IECEx ITS 16.0041X 001
IECEx ITS 16.0041X 001
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Equipment: Cable Glands, Blanking Elements/Stopping Plugs, Reducer, Adaptor, Adapter Nipple & Couplings and Breather/
drain plugs
Optional accessory:
Type of Protection: Flameproof, Increased Safety and Dust Ignition Protection by enclosure
Marking:
Ex db IIC Gb / Ex eb IIC Gb
Ex tb IIIC Db
Signature:
(for printed version)
Date:
(for printed version)
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended
STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards
IEC 60079-1:2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0
IEC 60079-31:2013 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
Edition:2
IEC 60079-7:2017 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:5.1
This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.
Test Reports:
GB/ITS/ExTR16.0040/00 GB/ITS/ExTR16.0040/01
EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:
Akshar Brass Industries manufacture CABTEK Brand Cable Glands, Blanking Elements/Stopping Plugs, Reducer, Adaptor, Adapter Nipple &
Couplings and Breather/drain plugs.
IECEx Certificate
of Conformity
Certificate No.: IECEx ITS 16.0041X Page 4 of 4
Annex:
Technical Documents
Title: Drawing No.: Rev. Level: Date:
Cable Glands
*E1F Ex Cable Gland Ex-CE1F 1 12/01/2022
*A2F Ex Cable Gland Ex-CA2F 1 12/01/2022
*CW Ex Cable Gland Ex-CCW 1 12/01/2022
*A2FMH/A2FFF/SS2KGPFF Cable Gland 2 Sheets Ex-A2FFF/RC 0 12/01/2022
*Explosion Proof Compound Barrier Cable Gland 2 Sheets Ex-CBC 0 12/01/2022
*IP68 Cable Gland Ex-IP68 0 12/01/2022
*Adapter 5 Sheets Ex-A# 0 12/01/2022
*Reducer 5 Sheets Ex-R# 0 12/01/2022
*Adaptor Nipple 2 Sheets Ex-AN# 0 12/01/2022
*Adaptor Coupling 2 Sheets Ex-AC# 0 12/01/2022
Stop Plug / Blanking Elements
*Hexagonal Stop Plug/Blanking Element Ex-CHSP 1 12/01/2022
*Allen Stop Plug/Blanking Element Ex-CASP 1 12/01/2022
*Breather Drain Plug for Ex e applications Ex-BDPE-# 0 12/01/2022
IM / Cable Gland A2F
Installation Manual for A2F Cable Gland 1 12.01.2022
series
IM / Cable Gland A2FFF
*Installation Manual for A2FFF Cable Gland 0 12.01.2022
series
IM / Cable Gland
Installation Manual for A2FFFC Cable Gland 0 12.01.2022
A2FFCF series
IM / Cable Gland
Installation Manual for A2FFRF Cable Gland 0 12.01.2022
A2FFRF series
IM / Cable Gland
Installation Manual for A2FFRM Cable Gland 0 12.01.2022
A2FFRM series
IM / Cable Gland
Installation Manual for A2FMH Cable Gland 0 12.01.2022
A2FMH series
IM / Cable Gland
Installation Manual for A2FMHFC Cable Gland 0 12.01.2022
A2FMHFC series
IM / Cable Gland
Installation Manual for A2FMHRF Cable Gland 0 12.01.2022
A2FMHRF series
IM / Cable Gland
Installation Manual for A2FMHRM Cable Gland 0 12.01.2022
A2FMHRM series
Installation Manual for Adaptor & Reducer IM / A-R-AN-AC Series 0 12.01.2022
Installation Manual for Stopping Plug/Blanking Element IM / Blanking Elements 01 12.01.2022
IM / Cable Gland
Installation Manual for Compound Barrier PX2K Cable
Compound Barrier PX2K 0 12.01.2022
Gland
Series
IM / Cable Gland
Installation Manual for Compound Barrier PXSS2K Cable
Compound Barrier 0 12.01.2022
Gland
PXSS2K Series
IM / Cable Gland
Installation Manual for Compound Barrier SS2KGP-FF Cable
Compound Barrier 0 12.01.2022
Gland
SS2KGP-FF Series
Installation Manual for CW Cable Gland IM / Cable Gland CW 01 12.01.2022
Certificate issued by: Intertek Testing & Certification Ltd. Page 1 of 11
Intertek House, Cleeve Road,
Leatherhead, Surrey, KT22 7SA, UK SFT-IECEx-OP-19f (26 October 2018)
Annex 1 to IECEx Certificate of Conformity
Certificate No: IECEx ITS 16.0041X Issue No. 1
Annex No. 1
Technical Documents
Title: Drawing No.: Rev. Level: Date:
series
IM / Cable Gland E1F
Installation Manual for E1F Cable Gland 01 12.01.2022
series
IM / Cable Gland IP68
Installation Manual for IP68 Cable Gland 0 12.01.2022
series
Installation Manual for Breather Drain Plug IM / BDPE series 0 12.01.2022
Cable Glands can be produced with extended entry thread with 20mm or 25mm length and conduit connection
facility in gland as per customer need without changing flame path and cable clamping range.
• E1FW, E1FX and E1FU Double Compression Cable Glands with Universal Armoured Ring are designed for
armoured cables
• CWe, CXe / CUe Single Compression Cable Glands with Universal Armoured Ring for armoured cables
• A2F and IP68 Cable Glands designed for non-armoured and braided cables
• PX2K Cable Gland are for armoured cable with Compound Barrier seal
• PXSS2K Cable Gland are for unarmoured cable with Compound Barrier Seal
• A2F-MH Cable Gland for Multi Core cable to terminate individually
• A2F-MHFC, A2F-MHRF, A2F-MHRM Cable Gland for multi core cable to terminate individually with
conduit connection
• A2F-FF Cable Gland for Flat/Tracer cable to terminate individually
• A2FFFFC, A2FFFRF, A2FFFRM Cable Gland for Flat/Tracer cable to terminate with conduit connection
• SS2KGP-FF Cable Gland for Flat/Tracer cable with double compression
The Blanking Elements/Stopping Plugs are manufactured with an external male thread along its length with the
exception of a Hexagonal (HSP Series) or Allen (Dome) Head (ASP Series) at one end.
Adapter/Reducer/Nipple/Coupling
• Adaptor having a male thread entry and adapting to female thread same size or higher size
• Reducer having male thread entry and reducing to female thread lower size
• Adaptor Nipple having same size male thread on both end
• Adaptor Coupling have same size female thread on both end
BDPE Series breather/drain plugs are designed to allow moisture emission from Ex e and Ex tb enclosures and to
Certificate issued by: Intertek Testing & Certification Ltd. Page 2 of 11
Intertek House, Cleeve Road,
Leatherhead, Surrey, KT22 7SA, UK SFT-IECEx-OP-19f (26 October 2018)
Annex 1 to IECEx Certificate of Conformity
Certificate No: IECEx ITS 16.0041X Issue No. 1
Annex No. 1
allow air within the enclosure to breathe with the surrounding atmosphere. Drainage channels through the body
allow for the passage of moisture through the filter. The device may be screwed into the wall of an enclosure or
into a through hole, being secured by a locknut.
Parallel threaded Breather Drains may be fitted with thread seal and screwed into the wall of an enclosure or into
a through hole, being secured with a castellated locknut, they will maintain IP66 degree of protection.
Tapered threaded Breather Drain may be fitted with or without thread seal, see below for approved seals. When
fitted with thread seal and secured into a through hole, they will maintain IP66 degree of protection.
Explanation on ordering coding and model nomenclature of E1FW / E1FX / E1FU / A2F / CWe / CXe / CUe / IP68
/ PX2K / PXSS2K Cable Glands:
“*” Cable Standard Entry Thread “C” Optional Entry Thread “C”
Gland Size Metric NPT/BSP ET (BSC) PG Metric NPT
16 M16x1.5 ⅜” ⅝” PG9 - -
20s16 M20x1.5 ½” ¾” PG11 M25x1.5 ¾”
20s M20x1.5 ½” ¾” PG11 M25x1.5 ¾”
20 M20x1.5 ½” ¾” PG13.5 M25x1.5 ¾”
25s M25x1.5 ¾” 1” PG16 M32x1.5 1”
25 M25x1.5 ¾” 1” PG21 M32x1.5 1”
32 M32x1.5 1” 1¼” PG29 M40x1.5 1¼”
40 M40x1.5 1¼” 1½” PG36 M50x1.5 1½”
50s M50x1.5 1½” 2” PG36 M63x1.5 2”
50 M50x1.5 2” 2” PG42 M63x1.5 2½”
63s M63x1.5 2” 2½” PG48 M75x1.5 2½”
63 M63x1.5 2½” 2½” - M75x1.5 3”
75s M75x1.5 2½” 3” - M90x2 3”
75 M75x1.5 3” 3” - M90x2 3½”
90 M90x2 3½” 3½” - M100x2 4”
Explanation on ordering coding and model nomenclature of A2F-MH, A2F-MHFC, A2F-MHRF, A2F-MHRM Cable
Glands:
*Cable Optional Entry Thread Multi Hole Seal Detail
Standard Entry Thread "C"
Gland "C" Seal Hole Number of
Size Metric NPT/BSP ET (BSC) PG Metric NPT/BSP Cable Ø (X) Holes
M16x1.5 ⅜” ⅝" PG9 M20x1.5 ½” 1.5 1 to 6
16
M16x1.5 ⅜” ⅝" PG9 M20x1.5 ½” 2.0 1 to 6
M20x1.5 ½” ¾” PG1 M25x1.5 ¾” 2.5 1 to 7
M20x1.5 ½” ¾” 6
PG1 M25x1.5 ¾” 3.0 1 to 7
20 6
M20x1.5 ½” ¾” PG1 M25x1.5 ¾” 3.6 1 to 7
M20x1.5 ½” ¾” 6
PG1 M25x1.5 ¾” 4.0 1 to 7
M25x1.5 ¾” 1" 6
PG2 M32x1.5 1" 2.5 1 to 7
M25x1.5 ¾” 1" 1
PG2 M32x1.5 1" 3.0 1 to 7
25 1
M25x1.5 ¾” 1" PG2 M32x1.5 1" 3.6 1 to 7
M25x1.5 ¾” 1" 1
PG2 M32x1.5 1" 4.0 1 to 7
M32x1.5 1" 1¼” 1
PG2 M40x1.5 1¼” 2.5 1 to 7
M32x1.5 1" 1¼” 9
PG2 M40x1.5 1¼" 3.0 1 to 7
32 9
M32x1.5 1" 1¼” PG2 M40x1.5 1¼" 3.6 1 to 7
M32x1.5 1" 1¼” 9
PG2 M40x1.5 1¼" 4.0 1 to 7
9
Explanation on ordering coding and model nomenclature of A2FFF, A2FFFC, A2FFFRF, A2FFFRM, SS2KGPFF Cable
Glands:
Standard Entry Optional Entry Thread Cable No. of
*Cable
Thread "C" “C” Range Flat
Gland
Cable
Size Metric NPT Metric NPT Min Max
used
20s M20x1.5 ½” M25x1.5 ¾” 4x6.2 6.8x11.7 1
20 M20x1.5 ½” M25x1.5 ¾” 5.7x8 8.7x13.5 1
25s M25x1.5 ¾” M32x1.5 1” 4x6.2 6.8x11.7 2
25 M25x1.5 ¾” M32x1.5 1” 5.7x8 8.7x13.5 1
32s M32x1.5 1” M40x1.5 1¼” 4x6.2 6.8x11.7 3
32 M32x1.5 1” M40x1.5 1¼” 5.7x8 8.7x13.5 3
Explanation on ordering coding and model nomenclature of Reducer(R), Adaptor(A), Adaptor Nipple (AN),
Adaptor coupling (AC)
Threaded Adaptor and Reducer
Female Metric/NPT/BSP/BSC Thread Size
Male
M16 M20 M25 M32 M40 M50 M63 M75 M90 M100
Metric/NPT/
⅜”, ½”, ¾” 1" 1¼” 1½” 2" 2½” 3" 3½”
BSP/BSC
⅝”ET ¾”ET 1"ET 1¼”ET 1½”ET 2"ET 2½”ET 3"ET 3½”ET 4”ET
Entry Size
M16 A A A
⅜”, ⅝”ET
M20
R A A A A
½”, ¾” ET
M25
R R A A A A
¾”, 1"ET
M32
R R R A A A A
1", 1¼”ET
M40
R R R R A A A A
1¼”, 1½” ET
M50
R R R A A A
1½”, 2”ET
M63
R R R A A
2", 2½”ET
M75
R R A A
2½”, 3”ET
M90
R R R A
3", 3½”ET
Male to Male (Adaptor Nipple) and Female to Female (Adaptor Coupling) Thread Converter
Male/Female Male/Female Metric/NPT/ BSP/ET(BSC) Thread Size
Metric/NPT/ M16 M20 M25 M32 M40 M50 M63 M75
BSP/ET(BSC) ⅜” ½” ¾” 1" 1¼” 1½” 2" 2½”
Entry Size ⅝”ET ¾”ET 1"ET 1¼”ET 1½”ET 2” ET 2½”ET 3”ET
M16
⅜”, ⅝”ET
M20
½”, ¾”ET
M25
¾”, 1"ET
M32
1", 1¼”ET
M40
1¼”, 1½”ET
M50
1½”, 2” ET
M63
2", 2½”ET
M75
2½”, 3”ET
Explanation on coding and model nomenclature of Blanking Elements / Stopping Plug ASP / Hexagonal HSP:
Size Entry Thread Type
Metric NPT/BSP ET (BSC) PG
16 M16x1.5 - - -
20 M20x1.5 - -
25 M25x1.5 - - -
32 M32x1.5 - - -
40 M40x1.5 - - -
Certificate issued by: Intertek Testing & Certification Ltd. Page 8 of 11
Intertek House, Cleeve Road,
Leatherhead, Surrey, KT22 7SA, UK SFT-IECEx-OP-19f (26 October 2018)
Annex 1 to IECEx Certificate of Conformity
Certificate No: IECEx ITS 16.0041X Issue No. 1
Annex No. 1
50 M50x1.5 - - -
63 M63x1.5 - - -
75 M75x1.5 - - -
90 M90x2 - - -
100 M100x2 - - -
⅝” - ⅝”
⅜” - ⅜” ⅜” -
½” - ½” ½” -
¾” - ¾” ¾” -
1” - 1” 1” -
1¼” - 1¼” 1¼” -
1½” - 1½” 1½” -
2” - 2” 2” -
2½” - 2½” 2½” -
3” - 3” 3” -
3½” - 3½” 3½” -
7 PG7
9 PG9
11 PG11
13.5 PG13.5
16 PG16
21 PG21
29 PG29
36 PG36
42 PG42
48 PG48
larger than 0.3 to 0.5mm above the major diameter of the male thread on the stopping plug.
6. The stopping plug is secured using a suitable locknut inside the enclosure for plain holes in increased
safety enclosures.
7. These stopping plugs can be used in clearance holes or tapped entries on increased safety or flameproof
enclosures as appropriate.
Adapter, Reducers & Nipples:
1. For Flameproof Ex “db” applications, only one adapter or reducer shall be used per cable entry.
2. The adaptors or reducers when used in flameproof applications must not be closed with a flameproof
stopping plug.
3. Its user’s responsibility to ensure the appropriate ingress protection level on the interfaces between
these devices and the associated enclosure.
4. When the adaptors and reducers are used for increased safety or dust protection with no thread seal
fitted the interface between the enclosure and the male thread and the female thread of the adaptor or
reducer are to be suitably sealed (in accordance with IEC 60079-14) to maintain the ingress protection
rating of the associated enclosure.
5. When the adaptors or reducers are used for increased safety or dust protection in threaded hole and the
thread seal is fitted the entry thread in the enclosure must be at right angles to the enclosure wall, the
female thread of the adaptor or reducer are to be suitably sealed, in accordance with IEC 60079-14, to
maintain the ingress protection rating of the associated enclosure.
6. When the adaptors or reducers are used for increased safety or dust protection in a plain hole, the hole
in the enclosure must be no greater than 0.7 mm greater than the male thread and the adaptor or
reducer must be secured with a locknut the female thread of the adaptor or reducer are to be suitably
sealed, in accordance with IEC 60079-14, to maintain the ingress protection rating of the associated
enclosure.
7. In the case of NPT connecting threads, the end-user must ensure that the necessary IP protection is
guaranteed; this can be done using a suitable thread sealing agent.