THAMAN

This report summarizes the structural analysis and design of a residential building in Nepal. It describes the building features, assumptions made, design methodology, and codes used. Loads including dead, live, and seismic loads are estimated. Structural analysis was conducted using 3D modeling software to determine member forces and story drift under different load cases. Structural elements including beams, columns, slabs, footings and staircases were then designed based on the analysis results and design codes. Required member sizes were adopted to satisfy design code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
75 views47 pages

THAMAN

This report summarizes the structural analysis and design of a residential building in Nepal. It describes the building features, assumptions made, design methodology, and codes used. Loads including dead, live, and seismic loads are estimated. Structural analysis was conducted using 3D modeling software to determine member forces and story drift under different load cases. Structural elements including beams, columns, slabs, footings and staircases were then designed based on the analysis results and design codes. Required member sizes were adopted to satisfy design code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 47

Report

On

Structural Analysis & Design


Of

MRS. THAMAN
Residential Building
Ward No.-3, Suddhodhan Rural Municipality, Rupandehi, Nepal
Submitted To:
SUDDHODHAN RURAL mUNICIPALITY office
Rupandehi, Nepal

For:
PUSKAR engineering CONSULTANT
Ward No.-3
Suddhodhan Rural Municipality, Rupandehi, Nepal
Prepared by:
Er. Praveen Rajbhandari
Structural Engineer
NEC Regd. No.- 12025 Civil ‘A’
December, 2022
TO WHOM IT MAY CONCERN

This report comprises the summary of the structural analysis & design of residential
building. The report consists of the design procedure adopted, assumptions made and
input and output from the design and analysis. It is assumed that the Client will
completely follow the Structural Design specified in the form of Design Drawings
attached in the report.

The Designer will not be responsible if any alteration to the structural system and
configuration made by Client without consultation and permission from the Designer.

The design calculations and derivations are limited to only a minimum to let the
concerned people know the methodology adopted. However, the calculations may be
provided to the Client or the concerned Authority upon request.

…………………………….
Er. Praveen Rajbhandari
NEC NO: 12025 Civil “A”
(STRUCTURAL ENGINEER)
Table of Contents
1 Introduction..................................................................................................................... 1
1.1 General ............................................................................................................................ 1
1.2 Salient Features .............................................................................................................. 1
1.2.1 Project Information......................................................................................................... 1
1.2.2 Building Features ........................................................................................................... 1
1.2.3 Site Condition .................................................................................................................. 2
1.3 Analysis Technology and Methodology ......................................................................... 2
1.4 Codes and Standard used ................................................................................................ 4
1.5 Software Used .................................................................................................................. 4
2 Analysis ........................................................................................................................... 4
2.1 Material properties .......................................................................................................... 4
2.1.1 Concrete........................................................................................................................... 4
2.1.2 Reinforcement Steel ........................................................................................................ 5
2.2 Section Properties ........................................................................................................... 5
2.3 Loadings .......................................................................................................................... 5
2.3.1 Load Cases....................................................................................................................... 5
2.4 Estimation of Load .......................................................................................................... 7
2.4.1 Unit Weight (Dead Load) ................................................................................................ 7
2.4.2 Live Load ........................................................................................................................... 9
2.4.3 Seismic Load ................................................................................................................. 11
3 Analysis Output ............................................................................................................. 11
3.1 Seismic Coefficient Method .......................................................................................... 11
3.2 Story Drift ...................................................................................................................... 12
3.3 Modal time period and mass participation ................................................................... 14
3.4 Force Diagram .............................................................................................................. 15
3.4.1 Axial Force Diagram .................................................................................................... 15
3.4.2 Shear Force Diagram ................................................................................................... 16
3.4.3 Moment Diagram ............................................................................................................ 17
3.5 Joint Reactions .............................................................................................................. 18
4 Design of Structural Members...................................................................................... 19
4.1 Design Input and Output .............................................................................................. 19
4.1.1 Section Input Diagram.................................................................................................. 19
4.1.2 Design Output Diagram ................................................................................................ 21
4.2 Design of Slab .................................................................................................................... 24
4.3 Design of Beam and Column............................................................................................. 26
4.3.1 Sample Beam Design ...................................................................................................... 26
4.3.2 Sample Column Design................................................................................................... 28
4.4 Footing Design from excel (sample) ................................................................................. 30
4.4 Staircase Design from excel (sample) ............................................................................... 36
5 Summary of the Analysis and Design .......................................................................... 37
5.1 COLUMN OUTPUT: ......................................................................................................... 37
5.2 BEAM OUTPUT: ............................................................................................................... 38
5.3 FOOTING OUTPUT ......................................................................................................... 39
5.4 SLAB REINFORCEMENT: SLAB THICKNESS – 125mm ............................................ 39
5.5 CANTILEVER SLAB REINFORCEMENT: SLAB THICKNESS – 125mm ................. 39
5.6 Staircase Bar: WAIST SLAB THICKNESS – 150mm...................................................... 40
Required sizes of structure were adopted ................................................................................ 40
6 References ..................................................................................................................... 41
List of Figure
Figure 1: First Floor Plan of Building ............................................................................ 2
Figure 2: 3D Modelling ................................................................................................. 3
Figure 3: Frame Load (Wall Load) in 3D .................................................................... 8
Figure 4: Frame Load (Wall Load) in Grid 2-2 ........................................................... 9
Figure 5: Area Load (live load<=3) First Floor ........................................................... 10
Figure 6: Floor Finish Load (Dead Load) on First Floor ............................................. 10
Figure 7: 1.5(DL+LL)- Axial Force diagram in Grid 2-2 ............................................ 15
Figure 8: 1.5(DL+LL)- Axial Force diagram in Grid B-B .......................................... 15
Figure 9: Envelope -Shear Force diagram in Grid 2-2................................................. 16
Figure 10: Envelope -Shear Force diagram in Grid B-B ............................................. 16
Figure 11: Envelope -Moment diagram Grid 2-2 ........................................................ 17
Figure 12: Envelope -Moment diagram Grid B-B ....................................................... 17
Figure 13: Section Input in Frame along Grid B-B ..................................................... 19
Figure 14: Section Input In Frame Along grid 2-2 ...................................................... 20
Figure 15: Section Input In Ground Floor ................................................................... 20
Figure 16: Design Output in Frame along Elevation ................................................... 23
Figure 17: Design Output in Frame on Floor ............................................................... 25
Figure 22: Column Layout ........................................................................................... 38
List of Table
Table 1: Load Cases ....................................................................................................... 5
Table 2: Load Combination ........................................................................................... 6
Table 3: Unit Weight of Materials ................................................................................. 7
Table 4: Dead Load Calculation .................................................................................... 7
Table 5: Live Load for Residential Building ................................................................. 9
Table 6: Mass Source for Seismic Load ...................................................................... 11
Table 7: Base Reaction ................................................................................................ 12
Table 8: Storey Drift .................................................................................................... 12
Table 9: Modal Result .................................................................................................. 14
Table 10: Joint Reaction .............................................................................................. 18
Detailed Analysis & Design Report of Building

1 Introduction
1.1 General
This report presents the structure analysis and design of Residential building. The building is Special
Reinforced Concrete Moment Resisting Frame (SMRF) type of building. It is designed to meet both
strength and serviceability requirements when subjected to gravity and earthquake loads.
The analysis and design have been based on NBC 2020 code that is in practice in Nepal. This report
consists of the design assumptions, design methodology, design inputs and outputs, and sample
design of structural members.
1.2 Salient Features
1.2.1 Project Information

Type of building : Residential Building


Location : Pharsatikar, Rupandehi, Nepal
Ground Floor Area : 624 Sq. ft

Total land Area :

Land Coverage (%) : 0%

1.2.2 Building Features


The building has some special features which are listed below:
Type of Buildings : Special RC Moment Resisting Frame Structure

Shape : Regular Shape

Plinth level : As per architectural drawing

Roof floor Type : Inaccessible Terrace

Walls : Brick walls

Footing Type : Strap and Isolated footings

Dimension : 24’ by 26’

Story Height : All floors- 3.2 m

Total Height : 9.6 m from Plinth lvl.

No of Story : FF + SF+ TF

1
Detailed Analysis & Design Report of Building

Figure First Floor Plan of Building

1.2.3 Site Condition

Type of soil : Type B, Medium Soil as per NBC 105

Safe bearing pressure : 150 KN/m2

Seismic Zone Factor : 0.3 for Rupandehi as per NBC 105

1.3 Analysis Technology and Methodology


General:
After completion of Architectural design, the layout of columns and beams are done without
affecting the Architectural functions of building so far. Structure is modeled using finite element
method.
The structure is analyzed by the linear elastic theory to calculate internal actions produced by
anticipated design loads. The analysis is carried out using state of art three-dimensional structural
analysis programs ETABS 2018. The design loads considered as per the relevant codes of practice
comprise dead load due to permanent structures, live load due to occupancy of the structure and
seismic load due to anticipated earthquake possible at the proposed location. A number of load
combinations are considered to obtain the maximum values of design stresses.
Following considerations is made during modeling, analysis and design.
• The structures are Special Reinforced Concrete Moment Resisting Frame (SMRF) type.
Beams and columns are considered as the structural load resisting elements. Although
non-structural components like wall plaster, infill walls, floor finishing etc. has comes
effects on structural performance, they are considered only as loading.
• For column M20 grade concrete is used. Except Column, for all structural
elements, M20 grade concrete is used.
• Centre-line dimensions are followed for modeling, analysis and design.
2
Detailed Analysis & Design Report of Building

• Floor slabs are assumed to be rigid in their own plane. The slab action has been
modeled by rigid floor diaphragms. Slabs are also considered in modeling. Slab is
modeled as shell element.
• Beam and columns are modeled as frame elements.
• The main beams rest centrally on columns to avoid local eccentricity.
• Foundation is assumed to be fully rigid at the plinth level.
• The beam-column joint is not modeled in detail.
• Preliminary sizes of structural components are assumed by experience.
• Seismic loads were considered acting in the horizontal direction (along either of the two
orthogonal directions of building) and not along the vertical direction, since it isnot
considered to be significant for design of structural members suitable load combinations
as suggested by IS NBC 105 are used.

Figure 2: 3D Modeling

3
Detailed Analysis & Design Report of Building

1.4 Codes and Standard used


For the structural analysis and design, the following codes and standard are followed:
• IS 456- 2000 Code of practice for plain and reinforced concrete
• IS 875-1987 Code of practice for design loads (other than earthquake) for buildings
and structures
• NBC Nepal Building Code 105:2020

1.5 Software Used


The following software is used for the structural analysis and design.
ETABS 2018 - For analysis and design of the structures
For structural modeling of the present building, ETABS software was used. ETABS is a
special purpose finite element analysis and design program developed specifically for building
systems. With ETABS, models are defined logically floor-by-floor, column-by-column, bay- by-
bay and wall-by-wall and not as a stream of non-descript nodes and elements as in general
purpose programs. The software has very powerful numerical methods, design procedures and
international design codes, all working from a single comprehensive database. At its core, it
utilizes the same analysis engine as used by SAP2000.
Among others, ETABS can do model generation, seismic and wind load generation, finite
element-based linear and non-linear static and dynamic analysis, concrete frame design (column
and beam) and shear wall design.

2 Analysis
2.1 Material properties
2.1.1 Concrete
All components of plain and reinforced concrete unless specified in design are M20 grade.
Modulus of Elasticity [Ec]= 5000 √fckN/mm2(Cl. 6.2.3.1, IS 456:2000)
= 22360 N/mm2 for M20 Grade.
Poisson’s Ratio [U] = 0.2
Unit Weight = 25 KN/m3
Characteristic Strength [ƒck] = 20 N/mm2 for M20 grade.
The structural design strength is derived from the characteristic strength multiplied by a
coefficient 0.67 and divided by the material partial safety factor. The partial factor for
concrete in flexure and axial load is 1.5.

4
Detailed Analysis & Design Report of Building

2.1.2 Reinforcement Steel


Characteristic strength of high yield steel is taken as TMT Fe500 for main rebar and TMT
Fe500 for shear rebar and material partial safety factor is to be 1.15.
Modulus of Elasticity [Es] = 2x105 N/mm2
Poisson’s Ratio [U] = 0.3
2.2 Section Properties
Preliminary Size of Members
The preliminary sizes of Beam, Column, and Slab were chosen based on experience.
Main Beam : 230 mm x 355 mm
Column : 300 mm x 300 mm
Slab Thickness : 125 mm
During the analysis, beam, column & slab are modeled as frame elements.
2.3 Loadings
The following considerations are made during the loading on the structural model:
• The loads distributed over the area are imposed on the area element and the loads
distributed over the length are imposed on the frame elements whenever possible.
• Where such loading is not possible, equivalent conversion to different loading
distribution is carried to load the model near the real case as far as possible.
• For lateral load, necessary calculations are performed to comply with the
requirements of NBC 105:2020.
2.3.1 Load Cases
The following load cases are used for the loading during analysis.

Table 1: Load Cases


Load
Load Name Description Unit Remarks
Type
Dead Dead Self-weight of the structure KN/m2
LIVE Live Imposed Load <=3 KN/m On floor slab
LIVE 2 Live Imposed Load >3 KN/m2 On floor slab
Roof Live Live Roof Live KN/m2 On floor slab
WALL LOAD Dead Partition Wall Load KN/m On floor beams
FINISHES Dead Floor Finish Load KN/m2 On floor slab
EQX Seismic Seismic Coefficient NBC X+0.1Y
EQY Seismic Seismic Coefficient NBC Y+0.1X

5
Detailed Analysis & Design Report of Building

2.3.2 Load Combination


The load combinations are based on NBC 105-2020. The following load combinations are
specified as per NBC 105, Cl: 3.6
Static Load Combination:
1.2DL + 1.5LL)
Seismic Load Combination:
DL + λLL ± EQ)
Where,
λ = 0.6 for storage facilities
= 0.3 for other usage.

The following load combinations are used during analysis

Table 2: Load Combination


S.N Type
1 1.2DL + 1.5LL
2 DL + 0.3LL+ EQx
3 DL + 0.3LL - EQx
4 DL + 0.3LL + EQy
5 DL + 0.3LL - EQy

6
Detailed Analysis & Design Report of Building

2.4 Estimation of Load


The loads on the building are based on Indian codes of Practices. The unit weight of different
structural and non-structural elements is derived from IS 875 Part 1 and presented in below.
The load calculations are based on actual measured drawings. The self-weight of beams,columns
and slabs are calculated by the program. Similarly, the imposed loads are applied onthe slab
as area load in KN/m2 and values of imposed loads are tabulated below. The weight of infill walls
are calculated and applied on beams as line weight in KN/m.
• Partition wall load are assigned as uniformly distributed area load in slab as area load in
KN/m2.
• Floor finishing load are assigned as area load in slab.
• Single type of Live load is assigned in each panel of slab.
• A frame load is applied as parapet loading on the exterior frame of the roof level.
• The roof is assumed inaccessible and loaded with roof live load as per Indian Standard, IS
875 -1987(part2) but this load is not considered during seismic load.

2.4.1 Unit Weight (Dead Load)


Dead loads for analysis are calculated as per Indian Standard, IS 875 -1987(part1). Unit
weights of different material used are given below

Table 3: Unit Weight of Materials


S.N Type Value
1 Reinforced Concrete 25 KN/m3
2 Brick Masonry 19.2 KN/m3
3 Screed 21.0 KN/m3
4 Marble 26.7 KN/m3
5 Mosaic finish 23.1 KN/m3
6 Plaster 20.4 KN/m3
7 Steel Rebar 78.6 KN/m3

Table 4: Dead Load Calculation

1 Unit Weights of materials


Brick masonry 19.2 kN/m3
Screed 21 kN/m3
Mosaic 23.1 kN/m3
Marble 26.7 kN/m3
Reinforced Concrete 25 kN/m3
cement plaster 20.4 kN/m3

2 Heights of Beams, Walls & Parapet Walls


Depth of Beam 0.355 m

Height of Floor 2.845 m

7
Detailed Analysis & Design Report of Building

Dead Loads of Walls

Particular Height Thickness Density Load Load with windows


Calculated applied (70% opening)
(Kn/m3)
(kn/m) (kn/m)
For brick 2.845 0.23 19.2 12.56 12.56 8.8
wall
For brick 2.845 0.110 19.2 6 6 4.2
wall
For Parapet 1 0.110 19.2 2.12 2.12 -
wall

Figure 3: Frame Load (Wall Load) in 3D

8
Detailed Analysis & Design Report of Building

Figure 4: Frame Load (Wall Load) in Grid 1-1

2.4.2 Live Load


The magnitude of live load depends upon the type of occupancy of the building. These are
to be chosen from code IS875:1987(part II) for various occupancies. The live load distribution
varies with time. Hence each member is designed for worst combination of dead load and
live loads. Live loads for Residential Building are given above.

Table 5: Live Load for Residential Building

S. N Area type Load Unit


1 Terrace (Accessible) 1.5 KN/m2
2 Terrace (Inaccessible) 0.75 KN/m2
Staircase Balcony and
3 3 KN/m2
Passage
4 Partition Load 1.5 KN/m2
5 Room 2 KN/m2

9
Detailed Analysis & Design Report of Building

Figure 5: Area Load (live load<=3) First Floor

Figure 6: Floor Finish Load (Dead Load) on First Floor

Figure 7: Roof live Load on Second Floor

10
Detailed Analysis & Design Report of Building

2.4.3 Seismic Load


The seismic load is applied to the building with user defined lateral load pattern in ETABS
2018 as per NBC 105-2020. This load case is assumed static linear and all the necessary data
are given as per the following conditions.
To determine the seismic load, it is considered that the country lies in the seismic zone
according to NBC 105-2020. The soil type is considered as medium with 10% damping to
determine average response acceleration. The building is analyzed as moment resisting frame
without consideration of infill wall. Therefore, the fundamental time period Ta is obtained by
using the following formula:

Ta = 0.075 h0.75[Cl.5.1.2, NBC 105:2020]


H= 9.6 m.
Soil Type: Type B
Other factors considered for seismic load calculations are as follows
Zone factor, Z = 0.3 for Rupandehi [Cl4.1.4, NBC 105-2020]
Importance factor, I = 1 [Cl 4.1.5, NBC 105:2020]
Ductility factor = 4 [Cl 5.3, NBC 105:2020]
Over Strength Factor =1.5[Cl 5.4, NBC 105:2020]

Value of Seismic Base Shear Coefficient (ULS): 0.125


Value of Seismic Base Shear Coefficient (SLS): 0.12

The seismic weight is determined based on the following mass source. (Cl: 5.2, NBC 105-
2020)

Table 6: Mass Source for Seismic Load


S. N Load Type Scale Factor
1 Dead Load 1
2 Live Load 0.3
3 Roof Live Load Nil

3 Analysis Output
The analysis results are discussed in this chapter. Both seismic coefficient and responsespectrum
methods are used. The major discussion are focused on the eccentricity, story shear, inter story
drift, maximum displacement and base shear along two orthogonal directions. The column and
beam size and reinforcement are designed for the maximum response.
3.1 Seismic Coefficient Method
The fundamental time period of the building as per NBC 105, total seismic weight and base
shear in both orthogonal directions are given in Table 7.

11
Detailed Analysis & Design Report of Building

TABLE: Load Pattern Definitions - Auto Seismic - User Coefficient


Ecc Weight Used Base Shear
Name Top Story Bottom Story C K
Ratio kN kN
EQ-X 0.1 TERRACE Base 0.125 1.044
EQ-X(1/3) 0.1 TERRACE Base 0.125 1.044 1733.5377 216.6922
EQ-X(2/3) 0.1 TERRACE Base 0.125 1.044 1733.5377 216.6922
EQ-X(3/3) 0.1 TERRACE Base 0.125 1.044 1733.5377 216.6922
EQ-Y 0.1 TERRACE Base 0.125 1.044
EQ-Y(1/3) 0.1 TERRACE Base 0.125 1.044 1733.5377 216.6922
EQ-Y(2/3) 0.1 TERRACE Base 0.125 1.044 1733.5377 216.6922
EQ-Y(3/3) 0.1 TERRACE Base 0.125 1.044 1733.5377 216.6922

Load Case/Combo Weight Used FX FY MX MY MZ


kN kN kN kN-m kN-m kN-m
EQ-X 1 1733.5377 -216.6922 0 0 -1168.5012 737.1378
EQ-X 2 1733.5377 -216.6922 0 0 -1168.5012 902.1767
EQ-X 3 1733.5377 -216.6922 0 0 -1168.5012 572.099
EQ-Y 1 1733.5377 0 -216.6922 1168.5012 0 -697.3717
EQ-Y 2 1733.5377 0 -216.6922 1168.5012 0 -908.1688
EQ-Y 3 1733.5377 0 -216.6922 1168.5012 0 -486.5747
Table 7: Base Reactions

Based on program/software calculated seismic coefficient, base shear and storey shear are
as shown in the table and to calculate these parameters, the following equation has been used
as per code.
3.2 Story Drift
As per Cl. no. 7.11.1 of NBC 105, the story drift in any story due to specified design lateral
force with partial load factor of 1.0, shall not exceed 0.025 times the story height. From the
analysis the displacements of the mass center of various floors are obtained and are shown in
along with story drift.
Table 8: Storey Drift ULS

Story Load Case/Combo Direction Drift


TERRACE FLOOR EX1 X 0.000871
TERRACE FLOOR EX2 X 0.000886
TERRACE FLOOR EX3 X 0.00095
SECOND FLOOR EX1 X 0.001983
SECOND FLOOR EX2 X 0.002047
SECOND FLOOR EX3 X 0.002223
FIRST FLOOR EX1 X 0.002071
FIRST FLOOR EX2 X 0.002236
FIRST FLOOR EX3 X 0.002348
TERRACE FLOOR EY1 Y 0.000853
TERRACE FLOOR EY2 Y 0.000853
TERRACE FLOOR EY3 Y 0.000953

12
Detailed Analysis & Design Report of Building

SECOND FLOOR EY1 Y 0.002173


SECOND FLOOR EY2 Y 0.001901
SECOND FLOOR EY3 Y 0.002649
FIRST FLOOR EY1 Y 0.002219
FIRST FLOOR EY2 Y 0.002113
FIRST FLOOR EY3 Y 0.002603

It is seen that drift does not exceed the code prescribed value of 0.025 where the design
horizontal deflections shall be determined by multiplying the
horizontal deflection found from Equivalent Static Method or Modal
Response Spectrum Method by the Ductility factor (Rμ). Thus, the drift check seems to comply with the safety
value mentioned in the code

Table 9: Storey Drift SLS

Story Load Case/Combo Direction Drift


TERRACE FLOOR EX1 X 0.001645
TERRACE FLOOR EX2 X 0.001902
TERRACE FLOOR EX3 X 0.001661
SECOND FLOOR EX1 X 0.002436
SECOND FLOOR EX2 X 0.002085
SECOND FLOOR EX3 X 0.003023
FIRST FLOOR EX1 X 0.00221
FIRST FLOOR EX2 X 0.00227
FIRST FLOOR EX3 X 0.002753
TERRACE FLOOR EY1 Y 0.001414
TERRACE FLOOR EY2 Y 0.001472
TERRACE FLOOR EY3 Y 0.001416
SECOND FLOOR EY1 Y 0.001992
SECOND FLOOR EY2 Y 0.001903
SECOND FLOOR EY3 Y 0.002081
FIRST FLOOR EY1 Y 0.001985
FIRST FLOOR EY2 Y 0.00192
FIRST FLOOR EY3 Y 0.002078

It is seen that drift does not exceed the code prescribed value of 0.006 times story height
Thus the drift check seems to comply with the safety value mentioned in the code.

13
Detailed Analysis & Design Report of Building

3.3 Modal time period and mass participation


NBC 105:2020 clause 7.3 states that number of modes to be used in the analysis should be such
that the sum total of modal masses of all modes considered is at least 90 percent of the total
seismic mass of the structure.
Number of Modes Considered = 12
Modal Mass Participation along X = 100%
Modal Mass Participation along Y = 100%

Table 9: Modal Result

Case Mode Period UX UY Sum UX Sum UY


sec
Modal 1 0.678 0.2159 0.4391 0.2159 0.4391
Modal 2 0.641 0.4798 0.3571 0.6957 0.7962
Modal 3 0.542 0.1773 0.0669 0.873 0.863
Modal 4 0.265 0.0002 0.0983 0.8732 0.9614
Modal 5 0.254 0.0951 1.609E-05 0.9683 0.9614
Modal 6 0.24 0.0003 0.0016 0.9687 0.963
Modal 7 0.177 0.002 0.0253 0.9707 0.9883
Modal 8 0.17 0.0264 0.0044 0.9971 0.9927
Modal 9 0.166 0.0029 0.0073 1 1

14
Detailed Analysis & Design Report of Building

3.4 Force Diagram


The output of forces obtained from ETABS analysis for Envelope have presented below as a
sample only. The output forces are axial force, Shear force and Moments.
3.4.1 Axial Force Diagram

Figure 7: 1.5(DL+LL)- Axial Force diagram in Grid 2-2

Figure 8: 1.5(DL+LL)- Axial Force diagram in Grid B-B

15
Detailed Analysis & Design Report of Building

3.4.2 Shear Force Diagram

Figure 9: Envelope -Shear Force diagram in Grid 2-2

Figure 10: Envelope -Shear Force diagram in Grid B-B

16
Detailed Analysis & Design Report of Building

3.4.3 Moment Diagram

Figure 11: Envelope -Moment diagram Grid 2-2

Figure 12: Envelope -Moment diagram Grid B-B

17
Detailed Analysis & Design Report of Building

3.5 Joint Reactions


The reactions at the support of column for load combination of 1.5(DL + LL) are as follows:

Table 10: Joint Reaction


Story Unique Name Load Case/Combo FZ MX MY
kN kN-m kN-m
BASE 2 1.5 (DL+LL) 250.6706 -1.1906 11.3853
BASE 9 1.5 (DL+LL) 443.6411 1.6792 2.0751
BASE 13 1.5 (DL+LL) 374.0478 -2.4489 -8.249
BASE 17 1.5 (DL+LL) 378.0555 -0.0636 1.7991
BASE 21 1.5 (DL+LL) 490.8422 0.1994 1.2106
BASE 25 1.5 (DL+LL) 306.34 3.6262 6.2966
BASE 29 1.5 (DL+LL) 189.0655 -0.0755 -3.7225
BASE 33 1.5 (DL+LL) 309.7597 0.8873 0.4173
BASE 37 1.5 (DL+LL) 226.1229 7.0211 1.4123

18
Detailed Analysis & Design Report of Building

4 Design of Structural Members


4.1 Design Input and Output
4.1.1 Section Input Diagram

Figure 13: Section Input in Frame along Grid 2-2

Figure 14: Section Input In Frame Along grid B-B

19
Detailed Analysis & Design Report of Building

Figure 15: Section Input In First Floor

20
Detailed Analysis & Design Report of Building

4.1.2 Design Output Diagram

21
Detailed Analysis & Design Report of Building

Figure 16: Design Output in Frame along Elevation

22
Detailed Analysis & Design Report of Building

Figure 17: Design Output in Frame on Floor

23
Detailed Analysis & Design Report of Building

4.2 Design of Slab


DESIGN OF F14 SLAB AT FIRST FLOOR
CASE 1
Short span S= 3.500 mts
Long span L= 3.83 mts
Assumed slab thickness t= 0.125 mts
Grade of concrete fck= 20 N/mm^2

Grade of reinforcement fy= 500 N/mm^2

Type of panel

Loads
3.83 mts
Self weight of slab w1= 3.13 kN/m^2
Floor finish 100 mm thk wpc w2= 1.50 kN/m^2
Live load - Accessible Terrace w3= 2.00 kN/m^2
Miscellaneous-Equipment Load w4= 1.50 kN/m^2 3.50 mts

Ratio of long span to short span R= 1.1 Two Way Slab


Design Load with load factor of 1.5 Wu= 12.19 kN/m^2

Design
Coeff BM k pt Ast Dia Spacing
Short span direction
Negative moment at continuous edge 0.053 7.91 0.70 0.17 179 8 150
Positive moment at midspan 0.04 5.97 0.53 0.13 150 8 150

Long span direction


Negative moment at continuous edge 0.047 7.02 0.64 0.15 159.7 10 150
Positive moment at midspan 0.035 5.23 0.56 0.13 150.0 10 150

Minimum effective depth reqd dre= 53.54 mm


Clear cover to any reinforcement c= 15 mm
Minimum effective depth provided dpr= 97 mm greater than 'min. eff depth reqd'. Hence ok
Minimum reinforcement Amin= 150 mm^2

Deflection check

Reinf provided at midspan along short direction 335.10 mm^2 Dia 8 at 150 mm
Stress in reinforcement fs= 129.81 N/mm^2
Percentage of reinforcement provided pt= 0.3161 %
Modification factor as per fig 4 of IS:456-2000 MF= 2

Type of slab for deflection check Continuous


Basic span to effective depth ratio 26
Minimum effective depth reqd from deflection criteria 67.31 mm
Effective depth provided 106 mm greater than 'min. eff depth reqd'. Hence ok

assume depth at support = 125 mm


effective depth at support = 106 mm
CHECK FOR SHEAR :

24
Detailed Analysis & Design Report of Building

At middle of Short edge Vy = w Lx / 3 per unit width


At middle of Long edge Vx = w Lx β
( 2β + 1 )
β = 1.0943
So, Vy = 14.22 KN
So, Vx = 14.639 KN
ζ vy = Vy / ( bd ) = 0.134 N/mm2
ζ vx = Vx / ( bd ) = 0.149 N/mm2
% steel provided along Long direction = 0.342 %
% steel provided along Short direction = 0.317 %
Permissible shear stress = Kζc
Provided thk of slab = 125 mm

k slab thickness 125 125.000 125


k 1.300 1.300 1.300

ζc % steel 0.250 0.342 0.500


ζc 0.370 0.418 0.500

Permissible shear stress, K ζ c = 0.543 N/mm2


HENCE OK
ζ c max = 2.800 N/mm2
HENCE OK

** Note: Refer Structural Dwg. for detail

25
Detailed Analysis & Design Report of Building

4.3 Design of Beam and Column


4.3.1 Sample Beam Design

ETABS Concrete Frame Design


IS 456:2000 + IS 13920:2016 Beam Section Design

Beam Element Details Type: Ductile Frame (Summary)


Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF
FIRST FLOOR B12 46 BEAM 355X230 DL+0.3LL+EQx 3683 3835.4 1

Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
230 355.6 230 0 35 35

Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Factored Forces and Moments


Factored Factored Factored Factored
Mu3 Tu Vu2 Pu
kN-m kN-m kN kN
-69.2933 0.0004 81.4431 0

Design Moments, Mu3 & Mt


Factored Factored Positive Negative
Moment Mt Moment Moment
kN-m kN-m kN-m kN-m
-69.2933 0.0006 0 -69.294

Design Moment and Flexural Reinforcement for Moment, Mu3 & Tu


Design Design -Moment +Moment Minimum Required
-Moment +Moment Rebar Rebar Rebar Rebar
kN-m kN-m mm² mm² mm² mm²
Top (+2 Axis) -69.294 610 0 610 158
Bottom (-2 Axis) 0 305 0 54 305

Shear Force and Reinforcement for Shear, Vu2 & Tu


Shear Ve Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
102.2758 0 102.2787 44.0459 884.04

26
Detailed Analysis & Design Report of Building

Torsion Force and Torsion Reinforcement for Torsion, T u & VU2


Tu Vu Core b1 Core d1 Rebar Asvt /s
kN-m kN mm mm mm²/m
0.0004 81.4431 180 305.6 0

** Note: Refer Structural Dwg. for detail

27
Detailed Analysis & Design Report of Building

4.3.2 Sample Column Design

ETABS Concrete Frame Design


IS 456:2000 + IS 13920:2016 Column Section Design

Column Element Details Type: Ductile Frame (Summary)


Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF
FIRST FLOOR C2 4 COL 300 x 300 DL+0.3LL+EQy 0 3200.4 0.776

Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
304.8 304.8 56 30

Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Axial Force and Biaxial Moment Design For Pu , Mu2 , Mu3


Design Pu Design Mu2 Design Mu3 Minimum M2 Minimum M3 Rebar Area Rebar %
kN kN-m kN-m kN-m kN-m mm² %
281.0933 66.3111 -5.6219 5.6219 5.6219 1438 1.55

Axial Force and Biaxial Moment Factors


K Factor Length Initial Moment Additional Moment Minimum Moment
Unitless mm kN-m kN-m kN-m
Major Bend(M3) 0.617997 2844.8 -0.826 0 5.6219
Minor Bend(M2) 0.57959 2844.8 26.5244 0 5.6219

Shear Design for Vu2 , Vu3


Shear Vu Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
Major, Vu2 48.718 66.9798 30.3333 48.718 337.85
Minor, Vu3 40.647 66.9798 30.3333 40.647 337.85

Joint Shear Check/Design


Joint Shear Shear Shear Shear Joint Shear
Force VTop Vu,Tot Vc Area Ratio
kN kN kN kN cm² Unitless
Major Shear, Vu2 N/A N/A N/A N/A N/A N/A
Minor Shear, Vu3 N/A N/A N/A N/A N/A N/A

28
Detailed Analysis & Design Report of Building

(1.4) Beam/Column Capacity Ratio


Major Ratio Minor Ratio
N/A N/A

Additional Moment Reduction Factor k (IS 39.7.1.1)


Ag Asc Puz Pb Pu k
cm² cm² kN kN kN Unitless
929 14.4 1375.3168 310.4357 281.0933 1

Additional Moment (IS 39.7.1)


Consider Length Section KL/Depth KL/Depth KL/Depth Ma
Ma Factor Depth (mm) Ratio Limit Exceeded Moment (kN-m)
Major Bending (M3 ) Yes 0.889 304.8 5.768 12 No 0
Minor Bending (M2 ) Yes 0.889 304.8 5.41 12 No 0

Notes:
N/A: Not Applicable
N/C: Not Calculated
N/N: Not Needed

** Note: Refer Structural Dwg. for detail

29
Detailed Analysis & Design Report of Building

4.4 Footing Design from excel (sample)

Isolated Footing Design Excel Sheet


Sample Design

1 Footing Size Design

Load Pu 375 KN
Design Load P 250 KN

Moment in x dir Mux -3 KN-m


Moment in y dir Muy -9 KN-m

Column size cx 300 mm


cy 300 mm

SBC q 150 KN/sqm

Footing Size required A req 1.83 sqmm

L 1.53 meters
Footing Size Provided
B 1.53 meters
Area Provided A prvd 2.34 meters

Zx 0.60
Zx 0.60

Net upward pressure Nup 94 KNm2

Footing Size OK

2 Slab Design
lx 0.615
ly 0.615

Bending Moment in x dir Mx 27 KN-m


Bending Moment in y dir My 27 KN-m

Concrete fck 20 MPa


Steel fy 500 MPa

Minimum Depth Required dmin 100

Depth Provided D 450 mm


Clear Cover c 50 mm
Effective Cover d' 56 mm
Effective Depth d' 394 mm

30
Detailed Analysis & Design Report of Building

Spacing c/c in mm
Area of Steel
12# 16# 20#
473 sqmm 239 c/c 425 c/c 664 c/c
473 sqmm 239 c/c 425 c/c 664 c/c
Minimum Ast required across x direcion
Minimum Ast required across y direcion

Ast across x direction 12 mm dia @ 150 mm c/c 754 sqmm


Ast across y direction 12 mm dia @ 150 mm c/c 754 sqmm

3 One Way Shear along x direction

Vu1 48 KN
ζv 0.079 MPa

ζc 0.260 MPa
Vc1 157 KN

One Way Shear Check OK

4 One Way Shear along y direction

Vu1 48 KN
ζv 0.079 MPa

ζc 0.260 MPa
Vc1 157 KN

One Way Shear Check OK

5 Two Way Shear


Vu2 262 KN
ζv 0.240 MPa

ks*ζc 1.118 MPa


Vc1 1223 KN

Two Way Shear Check OK

31
Detailed Analysis & Design Report of Building

32
Detailed Analysis & Design Report of Building

Strap Beam Footing Design Excel Sheet

33
Detailed Analysis & Design Report of Building

34
Detailed Analysis & Design Report of Building

35
Detailed Analysis & Design Report of Building

4.4 Staircase Design from excel (sample)


Staircase Design
Data
Effective Span (l) 3.00 mm
Riser (R) 175 mm
Thread (T) 250 mm
Waist Slab thickness (t) 150 mm
Clear Cover 15 mm
Effective Depth of Waist Slab (d) 135 mm

Grade of Concrete (fck) 20 MPa


Grade of Steel (fy) 500 MPa

Loading
Loads on going Loads on waist slab
Self weight of waist slab 4.58 KN/m Self weight of landing slab 3.75 KN/m
Self weight of steps 2.19 KN/m Live Load 3.00 KN/m
Live Load 3.00 KN/m Floor Finish Load 1.00 KN/m
Floor Finish Load 1.00 KN/m Total Load 7.75 KN/m
Total Load 10.76 KN/m Factored Load 11.63 KN/m
Factored Load 16.15 KN/m

Bending Moment
Calculate Bending Moment using the equation (W*L*L )/8

Bending Moment = 18 KN-m

Reaction
to be used as UDL = 24 KN
60 KN-m

Area of Main Steel


Ast 330 sqmm

Spacing
Diameter of bar 12ø 16ø
610
Spacing across x 343 c/c c/c

Provded Main Steel: 12ø @150mm c/c

Area of Distribution Steel


Ast 180 sqmm

Spacing
Diameter of bar 8ø 10ø
436
Spacing across y 279 c/c c/c

Provided Distridution Steel: 10ø @200mm c/c

36
Detailed Analysis & Design Report of Building

5 Summary of the Analysis and Design


5.1 Column Output:
Concrete Grade: M20
Steel Grade: Fe 500
Clear Cover: 40 mm

Fig.6.7
Column ID Size (mm) Up to 1st Floor Up to 2nd Floor Up to Terrace

C1 300X300 4-16ф+4-12ф 4-16ф+4-12ф 4-16ф+4-12ф

C2 300X300 4-16ф+4-16ф 4-16ф+4-16ф 4-16ф+4-12ф

NOTE:
1. The transverse reinforcement in the column should be 8mm ф, 4- legged @ 100mm c/c at below
and above the face of the beam for a distance of 0.8m.
2. The spacing of 8mm ф, 4- legged transverse reinforcement should be @ 100mm c/c in lap zone.
3. Other detailing is as per structural drawings sheet.

37
Detailed Analysis & Design Report of Building

5.2 Beam Output:


Design Parameters: Concrete Grade: M20
Steel Grade: Fe 500
Clear Cover: 30 mm
Beams Rebars at Support Rebars at mid span

Top Bottom Top Bottom

Plinth Beam 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars
(230x300mm) (TH) (TH)

First Floor Beam


MB (230x355mm) 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars
(TH) +2-16mm (EX) (TH)

MB (230x300mm) 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars
(TH) (TH) (TH)

Second Floor Beam


MB (230x355mm) 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars 2-16mm dia. Bars
(TH) +2-12mm (EX) (TH)

Terrace Beam
MB (230x355mm) 2-12mm dia. Bars 2-12mm dia. Bars 2-12mm dia. Bars 2-12mm dia. Bars
(TH) (TH) (TH)

Vertical Stirrups 8mm dia. Vertical Stirrups @ 100mm c/c 8mm dia. Vertical Stirrups @ 150mm c/c
upto L/4 from end of support upto midspan

NOTE:

1. The shear reinforcement in the L/4 of beam span measured from supports face should be 8mm ф
provided @ 100mm c/c and can be placed @ 150mm c/c in remaining span.
2. The shear reinforcement in the main beam in which secondary beams are tied should be 8mm ф
provided @ 75mm c/c throughout.
3.The shear reinforcement in the lapping zone should be also provided @ 150mm c/c
4.The shear reinforcement in the circular beam should be provided @ 100mm c/c

38
Detailed Analysis & Design Report of Building

5.3 Footing Output

FOOTING REINFORCEMENT IN
TYPE FOOTING SIZE DEPTH FOOTINGS STRAP DETAIL
X-DIRECTION Y-DIRECTION
Spacing (Sv)
ECENTRIC SYMETRIC D te (Hs X Bs) Ast (Top) Asc
(Bf X L1) (Bf X L2) m (Bottom) 4-Legged
m

STRAP 1.83mX1.83m 1.83mX1.83m 450mm 250mm 12 mm dia. @ 150 12 mm dia. @ 600 mm X 300 mm 8mm ф
mm c/c 150 mm c/c 4-20 mm ф 2-16 mm ф
@ 150mm c/c

Schedule of RCC Footing- SBC 150 KN/m2

Footing Footing size Footing Depth of Top and Bottom Top and Bottom
mm (L x B) type footing
footing Rebar along footing Rebar along length
Breadth
F1 1530X1530 Isolated 450 mm 12mm dia@150mmc/c 12mm dia@150mmc/c

5.4 SLAB REINFORCEMENT: SLAB THICKNESS – 125mm


Main bar 10 mm and extra bar 8 mm @ 150 mm C/C.

5.5 CANTILEVER SLAB REINFORCEMENT: SLAB THICKNESS – 125mm


Main bar 10 mm and extra bar 8 mm @ 150 mm C/C.

39
Detailed Analysis & Design Report of Building

5.6 Staircase Bar: WAIST SLAB THICKNESS – 150mm


Use 12mm dia. bar as main bar @ 150 mm C/C and 10 mm as distribution bar @ 200 mm C/C.

Required sizes of structure were adopted


SN Structures Sizes(mm)
1 Column (300mmX300mm)
2 Main Beam MB (230mm X 355mm)
3 Slab 125mm
4 Concrete grade M20 Column, M20 Beam, Footing
and Slabs
5 Steel grade Fe500 for main bar and Fe450
(stirrups)

40
Detailed Analysis & Design Report of Building

6 References
[1] IS 456- 2000 Code of practice for plain and reinforced concrete

[2] IS 875-1987 Code of practice for design loads (other than earthquake) for buildings and structures

[3] IS 1893-2002 Criteria for Earthquake Resistant Design of Structures,

[4] IS 13920-1993 Code of practice for ductile detailing of reinforced concrete

[5] Structures subjected to seismic forces

[6] NBC Nepal Building Code 2020

[7] Design of Reinforced Concrete Structure – A.K. Jain

[8] Limit State Design of Substructure- Swamisharan

[9] ETABS manual

END OF REPORT