Electric Motor Drive Installation Procedure
Electric Motor Drive Installation Procedure
electric motor drive and motor circuit. The motor controlled by the electric
motor drive, system power quality, safety, installation factors, and both
power and control wiring all need to be checked for compatibility with the
motor and drive. A properly installed electric motor drive can function cor-
rectly and safely for a long time without introducing any problems into an
existing electrical distribution system.
−650 VDC
233
234 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
Inverter Duty Motors power from an electric motor drive to a standard motor,
An inverter duty motor is an electric motor specifically contact the manufacturer to verify compatibility of the
designed to work with electric motor drives. A PWM motor in a drive circuit.
waveform creates insulation problems for standard Service Factor. Service factor (SF), is a multiplier
electric motors because the leading edge of each PWM that represents the percentage of extra load that can
pulse begins with a voltage spike. A voltage spike is be placed on a motor for short periods of time without
due to the rapid rise time of the IGBTs. A voltage damaging the motor. A motor with a service factor of
spike is typically twice the DC bus voltage of the AC 1.25 can be overloaded by 25% for a short time. Motors
drive. See Figure 9-2. Voltage spikes create damage that are NEMA MG-1, Section IV, Part 31 compliant
insulation and shorten the life expectancy of standard have a service factor of 1.0 per NEMA requirements.
electric motors. Inverter duty motors are designed to A motor that is used with an electric motor drive that is
withstand voltage spikes. not NEMA MG-1, Section IV, Part 31 compliant must
not be operated beyond a service factor of 1.0 regardless
of the nameplate rating.
Lead Length. Lead length is the length of the conduc-
PWM VOLTAGE SPIKES tors (motor leads) between the electric motor drive and
the motor. The motor leads T1, T2, and T3 have a line-
SPIKE ON LEADING to-line capacitance and a line-to-ground capacitance.
EDGE OF PULSE
DAMAGES STANDARD Capacitance increases the magnitude of the voltage spikes
MOTOR INSULATION
+1300 V at the motor terminals. The longer the motor leads, the
greater the capacitance and the greater the magnitude of
+650 V
NORMAL
the voltage spikes.
0
Long lead lengths also cause reflected waves, known
−650 V as standing waves or voltage ring-up. Reflected waves are
dependent on lead length and carrier frequency. The longer
−1300 V
SPIKE the lead length and the higher the carrier frequency, the
more pronounced the problem. Reflected waves are the
SPIKE TYPICALLY result of a portion of the voltage waveform being reflected
TWICE ELECTRIC MOTOR
DRIVE BUS VOLTAGE back from the motor terminal due to an impedance mis-
match. The reflected portion combines with the voltage
from the AC drive, increasing the voltage at the motor ter-
Figure 9-2. The spike on the leading edge of each pulse is
caused by the rapid rise time of the IGBTs.
minals. The voltage can be as high as 1500 V at the motor
terminals when fed from a 480 V electric motor drive.
The easiest way to avoid problems caused by lead
The National Electrical Manufacturers Associa- length is to keep the lead lengths as short as possible.
tion (NEMA) has developed a set of specifications for Typically, lengths less than 100 ft should not pose a
electric motors used with electric motor drives. The problem. It is not always possible to avoid long lead
NEMA standard MG-1, Section IV, Part 31 provides lengths. Electric motors may be located in harsh envi-
an enhanced insulation requirement for electric motors, ronments with the electric motor drive located a long
allowing compatibility with electric motor drives. Most distance away in a clean, air-conditioned control room.
motor manufacturers produce motors to comply with In this case an output reactor, also referred to as a load
NEMA MG-1, Motors and Generators, Section IV, Part reactor, can be installed at the electric motor drive. A
31; these motors are referred to as “inverter rated” or load reactor helps eliminate voltage spikes by slowing
“inverter duty” motors. down the rate of change in the output voltage.
Standard motors that are not compliant with the Load reactors are installed as close as possible to
NEMA MG-1, Section IV, Part 31 standard, and are the output of the electric motor drive. Load reactors are
used with electric motor drives may fail prematurely. sized based on the electric motor drive input voltage and
The speed at which a standard motor fails depends frequency, the drive horsepower, and the impedance of
upon the specific motor application. Before connecting the reactor. See Figure 9-3.
Chapter 9 — Electric Motor Drive Installation Procedures 235
LOAD REACTORS
OUTPUT REACTOR
ELECTRIC MOTOR DRIVE
Jog
EACH COIL
P
WOUND ON
SEPARATE CORE
TERMINAL STRIP FOR
INPUT AND OUTPUT
WIRING
THREE COILS
(ONE FOR
EACH PHASE)
MTE C
Corporation 3φ
MOTOR
Figure 9-3. Output reactors are installed as close as possible to the output of an electric motor drive to reduce the level of
voltage spikes at the motor.
Electric motor drive manufacturers may recommend AC drives are often used in industrial and commercial
output filters instead of load reactors. Output filters are HVAC systems, and are increasingly used in residential
also referred to as motor terminators. Output filters HVAC systems.
consist of inductance, capacitance, and resistance. An Electric motor drive manufacturers provide speci-
output filter may be installed at the output of the electric fications for maximum lead lengths for various carrier
motor drive or at the motor. See Figure 9-4. frequencies and for shielded or unshielded cable with
Another method to diminish the effects of lead output reactors or output filters.
length is to lower the carrier frequency. The result is Bearing Currents. A bearing current is the result of
fewer voltage pulses per unit of time and less stress induced voltage in the motor rotor created by the electric
on the motor insulation. At lower carrier frequencies, motor drive. Bearing current causes premature failure
motors make more audible noise. Noise can be a prob- of motor bearings. The spikes on the leading edge of
lem for people working near the motor or if an HVAC the PWM waveform are induced into the rotor, and a
fan motor transmits the noise through the ductwork. voltage potential is developed between the rotor and the
stator. The bearing race and balls or rollers serve as the
current path for the voltage potential, and a continuous
TECH FACT flow of current through the bearing occurs. The current
Follow manufacturer installation guidelines on motor lead flow causes atoms of metal to be removed. Over time,
length to avoid premature failure of motors. roughness, known as fluting, develops in the race, which
eventually destroys the bearing.
236 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
OUTPUT FILTERS
OUTPUT FILTER
Jog
P
GROUND PER
LOCAL CODES
MTE C
Corporation
3φ
T2 MOTOR
T1
PE (MOTOR FRAME)
Figure 9-4. An output filter/terminator installed at the motor termination box reduces reflected waves.
Electric motor manufacturers have developed shaft electric motor drive through a relay. The leads of a tempera-
grounding systems to eliminate the problem. A shaft ture sensor are labeled J1 (P1) and J2 (P2). When internal
grounding system is a system that connects (shorts) temperatures of a motor exceed safe limits, the temperature
the rotor voltage to ground via a brush or other de- sensor opens, de-energizing the relay, shutting down the
vice in contact with the shaft to discharge unwanted electric motor drive and motor. See Figure 9-6.
voltage. See Figure 9-5. Another method to reduce Operating Temperature. NEMA has standardized the
or eliminate bearing currents is to lower the carrier maximum ambient temperature for motors as 104°F
frequency of the electric motor drive. Bearing currents (40°C). Ambient temperature is the temperature of the
are common in HVAC fan applications. Bearings are air surrounding an object. Electric motors operated at
the only path for the potential to discharge to ground a higher than ambient temperature must be derated.
in fan applications. NEMA has also standardized altitude ratings for motor
Low-Speed Operation. The cooling effect of a fan at- operation. Electric motors are designed to operate up to
tached to the motor shaft, and/or fins that are part of the 3300′ (1000 m). Electric motors operated above 3300′
rotor end ring, is reduced when a motor is operated at low must be derated. The derating is requried because at
speeds. Electric motors that are continuously operated at higher altitudes, air is thinner and does not dissipate
low speeds must be derated or provided with auxiliary cool- heat as quickly. Consult the charts provided by motor
ing. Auxiliary cooling is accomplished by using a separate manufacturers for specific derating tables.
blower and motor mounted to the motor to provide cooling.
Auxiliary blower motors operate on fixed voltages, and are TECH FACT
either ON or OFF. The blower motor must be connected to
Failure to derate or provide auxiliary cooling to
a power source independent of the variable voltage output motors operating at low speeds results in premature
of an electric motor drive. Temperature sensors are installed failure of motors.
in the stator windings of a motor and are connected to an
Chapter 9 — Electric Motor Drive Installation Procedures 237
MOTOR BEARING
RACE SECTION
TOTALLY ENCLOSED
NON-VENTILATED
(TENV) MOTOR
Figure 9-5. A shaft grounding system eliminates bearing currents that lead to bearing failures.
TEMPERATURE SENSOR
RELAY CONTACT
FROM EXTERNAL CONNECTED TO
VOLTAGE SOURCE ELECTRIC MOTOR
ELECTRIC MOTOR DRIVE DRIVE CONTACT
Jog TERMINAL STRIP
P
TEMPERATURE
SENSOR
CR1
RELAY ISOLATES
ELECTRIC MOTOR
DRIVE FROM EXTERNAL
VOLTAGE SOURCE
PE PE DC DC T1/U T3/W The
hermik Corporation
TEMPERATURE
T2 J1 (P1)
T3 SENSOR LEADS
T1
3φ J2 (P2)
MOTOR
Figure 9-6. When excessive motor heat is detected, the temperature sensor opens, de-energizing the relay and sending
a signal to the electric motor drive to stop the motor.
238 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
ELECTRIC
EARTH GROUND MOTOR
PER NEC® DRIVE
L1
Jog
P
L3 L2
DELTA-WYE
TRANSFORMER L1/R L2/S L3/T PE PE
OVERCURRENT
PROTECTION
AND DISCONNECT
OVERCURRENT
PROTECTION
AND DISCONNECT
ELECTRIC
METAL MOTOR
OXIDE DRIVE
L1 VARISTORS
Jog
P
L3 L2
NO PATH FOR DESTRUCTIVE
CURRENT TO RETURN TO
POWER SOURCE
DELTA
TRANSFORMER
L1/R L2/S L3/T PE PE
OVERCURRENT
PROTECTION
AND DISCONNECT
Figure 9-7. Electric motor drives are intended to be powered from 3φ lines with a common ground.
240 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
+VOLTS
CURRENT DRAW
IN SHORT PULSES
-VOLTS
ASI Robicon
PHASE B OR T2
0 L2 CAPACITOR
T3
PHASE C L3
- VOLTS
IGBT
PHASE B OR T2
0 L2 CAPACITOR
T3
PHASE C L3
-VOLTS
MAX
-VOLTS
FLAT-TOPPING IGBT
REDUCES CAPACITY
Figure 9-8. In nonlinear loads, instantaneous load current is not proportional to the instantaneous voltage, allowing flat-
topping to occur and causing electric motor drive faults.
Chapter 9 — Electric Motor Drive Installation Procedures 241
MAIN
DISCONNECT Jog
P
LINE
REACTOR
Figure 9-9.. The effects of inductive and nonlinear loads can be compensated using properly sized power factor capacitors.
FROM DISCONNECT
L1 L2 L3 DRUM MOUNTED
FROM SEPARATE (R) (S) (T) ON MOTOR SHAFT
VOLTAGE SOURCE
CONVERTER
L1 N SECTION SOLENOID
FILTER ENERGIZED,
OPENS BRAKE,
C
SECTION
L
CONTROL LOGIC LOAD ROTATES
CR2
BUS
DC
INVERTER
SECTION
SOLENOID
DE-ENERGIZED,
ELECTRIC SPRING CLOSES,
MOTOR LOAD HELD
BRAKE SOLENOID T1 T2 T3 DRIVE
RELAY CONTROLLED BY (U) (V) (W)
ELECTRIC MOTOR DRIVE BRAKE SHOES
3φ
MOTOR
Figure 9-10. An electromechanical brake is used to hold a motor shaft stationary after voltage is removed from the motor.
ENGINEERED APPLICATIONS the point where full armature voltage is applied with
An engineered application is an electric motor drive full rated field excitation. Operation of a motor above
base speed is governed by the mechanical limits of the
application that requires a licensed engineer to be
rotor, armature, and bearings.
safely implemented. A licensed engineer provides
drawings, answers questions, and oversees the in-
stallation to ensure that it conforms to all applicable ELECTRIC MOTOR DRIVE INSTALLATION
codes. Engineered applications include those where a
motor is operated above its rated base speed, where an An electric motor drive installation process requires
emergency stop button is required, or where a drive is receiving shipment of a drive from a manufacturer,
controlling people-moving equipment. Base speed is selecting a suitable location and enclosure, mounting
the nameplate speed (rpm) at which a motor develops the drive (taking into account derating factors), and
rated horsepower at rated load and voltage. When minimizing electromagnetic interference. Paying close
using an AC motor, base speed is typically the point attention to all installation factors results in a smooth
where nameplate voltage and nameplate frequency start-up and years of trouble-free service.
are applied. When using a DC motor, it is typically
Receiving Drive and Hardware
Upon receipt of an electric motor drive and any associ-
ated hardware, there are several steps to follow:
• Thoroughly inspect the items for any damaged or
WARNING missing parts. Immediately report any problems to
Always consult the electric motor drive manufacturer or the freight company.
licensed engineer regarding drive application questions.
• Verify the size, rating, configuration, etc., of the
Incorrect application of an electric motor drive can result
in serious personal injury or damage to the drive and/or items ordered.
driven load. • Remove the instructions and other documentation,
and store in a safe location for future reference.
Chapter 9 — Electric Motor Drive Installation Procedures 243
Enclosures
Derating
NEMA rates enclosures based on use and service.
Most electric motor drives are delivered from a Electric motor drives are designed for specific op-
manufacturer in NEMA Type 1 enclosures. An elec- erating ranges of temperature, voltage, altitude, and
tric motor drive in a NEMA Type 1 enclosure may humidity. Derating is required if an electric motor
be placed in a suitable environment or in another drive is operated outside the normal operating ranges
encosure. Other NEMA rated enclosures are available specified by the manufacturer. Electric motor drives
for installing electric motor drives in hostile environ- operated above the normal temperature range, from a
ments. See Figure 9-11. 1φ power source or from a power source with reduced
voltage, or at a high altitude, or higher carrier frequen-
An electric motor drive in a NEMA Type 1 enclo-
cies, must be derated. Manufacturers supply charts and
sure may require a NEMA Type 3R enclosure if the
derating multipliers for each particular condition.
enclosure is subjected to falling rain, ice, or other
damaging environments. The enclosure that is to house
the electric motor drive should be mounted, and any
metal debris must be discarded before the drive is in-
stalled in the enclosure. All precautions must be taken
to prevent debris from falling into an electric motor
drive and causing a problem. The person responsible
for installing the electric motor drive must decide
whether the drive can be installed as is or whether it
requires installation in another enclosure.
When an electric motor drive is installed in an
enclosure, heat buildup can be a problem. The elec-
tric motor drive radiates heat and the enclosure may
not be able to dissipate the heat. The heat may cause
electric motor drive faults, or premature component
failure. Extra cooling may be required to supplement
the fan(s) that are integral to the electric motor drive.
Omron IDM Controls
The additional cooling can be in the form of a fan or Cabinets with multiple electric motor drives require extra attention to mounting
a cooling unit. positions, airflow, and derating to avoid heat buildup and drive failures.
244 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
ENCLOSURE SELECTION
ENCLOSURES
Type Use Service Conditions Tests Comments Type
1 Indoor No unusual Rod entry, rust resistance
3 Outdoor
Windblown dust, rain, sleet, and ice Rain, external icing, dust, Do not provide protection against 1
on enclosure and rust resistance internal condensation or internal icing
Rod entry, rain, external Do not provide protection against dust,
3R Outdoor Falling rain and ice on enclosure
icing, and rust resistance internal condensation, or internal icing
Windblown dust and rain, splashing
Hosedown, external icing, Do not provide protection against 4
4 Indoor/outdoor water, hose-directed water, and ice
and rust resistance internal condensation or internal icing
on enclosure
Corrosion, windblown dust and rain,
Hosedown, external icing, Do not provide protection against
4X Indoor/outdoor splashing water, hose-directed
water, and ice on enclosure
and corrosion resistance internal condensation or internal icing 4X
Occasional temporary submersion at
6 Indoor/outdoor
a limited depth
Prolonged submersion at a limited
6P Indoor/outdoor
depth
Withstand and contain an internal Enclosed heat-generating devices shall
Indoor locations classified as explosion of specified gases, contain not cause external surfaces to reach
7 Class I, Groups A, B, C, or D, an explosion sufficiently so an
Explosion, hydrostatic, and
temperature
temperatures capable of igniting 7
as defined in the NEC ® explosive gas-air mixture in the explosive gas-air mixtures in the
atmosphere is not ignited atmosphere
Enclosed heat-generating devices shall
Indoor locations classified as Dust penetration, not cause external surfaces to reach
9 Class II, Groups E or G, as Dust temperature, and gasket temperatures capable of igniting 9
defined in the NEC ® aging explosive gas-air mixtures in the
atmosphere
Dust, falling dirt, and dripping Drip, dust, and rust Do not provide protection against
12 Indoor
noncorrosive liquids resistance internal condensation
Dust, spraying water, oil, and Oil explosion and rust Do not provide protection against
12
13 Indoor
noncorrosive coolant resistance internal condensation
HEATED
AIR OUT
ELECTRIC MOTOR
DRIVE ENCLOSURE Baldor Motors and Drives
Figure 9-11. Depending on the application, an enclosure with a cooling unit may be required.
Chapter 9 — Electric Motor Drive Installation Procedures 245
MOUNTING HOLES
FOR SCREWS
MODULAR ELECTRIC MOTOR DRIVE
MOUNTED IN RACK SLOTS
LARGE
ELECTRIC
MOTOR DRIVE
SMALL ELECTRIC
MOTOR DRIVES
DIN RAIL
Control Techniques
RACK SLOT MOUNT
Danfoss Drives
MEDIUM ELECTRIC MOTOR
DRIVE MOUNTED ON MOTOR MOTOR MOUNT
Figure 9-12. Mounting methods vary with the size of electric motor drive.
An electric motor drive model may have multiple out- High frequency electric-field EMI can emanate from
put ratings, depending on the type of load and the carrier equipment as electromagnetic radiation, also known
frequency used. Constant torque loads require the same as radio frequency interference (RFI). EMI can be re-
current from zero to base speed. Variable torque loads re- ceived by other equipment and interfere with its proper
quire less current at lower speeds. Consequently, an electric operation. EMI problems range from corrupted data
motor drive model typically has higher output ratings for transmissions to electric motor drive damage.
a variable torque load than for a constant torque load. All electrical and electronic equipment should have
Power losses occur when the IGBTs of an electric mo- some level of immunity to EMI. Electromagnetic com-
tor drive are between states (neither ON nor OFF). The patibility (EMC) is a comparison of how different pieces
higher the carrier frequency, the more pulses per unit of of equipment work together with varying levels of in-
time, and the more loss of power the IGBTs create. An terference. As use of electronic equipment in industrial
electric motor drive has lower output ratings at higher environments has increased, manufacturers have taken
carrier frequencies because of IGBT power losses. steps to both minimize emissions and maximize EMI
immunity in the design of equipment.
Electromagnetic Interference Regulations regarding EMC/EMI are very complicat-
Electromagnetic interference (EMI), also known as electri- ed and vary from country to country. A properly installed
cal noise, is the unwanted signals generated by electrical electric motor drive minimizes potential problems from
and electronic equipment. All electrical and electronic EMI. Installation techniques and supplemental devices
equipment generate EMI. Low frequency magnetic-field that minimize emissions and maximize immunity in-
EMI can be emitted from the cables connected to equip- clude wiring techniques, grounding, shielding, and
ment, or from inductive loads in proximity to equipment. isolation of power and signal or control cable.
246 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
Power Wiring. The drive output power wiring (load grounding conductors contained in the cable need to be
conductors) contains high-voltage switching wave- connected at each end.
forms which can affect the line conductors. The line Control Wiring. Control wiring is all external wiring con-
and load conductors of an electric motor drive need to nected to an electric motor drive, excluding the line and
be installed in separate metal conduits. Metal conduit load conductors. Electric motor drives have control wiring
serves as a shield, preventing conductors from radiating that communicate signals to start and stop the drive, com-
EMI and protecting conductors from any radiated EMI. municate sensor conditions to the drive, and carry output
Nonmetallic conduit does not provide the shielding ef- signals from drive auxiliary contacts. See Figure 9-13.
fect. A separate grounding conductor must be installed Control wiring can communicate four types of signals: AC
in each conduit and connected at each end. In the event digital signals, DC digital signals, DC analog signals, and
that multiple electric motor drives feed multiple motors, serial communication signals. Digital signals are signals
the line and load conductors of each drive need to be that have only two states, ON or OFF like a momentary
installed in separate metal conduits. pushbutton. Analog signals are signals that vary over a
When cable trays are used, armored metal cable with range of values such as 0 VDC to 10 VDC for speed refer-
a separate grounding conductor, or shielded power cable ence. Serial communication signals are digital data signals
with a separate grounding conductor, must be used. The from an external source such as a PLC or PC.
D SHELL CONNECTOR
FOR SERIAL COMMUNICATION
1 2 3 4 5 6 7 8 9 10 11
P10 0V AIN AIN DIN1 DIN2 DIN3 P15 0V RL1B RL1C
OUTPUT RELAY
(NORMALLY OPEN)
110 VAC MAX,
POWER ANALOG 1 A/30 VDC MAX, 1 A
SUPPLY INPUTS (RESISTIVE RATING)
DIGITAL INPUTS
(+10 V MAX, (0 V – 10 V)
(7.5 V – 33 V MAX, 5 mA)
10 mA) (2 V – 10 V)
OUTPUT RELAY (NORMALLY OPEN)
110 VAC MAX, 1 A/30 VDC MAX, 1 A
T1/U T2/V T3/W (RESISTIVE RATING)
MOTOR TERMINALS
POTENTIAL
EARTH 12 13 14 15 16 17 18 19 20
(GROUND) DC DC DIN4 DIN5 DIN6 P15 0V AIN AIN RL2B RL2C
DC BUS
TERMINALS
L1/R L2/S L3/T
ANALOG INPUTS
MAIN POWER PE PE (0 V – 10 V) OR
SUPPLY TERMINALS POTENTIAL EARTH (2 V – 10 V)
(GROUND)
POWER SUPPLY FOR P1
DIGITAL INPUTS FEEDBACK TRANSDUCER
(7.5 V – 33 V MAX, 5 mA) OR OTHER LOAD
(+15 V MAX, 50 mA)
Figure 9-13. Power wiring and control wiring are terminated at separate locations on an electric motor drive.
Chapter 9 — Electric Motor Drive Installation Procedures 247
The harmful effects of EMI from control wiring can protective devices (OCPDs). Equipment grounding
be minimized by the following procedure: also aids in containing EMI. All equipment grounds
• Control and power wiring should be separated as much should be brought back to a single point at the elec-
as possible inside an electric motor drive enclosure. If tric motor drive. The connections should be tight and
control and power wiring must cross, they should cross mechanically sound to guarantee a good electrical
at a 90° angle. connection. When making a grounding connection to
• Control wiring should not be installed in the same the interior of a metal enclosure, scrape away any pro-
conduit as power wiring. Control wiring should be tective coating to ensure bare metal-to-metal contact.
installed in a separate metal conduit. See Figure 9-14.
• Install each category of control wiring in its own Control wires carry analog signals and serial com-
metal conduit. munication signals using twisted shielded pair cable. A
• DC analog signals and serial communication signals shield is constructed of metal foil or mesh and a bare
should run in twisted shielded pair cable. wire wrapped around the twisted conductors. The bare
Grounding. Proper grounding is required for the safe and wire is also referred to as the drain wire. The shield/drain
reliable operation of electric motor drives, motors, and wire and the twisting of the conductors provide en-
related equipment. Grounding requirements can be divided hanced noise protection. The shield/drain wire is only
into equipment grounding and signal wire grounding. grounded at the electric motor drive end. A shield/drain
Equipment grounding is an equal potential between wire that is grounded at both ends introduces EMI into
all metal components of an installation and a low-im- the signal circuit because of the difference of potential
pedance path for fault currents to operate overcurrent between the two points of grounding.
L1
AC MAIN SUPPLY
L2
CONNECT ALL WIRES
CON
T1, T2, T3, AND
T1
EQUIPMENT GROUND INSIDE
4-WIRE DELTA-WYE
TRANSFORMER
ROUTE ALL WIRES L1, L2, L3, ROUTE ALL WIRES T1, T2, T3,
AND EQUIPMENT GROUND AND EQUIPMENT GROUND
TOGETHER IN ONE CONDUIT TOGETHER IN ONE CONDUIT
Figure 9-14. Equipment grounds for line and load conductors are terminated at the electric motor drive.
248 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
Inductive Loads. Inductive loads such as solenoids or INDUCTIVE LOAD EMI SUPPRESSION
the coils of relays and contactors are a source of EMI.
When inductive loads are de-energized, a large counter
FROM
electromotive force (CEMF) is generated. CEMF is OUTPUT POWER SOURCE
DEVICE COIL
a voltage spike created by the inductive loads when
CONTROL CIRCUIT
de-energized that can cause electric motor drive faults.
TO
Coils in the same enclosure as an electric motor drive
or coils controlled by relay contacts of a drive need to
suppress voltage spikes.
Devices are installed across the coils to dissipate
CAPACITOR RESISTOR
the CEMF and suppress EMI. Resistor-capacitor net-
works (RC snubber networks) or MOVs are connected SMALL AC LOADS
across the AC coils. Diodes are connected across DC OUTPUT
FROM
POWER SOURCE
coils to suppress EMI. The diodes are connected in re- DEVICE COIL
CONTROL CIRCUIT
verse bias across the DC coils in the same way fly-back
diodes are used with transistors. See Figure 9-15.
TO
Other EMI/RFI Reducing Devices. Other devices
and techniques are used for reducing EMI/RFI. An
output reactor or an output choke may be used to reduce
interference with sensitive equipment. An RFI filter
installed at the input of an electric motor drive reduces
RFI interference. Lowering the PWM frequency also METAL OXIDE
reduces EMI. See Figure 9-16. VARISTOR
LARGE AC LOADS
WIRING FROM
OUTPUT POWER SOURCE
The National Electrical Code (NEC ) must be followed
® DEVICE COIL
CONTROL CIRCUIT
DIODE
DC LOADS
OUTPUT CHOKE
ASSEMBLY
T2
T1
MOTOR CONDUCTORS
GROUND TO MOTOR
T1 T2
MOTOR
T3
CHOKE
T3
CONDUCTORS
T1 T2 T3 FROM ELECTRIC
MOTOR DRIVE WRAPPED WIRE
SCHEMATIC DEVICE
OUTPUT CHOKE
ELECTRIC MOTOR DRIVE AND
RFI FILTER MOUNTED TO COMMON
BACK PLATE WITH POSITIVE
ELECTRICAL BOND AND IN CLOSE
PROXIMITY TO EACH OTHER
IRON TERMINAL
3 POWER SUPPLY CORE BLOCK
ELECTRIC
MOTOR DRIVE
g
Jo P
PHASE C
RFI FILTER PHASE A COIL
INSTALLED AT COIL
ELECTRIC MOTOR
DRIVE INPUT
PHASE B
COIL
CABLE SUPPLIED
WITH RFI FILTER
RFI FILTER OUTPUT REACTOR
Figure 9-16. Output chokes, RFI filters, and output reactors are used to reduce EMI.
Manufacturer Instructions. NEC® Section 110.3(B) information on wire size, recommended mounting
states, “Listed or labeled equipment shall be installed location, and the size and type of overcurrent devices.
and used in accordance with any instructions included in Electric motor drives may us fuses or circuit breakers
the listing or labeling.” NEC® Section 110.3(B) makes as circuit overcurrent protection. Electric motor drive
the instructions of the manufacturer the primary refer- manufacturers specify the type of overcurrent protection
ence for installation. Manufacturer instructions provide to be used with particular drives.
250 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
MANUFACTURER
TM
PE 21 PLUS PREMIUM EFFICIENCY
®
NEC ARTICLE 430 ORD. NO. 1LA02864SE41 MAG. 21.8
PART III TYPE RGZESD I FRAME 286T
SERVICE
HP 30.00 FACTOR 1.0 3 PH
CONTROLLER MAY AMPS 34.9 VOLTS 460
PROVIDE OVERLOAD Square D Company RPM 1765 HERTZ 60
PROTECTION
51-770-642
o DATE
DUTY CONT 40 C AMB. CODE
CLASS NEMA KVA NEMA
INSUL H DESIGN B CODE G NOM. EFF. 93.6
SH. END
BRG. 50BC03JPP3 OPP. END
BRG. 50BC03JPP3
OVERLOAD CURRENT
PARAMETERS AND
OVERLOAD MODE
PARAMETERS MAY
BE USED TO MEET
CODE REQUIREMENTS
Figure 9-17. NEC® Article 430 contains several parts that apply to electric motor drives.
Wire Size. In the event the instructions do not specify Disconnects. A disconnect is a device that isolates
wire size, NEC® Section 430.122(A) states, “Circuit an electric motor drive and/or motor from the voltage
conductors supplying power conversion equipment source to allow safe access for maintenance or repair.
included as part of an adjustable-speed drive system NEC® Article 430 Part IX contains general requirements
shall have an ampacity not less than 125% of the rated for disconnects. Article 430 Part X contains specific
input to the power conversion unit.” The wire size can requirements for the disconnect located in the incoming
be calculated using the electric motor drive (power line to the electric motor drive. NEC® Section 430.128
conversion equipment) nameplate current and NEC® states “The disconnecting means shall be permitted to
Table 310.16. be in the incoming line to the conversion equipment
Chapter 9 — Electric Motor Drive Installation Procedures 251
and shall have a rating of not less than 115 percent of motor. See Figure 9-18. NEC® Section 430.124(A) states,
the rated input current of the conversion unit.” Circuit “Where the power conversion equipment is marked to
breakers and motor-circuit switches rated in horsepower indicate that overload protection is included, additional
are devices used as disconnecting means. A circuit overload protection shall not be required.” In order for
breaker or fused motor-rated disconnect can serve as the electric motor drive to provide overload protec-
both a disconnecting means and overcurrent device. A tion, the nameplate information of the motor must be
motor-circuit switch is commonly referred to as a mo- programmed into the drive. The electric motor drive
tor-rated disconnect. control board provides the overload protection based
NEC® Article 430 Part IX has specific rules regard- on the information entered.
ing disconnects for various applications. One of the If an electric motor drive is not approved for use as an
more commonly applied sections, NEC® 430.102(B) overload, or if multiple motors are fed from the drive, an
exception, allows a controller disconnect that is capable external overload relay(s) must be provided. See Figure 9-
of being locked open to also serve as the motor discon- 19. NEC® Article 430 contains information on selecting
necting means. Articles and exceptions in the NEC® and sizing overcurrent devices and overload protection.
may be superseded by other building codes such as a The normally closed contacts of the overload relays are
mechanical code requiring a disconnect be located at connected in series and terminate at the control terminal
all HVAC equipment. strip of the electric motor drive. An overload in any mo-
Overload Protection. In a majority of electric motor drive tor opens the circuit and causes the electric motor drive
applications, the drive provides overload protection for the to stop outputting voltage to the motors.
MANUFACTURER
Jog
TM
P
PE 21 PLUS PREMIUM EFFICIENCY
ORD. NO. 1LA02864SE41 MAG. 21.8
NUMBER
HORSEPOWER TYPE RGZESD I FRAME 286T OF PHASES
SERVICE
HP 30.00 FACTOR 1.0 3 PH
FULL LOAD AMPS 34.9 VOLTS 460
CURRENT
RPM 1765 HERTZ 60
SUPPLY
51-770-642
o DATE
DUTY CONT 40 C AMB. VOLTAGE
SPEED CLASS NEMA KVA NEMA
CODE
3φ MOTOR
MOTOR
NAMEPLATE
Figure 9-18. Motor nameplate information is entered into an electric motor drive and the information is processed by the
CPU to calculate overload protection levels.
252 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
NORMALLY CLOSED
27 OVERLOAD RELAY
CONTACT
25
23
22
21
3φ
MOTOR
PE PE DC DC T2/V T3/W
OVERLOAD BOX
CONTACT OPENS ON
ELECTRIC
THERMAL OVERLOAD
MOTOR NORMALLY CLOSED
SIGNALING ELECTRIC
DRIVE OVERLOAD RELAY
MOTOR DRIVE TO
SHUT DOWN MOTOR CONTACT
27
Jog
P
26
24
23
22 3φ
MOTOR
21
3φ
MOTOR
Figure 9-19. External fuses and overload relays may be required along with the electric motor drive in certain applications.
Chapter 9 — Electric Motor Drive Installation Procedures 253
Clearances. NEC® Article 110 Part II lists requirements safety and enhanced EMI reduction, electric motor drive
for dedicated working space and dedicated electrical manufacturers require an equipment grounding conductor
space. The working space requirements are intended to in addition to the metal raceway containing the power and
protect the technician who must adjust or service the control conductors of the drive. Grounding requirements
equipment by providing minimum working spaces, and and the sizing of equipment grounding conductors are
include illumination requirements. The equipment space covered in NEC® Article 250.
requirements are intended to protect the electrical equip-
ment by limiting nonelectrical piping systems above CAUTION
electrical equipment. Electric motor drive installations Consult the electric motor drive manufacturer before powering
must comply with NEC® Article 110 Part II requirements. a drive from an ungrounded system or a 3φ supply whose line
See Figure 9-20. voltages are not symmetrical to ground to avoid injuries to
personnel and avoid damaging the drive.
Grounding. Proper grounding of an electric motor drive
provides equal potential between all metal surfaces, a
low-impedance path to activate overcurrent devices, and Power Wiring
EMI reduction. NEC® Article 100 defines an equipment Power wiring for an electric motor drive consists of the con-
grounding conductor as “The conductor used to con- ductors supplying power to the drive (line conductors) and the
nect the non-current-carrying metal parts of equipment, conductors supplying power to the motor (load conductors).
raceways, and other enclosures to the system grounded A variety of wiring methods are available, depending upon
conductor, the grounding electrode conductor, or both, at installation considerations. The load conductors may power
the service equipment or at the source of a separately de- a single motor or multiple motors. Certain applications use a
rived system.” The NEC® permits certain metal raceways line bypass contactor to provide standard 60 Hz power to the
to be used as equipment grounding conductors. For added motor in the event the electric motor drive fails.
EXHAUST DUCTS
LIGHTING
SPRINKLER
HEADS
DEDICATED
ELECTRICAL SPACE
6′ DEDICATED
WORKING SPACE
6¹⁄₂′
6′
DIMENSION
VARIES WITH
STATE AND
LOCAL CODES
Figure 9-20. The NEC® requires a dedicated working space and a dedicated electrical space for indoor installations of
electrical equipment.
254 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
Power Terminal Strip. The power terminal strip and R, S, and T for line; and U, V, W for load. Care must be
the control wiring terminal strip are separated from one taken to ensure the line conductors are connected at the
another to reduce EMI. The line conductors and load line terminals, and the load conductors are connected at
conductors are terminated at the power terminal strips. the load terminals. The DC bus connection is designated
Many electric motor drives have a location on the power by DC+, DC–. Some drive manufacturers denote the DC
terminal strip to connect an auxiliary braking unit direct- bus with B+ and B–. This is done to indicate the location
ly to the DC bus. The North American designations for where a dynamic braking resistor can be installed. The
conductors are L1, L2, and L3 for line; and T1, T2, T3 ground terminal is designated by potential earth (PE),
for load. The European designations for conductors are or the ground symbol ( ). See Figure 9-21.
DC
THREADED STUD BRAKE
RING
LUG
PRESSURE
PLATE DC
BRAKE
BOLT
Figure 9-21. Power terminal strips use various termination methods according to horsepower requirements and have
multiple designations for the line and load terminations.
Chapter 9 — Electric Motor Drive Installation Procedures 255
TECH FACT
Nonmetallic conduits and raceways must not be used for
power wiring and control wiring when nonshielded cable
(wiring) is used.
DISCONNECT
EMT WITH
Jog INDIVIDUAL
CONDUCTORS
P
SEALTITE™ Siemens
CONDUCTOR CONDUIT
PULL BOX
PUMP MOTOR
ELECTRIC MOTOR
DRIVE CABINET
CONVEYOR
MOTOR
Siemens
CONVEYOR MOTOR
SHIELD
INSULATION CONDUCTOR
BOX FITTING
GROUND
CONDUCTORS
Figure 9-22. A wide variety of wiring methods are available for installing an electric motor drive and motor.
Chapter 9 — Electric Motor Drive Installation Procedures 257
POWER FROM
ELECTRIC MOTOR DRIVE
MACHINE PULLEY
(DRIVEN PULLEY)
3 MOTOR
MOTOR
DISCONNECT
ADJUSTMENT
ADJUSTABLE
PIVOT BASE
Figure 9-23. A flexible connection to a motor allows motor adjustment and negates the effects of vibration from the motor
or building.
FUSED MOTOR
RATED DISCONNECT
HVAC FAN
MOTOR-RATED
DISCONNECT
Square D Company
RIGID CONDUIT
ELECTRIC MOTOR
DRIVE PROVIDES
OVERLOAD
PROTECTION
FOR MOTOR
Figure 9-24. A basic electric motor drive application involves a single motor powered by a drive.
258 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
Multiple-Motor Installation. A multiple-motor instal- motor drive controlling an exhaust fan that removes
lation involves multiple motors being fed from a single fumes from a parking garage is a common application
electric motor drive. An electric motor drive controlling requiring a bypass contactor. Speed control is not pos-
a conveyor with multiple motors that operate at the sible when operating in bypass mode.
same speed is a common multiple-motor installation. The bypass contactor works in conjunction with an
Each motor has its own set of conductors. Supplemen- input contactor, output contactor, overload relay, and
tal overcurrent devices and overload protection must
other control components. See Figure 9-26. When in the
be installed, as the rating of the individual motors is
electric motor drive mode, the bypass contactor is open,
less than the electric motor drive rating. A multiple-
motor installation requires that all the motors have the the input contactor and output contactor are closed, and
same NEMA design letter. Open-loop or closed-loop the motor is powered by the drive. In the bypass mode,
vector drives cannot be fed from a single electric mo- the bypass contactor is closed, the input and output
tor drive. See Figure 9-25. NEC® Article 430 contains contactors are open, and the motor is powered by the
information on sizing overcurrent devices and overload line voltage, not the electric motor drive.
protection for multiple-motor installations. The bypass contactor is mechanically interlocked to
Bypass Contactor. A bypass contactor is a contactor the output contactor and electrically interlocked to the
that allows line power to a motor that is normally con- input contactor. The interlocking ensures that both the
trolled by an electric motor drive. A bypass contactor output contactor and input contactor are de-energized
allows a critical load to operate during electric motor (open) when the bypass contactor is closed. Isolating the
drive maintenance, or when a drive fails. An electric electric motor drive prevents line power from reaching
MULTIPLE-MOTOR INSTALLATION
FROM
POWER SUPPLY
FUSES PROVIDE
OVERCURRENT
PROTECTION FOR
INDIVIDUAL MOTORS
JUNCTION BOX
FUSE
MOTOR-RATED EXTERNAL
DISCONNECT EXTERNAL OVERLOAD OVERLOAD
AND FUSE ENCLOSURE AND FUSE
ENCLOSURE
OVERLOAD RELAY
OVERLOAD RELAY ENCLOSURE
ENCLOSURE
General Electric Company
General Electric Company
General Electric Company
3 MOTORS
Figure 9-25. Multiple motors fed from a single electric motor drive require supplemental overcurrent and overload protection.
Chapter 9 — Electric Motor Drive Installation Procedures 259
the drive output. The overload relay is provided to The input contactor and output contactor do not control
protect the motor when the electric motor drive with stopping and starting of an electric motor drive. The start-
its integral overload protection is bypassed. The con- ing and stopping of an electric motor drive is controlled
trols to initiate the bypass function may be manual or by inputs to the drive. The output contactor must be closed
automatic. Other bypass control systems are found in prior to starting an electric motor drive, and the drive must
industry for specific applications. be OFF before opening the output contactor.
FROM ELECTRIC
POWER SUPPLY MOTOR DRIVE
SELECTOR SWITCH CONDITIONS
L1 L2 L3
Jog
CONTACTOR DRIVE OFF BYPASS
FUSED MOTOR P
OUTPUT CONTACTOR
LINE EXTERNAL
REACTOR L1/R L2/S L3/T PE PE DC DC T1/U T2/V T3/W OVERLOADS
IC OC
INPUT
CONTACTOR
F1
BYPASS BYP
F2 CONTACTOR
TRANSFORMER 3φ
MOTOR
LADDER
2 1 F3 DIAGRAM
BYPASS
CONTACTOR
OC
SELECTOR
1
SWITCH
ELECTRICAL IC
INTERLOCK BYP MECHANICAL
IC
2 6 INTERLOCK
3
BYP
BYPASS
2 BYP 7 5
4
ELECTRIC Square D -
MOTOR DRIVE Schneider Electric
LINE NUMBER WIRE-REFERENCE NUMBER
Figure 9-26. A bypass contactor provides line power to a motor if the electric motor drive fails.
260 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
Control Wiring The outputs can control devices related to the electric
Control wiring consists of inputs and outputs con- motor drive or provide metering and annunciation func-
nected to the electric motor drive, excluding the power tions. A digital output such as a relay can be used to start
wiring. The inputs and outputs are connected to the and stop an external electromechanical motor brake. An
electric motor drive at the control terminal strips. analog output can be used with an external meter that
The type of inputs and outputs determine the wiring displays frequency or motor current. See Figure 9-27.
method. Various wiring schemes are used, depending Wiring Methods. Digital inputs and outputs are
upon the specific application. connected to an electric motor drive with individual
Control Terminal Strips. Digital inputs, analog inputs, conductors. Analog inputs and outputs are connected
digital outputs, and analog outputs are connected to the to an electric motor drive with twisted shielded pair
control terminal strips. The number and type of inputs cables. See Figure 9-28. The following items must be
and outputs varies with the complexity of the electric mo- considered when installing control wiring:
tor drive. The functionality of an input or output may be • Control wiring and power wiring should be installed
controlled by the programming parameters of an electric in separate metal conduits.
motor drive. The functionality of a relay output (digital • Wiring for digital signals, analog signals, and serial
output) may be programmed to indicate motor over-cur- communication signals should be installed in separate
rent, motor overload, or an electric motor drive fault. metal conduits.
Electric motor drive inputs control the starting, • Do not mix wiring for AC and DC control signals in
stopping, and speed of a motor. Digital inputs consist the same conduit.
of control devices that provide an on/off signal such • Inside an electric motor drive enclosure, control and
as a selector switch or pushbutton. Analog inputs con- power wiring should be separated as much as pos-
sist of signals that vary over a range of values, such sible. If control and power wiring must cross, they
as a potentiometer with a 0 VDC–10 VDC signal. A should cross at a 90° angle.
combination of digital and analog inputs can control an • Care must be taken when terminating the twisted shield-
electric motor drive by using a selector switch to start ed pair cables to ensure the shield is terminated only at
a motor and a 4 mA–20 mA signal to control the speed the electric motor drive end, and the pairs should be
of the motor. twisted as close as possible to the terminals.
DRAIN WIRE
GND 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
DRAIN
WIRE
POTENTIOMETER
0 VDC – 10 VDC
INPUT
4 mA – 20 mA
INPUT
PROGRAMMABLE
ANALOG OUTPUT
DIGITAL
INPUT 1
DIGITAL
INPUT 2
DIGITAL
INPUT3
PROGRAMMABLE
OUTPUT RELAY
Figure 9-27. Programming the parameters of an electric motor drive allows the functions of the inputs and outputs to
be modified.
Chapter 9 — Electric Motor Drive Installation Procedures 261
SIGNAL WIRES
DRAIN SHIELD/DRAIN WIRE COVERED TERMINATE
WIRE WITH SHRINK TUBING TO ALLOW AT DEVICE
GROUNDING AT ONE POINT
SIGNAL WIRES
TERMINATE
AT ELECTRIC
MOTOR DRIVE SHRINK
MESH SHIELD TRIMMED BACK TUBING
AND SHRINK TUBING ADDED
TO PREVENT SHIELD TOUCHING
GROUNDED SURFACES
SIGNAL WIRES
Figure 9-28. The termination of twisted shielded pair cable requires that shrink tubing be added correctly.
Control Wiring Schemes. Wiring schemes involving Wiring schemes involving analog signals fall into two
digital inputs fall into two categories, 2-wire control and categories, 2-wire control and 3-wire control. Certain ana-
3-wire control. Two-wire control is the simplest. Two-wire log signals only require a two-conductor twisted shielded
control consists of two wires to an electric motor drive from pair cable with a 4 mA–20 mA or a 0 VDC–10 VDC
a single digital input such as a selector switch. Opening signal. Other analog signals require a three-conductor
and closing the digital input stops and starts the electric twisted shielded pair cable as with a potentiometer.
motor drive operation. Three-wire control consists of Many electric motor drives have the capability to
three wires from two digital inputs. One of the inputs is communicate with PLCs, other drives, building automa-
a normally open start and the other is a normally closed tion systems, HMIs, and PCs via serial communication.
stop. The scheme is similar to the 3-wire control used The serial communication may be RS-232 or RS-485.
with magnetic motor starters. See Figure 9-29. The serial communication may be integral to the electric
motor drive or require an interface board. An electric
TECH FACT motor drive is connected to other devices with twisted
shielded pair cables. The advantages of serial commu-
Electric motor drives on HVAC fans include a bypass
contactor that is used to power the fan with utility power nication include less wiring between control equipment,
when drive failure occurs. and the electric motor drive can be monitored and con-
trolled from a central location.
262 ELECTRIC MOTOR DRIVE INSTALLATION AND TROUBLESHOOTING
1 2 3 14 15 16 17 18 19
Jog
P
S
START/STOP
2-WIRE CONTROL
1 2 3 14 15 16 17 18 19
Jog
P
NO
NORMALLY
N CLOSED
(STOP)
NORMALLY OPEN
(START)
3-WIRE CONTROL
1 2 3 14 15 16 17 18 19
Jog
P
DRAIN OF TWISTED
SHIELDED CABLE
POTENTIOMETER 4 mA – 20 mA
ANALOG INPUT
ANALOG CONTROL
INPUT &
STATUS OUTPUT INPUT OUTPUT SPARE
D SHELL
POWER
PC RUN
CPU FAULT
Jog
P
COMMUNICATIONS CABLE
SERIAL COMMUNICATION
Figure 9-29. Electric motor drive control wiring schemes include 2-wire control, 3-wire control, analog control, and serial
communication.