Dwg.38 B-AHU-19
Dwg.38 B-AHU-19
21
Order 21-298-0240
Position 38
B/AHU-19
Project PA-19 PEARL QATAR PROJECT (THE F
[Pcs]
Drawing 38 1
Date 15.03.2021
Client
Street
Supply air Size:9/4,5 Weight:208 [kg] Surface: 4,6 [m2] Velocity: 1,09 [m/s]
design FTH-K-L-VF Dimensions [mm] L: 1.677,5 W: 1.015 H: 588
Air volume [cfm] 965 Panel inside 50 [mm] galvanized steel 1,00 mm
external pressure drop [Pa] 150 Panel inside bottom galvanized steel
total pressure drop [Pa] 499 Guides galvanized steel
Specific fan power [w/m3/s] 931 Panel outside White A47SME 1,00 mm
FTH Bag Filter section with prefilter 610,0 [mm] 1,68 [m2] 58,00 [kg] 233 [Pa]
Manufacture AAF Cells pcs x size [mm] 1 x 592,0 x 287,0
Type RedPleat Coarse/50- tmax.=70°C
Class ISO 16890 Coarse 70%
Init.-Dim.-Fin. press. drop [Pa] 63-88-113
Airflow [cfm] 965
filter thickness [mm] 48,0 Galvanized frames ( front removable ) clean air side
Filter surface [m2] 0,74
Filter media type Synthetic
Final pressure drop acc. EN 13053
Manufacture AAF Filter surface [m2] 2,00
Type DriPak SX ePM2,5 65%-F tmax.=70°C Cells pcs x size [mm] 1 x 592,0 x 287,0 vert
Init.-Dim.-Fin. press. drop [Pa] 94-144-194
Class ISO 16890 ePM2.5 65%
Airflow [cfm] 965
Bag length [mm] 525,0
Filter energy class (EN 779:2012) E
Filter media type Synthetic+Ultra Final pressure drop acc. EN 13053
Standard hinged door ZIS Access side: right Dimensions [mm] 457,5 x 457,5 -[L]
( 300 ) 1 Pcs Door lock
Opening: 7 Full opening Dimensions [mm] 855,0 x 397,5 1 [Pa]
Inspection window
Illumination Protection IP44 Voltage [V] 230
Typ Bulkh.light Plast. LED with cabling Power [W] 8
( 172 ) 2 Pcs Inclined manometer 0...500 Pa
( 178 ) 2 set Pressure test points mounted
Order 21-298-0240
Drawing 38 Pieces 1
Position 38 Rev. Nr.
Unit B/AHU-19 Rev. date
VF Supply air-Plug fan 610,0 [mm] 1,68 [m2] 84,00 [kg] 6 [Pa]
Fan Comefri/TE 250 S4-2-0.75-IE2-C Motor TECUK__200207508050
Air volume [cfm] ( density: [kg/m³] 1,20 ) 965,00 Protection IP55
External press [Pa] 150 Insulation class F
ext. press. on intake / outlet [Pa] -75 / 75 Nominal power [kW] 0,750
dyn.press.drop [Pa] 48 Speed +-2% [1/min] 2.840
Tot. pressure [Pa] 499 Current +-5% [A] 1,75
Speed [1/min] 2.786 Voltage [V] 3x400 / 50
sound power [dB(A)] 83,5 Starting mode Suitable for freq. inv.
shaft capacity [kW] 0,378 Efficiency +-2 [%] 77
total fan efficiency [%] 60,1 Electrically absorbed power [kW] 0,49
max. nom. RPM [1/min] 3.544 operating point of FC [Hz] 49,7
Calibration faktor K_A [m²s/h] 47 maximal frequence [Hz] 62,4
Speed control: FC needed, not included! Motor efficiency class IEC60034: IE 2
Temperature increase fan section [gF] 1,60
Fan octave band sound power level Lokt / dB fan connection : Flexible canvas
Frq. [Hz] 63 125 250 500 1000 2000 4000 8000 Antivibration insulators Rubber insulators
Inlet 76,5 74,5 81,5 79,5 77,5 77,5 70,5 66,5 Pos. 1 1x25 X 20 55 Sh Typ Pos. 3 1x25 X 20 55 Sh Typ
Outlet 76,5 74,5 81,5 79,5 77,5 77,5 70,5 66,5 Pos. 2 1x25 X 20 55 Sh Typ Pos. 4 1x25 X 20 55 Sh Typ
( 22 ) 1 set Equipotential wire on insulator
( 41 ) 1 set Protection PTC 1 x M16
( 53 ) 1 set Gland for power cable 1 x M20
( 47 ) set Motor precabeled
Standard hinged door ZIS Access side: right Dimensions [mm] 457,5 x 457,5 -[R]
( 300 ) 1 Pcs Door lock
Opening: 7 Full opening Dimensions [mm] 855,0 x 397,5
( 25 ) Flexible canvas GI Temp. [gF] 176,00 Dimensions [mm] 855,0 x 397,5 x 140,0 1 [Pa]
( 22 ) 1 Pcs Equipotential wire 6 mm²
Inspection window
Illumination Protection IP44 Voltage [V] 230
Typ Bulkh.light Plast. LED with cabling Power [W] 8
Order 21-298-0240
Drawing 38 Pieces 1
Position 38 Rev. Nr.
Unit B/AHU-19 Rev. date
AHU sound levels ME 63 125 250 500 1000 2000 4000 8000 Tot db (A)
1> Airborne SWL over casing [db] 65,0 56,5 55,1 51,3 47,7 47,3 37,9 34,1 54,3
2> SWL at air inlet [db] 68,0 70,0 74,0 70,5 68,5 66,5 56,5 46,5 73,6
3> SWL at air outlet [db] 72,3 74,0 81,5 79,5 77,5 77,5 70,5 66,5 83,2
4> Sound press. for 1 [m] distance from AHU 50,7 42,2 40,8 37,0 33,4 33,0 23,6 20,0 40,0
5> Sound press. for 1 [m] distance from air inlet 60,6 63,3 68,0 65,0 63,2 61,3 51,6 41,6 68,1
6> Sound press. for 1 [m] distance from air outlet 64,9 67,3 75,5 74,0 72,2 72,3 65,6 61,6 77,9
Calculated sound pressure levels are indicative only. It corresponds to : free field hemispheric sound radiation from the unit
casing (4), the inlet (5) and the outlet (6) opening. Other sound sources, acoustic character of the room, air flow noise, duct
connections and vibrations can influence the sound pressure in dependence. In practice, therefore measured values on site
May be different from the calculated ones.
Order 21-298-0240
Drawing 38 Pieces 1
Position 38 Rev. Nr.
Unit B/AHU-19 Rev. date
Safety and unloading instructions supplied in printed form together with the AHU
Please download maintenance & service instructions with the following QR-Link
Euroclima participates in the ECP programme for: Air Handling Units (AHU). Check ongoing validity of certificate: www.eurovent-certification.com