0% found this document useful (0 votes)
84 views

Fault Level CA.

This document discusses how to calculate fault levels at the distribution side of a power system. It provides a step-by-step process using data from a sample single line diagram to calculate fault levels at two points. The key steps are: 1) Calculate the source impedance from the given fault MVA, 2) Calculate the transformer impedance from its percentage impedance rating, 3) Calculate total impedance up to the transformer, 4) Convert the impedance to the low voltage side, 5) Calculate fault current without cable impedances, 6) Include cable impedances to calculate the fault current at a point downstream.

Uploaded by

Kunal Kadia
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views

Fault Level CA.

This document discusses how to calculate fault levels at the distribution side of a power system. It provides a step-by-step process using data from a sample single line diagram to calculate fault levels at two points. The key steps are: 1) Calculate the source impedance from the given fault MVA, 2) Calculate the transformer impedance from its percentage impedance rating, 3) Calculate total impedance up to the transformer, 4) Convert the impedance to the low voltage side, 5) Calculate fault current without cable impedances, 6) Include cable impedances to calculate the fault current at a point downstream.

Uploaded by

Kunal Kadia
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

FAULT LEVEL CALCULATION AT DISTRIBUTION SIDE 
 

™ Here in Fig‐1 a simple single line diagram is shown. Here we have to select HT & LT switch gear 
from the fault level. 
™ Generally Supply provider provides us a Fault level for HT side. 
™ From the above theory we know that for the fault calculation we require 
1. HT side fault level 
2. Transformer ‘s  % impedance value 
3. Cable impedance value 
™ HT side fault level is provided from supply provider company. 
™ % impedance value is given in the Transformer name plate or Datasheet. If not we can get it 
from manufacturer. 
™ Cable impedance value is not directly given in the manufacturers catalogue but they provide 
resistance & reactance value per 1000 m. So we have to convert that R & X values into Total 
impedance . Using following Formula, 
Z=Squareroot of (R2 + X2). 
Than we have to convert this Z value in Per meter. 
Than,   Total impedance Z = (Z/meter)*(Total cable length to the fault ). 
™ Now we are able to collect all the data required for calculation of Fault level. See first how to 
calculate it using following example. 
™ But keep in mind that if have to calculate Fault level near the transformer area like in the PCC 
terminals we are neglecting the cable or busbar impedance values  between PCC & Transformer. 
 

 

FAULT LEVEL CALCULATION AT DISTRIBUTION SIDE 
 

Above Single line diagram contains tentative values. 

Now Calculating the Fault level at Point F1 & F2. Following steps should be Proceed. 

Step – 1  First calculate Source Imedance from the given HT fault Level. For this use following Formula. 

 
Here in the SLD we have HT voltage 11 KV & Fault MVA = 350 MVA 

We can also Reduce above equation in terms of KV & MVA 

Like,    Source Z Ω     =      KV2 

             Fault MVA 

Now putting the above values, 

Source Z Ω =  (11)2 / 350 = 0.346 Ω 

Step – 2 Calculate Transformer Impedance from the given % impedance value using following formula. 

 

FAULT LEVEL CALCULATION AT DISTRIBUTION SIDE 
Here put the value of  % impedance directly into the above equation no need to convert it into actual 
value. 

From the SLD, % impedance value of Transformer is 6.5 % as given on Manufacturer Datasheet. & MVA 
is the Transformer Rating not fault level. 

So,  Transformer Z in Ω = (6.5 * 112) / 2.25 = 3.5 Ω 

Step – 3 Now calculate total HT impedance up to transformer using following formula. 

 
So from above calculated data,  Total Z Ω HT = 0.346 + 3.5 = 3.84 Ω 

Step – 4 Now convert  this Z Ω HT side value to LT side using following formula. 

 
HV & LV voltage ratings are given on the Transformer Name plate or Datasheet. Like 11 / 0.433 KV. 

So here HV = 11 KV    &    LV = 0.433 KV. 

Therefore,  Z Ω LT side = (3.84 * 0.4332) / 112 = 0.006 Ω 

Step – 5  Calculate LT fault current From following equation using above values. 

 
 

So that LT Fault Current  =  (0.433) / (√3 * 0.006) =  41.6 KA. 

Step – 6  If required Calculate fault MVA from the calculated fault current from following equation. 

LT Fault Level in MVA = √3 *LV in KV*Fault Current in KA.  

™ Up to step – 6 we have calculated fault current at point F1 i.e. here we have neglected the cable 
from transformer to PCC & busbar in the PCC panel because they are very near to the 
Transformer.  

™ Now to calculate Fault current at point F2 which is far from transformer & near to load. In the 
SLD  location of fault point is on the motor terminal. For this condition we have to consider 
impedences of cable up to the fault point from PCC panel. 

™ We know the impedance values upto the PCC panel is 0.006 Ω that we have calculated earlier. 

FAULT LEVEL CALCULATION AT DISTRIBUTION SIDE 
So take following steps further. 

Step – 7  Calculate cable impedance from PCC to MCC panel. 

For calculation of Cable Impedance we require Resistance & Reactance of the cable which is provided in 
the Cable manufacturer catalogue or in the datasheet of it. 

Here in SLD we given Cable from PCC to MCC  is 3.5 Core 120 Sq.mm. Aluminium  & 100 m long. 

From the catalogue or Datasheet  R = 20 Ω/km  & X = 10 Ω/km. 

Therefore  R = 20 / 1000 = 0.02 Ω/m 

                    X = 10 / 1000 = 0.01 Ω/m 

Therefore Z1 = √(0.022 + 0.012 ) = 0.022 Ω/m. 

Cable is 100 m long so Z1 = 0.022*100 = 2.2 Ω 

Step – 8  Calculate cable impedance from MCC to motor terminal. 

From the SLD cable size is 3C X 6 Sqmm Aluminium, 150 m long. 

From the catalogue or Datasheet  R = 35 Ω/km  & X = 29 Ω/km. 

Therefore R = 35 / 1000 = 0.035 Ω/m 

                   X = 29 / 1000 = 0.029 Ω/m 

Therefore Z2 = √(0.0352 + 0.0292 ) = 0.046 Ω/m 

Cable is 150 m long so Z2 = 0.046 * 150 = 6.9 Ω/m 

Step – 9  Calculate total cable impedance from PCC to Fault point. 

Total Cable impedance = Z1 + Z2 = 2.2 + 6.9 = 9.1 Ω 

Step – 10 Calculate total impedance from source to Fault point. 

Total Impedance = Impedance to PCC + Impedance from PCC to Fault point 

                               = 0.006 + 9.1 =9.11 Ω 

Step – 11 Calculate fault current using formula given in step – 5 . 

Therefore Fault current at Fault point F2 = (0.433) / (√3 * 9.11) = 0.03 KA. 

This value of fault current is not practical possible because here we have consider the tentative values of 
impedances for the cable put the actual value of impedances of cable from catalogue then you will find 
exact value of fault current . 

™ According to this fault current values we can select the Protection switch gear breaking capacity. 

You might also like