Apfc 1448 Automatic Power Factor Controller
Apfc 1448 Automatic Power Factor Controller
APFC 1448
MultispanControlInstrumentsPvtLtd
72/B, Phase 1, GIDC Estate, Vatva, Ahmedabad-382445, Gujarat, India.
[email protected] +91-9978991471
www.multispanindia.com
100
Current
Set cosø
Mode Steps
Time Alarm
AUTO MANUAL ROT KVAR
1 2 3 4 5 6 7 8
CapacitorBank
SET
ENT
Technical Specification
Power Supply/
Operation 380 To 450V AC,
Voltage
Protection
Level IP-65 (Front side) As per IS/IEC 60529 : 2001
(As per request)
Operating
Temperature 0°C To 55°C
Relative
Up to 95% RH Non Condensing
Humidity
Power ON
73
CAP IND Current 5.000 (If CAP & IND led is indicated capacitor
CT current & Main CT current )
h
Mode PF VAR
AUTO Automatic
Step3
Step8
Presskey
MCUR Minimumoperatingcurrent
0200 SecondaryCTcurrent
Range(50mAto500mA)
Presskey
p-ON Minimumcapacitor
bankpercentageOn
0065
P-OF Minimumcapacitor
bankpercentageOff
0065
PMOD PasswordMode
PASS Password
O073 PreviousPassword
Presskeytosave&exit
Factory Set
If press + key for 5 sec
faCt
Yes No
Press Key Press Key
Main CT Current
This function display mode is indicated by the "CURRENT" light indicator. The numeric display shows
the true-rms value of the secondary current measured by the 5A current transformer (CT).
Example:
If a 1000/5A CT is used and the display shows "2.50", the primary
measured current is 500A.
Set CosØ
This set the targeted power factor required when the system is under automatic mode. The power
factor regulator will switch the capacitors in or out in order to achieve this set value.
Mode
If we use PF mode no need for external capacitor CT. In PF Mode Three switching program such as
Manual, Rotational, Automatic for there.
If we use KVAR mode in tuning capacitor KVAR values for each capacitor bank will be sense
automatically through capacitor bank CT..
If we use KVAR mode without external capacitor CT. We have to put manually each capacitor bank
KVAR value in rated steps.
Time (TIME)
This parameter set the speed of the switching. A larger sensitivity Time will result in slower switching
speed and conversely, a smaller sensitivity time will result in a faster switching speed. This sensitivity
applies to both switching on and switching off of the capacitor. If switching program is automatic
switching . Then sensitivity time is based on current power factor and target power factor.
Setting Steps
Total 8 capacitor rated steps is indicated capacitor bank sensing. If Capacitor bank is sensing then
capacitor step value is 1 & not sensing (Not Connected) then capacitor step value is 0
Alarm
Alarm LED & Alarm RELAY is indicated power factor is not achieve, capacitor bank is under compensation.
Mechanical Dimension
91mm
144mm
136mm 77mm
Front Panel
144mm
Side
136mm
Cutout
APFC 1448
Contactors N
K1.........K8
Capacitor
K1 K2 K3 K4 K5 K6 K7 K8
C
L1 L2 L3
CT
Capacitor
L1 R1 R2 R3 R4 R5 R6 R7 R8
N
L1 Plant
L2 Load
L3
S1 S2 S1 S2 C NO C NO
AUX SUPPLY
380 ~ 450V AC Main CT Capacitor CT Fan Alarm
/5A /5A