Solved Examples Based On Draft IS875pt.3-2nd Ed
Solved Examples Based On Draft IS875pt.3-2nd Ed
Prepared by
Er.(Dr) Abhay Gupta (Ex. 1-26)
Director, Skeleton Consultants P. Ltd. NOIDA-201301
Reviewed by
Prof. Prem Krishna
= 0o
10 m 5m
50 m
Fig. 1.1
OR
0.8 0.4 1.3 0.9
=
E G E G
0.5 0.5
For 90o wind incidence, for E/G (End Zone)
0.8 0.3
EG = EG
0.5
OR
0.8 1.3
=
EG EG
0.5
o
For 0 wind incidence, for F/H (Mid Zone)
OR
0.8 0.4
1.3 0.9
=
F H F H
0.5 0.5
For 90o wind incidence, for F/H (Mid Zone)
0.4 0.1
FH = FH
0.5
OR
0.4 0.9
=
FH FH
0.5
Example-2: Wind Pressure and Forces on a Rectangular Clad
Building with Parapet & Overhangs: Flat Roof
Problem Statement:
What difference will occur if the building in Ex.1 has 1.5m overhangs and 1m high parapets, as shown in
figure 2.1?
= 0o
1m
10 m
5m
50 m
Fig. 2.1
OR
0.8 0.4 1.3 0.9
=
E G E G
0.5 0.5
For 90o wind incidence, for E/G (End Zone)
0.8 0.3
EG = EG
0.5
OR
0.8 1.3
=
EG EG
0.5
o
For 0 wind incidence, for F/H (Mid Zone)
OR
0.8 0.4
1.3 0.9
=
F H F H
0.5 0.5
For 90o wind incidence, for F/H (Mid Zone)
0.4 0.1
FH = FH
0.5
OR
0.4 0.9
=
FH FH
0.5
Example 3: Wind Pressure and Forces on a Rectangular Clad
Building: Taller with Flat Roof.
Problem Statement:
What difference will occur if the height of building in Ex.1 is 18m and it is to be used for a cold storage?
The structure consists of RC column-beam frame at 5mc/c horizontally and 3m c/c vertically, supporting the
wall. The Building has a flat roof with beams at 5m c/c. The building has 40 openings 1.5 m 1.5m.
18 m
10 m
50 m
Fig. 3.1
0.9 0.7
EG =
EG
0.2
or
0.9 1.1
=
EG EG
0.2
For 0o wind incidence, for F/H (Mid Zone)
0.7 0.5
FH =
FH
0.2
0.7
0.9
=
FH FH
0.2
Example 4:Wind Pressure and Forces on a Rectangular Clad
Building: Pitched Roof
Problem Statement:
Calculate wind pressures and design forces on walls and roof of a rectangular clad building with
pitched roof, having plan dimensions 10m50m and height 5m, as shown in figure-4.1. The building
is situated in Dhanbad (Bihar) in an industrial area 500m inside open land on a fairly level
topography. Walls of building have 20 openings of 1.5m1.5m size. The roof is of GC sheeting & the
roof angle is 150. Calculate also the local wind pressures on roof & wall cladding. The columns &
trusses are at 5m c/c, longitudinally, purlins are at 1.4m c/c and columns at Gable ends are at 5m c/c.
= 0o
10 m 5m
50 m
Fig. – 4.1
0.5 0.5
OR
0.8 0.4 0.3 0.1
0.5 0.5
0.5 0.5
OR
0.75 0.75 0.25 0.25
0.5 0.5
0.5 0.5
OR
0.8 0.4 0.3 0.1
0.5 0.5
0.5 0.5
OR
0.6 0.6 0.1 0.1
0.5 0.5
Example 5 - Wind Pressure and Forces on a Rectangular Clad Taller
Building with Pitched Roof
Problem Statement:
What difference will occur if the height of the building in Example 4 is 18m and it has 40 openings of
1.5m1.5m size as shown in figure 5.1?
= 0o
18 m
10 m
50 m
Fig. – 5.1
Solution:
Wind Data: Wind Directionality factor Kd = 0.90
1. Dhanbad is situated in Zone II at the boundary of (IS:875-pt.3, Sec 6.2.1
Zone II & Zone IV. For such places higher Zone is Area Averaging factor Ka:
recommended. Therefore, (IS:875-pt.3, Sec 6.2.2, Table-4)
Wind Zone: Zone IV (Vb= 47 m/s) Tributary area for columns = 5 18 = 90m2
(IS:875-pt.3, Sec 5.2) ===============================0.813
2. Terrain category: Tributary area for Trusses = 25.176 5= 51.76m2
Transition from Category 1 (open land) to Category ============================== 0.864
2 (open land with few structures of low height) Tributary area for Purlins = 1.4 5 = 7.0m2
(IS:875-pt.3, Sec 5.3.2.1) ================================ 1.0
Note: A combined wind speed profile is to be worked Tributary area of short walls for design of wind
out as per Appendix – B ((IS:875-pt.3, Sec 5.3.2.4) but
braces in plan = 10 18 + 0.5 10 1.34 =
since height of boundary layer developed after 500m
fetch length is more than building height of 18m, only 186.7m2 ======================== 0.80
effects due to Terrain Category 2 are to be considered. A
combined profile would be needed in case of taller Permeability of the Building:
structures. Area of all the walls = 18 (210+250) = 2160 m2
Area of all the openings = 401.51.5 = 90 m2
Design Factors: % opening area = 4.166 %, less than 5%
Risk Coefficient factor k1 = 1.00 Hence the building is of low permeability.
(IS:875-pt.3, Sec 5.3.1, Table-1) (IS:875-pt.3, Sec 6.3.2.2)
Terrain & Height factor k2: Varies with height, as
given Table 5.1 Design Wind Pressure
(IS:875-pt.3, Sec 5.3.2.2, Table-2)
Design Wind Speed = VZ = Vbk1k2k3k4 =
Topography factor k3 = 1.00
(IS:875-pt.3, Sec 5.3.3.1) 471.0 k21.01.0 = (47 k2) m/s
Importance Factor for Cyclonic Region k4 = 1.00 (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.4) pZ = 0.6 (VZ)2 & pd = pZ KdKa
(IS:875-pt.3, Sec 5.4 & Sec 6.2)
Table 5.1 Table 5.3
Calculations of variation in design wind speed & Angle of Incidence 0o 90o
pressure with height Wall – A + 0.7 - 0.5
Wall – B - 0.4 - 0.5
Height from k2 VZ pZ pd Wall – C - 0.7 + 0.8
Ground, m m/s kN/m2 column truss purlin Wall – D - 0.7 - 0.1
Up to 10m 1.00 47.00 1.325 0.970 --- --- 1
: Since the pressure coefficients are given only for
15m 1.05 49.35 1.461 1.069 --- --- buildings with l/w ratio up to 4, for longer buildings
18m 1.07+ 50.20 1.512 1.106 1.176 1.361 i.e. l/w > 4, at present values up to 4 are being used.
0.2 0.2
OR
0.75 0.6 0.55 0.4
0.2 0.2
0.2 0.2
OR
0.8 0.8 0.6 0.6
0.2 0.2
0.2 0.2
OR
0.75 0.6 0.55 0.4
0.2 0.2
0.2 0.2
OR
0.8 0.8 0.6 0.6
0.2 0.2
Example 6 - Wind Pressure and Forces on a Rectangular Clad
Pitched Roof Short Building in Coastal Region
Problem Statement:
What difference will occur if the building in Example 4 is an industrial building situated in
Vishkhapattanam (Andhra Pradesh) near seacoast?
= 0o
10 m 5m
50 m
Fig. – 6.1
Solution:
Wind Data: Tributary area of short walls for design of wind
braces in plan = 10 5 + 0.5 101.34 =56.7 m2
1.Wind Zone: Zone V (Vb= 50m/s)---------
(IS:875-pt. 3, Sec 5.2) =========================== 0.858
Note: Vishakhapattanam is situated near seacoast in * : use 1.15 for Industrial structures
Zone V. For such places special importance factor for Permeability of the Building:
cyclonic region is to be used. Area of all the walls
(IS:875-pt. 3, Fig. 1) = 5 (210 + 250) + 20.51.3410 = 613.4 m2
Area of all the openings
2. Terrain category: for open seacoast
= 201.51.5 = 45 m2
conditions, use Category 1----
% opening area = 7.336 %, between 5% and 20%.
(IS:875-pt. 3, Sec 5.3.2.1)
Hence the building is of medium permeability.
Design Factors:
(IS:875-pt.3, Sec 6.3.2.2)
Risk Coefficient factor ‘k1’ = 1.00
(IS:875-pt.3, Sec 5.3.1, Table-1) Design Wind Pressure
Terrain & Height factor‘k2’ = 1.05 Design Wind Speed = VZ =Vbk1k2k3k4 =
(IS:875-pt.3, Sec 5.3.2.2, Table-2) 501.01.051.01.15 = 60.375 m/s
0.5 0.5
OR
0.8 0.4 0.3 0.1
0.5 0.5
o
For End Zone E/G; 90 wind incidence
0.5 0.5
OR
0.75 0.75 0.25 0.25
0.5 0.5
For Mid Zone F/H; 0o wind incidence
0.5 0.5
OR
0.5 0.5
0.5 0.5
OR
0.6 0.6 0.1 0.1
0.5 0.5
Example 7 - Wind Pressure and Forces on a Rectangular Partially
Clad Building: Pitched Roof
Problem Statement:
What difference will occur if the walls of the building in Example 4 is half clad in upper part and
half open as shown in figure 7.1?
Cladding = 0o
2.5 m
2.5 m
10 m
50 m
Fig. – 7.1
Solution:
Wind Data: Tributary area for Trusses =2 5.176 5 =
Dhanbad is situated in Zone II at the boundary of 51.76m2
Zone II & Zone IV. For such places higher Zone ============================= 0.864
is recommended. Therefore, Tributary area for Purlins = 1.4 5 = 7.0 m2
Wind Zone: Zone IV (Vb= 47 m/s) ============================= 1.0
(IS:875-pt.3, Sec 5.2) Tributary area of short walls for design of wind
braces in plan= 10 2.5 + 0.5 101.34 =31.7 m2
2. Terrain category: Transition from Category 1 to =========================== 0.891
Category 2. (IS:875-pt.3, Sec 6.2.2, Table-4)
(IS:875-pt.3, Sec 5.3.2.1)
Permeability of the Building:
Note: A combined wind speed profile is to be worked Since the walls are half open, the building comes
out as per Appendix – B (Sec 5.3.2.4) but since height under the category of large openings and analysis
of boundary layer developed after 500m fetch length is
is to be carried out as per Section 6.3.2.2. As per
more than building height of 5m, only effects due to
Terrain Category 2 are to be considered. A combined para 1 of section 6.3.2.2 use more than 20%
profile would be needed in case of tall structures. opening clause and consider 0.7 internal
pressure on walls and roof.
Design Factors:
Risk Coefficient factor ‘k1’ = 1.00 Design Wind Pressure:
(IS:875-pt.3, Sec 5.3.1, Table-1) Design Wind Speed = VZ = Vbk1k2k3k4 =
Terrain & Height factor ‘k2’ = 1.00 471.01.01.01.0 = 47.00 m/s
(IS:875-pt.3, Sec 5.3.2.2, Table-2) (IS:875-pt.3, Sec 5.3)
Topography factor ‘k3’ = 1.00 pZ = 0.6 (VZ)2 = 0.6 (47.00)2 = 1325.4 N/m2
(IS:875-pt.3, Sec 5.3.3.1) (IS:875-pt.3, Sec 6.2)
pd = pZ KdKa = 1.32540.9 Ka
Importance Factor for Cyclonic Region
‘k4’= 1.00 = 1.193Ka kN/m2
(IS:875-pt.3, Sec 5.3.4) (IS:875-pt.3, Sec6.2)
Wind Directionality factor ‘Kd’ = 0.90 For various members and components, use proper
(IS:875-pt.3, Sec 6.1.1) value of Ka, as above. Refer note below Sec. 5.3
Area Averaging factor Ka for buildings less than 10m height, while making
(IS:875-pt.3, Sec 6.1.2, Table-4) stability calculations and design of the frame.
Tributary area for columns = 5 2.5 = 12.5 m2 Wind Load Calculations:
============================= 0.983 F = (Cpe-Cpi) A pd = CpnetA pd
(IS:875-pt.3, Sec 6.3.1)
Internal Pressure Coefficient Cpi = 0.7 Local pressure coefficients for the design of
claddings and fasteners:
External Pressure Coefficients: Refer Table 6 of IS-875 for Roof Angle = 150
Using the Table 6 with roof angle 15o Local Cpe for eaves portion in end zone: NA
For h/w = 0.5, pressure coefficients are tabulated Local Cpe for eaves portion in mid zone:NA
below (refer figure below Table 6 of code) Local Cpe for ridge portion: -1.2
Local Cpe for gable edges: -1.2
Table 7-1 Local Cpe for corners of walls: -0.6
Portion of roof Wind Incidence Angle
0o 90o Therefore Max. local Cpnet for roof at the edges
E -0.8 -0.75 and the ridge = -1.2 – (+0.7) = -1.9
F -0.8 -0.6 Likewise at the wall edges = -0.6 – (+0.7) = -1.3
G -0.4 -0.75 However, for the use of the local pressure
H -0.4 -0.6 coefficients, the design pressure pd will be
Design Pressure Coefficients for Roof: computed with Ka = 1. Therefore, pd = 1.3254
Positive internal pressure will act towards the roof 0.9 = 1.193 kN/m2
while negative internal pressure will be away
from the roof. Hence +ve internal pressure will be Zone of local coefficients = 0.1510 = 1.5m, at
added to –ve external pressure coefficient and ridges, eaves and gable ends & 0.2510 = 2.5m
vice-a-versa. The combinations will have to be for wall corners. In this region the cladding and
made separately for zones E, F, G, H etc., as in fasteners shall be checked for increased force.
figure 7.2. (IS:875-pt.3, Table-5)
Design Pressure Coefficients for Walls: Calculations of Force due to Frictional Drag:
Refer Table 5 of code: h/w = 0.5, and l/w = 5 (IS:875-pt.3, Sec 6.4.1)
therefore Cpe for walls* This will act in the longitudinal direction of the
building along the wind. Here h<b, therefore, first
Table 7-2 equation will be used & Cf’ = 0.02. This will be
Angle of Incidence 0o 90o added to the wind force on gable walls. Ka for
Wall – A +0.7 - 0.5 roof and walls is 0.8, as area is more than 100m2.
Wall – B - 0.25 - 0.5
Wall – C - 0.6 + 0.7
Wall – D - 0.6 - 0.1
*: Since the pressure coefficients are given only for
buildings with l/w ratio up to 4, for longer buildings
i.e. l/w > 4, at present values up to 4 are being used.
These will be combined with internal pressure
coefficients as earlier, equal to Cpi = 0.7
Cpnet for Walls A or B = 0.7 – (-0.7) = +1.4,
pressure
= -0.5 – (+0.7) = -1.2, suction
Cpnet for Walls C or D = 0.7 – (-0.7) = +1.4,
pressure
= -0.6 – (+0.7) = -1.3, suction
Figure 7.2 - Net Roof Pressure Coefficients for different zones and combinations
0.7 0.7
0.7 0.7
0.7 0.7
= 0o
1m 1m
10o
1m
10 m
50 m
5m
Fig. – 8.1
Solution:
Wind Data: Tributary area for columns = 5 6.76 = 33.81 m2
Dhanbad is situated in Zone II at the boundary of = 0.888
Zone II & Zone IV. For such places higher Zone Tributary area for Trusses =12.19 5=60.95m2
is recommended. Therefore, = 0.852
Wind Zone: Zone IV (Vb= 47 m/s) Tributary area for Purlins = 1.4 5 = 7.0 m2 =
(IS:875-pt.3, Sec 5.2) 1.0
2. Terrain category: Transition from Category 1 to Tributary area of short walls for design of wind
Category 2. braces in plan
(IS:875-pt.3, Sec 5.3.2.1) = 10 5 + 0.5 10 1.76 = 58.8 m2 = 0.855
Note: A combined wind speed profile is to be worked Permeability of the Building:
out as per Appendix – B (IS:875-pt.3, Sec 5.3.2.4) but
since height of boundary layer developed after 500m
Area of all the walls = 5 (210 + 250) +
fetch length is more than building height of 5m, only 0.51.7610 + 1.7650 = 696.8 m2
effects due to Terrain Category 2 are to be considered. Area of all the openings = 201.51.5 = 45 m2
A combined profile would be needed in case of tall % opening area = 6.458 %, between 5% and 20%
structures. Hence the building is of medium permeability
Design Factors:
Risk Coefficient factor ‘k1’ = 1.00 (IS:875-pt.3, Sec 6.3.2.2)
(IS:875-pt.3, Sec 5.3.1,Table-1) Design Wind Pressure
Terrain & Height factor ‘k2’ = 1.00 Design Wind Speed = VZ = Vbk1k2k3k4
(IS:875-pt.3, Sec 5.3.2.2, Table-2) = 471.01.01.01.0 = 47.00 m/s
Topography factor ‘k3’ = 1.00 (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.3.1) pZ = 0.6 (VZ) = 0.6 (47.00) = 1325.4 N/m2
2 2
Table 8-3
Roof side ↓ Wind angle-- 0o 90o 180o 270o
Above wall A (higher end) +0.75 -0.50 -0.25 -0.50
Above wall B (Lower end) -0.25 -0.50 +1.25 -0.50
Above wall C (gable end) -0.60 +1.00 -0.60 -0.10
Above wall D (gable end) -0.60 -0.10 -0.60 +1.00
(Refer Clause 6.3.3.5 & Table 5)
Design Pressure Coefficients for Roof: These will be combined with internal pressure
coefficients as earlier, equal to Cpi = 0.5
Table 8-1 Cpnet for Walls A or B = 0.7 – (-0.5) = +1.2,
Portion of Wind Incidence Angle pressure = -0.5 – (+0.5) = -1.0, suction
Roof 0o 45o 90o 135o 180o Cpnet for Walls C or D = 0.7 – (-0.5) = +1.2,
Windward -1.0 -1.0 -1.0/ -0.8 -0.4 pressure = -0.6 – (+0.5) = -1.1, suction
(widthwise -0.5 Local pressure coefficients:
left half) Local coefficients for roof: Max. value from all
Leeward -0.5 -0.8 -1.0/ -1.0 -1.0 the values given in Table 7 of IS:875-pt.3, i.e.{–
(widthwise -0.5 2.0- (+0.5)} = -2.5, up to 0.15 x w = 0.15 x 12 =
right half) 1.8m on all edges of roof.
Local coefficients for walls: From Table 5 of the
Positive internal pressure will act towards the roof IS:875-pt.3, it is {-1.0 –(0.5)}= -1.5, for a
while negative internal pressure will be away distance of 0.25 x w = .25 x 10 = 2.5m at all
from the roof. Hence +ve internal pressure will be corners.
added to –ve external pressure coefficient and
vice-a-versa. The combinations will have to be Calculations of Force due to Frictional Drag:
made separately for different zones, as given in (IS:875-pt.3, Sec 6.4.1)
Figure 8-2. This will act in the longitudinal direction of the
building along the wind. Here h<b, therefore, first
equation will be used & Cf’ = 0.02. This will be
Design Pressure Coefficients for Walls:
added to the wind force on gable walls. Ka for
Refer Table 5 of code: h/w = 5/10 = 0.5, and l/w =
roof and long walls is 0.8, as area is more than
50/10 = 5 therefore Cpe for walls* are given in
100m2.
Table 8-2.
Figure 8.2 - Net Roof Pressure Coefficients for different zones and combinations
o
For 0 wind incidence, Cpi = +0.5
2.0* 2.0* 1.0 0.5
2.0* 2.0*
0.75 0.5
0.25
Which is equivalent to ↓
2.75 2.5 1.5 1.0 2.5
1.75
0.75 0.5
0.25
Which is equivalent to ↓
2.75 1.5 0.5 0.0
1.5 1.75
0.5 0.5
0.5
Which is equivalent to ↓
1.5 2.5 1.5 1.5
2.5 1.5
5m
10o
50 m
= 0o
Fig. – 9.1
Solution:
Wind Data: Area Averaging factor Ka
Dhanbad is situated in Zone II at the boundary of (IS:875-pt.3, Sec 6.2.2, Table-4)
Zone II & Zone IV. For such places higher Zone Tributary area for columns = 5 6.76 = 33.81 m2
is recommended. Therefore, = 0.888
Wind Zone: Zone IV (Vb= 47 m/s) Tributary area for Trusses =10.155=60.95m2
(IS:875-pt.3, Sec 5.2) = 0.852
2. Terrain category: Transition from Category 1 to Tributary area for Purlins = 1.4 5 = 7.0 m2 =
Category 2. 1.0
(IS:875-pt.3, Sec 5.3.2.1) Tributary area of short walls for design of wind
braces in plan
Note: A combined wind speed profile is to be worked = 10 x 5 + 0.5 x10x1.76 =58.8 m2 = 0.855
out as per Appendix – B (Sec 5.3.2.4) but since height
Permeability of the Building:
of boundary layer developed after 500m fetch length is
more than building height of 5m, only effects due to
Since one of the walls of the structure is open, it
Terrain Category 2 are to be considered. A combined comes under the category of large permeability
profile would be needed in case of tall structures. exceeding 20% opening.
0.8
Which is equivalent to ↓
2.8 1.8 1.3
2.8
0.4
Which is equivalent to ↓
1.6 0.0 0.6
1.6
For 90o / 270o wind incidence, Cpi = -0.5, up to w/2 from ends
2.0* 1.0 1.0
2.0*
0.5
Which is equivalent to ↓
1.5 0.5 0.5
1.5
= 180o
5m
10 m 4 m
5m 3m
50 m
Fig. – 10.1
Solution:
Wind Data: Tributary area for columns = 5 x 5 = 25 m2 =
Dhanbad is situated in Zone II at the boundary of 0.9
Zone II & Zone IV. For such places higher Zone Tributary area for main Trusses = 2 5.176 5 =
is recommended. Therefore, 51.76m2 = 0.864
Wind Zone: Zone IV (Vb= 47 m/s) Tributary area for Purlins = 1.4 x 5 = 7.0 m2=
(IS:875-pt.3, Sec 5.2) 1.0
2. Terrain category: Transition from Category 1 to Tributary area of short walls for design of plan
Category 2. braces,
(IS:875-pt.3, Sec 5.3.2.1) Main portion = 5 10 + 10 1.33 ½ =56.65 m2
0.858
Note: A combined wind speed profile is to be worked Annexe = 5 3 + 5 1 ½ = 16.5 m2 0.957
out as per Appendix – B (Sec 5.3.2.4) but since height
of boundary layer developed after 500m fetch length is
more than building height of 5m, only effects due to
Permeability of the Building: (keeping same as in
Terrain Category 2 are to be considered. A combined Ex.4, all openings on the external walls)
profile would be needed in case of tall structures. Area of all the walls = 5(210+50+23.5)
Design Factors: +1.33 10 1/2 2 +350 + 1 50 = 598.6 m2
Risk Coefficient factor ‘k1’ = 1.00 Area of all the openings =201.51.5= 45 m2
(IS:875-pt.3, Sec 5.3.1, Table-1) % opening area =7.6 %, between 5% and 20%
Terrain & Height factor ‘k2’ = 1.00 Hence the building is of Medium permeability.
(IS:875-pt.3, Sec 5.3.2.2, Table-2) (IS:875-pt.3, Sec 6.3.2.2)
Topography factor ‘k3’ = 1.00
(IS:875-pt.3, Sec 5.3.3.1) Design Wind Pressure
Importance Factor for Cyclonic Region k4 =1.00 Design Wind Speed = VZ = Vbk1k2k3k4
(IS-875-pt.3, Sec 5.3.4)
= 471.01.01.01.0 = 47.00 m/s
Wind Directionality factor ‘Kd’ = 0.90
(IS:875-pt.3, Sec 6.2.1) (IS:875-pt.3, Sec 5.3)
Area Averaging factor Ka
(IS:875-pt.3, Sec 6.2.2, Table-4) pZ = 0.6 (VZ)2 = 0.6 (47.00)2 = 1325.4 N/m2
(IS:875:pt.3, Sec 6.2)
pd = pZ KdKa = 1.32540.9Ka = 1.193 Ka Design Pressure Coefficients for Walls:
(IS:875-pt.3, Sec 6.2) Refer Table 5 of code: h/w = 0.5, and l/(w1+w2)
For various members and components, use proper = 3.33 therefore Cpe for walls
value of Ka, as above.
Refer note below Sec. 5.3 of IS:875-pt.3 for Table 10-2
buildings less than 10m height, while making Angle of Incidence 0o 90o
stability calculations and design of the frame. Wall – A +0.7 - 0.5
Wall – B - 0.25 - 0.5
Wind Load Calculations: Wall – C - 0.6 + 0.7
Total wind force on a joint or member or element, Wall – D - 0.6 - 0.1
F = (Cpe-Cpi)*A* pd Note: Here Walls A, B, C & D refers to the external
(IS:875-pt.3, Sec 6.3.1) walls of combined building.
Internal Pressure Coefficient Cpi = 0.5 These will be combined with internal pressure
coefficients as earlier, equal to Cpi = 0.5
(IS:875-pt.3, Sec 6.3.2.2) Cpnet for Walls A or B = 0.7 – (-0.5) = +1.2,
Note: buildings shall be analysed once for pressure
pressure of 0.5 from inside and then for a suction = -0.5 – (+0.5) = -1.0, suction
of –0.5 from inside (refer Sec 6.3.2.1) along-with Cpnet for Walls C or D = 0.7 – (-0.5) = +1.2,
external pressure coefficient. pressure
= -0.6 – (+0.5) = -1.1, suction
External Pressure Coefficients
For Main Building: Using the Table 6 with roof Design Pressure coefficients for Overhangs:
angle 15o (for ‘c’ & ‘d’ in table 21) For 00 wind incidence, i.e. from overhang side,
For h/w = 5/10 = 0.5, pressure coefficients are Cpi = +1.25
tabulated in Table 10-1. For other directions, Cpi shall be the same as on
the adjoining wall, as above, +0.7 or –0.5.
Table 10-1 Cpe = -2.0, being the max. on the nearest non-
Portion of roof Wind Incidence Angle overhanging portion of canopy roof.
0o 90o Design pressure coefficient on overhang: -2.0-
E -0.8 -0.75 (+1.25) = -3.25
F -0.8 -0.6 (IS:875-pt.3, Sec. 6.3.3.5)
G -0.4 -0.75
H -0.4 -0.6 Local pressure coefficients for the design of
For portions ‘a’ and ‘b’ of the canopy: h1/h2 = 5/4 claddings and fasteners
= 1.25 < 1.75 Refer Table 6 of IS-875 for Roof Angle = 150
Local Cpe for eaves portion in end zone:NA
(IS:875-pt.3, Table 21)
Local Cpe for eaves portion in mid zone:NA
For 0 wind incidence: on ‘a’: Cpe = -0.45 & on
o
Local Cpe for ridge portion: -1.2
‘b’: Cpe = -0.5 Local Cpe for gable edges: -1.2
For 180o wind incidence: on ‘a’: Cpe = -0.4 & on
‘b’: Cpe = -0.4 Local Cpe for canopy roof: -2.0
For 90o/ 270o wind incidence: on ‘a’: Cpe = -1.0
(IS:875-pt.3, Table 7)
up to 2.5m from ends and –0.5 thereafter, from
IS:875-pt3., Table 7. On ‘b’: Cpe = - 0.5, from
IS:875-pt.3, Table 5. Therefore Max. Cpnet = -1.2 – (+0.5) = -1.7, for
pitched roof = -2.0 – (+0.5) = -2.5, for canopy
Design Pressure Coefficients for Roof: roof
Positive internal pressure will act towards the roof
while negative internal pressure will be away However, for the use of the local pressure
from the roof. Hence +ve internal pressure will be coefficients, the design pressure pd will be
added to –ve external pressure coefficient and computed with Ka = 1. Therefore, pd = 1.3254
vice-a-versa. The combinations will have to be 0.9 = 1.193 kN/m2
made separately for different zones, as given in
figure 10-2.
Zone of local coefficients = 0.15 10 = 1.5m, at Calculations of Force due to Frictional Drag:
ridges, eaves and gable ends of pitched roof and (IS:875-pt.3, Sec 6.4.1)
0.15 5 = .75m for canopy roof. In this region This will act in the longitudinal direction of the
the fasteners shall be designed to carry increased building along the wind. Here h<b, therefore, first
force. equation will be used & Cf’ = 0.02. This will be
added to the wind force on gable walls. Ka for
(IS:875-pt.3, Table 6) roof and walls is 0.8, as area is more than 100m2.
Figure 10-2 - Net Roof Pressure Coefficients for different zones and combinations
For End Zone E/G; 0o wind incidence
0.8 0.4 1.3 0.9
=
0.45 0.5 0.5 0.5 0.95 1.0
0.5
OR
0.8 0.4 0.3 0.1
=
0.45 0.5 0.5 0.5 0.05 zero
0.5
For End Zone E/G; 180o wind incidence
0.5
OR
0.4 0.8 0.1 0.3
=
0.4 0.4 0.5 0.5 0.1 0.1
0.5
For End Zone E/G; 90o wind incidence
0.75 0.75 1.25 1.25
=
1.0 0.5 0.5 0.5 1.5 1.0
0.5
OR
0.75 0.75 0.25 0.25
=
1.0 0.5 0.5 0.5 0.5 0.0
0.5
For Mid Zone F/H; 0o wind incidence
0.8 0.4 1.3 0.9
=
0.45 0.5 0.5 0.5 0.95 1.0
0.5
OR
0.8 0.4 0.3 0.1
=
0.45 0.5 0.5 0.5 0.05 zero
0.5
0.5
OR
0.4 0.8 0.1 0.3
=
0.4 0.4 0.5 0.5 0.1 0.1
0.5
0.5
OR
0.6 0.6 0.1 0.1
=
0.5 0.5 0.5 0.5 0.0 0.0
0.5
Example 11 - Wind Pressure and Forces on a Rectangular Clad
Pitched Roof Building with Open Verandah
Problem Statement:
What difference will occur if the mono-slope annexe in Example 10 is unclad (open) on all the
three sides as shown in figure 11.1?
= 180o
5m
10 m 4 m
5m 3m
50 m
Fig. – 11.1
Solution:
Wind Data: Tributary area for main Trusses = 2 5.176 5 =
Dhanbad is situated in Zone II at the boundary of 51.76m2 = 0.864
Zone II & Zone IV. For such places higher Zone Tributary area for Purlins = 1.4 5 = 7.0 m2 =
is recommended. Therefore, 1.0
Wind Zone: Zone IV (Vb= 47 m/s) Tributary area of short walls for design of wind
(IS:875-pt.3, Sec 5.2) braces in plan = 10 5 + 6.7 = 56.7m2 = 0.858
2. Terrain category: Transition from Category 1 to
Category 2. Permeability of the Building: (keeping same as in
(IS:875-pt.3, Sec 5.3.2.1) Ex.4, all openings on the external walls)
Area of all the walls =5 (210 + 250) + 2 6.7
Note: A combined wind speed profile is to be worked = 613.4 m2
out as per Appendix – B (IS:875-pt.3, Sec 5.3.2.4) but
since height of boundary layer developed after 500m Area of all the openings = 201.51.5 = 45 m2
fetch length is more than building height of 5m, only % opening area =7.3 %, between 5% and 20%
effects due to Terrain Category 2 are to be considered. Hence the building is of Medium permeability.
A combined profile would be needed in case of tall (IS:875-pt.3, Sec 6.3.2.2)
structures.
Design Wind Pressure
Design Factors:
Design Wind Speed = VZ = Vbk1k2k3k4 =
Risk Coefficient factor, ‘k1’ = 1.00
(IS:875-pt.3, Sec 5.3.1, Table-1) 471.01.01.01.0 = 47.00 m/s
Terrain & Height factor,‘k2’ = 1.00 (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.2.2, Table-2)
Topography factor, ‘k3’ = 1.00 pZ = 0.6 (VZ)2 = 0.6 (47.00)2 = 1325.4 N/m2
(IS:875-pt.3, Sec 5.3.3.1) (IS:875-pt.3, Sec 6.2)
Importance Factor for Cyclonic Region,‘k4’=1.00
(IS:875-pt. 3, Sec 5.3.4) pd = pZ *Kd*Ka = 1.3254*0.9*Ka = 1.193 Ka
Wind Directionality factor, ‘Kd’ = 0.90 (IS:875-pt.3, Sec6.2)
(IS:875-pt.3, Sec 6.2.1) For various members and components, use proper
Area Averaging factor Ka value of Ka, as above.
(IS:875-pt.3, Sec 6.2.2, Table-4)
Refer note below Sec. 5.3 of IS:875-pt.3 for
Tributary area for columns = 5 5 = 25 m2
buildings less than 10m height, while making
=0.9
stability calculations and design of the frame.
Wind Load Calculations: Table 11-2
F = (Cpe-Cpi) A pd Angle of Incidence 0o 90o
(IS:875-pt.3, Sec 6.3.1) Wall – A +0.7 - 0.5
Wall – B - 0.25 - 0.5
Internal Pressure Coefficient Cpi = 0.5 Wall – C - 0.6 + 0.7
(IS:875-pt.3, Sec 6.3.2.2) Wall – D - 0.6 - 0.1
Note: buildings shall be analysed once for pressure of *: Since the pressure coefficients are given only for
0.5 from inside and then for a suction of –0.5 from buildings with l/w ratio up to 4, for longer buildings
inside (IS:875-pt.3, Sec 6.3.2.1) along-with external i.e. l/w > 4, at present values up to 4 are being used.
pressure coefficient.
These will be combined with internal pressure
External Pressure Coefficients
For Main Building: Using the Table 6 with roof coefficients as earlier, equal to Cpi = 0.5
angle 15o (for ‘c’ & ‘d’ in IS:875-pt.3, Table 21) Cpnet for Walls A or B = 0.7 – (-0.5) = +1.2,
For h/w = 0.5, pressure coefficients are tabulated pressure = -0.5 – (+0.5) = -1.0, suction
in Table 11-1. (Refer figure below IS:875-pt.3, Cpnet for Walls C or D = 0.7 – (-0.5) = +1.2,
Table 6) pressure = -0.6 – (+0.5) = -1.1, suction
1.25
OR
0.8 0.4 0.3 0.1
=
0.45 0.5 0.5 0.5 1.7 zero
1.25
For End Zone E/G; 180o wind incidence
0.5
OR
0.4 0.8 0.1 0.3
=
0.4 0.4 0.5 0.5 0.1 0.1
0.5
For End Zone E/G; 90o wind incidence
0.75 0.75 1.25 1.25
=
1.0 0.5 0.5 0.5 0.5 1.0
0.5
OR
0.75 0.75 0.25 0.25
=
1.0 0.5 0.5 0.5 0.5 0.0
0.5
For Mid Zone F/H; 0o wind incidence
0.8 0.4 1.3 0.9
=
0.45 0.5 0.5 0.5 1.7
1.25
OR
0.8 0.4 0.3 0.1
=
0.45 0.5 0.5 0.5 1.7 zero
1.25
0.5
OR
0.4 0.8 0.1 0.3
=
0.4 0.4 0.5 0.5 0.1 0.1
0.5
For Mid Zone F/H; 90o wind incidence
0.5
OR
0.6 0.6 0.1 0.1
=
0.5 0.5 0.5 0.5 0.0 0.0
0.5
Example 12 - Wind Pressure and Forces on a Rectangular Clad
Building on A Ridge or Hill: Pitched Roof
Problem Statement:
Calculate wind pressures and design forces on walls and roof of a rectangular clad resort building with
pitched roof, having plan dimensions 10m30m and height 5m, as shown in figure-12.1. The building is
situated in outskirts of Jaipur on a hilltop 10m high having upwind and downwind slopes of 180 and 100,
respectively. The building has 16 openings of 1.5m 1.5m size. The roof is of GC sheeting & the roof angle
is 150. Calculate also the local wind pressures on roof & wall cladding. The columns and trusses are at 5m
c/c longitudinally, purlins are at 1.4m c/c and columns at Gable ends are at 5m c/c.
=0o
10 m
10o
o
18
Fig. – 12.1
Solution:
Wind Data: = 50 + 6.7 = 56.7 m2 = 0.858
1. Wind Zone: Zone IV (Vb= 47m/s) Permeability of the Building:
Note: Jaipur is situated in Zone IV. Area of all the walls = 5 (210 + 230) + 2 6.7
(IS:875-pt.3, Sec 5.2) = 413.4m2
2. Terrain category: Category 2 for the Area of all the openings = 161.51.5 =36 m2
moderately developed area. % opening area = 8.71 %, between 5% and 20%
(IS:875-pt.3, Sec 5.3.2.1) Hence the building is of medium permeability.
Design Factors: (IS:875-pt.3, Sec 6.3.2.2)
Risk Coefficient factor ‘k1’ = 1.00 Design Wind Pressure
(IS:875-pt.3, Sec 5.3.1, Table-1)
Terrain & Height factor ‘k2’ = 1.00 Design Wind Speed = VZ = Vbk1k2k3k4 =
(IS:875-pt.3, Sec 5.3.2.2, Table-2) 471.01.01.1981.0 = 56.3 m/s
Topography factor ‘k3’ = 1.198* (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.3.1 & App. ‘C’) pZ = 0.6 (VZ)2 = 0.6 (56.3)2 = 1902.22 N/m2
* : see calculations of k3 at the end. (IS:875-pt.3, Sec 6.2)
pd = pZ KdKa = 1.90220.9Ka = 1.712 Ka
Importance Factor for Cyclonic Region k4 =1.00 (IS:875-pt.3, Sec 6.2)
(IS:875-pt.3, Sec 5.3.4) For various members and components, use proper
Wind Directionality factor ‘Kd’ = 0.90 value of Ka, as above.
(IS:875-pt.3, Sec 6.2.1)
Area Averaging factor Ka Refer note below Sec. 5.3 of IS:875-pt.3 for
(IS:875-pt.3, Sec 6.2.2, Table-4) buildings less than 10m height, while making
Tributary area for columns = 5 5 = 25 m2 = stability calculations and design of the frame.
0.9
Tributary area for Trusses = 2 5.176 5 = Wind Load Calculations:
51.76m2 = 0.864 F = (Cpe-Cpi) A pd
Tributary area for Purlins = 1.4 5 = 7.0 m2= (IS:875-pt.3, Sec 6.3.1)
1.0 Internal Pressure Coefficient Cpi = 0.5
Tributary area of short walls for design of wind (IS:875-pt.3, Sec 6.3.2.2)
braces in plan
Note: buildings shall be analysed once for pressure of Local pressure coefficients for the design of
0.5 from inside and then for a suction of –0.5 from claddings and fasteners
inside (IS:875-pt.3, 2 Sec 6.3.2.1) along-with external Refer Table 6 of IS-875 for Roof Angle = 150
pressure coefficient Local Cpe for eaves portion in end zone:NA
Local Cpe for eaves portion in mid zone:NA
External Pressure Coefficients Local Cpe for ridge portion: -1.2
Using the Table 6 with roof angle 15o Local Cpe for gable edges: -1.2
For h/w = 0.5, pressure coefficients are tabulated Local Cpe for corners of walls: -1.0
in Table 12-1. (refer figure of IS:875-pt.3, Table
6) Max. local Cpnet for roof at the edges and the ridge
= -1.2 – (+0.5) = -1.7
Table 12-1 Likewise at the wall edges = -1.0 – (+0.5) = -1.5
Portion of roof Wind Incidence Angle However, for the use of the local pressure
0o 90o coefficients, the design pressure pd will be
E -0.8 -0.75 computed with Ka = 1. Therefore, pd = 1.90220.9
F -0.8 -0.6 = 1.712 kN/m2
G -0.4 -0.75
H -0.4 -0.6
Zone of local coefficients = 0.1510 = 1.5m, at
ridges, eaves and gable ends & 0.2510 = 2.5m
Design Pressure Coefficients for Roof:
for wall corners. In this region the cladding and
Positive internal pressure will act towards the roof
while negative internal pressure will be away fasteners shall be checked for increased force.
(IS:875-pt.3, Table 6)
from the roof. Hence +ve internal pressure will be
added to –ve external pressure coefficient and Calculations of Force due to Frictional Drag:
vice-a-versa. The combinations will have to be (IS:875-pt.3, Sec 6.3.1)
made separately for zones E, F, G, H etc., as This will act in the longitudinal direction of the
given in figure 12-2. building along the wind. Here h<b, therefore, first
equation will be used & Cf’ = 0.02. This will be
Design Pressure Coefficients for Walls: added to the wind force on gable walls. Ka for
roof and walls is 0.8, as area is more than 100m2.
Refer Table 5 of code: h/w = 0.5, and l/w = 5
therefore Cpe for walls* are given in Table 12-2. CALCULATIONS FOR TOPOGRAPHY
FACTOR k3
Table 12-2
Angle of Incidence 0o 90o
Wall – A +0.7 - 0.5 10 m
Wall – B - 0.25 - 0.5
Wall – C - 0.6 + 0.7 Wind from left:
Wall – D - 0.6 - 0.1 H = 10 m, z = 10 m, L = 10/tan 18o = 30.777 K3 =
*: Since the pressure coefficients are given only 1 + C.s
for buildings with l/w ratio up to 4, for longer For = 18o, C = 0.36 (C-2)
buildings i.e. l/w > 4, at present values up to 4 are Factor ‘s’ is obtained from C-2.1 and figure15, for
being used. crest position
Le = z/0.3 = 10/0.3 H/Le = 10/10/0. = 0.3
These will be combined with internal pressure ===== s = 0.55
coefficients as earlier, equal to Cpi = 0.5 k3 = 1 + 0.36 0.55 = 1.198
Cpnet for Walls A or B = 0.7 – (-0.5) = +1.2,
pressure Wind from right:
= -0.5 – (+0.5) = -1.0, suction H = 10 m, z = 10 m, L = 10/tan 10o = 56.7 m
Cpnet for Walls C or D = 0.7 – (-0.5) = +1.2, C = 1.2 (z/L) = 1.2 (10/56.7) = 0.21
pressure For = 10o, Le = L = 56.7 m
= -0.6 – (+0.5) = -1.1, suction H/Le = 10/56.7 = 0.176 ==== s = 0.7
k3 = 1 + 0.21 0.7 = 1.147
Using k3 = 1.198, being the critical one.
Figure 12-2 - Net Roof Pressure Coefficients for different zones and combinations
For End Zone E/G; 0o wind incidence
0.8 0.4 1.3 0.9
=
0.5 0.5
OR
0.8 0.4 0.3 0.1
=
0.5 0.5
0.5 0.5
OR
0.75 0.75 0.25 0.25
=
0.5 0.5
For Mid Zone F/H; 0o wind incidence
0.5 0.5
OR
0.8 0.4 0.3 0.1
=
0.5 0.5
0.5 0.5
OR
0.6 0.6 0.1 0.1
=
0.5 0.5
Example 13 - Wind Pressure and Forces on a Rectangular Clad
Building on A Cliff & Escarpment: Pitched Roof
Problem Statement:
What difference will occur if the building in Example12 is situated on a hill having upwind and downwind
slopes of 150 and 010, respectively as shown in figure 13.1?
=0o
01o
10 m
15o
Fig. – 13.1
Solution:
Wind Data: Area of all the openings = 161.51.5 =36 m2
% opening area =8.71 %, between 5% and 20%
1. Wind Zone: Zone IV (Vb= 47m/s) Hence the building is of medium permeability.
(IS:875-pt.3, Sec 5.2) (IS:875-pt.3, Sec 6.3.2.2)
2. Terrain category: Category 2 for the
moderately developed area. Design Wind Pressure
(IS:875-pt.3, Sec 5.3.2.1)
Design Factors: Design Wind Speed = VZ = Vbk1k2k3k4 =
Risk Coefficient factor ‘k1’ = 1.00 471.01.01.1931.0 = 56.071 m/s
(IS:875-pt.3, Sec 5.3.1, Table-1) (IS:875-pt.3, Sec 5.3)
Terrain & Height factor ‘k2’ = 1.00 pZ = 0.6 (VZ)2 = 0.6 (56.071)2 = 1886.37 N/m2
(IS:875-pt.3, Sec 5.3.2.2, Table-2) (IS:875-pt.3, Sec 6.2)
Topography factor ‘k3’ = 1.193* pd = pZ KdKa = 1.8860.9Ka = 1.700 Ka
(IS:875-pt.3, Sec 5.3.3.1 & App. ‘C’) (IS:875-pt.3, Sec 6.2)
* : see calculations of k3 at the end. For various members and components, use proper
Importance Factor for Cyclonic Region k4 =1.00 value of Ka, as above.
(IS:875-pt.3, Sec 5.3.4) Refer note below Sec. 5.3 of IS:875-pt.3 for
Wind Directionality factor ‘Kd’ = 0.90 buildings less than 10m height, while making
(IS:875-pt.3, Sec 6.2.1) stability calculations and design of the frame.
Area Averaging factor Ka
(IS:875-pt.3, Sec 6.2.2, Table-4) Wind Load Calculations:
Tributary area for columns = 5 x 5 = 25 m2 = F = (Cpe-Cpi) A pd
0.9 (IS:875-pt.3, Sec 6.2.1)
Tributary area for Trusses = 2 x 5.176 x 5 = Internal Pressure Coefficient Cpi = 0.5
51.76m2 = 0.864 (IS:875-pt.3, Sec 6.3.2.2)
Tributary area for Purlins = 1.4 x 5 = 7.0 m2= Note: buildings shall be analysed once for pressure of
1.0 0.5 from inside and then for a suction of –0.5 from
Tributary area of short walls for design of wind inside (IS:875-pt.3, Sec 6.2.2.1) along-with external
braces in plan pressure coefficient
= 50 + 6.7 = 56.7 m2 = 0.858
External Pressure Coefficients
Permeability of the Building: Using the IS:875-pt.3, Table 6 with roof angle 15o
Area of all the walls = 5 (210 + 230) + 2 For h/w = 0.5, pressure coefficients are tabulated
6.7 = 413.4m2 in Table 13-1. (IS:875-pt.3, Table 6)
Table 13-1 Max. local Cpnet for roof at the edges and the ridge
Portion of roof Wind Incidence Angle = -1.2 – (+0.5) = -1.7
0o 90o Likewise at the wall edges = -1.0 – (+0.5) = -1.5
E -0.8 -0.75 However, for the use of the local pressure
F -0.8 -0.6 coefficients, the design pressure pd will be
G -0.4 -0.75 computed with Ka = 1. Therefore, pd = 1.886*0.9
H -0.4 -0.6 = 1.700 kN/m2
Design Pressure Coefficients for Roof: Zone of local coefficients = 0.1510 = 1.5m, at
ridges, eaves and gable ends & 0.2510 = 2.5m
Positive internal pressure will act towards the roof for wall corners. In this region the cladding and
while negative internal pressure will be away fasteners shall be checked for increased force.
from the roof. Hence +ve internal pressure will be (IS:875-pt.3, Table 6)
added to –ve external pressure coefficient and
vice-a-versa. The combinations will have to be Calculations of Force due to Frictional Drag:
made separately for zones E, F, G, H etc., as (IS:875-pt.3, Sec 6.3.1)
given in figure 12-2.
This will act in the longitudinal direction of the
Design Pressure Coefficients for Walls: building along the wind. Here h<b, therefore, first
equation will be used & Cf’ = 0.02. This will be
Refer Table 5 of code: h/w = 0.5, and l/w = 5 added to the wind force on gable walls. Ka for
therefore Cpe for walls* are given in Table 13-2. roof and walls is 0.8, as area is more than 100m2.
0.5 0.5
OR
0.8 0.4 0.3 0.1
=
0.5 0.5
0.5 0.5
OR
0.75 0.75 0.25 0.25
=
0.5 0.5
0.5 0.5
OR
0.8 0.4 0.3 0.1
=
0.5 0.5
0.5 0.5
OR
0.6 0.6 0.1 0.1
=
0.5 0.5
Example 14 - Wind Pressure and Forces on a Rectangular Clad
Building on Slope of A Ridge or Hill: Pitched Roof
Problem Statement:
What difference will occur if the building in Example12 is situated in the middle of the upwind slope of a
hill 50m high, upwind and downwind slopes being 180 and 100 respectively, as shown in figure 14.1?
10o
=0o
50 m
25 m
18o
Fig. – 14.1
Solution:
Wind Data: Permeability of the Building:
1. Wind Zone: Zone IV (Vb= 47m/s) Area of all the walls = 5 (210 + 230) + 2
(IS:875-pt.3, Sec 5.2) 6.7 = 413.4m2
2. Terrain category: Category 2 for the Area of all the openings = 161.51.5 =36 m2
moderately developed area. % opening area =8.71 %, between 5% and 20%
(IS:875-pt.3, Sec 5.3.2.1) Hence the building is of medium permeability.
Design Factors: (IS:875-pt.3, Sec 6.3.2.2)
Risk Coefficient factor ‘k1’ = 1.00
(IS:875-pt.3, Sec 5.3.1, Table-1) Design Wind Pressure
Terrain & Height factor ‘k2’ = 1.00 Design Wind Speed = VZ = Vbk1k2k3k4 =
(IS:875-pt.3, Sec 5.3.2.2, Table-2) 471.01.01.1271.0 = 52.97 m/s
Topography factor ‘k3’ = 1.127* (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.3.1 & App. ‘C’) pZ = 0.6 (VZ)2 = 0.6 (52.97)2 = 1683.5 N/m2
* : see calculations of k3 at the end. (IS:875-pt.3, Sec 6.2)
Importance Factor for Cyclonic Region k4 =1.00 pd = pZ KdKa = 1.68350.90.867 = 1.313
(IS:875-pt.3, Sec 5.3.4) kN/m2 (short wall)
Wind Directionality factor ‘Kd’ = 0.90
= 1.68350.90.8 = 1.212 kN/m2
(IS:875-pt.3, Sec 6.2.1)
(long wall & roof)
Area Averaging factor Ka= 0.867, for short walls
(IS:875-pt.3, Sec 6.2)
= 0.80, for long walls & roofs
(IS:875-pt.3, Sec 6.2.2, Table-4)
Refer note below Sec. 5.3 of IS:875-pt.3 for
Tributary area for columns = 5 x 5 = 25 m2 =
buildings less than 10m height, while making
0.9
stability calculations and design of the frame.
Tributary area for Trusses = 2 x 5.176 x 5 =
51.76m2 = 0.864
Wind Load Calculations:
Tributary area for Purlins = 1.4 x 5 = 7.0 m2=
F = (Cpe-Cpi) A pd
1.0
(IS:875-pt.3, Sec 6.3.1)
Tributary area of short walls for design of wind
braces in plan Internal Pressure Coefficient Cpi = 0.5
= 50 + 6.7 = 56.7 m2 = 0.858 (IS:875-pt.3, Sec 6.3.2.2)
Note: buildings shall be analysed once for
pressure of 0.5 from inside and then for a suction
of –0.5 from inside (refer Sec 6.3.2.2) along-with Local Cpe for eaves portion in end zone:NA
external pressure coefficient Local Cpe for eaves portion in mid zone:NA
Local Cpe for ridge portion: -1.2
External Pressure Coefficients Local Cpe for gable edges: -1.2
Using the IS:875-pt.3, Table 6 with roof angle 15o Max. local Cpnet for roof at the edges and the ridge
For h/w = 0.5, pressure coefficients are tabulated = -1.2 – (+0.5) = -1.7
in Table 14-1. (refer figure Table 6 of code)
Zone of local coefficients = 0.1510 = 1.5m, at
Table 14-1 ridges, eaves and gable ends. In this region the
Portion of roof Wind Incidence Angle cladding and fasteners shall be checked for
0o 90o increased force.
E -0.8 -0.75 (IS:875-pt.3, Table 6)
F -0.8 -0.6 However, for the use of the local pressure
G -0.4 -0.75 coefficients, the design pressure pd will be
H -0.4 -0.6 computed with Ka = 1. Therefore pd = 1.6835 0.9
= 1.515 kN/m2.
Design Pressure Coefficients for Roof:
Calculations for Topography Factor k3
Positive internal pressure will act towards the roof (Refer IS:875-pt.3, Appendix-C)
while negative internal pressure will be away
from the roof. Hence +ve internal pressure will be
added to –ve external pressure coefficient and 50 m
18o 25 m
vice-a-versa. The combinations will have to be 10o
made separately for zones E, F, G, H etc., as For wind from left to right: Z = 50m H = 25m
given in figure 14-2.
Le = Z/0.3 = 50/0.3 = 166.67m for = 180 , C =
Design Pressure Coefficients for Walls: 0.36 and {from C-2}
Refer Table 5 of code: h/w = 0.5, and l/w = 5 factor ‘s’ is obtained from C-2.1 and IS:875-pt.3,
therefore Cpe for walls* are given in Table 14-2. Figure 15 for upwind position
These will be combined with internal pressure factor ‘s’ is obtained from C-2.1 and IS:875-pt.3,
Figure 15 for downwind position
coefficients as earlier, equal to Cpi = 0.5
H/Le = (25/283.56) = 0.09 & X/Le = (77/283.56)
= 0.271 == s = 0.6
Cpnet for Walls A or B = 0.7 – (-0.5) = +1.2,
pressure Therefore k3 = 1 + 0.2116 0.6 = 1.127
= -0.5 – (+0.5) = -1.0, suction Using k3 = 1.127, being the critical one.
Cpnet for Walls C or D = 0.7 – (-0.5) = +1.2,
pressure
= -0.6 – (+0.5) = -1.1, suction
0.5 0.5
OR
0.8 0.4 0.3 0.1
=
0.5 0.5
0.5 0.5
OR
0.75 0.75 0.25 0.25
=
0.5 0.5
o
For Mid Zone F/H; 0 wind incidence
0.5 0.5
OR
0.8 0.4 0.3 0.1
=
0.5 0.5
0.5 0.5
OR
0.6 0.6 0.1 0.1
=
0.5 0.5
Example 15 - Wind Pressure and Forces on a Rectangular Clad
Building: Hipped Roof
Problem Statement:
Calculate wind pressures and design forces on walls and roof of a rectangular clad building with hipped roof,
having plan dimensions 10m20m and height 5m, as shown in figure-15.1. The building is situated in Jaipur
on a fairly level topography. Walls of building have 20 openings of 1.5m1.5m size. The roof is of GC
sheeting & the roof angle is 150. Calculate also the local wind pressures on roof & wall cladding. The
columns & trusses are at 5m c/c longitudinally, purlins are at 1.4m c/c and columns at Gable ends are at 5m
c/c.
= 0o
10 m 5m
20 m
Fig. – 15.1
Solution:
Wind Data: Area of all the walls =5 (210 +
1. Wind Zone: Zone IV (Vb= 47m/s)----- 220) + 6.7= 306.7 m2
(IS:875-pt.3, Sec 5.2) Area of all the openings = 201.51.5 = 45 m2
% opening area = 14.67 %, between 5% and 20%
2. Terrain category: Terrain Category 2
(IS:875-pt.3, Sec 5.3.2.1) Hence the building is of medium permeability.
Design Factors: (IS:875-pt.3, Sec 6.3.2.2)
Risk Coefficient factor ‘k1’ = 1.00
(IS:875-pt.3, Sec 5.3.1, Table-1) Design Wind Pressure
Terrain & Height factor ‘k2’ = 1.00 Design Wind Speed = VZ = Vbk1k2k3k4
(IS:875-pt.3, Sec 5.3.2.2, Table-2) =471.01.01.01.0 = 47.00 m/s
Topography factor ‘k3’ = 1.00 (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.3.1) pZ = 0.6 (VZ) = 0.6 (47.00)2 = 1325.4 N/m2
2
Importance Factor for Cyclonic Region k4 =1.00 (IS:875-pt.3, Sec 6.2)
(IS:875-pt.3, Sec 5.3.4)
pd = pZ KdKa = 1.32540.9Ka = 1.193 Ka
Wind Directionality factor ‘Kd’ = 0.90
(IS:875-pt.3, Sec 6.2)
(IS:875-pt.3, Sec 6.2.1)
For various members and components use proper
Area Averaging factor Ka:
value of Ka, as above
(IS:875-pt.3, Sec 6.2.2, Table-4)
Tributary area for columns = 5 5 = 25 m2 Refer note below Sec. 5.3 for buildings less than
==== 0.9 10m height, while making stability calculations
Tributary area for Trusses = 5.176 5 2 = 51.76 and design of the frame.
m2 ===== 0.864
Tributary area for Purlins = 1.4 5 = 7.0 m2 Wind Load Calculations:
====== 1.0
Tributary area of short walls = 10 5 = 50 m2 F = (Cpe-Cpi) A pd
===== 0.867 for design of wind braces in plan (IS:875-pt.3, Sec 6.3.1)
Permeability of the Building:
Internal Pressure Coefficient Cpi = 0.5 These will be combined with internal pressure
(IS:875-pt.3, Sec 6.3.2.2) coefficients as earlier, equal to Cpi = 0.5
Note: buildings shall be analysed once for pressure of
0.5 from inside and then for a suction of –0.5 from Cpnet for Walls A or B = 0.7 – (-0.5) = +1.2,
inside (refer Sec 6.3.2.1) along-with external pressure pressure
coefficient = -0.5 – (+0.5) = -1.0, suction
Cpnet for Walls C or D = 0.7 – (-0.5) = +1.2,
External Pressure Coefficients pressure
Using the Table 6 with roof angle 15o = -0.6 – (+0.5) = -1.1, suction
For h/w = 0.5, pressure coefficients are tabulated
in Table 15-1. (refer figure below Table 6 of Local pressure coefficients for the design of
code) claddings and fasteners
Refer Table 6 of IS-875 for Roof Angle = 150
Table 15-1 Local Cpe for eaves portion in end zone: NA
Portion of roof* Wind Incidence Angle Local Cpe for eaves portion in mid zone: NA
0o 90o Local Cpe for ridge portion: -1.2
E -0.8 -0.75 Local Cpe for gable edges (hipped part): -1.2x0.8
F -0.8 -0.6 = -0.96
G -0.4 -0.75
H -0.4 -0.6 Local Cpe for corners of walls: -1.0
** **
Hipped slope, M,N -0.75 -0.8 (windward) (IS:875-pt.3, Table 5)
-0.4** (leeward)
* See Figure 15.2.
Therefore Max. local Cpnet for roof at the edges
** These values may be reduced by 20% as per
and the ridge = -1.2 – (+0.5) = -1.7
IS:875-pt.3, Sec 6.3.3.2, note 3.
Likewise at the wall edges = -1.0 – (+0.5) = -1.5
Design Pressure Coefficients for Roof:
However, for the use of the local pressure
Positive internal pressure will act towards the roof
coefficients, the design pressure pd will be
while negative internal pressure will be away
computed with Ka = 1. Therefore, pd = 1.32540.9
from the roof. Hence +ve internal pressure will be
= 1.193 kN/m2
added to –ve external pressure coefficient and
vice-a-versa. The combinations will have to be
made separately for zones E, F, G, H etc., as Zone of local coefficients = 0.1510 = 1.5m, at
given on figure 15.3. ridges, eaves and gable ends & 0.2510 = 2.5m
for wall corners. In this region the cladding and
Hipped slopes shall be subjected to a net pressure fasteners shall be checked for increased force
coefficient of
-0.8 – (+0.5) = -1.3 or Calculations of Force due to Frictional Drag:
–0.4 – (-0.5) = +0.1 (IS:875-pt.3, Sec6.4.1)
but all the elements of roof in hipped slope shall
be designed for a reduced pressure of 80%. This will act in the longitudinal direction of the
building along the wind. Here h<b, therefore, first
equation will be used & Cf’ = 0.02. This will be
Design Pressure Coefficients for Walls:
Refer Table 5 of code: h/w = 0.5, and l/w = 2 added to the wind force on gable walls. Ka for
roof and walls is 0.8, as area is more than 100m2.
therefore Cpe for walls* are given in Table 15-2.
Table 15-2
Angle of Incidence 0o 90o
Wall – A +0.7 - 0.5
Wall – B - 0.25 - 0.5
Wall – C - 0.6 + 0.7
Wall – D - 0.6 - 0.1
N G
E
F H
Figure 15.3 –Net Roof Pressure Coefficients for different zones and combinations
0.5 0.5
OR
0.6 0.6 0.1 0.1
=
0.5 0.5
0.64
0.32
0.5
0.5
M
0.32 N
0.64
0.5 0.5
Example 16 - Wind Pressure and Forces on a free standing duo-
pitch roof of an unclad parking shed
Problem Statement:
Calculate wind pressure and design forces on a free standing duo-pitch roof of an unclad parking shed
having dimensions 10m50m and height of 5m up to eaves. The roof of shed is bent down, as in figure 16.1.
The shed is located at Bareilly (UP) in the Transport Nagar area. A facia of 1m has been provided at both the
longitudinal walls. The roof angle is 150. Assume that full obstruction can occur on one side i.e. the
solidity ratio may vary from 0 to 1.0.
= 0o
=15o
10 m 5m
50 m
Fig. – 16.1
Solution:
Wind Data: Design Wind Pressure
1. Wind Zone: Zone IV (Vb= 47m/s) Design Wind Speed = VZ = Vbk1k2k3k4 =
(IS:875-pt.3, Sec 5.2) 471.01.01.01.0 = 47.00 m/s
Note: Bareilly is situated in Zone IV. (IS:875.pt.3, Sec 5.3)
2. Terrain category: Category 2 pZ = 0.6 (VZ)2 = 0.6 (47.00)2 = 1325.4 N/m2
(IS:875-pt.3, Sec 5.3.2.1) (IS:875-pt.3, Sec 6.2)
pd = pZ KdKa =1.32540.9 Ka = (1.193 Ka)
Design Factors: kN/m2
Risk Coefficient factor ‘k1’ = 1.00 (IS:875.pt.3, Sec6.2)
(IS:875-pt.3, Sec 5.3.1, Table-1) Refer note below Sec. 5.3 of IS:875-pt.3 for
Terrain & Height factor ‘k2’ = 1.00 buildings less than 10m height, while making
(IS:875-pt.3, Sec 5.3.2.2, Table-2) stability calculations and design of the frame.
Topography factor ‘k3’ = 1.00
(IS:875-pt.3, Sec 5.3.3.1) Wind Load Calculations:
Importance Factor for Cyclonic Region k4 =1.00 F = (Cpe-Cpi) A pd
(IS:875-pt.3, Sec 5.3.4) (IS:875-pt.3, Sec 6.3.1)
Wind Directionality factor ‘Kd’ = 0.90
(IS:875-pt.3, Sec 6.2.1) Net Pressure Coefficients
Area Averaging factor ‘Ka’ = 0.80*, for Roof (IS:875-pt.3, Table 9)
(IS:875-pt.3, Sec 6.2.2, Table-4) Roof angle +15o: h/w = 0.5 & L/w = 5
* The value of Ka is dependent on the tributary area.
Max. +ve roof pressure, for = 0 = +0.4
Thus, Ka may be computed by working out the Max. -ve roof pressure, for = 0 = -0.8
tributary area for different elements, and using Table 4 Max. +ve roof pressure, for = 1 = +0.4
of IS:875-pt.3, as illustrated in some of the previous Max. -ve roof pressure, for = 1 = -1.2
examples. (IS:875-pt.3, Sec. 6.3.3.3)
Force coefficient on facia = +1.3
Calculating solidity ratio: Positive internal pressure will act towards the roof
(IS:875-pt.3, Sec 6.3.3.3) while negative internal pressure will be away
= area of obstruction perpendicular to wind / from the roof. As per note below Table 9, each
min. area under canopy perpendicular to wind slope of the duo pitch canopy should be able to
withstand forces using both the max. and min.
Now depending on position as upwind or coefficients, and the whole canopy should be able
downwind, effect is to be considered. Only for to support forces using one slope at the max.
downwind obstruction is to be considered. For coefficient with the other slope at the min.
upwind blockage = 0 is to be used
Hence, the design roof pressure combinations
Design Pressure Coefficients for Roof: would be as given in figure 16.2.
Table 16-1
mid zone gable ends eaves zone ridges
= 0, +ve +0.9 +1.9 +1.4 +0.4
= 0, -ve -0.9 -1.7 -1.4 -1.8
= 1, +ve +0.9 +1.9 +1.4 +0.4
= 1, -ve -1.5 -2.2 -1.9 -2.8
Therefore, the fasteners shall be designed for computed with Ka = 1. Therefore, pd = 1.3254
increased force as per Cpnet = –2.8 to –1.7, 0.9 = 1.193 kN/m2
according to . The spacing in all end zones,
extending upto L/10 = 5m at gable ends and w/10 Force on facia shall be used for the design of truss
= 1 m at eaves and ridges shall be reduced and columns.
appropriately.
Figure 16-2: Net Roof Pressure Coefficients for different zones and combinations
Both slopes at –ve pressure coefficients and = 0 (case 1)
0.8 0.8
1.3
1.3
Both slopes at –ve pressure coefficients and = 1 (case 3)
1.2 1.2
1.3
1.3
One slope at –ve and other at +ve pressure coefficient and = 0 (case 5)
0.8 0.4
1.3
One slope at -ve and other at +ve pressure coefficient and = 1 (case 6)
1.2 0.4
1.3
= 0o
= 15o
5m
5m
5m
50 m
Fig. – 17.1
Solution:
Wind Data: pd = pZ KdKa =1.32540.9 0.8 = (0.9544)
1. Wind Zone: Zone IV (Vb= 47m/s) kN/m2, for roof
(IS:875-pt.3, Sec 5.2) (IS:875.pt.3, Sec 6.2)
2. Terrain category: Category 2
Refer note below Sec. 5.3 of IS:875-pt.3 for
Design Factors: buildings less than 10m height, while making
Risk Coefficient factor ‘k1’ = 1.00 stability calculations and design of the frame.
(IS:875-pt.3, Sec 5.3.1, Table-1)
Terrain & Height factor ‘k2’ = 1.00 Wind Load Calculations:
(IS:875-pt.3, Sec 5.3.2.2, Table-2) F = (Cpe-Cpi) A pd
Topography factor ‘k3’ = 1.00 (IS:875-pt.3, Sec 6.3.1)
(IS:875-pt.3, Sec 5.3.3.1)
Importance Factor for Cyclonic Region k4 =1.00
(IS:875-pt.3, Sec 5.3.4) Net Pressure Coefficients
Wind Directionality factor ‘Kd’ = 0.90
(IS:875-pt.3, Sec 6.2.1) With roof angle 15o : h/w = 0.5 & L/w = 5
Area Averaging factor ‘Ka’ = 0.80*, for Roof (IS:875-pt.3, Table 9)
(IS:875-pt.3, Sec 6.2.2, Table-4) Max. +ve roof pressure, for = 0 = +0.5
* The value of Ka is dependent on the tributary area.
Thus, Ka may be computed by working out the
Max. -ve roof pressure, for = 0 = -0.6
tributary area for different elements, and using Table 4 Max. +ve roof pressure, for = 0.82* =+0.5
of IS:875-pt.3, as illustrated in some of the previous Max. -ve roof pressure, for = 0.82* =-0.76
examples.
Calculating solidity ratio, :
Design Wind Pressure (IS:875-pt.3, Sec 6.3.3.3)
Design Wind Speed = VZ = Vbk1k2k3k4 = = area of obstruction perpendicular to wind / min.
471.01.01.01.0 = 47.00 m/s area under canopy perpendicular to wind
(IS:875.pt.3, Sec 5.3) = {3/(5-5 tan 15o) = 3/3.66 = 0.82. Assuming
pZ = 0.6 (VZ) = 0.6 (47.00)2 = 1325.4 N/m2
2
3m height blockage. For upwind blockage = 0 is
(IS:875-pt.3, Sec 6.2) to be used.
Design Pressure Coefficients for Roof: Hence, the design roof pressure combinations
Positive internal pressure will act towards the roof would be as shown in Fig. 17.2.
while negative internal pressure will be away
from the roof. As per note below Table 9, each Local Pressure Coefficients :
slope of the duo pitch canopy should be able to Local pressure coefficients for design of cladding
withstand forces using both the max. and min. and fasteners obtained from IS:875-pt.3, Table 9
coefficients, and the whole canopy should be able are given below:
to support forces using one slope at the max.
coefficient with the other slope at the min.
Table 17-1
mid zone gable ends eaves zone ridges
= 0, +ve +0.6 +1.5 +0.7 +1.4
= 0, -ve -0.8 -1.3 -1.6 -0.6
= .82, +ve +0.6 +1.5 +0.7 +1.4
= .82, -ve -1.05 -1.63 -1.85 -1.09
Therefore, the fasteners shall be designed for Cpnet However, for the use of the local pressure
= 1.85. The spacing in all end zones, extending coefficients, the design pressure pd will be
up to L/10 = 5m at gable ends and w/10 = 1m at computed with Ka = 1. Therefore, pd = 1.3254
eaves and ridges, shall be reduced accordingly. 0.9 = 1.193 kN/m2
Fig. 17.2 Net Roof Pressure Coefficients for different zones and combinations
One slope at –ve and other at +ve pressure coefficients and = 0 (case 5)
0.6 0.5
One slope at -ve and other at +ve pressure coefficients and = 0.82 (case 6)
0.76 0.5
= 0o
20 m
10o
3m
Fig. – 18.1
Solution:
Wind Data: Area Averaging factor ‘Ka’ = 0.80*, for Roof
1. Wind Zone: Zone IV (Vb= 47m/s) (IS:875-pt.3, Sec 6.2.2, Table-4)
(IS:875.pt.3, Sec 5.2) * The value of Ka is dependent on the tributary area.
2. Terrain category: The structure is located near Thus, Ka may be computed by working out the
to city center where there will be numerous tributary area for different elements, and using Table 4
structures of medium height. This corresponds to of IS:875-pt.3, as illustrated in some of the previous
examples.
the Terrain Category 3.
Depending on the type of development, an
intermediate condition between category 2 and 3 Design Wind Pressure
may also be selected and factor ‘k2’ may be taken Design Wind Speed = VZ =Vbk1k2k3k4 =
as mean-value. 471.00.911.01.0 = 42.77 m/s
(IS:875-pt.3, Sec 5.3.2.1) (IS:875-pt.3, Sec 5.3)
pZ = 0.6 (VZ)2 = 0.6 (42.77)2 = 1097.56 N/m2
Design Factors: (IS:875-pt.3, Sec 6.2)
Risk Coefficient factor ‘k1’ = 1.00 pd = pZ KdKa =1.0970.90.8 = 0.79
(IS:875-pt.3, Sec 5.3.1, Table-1) kN/m2 , for roof
Terrain & Height factor ‘k2’ = 0.91 IS:875-pt.3, Sec 6.2)
(IS:875-pt.3, Sec 5.3.2.2, Table-2) Refer note below IS:875-pt.3, Sec. 5.3 for
Topography factor ‘k3’ = 1.00 buildings less than 10m height, while making
(IS:875-pt.3, Sec 5.3.3.1) stability calculations and frame designing.
Importance factor for Cyclonic Region ‘k4’=1.00 Wind Load Calculations:
(IS:875-pt.3, Sec 5.3.4) F = (Cpe-Cpi) A pd
Wind Directionality factor ‘Kd’=0.90 (IS:875-pt.3, Sec 6.3.1)
(IS:875-pt.3, Sec 6.2.1)
Net Pressure Coefficients
Using the IS:875-pt.3, Table 8 with roof angle 10o Design Pressure Coefficients for Roof:
and solidity ratio = 0 Positive internal pressure will act towards the roof
while negative internal pressure will be away
For h/w = 3.9/5 = 0.78, and L/w = 20/5 = 4, from the roof. Net design pressure coefficient
pressure coefficients are tabulated below (though shall be either +0.5 or –0.9. For cladding and
values are only given for L/w up to 3. fasteners, -1.5 shall be used. In end zones, spacing
of fasteners shall be reduced to account for larger
Max. (largest +ve) overall coefficient = +0.5 local pressures. For cladding design, value of +2.4
should be used.
Max. (largest -ve) overall coefficient = -0.9
Local coefficients: However, for the use of the local pressure
At eaves, up to 0.10 w = 0.10 5 = 0.5 m coefficients, the design pressure pd will be
= +1.6 or –2.1 computed with Ka = 1. Therefore, pd = 1.097 0.9
At ends, up to 0.10 L = 0.10 20 = 2.0 m = 0.987 kN/m2
= +2.4 or –2.0
In mid zone
= +1.2 or –1.5
Example 19 - Wind Pressure and Forces on a Rectangular Clad
Building: Multi-span Saw-tooth Roof
Problem Statement:
Calculate wind pressures and design forces on the walls and roof of a multi-span saw tooth (North light) roof
building having 5 bays of 10m each. The building is 100m long and height to eaves is 10m, as shown in
figure 19.1. The building is situated in Bokaro (WB) in an industrial area 500m inside open land on a fairly
level topography. Walls of building have 40 openings of 1.5m1.5m size. The roof is of GC sheeting & the
roof angle is 150. Calculate also the local wind pressures on roof & wall cladding. The columns & trusses
are at 5m c/c longitudinally, purlins are at 1.4m c/c and columns at Gable ends are at 5m c/c.
= 0o
10 m
10 m
15o
10 m
10 m
10 m
10 m
100 m
Fig. – 19.1
Solution:
Wind Data: (IS:875-pt.3, Sec 5.3.2.2, Table-2)
1. Wind Zone: Zone IV (Vb= 47m/s) Topography factor ‘k3’ = 1.00
(IS:875.pt.3, Sec 5.2) (IS:875-pt.3, Sec 5.3.3.1)
Importance factor for Cyclonic Region ‘k4’= 1.00
2. Terrain category: Category 2 (IS:875-pr.3, Sec 5.3.4)
(IS:875-pt.3, Sec 5.3.2.1) Wind Directionality factor ‘Kd’=0.90
(IS:875-pt.3, Sec 6.2.1)
Note: A combined wind speed profile is to be worked Area Averaging factor ‘Ka’ = 0.80, Short walls,
out as per Appendix – B (Sec 5.3.2.4) but since height for Long walls & Roof*
of boundary layer developed after 500m fetch length is (IS:875-pt.3, Sec 6.2.2, Table-4)
more than building height of 12.68m, only effects due
Area of short (gable) walls = 5 2
to Terrain Category 2 are to be considered. A
combined profile would be needed in case of tall (10+12.68) 0.5 10 = 1134 m2
structures. Area of long walls = 100 12.68 + 100 10
= 2268 m2
Design Factors: Area of roof = 100 10.35 = 1035 m2
Risk Coefficient factor ‘k1’ = 1.00
(IS:875-pt.3, Sec 5.3.1, Table-1) * The value of Ka is dependent on the tributary area.
Terrain & Height factor ‘k2’ = 1.00 for walls, 1.03 Thus, Ka may be computed by working out the
for roofs tributary area for different elements, and using Table 4
of IS:875-pt.3, as illustrated in some of the previous =1.40610.90.8 = 1.0124 kN/m2 (for Roof)
examples.
Wind Load Calculations:
Permeability of the Building: F = (Cpe-Cpi) A pd
Area of all the walls = 1134+ 2268 = 3402 m2 (IS:875-pt.3, Sec 6.3.1)
Area of all the openings =201.51.5 2= 90 m2
% Opening area = 2.65 %, less than 5% Internal Pressure Coefficient Cpi = 0.2
Hence the building is of low permeability. (IS:875-pt.3, Sec 6.3.2.1)
(IS:875-pt.3, Sec 6.3.2.2) Note: buildings shall be analysed once for
pressure of 0.2 from inside and then for a suction
Design Wind Pressure of –0.2 from inside (refer note 2 Sec 6.3.1) along-
Design Wind Speed = VZ = Vbk1k2k3k4 = with external pressure coefficient.
471.01.01.01.0 = 47.00 m/s, for walls
471.01.031.01.0 = 48.41 m/s, for roof External Pressure Coefficients
(IS:875-pt.3, Sec 5.3) Using Tables 5, 6 and 11 (with values in table 11
to take precedence).
hav / w = 11.34/50 = 0.227 & l/w = 100/50 = 2.0
pZ = 0.6 (VZ)2 = 0.6 (47.00)2 = 1325.4 N/m2, for
(IS:875-pt.3, Sec 6.3.3.4)
walls
= 0.6 (48.41)2 = 1406.1 N/m2, for roof
Pressure coefficients for roof are tabulated in
(IS:875-pt.3, Sec 6.2)
Table 19-1.
pd = pZ KdKa =1.32540.90.8
= 0.9543 kN/m2 (for walls)
IS:875-pt.3, Sec 6.2)
Table 19-1
Portion of roof Wind Incidence Angle
0o 90o** 180o
A +0.7 -0.5 -0.2
B -0.9 -0.2/0.2
C -0.9 -0.3
+
D -0.5/0.2 End -1.0 -0.2/0.2
Zones
M -0.5/0.5 Mid -0.5+ -0.4
Zones
N -0.5/0.3 -0.4
W -0.3/0.5 -0.7
X -0.4 -0.3
Y -0.2 -0.5 +0.7
Note: As there is no mention of l/w ratio & extent of End zones, at ends, these can be considered up to width of one
bay i.e. 10 m in this case.
**: Values are from IS:875-pt.3, Table 5 & 7. (=10m) from Gable ends. However, local pressure
+ : Additional values of {-0.05(n-1)}, with n=4 is coefficients are to be considered above these.
applicable in zone E/G for a distance equal to h
Cpe for walls is taken from table 5 for h/w < 0.5
and l/w = 2 and from Table 11. This is as follows:
Table 19-2
Wind angle Short Wall 50 m wide Long wall 100m long
0o -0.6 +0.7/-0.2
90o +0.7/-0.1 -0.5
Design Pressure Coefficients for Roof: added to –ve external pressure coefficient and
vice-a-versa. The combinations will have to be
Positive internal pressure will act towards the roof made separately for all the surfaces, as under:
while negative internal pressure will be away
from the roof. Hence +ve internal pressure will be
B C D M N M N W X
A
B C D M N W X
o
0 wind, Cpi = +0.2 -1.1 -1.1 -0.7 -0.7 -0.7 -0.5 -0.6
0o wind, Cpi = -0.2 -0.7 -0.7 +0.4 +0.7 +0.5 +0.7 -0.2
180o wind, Cpi = +0.2 -0.4 -0.5 -0.4 -0.6 -0.6 -0.9 -0.5
180o wind, Cpi = -0.2 +0.4 -0.1 +0.4 -0.2 -0.2 -0.5 -0.1
90o wind, Cpi = +0.2 ================= -1.2 =====================
(end zones)
90o wind, Cpi = -0.2 ================= -0.8 =====================
(end zones)
90o wind, Cpi = +0.2 ================= -0.8 =====================
(mid zones)
90o wind, Cpi = -0.2 ================= -0.4 =====================
(mid zones)
Analysis of truss is to be done for all above 100 = 10.0m on ends & 0.1 x 10m = 1.0m at
combinations. ridges towards sloping side of roof. In this region
the fasteners shall be designed to carry increased
Design Pressure Coefficients for Walls: force calculated with Cpnet = -2.0 – (+0.2) = -2.2
Cpe will be combined with internal pressure However, for the use of the local pressure
coefficients as earlier, equal to Cpi = 0.2 coefficients, the design pressure pd will be
Cpnet for Walls A or Y = +0.7 – (-0.2) = computed with Ka = 1. Therefore, pd = 1.4061
+0.9, pressure 0.9 = 1.2655 kN/m2
= -0.5 – (+0.2) = -0.7, suction
Cpnet for Gable Walls = +0.7 – (-0.2) = +0.9,
pressure
Problem Statement:
Calculate wind pressure and design forces on a continuous compound wall 2.1m high in RC frame and
masonry construction with barbed wire fencing over it, as shown in figure 20.1, and located in Indore (MP)
to enclose a land piece near the Airport.
2.1 m
3.0 m
Fig. – 20.1
Solution:
Wind Data: Design Wind Pressure
1. Wind Zone: Zone II (Vb= 39m/s)
(IS:875.pt.3, Fig. 1, Sec 5.2) Design Wind Speed = VZ = Vbk1k2k3k4 =
470.921.051.01.0 = 45.402 m/s
2. Terrain category:Category 1 (open land) (IS:875-pt.3, Sec 5.3)
(IS:875-pt.3, Sec 5.3.2.1)
pZ = 0.6 (VZ)2 = 0.6 (45.402)2 = 1236.805 N/m2
Design Factors: (IS:875-pt.3, Sec 6.2)
Risk Coefficient factor ‘k1’ = 0.92* pd = pZ KdKa =1.23680.91.00 =1.113 kN/m2
(IS:875-pt.3, Sec 5.3.1, Table-1) (IS:875-pt.3, Sec 6.2)
Terrain & Height factor ‘k2’ = 1.05 These are to be reduced by 20% as the wall is less
(IS:875-pt.3, Sec 5.3.2.2, Table-2) than 10m high, as per note below section 5.3.
Topography factor ‘k3’ = 1.00 Hence pd = 1.113 0.8 = 0.8905 kN/m2
(IS:875-pt.3, Sec 5.3.3.1)
Importance factor for Cyclonic Region ‘k4’=1.00 Wind Load Calculations:
(IS:875-pt.3, Sec 5.3.4) F = Cf A pd
Wind Directionality factor ‘Kd’=0.90 (IS:875-pt.3, Sec 6.4)
(IS:875-pt.3, Sec 6.2.1)
Area Averaging factor ‘Ka’ = 1.0** Wind Force on Barbed wire fencing:
(IS:875-pt.3, Sec 6.2.2, Table-4) Assuming the solidity ratio of wire fencing and
angles = 0.1
* : though table 1 mentions boundary walls to be Ae = 0.1 1.0 0.6 = 0.06m2, taking 1m length of
designed for 5 yrs. life, but considering 25 years wall.
of period for framed walls. Cf = 1.9, for flat sided single member frames
** : considering tributary area = 3 2.1 = 6.3m2, (IS:875-pt.3, Sec 6.4.3.3, Table 31)
for the design of columns Force on wire fencing per m length = 1.9 0.06
0.8905 = 0.1015 kN
acting at 2.1 + 0.3 = 2.4m above ground.
Reduction factor K = 1 is taken Design Wind Force on walls, therefore
F = 1.55 1.0 0.8905 2.1 = 2.90 kN acting at
Wind Force on wall: 1.05m from ground.
Oblique wind effects as per 6.4.2.3 and now
Since the length of wall is more than 100m, b/h = considered necessary as the wall has l >> b.
100/2.1 = 47.62 and the wall is from ground, Cf =
1.55, after linear interpolation
(IS:875-pt.3, Table 26)
Example 21 - Wind Forces on a Sign Board Hoarding
Problem Statement:
Calculate wind pressure and design forces on a hoarding 10m long and 5m high, to be fixed at the roof of a
24m high building near Cannaught Place area in New Delhi. The base of the hoarding board is 2.0m above
the roof level. See figure 21.1.
5m
10 m
2m
1m
= 0o
24 m
Fig. – 21.1
Solution:
Wind Data: Topography factor ‘k3’ = 1.00
1. Wind Zone: Zone IV (Vb= 47m/s) (IS:875-pt.3, Sec 5.3.3.1)
(IS:875.pt.3, Fig. 1, Sec 5.2) Importance factor for Cyclonic Region ‘k4=1.00
2. Terrain category: Category 3 (near City Center) (IS:875-pt.3, Sec 5.3.4)
(IS:875-pt.3, Sec 5.3.2.1) Wind Directionality factor ‘Kd’=0.90
(IS:875-pt.3, Sec 6.2.1)
Design Factors: Area Averaging factor ‘Ka’ = 1.0***
Risk Coefficient factor ‘k1’ = 0.71* (IS:875-pt.3, Sec 6.2.2, Table-4)
(IS:875-pt.3, Sec 5.3.1, Table-1) * : considering design life of 5 yrs.
Terrain & Height factor ‘k2’ = 1.05** **: For average height of the hoarding, 28.5 m
(IS:875-pt.3, Sec 5.3.2.2, Table-2)
*** : considering tributary area = 5 2.0 = Design Wind Force on hoarding, therefore
10.0m2, for the design of Frame supports F = 1.2 1.0 0.6633 5.0 = 3.98 kN acting at (2
+ 2.5) = 4.5m above roof
Design Wind Pressure
To allow for oblique winds, force coefficients of
Design Wind Speed = VZ = Vbk1k2k3k4 = 1.7 and 0.44 are to be taken at two ends, as per
470.711.051.01.0 = 35.04 m/s section 6.4.2.3.
(IS:875-pt.3, Sec 5.3)
Accordingly, 3.98 1.7/1.2 = 5.64 kN at
windward edge and
pZ = 0.6 (VZ)2 = 0.6 (35.04)2 = 736.62 N/m2 3.98 0.44/1.2 = 1.46 kN at leeward edge shall be
(IS:875-pt.3, Sec 6.2) considered, per meter width of hoarding.
pd = pZ KdKa =0.7370.91.00 =0.6633 kN/m2
(IS:875-pt.3, Sec 6.2) Pressure distribution
In vertical direction the wind force may be
Wind Load Calculations: considered constant over the height.
F = Cf A pd
(IS:875-pt.3, Sec 6.4) The hoarding sheet will be designed for a force of
5.64/5 = 1.128 kN/m2
Wind Force on Hoarding:
The frame of hoarding will be designed for
Since the length of hoarding is 10m, b/h = 10/5 = average pressure intensity depending on the
2.0 and the hoarding is 2m above roof, Cf = 1.2 spacing of vertical frames.
(IS:875-pt.3, Table 26)
Example 22: Wind Pressure and Forces on an Overhead Intze Type
RCC Water Tank on Framed Staging
Problem Statement:
Calculate design wind pressure on a circular overhead water tank of Intze type, supported on a 12-column
staging 12m high, as shown in figure-22.1. The columns are 40 cm dia and the braces 20 cm 40 cm. The
tank is proposed to be constructed in a residential locality of New Delhi.
1.5 m
12m 4m
2m
12 m
8m
Fig. 22.1
Solution:
Wind Data: Design Wind Pressure
1.Wind Zone: Zone IV (Vb= 47m/s)
Design Wind Speed` = VZ = Vb*k1*k2*k3*k4
(IS:875-pt.3, Sec 5.2, Fig. 1)
2.Terrain Category: A residential locality = 47*1.07* k2*1.0*1.0 = (50.3* k2) m/s
corresponds to Terrain Category 3, as defined in IS-
(IS:875-pt.3, Sec 5.3)
875
pZ = 0.6 (VZ)2 & pd = pZ *Kd*Ka
(IS:875-pt.3, Sec 5.3.2.1)
(IS:875-pt.3, Sec 5.4 & Sec 6.2)
Design Factors:
Wind Load Calculations:
Risk Coefficient Factor k1 =1.07
External pressure coefficients for roof and bottom of
(IS:875-pt.3, Sec 5.3.1, Table-1)
tank:
Terrain & Height Factor k2 , varies with height and
(z/H) – 1 = (19.5/7.5) – 1 = 1.6
is given in Table 22.1.
(IS:875-pt.3, Sec 6.3.3.8, Table 20)
(IS:875-pt.3, Sec 5.3.2.2,Table-2)
Therefore, Cpe = -0.75 for roof and –0.6 for bottom.
Topography Factor k3 = 1.00
Eccentricity of force at roof
(IS:875-pt.3, Sec 5.3.3.1)
= 0.1 x D = 0.1 x 12 = 1.2m
Importance Factor for Cyclonic Region k4 = 1.00
(IS:875-pt.3, Sec 5.3.4)
Total force acting on the roof of structure
Wind Directionality Factor Kd =1.00
P = 0.785 x D2 x (pi - Cpe x pd)
(IS:875-pt.3, Sec 6.2.1)
= 0.785 x 122 x {0-(-.75) x 1.082}
Area Averaging Factor Ka =1.00, for Staging
= 91.732 kN acting upwards at 1.2m from center
= 0.842*, for tank portion
of dome
(IS:875-pt.3, Sec 6.2.2, Table-4)
(IS:875-pt.3, Sec 6.3.3.8)
* : area of tank (cylindrical and conical part) = 12 x
4 + 10 x 2 = 68 m2
Note: pi, the internal pressure inside the tank may be = 0.955 kN/m2 at bottom
due to any liquid stored or for water tanks where This being a very small difference, higher value may
there is no pressure due to stored water, internal be taken.
pressure will be generated due to small permeability
which may exist due to openings at roof level e.g. in Fconicaldome = 0.7 x 10 x 1.173
steel tanks. If no openings exist, as in RCC water = 8.211 kN/m height
tanks, pi = 0.
Staging:
Roof pressure will be used with Gravity loads for pd = 1.257 x 1 x 1 = 1.257 kN/m2 up to 10m
design of dome. = 1.324 x 1 x 1 = 1.324 kN/m2 above 10m height.
Overall Horizontal Force on the Tank: In order to calculate the wind force on columns,
F = Cf x Ae x pd each column is considered as an individual member
(IS:875-pt.3, Sec 6.4) (IS:875-pt.3, Sec 6.4.2.2, table 25) and no shielding
No horizontal force will act on top dome. The effect effect is considered on leeward columns, as the
of wind pressure on dome has been included in the columns are placed far apart on periphery only .
net vertical force, as above, associated with an
eccentricity. Therefore, for one column:
Vz x b = 42.96x0.4 = 17.2 > 6
Cylindrical portion: h/b = 11.4/0.4 = 28.5 > 20
Vz (avg) = (46.276+44.16)/2 = 45.218 m/s Therefore, Cf = 1.2, from table 25 for rough surface
Vz x b = 45.218x12 = 542 > 6, finish.
h/b = 4/12 = 0.333 < 2 Fcolumn = 1.2 x 0.4 x 1.257
= 0.603 kN/m height, up to 10m height
Therefore, Cf = 0.7, from table 25(rough) & Fcolumn = 1.2 x 0.4 x 1.324
pd = 1.50 x 1.0 x 0.842 = 0.6355 kN/m height, above10m height
= 1.263 kN/m2 at top & Fbracings =1.0 x {2 x (8.0-7x.4)} x 1.257
= 1.393 x 1.0 x 0.842 =13.072 kN/m height, acting at two brace
= 1.173 kN/m2 at bottom levels, 4m and 8m. This is calculated considering it
as an individual member and using table 25 with h/b
This being a very small difference, higher value may ratio < 2. (Assuming 0.2x0.4m size braces)
be taken.
Fcylinder = 0.7 x 12 x 1.263 Fringbeam = 1.0 x 8.0 x 1.324
= 10.61 kN/m height = 10.592 kN/m height, as above.
Conical bottom: Note: Cf values taken from Table 25 are for members of
Vz (avg) = (44.16+42.96)/2 = 43.56 m/s infinite length. Reduction factors for finite length of
Vz x b = 43.56x10 = 435 > 6, container, columns and other members can be taken from
h/b = 2/10 = 0.2 < 2 Table 29, which will further reduce wind forces.
****************************
Therefore, Cf = 0.7, from table 20 &
pd = 1.393 x 1.0 x 0.842
= 1.173 kN/m2 at top &
= 1.324 x 1.0 x 0.842
Table 22-1: Calculations of Variation in Design Wind Speed & Pressure with Height
Height from k2 * VZ pZ pd
Ground, m m/s kN/m2 kN/m2
**********************
Example 23: Wind Pressure and Forces on a Square Overhead
RCC Water Tank on Framed Staging
Problem Statement:
Calculate design wind pressure on a square overhead RCC water tank of size 12m x 12m supported on a
16-column framed staging 12m high, as shown in figure-23.1. The columns are 400mm square and the
braces 20 cm 40 cm. The tank is proposed to be constructed in a residential locality of New Delhi.
12m
4m
12 m
Fig. 23.1
Solution:
Wind Data: = 0.87*, for tank portion
1.Wind Zone: Zone IV (Vb= 47m/s) (IS:875-pt.3, Sec 6.2.2, Table-4)
(IS:875-pt.3, Sec 5.2, Fig. 1) *: exposed area of tank container =12 x 4= 48m2
2.Terrain Category: A residential locality
corresponds to Terrain Category 3, as defined in Design Wind Pressure
IS-875 Design Wind Speed` = VZ = Vb*k1*k2*k3*k4
(IS:875-pt.3, Sec 5.3.2.1)
= 47*1.07* k2*1.0*1.0 = (50.3* k2) m/s
Design Factors: (IS:875-pt.3, Sec 5.3)
Risk Coefficient Factor k1 =1.07 pZ = 0.6 (VZ)2 & pd = pZ *Kd*Ka
(IS:875-pt.3, Sec 5.3.1, Table-1) (IS:875-pt.3, Sec 6.2 & Sec 6.2)
Terrain & Height Factor k2 , varies with height
and is given in Table 23.1. Wind Load Calculations:
(IS:875-pt.3, Sec 5.3.2.2,Table-2) External pressure coefficients for roof and
Topography Factor k3 = 1.00 bottom of tank:*
(IS:875-pt.3, Sec 5.3.3.1) (z/H) – 1 = (16/4.0) – 1 = 3.0
Importance Factor for Cyclonic Region k4 = 1.00 H/D = 4/12 = 0.333
(IS:875-pt.3, Sec 5.3.4) (IS:875-pt.3, Sec6.3.3.8, Table 20)
Wind Directionality Factor Kd =0.9 *: as there is no direct mention about square or
(IS:875-pt.3, Sec 6.2.1) rectangular tanks, parameters from different clauses
Area Averaging Factor Ka =1.00, for Staging of code are to be taken.
Therefore, Cpe = –0.65 for roof & –0.6 for Solidity ratio of one frame = (4 x 0.4 x 12 + 10.4
bottom. x 0.4 x 2)/ (12 x 12) = 0.19
Eccentricity of force at roof = 0.1 x D = Cf = 1.8, for windward frame members.
= 0.1 x 12 = 1.2m
Shielding Effect on leeward frame:
The total force acting on the roof of the tank Frame- spacing ratio = 4.0/0.4 = 10 = = 1.0
= Ae x (pi – Cpe x pd) = 12x12x {0-(-0.65)x1.35} Hence no shielding occurs.
= 126.36 kN acting upwards at 1.2 m from
center. Alternatively considering each column/bracing
Note: pi, the internal pressure inside the tank may be as an individual member, for columns:
due to any liquid stored or for water tanks where Vz x b = 42.96x0.4 = 17.2 > 10
there is no pressure due to stored water, internal h/b = 12/0.4 = 30 > 20
pressure will be generated due to small permeability
Therefore, Cf = 1.2, from table 25 for rough
which may exist due to openings at roof level e.g. in
steel tanks. If no openings exist, as in RCC water
surface finish. The higher value of Cf i.e. 1.8 is
tanks, pi = 0. used
Roof pressure will be used with Gravity loads Fcolumn = 1.8 x 0.4 x 1.131
for design of slab. = 0.814 kN/m height, up to 10m height
Fcolumn = 1.8 x 0.4 x 1.192
Overall Horizontal Force on the Tank: = 0.858 kN/m height, above10m height
F = Cf x Ae x pd
(IS:875-pt.3, Sec 6.4, 6.4.2.2) for Bracings:
Vz x b = 42.96x0.4 = 17.2
Container portion: h/b = 0.4/3.466 = 0.155 < 2
b/d = 1, Vz x b = 49.19 x 12 = 590>10, H/b=0.33 Therefore, Cf = 1.0, from table 25 for rough
Cf = 0.5, from table 25. surface finish.
Height from k2 * VZ pZ pd
Ground, m m/s kN/m2 kN/m2
Up to 10m 0.91 45.774 1.257 1.131 (for staging)
12m 0.934 46.98 1.324 1.192 (for staging)
1.037 (for tank)
16m 0.978 49.19 1.451 1.137 (for tank)
k2 values are linearly interpolated.
**********************
Example 24: Wind Pressure and Forces on an Overhead Intze Type
RCC Water Tank on Shaft Staging
Problem Statement:
Calculate design wind pressures on a circular overhead water tank of Intze type, supported on an RC shaft
staging 12m high, as shown in figure 24.1. The tank is proposed to be constructed in a residential locality of
New Delhi.
1.5 m
12 m
4m
2m
RCC Shaft
8m (o/o)
12 m
Fig. - 24.1
Solution:
Wind Data: Design Wind Pressure
1.Wind Zone: Zone IV (Vb= 47m/s) Design Wind Speed = VZ = Vb*k1*k2*k3*k4
(IS:875-pt.3, Sec 5.2 Fig. 1) = 47*1.07* k2*1.0*1.0 = (50.3* k2) m/s
2.Terrain Category: A residential locality (IS:875-pt.3, Sec 5.3)
corresponds to Terrain Category 3. pZ = 0.6 (VZ)2 & pd = pZ *Kd*Ka
(IS:875-pt.3, Sec 5.3.2.1) (IS:875-pt.3, Sec 6.2 & Sec 6.2)
Design Factors:
Risk Coefficient Factor k1 =1.07 Wind Load Calculations:
(IS:875-pt.3, Sec 5.3.1, Table-1) External pressure coefficients for roof of tank:
Terrain & Height Factor k2 = Varies with height, (IS:875-pt.3, Sec 6.3.3.8)
and is given in Table 23.1 (z/H) – 1 = (19.5/7.5) – 1 = 1.6
(IS:875-pt.3, Sec 5.3.2.2,Table-2) (IS:875-pt.3, Table 20)
Topography Factor k3 = 1.00 Therefore, Cpe = -0.75 for roof
(IS:875-pt.3, Sec 5.3.3.1) Eccentricity of force at roof
Importance Factor for Cyclonic Region k4 = 1.00 = 0.1 x D = 0.1 x 12 = 1.2m
(IS:875-pt.3, Sec 5.3.4)
Wind Directionality Factor Kd =1.00 Total vertical force acting on the roof of structure
(IS:875-pt.3, Sec 6.2.1) P = 0.785 x D2 x (pi - Cpe x pd)
Area Averaging Factor Ka =0.805*, for Staging = 0.785 x 122 x {0-(-.75) x 1.082}
= 0.842**, for tank = 91.732 kN acting upwards at 1.2m from center
portion (IS:875-pt.3, Sec 6.2.2, Table-4) of dome
* : area of shaft = 12.0m x 8.0m = 96m2 (IS:875-pt.3, Sec 6.3.3.8)
** : area of tank (cylindrical and conical part) Note: pi, the internal pressure inside the tank may be due
=12 x 4 + 10 x 2 = 68 m2 to any liquid stored or for water tanks where there is no
pressure due to stored water, internal pressure will be Conical bottom:
generated due to small permeability which may exist due Vz (avg) = (44.16+42.96)/2 = 43.56 m/s
to openings at roof level e.g. in steel tanks. If no Vz x b = 43.56x10 = 435 > 6,
openings exist, as in RCC water tanks, pi = 0. h/b = 2/10 = 0.2 < 2
Therefore, Cf = 0.7, from table 25, for rough
Roof pressure will be used with Gravity loads for surface &
design of dome. pd = 1.393 x 1.0 x 0.842
= 1.173 kN/m2 at top &
Overall Horizontal Force on the Tank: = 1.324 x 1.0 x 0.842
F = Cf x Ae x pd = 1.115 kN/m2 at bottom
(IS:875-pt.3, Sec 6.4,6.4.2.2) This being a very small difference, higher value
No horizontal force will act on top dome. The may be taken.
effect of wind pressure on dome has been included Fconicaldome = 0.7 x 10 x 1.173
in the net vertical force, as above, associated with = 8.211 kN/m height
an eccentricity. Staging:
Cylindrical portion: Shaft is considered as circular member with rough
Vz (avg) = (46.276+44.16)/2 = 45.218 m/s roughness at surface for which
Vz x b = 45.218x12 = 542 > 6, Vz x b = 42.96 x 8.0 = 343 > 6,
h/b = 4/12 = 0.333 < 2 h/b = 12.0/8.0 = 1.5 < 2
Therefore, Cf = 0.7, from table 25, for rough Therefore, Cf = 0.7, from table 25, for rough
surface & surface
pd = 1.50 x 1.0 x 0.842 Fshaft = 0.7 x 8.0 x 1.257 x 0.805
= 1.263 kN/m2 at top & = 5.67 kN/m height, up to 10m height
= 1.393 x 1.0 x 0.842
= 1.173 kN/m2 at bottom Fshaft = 0.7 x 8.0 x 1.324 x 0.805 = 5.97 kN/m
This being a very small difference, higher value height, above10m height
may be taken.
Note: Cf values taken from Table 25 are for members of
Fcylinder = 0.7 x 12 x 1.263 infinite length. Reduction factors for finite length of
= 10.61 kN/m height container, columns and other members can be taken
from Table 25, which will further reduce wind forces.
Table24-1: Calculations of variation in design wind speed & pressure with height
Height from k2 * VZ pZ
Ground, m m/s kN/m2
Up to 10m 0.91 45.773 1.257
12m 0.934 46.98 1.324
14m 0.958 48.187 1.393
18m 0.994 50.00 1.50
* : k2 values are linearly interpolated.
51 m
Sea Front
12 m
18 m
96 m
Sea Front
12 m
24 m
Fig. – 26.1
(i) For base floor (s = 0) B. Wind from Sea (on smaller face)
h = 96m, d = 24m, b = 12 m, Lh =149.62 m
Bs= 1/[1+(.26962+.46 242)0.5 / ()123.22] = na= I/T = 24 /(0.09 96) = 0.567 Hz,
.71 = 0.016
Hs = 1+(0/96)2 = 1.0, Vh = 48.0 m/s at h = (IS:875-pt.3, Table 36)
96 m
gR = 2 log e (3600 0.40) = 3.814 (i) For base floor (s = 0)
Ih = .1018 for Terrain Category 4 Bs= 1/[1+.26962+.46 122)0.5 / (149.62)]
(IS:875-pt.3, Sec. 5.5) = 1.33
Hs = 1+(0/96)2 = 1.0, Vh = 60.5 m/s
gR = 2 log e (3600 0.567) = 3.904
Ih = 0.110 for Terrain Category 1
(IS:875-pt.3, Sec. 5.5)
gv = 3
S=1/[1+(3.5x.567x96)/34.5][1+(4x.567x12)/
34.5]
=.086
N =na Lh /vh
= 0.567149.62 / 34.5
= 2.46
E = N / (1+70.8N2)5/6 =.05
A. Wind onto wider face (short afterbody
Ø =gvIh Bs/2 orientation)
= 3x.1018x1.33 /2 = 0.173 For z = h
G = 1+r[gv Bs (1+ Ø)2+(Hsxgr2xSxE)/ ] Vz
=1+2x.1018x[32x1.33x(1+.173)2+(1x3.92x Vn
0.086x.05)/.016] f 0 b(1 g v I h )
= 1.91
(ii) Floor level at mid-height (s=48m) 48.0
2.75
Hs = 1.25, Bs = 0.85, 0.4 24 1 3.5 0.235
Ø = 3x.1018x0.85 /2 = 0.138 Ih = 0.261 (at 2h/3 height)
G = 1+r[gv Bs (1+ Ø)2+(Hsxgr2xSxE)/ ]
=1+2x.1018x[32x0.85x(1+.138)2+(1.25x Using dashed line of IS:875-pt.3, Fig-12
3.8142x0.086x.05)/.016]
= 1.78 Log10 Cfs = -3.0 ; Cfs = 0.0010
(iii) Top floor level (s = 96 m)
Hs = 2.0, Bs = 0.95, 24
C dyn 1.5 3.814
1.00
11.0 0.0010
12 1 3.5 0.261
2
Ø = 3x.1018x0.95 /2 = 0.146 0.02
G = 1+r[gv Bs (1+ Ø)2+(Hsxgr2xSxE)/ ] = 1.24
=1+2x.1018x[32x0.95x(1+.146)2+(2x However, at the base the 0.261 mode shape
3.8142x0.086x.05)/.016] deflection is zero and varies linearly with
= 1.88 height in this case as k = 1.
Table 26.2 : Calculations of variation in design pressure with height
Height from pZ (kN/m2) pd, for building pd, for
cladding
ground, m Sea face Other face Sea face Opp. Sea face Wide faces All
faces*
Up to 9m 1.097 0.848 0.987 0.763 0.763 0.987
12m 1.156 0.848 1.040 0. 763 0. 763 1.404
18m 1.310 0.848 0.179 0. 763 0. 763 1.179
24m 1.406 0.998 1.265 0.898 0.897 1.265
30m 1.489 1.247 1.340 1.122 1.122 1.34
36m 1.80 1.349 1.62 1.214 1.214 1.62
42m 1.845 1.456 1.660 1.311 1.311 1.66
48m 1.893 1.566 1.704 1.410 1.410 1.704
54m 1.924 1.627 1.732 1.464 1.464 1.732
60m 1.947 1.662 1.752 1.496 1.496 1.752
66m 1.973 1.698 1.776 1.528 1.528 1.776
72m 1.992 1.734 1.793 1.560 1.560 1.793
78m 2.017 1.771 1.815 1.594 1.594 1.815
84m 2.041 1.808 1.837 1.627 1.627 1.837
90m 2.064 1.845 1.857 1.660 1.660 1.86
96m 2.087 1.883 1.878 1.695 1.695 1.878
Notes: For cladding, only higher wind speed is used for all four faces. However, the designer may
choose to vary it face to face.
Example 27 - Wind Pressure and Forces on a Microwave Tower
by Force Coefficient Method
Problem Statement:
Calculate design wind forces using Force Coefficient method on a square Microwave Tower 21m tall,
as in figure 27.1, situated in Roorkee. It is proposed to be constructed in an open terrain with well
scattered obstructions having heights generally between 1.5 to 1.0 m. A Microwave antenna shaped in
the form of a hemispherical bowl with 1.2m diameter is to be placed at the top.
Solution:
The calculation of solidity ratio for panel 1 and 2 are shown below:
For Panel 1
(2x3x0.2)+(2x0.065x3.35)
Φ1 =
½ (3+2.55)x3
= 0.196
For Panel 2
(2x3x0.2)+(2x0.065x3.8)+(0.065x2.55)
Φ2 =
½ (2.55+2.1)x3
= 0.26
7
Similar calculations are carried out for other panels and their respective force coefficients are
tabulated.
Table 27.1
Effective Force
Panel Solidity
Area, Coefficient,
No. Ratio,(Φ)
Ae(m2) Cf
1 1.636 0.196 3.32
2 1.859 0.267 2.965
3 1.797 0.319 2.705
4 1.739 0.407 2.286
5 0.702 0.39 2.35
6 0.702 0.39 2.35
7 0.702 0.39 2.35
8 0.702 0.39 2.35
9 0.702 0.39 2.35
10 0.762 0.423 2.254
Table 27.2
Forces on antenna
F = Cf x Ae x Pz
= 1.4x1.22xπ/4x1066.477
Forces on nodes
= 1.687 kN (to be distributed at 4 joints of the topmost panel)
(5.013)
F1-4 = = 0.627 kN
8
(5.013+5.087)
F5-8 = = 1.262 kN
8
(5.087+4.486)
F9-12 = = 1.197 kN
8
(4.486+3.705)
F13-16 = = 1.024 kN
8
(3.705+1.607)
F17-20 = = 0.664 kN
8
(1.607+1.655)
F21-24 = = 0.408 kN
8
(1.655+1.688)
F25-28 = = 0.418 kN
8
(1.688+1.707)
F29-32 = = 0.424 kN
8
(1.707+1.727)
F33-36 = = 0.429 kN
8
(1.727+1.819)
F37-40 = = 0.443 kN
8
1.819 1.687
F41-44 = + = 0.649 kN
8 4
Example 28 - Wind Pressure and Forces on a Microwave Tower
by Gust Factor Method
Problem Statement:
Calculate design wind forces using the Gust factor approach on a square Microwave Tower
21m tall, as in figure 28.1, situated in Roorkee. It is proposed to be constructed in an open
terrain with well scattered obstructions having heights generally between 1.5 to 1.0 m. A
Microwave antenna shaped in the form of a hemispherical bowl with 1.2m diameter is to be
placed at the top.
Solution:
Wind Data:
1. Wind Zone: Zone II (Vb= 39m/s) (IS:875-pt.3, Sec 5.2)
(Refer Basic Wind Speed Map (Fig. 1)
2. Terrain category: Terrain Category 2 (IS:875-pt.3, Sec 5.3.2.1)
Design Factors:
Risk Coefficient Factor k1 = 1.06 (IS:875-pt.3, Sec 5.3.1, Table-1)
(Taking design life of 100 years)
Mean Hourly Wind Speed coefficient, k2,i Varies with height and terrain category
(IS: 875-pt.3, Sec 5.4)
Topography Factor k3 = 1.00 (IS: 875-pt.3, Sec 5.3.3.1)
Importance Factor for Cyclonic Region k4 = 1.00 (IS: 875-pt.3, Sec 5.3.4)
Wind Directionality Factor Kd = 0.90 (IS: 875-pt.3, Sec 6.2.1)
Area Averaging Factor Ka = 1.0 (IS: 875-pt.3, Sec 6.2.2, Table-4)
Design Wind Speed Pressure
Design Wind Speed = VZ = Vbk1k2k3k4 = 39 1.06 k2 1.0 1.0 = (41.34 k2) m/s
(IS: 875-pt.3, Sec 5.3)
Design Wind Pressure
pd = 0.6 (VZ)2 x Kd x Ka = 0.6 x (41.34 x k2)2 x 0.9 x 1.0 = 922.86 k22
(IS: 875-pt.3, Sec 6.2, 6.2)
Table 28.1
Height Design
Design wind
from wind
k2 Pressure,
ground, speed,
Pd(N/m2)
m Vz(m/s)
1.5 0.67 27.70 414.27
H g 2 SE
G 1 r gv2 Bs (1 )2 s R
where,
r = a roughness factor which is twice the longitudinal turbulence intensity, Ih
= 2 x 0.17 = 0.34
gv = a peak factor for upwind velocity fluctuation = 3.0 for terrain category 2
Bs = background factor indicating the measure of slowly varying component of fluctuating
wind load caused by the lower frequency wind speed variations
1
0.26(h s ) 2 0.46bsh2
1
Lh
where,
h = 21 m
s = Levels at which action effects are calculated = 0 to 21m.
bsh = average breadth of the structure between heights s and h
Lh = measure of effective turbulence length scale at the height, h in m
0.25
h
= 85 for terrain category 1 to 3
10
0.25
21
= 85 102.323
10
The values of Bs is tabulated in Table 28.3
= factor to account for the second order turbulence intensity
g v I h Bs
=
2
The values of is tabulated in Table 28.3
Hs = height factor for resonance response
2
s
= 1
h
The values of Hs is tabulated in Table 28.3
S = a size reduction factor given by
1
3.5na h 4na boh
na = first mode along wind 1 1 frequency of the structure in Hz
Vh Vh
d 3
0.916 Hz
0.09h 0.09 x 21
h = total height of the main structures of the building in meters, and
d = maximum base dimension in meters in a direction parallel to the applied wind force
b0h = average breadth of the structure between 0 and h
3 2.55 2.1 1.65 (7x1.2)
1.61 m
11
Vh = design mean value wind speed at height, h =
31.05 m/s (from table 1)
So,
1
S= 0.265
3.5 x 0.916 x 21 4 x 0.916 x 1.61
1 31.05 1 31.05
g R = peak factor for resonant response
= 2ln(3600na ) 2ln(3600 x 0.916) 4.025
E = spectrum of turbulence in the approaching wind stream
N 3.141 x 3.02
= 0.0432
1 70.8 N (1 70.8x3.02 2 ) 5/6
5/6
2
where,
na Lh 0.916 x 102.323
N = an effective reduced frequency = 3.02
Vh 31.05
β = 0.02 for bolted steel structures
Table 28.3
Height, m Bs Hs G Forces, kN
1.5 0.911 0.243 1.005 2.595 5.839
4.5 0.924 0.245 1.046 2.616 5.974
7.5 0.936 0.247 1.128 2.651 5.338
10.5 0.950 0.249 1.250 2.698 4.525
Forces on antenna
F = CfxAexPzxG
= 1.4x1.22xπ/4x520.52x2.942
= 2.423 kN (to be distributed at 4 joints of the topmost panel)
Forces on nodes