Fuzhou Tianyu Electric Co., LTD.: KYN31-24 Armored Metal-Enclosed Switchgear
Fuzhou Tianyu Electric Co., LTD.: KYN31-24 Armored Metal-Enclosed Switchgear
Switchgear
Contents
Product Introduction....…………….2
Technical Parameters.....……………3
Ordering Instructions....…………….20
1
天宇电气
TIANYU ELECTRIC
1 Overview
The KYN31-24 armored metal-enclosed switchgear (hereinafter referred to as the "switch cabinet")
complies with the Alternating-current Metal-enclosed Switchgear and Controlgear for Rated Voltages above 3.6
kV and Up to and Including 40.5 kV (GB 3906-2006) and the power industry standard, Indoor AC High Voltage
Switchgear Panel (DL/404-1997), with full reference to High-voltage Switchgear and Controlgear -
Metal-enclosed Switchgear and Controlgear for Rated Voltages above 1 kV and up to and including 52 kV (IEC
62271-200: 2003). This switch cabinet is a complete package of indoor power distribution equipment for the
three-phase AC 50Hz single busbar and single busbar subsection system, which is used to receive and distribute
the 24kV network power, and control, protect and monitor the circuit.
This type of switch cabinet features the functions of preventing misoperation of circuit breakers, preventing
pushing and pulling removable parts with load, preventing closing grounding switch with electricity, preventing
sending electricity by grounding switch at grounding position, and preventing entry into the live bay, which is
known as "Five Preventions".
2 Conditions of Operating Environment
a) Ambient temperature: the upper limit is +40°C, the lower limit is -15°C, and the daily temperature
difference shall not be higher than 15K;
b) Relative humidity: daily mean value not more than 95%, and monthly mean value not more than 90%;
c) Altitude not exceeding 1000m;
d) Seismic intensity scale: not higher than M8;
e) Places without any risk of fire, explosion and violent vibration.
Note: If the operating environment conditions are different from what is specified in the above
regulations, the user should consult with the manufacturer.
3 Product Model and Explanation
K Y N 31-24 ( ) / □□-□
Rated short-circuit breaking current (kA)
Rated current (A)
Operating mechanism type: electromagnetic
operating mechanism D
Spring operating mechanism T
Main switch type
Rated voltage, kV
Serial number designed
For indoor use
Removable type
Armored Metal Enclosed Switchgear
2
天宇电气
TIANYU ELECTRIC
3
天宇电气
TIANYU ELECTRIC
4
天宇电气
TIANYU ELECTRIC
Table 5 Technical Data of Fuse
Time-limited current
Rated Maximum Rated
Rated current of fuse peak value of breaking
Model voltage breaking current
A limit short-circuit
kV current kA A
current (kA)
XRNP-24 24 40 2 0.5, 1, 2, 3.15
XRNT-2 6.3, 10, 16, 25, 31.5, 40,
24 40 100
4 50, 63, 80
Table 6 Main Technical Parameters of AC Silicon Rubber Insulated Gapless Zinc Oxide
Arrester
Residu
Lightn
Nomina al Operati
ing 2ms
DC 1mA l voltage ng
Rated Continu impuls square
System Reference discharg under impuls
voltage ous e wave
rated voltage e steep e
Model of running residua flow
voltage kV current slope residua
arrester voltage l capacit
kV (peak kA impuls l
kV kV voltag y
value) (Peak e voltage
e A
value) current ≤kV
≤kV
≤kV
YH10W-24/68 20 24 19.2 34.4 68 78.2 250
5
天宇电气
TIANYU ELECTRIC
Scheme No. 01 02 03 04 05
Scheme
Scheme No. 06 07 08 09 10
Scheme
Scheme No. 11 12 13 14 15
Scheme
Remarks
Scheme No. 17 18 19 20 16
Scheme
BW 10.5
3
M -12-1W
ain
XRNP-24 3 3 3
eq
JDZ11-20 or
uip
JDZX11-20 or 2 3
me
JDZX11-20G
nt
YH10W-24/6
3 3 3
8
Remarks
7
天宇电气
TIANYU ELECTRIC
Scheme No. 21 22 33 34 25
Scheme
Scheme No. 28 29 30
Scheme
8
天宇电气
TIANYU ELECTRIC
Scheme No. 31 32 35 36 37
Scheme (JN7)
Scheme No. 41 42 43 44
Scheme
9
天宇电气
TIANYU ELECTRIC
Scheme No. 45 46 47 48 49
Scheme
Scheme No. 50 51 52 54 55
Scheme
10
天宇电气
TIANYU ELECTRIC
2435
2350
1830 1000
See Fig. 1 ~ Fig. 3 for the outline and internal structure of the switch cabinet.
Fig. 1 Schematic Diagram of Overall Dimensions of Switch Cabinet
11
天宇电气
TIANYU ELECTRIC
During the pushing or pulling, the interlocking mechanism must be operated. When the circuit breaker is in the
closing state, the removable parts cannot swing in and out.
6.3 Compartment of removable parts and valves
The compartment of removable parts is in front of the switch cabinet. The primary isolation contact box is
located on the rear blanking plate of the compartment of removable parts, and the operating connecting rod of the
grounding switch passes through the right side of the compartment.
The valve is made of metal steel plates and installed on the rear blanking plate of the compartment of
removable parts. When the removable parts advance to the working position, the valve opens automatically. When
retreating to the isolation or test position, the valve will automatically close. The upper and lower valves can be
opened or closed independently.
12
天宇电气
TIANYU ELECTRIC
1 2 3 4 5 6 7 8
23
22
21 10
20
11
19
12
18
13
17
16 15 14
13
天宇电气
TIANYU ELECTRIC
2 3 4 5 6
1
17 7
16
8
15
9
14
10
13
11
12
14
天宇电气
TIANYU ELECTRIC
15
天宇电气
TIANYU ELECTRIC
the car.
6.10 Instrument door and relay compartment
The instrument door and relay compartment shall be located at the upper part of the switch cabinet for
installing instruments, relays and other secondary equipment.
6.11 Secondary terminal compartment
The terminal compartment for internal wiring of the switch cabinet shall be located at the bottom of relay
compartment, and about 150 SAK terminals can be installed inside.
6.12 Pressure relief device
Pressure relief devices are provided above the compartment of removable parts, busbar compartment and
cable compartment of the switch cabinet to release pressure and discharge gas in case of failure of circuit breaker
or busbar and cable compartment, so as to ensure the safe operation of the switch cabinet.
6.13 Insulation
The main circuit of the switch cabinet is air insulated, and partial composite insulation is adopted.
16
天宇电气
TIANYU ELECTRIC
1 2 3 4 5 6
7
9
22
10
21 11
20
12
19
18
13
17
16 15 14
17
天宇电气
TIANYU ELECTRIC
18
天宇电气
TIANYU ELECTRIC
2350
19
天宇电气
TIANYU ELECTRIC
Fig. 8 Schematic Diagram of Overhead Busbar Directly Overlapping Bridge Exit Surface and Wall
9 Ordering Instructions
It is necessary for the user to provide the following information at the time of ordering:
a) The primary wiring diagram of main wiring shall indicate the model of the cabinets, number of main
wiring scheme, rated voltage, current and models and specifications of main electrical components, such
as current and voltage transformer ratio and accurate level;
b) For the layout plan of inflatable cabinet, if the busbar bridge or non-standard cabinet or attached cabinet
is to be ordered, its overall dimensions and technical requirements should be marked;
c) Schematic diagram and terminal diagram of secondary circuit. When the standard atlas is used, please
indicate the scheme number, the voltage value of the control circuit, as well as the model and parameters
of the variable secondary devices.
Note: If it is necessary to select the modified primary line scheme, such request should be put forward
at the time of ordering and negotiated.
20
天宇电气
TIANYU ELECTRIC
21