Neutral Shift and Arcing Ground in Power System
Neutral Shift and Arcing Ground in Power System
The Capacitive currents lead respective voltage by 90°. There is no change in line voltages
but the voltages to ground of unfaulted phases rise to line voltage level.
| VRY |=| VYB |=| VYB |= √3 pu (i.e. 11 kV)
Phase voltages at healthy phase is given by,
| VY |=| VB |= √3 pu (i.e. 11 kV)
| VR|= 0 (faulted Phase)
The Fault current can be calculated as follows,
|IRB|=|IRY|=√3/ XC
IF=IRB+IRY=3/ XC
The Capacitive current per phase 1/XC of typical industrial system can be from 2A to 5A.If
the fault current exceeds 4A-5A, then it is sufficient to maintain the arc in the ionized path
of the fault, even though the fault has cleared itself .The capacitive current over 4A to 5A
flows through the fault give rise to an arc in the ionized path of the fault. With the formation
of the arc, the voltage across it becomes zero and therefore the arc is extinguished. Then
potential (voltage) of the fault current is restored due to which the formation of a second arc
takes places. The phenomenon of intermitting arcing is called the arcing ground. The breaker
duty becomes onerous due to possibility of restrikes when trying to break the capacitive
currents. The alternating extinction and re-ignition of the charging current flowing in the arc
build up the potential (voltage) of the other two healthy conductors which may cause
insulation failure.
Peterson coil (arc suppression coil) is used for the elimination of arcing ground. Peterson
coil extinguishes the arcing ground by neutralizing the capacitive current.
Figure 1
Figure 2
Reference:
“Electrical Power Systems: Concept, Theory and Practice” by Subir Ray.
“KR Monograph” by Rajamani Krishnamurti.