for On Board Panel and RDSO/PE/SK/AC/0220-
2020 (Rev-1) for Under-slung Panel
10.2 The manufacturer shall submit complete design details of SBC and its accessories, sub-
assemblies, necessary calculation of rating of major components used.
10.3 Manufacturer shall develop and submit the 3D model of SBC for better appreciation.
10.4 The manufacturer shall also supply one set of operating and trouble-shooting manual with
every 10 units.
11.0 COMMISSIONING:
Firm shall be responsible for commissioning of prototype unit in one coach at Production
Units (Pus). The SBC shall be compatible with the coach harness provided for various
circuits. Firm shall prove out the scheme in one coach for proper functioning of all related
equipment.
11.1 For the commissioning of first set of panel, panel manufacturer shall depute his staff at
production unit (PUs) for interface with respect of items falling in Production Units (Pus)
scope of supply.”
12.1 The supplier shall be fully responsible for ensuring that all equipment forming part of the
supply are entirely fit for the purpose and no part of this specification shall, in any way
remove or reduce his obligation in this respect. In addition, it is the supplier’s
responsibility to underwrite the complete switchgear system design and ensure that it is
compatible with and will, in no way, compromise the design and performance of switch
board cabinet of his supply.
12.2 The supplier shall provide “in the field” service support during the guarantee/warranty
period.
12.3 The supplier shall supply any purpose built or special tools or equipment that may be
necessary for the correct operation, servicing, testing or installation of the equipment of
the switch board cabinet.
12.4 The supplier will provide assistance, both in terms of material and technical, in
development of the system as a whole to ensure that when this switch board cabinet is
installed as part of the integrated vehicle system, the performance of the system meets
or exceeds the requirements specified.
12.5 If the Switch Board Cabinet fails to achieve any of the stipulated requirements, the same
shall be modified at the supplier’s expense and within a time line to be agreed with
purchaser/consignee/RDSO.
13.1 All the switch board cabinets and its main component/accessories shall be provided with
a name/rating plate of bright anodized aluminium on the enclosure. The following
information shall be available either by etching process or by engraving or durable
screen-printed with black letters on white background and shall be fitted with riveting at
the front door on each panel:
Prepared By Checked by
13.2 All components provided inside the SBC shall be identified by screen/photo printed or
computer generated designation labels/legends marking plates. These should be
mounted near the concerned component duly ensuring visibility. Labels provided on
component will not be acceptable. Components shall also be provided with the name
plates indicating the operation/function of the switches/circuits. Contactors and circuit
codification diagram shall be identified by 17 aluminium anodized legend plates by
adhesive of approved make on back side of left hand front doors in place of pump
controller and AC control display area. Balance indicating/measuring switchgear /devices
installed on front door shall be identified by 18aluminium anodized legend plates by
adhesive of approved make on the front doors itself. No riveting for these items is
allowed on front door.
13.3 Danger Notice plate shall be screen printed or sticker shall be provided on front of the
lower panel door conforming to IS:2551-82 for 750V.
13.4 The switch board cabinet and its sub-assemblies shall be packed in suitable packing
material such as suitable sheets/bubble sheet and filling material as suited to protect the
various components and subassemblies to prevent damage in transport/storage. The
SBC shall be finally packed in a wooden case of sufficient strength, so that it can
withstand bumps and jerks encountered in road/rail journey.
14.0 GUARANTEE/WARRANTY
Guarantee/Warranty obligation of the complete Switch Board shall be as per IRS condition
of contract.
15.1 The contractor shall undertake to train, free of cost, the supervisors & staff of the Indian
Railways for operation, maintenance, fault finding, trouble shooting, repair of the offered
Switch Board Cabinet under the guidance of the skilled engineers as and when asked for
by Railways.
15.2 The manufacturer shall be required to make available the services of his engineers free of
cost to watch/monitor the performance of the equipment in service periodically and also
carry necessary repairs or replacement under warranty obligations. The necessary spares
needed for replacement during service should be available with the service engineers at all
the zonal Railways, Divisions Head Quarter & Production Units, Workshops and Coaching
Depot to cover entire Indian Railways network. The service engineers shall be fully
conversant with Switch Board Cabinet & its electrical circuitry.
16.1 Indian Railway shall not be responsible for infringement of patent rights arising due to
similarity in design, manufacturing process, use of similar components in design &
development of this item and any other factor not mentioned herein which may cause such
Prepared By Checked by
a dispute. The entire responsibility to settle any dispute/matters lies with the
manufacturer/supplier.
16.2 It shall be responsibility of firm to ensure that details/design/documents given by them are
not infringing any IPR and they are responsible in absolute and full measure instead of
Railways for any such violations. Data, specifications and other IP as generated out of
interaction with Railways shall not be unilaterally used without the consent of RDSO and
right of Railways/RDSO on such IP is acceptable to them.
The firm will not engage in cartel formation with other firms and will also submit a
declaration in this regard as per attached Annexure –A.
18.0 ANNEXURES
SN Annexure Description
1 Annexure A Undertaking against Cartel Formation.
2 Annexure B List of layout drawings
3 Annexure C List of wiring diagrams
4 Annexure D Bill of Material
5 Annexure E Particulars of connectors
6 Annexure F Schedule of cable sizes
7 Annexure G Technical requirements of aerosol fire detection and
suppression system.
8 Annexure H Technical requirements of hinges/locks/Accessories
9 Annexure I Temperature rise Scheme for guidance
10 Annexure J Modifications in Bill of Material of Annexure D with
suitable Switchgears (MPCB/MCB/Contactors) for LHB
GS AC Coaches
11 Annexure K Format for feedback given by user railways regarding
performance of set of electrical panels for LHB
EOG/HOG 3-tier economy class type and general type
AC coaches of Indian Railways
Prepared By Checked by
Annexure- A
We …………………………… are aware of the fact that the Registering Authority i.e. RDSO
may de-list the name of our firm from the Master List of Approved Vendors, if complaint is received
about such cartel formation from any of the Railways/Production Units.
Date:
Place:
Seal
Prepared By Checked by
Annexure-B
Prepared By Checked by
Annexure C
List of wiring diagrams for Set of panels
(On Board Cubicle and Under Slung cubicle)
Prepared By Checked by
Annexure- D
Bill of Material (BOM) for Set of panels
(On Board Cubicle and Under Slung cubicle)
Firm shall submit separate BOM for both cubicles with details of make & catalogue no. of
component actually used in prototype unit.
.
For abbreviations in columns refer drawing no. RDSO/PE/SK/0206236-20192021 (Rev.’0’).
S. Item Quan Drawing/Ca Place of
Gr Description Make
N Code tity talogue no. Installation
Disconnecting and
earthing device, 8pole ,
2 way, without OFF , on 74168SLB3 L&T- Salzer
load 125A at 1000V AC 2LOGBSS
, 2 NO+2NC and with O
heavy duty handle and
pad locking M137.0827
Schaltbau
arrangement in off 407.R1
1 12 S1 1 S1A2
position, mounted in a
stainless steel #Techno
enclosure, suitable for IS81210TT trends
AC 23 duty and 19L (#25%
conforming to IEC Quantity)
60947, Max depth #Kaycee
including handle 480 12580892A
(#25%
mm 34V49XE
Quantity)
2138903
2028003.1
Siba
25 (Link)
+ 2128001
(Holder)
* EFEN
* Ferraz
4182495
High voltage fuse (with (Link) +
F01 ETI
holder) net 1 and net 2 4132035
F02
Rated Current: 125 A, (Holder) S1F50
F03
2 12 Rated Voltage: 1000 V 6 to
F04
AC S1 F55
F05
Breaking Capacity: 125NH1LIR
F06
80kA -1000 + Eaton
SD1L-1000 Bussmann
Seimens
Prepared By Checked by
LC1D11500
Contactor for Net 1& 2, 46N5 +
Rated Voltage: 1000 V LA4DA2N +
AC, LADN22
Rated kVA - 100 at Schneider
rated voltage & 70° C
and utilization category
6 a. AF190B-
ABB
3 K01 40-22
Main Pole: 4 3RT13636A S1K01
12 2
Aux. contact: 2 NO + R36 S1K02
K02
2NC
Control Voltage: 415 V 3RT23461A
AC+/- 15%. V004AA0+3 Siemens
Breaking Current RH29111H
A11+3RT29
With surge suppressor 361BE00
MCX-34 L&T
S1T8
S1T9
RDSO
approved
source as
per RDSO
200 VA single phase, H specificatio
4 T8 class, insulation – 6 kV, n no.
12 2 Type-II
T9 750/415V control RDSO/PE/
transformer SPEC/AC/0
203-
2020(Rev-
0) for Type-
II
Prepared By Checked by
002621001
+00910002
ST30725
with HD32
Base L&T
SF90144+S
K91314
3NW60021(
Link)
Siemens
+3NW7013
(Holder)
OFFNF1G
G2+
1SYN8330
ABB
01R2005
E9F10GG2
+E91/32S
3SB50002A
B01+3SB54 Siemens
000E
EMNCSK1
L&T- Salzer
+EC1C
* TEKNIC
Power supply on/off XB5AD33N
6 12 S7 1 S1S01
Switch XB5AD21N
Schneider
+ZBE101N
+ZBE102N
M2SS2-
10B
ABB
+MCBH-00
+ MCB-10
3SB5000-
2DB01+3S Siemens
B5400-0A
EMNCSL1+
EC1C
L&T
Feeder selection Rotary 61069SCB
switch with marking “I-0- 03TDY
II” * TEKNIC
net1 – Local main K2F022QC
7 12 S1 supply – net 2 1 H S1S02
(change over switch XB5AD33N
with 0-position 3-pole) SCHNEIDE
+ZBE101N
Rated voltage 690 V AC R
+ZBE102N
Rated current 16 A
M3SS1-
10B
ABB
+MCBH-00
+ MCB-10
Fuse (with holder) for 60 3NA78300 S1F44
F10 kVA transformer RC + S1F45
Siemens
8 12 F11 (secondary) 6 3NH30300 S1F46
F12 Rated Current: 100 A, RC
Rated Voltage: 500 V OFAFN00G ABB SIF47
Prepared By Checked by
AC G100+ SIF48
Breaking Capacity: 1SCA8330 SIF49
100kA 01R2001
03919,
Wohner-
03760
* Italweber
* Eaton
100NHG00
0B –SB00- Bussman
PB
SF94942
L&T
+SK90405
* Ferraz
DIGITAL AMMETER WITH * L&T
LED DISPLAY SIZE 96 sq. * AE
Cm mm, MULTI LINE FOR * SOCOMEC
MEASURING INPUT * SIEMENS S1P1
9 12 P13 CURRENT R,Y&B 0- 600A 21 * SCHNEIDER
0-150A,CT-1A/5A * Y9-3A3 YOKINS
PROGRAMABLE WITH AUX
SUPPLY 24/110V DC, 4VA RISH DELTA
RISHABH
CLASS 1.0 3A
4NC5117-
0CC21
8PU92001 Siemens
AC211AE1-
3 Z
10 T2 Current transformer S1T2
CM-CT
12 T3 100A/1A :2.5VA:class1, ABB S1T3
100/1
T4 UN800V; 50 Hz S1T4
YOK-SR-
Yokins
21-100/1 *
CT20-
100/1A FANOX
414034
Bhasin
RC filter consist of 1 Packard
ohm, 6 W resistor NACEI
connected in series with AEL
parallel connected 1.5
RAMYAA
11 Micro Farad , 850 V S1RC1
RC1 Trolex
12 capacitor of Vishay or 2
RC2 ABROL
Epcos make in each S1RC2
NEC
arm of 415 V circuit
between phase to ISG
neutral and phase to Trinitron
earth circuit. Ask
Powertech
BASE)
* Wohner
* Ferraz
Voltage phase control DPC01DM1 Carlo
(MMR-Measuring KB001 Gavazzi
Monitoring Relay) BD9080.12/
K01 Dold S1K03
13 21 Net 1&2 2 003
K02 S1K04
3AC, 1000V * ABB
aux. Voltage 110 V * Phoenix
AC/DC SMB110 L&T-GIC
DIGITAL VOLTMETER WITH 2 * AE
LED DISPLAY, SIZE 96 sq.
cm mm, MULTI LINE FOR * SIEMENS
MEASURING RY,YB& BR.
INPUT VOLTAGE 800V L-L.
P01 WITH AUX SUPPLY * Y9-3V3 YOKINS S1P2
14 21
P02 24/110V DC. 4VA. S1P3
RISH DELTA RISHABH
CLASS:1.0 3V
* SOCOMEC
* L&T
CT-ARS.21
ABB
11S
3RP25401
Siemens
AW30
Drop out time delay DBB02CM2 Carlo
relay for Anti skid 4 Gavazzi
15 23 K01 true OFF delay 1 RE22R2KM S1K05
Schneider
control supply voltage R
110-240V AC/DC 23GDT0 L&T
MK7873N DOLD
ETD-BL-
Phoenix
1T-230-PT
* Luetze
3NA78100
RC+3NH30 Siemens
Fuse (with holder) for 300RC
battery circuit 03912, Wohner-
Rated Current: 25 A, 03760 Italweber
Rated Voltage: 500 V OFFNF1G
AC, G25 +
16 ABB S1F42
F01 Breaking Capacity: 1SYN8330
32 2 S1F43
F02 100kA, 01R2005
25NHG000
B + SB00- Eaton
PB
SF90152+S
L&T
K9114
* SIBA
* Ferraz
17 MCB for RBC 5SL43257R
32 01 Rated Current : 25 A, 1 C Siemens S1F160
Curve: CD, 5SL73258R
Prepared By Checked by
Accidental Emergency
32 F162
Light
50% Main Light
32 F39
passenger area
50% Main Light
32 F40
passenger area
Air conditioning
61 F35 Microprocessor
controller unit A1
32 F164 CCTV
32 F168 LED light for SBC
32 F169 Spare
BJB2016D
L&T
C
5SL52167R
Siemens
C
MCB 2 POLE 16 Amp A9N61531 Schneider
21 32 F163 for light contactor 1 S202MT- S1F163
S1K49 200 V DC C16UC
ABB
SB202-
C16DC
Eaton
FAZ-C16/2
Bussman
MCB 2 Pole, 406821/408
Legrand
Current rating: 10A, 823
Breaking capacity:10kA BJ2010DC L&T
Voltage rating: 200V 5SL5210-
DC, Siemens
6 7RC
for A9N61528 Schneider
(i) Power supply (F33) S202M-C 6
F33 (1 S1F33
(ii) Sanitary control DC SB202- ABB
F37 for S1F37
(F37) C10DC
F38, eac S1F38
22 (iii) Loud speaker FAZ-C10/2-
32 F165 h S1F165
system- /PIS (F38), DC PLS6- Eaton
F166 appl S1F166
(iv) Automatic sliding C10/2-DC
F167 icati S1F167
Door 1 rating 10
on)
Amp (F165)
(v) Automatic sliding S202MT-
Door 2 rating 10 C10UC
ABB
Amp (F166)
(vi) Infotainment system
rating 10 Amp
(F167)
CP-C.1
ABB
24/10
TRIO-PS-
2G/1AC
Phoenix
23 /24DC/10-
DC/DC converter 2903149
32 U1 1 S1U2.1
110V/24V, 240W, 10A KLEA240F-
COSEL
24
6EP13363B
Siemens
A10
ASK-CS- ASK
24V,10A Powertech
Prepared By Checked by
3SB5000-
Push button (Red) 110 0AC01+3S Siemens
V DC, dia. 22.5 mm B5400-0A
for switching OFF K49 EMNRFD1
Light contactor and for +EC1C L&T
checking AEL +EC2C
Emergency light unit M22-D-GR-
24
S09 X1/K10 ; S1S10
32 S10 2 LED-G + Eaton S1S09
S06 M22 ; S1S06
A+M22-K10
CP1-10
ABB
GR10
XB5AA42N
Schneider
+ NO/NC
* Yokins
* Teknic
3SB5000-
0AE01+3S Siemens
B5400-0A
* Teknic
EMNGFD1
+ EC1C + L&T
Push button(Green) to EC2C
switch on K49 Light M22-D-G-
25 S08 S1S08
32 contactor 110 V DC, Dia 1 X1/K10 ;
S07 S1S07
22.5 mm LED-G + Eaton
M22 ;
A+M22-K10
CP1-10G-
ABB
10
XB5AA31N
Schneider
+ NO/NC
* Yokins
3SB5000-
0AG01+3S Siemens
B5400-0A
XB5AA11N
Schneider
+ NO/NC
* Teknic
26 Push button (white)
S05 EMNWFD1 S1S05
32 for test Indication lamp 1
S11 + EC1C + L&T S1S11
110 V DC
EC2C
CP1-10W-
ABB
10
M22-DW-
Eaton
X1
* Yokins
27 MCBs for mobile/laptop 408592 Legrand
F98 charging circuit 5SL41167R S1F100
33 F99 Rated Current: 16 A, 3 Siemens S1F101
C
F100 Curve: C, S201MT- S1F102
Rated Voltage: 230 V ABB
C16
Prepared By Checked by
AC, SB201M-
Pole: 1 P, C16
Breaking Capacity: 10 BB10160C L&T
kA A9N1P16C Schneider
FAZ-C16 Eaton
408592 Legrand
Miniature Circuit S202MY-
Breaker (MCB) for C6
ABB
electrical socket: SB202M-
28
Rated Current: 6 A C6
33 F41 1 S1F41
Rated Voltage:230 V AC A9N2P06C Schneider
Pole: 2 P FAZ-C6/2 EATON
Breaking Capacity: 10 BB20060C L&T
kA 5SL42067R
SIEMENS
C
MCB for 5 KVA 408679 Legrand
transformer(secondary) 5SL4425-
for mobile/laptop Siemens
7RC
charging circuit S204MT-
Rated Current: 25 A, C25 SB204 ABB
29 33 F97 Curve: C, 1 M-C25 S1F106
Rated Voltage: 230 V BB40250C L&T
AC, A9N4P25C Schneider
Pole: 4 P,
Breaking Capacity: 10 FAZ-C25/4 Eaton
kA
408762 Legrand
MCB for 5 KVA
5SL73168R
transformer (primary) Siemens
C
Rated Current: 16 A,
30 Curve: D, S202MT-
33 F92 Rated Voltage: 415 V 1 D16 S1F107
ABB
AC SB203M-
Pole: 3 P, D16
Breaking Capacity: 10 BB30160D L&T
kA FAZ-D16/3 Eaton
A9N3P16D Schneider
AF116B-40 ABB
Contactor for Local main LC1D11500
supply 1 (K41) & Local 46P7
main supply 2 (K42) and +LADN22
K43, (230 V AC) Schneider
Rated Current: 95 A (at LC1D11500
rated voltage and AC-3 46M7/M5
31
K02 utilization category) +LA4DA2U S1K42
33 K03 Rated Voltage: 690 V 3 (220 V AC) S1K41
K08 AC MCX34 L&T S1K43
Main Pole: 4 3RT23461
Aux. contact: 2NO+1NC NP30 4AA0
Control Voltage: 230 V +
Siemens
+/-15% AC 3RH29111
HA10
With surge suppressor
Prepared By Checked by
RM22TR33
Schneider
BD 9080.12
DOLD
EMD-FL-
3V-400
MR-ES-3v- Phoenix
400
(1217805)
Prepared By Checked by
10kA +A9N26924
Pole: 3 P BB30160C
Rated Voltage : 415 V +AUX L&T
AC BZA11006
5SL43167R
C+55ST301 Siemens
0
Eaton
FAZ-C16/3
MS132-
2.5B+ HK1-
ABB
MPCB 11 MS116- S1F06
for condenser fan unit 2.5 S1F07
1.1 & 1.2, 2.1 & unit 2.2 GV2ME07 Schneider S1F12
Thermal release range: ST41895O S1F13
F10 L&T
Rated Current 1.6-2.5 A OOO
F11 4
36 33 Class: 10 PKZM01-
F16 no.
Breaking Capacity: 1.6 + NHI- Eaton
F17
50kA E-11-PKZ0
Pole: 3 P 3RV2011-
Rated Voltage: 415 V 1BA15
AC 1CA10+3R Siemens
V2901-1E
Prepared By Checked by
Prepared By Checked by
Pump1&2: CA4KN31F
Schneider
Contacts: 3 NO + 1 NC W3
Control Voltage: 77-143 3RH2131-
V DC 1BF40+3R
Siemens
Rated Voltage: 690 V T29161JL0
AC 0
Rated Current : 10A (at MO0DC L&T
rated voltage & AC-3
utilization category) * C&S
MPCB for Exhaust Fan MS132116-
1, 2 AND 3 WC MBS 25 0.63B, ABB
with auxilary contact HK1-11
(1NO+1NC) and GV2-
Schneider
terminal block ME04+GV-
And AE11
MPCB for water pump 1 3RV2011-
Q1 & 2 MBS 25 with aux. 0GA150 SIF85
Q2 contact: Siemens SIF86
45( +3RV2901-
33 Q3 53 1E SIF87
a)
Q4 Rated Voltage : 415 V PKZM01- S1F21
Q5 AC 0.63 + NHI- EATON S1F22
Rated Curent : 0.63 A E-11-PKZ0
Thermal release range:
0.4-0.63 A ST41892O
Class: 10 OOO
Breaking Capacity: L&T
+ST41945
50kA OOOO
Pole: 3 P
MS116-1.6,
ABB
HK1-11
MPCB for water pump
1&2 MBS 25 with aux. GV2-ME06
contact (1NO + 1NC) Schneider
+ GV-AE11
and terminal block.
3RV1011-
Rated Voltage : 415 V 1AA10 or
AC 3VU1340-
45( 0MG00 S1F21
33 Q1 Q2 Rated Current : 1.6 A 2
b) 1NO + S1F22
Thermal Release Seimens
Range: 0.4-0.63A Class 1NC:
10 3RV1901-
Breaking Capacity: 50 1A or
kA 3VU9131-
Pole: 3 P 3AA00
ST41894O
OOO
L&T
+ST41945
OOOO
33/F15 Miniature circuit breaker 5SL3067R
(MCB) for Exhaust fan 6 C
Siemens
33 Amp, Voltage rating: 5SL43067R
46 1 S1F15
415 V AC, 3 pole, C
Current rating: 6A,
BB30060C L&T
Breaking capacity: 10
Prepared By Checked by
KA
A9N3P06C Schneider
C Curve
S203MT-
ABB
C6
P01 DIGITAL AMMETER WITH 2 *
L&T
P02 LED DISPLAY SIZE 96 sq.
Cm mm, MULTI LINE FOR *
AE
MEASURING INPUT
CURRENT R,Y&B 0- 600A *
SOCOMEC
50-0-50A,CT-1A/5A
PROGRAMABLE WITH AUX *
SIEMENS S1P8
47 42 SUPPLY 24/110V DC, 4VA
* S1P9
CLASS 1.0 SCHNEIDER
* Y9-DA
YOKINS
RISH DELTA
3A RISH Rishabh
EINE+
DIGITAL VOLTMETER * AE
WITH LED DISPLAY,
SIZE 96SQ CM mm, * Muller+
MULTI LINE FOR Zeigler
48 42 P03 MEASURING RY, YB 1 * RISH EINE+ Rishabh S1P10
&BR. INPUT VOLTAGE * L&T
800V L-L 0-150V WITH * Y9-DV
AUX SUPPLY 24/110V Yokins
DC, 4VA CLASS: 1.0
For
(+ve)3SB50
00-0AF01
+
3SB54 00-
0A; For (-
Siemens
ve)
3SB5000-
0AC01
Push button +
Insulation test battery 3SB54 00-
49 S01 net , Red, dia 22.5 mm 0A S1S03
42 1
S02 XB5AA11N Schneider S1S04
blue for +ve insulation (White)
color and red for -ve
EMNRFD1
L&T
+EC1C+EC
2C
CP1-10R-
ABB
11
M22-D-
R+M 22- Eaton
A+M22-K01
H01 LED type indicator 1 3SB52 85 - Siemens/ S1H01
50 42
Net 1 OK 6HG04 of Group
Prepared By Checked by
Prepared By Checked by
Prepared By Checked by
compressor 2.2(F143),
heater 2 (F144)
Contactor (with diode) AF16ZB-
for ventilation fan unit 1 30-01 TAL
ABB
&2 16-30-10
Condenser CD 1.1, CD +RV5/250
1.2, CD 2.1 CD 2.2
K03 S1K26
Heater 1 & 2: LC1D18FD Schneider
K05 S1K28
Rated Current: 16 A (at
K12 S1K31
rated voltage & AC-3 MDX25 L&T
K13 S1K32
53 61 Utilization Category) 8
K17 S1K36
Rated Voltage: 690 V
K18 S1K37
AC
K16 3RT20181B S1K35
Main Pole: 3 NO
K21 F42+3RT29 Siemens S1K40
Aux contact: 1NC,
161JL00
Control Voltage: 77-143
V DC
Prepared By Checked by
4030
6EP33216S
Siemens
B100AY0
Auto-Manual Bye-pass 16A-D16-
Rotary switch for Air- 61031-B13-
L&T- Salzer
Front conditioning; FHYR
S1S15,
57 61 right Rated Current: 16 A, 2
S1S16
door Position: 3 (Auto,
Manual, Off), * Seimens
No. of Poles : 7
On/Off switch for Air- 61198 L&T- Salzer
conditioning; 3LD40012B
58 Front Rated Voltage: 110 V C000RC0
61 right DC +/-30% 1 S1S17
door Rated Current: 6 A, Siemens
Position : 2
(PU scope)
281-665/
Resistor (resistor clamp WAGO
281-663
at the X1.2) Air
59 Condition Humidity 5792641 Phoenix
61 R1 1 S1R2
circuit
* Weidmuller
10 kohm, +-1%,0.25W
* Connectwell*
281-
Resistor (resistor clamp 665/281- WAGO
at the X1.2) Air 559
Condition Humidity 5792640 Phoenix
60 61 R2 1 S1R3
circuit
1 kohm, +-1%,0.25W * Weidmuller
* Connectwell*
281-665/
WAGO
281-400 S1V1
V1 V2 Diode 1N4007 (diode
61 61 3 3037782 Phoenix S1V2
V3 clamp at the X1.2)
* Weidmuller S1V3
* Connectwell*
IR 140Y-4,
Contrel
Insulation control 110V RI-R22
AC Measuring range 1- * Bender
100 k Ohm Control * Woka
voltage 24-240 V CM-IWS.1S ABB
93 A1 AC/DC Output 1 1 Vigil S1A6
62
C/0(SPDT) Contact Ohm/IMD- Schneider
System leakage IM10
capacitance 10 Micro 3UG4581-
Farad SIEMENS
1AW301
IL 5880.12 DOLD
Insulation control 415V IR 470LY-
AC 21A, RI- Contrel
63 R138
93 A2 Rated voltage 0-500 V 1 S1A7
AC * Woka
Control voltage 24-240 * Bender
Prepared By Checked by
Nos D
For K44 contactor 415 V A9N1P032
AC D
For K43 LMS contactor
coil Schneider
cables or other
equivalent
With prior
approval of
RDSO
approved
source.
FP-100S FIREPRO/S
(Firepro), TAT-
100T (Stat- X/#Pyrogen
X), EXA1 Technology
(Pyrogen) Pvt. Ltd.
(#25%
4 3 Quantity)/
Fire suppression
piec DSPA BV
76 Cartridge
es (#25%
(100gm+100gm)
Quantity)As
per
Annexure G
and with
prior
approval of
RDSO
* Tyco
Computer generated
ferrules class R22/R23
in EN 45545-2 with HL- Phoenix
23 category (self-fire
extinguishing low smoke
& low toxicity)
Test report from EN
LOT MV Electro
certified lab for
77 systems
EN45545-2 HL-3 shall
be furnished by the firm
with supplied model no.
and company name at
the time of prototype L&T
and acceptance test. SALZER
Prepared By Checked by
With prior
approval of
Schematic laminated
RDSO
79 drawings in A0 Size to 1
be kept in each SBC
Note:
1. * Part number shall be decided at design approval stage before prototype manufacturing.
2. The part numbers mentioned in the above Bill of Material (BOM) are based on information
furnished by respective OEMs. Change of any shall be brought out at design approval
stage of prototype. The latest equivalent part no if required shall be submitted by firm with
technical details to RDSO for approval during prototype.
3. Firm has to obtain prior approval of part numbers at the design stage before use in
prototype SBC.
4. All contactors for RMPU motors shall be of AC-III utilization category.
5. Inspection agency will check all the components and maintain record for future reference.
6. The DIN rail used shall have minimum depth of 15mm.
7. All materials including switchgears (Contactors, MCB & MPCB) provided in SBC shall
conform to EN 45545 with hazard level HL-2, vibration shock to IEC 61373 and suitable to
work in temperature range -5°C to 70°C & relative humidity up to 98 % and suitable for
rolling stock application.
8. Stipulated current rating for all switchgears items shall be at rated voltage and specified
utilization category and at 70°C temperature.
9. Rated voltage for components used on 750 Volts AC & 415 Volts AC side shall be 1000
volts AC & 690 Volts AC respectively.
10. All auxiliary contacts to be suitable for 3Ampere inductive load& for 415 V AC.
11. All switchgears shall be accepted after verification of compliance for HL-2, vibration &
shock and stipulated rating on rated voltage at given utilization category on 70 Deg C as
per respective governing standards.
Prepared By Checked by
Annexure E
Prepared By Checked by
Annexure-F
Note:- 1. Red Yellow Blue & black colour shall be used for 750 V, 415 V ,110 V AC cable
R,Y,B & N respectively.
Prepared By Checked by
Annexure-G
1 Type of system - Thermal type & suitable for fires arising out of electrical abnormalities
(Class E fire).
3 The aerosol generator should be UL-2775 or ISO 15779 certified and certificate from 3rd
party to be furnished at the time of inspection of Switch board cabinet.
7 System shall not require any battery/electric supply for operation. However, if battery
required that should be with 10 years life.
8 System with mounting arrangements shall be suitable for installation in switch board
cabinet (Electrical panel) installed on Railway passenger coach (non passenger area).
Prepared By Checked by
Annexure-H
Technical requirements of hinges/locks/Accessories
Prepared By Checked by
1. Material:-
- Frame part & Door part:- SS-
304 / SS-304L (AISI 304) /
ASTM276
-Sleeve cover:- Stainless steel
AISI 304, 1.4301 (X5CrNi1810)
2. Surface finish:-
- Frame part & Door part:-
Vibro finish.
- Sleeve cover:- Glossy finish.
3. Shock & Vibration proof:-
IEC 61373 -2010. 379-
Lift off
4. Life Cycle:- Min 50,000 0569.04-
2 hinge
mechanical cycles. 09001 of
55mm
5. Load bearing capacity:- Dirak
500N*
6. Applications:-
-180° Profile Hinge, screw-on
or weld-on.
-RH / LH application.
-180° Opening angle.
-Door is lift-off.
-RoHS / WEEE.
-Hinges will have smooth
movement without any rattle
sound, jerks & vibration.
1. Material:- - Hinge part:- SS-
304 (S22-1) -Pin:- Stainless
steel AISI 303, 1.4305
(X8CrNiS189)
2. Surface finish:- - Hinge
part:- E-Polish.
3. Shock & Vibration proof:-
IEC 61373 -2010.
4. Life Cycle:- Min 50,000
mechanical cycles.
5. Load bearing capacity:- 200N
6. Applications:- -180° 354-
Opening angle.. -RH / LH 2160.04-
3.a Mini hinge
application. -RoHS / WEEE. - 00000 of
Adjustments are possible with Dirak
respective bores provided. -For
nested doors. -Hinges will have
smooth movement without any
rattle sound, jerks & vibration.
Prepared By Checked by
Prepared By Checked by
Prepared By Checked by
1. Material:-
- Finger pull:- SS-304 / AISI
304 ASTM A240M -1 5
2. Colour:-
- Finger pull:- Vibro finish.
3. Applications:- 370-
Finger pull
-For head Ø28m. 0447.04-
6 for snap
-Thickness 2mm. 04703 of
lock
-The finger pull shall be Dirak
ergonimic to operate and should
not deform.
-By using a finger pull the H-
dimension changes by 2mm.
-RoHS / WEEE.
1. Material:-
- Edge protection: EPDM
EN45545-2, HL3.
- Material RoHS / WEEE
compliant.
2. Applications / Advantages:-
-Edge protections are used
when steel edges have to be
370-
Edge smooth.
0395.05-
7 protection -Additional metal machining
A4778 of
gasket work can be avoided and an
Dirak
decorative effect is achieved.
-Clamping range:- 1 to 2mm.
-Temperature stability:- -40° C
to +100° C.
-Hardness:- 70+/- 5 Shore A.
-Tensile strength:- ≥7.0Mpa
-Elongation at break:- 250 ~
550%
3-Point locking with wing handle
8
Prepared By Checked by
1. Material:-
- Wing handle:- SS-304 /
ASTM276
2. Colour:-
- Surface finish:- E-Polish
3. Shock & Vibration proof:-
IEC 61373 -2010.
4. Life Cycle:- Min 50,000
mechanical cycles (opening &
closing) at 50N compressive load
(i,e Wing knob + Rod latch).
5. Applications:-
-Wing knob for use with rod 352-
Wing
latch system. 2199.04-
8.1 handle with
-All handles are supplied with 00000 of
key
2pcs of 1333 keys. Dirak
-Mounting screws are included.
-Door-thickness 1 - 2.5mm
-RoHS / WEEE
-Wing knob will have smooth
movement without any rattle
sound, jerks & vibration.
Prepared By Checked by
1. Material:-
- Housing :- SS-316 / 1.4401 (X
5 CrNiMo 1712 2)
- Pinion :- AISI 316 SINTERED
METAL D40 (X 5 CrNiMo 1712 2)
- Flat rod:- AISI 304 / 1.4301
(X5CrNi1810).
- Rod stub:- AISI 304 / 1.4301
(X5CrNi1810).
2. Surface fnish:-
- Houising:- PASSIVATED TO
EN 2516 C1.
- Flat rod:- PASSIVATED TO
EN 2516 C1.
3. Both shells are sealed for
Non-Visible of internal
mechanism (i,e bearing). 208-
4. Applications:- 9025.00-
8.2 Rod latch
-For cutout A 25x50mm. 00000 of
-Stroke 24mm. Dirak
-RoHS / WEEE.
-Installation with or without
cam.
-For application within the
sealed area.
-Can also be used outside the
seal in edge area.
-RH or LH application through
double symmetry.
-Rod latch will have smooth
movement without any rattle
sound, jerks & vibration.
1. Material:-
-Round rod:- AISI 304 ASTM A
276.
2. Surface finish:-
- Round rod:- Vibro finish
Round rod 3. Applications:- 201-
8.3 (Quantity 2 -RoHS / WEEE. 0112.04
Nos.) of Dirak
Prepared By Checked by
1. Material:-
- Clip-on gasket
- Material EPDM EN45545-2,
HL3.
RoHS / WEEE compliant.
2. Applications / Advantages: -
- Clip-on gasket are used for IP
65.
-Clamping range: - 1 to 3.5mm. 370-
Clip-on -Temperature stability: - -40° C 0563.05-
9
gasket to +100° C. A4784 of
-Hardness of clipping part of Dirak
gasket :- 70+/- 5 Shore A.
Side Bulb Density: 0.6+ 0.1g/cm3
-Tensile strength of clipping
part of gasket: - ≥7.0Mpa
-Elongation at break for clipping
part of gasket :- 250 ~ 550%
Note: The Test report of the mentioned parameters needs to be submitted from NABL
Accredited/Govt. recognised/ILAC (International Laboratory Accreditation Co-operation)
accredited Laboratory before finalisation of part no. of other approved make by RDSO.
Prepared By Checked by
Annexure-I
Temperature rise test scheme for guidance
Time 10:00 11:00 12:00 13:00 14:00 15.00 15.30 16.00 16.30 1700
SN Temp. on
1 Amb. Temp.
2 Earth Device
3 Panel inside (OB)
4 Panel inside (US)
5 S1F150
6 S1F151
7 S1F152
8 S1F153
9 S1F154
10 S1F155
11 S1K02
12 S1K01
13 S1K44
14 S1K43
15 S1K41
16 S1F44
17 S1F46
18 S1F48
19 S1F02
20 S1F09
Prepared By Checked by
21 S1F13
22 S1F14
23 S1F106
24 S1K35
25 S1K26
26 S1F160
27 S1K40
28 S1F120
29 S1F124
30 S1F33 (DC)
31 S1F163 (DC)
32 S1F24 (DC)
Prepared By Checked by
Annexure J
Prepared By Checked by
Prepared By Checked by
Annexure- K
Prepared By Checked by
DISTRIBUTION LIST
Prepared By Checked by