(a) Connect PV or Grid power to wake up inverter; Connect the communication cable from
Inverter to computer.
(d) Set the parameter according to below recommendation, the max. charge current refer
to the specific battery amount of real application. Then click ‘Apply’. According to the
inverter limitation, for 2kW&3kW inverter max. is 25A, for 5kW max. is 100A, for 10kW
max. is 200A.
PIP-MS/MG INVERTER SETUP SOP - PYLONTECH BATTERY
(1) Inverter Spec.:
Note:
1. PIP Inverters can only be waked up via battery, if the battery is turned off due to over-discharge,
over temp. or other reasons, in order to wake up the inverter you need turn on the battery manually.
2. As there is no communication between inverter and battery, for a better using experience, it`s also
acceptable to introduce monitoring device to visually display the real-time information from battery
management system via the communication channel, such as Inverter Control Center(ICC) from
centurionsolar. Same as the inverter compatibility condition, such a monitoring system needs get
authorization from Pylontech in advance for the compatibility before using with the products from
Pylontech mentioned above, otherwise the products from Pylontech will be exclusive of warranty.
(4) Change the setting of inverter via Watchpower software:
(a) Connect computer and inverter with a USB communication cable.
(b) Run Watchpower software, click the icon marked with red circle in picture 1, to open the
login dialog.
Picture 1
(c) Input the password in the dialog as picture 2, the default password is ‘administrator’ , then
click ‘login’.
Picture 2
(d) Select ‘Device control’-> ‘Parameters Setting’.
Picture 3
(e) Change the ‘maximum charging current’, ‘battery type’, ‘back to grid voltage’, ‘back to
discharge voltage’, ‘CV voltage’, ‘floating charging voltage’ in the setting page, all these
setting must be set to the value listed in below table. Select the right value, then click ‘Apply’
for the changes to take effect.
Item Setting Value
Maximum charging current Set to N*25A, N=battery amount
Battery type Set to USE
Back to grid voltage Set to 48V
Back to discharge voltage Set to 51V
Bulk charging voltage Set to 53.2V
Float charging voltage Set to 47.5V
PIP-GK INVERTER SETUP SOP - PYLONTECH BATTERY
PIP5048GK
(1) Inverter Spec.:
INVERTER MODEL 5KW
Line Mode Specification
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage 230Vac
Max AC Input Voltage 300Vac
Inverter Mode Specification
Output Voltage Waveform Pure Sine Wave
Output Voltage Regulation 230Vac±5%
Peak Efficiency 93%
Overload Protection 5s@≥130% load; 10s@105%~130% load
Surge Capacity 2* rated power for 5 seconds
Nominal DC Input Voltage 48Vdc
Cold Start Voltage 46.0Vdc
Low DC Warning Voltage
@ load < 50% 46.0Vdc
@ load ≥ 50% 44.0Vdc
Low DC Warning Return Voltage
@ load < 50% 47.0Vdc
@ load ≥ 50% 46.0Vdc
Low DC Cut-off Voltage
@ load < 50% 43.0Vdc
@ load ≥ 50% 42.0Vdc
High DC Recovery Voltage 62Vdc
High DC Cut-off Voltage 63Vdc
Charge Mode Specification
INVERTER MODEL
Charging Algorithm 3-Step
AC Charging Current (Max) 60Amp (@VI/P=230Vac)
Flooded Battery 58.4
Bulk Charging Voltage
AGM / Gel Battery 56.4
Floating Charging Voltage 54Vdc
MPPT Solar Charging Mode
Max. PV Array Power 4000W
Nominal PV Voltage 240Vdc
Start-up Voltage 150Vdc +/- 10Vdc
PV Array MPPT Voltage Range 120~450Vdc
Max. PV Array Open Circuit Voltage 500Vdc
Max Charging Current (AC charger plus solar charger) 80Amp
General
Operating Temperature Range -10°C to 50°C
Storage temperature -15°C~ 60°C
Humidity 5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm 115 x 300 x 440
Net Weight, kg 10
Communication Interface RS232+RS485+USB+BLE+CAN
1
(2) General Compatible Condition:
Battery Type US2000B/US2000BPlus/Phantom-S/US3000
Inverter Type PIP 5048GK
Recommend According to load requirement and inverter rated power.
battery Amount Battery Amount N = Load power/1200W
Communication Not required, but need finish the setting on Inverter.
DOD 80%
Working Temp. 0 - 50℃(Indoor operation)
Charge/Discharge Current N*25, N = Battery amount
Warranty Refer to each country`s warranty terms, please contact your distributor
(d) Set the parameter according to below recommendation, the max. charge current refer
to the specific battery amount of real application. Then click ‘Apply’, enter password to
login. According to the inverter limitation, for 5kW max is 80A.
Method2: Through remote panel
(a) Connect Inverter with battery, wake up inverter.
(c) Press ‘Up’ and ‘Down’ to choose the setting item No., press ‘Enter’ to enter into the
detailed setting parameter, when finish press ‘Enter’ again. The following setting items
need to be set follow the recommended value:
Recommended value:
Item No. Setting Value
Program 02 Set to N*25A, N=battery amount, If
N = 1, 3…., minus single digit
Program 05 Set to USE
Program 12 Set to 48V
Program 13 Set to 51V
Program 26 Set to 53.2V
Program 27 Set to 53.2V
Program 29 Set to 47.5V