Relion® 670 series

Busbar protection REB670


Pre-configured
Product Guide
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Contents

1. Application.....................................................................3 9. Basic IED functions......................................................19


2. Available functions..........................................................9 10. Human machine interface............................................19
3. Differential protection....................................................12 11. Station communication ...............................................20
4. Zone selection..............................................................13 12. Remote communication..............................................21
5. Current protection........................................................16 13. Hardware description..................................................21
6. Control.........................................................................16 14. Connection diagrams..................................................24
7. Logic............................................................................17 15. Technical data.............................................................30
8. Monitoring....................................................................17 16. Ordering......................................................................54

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2 Issued: February 2015
Revision: E

1. Application setting value for the minimum differential operating current is


REB670 is designed for the selective, reliable and fast from 50% to 150% of the biggest CT. This setting is made
differential protection of busbars, T-connections and meshed directly in primary amperes. The operating slope for the
corners. REB670 can be used for protection of single and differential operating characteristic is fixed to 53% in the
double busbar with or without transfer bus, double circuit algorithm.
breaker or one-and-half circuit breaker stations. The IED is
applicable for the protection of medium voltage (MV), high The fast tripping time of the low-impedance differential
voltage (HV) and extra high voltage (EHV) installations at a protection function is especially advantageous for power
power system frequency of 50Hz or 60Hz. The IED can system networks with high fault levels or where fast fault
detect all types of internal phase-to-phase and phase-to- clearance is required for power system stability.
earth faults in solidly earthed or low impedance earthed
The advanced open CT detection algorithm detects instantly
power systems, as well as all internal multi-phase faults in
the open CT secondary circuits and prevents differential
isolated or high-impedance earthed power systems.
protection operation without any need for additional check
REB670 has very low requirements on the main current zone.
transformers (that is, CTs) and no interposing current
Differential protection zones in REB670 include a sensitive
transformers are necessary. For all applications, it is possible
operational level. This sensitive operational level is designed
to include and mix main CTs with 1A and 5A rated secondary
to be able to detect internal busbar earth faults in low
current within the same protection zone. Typically, CTs with
impedance earthed power systems (that is, power systems
up to 10:1 ratio difference can be used within the same
where the earth-fault current is limited to a certain level,
differential protection zone. Adjustment for different main CT
typically between 300A and 2000A primary by a neutral point
ratios is achieved numerically by a parameter setting.
reactor or resistor). Alternatively this sensitive level can be
The numerical, low-impedance differential protection function used when high sensitivity is required from busbar differential
is designed for fast and selective protection for faults within protection (that is, energizing of the bus via long line).
protected zone. All connected CT inputs are provided with a
Overall operating characteristic of the differential function in
restraint feature. The minimum pick-up value for the
REB670 is shown in figure 1.
differential current is set to give a suitable sensitivity for all
internal faults. For busbar protection applications typical

Sensitive
differential
protection
Id [Primary Amps]

Operate
I in region
I d=
Differential protection
operation characteristic
Diff Oper Level
Sens Iin Block
Sensitive Oper Level
s=0.53

Iin [Primary Amps]


en06000142.vsd
IEC06000142 V1 EN

Figure 1. REB670 operating characteristic

Integrated overall check zone feature, independent from any protection in case of entirely wrong status indication of
disconnector position, is available. It can be used in double busbar disconnector in any of the feeder bays.
busbar stations to secure stability of the busbar differential

ABB 3
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Flexible, software based dynamic Zone Selection enables A20. The version is intended for simpler applications such as
easy and fast adaptation to the most common substation T-connections, meshed corners, and so on.
arrangements such as single busbar with or without transfer
bus, double busbar with or without transfer bus, one-and-a- Description of 3 ph package A31
half breaker stations, double busbar-double breaker stations, Three-phase version of the IED with two low-impedance
ring busbars, and so on. The software based dynamic Zone differential protection zones and eight three-phase CT inputs
Selections ensures: A31. The version is intended for applications on smaller
busbars, with up to two zones and eight CT inputs.
• Dynamic linking of measured CT currents to the
appropriate differential protection zone as required by Description of 1 ph packages B20 and B21
substation topology One-phase version of the IED with two low-impedance
• Efficient merging of the two differential zones when differential protection zones and twelve CT inputs B20, B21.
required by substation topology (that is load-transfer)
• Due to three available binary input modules, the B20 is
• Selective operation of busbar differential protection
intended for applications without need for dynamic Zone
ensures tripping only of circuit breakers connected to
Selection such as substations with single busbar with or
the faulty zone
without bus-section breaker, one-and-half breaker or
• Correct marshaling of backup-trip commands from
double breaker arrangements. Three such IEDs offer
internally integrated or external circuit breaker failure
cost effective solutions for such simple substation
protections to all surrounding circuit breakers
arrangements with up to twelve CT inputs.
• Easy incorporation of bus-section and/or bus-coupler
• The B21 is intended for applications in substations
bays (that is, tie-breakers) with one or two sets of CTs
where dynamic Zone Selection or bigger number of
into the protection scheme
binary inputs and outputs is needed. Such stations for
• Disconnector and/or circuit breaker status supervision
example are double busbar station with or without
Advanced Zone Selection logic accompanied by optionally transfer bus with up to 12 CT inputs. Note that binary
available end-fault and/or circuit breaker failure protections inputs can be shared between phases by including the
ensure minimum possible tripping time and selectivity for LDCM communication module. This simplifies panel
faults within the blind spot or the end zone between bay CT wiring and saves IO boards.
and bay circuit breaker. Therefore REB670 offers best
• This version can be used with external auxiliary 3-phase
possible coverage for such faults in feeder and bus-section/
to 1-phase summation current transformers with
bus-coupler bays.
different turns ratio for each phase.
Optionally available circuit breaker failure protection, one for
every CT input into REB670, offers secure local back-up Description of 1 ph package B31
protection for the circuit breakers in the station. One-phase version of the IED with two low-impedance
differential protection zones and twenty-four CT inputs B31.
Optionally available four-stage, non-directional overcurrent
protections, one for every CT input into REB670, provide • The IED is intended for busbar protection applications in
remote backup functionality for connected feeders and big substations where dynamic Zone Selection, quite
remote-end stations. large number of binary inputs and outputs and many CT
inputs are needed. The IED includes two differential
It is normal practice to have just one busbar protection IED
zones and twenty-four CT inputs. Note that binary inputs
per busbar. Nevertheless some utilities do apply two
can be shared between phases by including the LDCM
independent busbar protection IEDs per zone of protection.
communication module. This simplifies panel wiring and
REB670 IED fits both solutions.
saves IO boards.
A simplified bus differential protection for multi-phase faults
• This version can be used with external auxiliary 3-phase
and earth faults can be obtained by using a single, one-phase
to 1-phase summation current transformers with
REB670 IED with external auxiliary summation current
different turns ratio for each phase.
transformers.

The wide application flexibility makes this product an Available configurations for pre-configured REB670
excellent choice for both new installations and the Three configurations have been made available for pre-
refurbishment of existing installations. configured REB670 IED. It shall be noted that all three
configurations include the following features:
Description of 3 ph package A20
Three-phase version of the IED with two low-impedance
differential protection zones and four three-phase CT inputs

4 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

• fully configured for the total available number of bays in from every disconnector and/or circuit breaker. Thus full
each REB670 variant disconnector/breaker supervision is available. This
• facility to take any bay out of service via the local HMI or configuration is available for only three REB670 variants
externally via binary input (that is A31, B21 and B31). It shall be noted that optional
• facility to block any of the two zones via the local HMI or functions breaker failure protection CCRBRF, end fault
externally via binary input protection and overcurrent protection PH4SPTOC can
• facility to block all bay trips via the local HMI or externally be ordered together with this configuration, but they will
via binary input, but leaving all other function in service not be pre-configured. Thus these optional functions
(that is BBP Zones, BFP and OCP where applicable) shall be configured by the end user.
• facility to externally initiate built-in disturbance recorder
• facility to connect external breaker failure backup trip
Configuration X03
signal from every bay
• This configuration includes BBP with breaker failure
• facility to connect external bay trip signal
protection CCRBRF, end fault protection and overcurrent
protection PH4SPTOC for double busbar-single breaker
Configuration X01 stations, where Zone Selection is done by using a and b
• This configuration includes just busbar protection for auxiliary contacts from every disconnectors and/or
simple stations layouts (that is One-and-a-half breaker, circuit breakers. Thus full disconnector/breaker
Double Breaker or Single Breaker stations). Additionally supervision is available. This configuration is available for
it can be used for double busbar-single breaker stations only three REB670 variants (that is A31, B21 and B31).
where disconnector replica is done by using just b
auxiliary contact from every disconnector and/or circuit
Application examples of REB670
breakers. As a consequence no disconnector/breaker
Examples of typical station layouts, which can be protected
supervision will be available. It is as well possible to
with REB670 are given below:
adapt this configuration by the Signal Matrix tool to be
used as direct replacement of RED521 · 1.0 terminals.
This configuration is available for all five REB670 variants
(that is A20, A31, B20, B21 & B31). It shall be noted that
optional functions breaker failure protection CCRBRF,
end fault protection and overcurrent protection
PH4SPTOC can be ordered together with this
configuration, but they will not be pre-configured. Thus
these optional functions shall be configured by the end
user.
xx06000009.vsd
IEC06000009 V1 EN

Configuration X02 Figure 2. Example of T-connection


• This configuration includes just busbar protection for
double busbar-single breaker stations, where Zone
Selection is done by using a and b auxiliary contacts

QB1
ZA ZB

QA1 QA1 QA1 QA1 QA1 QA1 QA1

BI1 BI1 BI1 BI1 BI1 BI1 BI1

xx06000012.vsd
IEC06000012 V1 EN

Figure 3. Example of single bus station

ABB 5
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

ZA

ZB
QB1 QB7 QB1 QB7 QB1 QB7 QB1 QB7 QB1 QB7 QB1 QB7

QA1 QA1 QA1 QA1 QA1 QA1

BI1 BI1 BI1 BI1 BI1 BI1

xx06000013.vsd
IEC06000013 V1 EN

Figure 4. Example of single bus station with transfer bus

ZA

ZB
QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2
BI1

QA1 QA1 QA1 QA1 QA1 QA1 QA1

BI1 BI1 BI1 BI1 BI1 BI1

xx06000014.vsd
IEC06000014 V1 EN

Figure 5. Example of double bus-single breaker station

ZA
ZB

QB1 QB2 QB7 QB1 QB2 QB7 QB1 QB2 QB7 QB20 QB1 QB2 QB7 QB1 QB2 QB7

QA1 QA1 QA1 QA1 QA1

BI1 BI1 BI1


BI1 BI1

xx06000015.vsd
IEC06000015 V1 EN

Figure 6. Example of double bus-single breaker station with transfer bus

QA1
BI1

ZA1 ZA2

ZB1 ZB2
QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2
BI1 BI1 QA1 BI1

QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1

BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1

xx06000016.vsd
IEC06000016 V1 EN

Figure 7. Example of double bus-single breaker station with two bus-section and two bus-coupler breakers

6 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

ZA

QA1 QA1 QA1 QA1 QA1

BI1 BI1 BI1 BI1 BI1

QA2 QA2 QA2 QA2 QA2


BI2 BI2 BI2 BI2 BI2

BI3 BI3 BI3 BI3 BI3

QA3 QA3 QA3 QA3 QA3

ZB
xx06000017.vsd
IEC06000017 V1 EN

Figure 8. Example of one-and-a-half breaker station

ZA

ZB
QA1 QA2 QA1 QA2 QA1 QA2 QA1 QA2 QA1 QA2

BI1 BI2 BI1 BI2 BI1 BI2 BI1 BI2 BI1 BI2

xx06000018.vsd
IEC06000018 V1 EN

Figure 9. Example of double bus-double breaker station

BI8 BI5
Q 5
B8 QB11 BI1 QA1 QB12 B
Q
ZA1 ZA2

QB41 QB21

QA4 QA2

BI4 BI2

QB42 QB22
QB31 BI3 QA3 QB32
ZB1 B
7 Q
B
6
ZB2
Q

BI7 BI6

xx06000019.vsd
IEC06000019 V1 EN

Figure 10. Example of mesh or ring bus station

ABB 7
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Note that customized REB670 is delivered without any configuration. Thus the complete IED engineering shall be done by the
customer or its system integrator. In order to secure proper operation of the busbar protection it is strictly recommended to
always start engineering work from the PCM600 project for the pre-configured REB670 which is the closest to the actual
application. Then, necessary modifications shall be applied in order to adopt the customized IED configuration to suite the
actual station layout. The PCM600 project for the pre-configured REB670 IEDs is available in the Connectivity Package DVD.

8 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

2. Available functions

Main protection functions

2 = number of basic instances


3-A03 = optional function included in packages A03 (refer to ordering details)

IEC 61850 ANSI Function description Busbar

REB670 (B20)

REB670 (B21)

REB670 (B31)
REB670 (A20)

REB670 (A31)
Differential protection

BUTPTRC, 87B Busbar differential protection, 2 zones, three phase/4 bays 1


BCZTPDIF,
BZNTPDIS,
BZITGGIO

BUTPTRC, 87B Busbar differential protection, 2 zones, three phase/8 bays 1


BCZTPDIF,
BZNTPDIF,
BZITGGIO

BUSPTRC, 87B Busbar differential protection, 2 zones, single phase/12 bays 1 1


BCZSPDIF,
BZNSPDIF,
BZISGGIO

BUSPTRC, 87B Busbar differential protection, 2 zones, single phase/24 bays 1


BCZSPDIF,
BZNSPDIF,
BZISGGIO

SWSGGIO Status of primary switching object for busbar protection zone selection 20 40 60 60 96

Back-up protection functions

IEC 61850 ANSI Function description Busbar


REB670 (B20)

REB670 (B21)

REB670 (B31)
REB670 (A20)

REB670 (A31)

Current protection

OC4PTOC 51_67 Four step phase overcurrent protection 4-C06 8-C07

PH4SPTOC 51 Four step single phase overcurrent protection 12- 12- 24-
C08 C08 C08

CCRBRF 50BF Breaker failure protection 4-C10 8-C11

CCSRBRF 50BF Breaker failure protection, single phase version 12- 12- 24-
C12 C12 C13

ABB 9
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Control and monitoring functions

IEC 61850 ANSI Function description Busbar

REB670 (A20)

REB670 (A31)

REB670 (B20)

REB670 (B21)

REB670 (B31)
Control

SMBRREC 79 Autorecloser 2-H05 2-H05 2-H05 2-H05 2-H05

QCBAY Apparatus control 1 1 1 1 1

LOCREM Handling of LRswitch positions 1 1 1 1 1

LOCREMCTR LHMI control of PSTO 1 1 1 1 1


L

SLGGIO Logic rotating switch for function selection and LHMI presentation 15 15 15 15 15

VSGGIO Selector mini switch 20 20 20 20 20

DPGGIO IEC61850 generic communication I/O functions 16 16 16 16 16

SPC8GGIO Single pole generic control 8 signals 5 5 5 5 5

AutomationBits AutomationBits, command function for DNP3.0 3 3 3 3 3

SingleComma Single command, 16 signals 4 4 4 4 4


nd16Signals

Logic

Configuration logic blocks 40-280 40-28 40-280 40-280 40-28


0 0

FixedSignals Fixed signal function block 1 1 1 1 1

B16I Boolean 16 to Integer conversion 16 16 16 16 16

B16IFCVI Boolean 16 to Integer conversion with Logic Node representation 16 16 16 16 16

IB16 Integer to Boolean 16 conversion 16 16 16 16 16

IB16FCVB Integer to Boolean 16 conversion with Logic Node representation 16 16 16 16 16

Monitoring

CVMMXN Measurements 6 6 6 6 6

EVENT Event function 20 20 20 20 20

DRPRDRE Disturbance report 1 1 1 1 1

SPGGIO IEC61850 generic communication I/O functions 64 64 64 64 64

SP16GGIO IEC61850 generic communication I/O functions 16 inputs 16 16 16 16 16

MVGGIO IEC61850 generic communication I/O functions 24 24 24 24 24

BSStatReport Logical signal status report 3 3 3 3 3

RANGE_XP Measured value expander block 28 28 28 28 28

10 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Designed to communicate

IEC 61850 ANSI Function description Busbar

REB670 (A20)

REB670 (A31)

REB670 (B20)

REB670 (B21)

REB670 (B31)
Station communication

SPA communication protocol 1 1 1 1 1

LON communication protocol 1 1 1 1 1

IEC60870-5-103 communication protocol 20/1 20/1 20/1 20/1 20/1

Operation selection between SPA and IEC60870-5-103 for SLM 1 1 1 1 1

DNP3.0 for TCP/IP and EIA-485 communication protocol 1 1 1 1 1

DNP3.0 fault records for TCP/IP and EIA-485 communication protocol 1 1 1 1 1

Parameter setting function for IEC61850 1 1 1 1 1

Goose binary receive 10 10 10 10 10

Multiple command and transmit 60/10 60/10 60/10 60/10 60/10

Ethernet configuration of links 1 1 1 1 1

IEC 62439-3 Edition 1 parallel redundancy protocol 1-P01 1-P01 1-P01 1-P01 1-P01

IEC 62439-3 Edition 2 parallel redundancy protocol 1-P02 1-P02 1-P02 1-P02 1-P02

Remote communication

Binary signal transfer receive/transmit 6/36 6/36 6/36 6/36 6/36

Transmission of analog data from LDCM 1 1 1 1 1

Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3

ABB 11
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Basic IED functions

IEC 61850 Function description

Basic functions included in all products

IntErrorSig Self supervision with internal event list 1

TIME Time and synchronization error 1

TimeSynch Time synchronization 1

ActiveGroup Parameter setting groups 1

Test Test mode functionality 1

ChangeLock Change lock function 1

TerminalID IED identifiers 1

Productinfo Product information 1

MiscBaseCommon Misc Base Common 1

IEDRuntimeComp IED Runtime Comp 1

RatedFreq Rated system frequency 1

SMBI Signal Matrix for binary inputs 40

SMBO Signal Matrix for binary outputs 40

SMMI Signal Matrix for mA inputs 4

SMAI Signal Matrix for analog inputs 24

Sum3Ph Summation block 3 phase 12

LocalHMI Parameter setting function for HMI in PCM600 1

LocalHMI Local HMI signals 1

AuthStatus Authority status 1

AuthorityCheck Authority check 1

AccessFTP FTP access with password 1

SPACommMap SPA communication mapping 1

DOSFRNT Denial of service, frame rate control for front port 1

DOSOEMAB Denial of service, frame rate control for OEM port AB 1

DOSOEMCD Denial of service, frame rate control for OEM port CD 1

3. Differential protection to give a suitable sensitivity for all internal faults. This setting
The function consists of differential protection algorithm, is made directly in primary amperes. For busbar protection
sensitive differential protection algorithm, check zone applications typical setting value for the minimum differential
algorithm, open CT algorithm and two supervision algorithms. operating current is from 50% to 150% of the biggest CT.
The settings can be changed from the front HMI or via the
Busbar differential protection parameter-setting tool, PCM600.
This protection function is intended for fast and selective
tripping of faults within protected zone. For each current All current inputs are indirectly provided with a restraint
input, the CT ratio can be set from the front HMI or via the feature. The operation is based on the well-proven RADSS
parameter-setting tool, PCM600. In this way adaptation to percentage restraint stabilization principle, with an extra
different CT ratios is provided in the simplest way. The stabilization feature to stabilize for very heavy CT saturation.
minimum pick-up value for the differential current is then set Stability for external faults is guaranteed if a CT is not

12 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

saturated for at least two milliseconds during each power restraint quantity. If required, the check zone operation can
system cycle. It is also possible to add external tripping be activated externally by a binary signal.
criteria by binary signal.
Open CT detection
The trip command from the differential protection including The innovative measuring algorithm provides stability for open
sensitive differential protection and circuit breaker failure or short-circuited main CT secondary circuits, which means
backup-trip commands can be set either as self-resetting or that no separate check zone is actually necessary. Start
latched. In second case the manual reset is needed in order current level for open CT detection can usually be set to
to reset the individual bay trip output contacts. detect the open circuit condition for the smallest CT. This
built-in feature allows the protection terminal to be set very
Sensitive differential level BZISGGIO sensitive, even to a lower value than the maximum CT primary
Differential protection zones in REB670 include a sensitive rating in the station. At detection of problems in CT
operational level. This sensitive operational level is designed secondary circuits, the differential protection can be instantly
to be able to detect internal busbar earth faults in low blocked and an alarm is given. Alternatively, the differential
impedance earthed power systems (i.e. power systems where protection can be automatically desensitized in order to
the earth-fault current is limited to a certain level, typically ensure busbar differential protection stability during normal
between 300A and 2000A primary by a neutral point reactor through-load condition. When problems in CT secondary
or resistor). For increased security, the sensitive differential circuits have been found and associated error has been
protection must be externally enabled by a binary signal (e.g. corrected a manual reset must be given to the IED. This can
from external open delta VT overvoltage relay or external be done locally from the local HMI, or remotely via binary
power transformer neutral point overcurrent relay). Finally it is input or communication link.
as well possible to set a time delay before the trip signal from
the sensitive differential protection is given. This sensitive However, it is to be noted that this feature can only be partly
level can be alternatively used in special applications when utilized when the summation principle is in use.
high sensitivity is required from busbar differential protection
(i.e. energizing of dead bus via a long line). Differential protection supervision
Dual monitoring of differential protection status is available.
Operation and operating characteristic of the sensitive The first monitoring feature operates after settable time delay
differential protection can be set independently from the when differential current is higher than the user settable level.
operating characteristic of the main differential protection. This feature can be, for example, used to design automatic
However, the sensitive differential level is blocked as soon as reset logic for previously described open CT detection
the total incoming current exceeds the pre-set level or when feature. The second monitoring feature operates immediately
differential current exceed the set minimum pickup current for when the busbar through-going current is bigger than the
the usual differential protection. Therefore, by appropriate user settable level. Both of these monitoring features are
settings it can be ensured that this sensitive level is blocked phase segregated and they give out binary signals, which can
for all external multi-phase faults, which can cause CT be either used to trigger disturbance recorder or for alarming
saturation. Operating characteristic of sensitive differential purposes.
characteristics is shown in figure 1.

Check zone 4. Zone selection


For busbar protection in double busbar stations when Typically CT secondary circuits from every bay in the station
dynamic zone selection is needed, it is sometimes required to are connected to the busbar protection. The built-in software
include the overall differential zone (that is, check zone). feature called “Zone Selection” gives a simple but efficient
Hence, the built-in, overall check zone is available in the IED. control over the connected CTs to busbar protection IED in
Because the built-in check zone current measurement is not order to provide fully operational differential protection
dependent on the disconnector status, this feature ensures scheme for multi-zone applications on both small and large
stability of Busbar differential protection even for completely buses.
wrong status indication from the busbar disconnectors. It is
The function consists of dedicated disconnector/circuit
to be noted that the overall check zone, only supervise the
breaker status monitoring algorithm, bay dedicated CT-
usual differential protection operation. The external trip
connection control algorithm and zone interconnection
commands, breaker failure backup-trip commands and
algorithm.
sensitive differential protection operation are not supervised
by the overall check zone. Switch status monitoring
For stations with complex primary layout (that is, double
The overall check zone has simple current operating
busbar single breaker station with or without transfer bus) the
algorithm, which ensures check zone operation for all internal
information about busbar disconnector position in every bay
faults regardless the fault current distribution. To achieve this,
is crucial information for busbar protection. The positions of
the outgoing current from the overall check zone is used as
ABB 13
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

these disconnectors then actually determine which CT input Note that the first scheme only requires fast breaking normally
(that is, bay) is connected to which differential protection closed auxiliary contact (that is, b contact) for proper
zone. For some more advanced features like end-fault or operation. The timing of normally open auxiliary contact is not
blind-spot protection the actual status of the circuit breaker in critical because it is only used for supervision of the primary
some or even all bays can be vital information for busbar object status. The second scheme in addition requires
protection as well. The switch function block is used to take properly timed-adjusted, early-making normally open auxiliary
the status of two auxiliary contacts from the primary device, contact (that is, early making a contact) for proper operation.
evaluate them and then to deliver the device primary contact
position to the rest of the zone selection logic. Regardless which scheme is used the time-delayed
disconnector/circuit breaker status supervision alarm is
For such applications typically two auxiliary contacts (that is, available (that is, 00 or 11 auxiliary contact status). How two
normally open and normally closed auxiliary contacts) from integrated differential protection zones behave when
each relevant primary switching object shall be connected to disconnector alarm appears is freely configurable by the end
the IED. Then the status for every individual primary switching user.
object will be determined. The dedicated function block for
each primary switching object is available in order to It is possible by a parameter setting to override the primary
determine the status of the object primary contacts. By a object status as either permanently open or permanently
parameter setting one of the following two logical schemes closed. This feature can be useful during testing, installation
can be selected for each primary object individually by the and commissioning of the busbar protection scheme. At the
end user: same time, separate alarm is given to indicate that the actual
object status is overwritten by a setting parameter.
• If not open then closed (that is, as in RADSS schemes)
It is to be noted that it is as well possible to use only normally
• Open or closed only when clearly indicated by aux closed auxiliary contacts for Zone Selection logic. In that case
contact status (that is, as in INX schemes) the Switch function blocks are not used.

Table 1 gives quick overview about both schemes.

Table 1. Treatment of primary object auxiliary contact status

Primary equipment Status in busbar protection Alarm facility

Normally Open Normally when when Alarm after Information visible on local HMI
auxiliary Closed “Scheme 1 “Scheme 2 settable time
contact status auxiliary RADSS” INX” delay
(that is, contact status is selected is selected
“closed” or (that is,
“a” contact) “open” or “b”
contact)

open open closed Last position yes intermediate_00


saved

open closed open open no open

closed open closed closed no closed

closed closed closed closed yes badState_11

the two internally available differential functions in software.


Bay This can be done by a parameter setting for simple station
Each CT input is allocated to one dedicated bay function layouts (that is, one-and-a-half breaker stations) or
block. This function block is used to provide complete user alternatively via dedicated logical scheme (that is, double
interface for all signals from and towards this bay. It is also busbar stations). For each bay the end user have to select
used to influence bay measured current. one of the following five alternatives:
It is possible by a parameter setting CTConnection to connect
or disconnect the CT input to the bay function block. Once
the CT input is connected to the bay function block this
associated current input can be included to or excluded from

14 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

• Permanently connect this bay current to zone A (that is, The third option ensures that the feeder, which is out of
ZA) service, is not connected to any of the two zones during zone
• Permanently connect this bay current to zone B (that is, interconnection.
ZB)
• Permanently connect this bay current to zone A and Within the Bay function block it is decided by a parameter
inverted bay current to ZB (that is, ZA and ZB) setting whether this bay should be connected to the check
• Connect this bay current to ZA or ZB depending on the zone or not. In this way the end user has simple control over
logical status of the two input binary signals available on the bays, which shall be connected to the overall check zone.
this bay function block. These two input signals will
By appropriate configuration logic it is possible to take any
include measured current to the respective zone when
bay (that is, CT input) out of service. This can be done from
their logical value is one (that is, CntrlIncludes ). This
the local HMI or externally via binary signal. In that case all
option is used together with above described Switch
internal current measuring functions (that is, differential
function blocks in order to provide complete Zone
protection, sensitive differential protection, check zone,
Selection logic
breaker failure protection and overcurrent protection) are
• Connect the bay current to ZA or ZB depending on the
disabled. At the same time, any trip command to this bay
logical status of the two input binary signals available on
circuit breaker can be inhibited.
this bay function block. These two signals will include
measured current to the respective zone when their Via two dedicated binary input signals it is possible to:
logical value is zero (that is, CntrlExcludes ). This option
is typically used when only normally closed auxiliary • Trip only the bay circuit breaker (used for integrated OC
contacts from the busbar disconnector are available to protection tripping)
the Zone Selection logic • Trip the whole differential zone to which this bay is
presently connected (used for backup-trip command
At the same time, an additional feature for instantaneous or from either integrated or external bay circuit breaker
time delayed disconnection or even inversion of the failure protection)
connected bay current via separate logical signals is also
available. This feature is provided in order to facilitate for bus- Finally dedicated trip binary output from the Bay function
section or bus-coupler CT disconnection for tie-breakers with block is available in order to provide common trip signal to
a CT only on one side of the circuit breaker. This ensures the bay circuit breaker from busbar differential protection,
correct and fast fault clearance of faults between the CT and breaker failure protection, backup overcurrent protection and
the circuit breaker within these bays. The same feature can so on.
be individually used in any feeder bay to optimize Busbar
differential protection performance, when feeder circuit In this way the interface to the user is kept as simple as
breaker is open. Thus, the end-fault protection for faults possible and IED engineering work is quite straight forward.
between circuit breaker and the CT is available. However, to
Zone interconnection (Load transfer)
use this feature circuit breaker auxiliary contacts and closing
When this feature is activated the two integrated differential
command to the circuit breaker shall be wired to the binary
protection zones are merged into one common, overall
inputs of the IED. Therefore, he IED offers best possible
differential zone. This feature is required in double busbar
coverage for these special faults between CT and circuit
stations when in any of the feeder bays both busbar
breaker in feeder and bus-section/bus-coupler bays.
disconnectors are closed at the same time (that is, load
Within the Bay function block it is decided by a parameter transfer). As explained in above section Bay each CT input
setting how this bay should behave during zone will then behave in the pre-set way in order to ensure proper
interconnection (that is, load transfer). For each bay current balancing during this special condition. This feature
individually one of the following three options can be selected: can be started automatically (when Zone Selection logic
determines that both busbar disconnectors in one feeder bay
• Bay current is forced out from both zones during zone are closed at the same time) or externally via dedicated binary
interconnection (used for bus-coupler bays) signal. If this feature is active for longer time than the pre-set
• Bay current is unconditionally forced into both zones vale the alarm signal is given.
during zone interconnection (used in special applications)
• Bay current is connected to both zones during zone
interconnection if the bay was previously connected to
one of the two zones (typically used for feeder bays)

ABB 15
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

5. Current protection CCRBRF can be single- or three-phase initiated to allow use


with single phase tripping applications. For the three-phase
Four step phase overcurrent protection OC4PTOC version of CCRBRF the current criteria can be set to operate
The four step phase overcurrent protection function only if two out of four for example, two phases or one phase
OC4PTOC has an inverse or definite time delay independent plus the residual current start. This gives a higher security to
for step 1 and 4 separately. Step 2 and 3 are always definite the back-up trip command.
time delayed.
CCRBRF function can be programmed to give a single- or
All IEC and ANSI inverse time characteristics are available three-phase re-trip of the own breaker to avoid unnecessary
together with an optional user defined time characteristic. tripping of surrounding breakers at an incorrect initiation due
to mistakes during testing.
The directional function is voltage polarized with memory. The
function can be set to be directional or non-directional Breaker failure protection, single phase version CCSRBRF
independently for each of the steps. Breaker failure protection, single phase version (CCSRBRF)
function ensures fast back-up tripping of surrounding
Second harmonic blocking level can be set for the function
breakers.
and can be used to block each step individually
A current check with extremely short reset time is used as
This function can be used as a backup bay protection (e.g.
check criteria to achieve a high security against unnecessary
for transformers, reactors, shunt capacitors and tie-breakers).
operation.
A special application is to use this phase overcurrent
protection to detect short-circuits between the feeder circuit CCSRBRF can be programmed to give a re-trip of the own
breaker and feeder CT in a feeder bay when the circuit breaker to avoid unnecessary tripping of surrounding
breaker is open. This functionality is called end-fault breakers at an incorrect starting due to mistakes during
protection. In such case unnecessarily operation of the testing.
busbar differential protection can be prevented and only fast
overcurrent trip signal can be sent to the remote line end. In
order to utilize this functionality the circuit breaker status and 6. Control
CB closing command must be connected to the REB670.
Autorecloser SMBRREC
One of the overcurrent steps can be set and configured to act
The autoreclosing function provides high-speed and/or
as end-fault protection in REB670.
delayed three pole autoreclosing. The autoreclosing can be
The function is normally used as end fault protection to clear used for delayed busbar restoration. One Autorecloser
faults between current transformer and circuit breaker. (SMBRREC) per zone can be made available.

Four step single phase overcurrent protection PH4SPTOC Logic rotating switch for function selection and LHMI
Four step single phase overcurrent protection presentation SLGGIO
(PH4SPTOC)has an inverse or definite time delay independent The logic rotating switch for function selection and LHMI
for each step separately. presentation (SLGGIO) (or the selector switch function block)
is used to get a selector switch functionality similar to the one
All IEC and ANSI time delayed characteristics are available provided by a hardware selector switch. Hardware selector
together with an optional user defined time characteristic. switches are used extensively by utilities, in order to have
different functions operating on pre-set values. Hardware
The function is normally used as end fault protection to clear switches are however sources for maintenance issues, lower
faults between current transformer and circuit breaker. system reliability and an extended purchase portfolio. The
logic selector switches eliminate all these problems.
Breaker failure protection CCRBRF
Breaker failure protection (CCRBRF) ensures fast back-up Selector mini switch VSGGIO
tripping of surrounding breakers in case the own breaker fails The Selector mini switch VSGGIO function block is a
to open. CCRBRF can be current based, contact based, or multipurpose function used for a variety of applications, as a
an adaptive combination of these two conditions. general purpose switch.
Current check with extremely short reset time is used as VSGGIO can be controlled from the menu or from a symbol
check criterion to achieve high security against inadvertent on the single line diagram (SLD) on the local HMI.
operation.
Single point generic control 8 signals SPC8GGIO
Contact check criteria can be used where the fault current The Single point generic control 8 signals (SPC8GGIO)
through the breaker is small. function block is a collection of 8 single point commands,
designed to bring in commands from REMOTE (SCADA) to

16 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

those parts of the logic configuration that do not need controls if the block's output should reset or return to the
extensive command receiving functionality (for example, state it was, after a power interruption. RESET input has
SCSWI). In this way, simple commands can be sent directly priority.
to the IED outputs, without confirmation. Confirmation (status)
of the result of the commands is supposed to be achieved by
Fixed signal function block
other means, such as binary inputs and SPGGIO function
The Fixed signals function (FXDSIGN) generates a number of
blocks. The commands can be pulsed or steady.
pre-set (fixed) signals that can be used in the configuration of
AutomationBits, command function for DNP3.0 AUTOBITS an IED, either for forcing the unused inputs in other function
AutomationBits function for DNP3 (AUTOBITS) is used within blocks to a certain level/value, or for creating certain logic.
PCM600 to get into the configuration of the commands
coming through the DNP3 protocol. The AUTOBITS function 8. Monitoring
plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON). Measurements CVMMXN, CMMXU, VNMMXU, VMMXU,
CMSQI, VMSQI
Single command, 16 signals The measurement functions are used to get on-line
The IEDs can receive commands either from a substation information from the IED. These service values make it
automation system or from the local HMI. The command possible to display on-line information on the local HMI and
function block has outputs that can be used, for example, to on the Substation automation system about:
control high voltage apparatuses or for other user defined
functionality. • measured voltages, currents, frequency, active, reactive
and apparent power and power factor
• primary and secondary phasors
7. Logic
• positive, negative and zero sequence currents and
Configurable logic blocks voltages
A number of logic blocks and timers are available for the user • mA, input currents
to adapt the configuration to the specific application needs. • pulse counters

• OR function block.
Event counter CNTGGIO
• INVERTER function blocks that inverts the input signal. Event counter (CNTGGIO) has six counters which are used for
storing the number of times each counter input has been
• PULSETIMER function block can be used, for example, for activated.
pulse extensions or limiting of operation of outputs, settable
pulse time. Disturbance report DRPRDRE
Complete and reliable information about disturbances in the
• GATE function block is used for whether or not a signal primary and/or in the secondary system together with
should be able to pass from the input to the output. continuous event-logging is accomplished by the disturbance
report functionality.
• XOR function block.
Disturbance report DRPRDRE, always included in the IED,
• LOOPDELAY function block used to delay the output signal acquires sampled data of all selected analog input and binary
one execution cycle. signals connected to the function block with a, maximum of
40 analog and 96 binary signals.
• TIMERSET function has pick-up and drop-out delayed
outputs related to the input signal. The timer has a settable The Disturbance report functionality is a common name for
time delay. several functions:

• AND function block. • Event list


• Indications
• SRMEMORY function block is a flip-flop that can set or
• Event recorder
reset an output from two inputs respectively. Each block
• Trip value recorder
has two outputs where one is inverted. The memory setting
• Disturbance recorder
controls if the block's output should reset or return to the
state it was, after a power interruption. Set input has The Disturbance report function is characterized by great
priority. flexibility regarding configuration, starting conditions,
recording times, and large storage capacity.
• RSMEMORY function block is a flip-flop that can reset or
set an output from two inputs respectively. Each block has
two outputs where one is inverted. The memory setting
ABB 17
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

A disturbance is defined as an activation of an input to the


AxRADR or BxRBDR function blocks, which are set to trigger Trip value recorder DRPRDRE
the disturbance recorder. All signals from start of pre-fault Information about the pre-fault and fault values for currents
time to the end of post-fault time will be included in the and voltages are vital for the disturbance evaluation.
recording.
The Trip value recorder calculates the values of all selected
Every disturbance report recording is saved in the IED in the analog input signals connected to the Disturbance report
standard Comtrade format. The same applies to all events, function. The result is magnitude and phase angle before and
which are continuously saved in a ring-buffer. The local HMI is during the fault for each analog input signal.
used to get information about the recordings. The
The trip value recorder information is available for the
disturbance report files may be uploaded to PCM600 for
disturbances locally in the IED.
further analysis using the disturbance handling tool.
The trip value recorder information is an integrated part of the
Event list DRPRDRE
disturbance record (Comtrade file).
Continuous event-logging is useful for monitoring the system
from an overview perspective and is a complement to specific Disturbance recorder DRPRDRE
disturbance recorder functions. The Disturbance recorder function supplies fast, complete
and reliable information about disturbances in the power
The event list logs all binary input signals connected to the
system. It facilitates understanding system behavior and
Disturbance report function. The list may contain up to 1000
related primary and secondary equipment during and after a
time-tagged events stored in a ring-buffer.
disturbance. Recorded information is used for different
Indications DRPRDRE purposes in the short perspective (for example corrective
To get fast, condensed and reliable information about actions) and long perspective (for example functional analysis).
disturbances in the primary and/or in the secondary system it
The Disturbance recorder acquires sampled data from
is important to know, for example binary signals that have
selected analog- and binary signals connected to the
changed status during a disturbance. This information is used
Disturbance report function (maximum 40 analog and 96
in the short perspective to get information via the local HMI in
binary signals). The binary signals available are the same as
a straightforward way.
for the event recorder function.
There are three LEDs on the local HMI (green, yellow and
The function is characterized by great flexibility and is not
red), which will display status information about the IED and
dependent on the operation of protection functions. It can
the Disturbance report function (triggered).
record disturbances not detected by protection functions. Up
The Indication list function shows all selected binary input to ten seconds of data before the trigger instant can be saved
signals connected to the Disturbance report function that in the disturbance file.
have changed status during a disturbance.
The disturbance recorder information for up to 100
Event recorder DRPRDRE disturbances are saved in the IED and the local HMI is used
Quick, complete and reliable information about disturbances to view the list of recordings.
in the primary and/or in the secondary system is vital, for
Event function
example, time-tagged events logged during disturbances.
When using a Substation Automation system with LON or
This information is used for different purposes in the short
SPA communication, time-tagged events can be sent at
term (for example corrective actions) and in the long term (for
change or cyclically from the IED to the station level. These
example functional analysis).
events are created from any available signal in the IED that is
The event recorder logs all selected binary input signals connected to the Event function (EVENT). The event function
connected to the Disturbance report function. Each recording block is used for LON and SPA communication.
can contain up to 150 time-tagged events.
Analog and double indication values are also transferred
The event recorder information is available for the through EVENT function.
disturbances locally in the IED.
IEC61850 generic communication I/O functions MVGGIO
The event recording information is an integrated part of the IEC61850 generic communication I/O functions (MVGGIO)
disturbance record (Comtrade file). function is used to send the instantaneous value of an analog
signal to other systems or equipment in the substation. It can
also be used inside the same IED, to attach a RANGE aspect
to an analog value and to permit measurement supervision on
that value.

18 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Measured value expander block RANGE_XP


The current and voltage measurements functions (CVMMXN,
CMMXU, VMMXU and VNMMXU), current and voltage
sequence measurement functions (CMSQI and VMSQI) and
IEC 61850 generic communication I/O functions (MVGGIO)
are provided with measurement supervision functionality. All
measured values can be supervised with four settable limits:
low-low limit, low limit, high limit and high-high limit. The
measure value expander block (RANGE_XP) has been
introduced to enable translating the integer output signal from
the measuring functions to 5 binary signals: below low-low
limit, below low limit, normal, above high-high limit or above
high limit. The output signals can be used as conditions in the
configurable logic or for alarming purpose.

9. Basic IED functions

Time synchronization
The time synchronization source selector is used to select a
common source of absolute time for the IED when it is a part
of a protection system. This makes it possible to compare
event and disturbance data between all IEDs in a station
automation system. IEC06000143 V1 EN

Figure 11. Example of medium graphic HMI

10. Human machine interface

Human machine interface


The local HMI is equipped with a LCD that is used among
other things to locally display the following crucial information:

• Connection of each bay, respecting the two differential


protection zones and the check zone. In the Parameter
Setting Tool the user sets individual bay names to
facilitate the identification of each primary bay for station
personnel.
• Status of each individual primary switchgear device, for
example, open, closed, 00 as intermediate state and 11
as bad state. In PCM600 the user sets the individual
primary switchgear object names to facilitate the
identification of each switchgear device for the station
personnel.

The local HMI is divided into zones with different functionality.

• Status indication LEDs.


• Alarm indication LEDs, which consist of 15 LEDs (6 red
and 9 yellow) with user printable label. All LEDs are
configurable from PCM600.
• Liquid crystal display (LCD).
• Keypad with push buttons for control and navigation
purposes, switch for selection between local and remote
control and reset.
• Isolated RJ45 communication port.

ABB 19
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

IEC06000191 V1 EN IEC06000192 V1 EN

Figure 12. Bay to zone connection example Figure 13. Example of status of primary switchgear objects

1 User settable bay name 1 User settable switchgear names


2 Internally used bay FB 2 Switchgear object status
3 Connections to internal zones

11. Station communication

Overview
Each IED is provided with a communication interface,
enabling it to connect to one or many substation level
systems or equipment, either on the Substation Automation
(SA) bus or Substation Monitoring (SM) bus.

Following communication protocols are available:

• IEC 61850-8-1 communication protocol


• LON communication protocol
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol

Theoretically, several protocols can be combined in the same


IED.

IEC 61850-8-1 communication protocol


The IED is equipped with single or double optical Ethernet
rear ports (order dependent) for IEC 61850-8-1 station bus
communication. The IEC 61850-8-1 communication is also
possible from the optical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from
different vendors to exchange information and simplifies
system engineering. Peer-to-peer communication according
20 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

to GOOSE is part of the standard. Disturbance files uploading 12. Remote communication
is provided.
Analog and binary signal transfer to remote end
Serial communication, LON Three analog and eight binary signals can be exchanged
Existing stations with ABB station bus LON can be extended between two IEDs. This functionality is mainly used for the
with use of the optical LON interface. This allows full SA line differential protection. However it can be used in other
functionality including peer-to-peer messaging and products as well. An IED can communicate with up to 4
cooperation between existing ABB IED's and the new IED remote IEDs.
670.
Binary signal transfer to remote end, 192 signals
SPA communication protocol If the communication channel is used for transfer of binary
A single glass or plastic port is provided for the ABB SPA signals only, up to 192 binary signals can be exchanged
protocol. This allows extensions of simple substation between two IEDs. For example, this functionality can be
automation systems but the main use is for Substation used to send information such as status of primary
Monitoring Systems SMS. switchgear apparatus or intertripping signals to the remote
IED. An IED can communicate with up to 4 remote IEDs.
IEC 60870-5-103 communication protocol
A single glass or plastic port is provided for the Line data communication module, short range LDCM
IEC60870-5-103 standard. This allows design of simple The line data communication module (LDCM) is used for
substation automation systems including equipment from communication between the IEDs situated at distances <110
different vendors. Disturbance files uploading is provided. km or from the IED to optical to electrical converter with G.
703 or G.703E1 interface located on a distances <3 km
DNP3.0 communication protocol away. The LDCM module sends and receives data, to and
An electrical RS485 and an optical Ethernet port is available from another LDCM module. The IEEE/ANSI C37.94 standard
for the DNP3.0 communication. DNP3.0 Level 2 format is used.
communication with unsolicited events, time synchronizing
and disturbance reporting is provided for communication to
RTUs, Gateways or HMI systems. 13. Hardware description

Multiple command and transmit Hardware modules


When 670 IED's are used in Substation Automation systems Power supply module PSM
with LON, SPA or IEC60870-5-103 communication protocols The power supply module is used to provide the correct
the Event and Multiple Command function blocks are used as internal voltages and full isolation between the terminal and
the communication interface for vertical communication to the battery system. An internal fail alarm output is available.
station HMI and gateway and as interface for horizontal peer-
Binary input module BIM
to-peer communication (over LON only).
The binary input module has 16 optically isolated inputs and
IEC 62439-3 Parallel Redundant Protocol is available in two versions, one standard and one with
Redundant station bus communication according to IEC enhanced pulse counting capabilities on the inputs to be
62439-3 Edition 1 and IEC 62439-3 Edition 2 are available as used with the pulse counter function. The binary inputs are
options in 670 series IEDs. IEC 62439-3 parallel redundant freely programmable and can be used for the input of logical
protocol is an optional quantity and the selection is made at signals to any of the functions. They can also be included in
ordering. Redundant station bus communication according to the disturbance recording and event-recording functions. This
IEC 62439-3 uses both port AB and port CD on the OEM enables extensive monitoring and evaluation of operation of
module. the IED and for all associated electrical circuits.

Binary output module BOM


Select IEC 62439-3 Edition 1 protocol at The binary output module has 24 independent output relays
the time of ordering when an existing and is used for trip output or any signaling purpose.
redundant station bus DuoDriver installation
is extended. Static binary output module SOM
Select IEC 62439-3 Edition 2 protocol at The static binary output module has six fast static outputs
the time of ordering for new installations and six change over output relays for use in applications with
with redundant station bus. high speed requirements.
IEC 62439-3 Edition 1 is NOT compatible
with IEC 62439-3 Edition 2. Binary input/output module IOM
The binary input/output module is used when only a few input
and output channels are needed. The ten standard output
channels are used for trip output or any signaling purpose.

ABB 21
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

The two high speed signal output channels are used for communication port. The RS485 is a balanced serial
applications where short operating time is essential. Eight communication that can be used either in 2-wire or 4-wire
optically isolated binary inputs cater for required binary input connections. A 2-wire connection uses the same signal for RX
information. and TX and is a multidrop communication with no dedicated
Master or slave. This variant requires however a control of the
Optical ethernet module OEM output. The 4-wire connection has separated signals for RX
The optical fast-ethernet module is used to connect an IED to and TX multidrop communication with a dedicated Master
the communication buses (like the station bus) that use the and the rest are slaves. No special control signal is needed in
IEC 61850-8-1 protocol (port A, B). The module has one or this case.
two optical ports with ST connectors.
GPS time synchronization module GTM
Serial and LON communication module SLM, supports SPA/ This module includes a GPS receiver used for time
IEC 60870-5-103, LON and DNP 3.0 synchronization. The GPS has one SMA contact for
The serial and LON communication module (SLM) is used for connection to an antenna. It also includes an optical PPS ST-
SPA, IEC 60870-5-103, DNP3 and LON communication. The connector output.
module has two optical communication ports for plastic/
plastic, plastic/glass or glass/glass. One port is used for serial IRIG-B Time synchronizing module
communication (SPA, IEC 60870-5-103 and DNP3 port or The IRIG-B time synchronizing module is used for accurate
dedicated IEC 60870-5-103 port depending on ordered SLM time synchronizing of the IED from a station clock.
module) and one port is dedicated for LON communication.
Transformer input module TRM
Line data communication module LDCM The transformer input module is used to galvanically separate
Each module has one optical port, one for each remote end and transform the secondary currents and voltages generated
to which the IED communicates. by the measuring transformers. The module has twelve inputs
in different combinations of currents and voltage inputs.
Alternative cards for Short range (850 nm multi mode) are
available. Alternative connectors of Ring lug or Compression type can
be ordered.
Galvanic RS485 serial communication module
The Galvanic RS485 communication module (RS485) is used Layout and dimensions
for DNP3.0 communication. The module has one RS485 Dimensions

B C
D

xx05000003.vsd

IEC05000003 V1 EN

Figure 14. 1/2 x 19” case with rear cover

22 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

xx05000004.vsd
IEC05000004 V1 EN

Figure 15. Side-by-side mounting

Case size A B C D E F

6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7

6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0

6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3

(mm)

Mounting alternatives See ordering for details about available mounting alternatives.
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
– 1/2 case size (h) 254.3 mm (w) 210.1 mm
– 1/1 case size (h) 254.3 mm (w) 434.7 mm
• Wall mounting kit

ABB 23
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

14. Connection diagrams

Table 2. Designations for 1/2 x 19” casing with 1 TRM slot

Module Rear Positions


PSM X11
BIM, BOM, SOM, IOM or X31 and X32 etc. to X51
MIM and X52
SLM X301:A, B, C, D
LDCM, IRIG-B or RS485 X302
LDCM or RS485 X303
OEM X311:A, B, C, D
LDCM, RS485 or GTM X312, 313
TRM X401

1MRK002801-AC-2-670-1.2-PG V1 EN

Table 3. Designations for 3/4 x 19” casing with 1 TRM slot

Module Rear Positions


PSM X11
BIM, BOM, SOM, IOM or X31 and X32 etc. to
MIM X101 and X102
SLM X301:A, B, C, D
LDCM, IRIG-B or RS485 X302
LDCM or RS485 X303
OEM X311:A, B, C, D
LDCM, RS485 or GTM X312, X313
TRM X401

1MRK002801-AC-3-670-1.2-PG V1 EN

24 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 4. Designations for 1/1 x 19” casing with 2 TRM slots

Module Rear Positions


PSM X11
BIM, BOM, SOM, X31 and X32 etc. to X131
IOM or MIM and X132
SLM X301:A, B, C, D
LDCM, IRIG-B or X302
RS485
LDCM or RS485 X303
OEM X311:A, B, C, D
LDCM, RS485 or X312, X313, X322, X323
GTM
TRM 1 X401
TRM 2 X411

1MRK002801-AC-6-670-1.2-PG V1 EN

ABB 25
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

1MRK002801-AC-10-670-1.2-PG V1 EN

Figure 16. Transformer input module (TRM)

■ Indicates high polarity

CT/VT-input designation according to figure 16


AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
Current/voltage
configuration
(50/60 Hz)

12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.

26 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

1MRK002801-AC-15-670-1.2-PG V1 EN

Figure 18. mA input module (MIM)

1MRK002801-AC-11-670-1.2-PG V1 EN

Figure 17. Binary input module (BIM). Input contacts


named XA corresponds to rear position
X31, X41, and so on, and input contacts
named XB to rear position X32, X42, and
so on.

1MRK002801-AC-8-670-1.2-PG V1 EN

Figure 19. IED with basic functionality and communication interfaces

ABB 27
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

1MRK002801-AC-7-670-1.2-PG V1 EN

Figure 20. Power supply module (PSM)

1MRK002801-AC-12-670-1.2-PG V1 EN

Figure 21. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output
contacts named XB to rear position X32, X42, and so on.

28 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

1MRK002801-AC-13-670-1.2-PG V1 EN

Figure 22. Static output module (SOM)

1MRK002801-AC-14-670-1.2-PG V1 EN

Figure 23. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts
named XB to rear position X32, X42, and so on.

ABB 29
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

15. Technical data

General

Definitions

Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment

Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements

Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements

Energizing quantities, rated values and limits


Analog inputs

Table 5. TRM - Energizing quantities, rated values and limits for protection transformer modules

Quantity Rated value Nominal range

Current Ir = 1 or 5 A (0.2-40) × Ir

Operative range (0-100) x Ir

Permissive overload 4 × Ir cont.


100 × Ir for 1 s *)

Burden < 150 mVA at Ir = 5 A


< 20 mVA at Ir = 1 A

Frequency fr = 50/60 Hz ± 5%

*) max. 350 A for 1 s when COMBITEST test switch is included.

Table 6. OEM - Optical ethernet module

Quantity Rated value

Number of channels 1 or 2

Standard IEEE 802.3u 100BASE-FX

Type of fiber 62.5/125 mm multimode fibre

Wave length 1300 nm

Optical connector Type ST

Communication speed Fast Ethernet 100 MB

Auxiliary DC voltage

Table 7. PSM - Power supply module

Quantity Rated value Nominal range

Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20%


EL = (90 - 250) V EL ± 20%

Power consumption 50 W typically -

Auxiliary DC power in-rush < 5 A during 0.1 s -

30 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Binary inputs and outputs

Table 8. BIM - Binary input module

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V RL ± 20%


48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%

Power consumption
24/30 V, 50mA max. 0.05 W/input -
48/60 V, 50mA max. 0.1 W/input
110/125 V, 50mA max. 0.2 W/input
220/250 V, 50mA max. 0.4 W/input
220/250 V, 110mA max. 0.5 W/input

Counter input frequency 10 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 Hz


Release settable 1–30 Hz

Debounce filter Settable 1–20ms

Maximum 176 binary input channels may


be activated simultaneously with influencing
factors within nominal range.

Table 9. BIM - Binary input module with enhanced pulse counting capabilities

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V RL ± 20%


48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%

Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input

Counter input frequency 10 pulses/s max -

Balanced counter input frequency 40 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 Hz


Release settable 1–30 Hz

Maximum 176 binary input channels may


be activated simultaneously with influencing
factors within nominal range.

ABB 31
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 10. IOM - Binary input/output module

Quantity Rated value Nominal range

Binary inputs 8 -

DC voltage, RL 24/30 V RL ± 20%


48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%

Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input

Counter input frequency 10 pulses/s max

Oscillating signal discriminator Blocking settable 1-40 Hz


Release settable 1-30 Hz

Debounce filter Settable 1-20 ms

Maximum 176 binary input channels may


be activated simultaneously with influencing
factors within nominal range.

Table 11. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)

Binary outputs 10 2

Max system voltage 250 V AC, DC 250 V DC

Test voltage across open contact, 1 min 1000 V rms 800 V DC

Current carrying capacity


Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A

Making capacity at inductive load with L/R>10 ms

0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A

Making capacity at resistive load


220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A

Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A 48 V/1 A


110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

32 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 12. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)

Binary outputs IOM: 10 IOM: 2

Max system voltage 250 V AC, DC 250 V DC

Test voltage across open 250 V rms 250 V rms


contact, 1 min

Current carrying capacity


Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, 12 A 12 A
continuous

Making capacity at inductive


loadwith L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A

Making capacity at resistive load


220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A

Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A


j>0.4

Breaking capacity for DC with L/ 48 V/1 A 48 V/1 A


R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

Table 13. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs

Function of quantity Static binary output trip

Rated voltage 48 - 60 VDC 110 - 250 VDC

Number of outputs 6 6

Impedance open state ~300 kΩ ~810 kΩ

Test voltage across open contact, 1 min No galvanic separation No galvanic separation

Current carrying capacity:

Continuous 5A 5A

1.0s 10A 10A

Making capacity at capacitive load with the


maximum capacitance of 0.2 μF :

0.2s 30A 30A

1.0s 10A 10A

Breaking capacity for DC with L/R ≤ 40ms 48V / 1A 110V / 0.4A

60V / 0.75A 125V / 0.35A

220V / 0.2A

250V / 0.15A

Operating time <1ms <1ms

ABB 33
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 14. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs

Function of quantity Trip and signal relays

Max system voltage 250V AC/DC

Number of outputs 6

Test voltage across open contact, 1 min 1000V rms

Current carrying capacity:

Continuous 8A

1.0s 10A

Making capacity at capacitive load with the maximum capacitance of


0.2 μF:

0.2s 30A

1.0s 10A

Breaking capacity for DC with L/R ≤ 40ms 48V / 1A

110V / 0.4A

125V / 0.35A

220V / 0.2A

250V / 0.15A

Table 15. BOM - Binary output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays

Binary outputs 24

Max system voltage 250 V AC, DC

Test voltage across open contact, 1 min 1000 V rms

Current carrying capacity


Per relay, continuous 8A
Per relay, 1 s 10 A
Per process connector pin, continuous 12 A

Making capacity at inductive load with L/R>10 ms


0.2 s 30 A
1.0 s 10 A

Breaking capacity for AC, cos j>0.4 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A


110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

Influencing factors

Table 16. Temperature and humidity influence

Parameter Reference value Nominal range Influence

Ambient temperature, operate +20 °C -10 °C to +55 °C 0.02% /°C


value

Relative humidity 10%-90% 10%-90% -


Operative range 0%-95%

Storage temperature -40 °C to +70 °C - -

34 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 17. Auxiliary DC supply voltage influence on functionality during operation

Dependence on Reference value Within nominal Influence


range

Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% /%


Operative range Full wave rectified

Auxiliary voltage dependence, operate ± 20% of EL 0.01% /%


value

Interrupted auxiliary DC voltage 24-60 V DC ± 20%

90-250 V DC ± 20%
Interruption interval
0–50 ms
No restart

0–∞ s Correct behaviour at power down

Restart time <300 s

Table 18. Frequency influence (reference standard: IEC 60255–1)

Dependence on Within nominal range Influence

Frequency dependence, operate value fr ± 2.5 Hz for 50 Hz ± 1.0% / Hz


fr ± 3.0 Hz for 60 Hz

Frequency dependence for differential protection fr ± 2.5 Hz for 50 Hz ± 2.0% / Hz


fr ± 3.0 Hz for 50 Hz

Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ± 1.0%

Harmonic frequency dependence for differential protection (10% 2nd, 3rd and 5th harmonic of fr ± 6.0%
content)

ABB 35
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Type tests according to standards

Table 19. Electromagnetic compatibility

Test Type test values Reference standards

1 MHz burst disturbance 2.5 kV IEC 60255-22-1

100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III

Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV

Surge withstand capability test 2.5 kV, oscillatory IEEE/ANSI C37.90.1


4.0 kV, fast transient

Electrostatic discharge 15 kV air discharge IEC 60255-22-2, Class IV


Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Class IV

Electrostatic discharge 15 kV air discharge IEEE/ANSI C37.90.1


Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge

Fast transient disturbance 4 kV IEC 60255-22-4, Class A

Surge immunity test 1-2 kV, 1.2/50 ms IEC 60255-22-5


high energy

Power frequency immunity test 150-300 V, 50 Hz IEC 60255-22-7, Class A

Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV

Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.

Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V

Radiated electromagnetic field disturbance 20 V/m, 80-1000 MHz IEC 60255-22-3

1.4-2.7 GHz

Radiated electromagnetic field disturbance 35 V/m IEEE/ANSI C37.90.2


26-1000 MHz

Conducted electromagnetic field disturbance 10 V, 0.15-80 MHz IEC 60255-22-6

Radiated emission 30-1000 MHz IEC 60255-25

Conducted emission 0.15-30 MHz IEC 60255-25

Table 20. Insulation

Test Type test values Reference standard

Dielectric test 2.0 kV AC, 1 min. IEC 60255-5

Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J

Insulation resistance >100 MW at 500 VDC

36 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 21. Environmental tests

Test Type test value Reference standard

Cold test Test Ad for 16 h at -25°C IEC 60068-2-1

Storage test Test Ad for 16 h at -40°C IEC 60068-2-1

Dry heat test Test Bd for 16 h at +70°C IEC 60068-2-2

Damp heat test, steady state Test Ca for 4 days at +40 °C and humidity 93% IEC 60068-2-78

Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 °C and humidity 93 to 95% (1 cycle = IEC 60068-2-30
24 hours)

Table 22. CE compliance

Test According to

Immunity EN 50263

Emissivity EN 50263

Low voltage directive EN 50178

Table 23. Mechanical tests

Test Type test values Reference standards

Vibration response test Class II IEC 60255-21-1

Vibration endurance test Class I IEC 60255-21-1

Shock response test Class II IEC 60255-21-2

Shock withstand test Class I IEC 60255-21-2

Bump test Class I IEC 60255-21-2

Seismic test Class II IEC 60255-21-3

ABB 37
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Differential protection

Table 24. Busbar differential protection

Function Range or value Accuracy

Operating characteristic S=0.53 fixed ± 2.0% of Ir for I < Ir


± 2.0% of I for I > Ir

Reset ratio > 95% -

Differential current operating level (1-100000) A ± 2.0% of Ir for I < Ir


± 2.0% of I for I > Ir

Sensitive differential operation (1-100000) A ± 2.0% of Ir for I < Ir


level ± 2.0% of I for I < Ir

Check zone operation level (0-100000) A ± 2.0% of Ir for I < Ir


± 2.0% of I for I > Ir

Check zone slope (0.0-0.9) -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Timers (0.00-6000.00) s ± 0.5% ± 10 ms

Operate time 19 ms typically at 0 to 2 x Id -


12 ms typically at 0 to 10 x Id

Reset time 21 ms typically at 2 to 0 x Id -


29 ms typically at 10 to 0 x Id

Critical impulse time 8 ms typically at 0 to 2 x Id -

38 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Current protection

Table 25. Four step phase overcurrent protection OC4PTOC

Function Setting range Accuracy

Operate current (5-2500)% of lBase ± 1.0% of Ir at I ≤ Ir


± 1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -

Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Relay characteristic angle (RCA) (40.0–65.0) degrees ± 2.0 degrees

Relay operating angle (ROA) (40.0–89.0) degrees ± 2.0 degrees

2nd harmonic blocking (5–100)% of fundamental ± 2.0% of Ir

Independent time delay at 0 to 2 x (0.000-60.000) s ± 0.2 % or ± 35 ms whichever is


Iset greater

Minimum operate time (0.000-60.000) s ± 2.0 % or ± 40 ms whichever is


greater

Inverse characteristics, see 16 curve types See table 63, table 64 and table 65
table 63, table 64 and table 65

Operate time, start non-directional Min. = 15 ms


at 0 to 2 x Iset
Max. = 30 ms

Reset time, start non-directional at Min. = 15 ms


2 to 0 x Iset
Max. = 30 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Table 26. Four step single phase overcurrent protection PH4SPTOC

Function Setting range Accuracy

Operate current (1-2500)% of lbase ± 1.0% of Ir at I £ Ir


± 1.0% of I at I > Ir

Reset ratio > 95% -

Second harmonic blocking (5–100)% of fundamental ± 2.0% of Ir

Independent time delay (0.000-60.000) s ± 0.5% ± 10 ms

Minimum operate time (0.000-60.000) s ± 0.5% ± 10 ms

Inverse characteristics, see 19 curve types See table 63 and table 64


table 63 and table 64

Operate time, start function 25 ms typically at 0 to 2 x Iset -

Reset time, start function 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

ABB 39
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 27. Breaker failure protection CCRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir


± 1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Operate residual current (2-200)% of lBase ± 1.0% of Ir at I £ Ir


± 1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Phase current level for blocking of contact function (5-200)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ±10 ms

Operate time for current detection 10 ms typically -

Reset time for current detection 15 ms maximum -

Table 28. Breaker failure protection, single phase version CCSRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir


± 1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Phase current level for blocking of contact function (5-200)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Operate time for current detection 10 ms typically -

Reset time for current detection 15 ms maximum -

40 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Control

Table 29. Autorecloser SMBRREC

Function Range or value Accuracy

Number of autoreclosing shots 1-5 -

Autoreclosing open time:


shot 1 - t1 1Ph (0.000-60.000) s ± 0.5% ± 10 ms
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld

shot 2 - t2 (0.00-6000.00) s
shot 3 - t3
shot 4 - t4
shot 5 - t5

Extended autorecloser open time (0.000-60.000) s

Autorecloser maximum wait time for sync (0.00-6000.00) s

Maximum trip pulse duration (0.000-60.000) s

Inhibit reset time (0.000-60.000) s

Reclaim time (0.00-6000.00) s

Minimum time CB must be closed before AR becomes ready for autoreclosing cycle (0.00-6000.00) s

Circuit breaker closing pulse length (0.000-60.000) s

CB check time before unsuccessful (0.00-6000.00) s

Wait for master release (0.00-6000.00) s

Wait time after close command before proceeding to next shot (0.000-60.000) s

ABB 41
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Logic

Table 30. Configurable logic blocks

Logic block Quantity with update rate Range or value Accuracy

fast medium normal

LogicAND 90 90 100 - -

LogicOR 90 90 100 - -

LogicXOR 15 15 10 - -

LogicInverter 45 45 50 - -

LogicSRMemory 15 15 10 - -

LogicRSMemory 15 15 10 - -

LogicGate 15 15 10 - -

LogicTimer 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms

LogicPulseTimer 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms

LogicTimerSet 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms

LogicLoopDelay 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms

Boolean 16 to Integer 4 4 8 - -

Boolean 16 to integer 4 4 8 - -
with Logic Node

Integer to Boolean 16 4 4 8 - -

Integer to Boolean 16 4 4 8 - -
with Logic Node

42 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Monitoring

Table 31. Measurements CVMMXN

Function Range or value Accuracy

Frequency (0.95-1.05) × fr ± 2.0 mHz

Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir


± 0.5% of I at I > Ir

Table 32. Phase current measurement CMMXU

Function Range or value Accuracy

Current (0.1-4.0) × Ir ± 0.2% of Ir at I ≤ 0.5 × Ir


± 0.2% of I at I > 0.5 × Ir

Phase angle (0.1–4.0) x Ir ± 0.5° at 0.2 × Ir < I < 0.5 × Ir


± 0.2° at 0.5 × Ir ≤ I < 4.0 × Ir

Table 33. Phase-phase voltage measurement VMMXU

Function Range or value Accuracy

Voltage (10 to 300) V ± 0.3% of U at U ≤ 50 V


± 0.2% of U at U > 50 V

Phase angle (10 to 300) V ± 0.3° at U ≤ 50 V


± 0.2° at U > 50 V

Table 34. Phase-neutral voltage measurement VNMMXU

Function Range or value Accuracy

Voltage (10 to 300) V ± 0.3% of U at U ≤ 50 V


± 0.2% of U at U > 50 V

Phase angle (10 to 300) V ± 0.3° at U ≤ 50 V


± 0.2° at U > 50 V

Table 35. Current sequence component measurement CMSQI

Function Range or value Accuracy

Current positive sequence, I1 (0.1–4.0) × Ir ± 0.2% of Ir at I ≤ 0.5 × Ir


Three phase settings ± 0.2% of I at I > 0.5 × Ir

Current zero sequence, 3I0 (0.1–1.0) × Ir ± 0.2% of Ir at I ≤ 0.5 × Ir


Three phase settings ± 0.2% of I at I > 0.5 × Ir

Current negative sequence, I2 (0.1–1.0) × Ir ± 0.2% of Ir at I ≤ 0.5 × Ir


Three phase settings ± 0.2% of I at I > 0.5 × Ir

Phase angle (0.1–4.0) × Ir ± 0.5° at 0.2 × Ir < I < 0.5 × Ir


± 0.2° at 0.5 × Ir ≤ I < 4.0 × Ir

ABB 43
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 36. Voltage sequence measurement VMSQI

Function Range or value Accuracy

Voltage positive sequence, U1 (10 to 300) V ± 0.3% of U at U ≤ 50 V


± 0.2% of U at U > 50 V

Voltage zero sequence, 3U0 (10 to 300) V ± 0.3% of U at U ≤ 50 V


± 0.2% of U at U > 50 V

Voltage negative sequence, U2 (10 to 300) V ± 0.3% of U at U ≤ 50 V


± 0.2% of U at U > 50 V

Phase angle (10 to 300) V ± 0.3° at U ≤ 50 V


± 0.2° at U > 50 V

Table 37. Event counter CNTGGIO

Function Range or value Accuracy

Counter value 0-100000 -

Max. count up speed 10 pulses/s (50% duty cycle) -

Table 38. Disturbance report DRPRDRE

Function Range or value Accuracy

Pre-fault time (0.05–9.90) s -

Post-fault time (0.1–10.0) s -

Limit time (0.5–10.0) s -

Maximum number of recordings 100, first in - first out -

Time tagging resolution 1 ms See table 59

Maximum number of analog inputs 30 + 10 (external + internally -


derived)

Maximum number of binary inputs 96 -

Maximum number of phasors in the Trip Value recorder per recording 30 -

Maximum number of indications in a disturbance report 96 -

Maximum number of events in the Event recording per recording 150 -

Maximum number of events in the Event list 1000, first in - first out -

Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz

Sampling rate 1 kHz at 50 Hz -


1.2 kHz at 60 Hz

Recording bandwidth (5-300) Hz -

Table 39. Event list

Function Value

Buffer capacity Maximum number of events in the list 1000

Resolution 1 ms

Accuracy Depending on time synchronizing

44 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 40. Indications

Function Value

Buffer capacity Maximum number of indications presented for single disturbance 96

Maximum number of recorded disturbances 100

Table 41. Event recorder

Function Value

Buffer capacity Maximum number of events in disturbance report 150

Maximum number of disturbance reports 100

Resolution 1 ms

Accuracy Depending on time


synchronizing

Table 42. Trip value recorder

Function Value

Buffer capacity Maximum number of analog inputs 30

Maximum number of disturbance reports 100

Table 43. Disturbance recorder

Function Value

Buffer capacity Maximum number of analog inputs 40

Maximum number of binary inputs 96

Maximum number of disturbance reports 100

Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz

ABB 45
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Station communication

Table 44. IEC 61850-8-1 communication protocol

Function Value

Protocol IEC 61850-8-1

Communication speed for the IEDs 100BASE-FX

Protocol IEC 608–5–103

Communication speed for the IEDs 9600 or 19200 Bd

Protocol DNP3.0

Communication speed for the IEDs 300–19200 Bd

Protocol TCP/IP, Ethernet

Communication speed for the IEDs 100 Mbit/s

Table 45. LON communication protocol

Function Value

Protocol LON

Communication speed 1.25 Mbit/s

Table 46. SPA communication protocol

Function Value

Protocol SPA

Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd

Slave number 1 to 899

Table 47. IEC60870-5-103 communication protocol

Function Value

Protocol IEC 60870-5-103

Communication speed 9600, 19200 Bd

Table 48. SLM – LON port

Quantity Range or value

Optical connector Glass fibre: type ST


Plastic fibre: type HFBR snap-in

Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)


Plastic fibre: 7 dB (10 m typically *)

Fibre diameter Glass fibre: 62.5/125 mm


Plastic fibre: 1 mm

*) depending on optical budget calculation

46 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 49. SLM – SPA/IEC 60870-5-103/DNP3 port

Quantity Range or value

Optical connector Glass fibre: type ST


Plastic fibre: type HFBR snap-in

Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *)


Plastic fibre: 7 dB (80ft/25 m typically *)

Fibre diameter Glass fibre: 62.5/125 mm


Plastic fibre: 1 mm

*) depending on optical budget calculation

Table 50. Galvanic RS485 communication module

Quantity Range or value

Communication speed 2400–19200 bauds

External connectors RS-485 6-pole connector


Soft ground 2-pole connector

Table 51. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol

Function Value

Protocol IEC 61850-8-1

Communication speed 100 Base-FX

ABB 47
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Remote communication

Table 52. Line data communication module

Characteristic Range or value

Type of LDCM Short range (SR) Medium range (MR) Long range (LR)

Type of fibre Graded-index Singlemode 9/125 µm Singlemode 9/125 µm


multimode
62.5/125 µm or
50/125 µm

Wave length 850 nm 1310 nm 1550 nm

Optical budget 13 dB (typical 22 dB (typical 26 dB (typical distance 110 km *)


Graded-index multimode 62.5/125 mm, distance about 3 distance 80 km *)
km *)
9 dB (typical
Graded-index multimode 50/125 mm distance about 2
km *)

Optical connector Type ST Type FC/PC Type FC/PC

Protocol C37.94 C37.94 C37.94 implementation **)


implementation **)

Data transmission Synchronous Synchronous Synchronous

Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s

Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal

*) depending on optical budget calculation


**) C37.94 originally defined just for multimode; using same header, configuration and data format as C37.94

48 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Hardware
IED

Table 53. Case

Material Steel sheet

Front plate Steel sheet profile with cut-out for HMI

Surface treatment Aluzink preplated steel

Finish Light grey (RAL 7035)

Table 54. Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)

Sides, top and bottom IP20

Rear side IP20 with screw compression type


IP10 with ring lug terminals

Table 55. Weight

Case size Weight

6U, 1/2 x 19” £ 10 kg

6U, 3/4 x 19” £ 15 kg

6U, 1/1 x 19” £ 18 kg

Connection system

Table 56. CT circuit connectors

Connector type Rated voltage and current Maximum conductor area

Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)


2 x 2.5 mm2 (2 x AWG14)

Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)

Table 57. Binary I/O connection system

Connector type Rated voltage Maximum conductor area

Screw compression type 250 V AC 2.5 mm2 (AWG14)


2 × 1 mm2 (2 x AWG18)

Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)

ABB 49
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Basic IED functions

Table 58. Self supervision with internal event list

Data Value

Recording manner Continuous, event controlled

List size 40 events, first in-first out

Table 59. Time synchronization, time tagging

Function Value

Time tagging resolution, events and sampled measurement values 1 ms

Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values

Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically

Table 60. GPS time synchronization module (GTM)

Function Range or value Accuracy

Receiver – ±1µs relative UTC

Time to reliable time reference with antenna in new <30 minutes –


position or after power loss longer than 1 month

Time to reliable time reference after a power loss <15 minutes –


longer than 48 hours

Time to reliable time reference after a power loss <5 minutes –


shorter than 48 hours

Table 61. GPS – Antenna and cable

Function Value

Max antenna cable attenuation 26 db @ 1.6 GHz

Antenna cable impedance 50 ohm

Lightning protection Must be provided externally

Antenna cable connector SMA in receiver end


TNC in antenna end

Accuracy +/-2μs

50 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 62. IRIG-B

Quantity Rated value

Number of channels IRIG-B 1

Number of channels PPS 1

Electrical connector:

Electrical connector IRIG-B BNC

Pulse-width modulated 5 Vpp

Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp

Supported formats IRIG-B 00x, IRIG-B 12x

Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x

Input impedance 100 k ohm

Optical connector:

Optical connector PPS and IRIG-B Type ST

Type of fibre 62.5/125 μm multimode fibre

Supported formats IRIG-B 00x, PPS

Accuracy +/- 2μs

ABB 51
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Inverse characteristic

Table 63. ANSI Inverse time characteristics

Function Range or value Accuracy

Operating characteristic: k = (0.05-999) in steps of 0.01 -

æ A ö
t = ç P + B÷ × k
ç ( I - 1) ÷
è ø
EQUATION1249-SMALL V1 EN

Reset characteristic:

tr
t = ×k
(I 2
)
-1

EQUATION1250-SMALL V1 EN

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1 ANSI/IEEE C37.112, 5%


+ 40 ms
ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85

ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

52 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Table 64. IEC Inverse time characteristics

Function Range or value Accuracy

Operating characteristic: k = (0.05-999) in steps of 0.01 -

æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms

IEC Normal Inverse A=0.14, P=0.02 IEC 60255-151, 5% + 40


ms
IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Programmable characteristic k = (0.05-999) in steps of 0.01


Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷
è ø TR=(0.005-100.000) in steps of 0.001
EQUATION1370-SMALL V1 EN
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
Reset characteristic:

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN

I = Imeasured/Iset

Table 65. RI and RD type inverse time characteristics

Function Range or value Accuracy

RI type inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-151, 5% + 40


ms
1
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN

I = Imeasured/Iset

RD type logarithmic inverse characteristic k = (0.05-999) in steps of 0.01

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

ABB 53
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

16. Ordering

Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REB670*1.2-A20X01-C06-X0-A-A-B-A-A2-X0-CAX-XXX-XD. Using the code of each position #1-12 specified as REB670*1-2 2-3 3 3-4-5-6-7 7-8-9 9
9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REB670* - - - - - . - -

10 - 11 - 12
. -

Position
SOFTWARE #1 Notes and Rules
Version number
Version no 1.2
Selection for position #1.

Configuration alternatives #2 Notes and Rules


3 phase, 4 bays A20
3 phase, 8 bays A31
1 phase, 12 bays, 1/2 19" case B20
1 phase, 12 bays, 1/1 19" case B21
1 phase, 24 bays B31
ACT configuration
Simple station layout, 1 1/2 CB, 2 CB, 1 CB, b-contacts, BBP only X01
Double busbar - 1 CB, a and b contacts, BBP only X02 Note: Only for A31, B21 and B31
Double busbar - 1 CB, a and b contacts, BBP, EnFP X03 Note: Only for A31, B21 and B31
Note: One each of Breaker failure
protection and Overcurrent
protection must be ordered
Selection for position #2.

Software options #3 Notes and Rules


No option X00 All fields in the ordering form do
not need to be filled in
Four step phase overcurrent protection, 4 bays C06 Note: Only for A20
Four step phase overcurrent protection, 8 bays C07 Note: Only for A31
Four step single phase overcurrent protection, 12 bays C08 Note: Only for B20 and B21
Four step single phase overcurrent protection, 24 bays C09 Note: Only for B31
Breaker failure protection, 4 bays C10 Note: Only for A20
Breaker failure protection, 8 bays C11 Note: Only for A31
Breaker failure protection, 12 bays, single phase C12 Note: Only for B20 and B21
Breaker failure protection, 24 bays, single phase C13 Note: Only for B31
Autorecloser, 2 circuit breakers H05
IEC 62439-3 Edition 1, parallel redundancy protocol P01 Note:Require 2-channel OEM
IEC 62439-3 Edition 2, parallel redundancy protocol P02
Selection for position #3

54 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

First local HMI user dialogue language #4 Notes and Rules


HMI language, English IEC B1
HMI language, English US B2
Additional local HMI user dialogue language
HMI language, German A1
HMI language, Russian A2
HMI language, French A3
HMI language, Spanish A4
HMI language, Polish A6
HMI language, Hungarian A7
HMI language, Czech A8
HMI language, Swedish A9
Selection for position #4.

Casing #5 Notes and Rules


1/2 x 19" case A Note: Only for A20/B20
3/4 x 19" case 1 TRM B Note: Only for A20/B20
1/1 x 19" case 2 TRM slots E Note: Only for A31/B21/B31
Selection for position #5.

Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A Note: Only for A20/B20
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B Note: Only for A20/B20
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with
fibre connection (SLM, OEM,
LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.

Connection type for Power supply, Input/output and Communication modules #7 Notes and Rules
Compression terminals K
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Selection for position #7.

Human machine hardware interface #8 Notes and Rules


Small size - text only, IEC keypad symbols A
Medium size - graphic display, IEC keypad symbols B
Medium size - graphic display, ANSI keypad symbols C
Selection for position #8.

Connection type for Analog modules #9 Notes and Rules


Compression terminals A
Ringlug terminals B
Analog system
First TRM, 12I, 1A 1
First TRM, 12I, 5A 2
No second TRM included X0 Note: A31/B31 must include a
second TRM, optional in B21
Second TRM, 12I, 1A 1
Second TRM, 12I, 5A 2
Selection for position #9.

ABB 55
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Binary input/output module, mA and time synchronization #10 Notes and Rules
boards. Note: 1BIM and 1 BOM included.
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand
capability is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Slot position (rear view) Note: Max 3 positions in 1/2 rack,

X31

X41

X51

X61

X71

X81

X91

X101

X111

X121

X131
8 in 3/4 rack with 1 TRM and 11
in 1/1 rack with 2 TRM
1/2 Case with 1 TRM █ █ █ Note: Only for A20/B20. Only
position X31 to X51 can be
selected
3/4 Case with 1 TRM █ █ █ █ █ █ █ █ Note: Only for A20/B20
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █ Note: Only for A31/B21/B31
No board in slot X X X X X X X X X Note: * Not in B21/B31
Binary output module 24 output relays (BOM) A A A A A A A A A A Note: Maximum 4 BOM+SOM
boards
BIM 16 inputs, RL24-30 VDC, 30 mA B B B B B B B B B B
Note: Basic configuration in A20,
BIM 16 inputs, RL48-60 VDC, 30 mA C C C C C C C C C C A31 and B20 adapted for 1 BIM
BIM 16 inputs, RL110-125 VDC, 30 mA D D D D D D D D D D and 1 BOM
Note: Basic configuration in B21
BIM 16 inputs, RL220-250 VDC, 30 mA E E E E E E E E E E and B31 adapted for 2 BIM and 1
BOM
BIM 16 inputs, RL24-30 VDC, 50 mA B B1 B B B B B B B B
1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, 50 mA C C1 C C C C C C C C
1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 VDC, 50 mA D D1 D D D D D D D D
1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 VDC, 50 mA E E1 E E E E E E E E
1 1 1 1 1 1 1 1 1
BIMp 16 inputs, RL24-30 VDC for pulse counting F* F F F F F F F F
BIMp 16 inputs, RL48-60 VDC for pulse counting G* G G G G G G G G
BIMp 16 inputs, RL110-125 VDC for pulse counting H* H H H H H H H H
BIMp 16 inputs, RL220-250 VDC for pulse counting K* K K K K K K K K
IOM 8 inputs, 10+2 output, RL24-30 VDC L* L L L L L L L L
IOM 8 inputs, 10+2 output, RL48-60 VDC M* M M M M M M M M
IOM 8 inputs, 10+2 output, RL110-125 VDC N* N N N N N N N N
IOM 8 inputs, 10+2 output, RL220-250 VDC P* P P P P P P P P
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA L1* L1 L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA M1* M M M M M M M M
1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA N1* N N N N N N N N
1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA P1* P P P P P P P P
1 1 1 1 1 1 1 1
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC U* U U U U U U U U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC V* V V V V V V V V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC W* W W W W W W W W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC Y* Y Y Y Y Y Y Y Y
mA input module MIM, 6 channels R* R R R R R R R R Note: No MIM board in 1/2 case
SOM Static outputs module, 12 outputs, 48-60 VDC T1* T1 T1 T1 T1 T1 T1 T1 T1
SOM static outputs module, 12 outputs, 110-250 VDC T2* T2 T2 T2 T2 T2 T2 T2 T2
Selection for position #10.

56 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Remote end communication, DNP serial comm. and time synchronization modules #11 Notes and Rules
Slot position (rear view)

X312

X313

X302

X303

X322

X323
Available slots in 1/2 case with 1 TRM █ █ █ █ Note: Max 1 LDCM
Available slots in 3/4 case with 1 TRM █ █ █ █ Note: Max 2 LDCM
Available slots in 1/1 case with 2 TRM slots █ █ █ █ █ █ Note: Max 2 LDCM
No remote communication board included X X X X X X
Optical short range SR LDCM A A A A A A
GPS Time module GTM S S S S
IRIG-B Time synchronization module, with PPS F
Galvanic RS485 communication module G G G G G G
Selection for position #11.

Serial communication unit for station communication #12 Notes and Rules
Slot position (rear view)

X301

X311
No first communication board included X
No second communication board included X
Serial and LON communication module (plastic) A Note: Optical ethernet module, 2
channel glass is not allowed
Serial (plastic) and LON (glass) communication module B
together with SLM.
Serial and LON communication module (glass) C
Serial IEC 60870-5-103 plastic interface F
Serial IEC 60870-5-103 plastic/glass interface G
Serial IEC 60870-5-103 glass interface H
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E
Selection for position #12.

Guidelines

Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in
combination with other functions and that some functions require specific hardware selections.
Please refer to the available functions table for included application functions.

Accessories
External current transformer unit

Note: Only for REB670 B20, B21 and B31


3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 1/1 A Quantity: 1MRK 000 643-EA

3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 5/1 A Quantity: 1MRK 000 643-FA

3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 2/1 A Quantity: 1MRK 000 643-GA

GPS antenna and mounting details

GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA

Cable for antenna, 20 m Quantity: 1MRK 001 665-AA

Cable for antenna, 40 m Quantity: 1MRK 001 665-BA

ABB 57
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Interface converter (for remote end data communication)

External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA

External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA

Test switch contacts. It is suitable when external CT grounding is required


The test system COMBITEST intended for use with the IED both for the three-phase version and single-phase versions.
670 products is described in 1MRK 512 001-BEN and 1MRK One such switch is then used per bay. With such
001024-CA. Please refer to the website: arrangement the best possible test facilities for BBP &
www.abb.com/substationautomation for detailed information. integrated BFP are available

Due to the high flexibility of our product and the wide variety Test switches type RTXP 24 is ordered separately. Please
of applications possible the test switches needs to be refer to Section "Related documents" for reference to
selected for each specific application. corresponding documents.

Select your suitable test switch based on the available RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and
contacts arrangements shown in the reference the on/off switch for dc-supply are ordered separately. Please
documentation. refer to Section "Related documents" for reference to
corresponding documents.
However our proposals for suitable variants are:

RK926 315-AV is provided with one three-phase CT input


with current shorting and with sixteen trip output blocking
Protection cover

Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE

Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC

Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB

Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA

Combiflex

Key switch for settings

Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A

Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.

Side-by-side mounting kit Quantity: 1MRK 002 420-Z

Configuration and monitoring tools

Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA

58 ABB
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

Manuals

Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.

Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB

User documentation
Rule: Specify the number of printed manuals requested
Operator’s manual IEC Quantity: 1MRK 505 209-UEN

ANSI Quantity: 1MRK 505 209-UUS

Technical reference manual IEC Quantity: 1MRK 505 208-UEN

ANSI Quantity: 1MRK 505 208-UUS

Installation and commissioning manual IEC Quantity: 1MRK 505 210-UEN

ANSI Quantity: 1MRK 505 210-UUS

Application manual IEC Quantity: 1MRK 505 211-UEN

ANSI Quantity: 1MRK 505 211-UUS

Engineering manual, 670 series Quantity: 1MRK 511 240-UEN

Reference information

For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

ABB 59
Busbar protection REB670 1MRK505212-BEN E
Pre-configured
Product version: 1.2

Related documents

Documents related to REB670 Identity number


Operator’s manual 1MRK 505 209-UEN
Installation and commissioning manual 1MRK 505 210-UEN
Technical reference manual 1MRK 505 208-UEN
Application manual 1MRK 505 211-UEN
Product guide pre-configured 1MRK 505 212-BEN

Connection and Installation components 1MRK 513 003-BEN


Test system, COMBITEST 1MRK 512 001-BEN
Accessories for 670 series IEDs 1MRK 514 012-BEN
670 series SPA and signal list 1MRK 500 092-WEN
IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN
Engineering manual 670 series 1MRK 511 240-UEN
Communication set-up for Relion 670 series 1MRK 505 260-UEN

More information can be found on www.abb.com/substationautomation.

60 ABB
61