Alternator
Alternator
124
323
324
30
198
347
37
28
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
CONTENTS
This manual applies to the alternator mounted on the genset. The latest addition to a whole new generation of products, this range benefits from the experience of one of the largest manufacturers in the world, using advanced technology and incorporating strict quality control. We would like to draw your attention to the contents of this maintenance manual. By following certain important instructions during installation, use and servicing of your alternator, you can look forward to many years of trouble-free operation.
CONTENTS
1 - RECEIPT
1.1 - Standards and safety measures ......... 1.2 - Checks ............................................... 1.3 - Identification ........................................ 1.4 - Storage ............................................... 3 3 3 3
4 - SERVICING - MAINTENANCE
4.1 - Safety measures ................................ 15 4.2 - Regular maintenance ......................... 15 4.3 - Fault detection .................................... 15 4.4 - Mechanical defects .............................. 16 4.5 - Electrical faults .................................... 16 4.6 - Dismantling, reassembly ...................... 18 4.7 - Installation / maintenance of PMG ....... 20 4.8 - Characteristics table ........................... 20
2 - TECHNICAL CHARACTERISTICS
2.1 - Electrical characteristics ..................... 4 2.2 - Mechanical characteristics .................. 4 2.3 - SHUNT field excitation system ............ 5 2.4 - AREP field excitation system .............. 6 2.5 - SHUNT + PMG .................................... 8
5 - SPARE PARTS
5.1 - First maintenance parts ....................... 21 5.2 - Technical support service .................... 21 5.3 - Exploded view, parts list ..................... 22
3 - INSTALLATION - COMMISSIONING
3.1 - Assembly ............................................ 3.2 - Inspection prior to first use ................. 3.3 - Electrical diagram ................................ 3.4 - Commissioning .................................... 3.5 - Setting up ........................................... 9 9 10 12 13
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
1 - RECEIPT
1.1 - Standards and Safety measures
Our alternators comply with most international standards and are compatible with: - the recommendations of the International Electro technical Commission IEC 34-1, (EN 60034). - the recommendations of the International Standards Organisation ISO 8528. - the European Community directive on Electromagnetic Compatibility (EMC) 89/336/EEC. - the European Community directives 73/23/EEC and 93/68/EEC (Low Voltage Directive). They are CE marked with regard to the LVD (Low Voltage Directive) in their role as a machine component. A declaration of incorporation can be supplied on request. Before using your generator for the first time, read with care the contents of this installation and maintenance manual, supplied with the machine. All operations performed on the generator should be undertaken by qualified personnel with specialist training in the commissioning, servicing and maintenance of electrical and mechanical machinery. This maintenance manual should be retained for the whole of the machine's life and be handed over with the contractual file. The various operations described in this manual are accompanied by recommendations or symbols to alert the user to the risk of accidents. It is vital that you understand and take notice of the different safety symbols opposite.
RECEIPT
1.3 - Identification
The alternator is identified by means of a nameplate (fig 1) fixed on the terminal box . Make sure that the nameplate on the machine conforms to your order. The machine name is defined according to various criteria (see below).
ISO 8528-3
IEC 34-1
BS 5000-PT3
NEMA MG1-22
VDE 0530
- Fig 1 -
1.4 - Storage
Whilst awaiting installation, the machines should be stored: - away from humidity: in conditions of relative humidity of more than 90%, the machine insulation can drop very rapidly to just above zero at around 100% ; monitor the state of the anti-rust protection on unpainted parts. For storage over an extended period, the machine can be placed in a sealed enclosure (heatshrunk plastic, for example) with dehydrating sachets inside, away from significant and frequent variations in temperature to avoid any condensation during storage.
WARNING
Safety symbol for an operation capable of damaging or destroying the machine or surrounding equipment.
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
2 - TECHNICAL CHARACTERISTICS
2.1 - Electrical characteristics
The 2000/3000 series alternators are machines without sliprings and revolving field brushes, wound as "2/3 pitch"; 12-wire, with class H insulation and a field excitation system available in either "SHUNT" fig 2 or "AREP" fig 3 or "PMG" fig 4 version (see sections 2.3, 2.4, 2.5). Interference suppression conforms with standard EN 55011, group 1, class B. 2.1.1 - Options - Stator temperature detection probes - Space heaters
CHARACTERISTICS
EXCITER Armature
MAIN FIELD
T1 T7
Varistor
T2 T8
T3 T9
5+
Field
6-
T4 T10
T5 T11
T6 T12
Series connection
R 230
T1 T7
T2 T8
T3 T9
Yellow
Green
Black
Red
5+
6-
T4 T10
T5 T11
T6 T12
R 438
- Fig 3 : System AREP with A.V.R. R 438 MAIN FIELD
Voltage sensing
EXCITER Armature
T1 T7
Varistor
T2 T8
T3 T9
PMG
5+
Field
6-
T4 T10
T5 T11
T6 T12
Parallel connection
R 438
- Fig 4 : System PMG with A.V.R. R 438 -
Voltage sensing
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
2.3 - SHUNT field excitation system
The alternator with Shunt field excitation is self-excited with a voltage regulator R 230 "fig 5". The regulator monitors the exciter excitation current as a function of the alternator output voltage. Very simple in design, the alternator with Shunt excitation has no sustaining shortcircuit capability.
Voltage
U/UN 100 % Knee-point
48 Hz 57.5 Hz
CHARACTERISTICS
50 Hz 60 Hz
R 230
50 Hz 60 Hz
Frequency
Hz
- Fig 7 -
- Fig 5 2.3.1 - R 230 regulator (see Fig 6) - Voltage regulation: around 0,5% - Voltage supply and sensing 85 to 139 V (50/60Hz) - Rapid response time (500 ms) for a transient voltage variation amplitude of 20% - Voltage setting P1 - Stability setting P2 - Power supply protected by 8 A fuse, slow-acting (tolerates 10 A for 10s). - Frequency: 50 Hz with strap ST3 - 60 Hz without strap ST3 - Factory set underspeed protection P3 (see fig 7)
Voltage sensing
4 x 5.8 x 50 mm 75 mm
2.3.3 - Working with A.V.R. R 448 As an option the 448 A.V.R. can replace the R 230 on shunt alternator in order to get the following functions : - Parallel operation between alternators (with current transformer) see fig 8. - Parallel operation with the mains (with current transformer and R 726 module). - 3 phase detection (R 731 module). - LAM function (integrated in the R448).
ST4
3 ph
50Hz
ST3
S1 S2
R 448
60Hz
140 mm
115 mm
110 0V E+ E-
1A
0V E- E+ Z2 X1 Z1 X2
L1 L2
P2
F1 slow-blow
fuse 250V 8 A
S2
5+
Voltage
L3
S1 P1
P1
Stability
P2
R 230
66Exciter field 5+
T11 T8 EXCITER FIELD SERIES CONNECTION ( 110V SUPPLY)
U V W
Underspeed
P3
ALTERNATOR
- Fig 8 For adjusting and fault detection refer to the section 4.5 of this manual (the function of R 438 and R 448 are the same).
ST4
Potentiometer for remote voltage adjustment
ST3
50Hz
Frequency
- Fig 6 -
60Hz
2.3.2 - R 230 regulator options: Potentiometer for remote voltage adjustment, 1000 / 0.5 W min : adjustment range 5%. - Remove strap ST4 .
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
2.4 - AREP field excitation system
With AREP excitation, the electronic A.V.R. R 438 (fig 9) is powered by two auxiliary windings which are independent of the voltage detection circuit. The first winding (X1,X2) has a voltage in proportion with the output voltage of the alternator (Shunt characteristic), the second (Z1,Z2) has a voltage in proportion with the stator current (compound characteristic: Booster effect). The power supply voltage is rectified and filtered before being used by the regulator monitoring transistor. This principle ensures that regulation is not affected by distortions generated by the load.
CHARACTERISTICS
- max. excitation current adjustment via P5: 4.5 to 10A - 50/60 Hz selection via strap ST3 2.4.2 - R 438 A.V.R. options - Current transformer for parallel operation - Remote voltage adjustment potentiometer : 470 , 0.5 W min: adjustment range 5% (range limited via internal voltage potentiometer P2). Remove ST4 to connect the potentiometer. A 1 k potentiometer can also be used to extend the adjustment range. - R 731 : detection of 3-phase voltage 200 to 500 V, compatible with parallel operation. Cut ST1 to connect the module; set the voltage via the module potentiometer. (The previous version module is not compatible with parallel operation). - R 726 module: 3 functions . P.F. regulation (2F) and voltage matching prior to pa ralleling with the mains (3 F).
R 438
- Fig 9 -
Frequency
ST3
50Hz
60Hz
F1/F2
WARNING
115 mm
P5
Excitation ceiling
P4
Under speed
P3
Stability
R438
ST9 P1
T.I.
SHUNT AREP PMG Quadrature droop
L3 (W)
P2
Voltage
ST1
Single phase detection 3 phase detection
L2(V)
340-520V
S2
R731
Option
Option
S1
170-260V 95-140V
ST4
Option
- Fig 10 -
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
2.4.3 - LAM characteristics (Fig 11)
The LAM system is integrated as standard in the R 438 regulator. - Role of the "LAM" (Load Adjustment Module): On load impact, the rotation speed of the generator set decreases. When it passes below the preset frequency threshold, the "LAM" causes the voltage to drop by approximately 15% and consequently the amount of active load applied is reduced by approximately 25%, until the speed reaches its rated value again. Hence the "LAM" can be used either to reduce the speed variation (frequency) and its duration for a given applied load, or to increase the applied load possible for one speed variation (turbo-charged engine). To avoid voltage oscillations, the trip threshold for the "LAM" function should be set approximately 2 Hz below the lowest frequency in steady state. - LAM: action eliminated by cutting strap ST5
CHARACTERISTICS
- 2 voltage recovery modes (normal / fast) selected via ST2 and adjusted via P3 (stability)
Voltage
ST5 cut
P2
Voltage
P4
0
ST3
48 or 58 Hz 50 or 60 Hz
fC
fN
- Fig 11 -
UN
0,9
Voltage
(U/f)
0,8
LAM
fN
0,9 0,8
Frequency
LAM
LAM
Power
Time (s)
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
2.5 - SHUNT + PMG field excitation system
WARNING For PMG running, the ST9 strap must be open. (from R438 LS C) This system is built with the fitting of a PMG (Permanent Magnet Generator) on a base SHUNT machine described on 2.3. The PMG is fitted at the rear end of the alternator and supplies a voltage to the A.V.R. R438. The PMG provides to the AVR constant power which is independant of the main stator load. The result is the alternator has a short circuit capability and a good immunity to distortions. By checking the voltage sensing circuit, the AVR adjust the excitation current required for maintaining the right voltage.
CHARACTERISTICS
2.5.2 - R 438 A.V.R. options - Same as section 2.4.2. 2.5.3 - LAM characteristics - Same as section 2.4.3.
2.5.1 - R 438 regulator (fig 13) WARNING Make sure that the ST9 strap is closed for AREP but open for PMG. - short-circuit current = 3 x IN for 10 seconds - standard power supply; PMG (X1, X2, Z2) - rated overload current: 8A - 10s - electronic protection (overload, short-circuit opening on voltage detection): excitation ceiling current for 10 seconds then return to approx. 1A The alternator must be stopped (or the power switched off) in order to reset the protection. - Fuse F1 on input side (X1, X2) - Fuse F2 on output side (E+, E-) - voltage detection: 5 VA isolated via transformer 0-110 V terminals = 95 to 140 V 0-220 V terminals = 170 to 260 V 0-380 V terminals = 340 to 520 V - voltage regulation 1% - rapid or normal response time via strap ST2 - voltage adjustment via potentiometer P2 other voltages via step down transformer - current detection: (parallel operation): C.T. 2.5 VA cl1, secondary 1A (Option) - quadrature droop adjustment via potentiometer P1 - underspeed protection (U/f) and LAM: frequency threshold adjustable via potentiometer P4 - max. excitation current adjustment via P5: 3,2 to 8A - 50/60 Hz selection via strap ST3
ST3
50Hz
60Hz
PMG
14
15
F1/F2
140 mm
115 mm
P5
Excitation ceiling
P4
Under speed
P3
Stability
R438
ST9 P1
T.I.
SHUNT AREP PMG Quadrature droop
L3 (W)
P2
Voltage
ST1
Single phase detection 3 phase detection
L2(V)
340-520V
S2
R731
Option
Option
S1
170-260V 95-140V
ST4
Option
- Fig 13 -
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
3 - INSTALLATION - COMMISSIONING
3.1 - Assembly
INSTALLATION
WARNING This alternator has been balanced with a 1/2 key. - Belt and pulley drive system Check that the shafts are parallel, the pulleys aligned, and that the belt tension is correct. The maximum permissible radial load at the middle of the shaft end is 520 da.N for a calculated service life "L10" of 20,000 hrs at 1800 min-1 or 3600 min-1 . Note: For special belt-pulley drive systems, please consult the factory. 3.1.3 - Location Ensure that the ambient temperature in the room where the alternator is placed cannot exceed 104 F for standard power ratings (for temperatures above 104 F, apply a derating coefficient). Fresh air, free from damp and dust, must be able to circulate freely around the air input louvres on the opposite side from the coupling. It is essential to prevent not only the recycling of hot air from the machine or engine, but also exhaust fumes.
All mechanical handling operations must be undertaken using approved equipment. While being handled, the machine should remain horizontal (when travelling bar removed). 3.1.1 - Handling The generously-sized lifting rings are for handling the alternator alone. They must not be used to lift the genset. Choose a lifting system which respects the positionning of the rings (see fig 14).
- Fig 14 3.1.2 - Coupling 3.1.2.1 - Single bearing alternator Before coupling to the prime mover, check that both are compatible by: - Undertaking a torsional analysis of the transmission. - Checking the dimensions of the flywheel and its housing, the flange, coupling discs and offset. WARNING When coupling the alternator to the prime mover, the holes of the coupling discs should be aligned with the flywheel holes by cranking the engine. Do not use the alternator fan to turn the rotor. Tighten the coupling discs screws to the recommended torque (see section 4.6.2) and check that there is lateral play on the crankshaft. 3.1.2.2 - Two-bearing alternator - Semi-flexible coupling Careful alignement of the machines by measuring the concentricity and parallelism of the two parts of the coupling is recommended, the difference bet ween the teadings should not exceed the specified values (say 0.1 mm).
Under no circumstances should an alternator, new or otherwise, be operated if the isolation is less than 1 megohm for the stator and 100,000 ohms for the other windings. There are two possible methods for restoring the above minimum values. a) Dry out the machine for 24 hours in a drying oven at a temperature of approximately 230 F. b) Blow hot air into the air input, having made sure that the machine is rotating with the exciter field disconnected. c) Run in short-circuit mode (disconnect the AVR) - Short-circuit the output phases using connections capable of supporting the rated current (try not to exceed 6 A/mm2). - Insert a clamp ammeter to monitor the current passing through the short-circuit connections. - Connect a 48 Volt battery in series with a rheostat of approximately 10 ohms (50 Watts), to the exciter field terminals, respecting the polarity. - Open fully all the alternator orifices. - Run the alternator at rated speed . Adjust the exciter field current using the rheostat to obtain the rated output current in the short-circuit connections. Note: Prolonged standstill: In order to avoid these problems, we recommend the use of space heaters, as well as turning over the machine from time to time. Space heaters are only really effective if they are working continuously while the machine is stopped.
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
3.2.2 - Physical and visual checks Before starting the machine for the first time, check that: - the fixing bolts on the feet are tight - the cooling air is drawn in freely - the protective louvres and housing are correctly in place - the standard direction of rotation is clockwise as seen from the shaft end (phase rotation in order 1 - 2 - 3). For anti-clockwise rotation, swap 2 and 3. - the winding connection corresponds to the site operating voltage (see section 3.3)
INSTALLATION
Any intervention on the alternator terminals during reconnection or checks should be performed with the machine stopped.
Connection codes
L.L voltage
Winding
Factory connection
A
3 phase
T1
L1(U)
T7
50 Hz
190 - 208 220 - 230
60 Hz
190 - 240
T5
T6
6
N
T2
N
T4
7 8
190 - 208
L3(W)
T3
T4 T12 T9 T6
T10 T5 T11
T8 T2 T7 T1
L2(V) L1(U)
L3(W)
T3
T8
L2(V)
R 230 voltage detection : 0 => (T8) / 110 V => (T11) R 438 voltage detection : 0 => (T3) / 220 V => (T2) Winding
NDE
D
3 phase
T1
L1(U)
50 Hz
380 - 415 440 - 460
60 Hz
380 - 480
T4 T7
6
N
T10
N
L3(W) L2(V) L1(U) NDE
7 8
380 - 416
T12 T9 T3 T6 T11 T8 T5 T2
L3(W)
L2(V)
R 230 voltage detection : 0 => (T8) / 110 V => (T11) R 438 voltage detection : 0 => (T3) / 380 V => (T2) Winding
FF
1 phase
T2 T6 T3 T11 T1 T4 T7 T8 T12
50 Hz
220 - 240 250 - 260 200
60 Hz
220 - 240
T11 T7
6 7
T9 T10
M
T3
220 - 240
T9 T10 T8
L
T6 T2
T5
8
L
R 230 voltage detection : 0 => (T1) / 110 V => (T4) R 438 voltage detection : 0 => (T10) / 220 V => (T1) Winding
T12
T5 T1
NDE
F
1 phase or 3 phase
T3 T12 T9 T6
L1(U)
T1 T4 T7 T10 T11 T8 T5 T2
50 Hz
220 - 240 250 - 260 200
60 Hz
220 - 240
T11 T6 T9 T5 T8 T4 T7 T3
6 7 8
L2(V) L
220 - 240
L3(W) L2(V)
T10 T2 T12 T1
L3(W) L
R 230 voltage detection : 0 => (T8) / 110 V => (T11) R 438 voltage detection : 0 => (T3) / 220 V => (T2) - Fig 15 -
L1(U) NDE
10
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
INSTALLATION
Connection codes
L.L voltage
Winding
Factory connection
G
1 PH
T6 T12 T7
50 Hz
220 - 240 250 - 260 200
60 Hz
220 - 240
T11 T10
T5
6
T1 T4
M
T4
7
T2 T5 T11 T8
220 - 240
T9 T3 T8 T12 T7 T2 T6 T1
L L
T3 T10 T9
8
L
R 230 voltage detection : 0 => (T8) / 110 V => (T11) R 438 voltage detection : 0 => (T3) / 220 V => (T2) Winding
AR
B
1 phase or 3 phase
T9 T12
L1(V)
50 Hz
110 - 120 120 - 130 -
60 Hz
120
T11
T5
L
T3 T9 T10 T8 T12 T7
6
T1 T6 T7 T4 T10
L3(W)
7 8
L2(V) L
110 - 120
T3 T5 T11 T2 T8
T4 T2 T6 T1
L2(V) L1(U) AR
L3(W) L
R 230 voltage detection : 0 => (T8) / 110 V => (T11) R 438 voltage detection : 0 => (T3) / 110 V => (T2)
WARNING : Connection (B) is not possible with a standard machine in serie 3000.
- Fig 16 3.3.1 - Exciter field connection (fig 17)
Black
5+ 66-
Black
R 230 R 448
- Fig 17 -
5+ 6+ 6+
Red
Red
R 438
Voltage potentiometer
ST4
Voltage adjustment via remote potentiometer .
- Fig 18 -
11
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
3.3.2 - Connection checks
INSTALLATION
3.4 - Commissioning
Electrical installations must comply with the current legislation in force in the country of use. Check that: - the differential circuit-breaker conforms to legislation on protection of personnel, in force in the country of use, and has been correctly installed on the alternator power output as close as possible to the alternator. (Disconnect the blue wire of the R 791 interference suppression module linking the neutral). - any protective devices in place have not tripped, - if there is an external regulator, the connections between the alternator and the cubicle are made in accordance with the connection diagram. - there is no short-circuit between phase or phase-neutral between the alternator output terminals and the generator set control cabinet (part of the circuit not protected by circuit-breakers or cubicle relays) - the machine should be connected with the terminal lugs on top of one another as shown in the terminal connection diagrams (see fig 19).
The machine can only be started up and used if the installation is in accordance with the instructions and advice defined in this manual. The machine is tested and set at the factory. When first used with no load, make sure that the drive speed is correct and stable (see the nameplate). On application of the load, the machine should maintain its rated speed and voltage; however, in the event of abnormal operation, the machine setting can be altered (follow the adjustment procedure in section 3.5). If the machine still operates incorrectly, the cause of the malfunction must be located (see section 4.4) .
3.5 - Setting up
The various adjustments during tests must be made by a qualified engineer. Take care that the drive speed specified on the nameplate is reached before commencing adjustment. After operational testing, replace all access panels or covers. The A.V.R. is used to make any adjustments to the machine. 3.5.1 - R 230 adjustments (Shunt system) Initial potentiometer settings
- Fig 19 -
R 230
3.3.3 - Electrical checks on the A.V.R. - Check that all connections have been made properly as shown in the attached connection diagram. - Check that the frequency selection strap "ST3" is on the correct frequency setting. - Check whether strap ST4 or the remote adjustment potentiometer have been connected. - Optional operating modes (R 438) - Strap ST1: cut to connect the R 731 3-phase detection module. - Strap ST2: cut for rapid response time. - Strap ST5: cut to suppress the function
- Potentiometer P1 (AVR voltage adjustment): fully anti clockwise. - Remote voltage adjustment potentiometer: middle Run the alternator at its rated speed: if the voltage does not increase, the magnetic circuit should be remagnetized (see section 4.5). - Turn the AVR voltage adjustment potentiometer P1 slowly until the output voltage rated value is obtai ned. - Adjust the stability using P2. - Sealed potentiometer P3 is factory set at 48 Hz for 50 Hz and 57.5 Hz for 60 Hz.
12
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
3.5.2 - R 438 adjustments (AREP or PMG system) WARNING Make sure that the ST9 strap is closed if AREP or open if PMG. Hz for 50 Hz, or 58 for 60 Hz. h) Adjust the output voltage to the desired value using P2. - rated voltage UN for solo operation (eg. 400 V) - or UN + 2 to 4% for parallel operation with C.T. (eg. 410V -) If the voltage oscillates, use P3 to make adjustments (try both directions) observing the voltage between E+ and E- (approx. 10V D.C.). The best response times are obtained at the limit of the instability. If no stable position can be obtained, try cutting or replacing the ST2 strap (normal /rapid). i) Check LAM operation : ST5 closed j)Turn potentiometer P4 slowly anti-clockwise until there is a significant voltage drop (approx. 15 %). k) Vary the frequency (speed) of both parts between 48 or 58 Hz according to the operating frequency, and check the change in voltage previously observed (~ 15%). l) Readjust the speed of the unit to its rated no-load value. - Adjustments in parallel operation
INSTALLATION
R 438
a) Initial potentiometer settings (see table below) - remote voltage adjustment potentiometer: centre (ST4 strap removed).
Action
Voltage
minimum fully CCW
Factory adjust.
400V - 50 Hz ( 0 - 380 V) Not adjusted ( middle) ST3 on 50 Hz
(factory=48 Hz)
Pot.
P2 P3
Before any intervention on the alternator, make sure that the speed quadrature droop is identical for all engine. m) Preset for parallel operation (with C.T. connected to S1, S2 of connector J2) - potentiometer P1 (quadrature droop) in centre position Apply the rated load (P.F. = 0.8 inductive). The voltage should drop by 2 to 3 %. If it increases, swap the 2 incoming wires of the C.T. secondary. n) The no-load voltages should be identical for all the alternators intended to run in parallel. - Couple the machines in parallel. - By adjusting the speed, try to obtain 0 Kw power exchange. - By altering the voltage setting P2 or Rhe on one of the machines, try to cancel (or minimise) the current circu lating between the machines. - From now on, do not touch the voltage settings. o) Apply the available load (the setting is only correct if a reactive load is available) - By altering the speed, equalize the KW (or divide the rated power of the units proportionally). - By altering the quadrature droop potentiometer P1, equalize or divide the currents.
ST3 on 60 Hz
(factory=58 Hz)
P4
P1
10 A maximum
P5
b) Install a D.C. analogue voltmeter (needle dial) cal. 50V on terminals E+, E- and an A.C. voltmeter cal. 300 500 or 1000V on the alternator output terminals. c) Make sure that the ST3 strap is positioned on the desired frequency (50 or 60 Hz). d) Voltage potentiometer P2 at minimum, fully to anticlockwise. e) Turn the V/Hz potentiometer P4, fully to clockwise. f) Stability potentiometer P3 approximately 1/3 of travel anti-clockwise. g) Start the engine and set its speed to a frequency of 48
13
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
3.5.2 .2 - Max. excitation adjustment (excitation ceiling)
ST3
INSTALLATION
Max. excitation
P5 P4 P3
50Hz 60Hz
48 V
R 438
Voltage
P2
S1 S2 ST4
110/220/380V
- Fig 20 - quadrature droop adjustment of the current limit, potentiometer P5 (factory setting: 7.5 A, fuse rating : 6.3A - 10 seconds) Fig 20. The factory setting corresponds to that of the excitation current required to obtain a 3-phase short-circuit current of approximately 3 x IN at 50 Hz for industrial power, unless otherwise specified.(*) It is possible to reduce the maximum excitation level by a static method which is safer for the alternator and the network. Disconnect power supply wires X1,X2 and Z1,Z2, and the sensing leads (0-110V-220V-380V) on the alternator. Connect the mains power supply (200-240V) as indicated (X1,X2 : 48V). Install a 10A D.C. ammeter in series with the exciter field. Turn P5 fully C.C.W. to activate the power supply. If there is no output current from the A.V.R., turn potentiometer P2 (voltage) C.W. until the ammeter indicates a stable current. Switch the power supply off, then on again, turn P5 C.W until the required max. current is obtained (no more than 8 A). Checking the internal protection: Open switch (D): the excitation current should increase to its preset ceiling, remain at that level for about 10 seconds and then drop to below 1A. To reset, switch off the power supply by opening switch (A). Note: After setting the excitation ceiling as described, adjust the voltage again (see section 3.5.2.) (*): A short-circuit current of 3 x IN is a legal requirement in some countries so as to offer selective protection. 3.5.2 .3 - Special type of use (AREP or PMG) - Field de-energizing (fig 21)
X2 Z1 X1 Z2 E+
R 438
- Fig 21 -
The exciter is switched off by disconnecting the AVR power supply (1 wire on each auxiliary winding) contact rating 10A - 250V A.C. Connection is identical for resetting the AVR internal protection. - Field forcing (fig 22)
X2 Z1 X1 Z2 E+ E-
J1
(400V - 10A)
Diode
Battery (B Volt)
R 438
B Volt
Forced excitation
t
- Fig 22 Time
Applications Guaranteed voltage build up Parallel operation, de-energized Parallel operation, at standstill Battery starting Sustained voltage on over load
14
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
4 - SERVICING - MAINTENANCE 4.1 - Safety measures
SERVICING
Servicing or troubleshooting must be carried out strictly in accordance with instructions so as to avoid the risk of accidents and to maintain the machine in its original state.
The isolating components and the impregnation system are not at risk of damage from solvents (see the list of authorised products above). Avoid letting the cleaning product run into the slots. Apply the product with a brush, sponging frequently to avoid accumulation in the housing. Dry the winding with a dry cloth. Let any traces evaporate before reassembling the machine. After cleaning the alternator it is essential to check the isolation of the windings (see sections 3.2. and 4.8). 4.2.5 Mechanical maintenance WARNING
All such operations performed on the alternator should be undertaken by personnel with training in commissioning, servicing and maintenance of electrical and mechanical components. Before any intervention on the machine, ensure that it cannot be started by a manual or automatic system and that you have understood the operating principles of the system.
Water and/or Pressure wash are strictly prohibited. Any problems caused by such treatement are not covered by our warranty. Degreasing : Use a brush and detergent (adapted to paint). Dusting : Use an air gun. If a machine is fitted with air inlet and outlet filters, in order to ensure correct ventilation, a regular cleaning of the filters must be done according to the environment conditions. After cleaning the alternator, it is essential to check the insulation of the windings (see sections 3.2. and 4.8).
15
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
4.4 - Mechanical defects
Fault
Bearing defect Excessive overheating of one or both bearings (temp of bearings over 176 F)(With of without abnormal bearing noise)
SERVICING
Action
- If the bearing has turned blue or if the grease has turned black , change the bearing. - Bearing race badly locked (moving in its housing) -Bracket misalignment.
Overheating
Vibration problem
Excessive overheating of alternator frame - Air flow (Inlet - outlet) partially clogged or hot air is being recycled either (temperature rise of more than 104 C abo- from alternator or prime mover ve ambient) - Aternator is functionning at too high a voltage (over 105 % of rated voltage on load). - Alternator overloaded. Too much vibration Misalignment (coupling) - Defective mounting or play in coupling - Incorrect balancing of shaft (Engine - Alternator) Excessive vibration and humming noise Three phase alternator is single phase loaded in excess of acceptable level. coming from the alternator - Short-circuit in the alternator stator - System short-circuit - Mis paralleling Possible consequences (according to the seriousness of the above faults): Alternator damaged by a significant impact - Broken or damaged coupling. which is followed by humming and vibration - Broken or bent shaft end. - Shifting and short circuit of main field rotor. - Fractured fan or coming loose on shaft. - Blown up rotating diodes, or and A.V.R.
Abnormal noises
The alternator builds up and voltage is correct when the battery is removed No voltage at Connect a battery of 4 to 12 The alternator builds up but voltage no load or start volts to terminals E+ or E- does not reach nominal value when up respecting the polarity on the battery is removed the A.V.R.for 2 to 3 seconds The alternator builds up but voltage collapses when the battery is removed
Correct speed
Speed too low Voltage too high Voltage oscillations Adjust potentiometer voltage
No adjustment of voltage
Adjust the stability potentio- If no effect : change recovery mode normal / rapid (ST2) meter on A.V.R.
Voltage correct on no load too Run on no-load and check Voltage between E+ and E- Faulty rotating diodes faulty low on load (*) voltage between E+ and E- SHUNT > 30 V - AREP / PMG > 15V - Short-circuit in the main field. Check resistance. - Faulty exciter armature. Check resistance. (*) Warning: During single-phase operation, check that the sensing wires from the AVR are connected to the correct output terminals. Voltage colCheck the AVR, the surge The output voltage does not return - Exciter winding open circuit the rated value . lapses during suppressor, the rotating - Faulty exciter armature normal opera- diodes and replace any de- Faulty AVR tion (**) fective part - Main field rotor winding open circuit or short circuit (**) Warning: The AVR internal protection may cut in (overload lost connection, short circuit)
Voltage between E+ and E- (DC) - Check speed (or LAM on R 438 set too high) SHUNT < 20 V - AREP / PMG < 10V
16
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
4.5.1 - Checking the windings You can check the winding insulation making a high voltage test. In this case, you must disconnect all AVR wires. WARNING Damages occuring to avr in such conditions will not be taken into account in a warranty claim. 4.5.2 - Checking the diode bridge (Fig 23)
+
SERVICING
~ ~ ~
C C C
A A
A +
+
A diode in a good condition enables the current to flow in only one direction, from anode to cathode.
~ ~ ~
A A
- Fig 23 -
4.5.3 - Checking the windings and rotating diodes using separate excitation
Assembly B: Connect a "Variac" variable power supply and a diode bridge on both exciter field wires (5+) and (6-). These two systems should have characteristics which are compatible with the exciter field excitation power of the machine (see the nameplate). 3) Run the unit at its rated speed. 4) Gradually increase the exciter field current by adjusting the rheostat or the variac and measure the output voltages on L1 - L2 - L3, checking the excitation voltage and current at no load and at full load (see machine nameplate or ask for the factory test report). When the output voltage is at its rated value and balanced within 1%, for the rated excitation level and rated speed, then the machine is in good working order. The fault must therefore come from the A.V.R. or its associated wiring (i.e. sensing, auxiliary windings)
During this procedure, make sure that the alternator is disconnected from any external load and inspect the terminal box to check that the connections are fully tightened. 1) Stop the unit, disconnect and isolate the AVR wires. 2) There are are two ways of carrying out a separate excitation (see fig 24.). Assembly A: Connect a 12 V battery in series with a rheostat of approximately 50 ohms - 300 W and a diode on both exciter field wires (5+) and (6-).
6 - Exciter field 5 +
Diode 1A Rh. 50 -300W
40
30
Variac
50
60
70
6 - Exciter field
+
5+
20
80
10
90
12V battery
ASSEMBLY A
- Fig 24 -
100
AC 220V
DC 12V
ASSEMBLY B
17
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
4.6 - Dismantling, reassembly (see section 5.5.1. & 5.5.2.)
SERVICING
During the warranty period, this operation should only be carried out in a LEROY SOMER approved workshop or in our factory, otherwise the warranty may be invalidated. The machine must be horizontal when handled (when travelling bar removed). See fig 25.
- Fig 25 -
screw
M4 M6 M6 M5 M 12 M 14 M6 M 12 M 16 M6 M6 M6 M10
Torque N.m 4 Nm 10 Nm 5 Nm 4 Nm 57 Nm 90 Nm 5 Nm 110 Nm 250 Nm 5 Nm 5 Nm 5 Nm 20Nm 4.6.5.2- Reassembly - Heat the inner slipring of a new bearing by induction or in a drying oven at 80 C (do not use an oil bath) and fit it to the machine. - Place the preloading wavy washer [79] in the flange and fit a new O ring seal [349]. Refit the NDE bracket (see fig 27) and pass the bundle of wires between the top bars of the flange. - Replace the fixing clamps on the cables and the R 791 module.
- Fig 26 -
18
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
- Refit the air intake louvre [51]. - Replace the terminal box lid [48].
SERVICING
- Fig 27 -
- Fig 28 -
4.6.7.2 - Reassembly - Follow the dismantling procedure in reverse order. Take care not to knock the windings when refitting the rotor in the stator. - If you replace the fan, respect the assembly guide (fig 29). Use a tube and a screw.
- Fig 29 -
Follow the procedure for reassembling the bearings (see section 4.6.5.2 and 4.6.6.2).
19
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
4.7 -Installation and maintenance of PMG
The PMG reference for 2000 and 3000 series is PMG 1 4.7.1 Mechanical fitting It is pointing out the following : - A adaptation shaft (centring of the rotor PMG on alternator shaft. - A tie rod with screw and washer. - A rotor with 16 magnets. - The housing stator set + the plastic tube. - The end plate with 4 CBLXS M5 screws. - The fixation of this set with 4 HM6 screws. The PMG mechanical assembly order is as follows : 1) Remove the end plate [297] and the plastic obturator of the bracket and top box. 2) Assemble the housing stator set [290] by tightening the 4 HM6 screws (Torque : 8,3 Nm). 3) Put "Loctite" on the screw [295] and tighten it in the shaft. 4) Put the rotor with magnets on the adaptation shaft and assemble the set using the two M10 holes in order to lodge two threaded rods to guide the rotor when inserting in the stator (mind the magnetic attraction strength. 5) Put the end washer [296] 6) Block the set with the nut M10 (Torque : 30 Nm) . 7) Put the end plate [297] and tighten the screws CBLX 5 M5 (Torque : 5 Nm) 8) Link up the plastic tube to the top box using the end link 9) Connect the PMG leads to the AVR (see section 2.5 and 4.7.2).
SERVICING
B
0,155 1,35 19,5 0,23
D
0,128 1,41 19,5 0,23
H
0,0836 1,76 19,5 0,23
J
0,0631 1,96 19,5 0,23
SHUNT 2000 : field excitation current i exc (A) Symbols : "i exc": excitation current of the exciter field.
2014 No-load
At rated load
B
0,5 1,6
D
0,5 1,7
H
0,4 1,5
J
0,5 1,6
For 60Hz machines the "i exc" values are approximately 5 to 10 % less. AREP 2000 :resistances at 20C ()
4.7.2 Electrical connection In case of a new connection in order to upgrade a shunt machine, - Disconnect the wires of R 230A. - Dismount the R 230 A. - Remove the voltage sensing wires 2 & 3 from terminals T8 and T11 and connect them on terminal T2 (wire 2) and T3 (wire 3). - Fit the AVR plate (2 screws HM6 tightened at 10 N.m) - Be sure that the ST9 strap is open. - Connect the 3 PMG wires (14/15/16), the 2 exciter field wires (5/6) avel the 2 voltage sensing wires (2/3) into the AVR according the wiring diagram enclosed with the PMG. Change the connection of the connecting located on the back panel of the terminal box (cf. fig 17 p 11). Typical electrical values of the PMG Stator resistance phase to phase 20C : 0,7 Voltage at no load : 73 V
B
0,155 1,35 0,32 0,52 4,9 0,23
D
0,128 1,41 0,29 0,5 4,9 0,23
H
0,0836 1,76 0,26 0,44 4,9 0,23
J
0,0631 1,96 0,21 0,4 4,9 0,23
Field Armature
AREP or PMG 2000 : field excitation current i exc (A) Symbols : "i exc": excitation current of the exciter field.
2024 No-load
At rated load
B
1 3,2
D
1 3,4
H
0,9 3
J
1 3,2
For 60Hz machines the "i exc" values are approximately 5 to 10 % less.
20
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
SHUNT 3000 :resistances at 20C ()
SPARE PARTS
B
0,55 2,37 19,5 0,5
F
0,0235 3,32 19,5 0,5
H
0,0186 3,66 19,5 0,5
B
0,055 2,37 0,28 0,44 4,9 0,5
F
0,0235 3,32 0,17 0,28 4,9 0,5
H
0,0186 3,66 0,16 0,21 4,9 0,5
SHUNT 3000 : field excitation current i exc (A) Symbols : "i exc": excitation current of the exciter field.
Field Armature
3014 No-load
At rated load
B
0,5 2
F
0,6 1,9
H
0,6 2
AREP 3000 : field excitation current i exc (A) Symbols : "i exc": excitation current of the exciter field.
3024 No-load
B
1 4
F
1,15 3,7
H
1,2 4
For 60Hz machines the "i exc" values are approximately 5 to 10 % less.
At rated load
For 60Hz machines the "i exc" values are approximately 5 to 10 % less.
5 - SPARE PARTS
5.1 - First maintenance parts
Emergency repair kits are available as an option. They contain the following items: No. Description Emergency Kit (Shunt) 198 Voltage regulator (AVR) 343 Diode bridge assembly 347 Surge suppressor AVR fuse Emergency Kit (AREP/MPG) 198 Voltage regulator (AVR) 343 Diode bridge assembly 347 Surge suppressor AVR fuse Other parts 60 70 D.E. bearing N.D.E. bearing 1 1 6312 2RS/C3 6307 2RS/C3 922-111 6315 2RS/C3 6309 2RS/C3 WARNING Part numbers should be identified from the exploded views and their description in the parts list. Our extensive network of "service stations" can dispatch the necessary parts without delay. To ensure correct operation and the safety of our machines, we recommend the use of original manufacture spare parts. In the event of failure to comply with this advice, the manufacturer cannot be held responsible for any damage. 922-232 1 1 1 2 R 438 LSA 432 9 03/04 LSA 432 1 13 250 V - 8 A / slow Qty 1 1 1 1 2 R 230 LSA 432 9 03/04 LSA 432 1 13 250 V - 8 A / slow
L 2000
Part number 922-216 922-197 922-230 922-231 922-222 922-217 922-045 922-230 922-231 922-222
L 3000
R 230 LSA 432 9 03/04 LSA 432 1 13 250 V - 8 A / slow R 438 LSA 432 9 03/04 LSA 432 1 13 250 V - 8 A / slow
Part number 922-218 922-197 922-230 922-231 922-222 922-219 922-045 922-230 922-231 922-222
21
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
5.3 - Exploded view, parts list.
5.3.1 - Single bearing (fig 30)
320
49 48 41 347 217 47 59 36 98
SPARE PARTS
325
16
15
124
198
343 37 28 1
107
100
70
349
79
91
90
51
30 324 322 15
33
323
- Fig 30 -
290
291
292
293
294
295
296
297
PMG option
Description
No.
1 4 15 16 28 30 33 36 37 41 47 48 49 51 59 70 79 90 91 98 100
Nbr.
1 1 1 6 1 1 1 1 4 1 1 1 20 1 3 1 1 1 4 3 1
Description
Stator assembly Rotor assembly Fan Fan fixing screw Earth terminal DE flange Air outlet louvre N.D.E. bracket Tie rod D.E. terminal box N.D.E. terminal box Terminal box lid Terminal box fixing screw Air intake louvre Inspection door NDE bearing Preloading wavy washer Wound exciter field Field fixing screw Corner plate Exciter armature
No.
107 124 198 207 217 290 291 292 293 294 295 296 297 320 322 323 324 325 343 347 349
Nbr.
1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1
Support diode assembly Terminal plate Regulator (AVR) Rubber Auxiliary terminal plate Housing Adaptation shaft Rotor magnets Stator Fixing screw Tie rod Washer + nut End plate Hub Coupling disc Fixing screw Clamping washer Spacer shim Diode bridge assembly Surge suppressor O ring seal
22
ALTERNATOR maintenance
2000 / 3000 Series 4 Pole
5.3.2 - Two bearing (fig 31)
49 320 15 62 68 16 48 41 347 124 217 47 59 36 98
SPARE PARTS
198
37
28
343
107
100
70
349
79
91
90
51
30 68 67 410 60 63 15
33
292
293
294
295
296
297
PMG option
Description
No.
1 4 15 16 28 30 33 36 37 41 47 48 49 51 59 60 62 63 67 68 70 79
Nbr.
1 1 1 6 1 1 1 1 4 1 1 1 20 1 3 1 2 or 4 1 1 1 1 1
Description
Stator assembly Rotor assembly Fan Fan fixing screw Earth terminal DE flange Air outlet louvre N.D.E. bracket Tie rod D.E. terminal box N.D.E. terminal box Terminal box lid Terminal box fixing screw Air intake louvre Inspection door DE bearing Cap fixing screw Washer Circlips Bearing cap NDE bearing Preloading wavy washer
No.
90 91 100 107 124 198 207 217 290 291 292 293 294 295 296 297 320 343 347 349 410
Nbr.
1 4 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1
Wound exciter field Field fixing screw Exciter armature Rotating diode support Terminal plate Regulator (AVR) Rubber Auxiliary terminal plate Housing Adaptation shaft Rotor magnets Stator Fixing screw Tie rod Washer + nut End plate Hub Diode bridge assembly Surge suppressor O ring seal DE flange
23