CT Manual-Final Version (With Composite Insulator)
CT Manual-Final Version (With Composite Insulator)
`
Page No: 1 of 21
CONTENTS
CAUTION!
If User fails to strictly comply with relevant requirements regarding
Storage Erection, Commissioning, Periodic Maintenance specified in this
Manual, CG reserves right to revoke guarantee on product quality.
`
Page No: 2 of 21
1.1 Scope
This instruction manual is applicable to live tank outdoor current transformers (CT) manufactured
by CG Power and Industrial Solutions Limited, India. These CTs step down current proportionally
for measurement and protection devices in the electrical system with highest system voltage
(HSV) from 24 kV to 170 kV and Rated frequency 50 or 60 Hz.
This instruction manual gives information on recommended procedures for inspection after
receipt, handling, commissioning and periodic maintenance of CT after dispatch from our works.
The drawings and other informative data in this manual may vary slightly from the equipment
supplied. In all cases drawings submitted by CG and identified with the respective equipment will
be correct in all details.
The contents of this manual cover majority of circumstances that may occur in practice. In case
additional understanding is needed, contact CG Power and Industrial Solutions Limited, India.
CAUTION!
Customers or users are required to perform installation, testing,
regular inspection and maintenance of the equipment by
qualified and trained personnel.
Design:
Aluminium alloy tank accommodates primary winding and shell. Shell is an aluminium cast
housing to accommodate secondary windings.
Primary winding consists of Aluminium / Copper rods tubes and or sections accommodated in
the tank. The primary connections are performed using primary terminals (P1 & P2) on the sides
of the tank. Ratio selection by primary turns adjustment can be achieved by changing terminal
position on P2 side of tank (as shown in figure No. 2 & 3). The Rating & Schematic diagram on
secondary box of CT indicates position of Primary terminal for ratio selection.
Tightening torque for primary reconnection bolts (in case if it is present): 20 N-m
The secondary windings are of insulated copper wire uniformly wound over the ring type toroidal
cores. Each layer of winding is perfectly insulated from each other using high quality insulating
material. The cores with secondary windings are accommodated in aluminium cast shell. The
secondary leads are taken through capacitor graded bushing to the base of the CT and are
terminated in the secondary box at the base of CT.
`
Page No: 3 of 21
1.2.4 Insulation
Major insulation between Shell [3] (at ground potential) and Aluminium Tank [5] (at high potential)
is of high quality electrical grade insulating Kraft paper. Complete CT after assembly is dried and
impregnated with high quality of mineral oil under fine vacuum. The drying and oil impregnation is
carried out in specially designed autoclaves and a well defined drying and impregnation cycle is
followed. The insulation of the bushing through which secondary leads are passed, is provided
with condenser grading. This helps in achieving optimum and consistent impulse withstand
capability.
The oil filled metallic bellows [2] compensates for the oil volume variation due to ambient
temperature variation. Bellows serves the purpose of oil level indication. The CT is hermetically
sealed by using these bellows. With this hermetic sealing, the insulating characteristics of
dielectric are maintained during the service life of product. We do not recommend any repair /
rework on CTs at site without our consent.
Brown or Grey (on request) glazed porcelain insulator / Composite insulator (Optional) are
offered. Shed profile and creepage distance are selected as per voltage level and ambient
conditions of site. Insulator is fixed to aluminium alloy flanges on both sides with suitable bonding
agent for providing optimum mechanical strength.
Primary terminal of CT can be cylindrical or NEMA pad type (palm / flat). For dimensions of
primary terminal, refer contractual drawings. Primary terminal of the CT can be with fixed or ratio
changeover arrangement. For details of offered primary changeover arrangement refer
contractual drawings.
`
Page No: 4 of 21
For higher ratio : Reconnection link should be bolted to the fixed terminal P2 of the CT. Threaded
holes are provided on the Reconnection link at the centre for fixing it to P2 terminal.
For lower ratio: Unscrew the Reconnection link from fixed terminal P2 and bolt it to the two
aluminium bosses which are welded on the tank on each side of the P2 terminal. Threaded holes
are provided on each aluminium boss for bolting.
For higher ratio the detachable terminal should be connected to fixed aluminium pad marked
P2-1.
For middle ratio the detachable terminal should be connected to aluminium pad marked P2-2.
For lower ratio the detachable terminal should be connected to aluminium pad marked P2-4.
`
Page No: 5 of 21
1.3.2 Secondary terminals
Secondary Terminals are housed inside the secondary terminal box at the base of CT. Terminal
designations are shown in the schematic diagram. Be sure that burden values given in rating
plate are adhered to and secondary windings not in use are short circuited. Use Torque wrench
to tighten secondary terminals. Use Torque values M4- 3 Nm; M5- 3 Nm; M6-5 Nm.
CAUTION!
Always ensure that terminals of unused secondary windings are short
circuited. If multiple ratios are present, the terminals of highest ratio must
be shorted.
CAUTION!
Capacitance & Tan delta terminal “Cx” must be grounded before
charging the CT.
CAUTION!
Tighten stud type secondary terminals to the respective maximum
torque.
Minimum two holes are provided on diagonally opposite legs of base [14] of CT for earthing
connection. It is necessary that CT is independently earthed. Separate earth lead needs to be
used for earthing. The earthing connection must be mechanically rigid and capable to carry the
system’s fault current.
CAUTION!
Inadequate or defective earthing connection may cause danger to life in
case of human contact with CT.
2.1 Packing
The CTs are suitably packed in wooden / steel crates OR base. Cushions are provided inside
packing case to hold the unit during shipment. Packed CTs are transported in horizontal position.
CAUTION!
Do not change orientation of packing during horizontal transportation.
Follow all transport markings on the packaging.
Scrutinize shipping documents with your contract and the markings on the packing case.
Conduct visual inspection for any external damage.
In case any damage is noticed and goods are insured by you, immediately inform your
insurance company and proceed further as guided by the insurance company.
In case any damage is noticed and goods are insured by us , proceed as below,
`
Page No: 6 of 21
- Inform us by email or fax, Conduct & Prepare FIR
- Take photographs of the damaged packing case and CT, send it to us.
- We would take necessary actions and would keep you informed.
Seal on Oil
Sampling Valve
CTs are transported in horizontal condition in packing case. It is necessary to remove CTs from
packing case immediately after it reaches to the site. If CT is required to be stored for longer
time, ensure that it is stored in vertical condition in a clean, protected, less polluted environment
on a hard levelled surface till commissioning.
CAUTION!
Do not keep Current Transformer (CT) in Horizontal Position for more than
3 months.
Open packing case and unscrew all nuts and bolts used for clamping CT (on tank side and base
side) in the packing case.
On removal from packing case, CT should be kept on levelled ground. Ensure wooden
supports are kept in a position to prevent damage to CT Primary terminal.
Refer Fig. 3 & 4 for making CT vertical. During whole erection phase, rope must be at 90
degree angle to ground. Also ensure that a wooden support is firm on the ground to avoid
heavy swinging of the CT during making it vertical.
During Vertical handling and shifting vertically avoid heavy jerks. Use lifting lugs which are
provided on top tank for vertical handling of CT. Ensure sufficient rope length to avoid the
damage of hood.
`
Page No: 7 of 21
3.2 Mounting of CT
Four mounting holes are provided on the Base [14] for fixing CT firmly on support structure.
Refer relevant drawings against contract for details.
3.3 Procedure for removal of PVC Sheet from Hood and Visual Check for Oil from Oil
Presence Indicator
`
Page No: 8 of 21
3.4 Electrical Connections
Use earthing holes provided on the base for connecting CT to Substation earth. Earthing system
should be capable of carrying full short circuit current of the system. Remove protecting coating
(in case provided) around the earthing holes to ensure firm contact.
Use Secondary Terminal Blocks for connecting leads of instruments, relays etc. Connections
must be done as per Rating plate & Schematic Plate. Ensure that Burden (VA) values given on
the rating plate are adhered to & are not exceeded.
CAUTION!
Secondary windings not in use must be short circuited firmly by
shorting links. Otherwise it will lead to dangerous high voltage across
the secondary windings & failure of product.
`
Page No: 9 of 21
4 Commissioning
Check following points before charging of CT. We recommend that the checks to be performed
on each CT and tick-marked in status column after having completed the check. After
completion of all pre-commissioning checks, the CT can be charged to its operating voltage.
`
Page No: 10 of 21
5.1 Periodic Maintenance
CAUTION!
Any site repairs conducted without written
consent of CGPISL will void the guarantee and
warranty of product
Inspect The terminal box should be kept clean dry and free from
cleanliness of insects.
G secondary If rain water has entered the box, inspect rubber gasket on
terminal box the door and if necessary tighten the clamping bolts of
& its sealing cover.
Minor damage to porcelain insulator shed can lead to hairline
cracks which are initially too small to see and later lead to oil
leakage.
Inspect In case of damage thorough examination is recommended.
insulator and Heavy pollution on the insulator surface combined with
H
its moisture can lead to surface corona, flashover etc.
cleanliness Keep insulators clean in accordance with local (plant)
experience, clean (if required).
Follow safety rules while cleaning. Refer local regulations.
(See IEC 60815).
Visual
inspection for Inspect connections for corrosion, especially if unlike metals
I corrosion of are in direct contact with one another.
secondary If necessary improve corrosion by painting.
terminal box
Check temperature of P1 and P2 terminals by thermo vision
Check
J camera.
Temperature
In case hot spot is observed, tighten connections.
Tan Delta
K Measurement Refer Clause No. 5.2
on CT
Ageing of oil is prevented by hermetical sealing of CT.
It is recommended that testing of oil sample be performed
after every 5 years of service life.
Ensure that oil sampling is done in dry air with procedure
Check recommended in IEC 60415.
Insulating Oil The sample should be taken only by a trained specialist and
L
analysed by a qualified laboratory.
Ensure that minimum oil volume is sampled from CT which
is sufficient for the required test.
Maximum four samples are recommended.
Tan Delta Tests to be performed as per IEC 60250.
BDV Tests to be performed as per IEC 60156.
`
Page No: 12 of 21
Moisture
(Water Tests to be performed as per IEC 60814.
Content)
`
Page No: 13 of 21
* Partial Discharge Measurement (PD)
The PD measurement as a diagnostic tool can only be used if there are suitable equipments to
measure on site. For tests in laboratories limits of IEC 61869 are recommended, Because of
the high noise on site, PD is not recommended for routine check of the Current Transformer
(CT), but only as additional information.
LEGEND
TIME INTERVAL A B C D E F G H I J K L M
Tan delta measurement can be conducted at site after CT is disconnected electrically from the
transmission line. Measurement needs to be conducted between HV terminal (P1-P2) and Tan
delta testing terminal, Cx. Test equipments by renowned manufacturers can be used. Test
procedure to be in line with the test equipment manufacturer. Ensure that measurements are
conducted between the test voltages of 5 kV to 10 kV.
5.2.1. Cx Terminal:
CG provides separate Tan delta testing terminal “Cx” inside secondary terminal box. This
terminal needs to be used for tan delta measurement.
`
Page No: 14 of 21
CAUTION!
Except for the measurements, Capacitance and Tan delta terminal
terminals MUST be connected to earth (ground). If left open, while the CT is
in operation, it will lead to explosive failure.
Notes:
Capacitance & tan delta measurements at site are most sensitive and can be affected
by the atmospheric conditions & electrical environment prevailing at site. Always
ensure that the measurements are carried out under dry atmospheric conditions.
We recommend the CT to be tested for tan delta before commissioning and the value
obtained shall be considered as a reference value for further monitoring during
service. Tan delta should be < 0.005 before commissioning.
CT is to be tested for tan delta as mentioned in Periodic Maintenance in this Manual.
Limiting value of tan delta is 0.010. In case tan delta exceeds this value, contact us.
CT is tested at factory for capacitance & tan delta under controlled conditions and at
rated voltages specified in standards.
Oil sampling is recommended for DGA and other tests as a part of periodic maintenance.
Since CT is hermetically sealed, oil sampling will result in to reduction of bellow level. CGPISL
supplies special oil filling kit and adaptor (optional) in order to restore the bellow level of CTs at
site. Without opening the air tight system, oil can be pumped back in to CTs in order to restore
correct level of bellows. In case of any requirements contact CGPISL.
`
Page No: 15 of 21
6.1 Cross-sectional drawing of a typical CT
Fig. 1
`
Page No: 16 of 21
6.2 Horizontal and Vertical Transportation
Note: Centre of Gravity lies approximately by the first or second porcelain shed.
Fig. 2
Ensure simultaneous
crane movement in
vertical and horizontal
direction to avoid
dragging of CT.
Ensure fixed
location of
wooden block to
avoid jerk on CT
while making it
vertical.
Fig. 3 Fig. 4
Note: The rope must always hang vertically (i.e. 90 0 to ground) when erecting.
`
Page No: 17 of 21
7.1 Instructions for disposal of materials
We have used environmental friendly materials for manufacture of CT. Treat this equipment as
industrial waste when disposing it.
After useful service life of CT, care should be taken to dispose insulating oil and some of below
components. Insulating oil used on our CTs is mineral, naphthenic base which is transparent
and free of particles. It does not contain PCBs.
In case of abnormal & emergency condition during life cycle of Current transformer & Condenser
Bushings to minimize environmental pollution:
Ensure no storage of packing wood for long duration in humid condition as it will cause land
pollution. Alternatively incinerate/bury the infected wood as per local regulation.
Rusting of steel used in packing case as it will cause contamination of water & soil. Take
action as per local regulation.
In case of fire caused by explosion of product, immediately switch off the high voltage circuit if
it is not tripped. Use fire protecting equipment to extinguish the fire. Take actions as
recommended by the local regulation. Inform us.
Insulating oil used on the CTs is Naphthenic base mineral oil conforming to IEC 60296 and IS
335. The oil is produced using Indian based refineries. The oil is stable during storage and
handling and is not hazardous in nature.
After service life of CT, in case insulating oil is taken out of CT, care should be taken that
it is stored at cool, dry and clean location. It must be protected from heat and flames.
`
Page No: 18 of 21
It is non-toxic, non-irritating, use of protective measures are recommended as below
Skin Contact : Remove oil – soaking clothing. Wash affected parts of the body thoroughly
with soap and water.
Eye contact : Hold eyelids open and flush eye with water.
Inhalation : In the event of dizziness or nausea, remove casualty to fresh air. If
symptoms persist obtain medical attention. If breathing stops give assisted respiration by the
mouth to mouth or mouth to nose method.
Absorb a small spillage with sand or earth. Sweep up and contain absorbent and then remove
it to an appropriate facility for disposal in compliance with local regulations.
Large spillages should be prevented from spreading by the use of sand or earth. If possible
transfer the spilled oil to a salvage tank; otherwise treat as for a small spillage.
Used oils may contain harmful impurities, which present risks to health that are not present
when handling the new oil. It is not possible to be more specific since the presence or absence
of harmful impurities is use dependent therefore used oil should not be allowed to contaminate
soil or water and should be disposed of in accordance with prevailing regulations, preferably to
a recognized collector or contractor.
This information is based on our knowledge as of and is intended to describe the product for the
purposes of health and safety requirements only. It should not therefore be construed as
guaranteeing any specific property of the product.
`
Page No: 19 of 21
…………………………...................................................................................................................
`
Page No: 20 of 21
CG Power and Industrial Solutions Limited, India.
(Formerly Crompton Greaves Limited)
Vacuum Interrupters and Instrument Transformers Division: Power Systems
D2 & D1/2, MIDC, Waluj, Aurangabad - 431 136, Maharastra, India,
Tel:-+91 0240-2558000, 2558031
Fax:- +91-240-2554697
Email: [email protected]
[email protected]
[email protected]
[email protected]