Test Report-Inter Locking Paver Block

The test report details testing conducted on interlocking paver blocks used for construction of roads, including measurements of compressive strength, water absorption, and dimensions which all met specification requirements, with the average compressive strength being 41.98 MPa and average water absorption being 0.95%.

Uploaded by

udit shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
350 views

Test Report-Inter Locking Paver Block

The test report details testing conducted on interlocking paver blocks used for construction of roads, including measurements of compressive strength, water absorption, and dimensions which all met specification requirements, with the average compressive strength being 41.98 MPa and average water absorption being 0.95%.

Uploaded by

udit shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

TEST REPORT- INTER LOCKING PAVER BLOCK

Letter Ref. - ULR No: TC8963210000001056


Discipline Mechanical Sampled By: EDRC Rep. Group Building Material
Location of Sample : - Sample I.D. BW-1056
Condition of Sample Good Qty of Sample: 8No
Construction of internal roads of Gram sabha padampur devaliya and jaipur
Name Of The Project:
kheema , Lalkuan, nainital consituency
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Refered By: Assistant Engineer-II, Construction Division, PWD Haldwani.
Contractor Name & Add,: M/S Kabiran Constructions
Date Of Receiving: 10-Apr-21 Date Of Initiating Testing: 15-Apr-21
Date of Completion : 16-Apr-21 Date Of Reporting: 16-Apr-21
CB Number: 282/EE ; Dated: 21-03-2021
Environmental Condition 29 ° c Deviation From Standard Procedure: No
Reference Standards: IS 15658-2006 ra: 2017 Grade of Interloking Paver: M-40
Area Calculation For Concrete Paver Block
Weight Of Rectangular Card Board Size: 200 x 100 mm 7.68 Gms. Chamfer
(M1):
corection
Weight Of Paver Size Card Board (M2): 13.99 Gms. factor for 80 1.18
Area [ { 20000 x Weight of M2 } / M1 ]: 36432.29 mm² mm thick

Compressive Strength
Weight of Sample in I.D. Area (mm²) Load (N) Comp. CS After Av. CS
gm Mark Strength. Chemfer (Mpa)
(Mpa) Correction
(Mpa)
4681 1 36432.29 1350000 37.06 43.72
4675 2 36432.29 1320000 36.23 42.75
4663 3 36432.29 1280000 35.13 41.46
4698 4 36432.29 1360000 37.33 44.05 42.02
4639 5 36432.29 1250000 34.31 40.49
4652 6 36432.29 1270000 34.86 41.13
4659 7 36432.29 1260000 34.58 40.81
4680 8 36432.29 1290000 35.41 41.78

Water Absorption:
Sample Requirement as
S. No. Parameter Sample 2 Sample 3
1 per Specification
1 Oven Dry Wt of Sample in Gm 4621 4657 4623 Max. 6.0% Average
2 Saturated Surface Dry Wt in Gm 4672 4699 4662 & Max. 7.0%
3 Water Absorption % 1.10 0.90 0.84 Individual

Avergae W.A% 0.95


Dimension Of Interlocking Paver
Width at
Length Width at Centre Thickness Specification
Test Artifact both end
in Cm in Cm in Cm Requirement
in Cm
For std thickness ˂100
Averge Dimension of 5 mm, Length ± 2 mm,
Interlocking Paver
20.01 15.96 12.00 8.02 thick. ± 3 mm,width ± 2
mm.of specified size.

Checked By: Quality Manager


Girish Bhatt
****End of Report****
The Test Report relates only to the item listed in report & applicable parameter.
Total liability of our Lab will be restricted to the invoice amount only.
The samples will be distroyed after retention period unless otherwise specified.
This reoprt is not to reproduced wholely or in part and can not be used as evidence in the court of Law.
TEST REPORT- INTER LOCKING PAVER BLOCK
Letter Ref. - ULR No: TC8963210000001056
Discipline Mechanical Sampled By: EDRC Rep. Group Building Material
Location of Sample : - Sample I.D. BW-1056
Condition of Sample Good Qty of Sample: 8No
Construction of internal roads of Gram sabha padampur devaliya and jaipur
Name Of The Project:
kheema , Lalkuan, nainital consituency
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Refered By: Assistant Engineer-II, Construction Division, PWD Haldwani.
Contractor Name & Add,: M/S Kabiran Constructions
Date Of Receiving: 21-May-21 Date Of Initiating Testing: 23-May-21
Date of Completion : 24-May-21 Date Of Reporting: 25-May-21
CB Number: 282/EE ; Dated: 21-03-2021
Environmental Condition 34° c Deviation From Standard Procedure: No
Reference Standards: IS 15658-2006 ra: 2017 Grade of Interloking Paver: M-40
Area Calculation For Concrete Paver Block
Weight Of Rectangular Card Board Size: 200 x 100 mm 7.62 Gms. Chamfer
(M1):
corection
Weight Of Paver Size Card Board (M2): 13.91 Gms. factor for 80 1.18
Area [ { 20000 x Weight of M2 } / M1 ]: 36509.19 mm² mm thick

Compressive Strength
Weight of Sample in I.D. Area (mm²) Load (N) Comp. CS After Av. CS
gm Mark Strength. Chemfer (Mpa)
(Mpa) Correction
(Mpa)
4622 1 36509.19 1350000 36.98 43.63
4687 2 36509.19 1380000 37.80 44.60
4653 3 36509.19 1240000 33.96 40.08
4663 4 36509.19 1260000 34.51 40.72 41.98
4647 5 36509.19 1290000 35.33 41.69
4618 6 36509.19 1320000 36.16 42.66
4629 7 36509.19 1300000 35.61 42.02
4691 8 36509.19 1250000 34.24 40.40

Water Absorption:
Sample Requirement as
S. No. Parameter Sample 2 Sample 3
1 per Specification
1 Oven Dry Wt of Sample in Gm 4615 4631 4639 Max. 6.0% Average
2 Saturated Surface Dry Wt in Gm 4669 4695 4678 & Max. 7.0%
3 Water Absorption % 1.17 1.38 0.84 Individual

Avergae W.A% 1.13


Dimension Of Interlocking Paver
Width at
Length Width at Centre Thickness Specification
Test Artifact both end
in Cm in Cm in Cm Requirement
in Cm
For std thickness ˂100
Averge Dimension of 5 mm, Length ± 2 mm,
Interlocking Paver
20.40 15.99 12.00 7.98 thick. ± 3 mm,width ± 2
mm.of specified size.

Checked By: Quality Manager


Girish Bhatt
****End of Report****
The Test Report relates only to the item listed in report & applicable parameter.
Total liability of our Lab will be restricted to the invoice amount only.
The samples will be distroyed after retention period unless otherwise specified.
This reoprt is not to reproduced wholely or in part and can not be used as evidence in the court of Law.
TEST REPORT: PHYSICAL TEST OF BURNT CLAY BUILDING BRICKS
Letter Ref. - ULR No: TC8963220000001056
Discipline Mechanical Sampled By: Ste Team Group Bricks
CB No: 282/EE ; Dated: 21-03-2021 Sample I.D. BW-1056
Condition of Sample Good Qty of Sample: 20 No
Construction of internal roads of Gram sabha padampur devaliya and jaipur kheema ,
Name Of The Project:
Lalkuan, nainital consituency
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Sample Refered By: Assistant Engineer II, Construction Division, PWD Haldwani.
Contractor Name & Add,:M/S Kabiran Constructions
Date Of Sampling: 21-May-21 Date of Start of Test: 24-May-21
Date of Completion : 28-May-21 Date of Reporting: 29-May-21
Brick Mark: RAMA
Grade / Class: Class Designation: -
Tested in Accordance With: IS: 3495 (Part 1 to 4)- 2019: Deviation From
Standard No
Environmental Condition For Test: 26° (Control Temp. Water Tank
Procedure:

BIS Requirement
TEST RESULT UNIT (As per IS:1077-1992 RA: 2016) if used for
Villas or important structures otherwise as
per Note-3
Dimension of 20 4310.0 -
X 1998.0 X 1302.0 in mm
Bricks (LxBxT)
Water Absorption 13.66 % Should not be more than 20 % for Class
Efflorescence NIL - Moderate up to class 12.5 and slight for higher classes.

# Compressive 11.19 11.01 11.10 10.96 10.96


Strength Should not be less than for Class Designation
N/mm² Specified as per IS 1077- 1992 RA: 2016.
(individual results AVERAGE: 11.05
of brick given)
Remarks: NA

(G. C. Bhatt)
Checked By: Quality Manager

***** End of Report*******


The Test Report relates only to the item listed in report & applicable parameter.
Total liability of our Lab will be restricted to the invoice amount only.
The samples will be distroyed after retention period unless otherwise specified.
This reoprt is not to reproduced wholly or in part and can not be used as evidence in the court of Law.
TEST REPORT- GRADATION ANALYSIS OF WBM GRADE III
Letter Ref. - ULR No: TC896321000001056
Discipline Mechanical Sampled By: EDRC Rep. Group Building Matrial
Location of Sample - Sample I.D. BW- 1056
Condition of Sample Good Qty of Sample: 20 Kg
Construction of internal roads of Gram sabha padampur devaliya and
Name Of The Project:
jaipur kheema , Lalkuan, nainital consituency
CB No.: 282/EE ; Dated: 21-03-2021
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Reffered By: Assistant Engineer-II, Construction Division, PWD Haldwani.
Contractor M/S Kabiran Constructions
Date Of Receiving: 21-May-21 Date Of Testing: 23-May-21
Date of Completion : 25-May-21 Date Of Reporting: 26-May-21
Tested in Accordance With: IS 2386- Part I- RA 2016 Environment Ambient
Condition:
Table 405-
IS SIEVE Wt. RET. Cummu % Wt.
% Wt. RET % Passing 2, QAH
(mm) (gms.) RET Vol.1
63 mm 0 0.00 0.00 100.00 100.00
53 mm 936 4.28 4.28 95.72 95-100
45 mm 6075 27.78 32.06 67.94 65-90
22.4 mm 13545 61.93 93.99 6.01 0-10
11.2 mm 729 3.33 97.32 2.68 0-5
Pan 586 2.68 100.00 0.00
TOTAL:
100
90
80
70
60
50
40
30
20
10
0
0 11.2 mm 22.4 mm 45 mm 53 mm 63 mm

ELONGATION & FLAKINESS INDEX


Spacification Requirement as per MoRD, QA
Parameter Result Hand book for Rural Road Table 405.1

Flakiness Index % 20.73 Max.30% for Sub Base, Max 25 % for Base
& Max 20% for Surfacing
Elongation Index % 20.10 -

GC. Bhatt
Checked By: Quality Manager
****End of Report******
The Test Report relates only to the item listed in report & applicable parameter.
Total liability of our Lab will be restricted to the invoice amount only.
The samples will be distroyed after retention period unless otherwise specified.
This reoprt is not to reproduced wholely or in part and can not be used as evidence in the court of Law.
Page No.1
TEST REPORT- GRADATION ANALYSIS OF WBM GRADE III
Letter Ref. - ULR No: TC896321000001056
Discipline Mechanical Sampled By: EDRC Rep. Group Building Matrial
Location of Sample - Sample I.D. BW-1056
Condition of Sample Good Qty of Sample: 20 Kg
Construction of internal roads of Gram sabha padampur devaliya and jaipur
Name Of The Project:
kheema , Lalkuan, nainital consituency
CB No.: 282/EE ; Dated: 21-03-2021
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Reffered By: Assistant Engineer-II, Construction Division, PWD Haldwani.
Contractor Name & Add,: M/S Kabiran Constructions
Date Of Receiving: 21-May-21 Date Of Testing: 23-May-21
Date of Completion : 25-May-21 Date Of Reporting: 26-May-21
SPECIFIC GRAVITY & WATER ABSORPTION: Tested As Per IS 2386 - Part 3- 1963 RA-2016
Specification
S. No. Test Parameter Observation Requirement AS PER
MoRD
1 Weight of Basket in Water A1 890
2 Weight of Basket +Saturated Aggregate in Water A2 2724
3 Weight of Saturated Aggregate in Water A (A1-A2) 1834
4 Weight of Saturated Aggregate in Air B 2894 WA% Max. 2.0%
5 Weight of Oven Dry Aggregate in Air C 2866
6 Water Absorption % =((B-C)/C)*100 0.98
7 Specific Gravity C/(B-A) 2.70
MECHENICAL PROPERTIES OF AGGREGATE:Tested As Per IS 2386 - Part 4- 1963 RA-2016
CRUSHING VALUE & IMPACT VALUE
CRUSHING VALUE IMPACT VALUE
Specificat
ion Specification
Requirem Requirement
S. NO. TEST PARAMETER OBSERVATION TEST PARAMETER OBSERVATION
ent AS AS PER
PER MoRD
MoRD
Total Weight of QA Hand Total Weight of Aggregate
1 Aggregate in gm 3125.00 book for 336.00 QA Hand book
in gm W1
W1 Rural Road for Rural Road
Weight of aggrgate Sub Base- Weight of aggrgate Sub Base- Max.
Max. 30%,
2 Passing 2.36 mm 664.00 Base Max -
Passing 2.36 mm Sieve in 69.45 50%, Base -
Sieve in gm W2 25%, gm W2 40%, Surfacing
Surfacing Max. 30%
3 C. V % 21.25 Max. 20 % IMPACT VALUE % 20.67
LOS ANGELES ABRASION VALUE:Tested As Per IS 2386 - Part 4- 1963 RA-2016
S. NO. TEST PARAMETER OBSERVATION Specification Requirement
1 Total Weight of Aggregate W1 5078
not > 50 % for Nonwearing
2 Weight of aggrgate Passing 2.36 mm Sieve 1132 surface & not > 30 % for
W2 wearing surface
3 L.A.V % 22.29

GC. Bhatt
Checked By: Quality Manager
****End of Report******
TEST REPORT- SIEVE ANALYSIS & PHYSICAL PROPERTY OF FINE AGGREGATE
Letter Ref. - ULR No: TC896321000001056
Discipline Mechanical Sampled By: Client Group Building Material
Location of Sample /Chainage: - Sample I.D. BW 1056
Condition of Sample Good Qty of Sample: 20 KG
Construction of internal roads of Gram sabha padampur devaliya and jaipur kheema , Lalkuan, nainital
Name Of The Project:
consituency
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Sample Refered By: Assistant Engineer II, Construction Division, PWD Haldwani.
Contractor Name & Add,: M/S Kabiran Constructions
Date Of Receiving: 21-May-21 Date Of Initiating Testing: 22-May-21
Date of Completion : 24-May-21 Date Of Reporting: 25-May-21
CB No. : 282/EE ; Dated: 21-03-2021 Environment Condition of Test: Ambient
Tested in Accordance With: IS: 2386- 1963: RA 2016 Deviation From Standard Procedure: No
IS SIEVE Wt. RET. Cumulative IS: 383 LIMITS
% Wt. RET % Passing
(mm) (gms.) % Wt. RET Zone-III
6.3 0.4 0.08 0.08 99.92 100
4.75 17.1 3.42 3.50 96.50 90-100
2.36 47.5 9.50 13.00 87.00 85-100
1.18 51.6 10.32 23.32 76.68 75-100
600 µ 71 14.20 37.52 62.48 60-79
300 µ 180.3 36.06 73.58 26.42 12-40
150 µ 81.7 16.34 89.92 10.08 0-10
Pan 50.4 10.08 100.00 - -
TOTAL: 500 a) FM= 2.41 b) Passing 75 µ= Not Done
( Shall be less than 3 % )
Note: For Crushed (Artificial) stone Sand, the permissible limit on 150 -micron IS Sieve is increased to 20%. This does not affect the 5% allowance permitted in the
above mentioned limits applying to other sieve sizes. (IS: 383-1970, Table-4, Note-1, Page 11)

120
GRADATION CURVE B (Sample)
100 SAND 100 100 100 100
A (Max.)
90
85
80 C (Min.)
% Of Passing

79 75
60 60

40 40

20
10 12
0 0
0.15 0.30 0.60 1.18 2.36 4.75 10.00
I.S.Sieves (mm)

G. C. Bhatt
Tested By Quality Manager
****End of Report******
The Test Report relates only to the item listed in report/ as submitted at the time of test & under conditions specified herein-
Any coorection in the test report invalidated unless signed by Quality Manager/ Technical Manager.
The test report can not be produced / reproduced as an evidence in the court of law & oreder.
The test report can not be used for advertising the particular prdoduct tested in the Labboratory.
The test reportshall not be reproduced in full, without the writted approval of the Laboratory.
Sample Submitted by Client, Not by the Laboratory.
TEST REPORT- SIEVE ANALYSIS & PHYSICAL PROPERTY OF FINE AGGREGATE
Letter Ref. - ULR No: TC896321000001056
Discipline Mechanical Sampled By: Client Group Building Material
Location of Sample /Chainage: - Sample I.D. BW 1056
Condition of Sample Good Qty of 20 KG
Construction of internal roads of Gram sabha padampur devaliya and
Name Of The Project:
jaipur kheema , Lalkuan, nainital consituency
Client Name: Executive Engineer, Construction Division, PWD Haldwani.
Sample Refered By: Assistant Engineer II, Construction Division, PWD Haldwani.
Contractor Name & Add,: M/S Kabiran Constructions
Date Of Receiving: 21-May-22 Date Of Initiating 22-May-21
Date of Completion : 24-May-21 Date Of Reporting: 25-May-21
Ref. Codes: IS 2386 (Part-3):1963, RA:2016
Deviation From Standard Procedure: No
CB No. : 282/EE ; Dated: 21-03-2021

Specific Gravity
S. No. Particular Observation
1 Oven Dry Sample in gm D 493.2
2 Mass of SSD Sample in gm A 505.3
3 Mass of Density bottle with Sample and Liquid in gm (B) 1829.4
4 Mass of Density Bottle filled with Liquid in gm (C) 1518
5 Specific Gravity = D/(A-(B-C)) 2.54
6 Apperent Specific Gravity = D/(D-(B-C)) 2.54
Water Absoroption
S. No. Particular Observation
1 Mass of Oven Dry Sample in gm (M1) 493.2
2 Mass of Saturated Surface Dry Sample in gm (M2) 505.3
3 Water Absorption % (M2-M1)/M1X 100 2.45

G. C. Bhatt
Tested By Quality Manager
****End of Report******
The Test Report relates only to the item listed in report/ as submitted at the time of test & under conditions specified herein-
Any coorection in the test report invalidated unless signed by Quality Manager/ Technical Manager.
The test report can not be produced / reproduced as an evidence in the court of law & oreder.
The test report can not be used for advertising the particular prdoduct tested in the Labboratory.
The test reportshall not be reproduced in full, without the writted approval of the Laboratory.
Sample Submitted by Client, Not by the Laboratory.
TEST REPORT - RIB STEEL REINFORCEMENT BAR
Letter Ref. - ULR No: TC896321000001056

Discipline Mechenical Sampled By: Group Steel

Location of Sample - Sample I.D. BW1056


Condition of Sample Good Qty of Sample:
3 Nos
Name Of The Project: Construction of internal roads of Gram sabha padampur devaliya and jaipur
kheema
Executive, Lalkuan,
Engineer,nainital consituency
Construction Division, PWD Haldwani.
Clent Name:
Sample Referred By : Assistant Engineer-II, Construction Division, PWD Haldwani.
Contractor Name : M/S Kabiran Constructions
Date Of Reciving: 21-May-21 Date Of Initiating Testing: 22-May-21
Date of Completion : 22-May-21 Date Of Reporting: 22-May-21
CB no. 282/EE ; Dated: 21-03-2021
Grade Of Steel: Fe-415 Make: SAIL Deviation No
From
Environmental Conditions
Tested in Accordance With: IS: 1608- 1995 RA 2018 Riv.4 Ambient
Of Test:
SAMPLE SAMPLE SAMPLE I. S. Requirement as per 1786-
Sl. No.
1 2 3 1985
Ø of Bar 8 Fe 415
2 50.46 50.40 50.27 - - -
Area mm
% Elongation - - - Min. 14.5
0.2 % Proof Stress (in
2
- - - Min. 415 Min. 415 Min. 500
N / mm )
Ultimate Tensile Strength Minimum 485 or more than
- - -
(in N / mm2) 10 % of 0.2 % Proof Stress

Unit Weight (in kgs./ mt.) 0.396 0.396 0.395 Tolerances On Nominal Mass:
Required (Unit Weight in 1) Upto & Including 10 mm (±) 7%,
0.395 0.395 0.395 individual Sample (-) 8%; 2) Over 10 mm
kgs./mt.)
upto including 16 mm (±) 5%, individual
( ± ) Difference From IS
0.27 0.17 -0.09 Sample (-) 6%; 3) Over 16 mm (±) 3%,
Limits individual Sample (-) 4%
Breakage - - - AVERAGE DIFFERENCE IN UNIT
Bend Test at 180° - - - WEIGHT FROM IS LIMITS:
Re- Bend Test at 157.5°
- - - = 0.12 %
including 135°

G. C. Bhatt
Sr. Technician Quality Manager
Legend: *WGL = With in Gauge Length, # OGL Out of Gauge Length
***** End of Report*******
The Test Report relates only to the item listed in report & applicable parameter.
Total liability of our Lab will be restricted to the invoice amount only.
The samples will be distroyed after retention period unless otherwise specified.
This reoprt is not to reproduced wholely or in part and can not be used as evidence in the court of Law.
TEST REPORT - RIB STEEL REINFORCEMENT BAR
Letter Ref. - ULR No: TC896321000001056
Discipline Mechenical Sampled By: Group Steel
Location of Sample - Sample I.D. BW1056
Condition of Sample Good Qty of Sample: 3 Nos
Name Of The Project: Construction of internal roads of Gram sabha padampur devaliya and jaipur
kheema
Executive, Lalkuan,
Engineer,nainital consituency
Construction Division, PWD Haldwani.
Clent Name:
Sample Referred By : Assistant Engineer-II, Construction Division, PWD Haldwani.
Contractor Name : M/S Kabiran Constructions
Date Of Reciving: 21-May-21 Date Of Initiating Testing: 22-May-21
Date of Completion : 22-May-21 Date Of Reporting: 22-May-21
CB no. 282/EE ; Dated: 21-03-2021
Deviation From Standard
Grade Of Steel: Fe-415 Make: SAIL
Procedure:
No
Environmental Conditions
Tested in Accordance With: IS: 1608- 1995 RA 2018 Riv.4 Ambient
Of Test:
SAMPLE SAMPLE SAMPLE I. S. Requirement as per 1786-
Sl. No.
1 2 3 1985
Ø of Bar 10 Fe 415
2 78.40 78.88 78.68 - - -
Area mm
% Elongation - - - Min. 14.5
0.2 % Proof Stress (in
- - - Min. 415 Min. 415 Min. 500
N / mm2)
Ultimate Tensile Strength Minimum 485 or more than
- - -
(in N / mm2) 10 % of 0.2 % Proof Stress

Unit Weight (in kgs./ mt.) 0.615 0.619 0.618 Tolerances On Nominal Mass:
Required (Unit Weight in 1) Upto & Including 10 mm (±) 7%,
0.617 0.617 0.617 individual Sample (-) 8%; 2) Over 10 mm
kgs./mt.)
upto including 16 mm (±) 5%, individual
( ± ) Difference From IS
-0.25 0.35 0.10 Sample (-) 6%; 3) Over 16 mm (±) 3%,
Limits individual Sample (-) 4%
Breakage - - - AVERAGE DIFFERENCE IN UNIT
Bend Test at 180° - - - WEIGHT FROM IS LIMITS:
Re- Bend Test at 157.5°
- - - = 0.07 %
including 135°

G. C. Bhatt
Sr. Technician Quality Manager
Legend: *WGL = With in Gauge Length, # OGL Out of Gauge Length
***** End of Report*******
The Test Report relates only to the item listed in report & applicable parameter.
Total liability of our Lab will be restricted to the invoice amount only.
The samples will be distroyed after retention period unless otherwise specified.
This reoprt is not to reproduced wholely or in part and can not be used as evidence in the court of Law.