Operational continuity

Safety and reliability of ABB H+Line,


switchboards and devices for group 2
medical locations
ABB technology and safety in
hospital segment
Over ten years experience, a complete Helpful for consultants and designers
What the Standards say it is said by everybody. ABB explains
and performing range of products: what the Standards don’t say. The “Practicle guide for group
this is H+Line, an ABB products range 2 medical locations” can be a useful daily tool for supporting
specific for group 2 medical locations, consultants, designers and installers in each step of the
design and installation process of group 2 medical locations
where operational continuity and electrical networks.
reliability are key requirements for safety
and protection of patients and medical
staff

2 | H+Line - Protection without supply breaking for hospital applications


H+Line Practical guide for group 2 hospital medical locations
Contacts

The document has been developed in a tight collaboration


with ABB customers. The aim is to add practical solutions and
ABB SACE

2CSC470010B0901 - 08/2009 - 1.500 Pz. - CAL.


Data and images are not binding. Depending on technical
development and the products, we reserve the right to
A division of ABB S.p.A.
modify the content of this document without notice.
Modular Devices
Copyright 2010 ABB. All right reserved.

suggestions coming from the field. In this way, the “Practical


Viale dell’Industria, 18
20010 Vittuone (MI) - Italy
Tel.: +39 02 9034 1
Fax: +39 02 9034 7609

bol.it.abb.com

guide to group 2 medical locations” turns into a kind help. Full


www.abb.com

of examples, it is a useful tool even for that ones who designs


hospital electrical networks for the first time ever. Inside the H+Line
practicle guide, ABB customers will find at their complete Practical guide for group 2 hospital
medical locations
disposal all the expertise and know-how of a company which
has always been promoting the issues about safety.

H+Line - Protection without supply breaking for hospital applications | 3


H+Line range

A broaden range of reliable products


to assure safety to patients and
medical staff inside intensive care units,
operating theatres, first aid and day
hospital premises, ambulatories, dental
care, nursing home

ISOLTESTER-DIG, SELVTESTER-24,
insulating monitoring insulating monitoring
devices for 230 V a.c. devices for SELV 24
IT-M circuits V a.c./d.c. circuits
supplying scialitic lamps

4 | H+Line - Protection without supply breaking for hospital applications


QSD-DIG 230/24, remote TI, insulating transformers QSO, wall mounted and floor
signaling panel with supplying IT-M circuits standing switchboards for
luminous and acoustic group 2 medical locations
fault indication

H+Line - Protection without supply breaking for hospital applications | 5


QSO switchboards and devices
for group 2 medical locations

ArTu enclosures
TI isolating QSO floor standing switchboards
are assembled with ArTu K
transformers for enclosures

medical use
It grants protection against indirect
contacts without breaking the
supply during the first fault to earth. DDA 200 RCD block
ABB TI allows also to completely
It protects emergency section in case
control the overtemperature on the
of leakage current to earth
primary and secondary windings due
to overload.

OVR surge
protection
ISOLTESTER-DIG-RZ
Designed for the safeguard of
electric devices from transient Insulating monitoring device for
overvoltages group 2 medical locations
fault detection

Safety lock E 930 fuse switch


The door can be locked to prevent disconnectors
unintentional intervention of
Switching the secondary winding
unskilled personnel
allows the maintenance on IT-M
circuits, assuring operational
continuity to light and emergency
circuits

S200
Miniature circuit Technical
brakers documentation
Instruction manual for switchboard
They protects IT-M circuits from short installation, commissioning and
circuits and overloads maintenance is located inside the
switchboard

6 | H+Line - Protection without supply breaking for hospital applications


To comply with medical requirements, ABB QSO are already assembled
with isolating transformers TI and insulation monitoring device
ISOLTESTER-DIG-RZ which detects and signals the first fault to earth

Transparent Free modules Fixing brackets


Door The modular architecture of the and lifting eyebolts
switchboard makes possible to add
The door of the further components easily They allows to safely move the
switchboard shall be switchboard and fix it on the wall
opened in two parts in
order to have an easier Terminals
maintenance of
modular devices IT-M and traditional TN-S
circuits are mechanically
separated

Equipotential
bonding bus bar
Extraneous conductive parts must
be wired on the equipotential node

Narrow in depth
Wall mounted QSO shall be
installed inside compartments or
nooks

ArTu Enclosures
Wall mounted QSO are
assembled with ArTu M eclosures

H+Line - Protection without supply breaking for hospital applications | 7


Protection by electrical separation as laid down by angiography and blood flow tests, premature births), where the
IEC standard 60364-7-710 (user electrical systems use of an IT-M (Medical IT) system is mandatory.
with a rated voltage of no more than 1000 V in In addition, they are suitable for installation in other kinds of
alternating current and 1500 V in direct current) medical locations and in any other room in which the service
prevents the generation of hazardous currents due to has not to be interrupted automatically at the first fault: industrial
a failure in the main insulation of the circuit. laboratories, workshops of jewellers and other craftsmen, test
laboratories, school laboratories, research institutes and other
rooms with similar problems.
By using insulating transformers, the protection against indirect QSO switchboards are equipped with pre-cabled outputs and
contacts can be guaranteed without having to shut off the free modules and are designed, built and tested in accordance
circuit automatically at the first earthing fault. Insulating with the provisions laid down by the IEC Standard 60601-1-1
transformers are therefore suitable for use in plants in which the (AS and ANS type low-voltage panels), IEC 60364-7-710,
sudden and automatic shutoff of the service could have serious (requirements for special installations or locations, medical
implications: examples of these applications are plants for locations); each panel comes with a conformity declaration,
medical and surgery rooms (in accordance with IEC Standard which guarantees that it complies to the reference Standards.
60364-7-710) in which specific medical devices perform patient The metal structure of the QSO switchboards is made using the
monitoring and attending functions. To meet the special needs modular framework of the ArTu distribution cabinets, which
of these fields of application, ABB supplies preassembled guarantee safety and reliability due to the characteristics of its
wall-mounted and floor-standing QSO switchboards, complete standardized elements. The colour is RAL 7032. The QSO
with an insulating transformer and an ISOLTESTER for detecting switchboards are available in wall mounted and floor-standing
and signalling the first earthing fault. versions having power values of 3 kVA, 5 kVA, 7.5 kVA and 10
QSO switchboards represent the ideal solution for all medical kVA. Some versions have insulating transformers with PT100
locations classified by the IEC Standard 60364-7-710 as group probes for detecting and controlling the overtemperature of the
2 medical locations (rooms for anaesthesia, surgery, pre- medical transformer.
operative preparation, surgical plaster application, post- All components used to build QSO switchboards can
operative wakening, heart catheter application, intensive care, also be ordered separately.

IT-M system
Supply
IT-M circuits

TEST
prova pushbutton

Insulating Insulation monitoring device


transfomer
intended for RESET pushbutton
medical use

TEST pushbutton

Remote signalling panel

MUTE pushbutton

Equipotential
bonding bus bar

8 | H+Line - Protection without supply breaking for hospital applications


- Easier installation: time
saving up to 20 hours
- Safety: certified insulating
transformers; no type approval
required
- Flexibility: available in different
versions for all kind of applications
which can be customized
- Reliability: the quality of ABB
technology in every component
- Compact size: limited overall
dimensions
- Completeness: 24 V line control,
embedded PT100 probes
- Effectiveness: complete network
monitoring

H+Line - Protection without supply breaking for hospital applications | 9


ISOLTESTER-DIG-PLUS
The solution to unwanted trippings

When it is necessary to guarantee safety and service continuity and avoid


interruptions in power supplies, for example in hospitals and other medical
locations, it is mandatory to use insulation transformers intended for medical use
and an insulation monitoring devices which detect and signal any possible first
fault to earth.

Risks derived from the use of a traditional


insulation monitor:
- impossible to distinguish between a
disturbance and a real fault
- unwanted trippings causing distraction of the
medical staff during surgical operation
- unjustified intervention of specialized technical
staff

Traditional CRT or LCD displays, A traditional insulation monitoring


undercarriage equipment for the device can provide an unwanted
oxygen distribution, x-ray machines alarm
and sterilization equipment
can generate interference within the
network

10 | H+Line - Protection without supply breaking for hospital applications


ISOLTESTER-DIG-PLUS is the new device for insulation
monitoring in IT systems. It ensures absolute reliability of
measurement by the means of a codified signal, that is able
to detect the disturbances generated by common devices in
surgery rooms, avoiding unwanted alarms signalling

Advantages of ISOLTESTER-DIG-PLUS:
- reliability of the monitoring under any
operational condition thanks to its codified
signal
- integration with supervision systems through
ModbusRTU protocol via RS485 serial port
- fault analysis by means of maximum and
minimum values measurement
- warning signal shall be delivered up to 4
rooms where medical and technical staff is
Despite network ripples and ISOLTESTER -DIG-PLUS avoids present
disturbances... unwanted trippings - complete control of any alarm thanks to a
programmable relay

H+Line - Protection without supply breaking for hospital applications | 11


ISOLTESTER-DIG
Insulation monitoring devices

ISOLTESTER-DIG-RZ
- Quality: the recognized standard in
hospital
- Specialization: properly designed for
hospitals
- Completeness: all electrical and
thermal parameters controlled by a
single device
- Flexibility: adjustable thresholds
according to the parameters
monitored
- Strength: high resistance to network
interference

Functioning principle
Insulation resistance is measured by applying a direct
current signal between the isolated line and earth: the level
of insulation can be determined by measuring the leakage
current to earth. ISOLTESTER-DIG-RZ ensures an effective
measurement of the insulation resistance even in the presence
of strong interference and high harmonic or direct-current
components, due to its sophisticated digital filter.

Programming
The device offers broad programming possibilities through its
user-friendly digital display menu and four selection keys.

Complete monitoring of all electrical parameters


ISOLTESTER-DIG-RZ tests the thermal and electric overload
of the insulating transformer, managing both PT100 or PTC
probes. The electric overload monitoring of the medical
transformer can also be tested by connecting a current
transformer and setting appropriate alarm thresholds. The
alarms can be controlled remotely by connecting up to four
QSD signalling panels.

Self testing system


Error-Link Fail system checkes that the terminals are
connected correctly: it prevents the possibility to operate
when the insulating monitoring device is disconnected.

12 | H+Line - Protection without supply breaking for hospital applications


ISOLTESTER-DIG-PLUS
- Reliability and safe monitoring under
every environmental condition, thanks
to the digital measuring signal
- Integration: with supervising systems
through ModbusRTU protocol via
RS485 serial port
- Fault analysis by means of the
measurement of the maximum and
minimum values
- Complete control of any alarm thanks
to the programmable relay

For higher safety


With ISOLTESTER-DIG-PLUS it is possible to operate even in
environments affected by heavy ripples and harmonics.
Furthermore it can be integrated with supervising systems
and PC/PLC networks thanks to its RS485 serial port with
ModbusRTU protocol. The measurement of the maximum and
minimum values of each parameter is an helpful information to
understand the cause of the fault.
Finally the programmable output relay allows to manage every
fault condition.

ISOLTESTER-DIG is the insulation monitoring device specifically designed by ABB


for group 2 medical locations. ISOLTESTER-DIG measures permanently the resi-
stance to earth in IT-M circuits and thermal and electrical overload of the insulating
transformers for medical use, complying completely with the requirements of the
international Standards: IEC 61557-8, IEC 60364-7-710 and UNE 20615
H+Line - Protection without supply breaking for hospital applications | 13
ISOLTESTER-DIG

Frontal operators functioning


Green LED, SET: Yellow LED, Alarm:
Led indicating tool programming status Led indicating parameter out of
alarm range

Display for viewing


the value of the Red LED, Output Relay:
parameters tested and the settings Led indicating the status of
auxiliary output relay

Red LED, R:
Led indicating insulation
resistance (kΩ), it blinks when Red LED, Error/Link Fail:
the parameter is out of range Led indicating internal fault alarm,
no link to the line or temperature
probe failure

Red LED, Z:
Led indicating insulation
impedance and line capacity,
it blinks when the parameter
is out of range
TEST | ENTER:
Button for device testing. And
confirmation of the programmed
parameters
Red LED, T1:
Led indicating temperature
on the 1st probe, it blinks when
the parameter is out of range

RESET | SET:
Buttons for device programming
Red LED, T2:
Led indicating temperature
on the 2nd probe, it blinks when
the parameter is out of range

Red LED, I: Buttons for selecting parameter


Led indicating line current, it blinks to be viewed and changing tool
when the parameter is out of range settings

Easy programming with


four pushbuttons only

14 | H+Line - Protection without supply breaking for hospital applications


Multiple rooms monitoring

1 Medical location 1 2 Medical location 2 3 Medical location 3

A Control room

4 Medical location 4 5 Medical location 5 6 Medical location 6

1 2 3 4 5 6

ModbusRTU

With ISOLTESTER-DIG-PLUS and automation devices


by ABB it is possible to monitor electrical parameters
from different medical locations from a single control
room, tanks to ModbusRTU protocol and CP400
touch screen terminals
H+Line - Protection without supply breaking for hospital applications | 15
SELVTESTER-24
Insulation monitoring device
for scialitic lamps
SELVTESTER-24 tests the earth insulation of 24 V a.c./d.c. - Flexibility: programmable alarm
SELV circuits and is particularly suitable for medical
locations (IT-M systems) in which both 24 V and 230 V
threshold
lines are present; in these environments, it is important to - Intelligence: recognition of faulty pole
have a permanent control of the low voltage line as, in the in direct current
event of a fault or short-circuit, this line could transfer a
potential of over 250 V with consequent damage to
- Compact size: fits into just 3 modules
equipment and people. - Practicality: extremely simple to install
and use
SELVTESTER-24 measures the variation in potential of the
two network polarities with reference to earth in order to
- Integration: ideal complement for
signal when insulation drops below a set value, identifying the ISOLTESTER-DIG
faulty pole in direct current. The output signal can be
connected to the remote signalling panel QSDDIG 230/24, to
be installed in the rooms powered by the controlled line.
The alarm threshold can be adjusted using microswitches

Frontal operators functioning


Green LED ON
Device is working correctly

Microswitches
They allows to set the alarm
threshold from 10 to 50 kΩ, as
shown in the picture.

Yellow LED ALARM


Indication of low insulation in a.c.
both LEDs blink, in d.c. it blinks
only the LED corresponding to the
faulty pole

TEST pushbutton
It tests that the device is working
properly

16 | H+Line - Protection without supply breaking for hospital applications


QSD-DIG 230/24
Remote signalling panel

The QSD remote signalling panel enables to control - Compact: narrow dimensions
the alarms from the insulation monitoring devices from
remote. Alarms shall be delivered to all rooms under
- Easy: it can be installed in a common
supervision of medical or technical personeel. 3 modules flush mounted box
- Reliable: it is immediate to recognize
The QSD panels provide an acoustic and luminous indication
for low isolation or thermal and electric overload. In
the fault type
addition, they have a TEST button to check their operating - Comfort: all QSDs in parallel shall be
status and a pushbutton for turning off the acoustic indication muted in a single touch
provided by the embedded buzzer.
They are assembled in universal 3-module flush-mounted
- Efficiency: both visual and acoustic
boxes. signalling

Frontal operators functioning


TEST pushbutton Green LED device is
working properly

Red LED for overload or


overtemperature alarm

Yellow LED for fault alarm


MUTE pushbutton

H+Line - Protection without supply breaking for hospital applications | 17


TI
Insulating transformers

- Specialization: designed specially for


Permanently connected to an IT power supply system,
single-phase medical insulating transformers provide
medical use
galvanic separation between the distribution network - Compact size: the insulating
and the user load in accordance with the IEC EN 61558-1 transformers are the most compact on
and IEC EN 61558-2-15 concerning power supply group 2
medical locations.
the market
- Quality: the insulation of the windings
ABB insulating transformers for medical use have small designed with exclusive vacuum-
dimensions, so that it is possibile to reduce the cost of the
overall switchboard. The range is made up by insulating
pressure technology, guarantees
transformers with 3, 5, 7,5 10 kVA rated power, available maximum heat dissipation
with two PT100 temperature probes, on the primary and the - Accessories: versions available with
secondary winding, which make possible to take precise
control over the overtemperature of the transformer. ABB
PT100
insulating transformers are built with a particular technology
which allows a better heating dissipation. Finally, the metallic
shield between the windings allows to reduce disturbances
and harmonics coming from the upstream supply. Simply
comunicating the serial number of the item , ABB will provide
the test reports of each medical TI: this prevent the installer
to deliver under his responsibility further tests after product
installation.

Primary winding Secondary winding


0-230: Primary 0-230: Secondary
SCH: Metallic shield SCH: Central socket

Probe 1
1: to 28 terminal of ISOLTESTER-DIG
PE 2: to 28 terminal of ISOLTESTER-DIG
3: to 30 terminal of ISOLTESTER-DIG

Probe 2
4: to 25 terminal of
230
SCH
0

ISOLTESTER-DIG
5: to 25 terminal of
PC
0

230

1
2

ISOLTESTER-DIG
3
4
5
6

6: to 27 terminal of
ISOLTESTER-DIG

Serial number
all ABB customers can receive the
test report by communicating the
serial number printed on the base
of each TI

18 | H+Line - Protection without supply breaking for hospital applications


QSO Switchboards for operating theatres
Technical features

Technical features
Rated power 3 kVA 5 kVA 7,5 kVA 10 kVA
Wall mounted QSO Rated voltage [V] 230/230 230/230 230/230 –
Rated current [A] 13,63 22,72 34,09 –
Dimensions LxHxD [mm] 700 x 1150 x 210 700 x 1150 x 210 700 x 1150 x 210 –
Floor standing QSO Rated voltage [V] 230/230 230/230 230/230 230/230
Rated current [A] 13,63 22,72 34,09 45,45
Dimensions LxHxD [mm] 538 x 2250 x 365 538 x 2250 x 365 538 x 2250 x 365 538 x 2250 x 365

Overall dimensions
Front view Side view Front view Side view
700 210 538 365
600

PV 4060
1123
1100
1000

1151

2250
PO 6069

629
751

Top view
130
69
130

210

556
Wall mounted QSO Floor standing QSO

H+Line - Protection without supply breaking for hospital applications | 19


QSO Switchboards for operating theatres
Logical operating diagrams

Input 1 2 3 Output 1

Output 2

6
5
6

QSD-DIG
230

Wall mounted QSO


Rated power 3 kVA 5 kVA 7,5 kVA
1 E 932/50 Fuse disconnector 25 A gL 32 A gL 40 A gL
2 Insulating transformer TI ... (S) 3 kVA 5 kVA 7,5 kVA
3 S202 L Miniature circuit breaker 16 A 25 A 40 A
4 E 91hN/32 Fuseholder 2 A gL 2 A gL 2 A gL
5 ISOLTESTER-DIG-RZ yes
6 PT100 probes S version S version S version

Input 14 14 14 14
1 6 QSD-DIG
2 4 11 230
7 12
11

9 14
5 10

Id
8 9
3 13

Aux
Linea 24 V

Output 10
Output....

line
Output 1

Output 2

QSD
230/24-C

Floor standing QSO


Rated power 3 kVA 5 kVA 7,5 kVA 10 kVA
1 E202 Disconnector 100 A
2 S202 Miniature circuit breaker 25 A - curve C
3 OVR T2 1N 40 275s P Surge protection device 40 kA - 275 V
4 S202 L Miniature circuit breaker 16 A - type AC
5 DDA 202 AC RCD block 25 A 30 mA - curve C
6 S202 Miniature circuit breaker 20 A - curve D 32 - curve D 50 - curve D 63 - curve D
7 Insulating transformer TI ...(S) 3 kVA 5 kVA 7,5 kVA 10 kVA
8 E 932/50 Fuse disconnector 50 A gL
9 E 92/32 Fuseholder 32 A gL 32 A gL 32 A gL 32 gL
10 ISOLTESTER-DIG-RZ yes
11 PT100 probes yes
12 TM-C 1000/12-24 Transfomer 24 V version
13 SELVTESTER-24 24 V version
14 S202 Miniature circuit breaker 16 A - curve C

20 | H+Line - Protection without supply breaking for hospital applications


ISOLTESTER-DIG
Technical features

Technical features ISOLTESTER-DIG-RZ ISOLTESTER-DIG-PLUS


Rated 110 - 230 V/50-60 Hz
Network voltage to be controlled 24 ÷ 230 V a.c.
Voltage max. measure 24 V
Current max. measure 1 mA
Insulation voltage 2,5 kV/60 sec.
Type of control’s signal Direct component with digital filter Codified signal
Sensed measures Measure range 0 ÷ 999 kohm/HIGH - resolution 1 kohm
Thermal-probe temperature PT100 0÷250 °C, accuracy 2%
Current measure from external CT with secondary 5 A , accuracy 2% (selectable statement value CT 1÷200)
Impedance measure 0 ÷ 999 Kohm/HIGH - Impedance measure 0 ÷ 999 Kohm/HIGH -
resolution 1 Kohm (test signal 2500 Hz) resolution 1 Kohm (codified composed signal)
Intervention threshold Low insulation 50 ÷ 500 kohm, accuracy 5%, hysteresis 5%, delay which can be setted
Overtemperature 0 ÷200 °C, accuracy 2%
Overload current 1 ÷ 999 A, accuracy 2%
Low impedance (which can be disarmed)
Error-Link Fail
Available output
Max. up to 2 QSD panels for remote signalling Max. up to 4 QSD panels for remote signalling

Programmable output relay NA-C-NC, 5 A, 250 V a.c.


Output relay NA-C-NC, 5 A, 250 V a.c.
Serial output RS485, standard protocol Modbus-rtu

Displays Insulation resistance value with signalling of over fullscale value and direct earth fault
Value of measured temperature 0 ÷ 200 °C per channel 1
Value of measured temperature 0 ÷ 200 °C per channel 2
Value of measured current 0 ÷ 999 A
Value insulation impedance
Setting parameters
Link fail
Relays output status
Value of network capacity to earth
Min and max values of measured parameters
Connection Max. section 2.5 sqmm
Operating temperature -10...60 °C
Storage temperature -25...70 °C, humidity < 90%
Modules 6
Weight 0,5 kg
Housing Plastic self-extinguishing housing for 35 mm,
with transparent sealable plate
Protection degree IP20
Power consumption 5 VA
Standards IEC 60364-7-710, IEC 61557-8, EN 60255-6, UNE 20615

H+Line - Protection without supply breaking for hospital applications | 21


ISOLTESTER-DIG
Technical features

ISOLTESTER-DIG Wiring diagrams

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 2 1 CT .../5 A RS485 2 1 CT .../5 A


(only PLUS PT100 PT100 Out (only PLUS PT100 PT100 Out
version) version)
ISOL TESTER-DIG-RZ ISOL TESTER-DIG-RZ
ISOL TESTER-DIG-PLUS ISOL TESTER-DIG-PLUS QSD-DIG 230/ 24
QSD-DIG 230/24
V aux.* V aux.* Insulation V aux.* Insulation
115 V 115 V 115 V 115 V Link Fail control QSD-DIG 230/24 115 V 115 V Link Fail control QSD-DIG 230/ 24

1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11

V aux. 115 V a.c. V aux. 230 V a.c. V aux. 230 V a.c.


Other QSD-D IG

Other QSD-DIG
PE PE

S S S S

L L
PC
IT-M Load IT-M Load

N N

Insulating transformer with PC Insulating transformer without PC

In case of insulating transformer with central socie (pc) In case of insulating transformer without central socket (pc)

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 2 1 CT .../5 A
(only PLUS PT100 PT100 Out.
version)

ISOL TESTER-DIG-RZ
ISOL TESTER-DIG-PLUS
QSD-DIG 230/ 24
V aux.* Insulation
115 V 115 V Link Fail control QSD-DIG 230/24

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11

V aux. 230 V a.c.


Other QSD-DIG

PE

S S

N
L3 IT-M Load
L2
L1
Insulating transformer

In case of three phase insulating transformer

* It is an option to wire temperature probes and current transformer

Overall dimensions
61 61
90

90

45
90

90

45

44 44
105 105
56 56
6 moduli
6 modules

22 | H+Line - Protection without supply breaking for hospital applications


selvtester-24
Technical features

Technical features SELVTESTER-24


Network voltage and auxiliary power supply 24 V a.c./d.c.
Frequency 50-60 Hz
Power consumption 3 VA
Max measuring current 0,5 mA
Internal impedance 50 kΩ
Threshold setting programmable to 10 ÷ 50 kohm (4 levels using microswitches)
Delay about 1 second
Signals LED ON, LED ALARM +, LED ALARM -
Output for up to 2 QSD-230/24-C, max. 24 V 1 A remote panels
Remote signalling panel max. 2 QSD-DIG 230/24
Operating temperature -10 ÷ 60 °C
Storage temperature -20 ÷ 70 °C
Relative humidity ≤ 95%
Insulation test 2,5 kV 60 s / 4 kV imp. 1,2/50 µs
Terminal cross section 4 mm2
Front degree of protection IP40 with cover / IP20 box
Modules 3
Weight about 200 g
Standards IEC 61010-1; IEC 60364-7-710; IEC 61326-1

Wiring diagram
SELVTESTER-24 QSD-DIG 230/24

1 2 3 4 5 6 7 8 9 10 11 1 2 3 C1 C2 C3 C4 X Y Z
Other QSD-230/24-C

PE

S S

L(+)
IT-M Load
N(-)

Insulating transformer

Overall dimensions
85,5

85,5

45

52,5 44

58
3 modules

H+Line - Protection without supply breaking for hospital applications | 23


Remote signalling panel
QSD-DIG 230/24
Technical features
Technical features QSD-DIG 230/24
Signals green led network, red led overload ALARM, yellow led low insulation FAULT ALARM, acoustic signaller,
emission 2400 Hz intermittence 2 Hz dB
Pushbuttons TEST and MUTE
Terminal cross section 2,5 mm 2
Protection degree IP30
Installation universal flush-mounted box
Weight 200 g
Operating temperature -10 ÷ 60 °C, max. humidity 95%
Storage temperature -25 ÷ +80 °C
Insulation 2.500 Vrms 50 Hz per 60 s
Cables section 0.35 mm 2 for 300 m
Standards IEC 61010-1; IEC 61557-8; IEC 60364-7-710; UNE 20615; IEC 61326-1

Wiring diagrams
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 2 1 CT .../5 A
(only PLUS PT100 PT100 Out
version) SELVTESTER-24 QSD-DIG 230/24

ISOL TESTER-DIG-RZ
ISOL TESTER-DIG-PLUS
QSD-DIG 230/24
V aux.* V aux.* Insulation 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
115 V 115 V 115 V 115 V Link Fail control QSD-DIG 230/24 V+ V- OUT-NO OUT-C OUT-NC PE COM-S F-S V-P ACUS ACK OVER FAULT COMP TEST- TEST-S TEST+

1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11

V aux. 115 V a.c. V aux. 230 V a.c.


Other QSD-D IG

PE
PE

OTHER
S S QSD-DIG 230/24
S S

L(+)
L
PC IT-M LOAD
IT-M Load
N(-)
N

Insulating transformer with PC Insulating transformer

ISOLTESTER-DIG SELVTESTER-24

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

ISOLTESTER- C ISOLTESTER-RZ

QSD-DIG 230/24 QSD-DIG 230/24


Out
Vaux: * Insulation Insulation Va ux: *
QSD-DIG 230/24
230V Link Fail control control
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 A B C D 11 10 9 8 7 6 5 4 3 2 1 C O M-S F - S V- P ACUS ACK OVER FA ULT COM-P TEST- T E S T - S TEST+
COM-S F-S V-P ACUS ACK OVER FAULT COM-P TEST- TEST-S TEST+
AUX-01 VC-L VC-PE COM-P FAULT V-P R-NC R-NO R-C AUX-L1 AUX-01 AUX-L2 AUX-02 R-NC R-C R-NO VC-PE VC-L V-P2 FAULT2 COM-P 2 V-P1 FAULT1 COM-P 1
AUX-L1 LF-L LF-PE

Vaux: 230Va.c.

PE
PE

OTHER
QSD-DIG 230/24
S S
S S

L
L
PC
PC
IT-M LOAD
N
N

Insulating transformer

ISOLTESTER-C ISOLTESTER-RZ

Overall dimensions
55
78
78

17
121

24 | H+Line - Protection without supply breaking for hospital applications


Insulating transformers TI
Technical features

Technical features
Rated output 3 kVA 5 kVA 7,5 kVA 10 kVA
Electrical protection class 1
Thermal insulation class [°C] B 130 B 130 F 155 F 155
Operating temperature max [°C] 40
Primary winding voltage [V] 230
Secondary winding voltage [V] 230
Secondary current [A] 13 21,7 32,6 43,5
Inrush current max [A] 221 369 553 738
Fuse rated current on the [A] T 12,5 T 20 T 32 T 40
secondary winding
Power dissipation [W]] 120 150 260 320
Frequency [Hz] 50 - 60
Secondary winding leakage [mA] < 0,5
current to earth
Leakage current to earth [mA] < 0,5
Short circuit voltage drop < 3%
No load current [In] < 3%
Leakage current between [mA] < 3,5
windings

Dimensions [mm] 205 x 340 x 150 240 x 380 x 150 240 x 380 x 160 277 x 380 x 260
Weight [kg] 29,5 44 50,5 73
Standards IEC EN 61558-1; IEC EN 61558-2-15; IEC EN 62041

Overall dimensions
3 KVA 5 KVA 7,5 KVA 10 KVA
b [mm] 205 240 240 277
c [mm] 170 170 170 176
f [mm] 115 115 115 173
h [mm] 340 380 380 380
h

p [mm] 150 150 160 203

f c

p b

H+Line - Protection without supply breaking for hospital applications | 25


Order codes

QSO order codes


BbN
PT 100 SELV
Wall mounted Type 8012542 Order code
probes circuit
EAN
QSO 3 kVA QSO 3kVA 2376101 2CSM110000R1551
QSO 5 kVA QSO 5kVA 2376200 2CSM120000R1551
QSO 7,5 kVA QSO 7,5kVA 2376309 2CSM130000R1551
QSO 3 kVA  QSO 3kVA-S 2526308 2CSM210000R1551
QSO 5 kVA  QSO 5kVA-S 2526407 2CSM220000R1551
QSO 7,5 kVA  QSO 7,5kVA-S 2526506 2CSM230000R1551
BbN
PT 100 SELV
Floor standing Type 8012542 Order code
probes circuit
EAN
QSO 3 kVA  QSO 3kVA-S-PV 2526605 2CSM310000R1551
QSO 5 kVA  QSO 5kVA-S-PV 2526704 2CSM320000R1551
QSO 7,5 kVA  QSO 7,5kVA-S-PV 2526803 2CSM330000R1551
QSO 10 kVA  QSO 10kVA-S-PV 2526902 2CSM340000R1551
QSO 3 kVA   QSO 3kVA-S-PV+24Vca 2614302 2CSM410000R1551
QSO 5 kVA   QSO 5kVA-S-PV+24Vca 2614401 2CSM420000R1551
QSO 7,5 kVA   QSO 7,5kVA-S-PV+24Vca 2614500 2CSM430000R1551
QSO 10 kVA   QSO 10kVA-S-PV+24Vca 2614609 2CSM440000R1551

Isoltester-DIG order codes


BbN
Type 8012542 Order code
EAN
ISOLTESTER-DIG-RZ 884507 2CSM244000R1501
ISOLTESTER-DIG-PLUS 884606 2CSM341000R1501

SELVTESTER-24 order codes


BbN
Monitored network Type 8012542 Order code
EAN
IT-M SELV 24 V a.c./d.c. SELVTESTER-24 884705 2CSM211000R1511

26 | H+Line - Protection without supply breaking for hospital applications


QSD-DIG 230/24 order codes
BbN
Compatibility Type 8012542 Order code
EAN
Universal QSD-DIG 230/24 730637 2CSM273063R1521

TI order codes
BbN
Rated output PT100 probe 8012542 Order code
EAN
3 kVA 2896005 2CSM110000R1541
5 kVA 2896104 2CSM120000R1541
7,5 kVA 2896203 2CSM130000R1541
10 kVA 2521204 2CSM140000R1541
3 kVA  2521402 2CSM210000R1541
5 kVA  2521501 2CSM220000R1541
7,5 kVA  2521600 2CSM230000R1541
10 kVA  2521709 2CSM240000R1541
Shock absorber 2CSM900000R1541

PLC order codes


Description Type Order code
PLC 8 input 6 digital output 24 V d.c. PM554-T 1TNE968900R0100
sink/source, 24 V d.c. supply

Touch screen CP400 order codes


Description Type Order code
Touch screen panel 3.5‘‘ CP415M 1SBP260191R1001

H+Line - Protection without supply breaking for hospital applications | 27


Contact us

ABB SACE

2CSC004033B0201 - 05/2010 - 2.000 Pz. - CAL.


The data and illustrations are not binding. We reserve
the right to modify the contents of this document on
A division of ABB S.p.A. the basis of technical development of the products,
Line Protection Devices without prior notice.
Viale dell’Industria, 18
Copyright 2010 ABB. All rights reserved.
20010 Vittuone (MI) - Italy
Tel.: +39 02 9034 1
Fax: +39 02 9034 7609

www.abb.com