THAMAN
THAMAN
On
MRS. THAMAN
Residential Building
Ward No.-3, Suddhodhan Rural Municipality, Rupandehi, Nepal
Submitted To:
SUDDHODHAN RURAL mUNICIPALITY office
Rupandehi, Nepal
For:
PUSKAR engineering CONSULTANT
Ward No.-3
Suddhodhan Rural Municipality, Rupandehi, Nepal
Prepared by:
Er. Praveen Rajbhandari
Structural Engineer
NEC Regd. No.- 12025 Civil ‘A’
December, 2022
TO WHOM IT MAY CONCERN
This report comprises the summary of the structural analysis & design of residential
building. The report consists of the design procedure adopted, assumptions made and
input and output from the design and analysis. It is assumed that the Client will
completely follow the Structural Design specified in the form of Design Drawings
attached in the report.
The Designer will not be responsible if any alteration to the structural system and
configuration made by Client without consultation and permission from the Designer.
The design calculations and derivations are limited to only a minimum to let the
concerned people know the methodology adopted. However, the calculations may be
provided to the Client or the concerned Authority upon request.
…………………………….
Er. Praveen Rajbhandari
NEC NO: 12025 Civil “A”
(STRUCTURAL ENGINEER)
Table of Contents
1 Introduction..................................................................................................................... 1
1.1 General ............................................................................................................................ 1
1.2 Salient Features .............................................................................................................. 1
1.2.1 Project Information......................................................................................................... 1
1.2.2 Building Features ........................................................................................................... 1
1.2.3 Site Condition .................................................................................................................. 2
1.3 Analysis Technology and Methodology ......................................................................... 2
1.4 Codes and Standard used ................................................................................................ 4
1.5 Software Used .................................................................................................................. 4
2 Analysis ........................................................................................................................... 4
2.1 Material properties .......................................................................................................... 4
2.1.1 Concrete........................................................................................................................... 4
2.1.2 Reinforcement Steel ........................................................................................................ 5
2.2 Section Properties ........................................................................................................... 5
2.3 Loadings .......................................................................................................................... 5
2.3.1 Load Cases....................................................................................................................... 5
2.4 Estimation of Load .......................................................................................................... 7
2.4.1 Unit Weight (Dead Load) ................................................................................................ 7
2.4.2 Live Load ........................................................................................................................... 9
2.4.3 Seismic Load ................................................................................................................. 11
3 Analysis Output ............................................................................................................. 11
3.1 Seismic Coefficient Method .......................................................................................... 11
3.2 Story Drift ...................................................................................................................... 12
3.3 Modal time period and mass participation ................................................................... 14
3.4 Force Diagram .............................................................................................................. 15
3.4.1 Axial Force Diagram .................................................................................................... 15
3.4.2 Shear Force Diagram ................................................................................................... 16
3.4.3 Moment Diagram ............................................................................................................ 17
3.5 Joint Reactions .............................................................................................................. 18
4 Design of Structural Members...................................................................................... 19
4.1 Design Input and Output .............................................................................................. 19
4.1.1 Section Input Diagram.................................................................................................. 19
4.1.2 Design Output Diagram ................................................................................................ 21
4.2 Design of Slab .................................................................................................................... 24
4.3 Design of Beam and Column............................................................................................. 26
4.3.1 Sample Beam Design ...................................................................................................... 26
4.3.2 Sample Column Design................................................................................................... 28
4.4 Footing Design from excel (sample) ................................................................................. 30
4.4 Staircase Design from excel (sample) ............................................................................... 36
5 Summary of the Analysis and Design .......................................................................... 37
5.1 COLUMN OUTPUT: ......................................................................................................... 37
5.2 BEAM OUTPUT: ............................................................................................................... 38
5.3 FOOTING OUTPUT ......................................................................................................... 39
5.4 SLAB REINFORCEMENT: SLAB THICKNESS – 125mm ............................................ 39
5.5 CANTILEVER SLAB REINFORCEMENT: SLAB THICKNESS – 125mm ................. 39
5.6 Staircase Bar: WAIST SLAB THICKNESS – 150mm...................................................... 40
Required sizes of structure were adopted ................................................................................ 40
6 References ..................................................................................................................... 41
List of Figure
Figure 1: First Floor Plan of Building ............................................................................ 2
Figure 2: 3D Modelling ................................................................................................. 3
Figure 3: Frame Load (Wall Load) in 3D .................................................................... 8
Figure 4: Frame Load (Wall Load) in Grid 2-2 ........................................................... 9
Figure 5: Area Load (live load<=3) First Floor ........................................................... 10
Figure 6: Floor Finish Load (Dead Load) on First Floor ............................................. 10
Figure 7: 1.5(DL+LL)- Axial Force diagram in Grid 2-2 ............................................ 15
Figure 8: 1.5(DL+LL)- Axial Force diagram in Grid B-B .......................................... 15
Figure 9: Envelope -Shear Force diagram in Grid 2-2................................................. 16
Figure 10: Envelope -Shear Force diagram in Grid B-B ............................................. 16
Figure 11: Envelope -Moment diagram Grid 2-2 ........................................................ 17
Figure 12: Envelope -Moment diagram Grid B-B ....................................................... 17
Figure 13: Section Input in Frame along Grid B-B ..................................................... 19
Figure 14: Section Input In Frame Along grid 2-2 ...................................................... 20
Figure 15: Section Input In Ground Floor ................................................................... 20
Figure 16: Design Output in Frame along Elevation ................................................... 23
Figure 17: Design Output in Frame on Floor ............................................................... 25
Figure 22: Column Layout ........................................................................................... 38
List of Table
Table 1: Load Cases ....................................................................................................... 5
Table 2: Load Combination ........................................................................................... 6
Table 3: Unit Weight of Materials ................................................................................. 7
Table 4: Dead Load Calculation .................................................................................... 7
Table 5: Live Load for Residential Building ................................................................. 9
Table 6: Mass Source for Seismic Load ...................................................................... 11
Table 7: Base Reaction ................................................................................................ 12
Table 8: Storey Drift .................................................................................................... 12
Table 9: Modal Result .................................................................................................. 14
Table 10: Joint Reaction .............................................................................................. 18
Detailed Analysis & Design Report of Building
1 Introduction
1.1 General
This report presents the structure analysis and design of Residential building. The building is Special
Reinforced Concrete Moment Resisting Frame (SMRF) type of building. It is designed to meet both
strength and serviceability requirements when subjected to gravity and earthquake loads.
The analysis and design have been based on NBC 2020 code that is in practice in Nepal. This report
consists of the design assumptions, design methodology, design inputs and outputs, and sample
design of structural members.
1.2 Salient Features
1.2.1 Project Information
No of Story : FF + SF+ TF
1
Detailed Analysis & Design Report of Building
• Floor slabs are assumed to be rigid in their own plane. The slab action has been
modeled by rigid floor diaphragms. Slabs are also considered in modeling. Slab is
modeled as shell element.
• Beam and columns are modeled as frame elements.
• The main beams rest centrally on columns to avoid local eccentricity.
• Foundation is assumed to be fully rigid at the plinth level.
• The beam-column joint is not modeled in detail.
• Preliminary sizes of structural components are assumed by experience.
• Seismic loads were considered acting in the horizontal direction (along either of the two
orthogonal directions of building) and not along the vertical direction, since it isnot
considered to be significant for design of structural members suitable load combinations
as suggested by IS NBC 105 are used.
Figure 2: 3D Modeling
3
Detailed Analysis & Design Report of Building
2 Analysis
2.1 Material properties
2.1.1 Concrete
All components of plain and reinforced concrete unless specified in design are M20 grade.
Modulus of Elasticity [Ec]= 5000 √fckN/mm2(Cl. 6.2.3.1, IS 456:2000)
= 22360 N/mm2 for M20 Grade.
Poisson’s Ratio [U] = 0.2
Unit Weight = 25 KN/m3
Characteristic Strength [ƒck] = 20 N/mm2 for M20 grade.
The structural design strength is derived from the characteristic strength multiplied by a
coefficient 0.67 and divided by the material partial safety factor. The partial factor for
concrete in flexure and axial load is 1.5.
4
Detailed Analysis & Design Report of Building
5
Detailed Analysis & Design Report of Building
6
Detailed Analysis & Design Report of Building
7
Detailed Analysis & Design Report of Building
8
Detailed Analysis & Design Report of Building
9
Detailed Analysis & Design Report of Building
10
Detailed Analysis & Design Report of Building
The seismic weight is determined based on the following mass source. (Cl: 5.2, NBC 105-
2020)
3 Analysis Output
The analysis results are discussed in this chapter. Both seismic coefficient and responsespectrum
methods are used. The major discussion are focused on the eccentricity, story shear, inter story
drift, maximum displacement and base shear along two orthogonal directions. The column and
beam size and reinforcement are designed for the maximum response.
3.1 Seismic Coefficient Method
The fundamental time period of the building as per NBC 105, total seismic weight and base
shear in both orthogonal directions are given in Table 7.
11
Detailed Analysis & Design Report of Building
Based on program/software calculated seismic coefficient, base shear and storey shear are
as shown in the table and to calculate these parameters, the following equation has been used
as per code.
3.2 Story Drift
As per Cl. no. 7.11.1 of NBC 105, the story drift in any story due to specified design lateral
force with partial load factor of 1.0, shall not exceed 0.025 times the story height. From the
analysis the displacements of the mass center of various floors are obtained and are shown in
along with story drift.
Table 8: Storey Drift ULS
12
Detailed Analysis & Design Report of Building
It is seen that drift does not exceed the code prescribed value of 0.025 where the design
horizontal deflections shall be determined by multiplying the
horizontal deflection found from Equivalent Static Method or Modal
Response Spectrum Method by the Ductility factor (Rμ). Thus, the drift check seems to comply with the safety
value mentioned in the code
It is seen that drift does not exceed the code prescribed value of 0.006 times story height
Thus the drift check seems to comply with the safety value mentioned in the code.
13
Detailed Analysis & Design Report of Building
14
Detailed Analysis & Design Report of Building
15
Detailed Analysis & Design Report of Building
16
Detailed Analysis & Design Report of Building
17
Detailed Analysis & Design Report of Building
18
Detailed Analysis & Design Report of Building
19
Detailed Analysis & Design Report of Building
20
Detailed Analysis & Design Report of Building
21
Detailed Analysis & Design Report of Building
22
Detailed Analysis & Design Report of Building
23
Detailed Analysis & Design Report of Building
Type of panel
Loads
3.83 mts
Self weight of slab w1= 3.13 kN/m^2
Floor finish 100 mm thk wpc w2= 1.50 kN/m^2
Live load - Accessible Terrace w3= 2.00 kN/m^2
Miscellaneous-Equipment Load w4= 1.50 kN/m^2 3.50 mts
Design
Coeff BM k pt Ast Dia Spacing
Short span direction
Negative moment at continuous edge 0.053 7.91 0.70 0.17 179 8 150
Positive moment at midspan 0.04 5.97 0.53 0.13 150 8 150
Deflection check
Reinf provided at midspan along short direction 335.10 mm^2 Dia 8 at 150 mm
Stress in reinforcement fs= 129.81 N/mm^2
Percentage of reinforcement provided pt= 0.3161 %
Modification factor as per fig 4 of IS:456-2000 MF= 2
24
Detailed Analysis & Design Report of Building
25
Detailed Analysis & Design Report of Building
Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
230 355.6 230 0 35 35
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
26
Detailed Analysis & Design Report of Building
27
Detailed Analysis & Design Report of Building
Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
304.8 304.8 56 30
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
28
Detailed Analysis & Design Report of Building
Notes:
N/A: Not Applicable
N/C: Not Calculated
N/N: Not Needed
29
Detailed Analysis & Design Report of Building
Load Pu 375 KN
Design Load P 250 KN
L 1.53 meters
Footing Size Provided
B 1.53 meters
Area Provided A prvd 2.34 meters
Zx 0.60
Zx 0.60
Footing Size OK
2 Slab Design
lx 0.615
ly 0.615
30
Detailed Analysis & Design Report of Building
Spacing c/c in mm
Area of Steel
12# 16# 20#
473 sqmm 239 c/c 425 c/c 664 c/c
473 sqmm 239 c/c 425 c/c 664 c/c
Minimum Ast required across x direcion
Minimum Ast required across y direcion
Vu1 48 KN
ζv 0.079 MPa
ζc 0.260 MPa
Vc1 157 KN
Vu1 48 KN
ζv 0.079 MPa
ζc 0.260 MPa
Vc1 157 KN
31
Detailed Analysis & Design Report of Building
32
Detailed Analysis & Design Report of Building
33
Detailed Analysis & Design Report of Building
34
Detailed Analysis & Design Report of Building
35
Detailed Analysis & Design Report of Building
Loading
Loads on going Loads on waist slab
Self weight of waist slab 4.58 KN/m Self weight of landing slab 3.75 KN/m
Self weight of steps 2.19 KN/m Live Load 3.00 KN/m
Live Load 3.00 KN/m Floor Finish Load 1.00 KN/m
Floor Finish Load 1.00 KN/m Total Load 7.75 KN/m
Total Load 10.76 KN/m Factored Load 11.63 KN/m
Factored Load 16.15 KN/m
Bending Moment
Calculate Bending Moment using the equation (W*L*L )/8
Reaction
to be used as UDL = 24 KN
60 KN-m
Spacing
Diameter of bar 12ø 16ø
610
Spacing across x 343 c/c c/c
Spacing
Diameter of bar 8ø 10ø
436
Spacing across y 279 c/c c/c
36
Detailed Analysis & Design Report of Building
Fig.6.7
Column ID Size (mm) Up to 1st Floor Up to 2nd Floor Up to Terrace
NOTE:
1. The transverse reinforcement in the column should be 8mm ф, 4- legged @ 100mm c/c at below
and above the face of the beam for a distance of 0.8m.
2. The spacing of 8mm ф, 4- legged transverse reinforcement should be @ 100mm c/c in lap zone.
3. Other detailing is as per structural drawings sheet.
37
Detailed Analysis & Design Report of Building
Plinth Beam 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars
(230x300mm) (TH) (TH)
MB (230x300mm) 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars
(TH) (TH) (TH)
Terrace Beam
MB (230x355mm) 2-12mm dia. Bars 2-12mm dia. Bars 2-12mm dia. Bars 2-12mm dia. Bars
(TH) (TH) (TH)
Vertical Stirrups 8mm dia. Vertical Stirrups @ 100mm c/c 8mm dia. Vertical Stirrups @ 150mm c/c
upto L/4 from end of support upto midspan
NOTE:
1. The shear reinforcement in the L/4 of beam span measured from supports face should be 8mm ф
provided @ 100mm c/c and can be placed @ 150mm c/c in remaining span.
2. The shear reinforcement in the main beam in which secondary beams are tied should be 8mm ф
provided @ 75mm c/c throughout.
3.The shear reinforcement in the lapping zone should be also provided @ 150mm c/c
4.The shear reinforcement in the circular beam should be provided @ 100mm c/c
38
Detailed Analysis & Design Report of Building
FOOTING REINFORCEMENT IN
TYPE FOOTING SIZE DEPTH FOOTINGS STRAP DETAIL
X-DIRECTION Y-DIRECTION
Spacing (Sv)
ECENTRIC SYMETRIC D te (Hs X Bs) Ast (Top) Asc
(Bf X L1) (Bf X L2) m (Bottom) 4-Legged
m
STRAP 1.83mX1.83m 1.83mX1.83m 450mm 250mm 12 mm dia. @ 150 12 mm dia. @ 600 mm X 300 mm 8mm ф
mm c/c 150 mm c/c 4-20 mm ф 2-16 mm ф
@ 150mm c/c
Footing Footing size Footing Depth of Top and Bottom Top and Bottom
mm (L x B) type footing
footing Rebar along footing Rebar along length
Breadth
F1 1530X1530 Isolated 450 mm 12mm dia@150mmc/c 12mm dia@150mmc/c
39
Detailed Analysis & Design Report of Building
40
Detailed Analysis & Design Report of Building
6 References
[1] IS 456- 2000 Code of practice for plain and reinforced concrete
[2] IS 875-1987 Code of practice for design loads (other than earthquake) for buildings and structures
END OF REPORT