Report
Report
INTRODUCTION
2001 is the result of power sector reforms and restructuring in UP (India) which is the focal point of the
Power Sector, responsible for planning and managing the sector through its transmission, distribution and
supply of electricity.
UPCL will be professionally managed utility supplying reliable and cost efficient
electricity to every citizen of the state through highly motivated employees and state of art technologies,
providing an economic return to our owners and maintaining leadership in the country. We shall achieve this
being a dynamic, forward looking, reliable, safe and trustworthy organization, sensitive to our customers
interests, profitable and sustainable in the long run, providing uninterrupted supply of quality power, with
1
1.1 ABOUT 33/11KV SUBSTATION PITHORAGARH
The main bus 33KV is connected to grid located at BIN, PITHORAGARH. Now the transmission line first
parallel connected with lightning arrester to diverge surge, followed by CVT connected parallel. CVT
110V. A.C. for control panel, at the location a wave trap is connected to carrier communication at higher
frequencies. A current transformer is connected in series with line which measure current and step down
current at ratio 800:1 for control panel. Switchgear equipment is provided, which is the combination of a
circuit breaker having an isolator at each end. A transformer is connected to main bus though a bus coupler.
The main bus has total capability of 160 MVA for 33 KV, which is subdivided into two transformer capacity
of 80 MVA (40MVA+40MVA) parallel connected for 33KV and other two transformer capacity of 80KV
(40KV+40KV) are parallel connected for substation. At both ends of transformer lightning arrester current
transformer and switchgear equipment provided. Transformer step downs voltage from 220KV to 33KV.
The main bus is provided with switchgear equipment & a current transformer. This gives way to six feeders
transmitting power to RAI, THULIGARH. The main bus is connected to jack bus or transfer bus
2
through a bus coupler & 11KV is provided with switchgear equipment. This gives way to feeders
transmitting power to A.P.S, WADDA. A step down transformer of 11KV/440V is connected to control
panel to provide supply to the equipments of the substation. Capacitor bank is connected to main bus of
3
CHAPTER 2. TRANSFORMER
Fig:-2.1 Transformer
Transformer is a static machine, which transforms the potential of alternating current at same frequency. It
means the transformer transforms the low voltage into high voltage & high voltage to low voltage at same
frequency. It works on the principle of static induction principle. When the energy is transformed into a
higher voltage, the transformer is called step up transformer but in case of other is known as step down
transformer.
4
2.1.1 POWER TRANSFORMER:
a) Current transformer
b) Potential transformer
5
2.1.3 AUTO TRANSFORMER:
6
2.1.4 ON THE BASIS OF STRUCTURE
7
CHAPTER 3. SPECIFICATION OF C.T. USED IN 33/11 KV SUB STATION, BIN,
PITHORAGARH
The resistance of the instrument’s current coil with which the CT’s secondary winding is connected is small.
The CT’s transformer operates under a state close to the short circuit under normal condition.
The primary winding is installed in series in the current. Current transformers are used for protections,
measurement and control in high-voltage electrical substations and the electrical grid. Current transformers
may be installed inside switchgear or in apparatus bushings, but very often free-standing outdoor current
8
CHAPTER 4. SUBSTATIONS
The present day electrical power system is A.C.i.e. electrical power is generated,transmitted & distributed in
the form of the alternating current. The electric power is produced at power plant stations which are located
at favorable places generally quite away from the consumers. It is delivered to the consumers through a large
network of transmission 7 distribution.At many places in the power system, it may be desirable and
necessary to change some characteristics e.g. voltage, ac to dc, frequency, power factor etc. of electric
supply. This accomplished by suitable apparatus called substation. For example; generation voltage (11 KV
or 33 KV) at the power station is set up to high voltage (say 220 KV or 132 KV) for transmission of electric
power. The assembly of apparatus (e.g. transformer etc.) used for this purpose in the substation. Similarly
near the consumer’s localities, the voltage may have to be step down to utilization level. This job is again
accomplished by suitable apparatus called substation. The assembly of apparatus to change some
characteristic of electric power supply is called substation. The two most ways to classify substation are:-
9
4.1.1.4 Frequency change substation
They are known as transformer substations as because transformer is the main component employed to
change the voltage level, depending upon the purposed served transformer substations may be classified
into:
The generation voltage is steeped up to high voltage to affect economy in transmission of electric power.
These are generally located in the power houses and are of outdoor type
10
4.1.1.1.2 PRIMARY GRID SUBSTATION
Here, electric power is received by primary substation which reduces the voltage level to 11KV for
At a secondary substation, the voltage is further steeped down to 11KV. The 11KV lines runs along the
important road of the city. The secondary substations are also of outdoor type.
These substations are located near the consumer’s localities and step down to 400V, 3-phase, 4-wire for
supplying to the consumers. The voltage between any two phases is 400V & between any phase and neutral
it is 230V.
4.2.1 Each circuit is protected by its own circuit breaker and hence plant outage does not necessarily result in
loss of supply.
4.2.2 A fault on the feeder or transformer circuit breaker causes loss of the transformer and feeder circuit,
one of which may be restored after isolating the faulty circuit breaker.
4.2.3 A fault on the bus section circuit breaker causes complete shutdown of the substation. All circuits may
4.2.4 Maintenance of a feeder or transformer circuit breaker involves loss of the circuit.
4.2.5 Introduction of bypass isolators between bus bar and circuit isolator allows circuit breaker maintenance
The function of an earthing and bonding system is to provide an earthing system connection to which
transformer neutrals or earthing impedances may be connected in order to pass the maximum fault current.
damage occurs on the equipment within the substation, thereby resulting in safety to operation and
maintenance personnel. The earthing system also guarantees equipotent bonding such that there are no
This is the difference in potential between the surface potential and the potential at earthed equipment whilst
This is the potential difference developed when a man bridges a distance of 1m with his feet while not
This is the maximum touch voltage that is developed in the mesh of the earthing grid.
12
4.3.2 Substation Earthing Calculation Methodology
Calculations for earth impedances, touch and step potentials are based on site measurements of ground
resistivity and system fault levels. A grid layout with particular conductors is then analyzed to determine the
effective substation earthing resistance, from which the earthing voltage is calculated.
In practice, it is normal to take the highest fault level for substation earth grid calculation purposes.
Additionally, it is necessary to ensure a sufficient margin such that expansion of the system is catered for.
To determine the earth resistivity, probe tests are carried out on the site. These tests are best performed in
4.3.3.4 Conductors:
Bare copper conductor is usually used for the substation earthing grid. The copper bars themselves usually
have a cross-sectional area of 95 square millimeters, and they are laid at a shallow depth of 0.25-0.5m, in 3-
separate above ground earthing ring is usually provided, to which all metallic substation plant is bonded.
4.3.3.4 Connections:
Connections to the grid and other earthing joints should not be soldered because the heat generated during
fault conditions could cause a soldered joint to fail. Joints are usually bolted.
The earthing grid must be supplemented by earthing rods to assist in the dissipation of earth fault currents
and further reduce the overall substation earthing resistance. These rods are usually made of solid copper, or
13
4.3.4 Switchyard Fence Earthing:
The switchyard fence earthing practices are possible and are used by different utilities. These are:
4.3.4.1 Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter. The fence is then bonded to
4.3.4.2 Place the fence beyond the perimeter of the switchyard earthing grid and bond the fence to its own
earthing rod system. This earthing rod system is not coupled to the main substation earthing grid.
4.4.1 Should be capable of carrying the specified load currents and short time currents.
4.4.2 Should be able to withstand forces on it due to its situation. These forces comprise self weight, and
weight of other conductors and equipment, short circuit forces and atmospheric forces such as wind and ice
loading.
The most suitable material for the conductor system is copper or aluminums. Steel may be used but has
In an effort to make the conductor ideal, three different types have been utilized, and these include: Flat
14
4.5.2 Tensioning conductors to ground winches.
The choice is influenced by the height of towers and the proximity to the substation. The following
15
CHAPTER 5. CHRONOLOGICAL TRAINING DIARY (based on study &
Reliable & fast communication is necessary for safe efficient & economical power supply. To reduce the
power failure in extent & time, to maintain the interconnected grid system in optimum working condition; to
coordinate the operation of various generating unit communication network is indispensable for state
electricity board. In state electricity boards, the generating & distribution stations are generally located at a
far distance from cities. Where P & T communication provided through long overhead lines in neither
As we have available very reliable physical paths viz. the power lines, which interconnected, hence power
line carrier communication is found to be most economical and reliable for electricity boards.
5.1.1 APPLICATIONS:
5.1.1.1 Telephony
5.1.1.5 Teleprinting
All type of information is modulated on carried wave at frequency 50Hz to 500 KHz. The modulated HF
carrier fed into the power line conductor at the sending end and filtered out again at the respective stations.
Long earlier system double side band amplitude modulation was more common but the present amplitude
modulated system. Since high voltage power lines are designed to carry large quantities of energy on the
high voltage and the communication system at low voltage, they cannot be directly connected to high
voltage lines. Suitably designed coupling equipments have therefore to be employed which will permit the
injection of high frequency carrier signal without undue loss and with absolute protection of communication
equipments or operating personal from high voltage hazard. Therefore, the coupling equipment essentially
Wave trap is connected in series with power line between the point of connection of coupling capacitor and
S/S. Wave trap offers negligible impedance to HF carrier. Wave trap stands electromechanically and
thermally for short circuit current in the event of fault on the line. On the basis of blocking frequency bank,
17
5.2.1.4 BROAD BAND
The modulated carrier is let into power line through coupling capacitor specially designed to with stand line
voltage under all weather condition. The upper end of the coupling capacitor is connected directly to the line
and the lower end is connected to the ground through a carrier frequency chock coil or drain coil. Thus
coupling capacitor forms the link between the PLCC equipment and power line. The coupling capacitor used
in UPSEB is 2200pf capacitance. The coupling capacitor are designed for outdoor use and hence to
withstand normal atmospheric phenomenon such as temperature & humidity changes, rain, snow, anticipated
wind load, nominal wire tension etc. at full rated voltage. In some case capacitive voltage transformers
(CVT) used as a source of line voltage for metering and protection as also used coupling capacitor for
PLCC.
This is connected across the primary of the coupling filter i.e. one end is connected to the bottom of the
coupling capacitor and other end is earthed. This is provided to protect the coupling filter against line surges.
An air gap is provided, where voltage of the order of 1.8 to 2KV as observed across due to lighting etc. on
line.
The coupling filter is inserted between the low voltage terminal of the coupling capacitor and the carrier
frequency connection of the carrier terminal. Some time an earth switch is also
provided with this unit. This unit mainly performs two functions; firstly it isolates the connection of
equipment from the power line. Secondly it serves to match characteristic impedance of the power line to
18
5.2.5 H.F. Cable:
H.F. cable normally used to connect the coupling filter to another coupling terminal. The cable is insulated
to withstand the test voltage of 4KV. The impedance of this H.F. cable is so as to match with the output of
The following three types of coupling are being used in UPSEB depending on the requirement:
19
CHAPTER 6. BUSBARS
When numbers of generators or feeders operating at the same voltage have to be directly connected
electrically, bus bar is used as the common electrical component. Bus bars are made up of copper rods
operate at constant voltage. The following are the important bus bars
In large stations it is important that break downs and maintenance should interfere as little as possible with
continuity of supply to achieve this, duplicate bus bar system is used. Such a system consists of two bus
bars, a main bus bar and a spare bus bar with the help of bus coupler, which consist of the circuit breaker and
isolator.
In substations, it is often desired to disconnect a part of the system for general maintenance and repairs. An
isolating switch or isolator accomplishes this. Isolator operates under no load condition. It does not have any
specified current breaking capacity or current making capacity. In some cases isolators are used to breaking
charging currents or transmission lines. While opening a circuit, the circuit breaker is opened first then
isolator while closing a circuit the isolator is closed first, then circuit breakers. Isolators are necessary on
supply side of circuit breakers, in order to ensure isolation of the circuit breaker from live parts for the
purpose of maintenance. A transfer isolator is used to transfer main supply from main bus to transfer bus by
using bus coupler (combination of a circuit breaker with two isolators), if repairing or maintenance of any
section is required.
20
CHAPTER 7. INSULATORS
The insulator serves two purposes. They support the conductors (bus bar) and confine the current to the
conductors. The most common used material for the manufacture of insulator is porcelain. There are several
types of insulators (e.g. pin type, suspension type, post insulator etc.) and their use in substation will depend
upon the service requirement. For example, post insulator is used for bus bars. A post insulator consists of a
porcelain body, cast iron cap and flanged cast iron base. The hole in the cap is threaded so that bus bars can
With the advantage of power system, the lines and other equipment operate at very high voltage and carry
high current. The arrangements of switching along with switches cannot serve the desired function of
switchgear in such high capacity circuits. This necessitates employing a more dependable means of control
such as is obtain by the use of the circuit breakers. A circuit breaker can make or break a circuit either
manually or automatically under all condition as no load, full load and short circuit condition. A circuit
breaker essentially consists of fixed and moving contacts. These contacts can be opened manually or by
remote control whenever desired. When a fault occurs on any part of the system, the trip coils of breaker get
energized and the moving contacts are pulled apart by some mechanism, thus opening the circuit. When
contacts of a circuit breaker are separated, an arc is struck; the current is thus able to continue. The
production of arcs are not only delays the current interruption, but is also generates the heat. Therefore, the
21
main problem is to distinguish the arc within the shortest possible time so that it may not reach a dangerous
value. The general way of classification is on the basis of the medium used for arc extinction.
Note: SF6 and Vacuum circuit breaker are being used in 33KV distribution substation.
22
Fig:-7.3 Oil circuit breaker
A high-voltage circuit breaker in which the arc is drawn in oil to dissipate the heat and extinguish the arc;
the intense heat of the arc decomposes the oil, generating a gas whose high pressure produces a flow of fresh
fluid through the arc that furnishes the necessary insulation to prevent a restrike of the arc.
The arc is then extinguished, both because of its elongation upon parting of contacts and because of
Fast operations, suitability for repeated operation, auto reclosure, unit type multi break constructions, simple
assembly, modest maintenance are some of the main features of air blast circuit breakers. A compressors
plant necessary to maintain high air pressure in the air receiver. The air blast circuit breakers are especially
suitable for railways and arc furnaces, where the breaker operates repeatedly. Air blast circuit breakers is
used for interconnected lines and important lines where rapid operation is desired.
High pressure air at a pressure between 20 to 30 kg/ cm2 stored in the air reservoir. Air is taken from the
compressed air system. Three hollow insulator columns are mounted on the reservoir with valves at their
basis. The double arc extinguished chambers are mounted on the top of the hollow insulator chambers. The
current carrying parts connect the three arc extinction chambers to each other in series and the pole to the
23
neighbouring equipment. Since there exists a very high voltage between the conductor and the air reservoir,
In such circuit breaker, sulphur hexafluoride (SF6) gas is used as the arc quenching
medium. The SF6 is an electronegative gas and has a strong tendency to absorb free electrons. The SF6
circuit breaker have been found to a very effective for high power and high voltage service. SF6 circuit
breakers have been developed for voltage 115 KV to 230 KV, power rating 10 MVA. It consists of fixed and
moving contacts. It has chamber, contains SF6 gas. When the contacts are opened, the mechanism permits a
high pressure SF6 gas from reservoir to flow towards the arc interruption chamber. The moving contact
Vacuum circuit breakers are circuit breakers which are used to protect medium and high voltage circuits
from dangerous electrical situations. Like other types of circuit breakers, vacuum circuit breakers literally
break the circuit so that energy cannot continue flowing through it, thereby preventing fires, power surges,
and other problems which may emerge. These devices have been utilized since the 1920s, and several
companies have introduced refinements to make them even safer and more effective.
25
CHAPTER 8. METERING AND INDICATION
EQUIPMENT
8.1 RELAY
In a power system it is inevitable that immediately or later some failure does occur
somewhere in the system. When a failure occurs on any part of the system, it must be quickly detected and
disconnected from the system. Rapid disconnection of faulted apparatus limits the amount of damage to it
and prevents the effects of fault from spreading into the system. For high voltage circuits relays are
employed to serve the desired function of automatic protective gear. The relays detect the fault and supply
the information to the circuit breaker. The electrical quantities which may change under fault condition are
voltage, frequency, current, phase angle. When a short circuit occurs at any point on the transmission line the
current flowing in the line increases to the enormous value. This result in a heavy current flow through the
relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip circuit of the
breaker making the circuit breaker open and isolating the faulty section from the rest of the system. In this
way, the relay ensures the safety of the circuit equipment from the damage and normal working of the
healthy portion of the system. Basically relay work on the following two main operating principles:
26
8.1.3 DIFFERENTIAL RELAY:
A differential relay is one that operates when vector difference of the two or more
electrical quantities exceeds a predetermined value. If this differential quantity is equal or greater than the
pickup value, the relay will operate and open the circuit breaker to isolate the faulty section.
This type of relay works when current in the circuit exceeds the predetermined value. The actuating source is
the current in the circuit supplied to the relay from a current transformer. These relay are used on A.C.
circuit only and can operate for fault flow in the either direction. This relay operates when phase to phase
fault occurs.
27
8.1.5 DIRECTIONAL RELAY:
This relay operates during earth faults. If one phase touch the earth due to any fault. A directional power
relay is so designed that it obtains its operating torque by the interaction of magnetic field derived from both
voltage and current source of the circuit it protects. The direction of torque depends upon the current relative
to voltage.
28
This type of relay is in the conjunction with main relay. When main relay sense any fault in the system, it
immediately operates the trip relay to disconnect the faulty section from the section.
An auxiliary relay is used to indicate the fault by glowing bulb alert the employee.
29
CHAPTER 9. MISCELLANOUS EQUIPMENT
The load on the power system is varying being high during morning and evening which increases the
magnetization current. This result in the decreased power factor. The low power factor is mainly due to the
fact most of the power loads are inductive and therefore take lagging currents. The low power factor is
highly undesirable as it causes increases in current, resulting in additional losses. So in order to ensure most
favorable conditions for a supply system from engineering and economical stand point it is important to have
power factor as close to unity as possible. In order to improve the power factor come device taking leading
power should be connected in parallel with the load. One of the such device can be capacitor bank. The
capacitor
draws a leading current and partly or completely neutralize the lagging reactive component of load current.
30
9.2 FUSE:
Fig:-9.4 Fuse
A fuse is a short piece of wire or thin strip which melts when excessive current through it for sufficient time.
It is inserted in series with the circuit under normal operating conditions; the fuse element is at a nature
below its melting point. Therefore it carries the normal load current overheating. It is worthwhile to note that
The bus coupler consists of circuit breaker and isolator. Each generator and feeder may be connected to
either main bus bar or spar bus bar with the help of bus coupler. Repairing, maintenance and testing of
feeder circuit or other section can be done by putting them on spar bus bar, thus keeping the main bus bar
undisturbed.
31
CHAPTER 10. PROTECTION OF SUBSTATION:
Transformers are totally enclosed static devices and generally oil immersed. Therefore chances of fault
occurring on them are very easy rare, however the consequences of even a rare fault may be very serious
unless the transformer is quickly disconnected from the system. This provides adequate automatic protection
When the oil expands or contacts by the change in the temperature, the oil level goes either up or down in
main tank. A conservator is used to maintain the oil level up to predetermined value in the transformer main
tank by placing it above the level of the top of the tank. Breather is connected to conservator tank for the
purpose of extracting moisture as it spoils the insulating properties of the oil. During the contraction and
expansion of oil air is drawn in or out through breather silica gel crystals impregnated with cobalt chloride.
Silica gel is checked regularly and dried and replaced when necessary.
It has two meter which indicate the temperature of the oil and winding of main tank. If
temperature of oil or winding exceeds than specified value, relay operates to sound an alarm. If there is
further increase in temperature then relay completes the trip circuit to open the circuit breaker controlling the
transformer.
When the transformer is in operation heat is generated due to iron losses the removal of heat is called
cooling.
In a dry type of self cooled transformers, the natural circulation of surrounding air is used for its cooling.
32
10.4.2 Air blast cooling:
It is similar to that of dry type self cooled transformers with to addition that continuous blast of filtered cool
air is forced through the core and winding for better cooling. A fan produces the blast.
Medium and large rating have their winding and core immersed in oil, which act both as a cooling medium
and an insulating medium. The heat produce in the cores and winding is passed to the oil becomes lighter
and rises to the top and place is taken by cool oil from the bottom of the cooling tank.
In this type of cooling, forced air is directed over cooling elements of transformers
immersed in oil.
Oil is circulated from the top of the transformers tank to a cooling tank to a cooling plant. Oil is then
In this type of cooling oil flow with water cooling of the oil in external water heat
exchanger takes place. The water is circulated in cooling tubes in the heat exchanger.
33
CHAPTER 11. CONCLUSION
Now from this report we can conclude that electricity plays an important role in our life. We are made aware
of how the transmission of electricity is done. We too came to know about the various parts of the Substation
system. The Uttarakhand Cooperation Limited has got radio communication in microwave range in order
to transmit and receive data with various Substations in Uttarakhand to get reliable transmission and
distribution of electricity.
Fig:-9.6 Distribution
34
Bibliography and References
Available:
http://www.alstom.com/Global/Group/Resources/Documents/Investors%20Documents/Investor%20
events/analysts%presentation/Analyst%20Day%20-%HDVC%20technology.pdf.
3. eia, U.S. Energy Information Administration -, "Updated Cost Estimates for Utility Scale Electricity
4. P. Konstantin, "Engineering Economics," in Power and Energy Systems - Engineering Economics, epubli,
Germany, 2015. [52] M. Milton Gussow, Theory and Problems of Basic Electricity, McGrawHill. [53]
35