GW SDT g2 User Manual-En
GW SDT g2 User Manual-En
Grid-Tied PV Inverter
SDT G2 Series
4-25kW
V1.1-2022-08-15
User Manual V1.1-2022-08-15 Copyright Statement
No part of this manual can be reproduced or transmitted to the public platform in any form or
by any means without the prior written authorization of GoodWe Technologies Co., Ltd.
Trademarks
Notice
The information in this user manual is subject to change due to product updates or other
reasons. This guide cannot replace the product labels or the safety precautions in the user
manual unless otherwise specified. All descriptions in the manual are for guidance only.
I
Content User Manual V1.1-2022-08-15
CONTENTS
1 About This Manual...........................................................1
1.1 Applicable Model........................................................................................ 1
1.2 Target Audience.......................................................................................... 1
1.3 Symbol Definition...................................................................................... 2
1.4 Updates....................................................................................................... 2
2 Safety Precaution............................................................3
2.1 General Safety............................................................................................ 3
2.2 DC Side........................................................................................................ 3
2.3 AC Side........................................................................................................ 4
2.4 Inverter Installation.................................................................................... 4
2.5 Personal Requirements.............................................................................. 4
3 Product Introduction.......................................................5
3.1 Application Scenarios................................................................................ 5
3.2 Supported Grid Types............................................................................... 5
3.4 Appearance................................................................................................. 6
3.4.1 Parts.....................................................................................................................6
3.4.2 Dimension............................................................................................................9
3.4.3 Indicators...........................................................................................................11
3.4.4 Nameplate.........................................................................................................13
5 Installation.................................................................... 16
5.1 Installation Requirements....................................................................... 16
5.2 Inverter Installation.................................................................................. 18
5.2.1 Moving the Inverter...........................................................................................18
5.2.2 Installing the Inverter.......................................................................................18
II
User Manual V1.1-2022-08-15 Content
6 Electrical Connection..................................................... 21
6.1 Safety Precautions.................................................................................. 21
6.2 Connecting the PE Cable......................................................................... 21
6.3 Connecting the PV Input Cable............................................................... 22
6.4 Connecting the AC Output Cable............................................................ 28
6.5 Communication....................................................................................... 32
6.5.1 Connecting the Communication Cable (optional)..........................................32
6.5.2 Installing the Communication Module (optional)...........................................36
7 Equipment Commissioning............................................ 37
7.1 Check Items Before Switching Power ON............................................... 37
7.2 Power On.................................................................................................. 37
8 System Commissioning.................................................. 38
8.1 Indicators and Button............................................................................. 38
8.2 Setting Inverter Parameters via LCD....................................................... 40
8.2.1 LCD Menu Introduction....................................................................................40
8.2.2 Inverter Parameter Introduction......................................................................42
8.3 Setting Inverter Parameters via App....................................................... 44
8.4 Monitoring via SEMS Portal..................................................................... 44
9 Maintenance................................................................. 45
9.1 Power Off the Inverter............................................................................. 45
9.2 Removing the Inverter............................................................................. 45
9.3 Disposing of the Inverter......................................................................... 45
9.4 Troubleshooting...................................................................................... 45
9.5 Routine Maintenance.............................................................................. 49
10 Technical Parameters................................................... 50
III
User Manual V1.1-2022-08-15 01 About This Manual
1
01 About This Manual User Manual V1.1-2022-08-15
DANGER
Indicates a high-level hazard that, if not avoided, will result in death or serious injury.
WARNING
Indicates a medium-level hazard that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a low-level hazard that, if not avoided, could result in minor or moderate injury.
NOTICE
Highlight and supplement the texts. Or some skills and methods to solve product-related
problems to save time.
1.4 Updates
The latest document contains all the updates made in earlier issues.
V1.0 2022-03-15
• First Issue
V1.1 2022-08-15
• Update 8.2.1 LCD Menu Introduction.
2
User Manual V1.1-2022-08-15 02 Safety Precaution
2 Safety Precaution
Notice
The inverters are designed and tested strictly complies with related safety rules. Read and
follow all the safety instructions and cautions before any operations. Improper operation
might cause personal injury or property damage as the inverters are electrical equipment.
• The information in this document is subject to change due to product updates or other
reasons. This manual cannot replace the product labels or the safety precaution unless
otherwise specified. All descriptions here are for guidance only.
• Before installations, read through the user manual to learn about the product and the
precautions.
• All installations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
• Use insulating tools and wear personal protective equipment when operating the
equipment to ensure personal safety. Wear anti-static gloves, cloths, and wrist strips when
touching electron devices to protect the inverter from damage.
• Strictly follow the installation, operation, and configuration instructions in this manual. The
manufacturer shall not be liable for equipment damage or personal injury if you do not
follow the instructions. For more warranty details, visit https://en.goodwe.com/warranty.
asp .
2.2 DC Side
DANGER
Connect the DC cables using the delivered DC connectors and terminals. The manufacturer
shall not be liable for the equipment damage if other connectors or terminals are used.
WARNING
• Ensure the component frames and the bracket system are securely grounded.
• Ensure the DC cables are connected tightly and securely.
• Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the
voltage should be under the permissible range.
• The PV modules used with the inverter must have an IEC61730 class A rating.
• If there are more than 3 PV strings on input side, an additional fuse installation will be
suggested.
• When exposed to sunlight, the PV array will generate very high voltage which can cause
electrical shock hazard. Please strictly follow the instruction we provided.
3
02 Safety Precaution User Manual V1.1-2022-08-15
2.3 AC Side
WARNING
• The voltage and frequency at the connecting point should meet the on-grid requirements.
• An additional protective device like the circuit breaker or fuse is recommended on the AC
side. Specification of the protective device should be at least 1.25 times the AC output rated
current.
• You are recommended to use copper cables as AC output cables. Contact the manufacturer
if you want to use other cables.
• Terminals at the bottom of the inverter cannot bear much load. Otherwise, the terminals
will be damaged.
• All labels and warning marks must be clear and distinct after the installation. Do not block,
alter, or damage any label.
• Warning labels on the inverter are as follows.
RCM marking. NA NA
NOTICE
• Personnel who install or maintain the equipment must be strictly trained, learn about
safety precautions and correct operations.
• Only qualified professionals or trained personnel are allowed to install, operate, maintain,
and replace the equipment or parts.
4
User Manual V1.1-2022-08-15 03 Product Introduction
3 Product Introduction
3.1 Application Scenarios
The SDT G2 Series inverter is a three-phase PV string grid-tied inverter. The inverter converts
the DC power generated by the PV module into AC power and feeds it into the utility grid. The
intended use of the inverter is as follows:
For the grid type with neutral wire, the N to ground voltage must be less than 10V.
TN-S TN-C TN-C-S TT
L1 L1 L1 L1
L2 L2 L2 L2
L3 L3 L3 L3
N PEN N N
PE PE
PE PE PE PE
Inverter Inverter Inverter Inverter
IT
L1
L2
L3
PE
Inverter
5
03 Product Introduction User Manual V1.1-2022-08-15
3.4 Appearance
3.4.1 Parts
GW12KT-DT, GW15KT-DT
13. Fan
6
User Manual V1.1-2022-08-15 03 Product Introduction
GW12K-SDT-20, GW12KLV-SDT-20,
GW8000-SDT-20, GW10K-SDT-20
GW15K-SDT-20, GW17K-SDT-20,
GW20K-SDT-20
Bluetooth or Wi-Fi/
DRED or Remote RS485 or Smart Meter
10. 11. LAN Kit or WiFi or 4G or 12.
Shutdown COM Port COM Port
GPRS Port
7
03 Product Introduction User Manual V1.1-2022-08-15
Name Description
USB Port Reserved. USB Port is used for system upgrade and configuration.
Ventilation valve -
Communication Used to connect communication modules like Bluetooth, WiFi, LAN, 4G,
Port etc.
Smart Meter +
Used to connect the Smart Meter or RS485 communication cable.
RS485
DRED(6Pin)
Used to connect DRED or remote shutdown communication cable. DRED
/ Remote
for Australia and New Zealand, Remote Shutdown only for Europe.
Shutdown (2pin)
AC Output
Used to connect AC output cable. Connect the inverter and the utility grid.
Terminal
8
User Manual V1.1-2022-08-15 03 Product Introduction
3.4.2 Dimension
Dimensions of GW4K-DT, GW4000-SDT-20, GW5K-DT, GW5000-SDT-20, GW6K-DT, GW6000-
SDT-20, GW10KT-DT:
354mm 147mm
200mm
45mm
433mm
200mm
45mm
433mm
110mm 120mm
120mm
511mm
9
03 Product Introduction User Manual V1.1-2022-08-15
415mm 198mm
110mm 120mm
120mm
511mm
10
User Manual V1.1-2022-08-15 03 Product Introduction
3.4.3 Indicators
As a human-computer interaction interface, LCD display panel comprises of LED indicators,
buttons and LCD display on the front panel of the inverter. LED indicates the working status of
the inverter. Buttons and LCD are used for configuration and viewing parameters.
ON = Wi-Fi IS CONNECTED/ACTIVE
OFF = NO FAULT
11
03 Product Introduction User Manual V1.1-2022-08-15
ON = EQUIPMENT POWER ON
ON = WIRELESS IS CONNECTED/ACTIVE
OFF = NO FAULT
12
User Manual V1.1-2022-08-15 03 Product Introduction
3.4.4 Nameplate
The nameplate is for reference only.
**.*A
Max current: a.c.
Technical parameters
Rated active power: *kW
Rated/Max apparent power: **/**kV A
Inverter topology: Non-isolated
Power factor range: Default >*.**,*.*cap...*.*ind
Operating temperature range: -**...**°C
Overvoltage-category: DCⅡ;ACⅢ
IP degree: IP65
Protective class: ClassⅠ
13
04 Check and Storage User Manual V1.1-2022-08-15
4.2 Deliverables
PV Box Positive PV
Negative PV
PV Box X N Bracket X N Connector
Inverter X 1 ConnectorX N
XN
14
User Manual V1.1-2022-08-15 04 Check and Storage
NOTICE
• The number of expansion bolts, screws, PV connectors, AC cable OT Terminal, and PIN
terminals are various depending on the different inverters. The actual accessories may
differ.
• Communication module types including WiFi, 4G, LAN, GPRS, Bluetooth, etc. The actual
module delivered depends on the communication method of the selected inverter.
• The model of the AC connector and mounting bracket are various depending the different
inverters. The actual accessories may differ.
• Only model GW15KAU-DT and GW20KAU-DT are equipped with PV box and PV box bracket.
4.3 Storage
If the equipment is not to be installed or used immediately, please ensure that the storage
environment meets the following requirements:
1. Do not unpack the outer package or throw the desiccant away.
2. Store the equipment in a clean place. Make sure the temperature and humidity are
appropriate and no condensation.
3. The height and direction of the stacking inverters should follow the instructions on the
packing box.
4. The inverters must be stacked with caution to prevent them from falling.
5. If the inverter has been long term stored, it should be checked by professionals before being
put into use.
15
05 Installation User Manual V1.1-2022-08-15
5 Installation
5.1 Installation Requirements
Installation Environment Requirements
1. Do not install the equipment in a place near flammable, explosive, or corrosive materials.
2. Install the equipment on a surface that is solid enough to bear the inverter weight.
3. Install the equipment in a well-ventilated place to ensure good dissipation. Also, the
installation space should be large enough for operations.
4. The equipment with a high ingress protection rating can be installed indoors or outdoors.
The temperature and humidity at the installation site should be within the appropriate range.
5. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a
sunshade if it is needed.
6. Do not install the equipment in a place that is easy to touch, especially within children’s
reach. High temperature exists when the equipment is working. Do not touch the surface to
avoid burning.
7. Install the equipment at a height that is convenient for operation and maintenance, electrical
connections, and checking indicators and labels.
8. Install the equipment away from electromagnetic interference.
16
User Manual V1.1-2022-08-15 05 Installation
RJ45 crimping
Goggles Safety shoes Safety gloves Dust mask tool
DC terminal
Diagonal Wire Hammer crimping tool
stripper drill Heat gun
pliers
M3/M5
Vacuum
Multimeter Cable tie Torque wrench cleaner
17
05 Installation User Manual V1.1-2022-08-15
CAUTION
Move the inverter to the site before installation. Follow the instructions below to avoid
personal injury or equipment damage.
1. Consider the weight of the equipment before moving it. Assign enough personnel to move
the equipment to avoid personal injury.
2. Wear safety gloves to avoid personal injury.
3. Keep balance when moving the equipment.
NOTICE
• Avoid the water pipes and cables buried in the wall when drilling holes.
• Wear goggles and a dust mask to prevent the dust from being inhaled or contacting eyes
when drilling holes.
• The anti-theft lock of appropriate size should be prepared by customers. Diameter of the
lock hole is 10mm.
• Make sure that all the DC input terminals are inside the PV box when installing the box.
Install the box cling to the bottom of the inverter.
Step 1 Put the mounting plate on the wall horizontally and mark positions for drilling holes.
Step 2 Drill holes to a depth of 80mm using the hammer drill. The diameter of the drill bit
should be 10mm.
Step 3 Secure the mounting plate using the expansion bolts.
Step 4 Install the inverter on the mounting plate.
Step 5 Tighten the nuts to secure the mounting plate and the inverter.
Step 6 Install the anti-theft lock.
Step 7 (For Australia and New Zealand) Install the PV box and the PV box mounting plate
together using the delivered M5 screws.
Step 8 (For Australia and New Zealand) Drill holes to a depth of 60mm using the hammer drill.
The diameter of the drill bit should be 8mm.
Step 9 (For Australia and New Zealand) Secure the PV box at the bottom of the inverter using
the delivered expansion bolts.
18
User Manual V1.1-2022-08-15 05 Installation
NOTICE
1 2 3
4
5
M5
1.2~2N·m
NOTICE
1 2 3
19
05 Installation User Manual V1.1-2022-08-15
4
5
M5
1.2~2N·m
NOTICE
7 8
9
M5
1.2~2N·m
20
User Manual V1.1-2022-08-15 06 Electrical Connection
6 Electrical Connection
6.1 Safety Precautions
DANGER
• Disconnect the DC switch and the AC output switch of the inverter to power off the
equipment before any electrical connections. Do not work with power on. Otherwise, an
electric shock may occur.
• Perform electrical connections in compliance with local laws and regulations. Including
operations, cables, and component specifications.
• If the tension is too large, the cable may be poorly connected. Reserve a certain length of
the cable before connecting it to the inverter cable port.
NOTICE
• Wear personal protective equipment like safety shoes, safety gloves, and insulating gloves
during electrical connections.
• All electrical connections should be performed by qualified professionals.
• Cable colors in this document are for reference only. The cable specifications should meet
local laws and regulations.
• The PE cable connected to the enclosure of the inverter cannot replace the PE cable
connected to the AC output port. Both of the two PE cables must be securely connected.
• Make sure that all the grounding points on the enclosures are equipotential connected
when there are multiple inverters.
• To improve the corrosion resistance of the terminal, it is recommended to apply silica gel
or paint on the ground terminal after installing the PE cable.
• The PE cable should be prepared by customers. Recommended specifications:
• Type: single-core outdoor copper cable.
• Conductor crosssectional area S≥10mm2 (GW8000-SDT-20, GW10K-SDT-20, GW12K-
SDT-20, GW12KLV-SDT-20, GW15K-SDT-20, GW17K-SDT-20, GW20K-SDT-20).
• Conductor crosssectional area S≥4mm2 (Other models).
1 L=L1+(1~2)mm L1
2 3
M5
1.2~2N·m
21
06 Electrical Connection User Manual V1.1-2022-08-15
Confirm the following information before connecting the PV string to the inverter. Otherwise,
the inverter may be damaged permanently or even cause fire and cause personal and
property losses.
1. Make sure that the max short circuit current and the max input voltage per MPPT are
within the permissible range.
2. Make sure that the positive pole of the PV string connects to the PV+ of the inverter. And
the negative pole of the PV string connects to the PV- of the inverter.
3. The minimum impedance to earth of the PV module shall be greater than R. R=Max.Input
Voltage (V)/30mA, i.e. R=1100V/30mA=36.7KΩ or R=1000V/30mA=33.4KΩ).
WARNING
• Connect the DC cables using the delivered PV connectors. The manufacturer shall not be
liable for the damage if other connectors are used.
• The PV strings cannot be grounded. Ensure the minimum isolation resistance of the
PV string to the ground meets the minimum isolation resistance requirements before
connecting the PV string to the inverter.
• The DC input cable should be prepared by customers. Recommended specifications:
• Type: the outdoor photovoltaic cable that meets the maximum input voltage.
• Conductor cross-sectional area: 2.5~4mm2
Click
22
User Manual V1.1-2022-08-15 06 Electrical Connection
NOTICE
Seal the PV input terminals using waterproof covers when they are not to be used. Otherwise,
the ingress protection rating will be influenced.
NOTICE
The PV box should be installed when GW15KAU-DT or GW20KAU-DT is used in Australia and
in New Zealand. Install the cover of the PV box after connecting the DC input cable to the
equipment.
Devalan DC Connector
23
06 Electrical Connection User Manual V1.1-2022-08-15
4
4 4
3 3
2 2
1 1
5 6
Click
2
Click
7 6
2
2
2 2
2 2
1 1
1
1
1
1
2 2 2 2
24
User Manual V1.1-2022-08-15 06 Electrical Connection
1 2
7~8mm
7~8mm
4 4
3 3
2 2
1 1
4 5
2 2 Click
Click
7
2 2
2 2
2 2
1
25
06 Electrical Connection User Manual V1.1-2022-08-15
Devalan DC Connector
Click
Click
26
User Manual V1.1-2022-08-15 06 Electrical Connection
1 2
7~8mm
7~8mm
3
4 4
3 3
2 2
1 1
4 5
2 2 Click
Click
27
06 Electrical Connection User Manual V1.1-2022-08-15
WARNING
• Do not connect loads between the inverter and the AC switch directly connected to it.
• Where an external RCD (Residual Current Device) is required in addition to the built-in
RCMU (Residual Current Monitoring Unit), a type A RCD must be used to avoid tripping.
The action current of RCD should be 300mA or higher.
An AC circuit breaker should be installed on the AC side to make sure that the inverter can safety
disconnect the grid when an exception happens. Select the appropriate AC circuit breaker in
compliance with local laws and regulations. Recommended AC circuit breakers:
NOTICE
Install one AC circuit breaker for each inverter. Multiple inverters cannot share one AC circuit
breaker.
4-10kW:13mm≤Φ≤18mm
Outside Diameter
12-15kW:18mm≤Φ≤25mm
4-10kW: 4mm²≤S≤10mm²
Conductor cross-sectional area
12-15kW: 6mm²≤S≤16mm²
WARNING
• Pay attention to the silkscreens L1, L2, L3, N, PE on the AC terminal. Connect the AC cables
to the corresponding terminals. The inverter may be damaged if the cables are connected
inappropriately.
• Make sure that the whole cable cores are inserted into the AC terminal holes. No part of
the cable core can be exposed.
• Make sure that the cables are connected securely. Otherwise, the terminal may be too hot
to damage the inverter when the inverter is working.
• Reserve certain length of PE cable. Make ensure that the PE cable is the last one to bear the
stress when the AC output cable is under tension.
28
User Manual V1.1-2022-08-15 06 Electrical Connection
NOTICE
1 L L 2
5
3
2 4
40mm 1
4-10kW: 13mm≤Φ≤18mm
12-15kW: 18mm≤Φ≤25mm
4-10kW: 4mm²≤S≤10mm²
12-15kW: 6mm²≤S≤16mm²
3 4
PE PE
4
L(L3)
4 L3 N
N
L1 L2
L1 2(L2)
L2 1(L1)
L3
3 N
PE
2
1
0.6N·m
29
06 Electrical Connection User Manual V1.1-2022-08-15
NOTICE
NOTICE
• Make sure that the cables are connected correctly and firmly after connections. Clean all the
debris in the maintenance compartment.
• Seal the AC output terminal to ensure the Ingress Protection Rating.
30
User Manual V1.1-2022-08-15 06 Electrical Connection
NOTICE
NOTICE
• Make sure that the cables are connected correctly and firmly after connections. Clean all the
debris in the maintenance compartment.
• Seal the AC output terminal to ensure the Ingress Protection Rating.
31
06 Electrical Connection User Manual V1.1-2022-08-15
6.5 Communication
6.5.1 Connecting the Communication Cable (optional)
NOTICE
Make sure that the communication device is connected to the right COM port. Route the
communication cable far away from any interference source or power cable to prevent the
signal from being influenced.
1: RS485 B
2: RS485 B Used to connect the inverter to other inverters or
RS485
3: RS485 A the RS485 port on the data logger.
4: RS485 A
32
User Manual V1.1-2022-08-15 06 Electrical Connection
GM3000
Inverter
Grid
Three-phase circuit breaker Meter
Load
RS485+ Ethernet
RS485- SEC1000
Router Cloud
L3
CT
CT
N
PE
Load
33
06 Electrical Connection User Manual V1.1-2022-08-15
NOTICE
Connect the RS485 cable, meter cable, and DRED cable using a 6PIN communication terminal
as follows.
DRED
RS485/
Meter
1 2 5
4
7
6.5mm
6
2
1
25mm 3
3
M2
RS485/Meter DRED
0.3~0.4N·m
1: RS485 B 1: DRM1/5
2: RS485 B 2: DRM2/6
3: RS485 A 3: DRM3/7
4: RS485 A 4: DRM4/8
5: Meter + 5: REFGen
6: Meter - 6: Com/DRM0
4 COM
NOTICE
34
User Manual V1.1-2022-08-15 06 Electrical Connection
NOTICE
Connect the remote shutdown cable using a 2PIN communication terminal as follows.
RSD
RS485
1 2 5
4
6.5mm
3
2
1
25mm
3 4
2
1
M3 3
0.6~0.8N·m
RS485/Meter Remote
+: METER+/RS485 A shutdown
-: METER-/RS485 B +: DRM4/8
-: REFGen
35
06 Electrical Connection User Manual V1.1-2022-08-15
Plug a communication module into the inverter to establish a connection between the inverter
and the smartphone or web pages. The communication module can be a Bluetooth module, WiFi
module, LAN module, or 4G module. Set inverter parameters, check running information and
fault information, and observe system status in time via the smartphone or web pages.
NOTICE
• Refer to the delivered communication module user manual to get more introduction to the
module. For more detailed information, visit https://en.goodwe.com/.
• Remove the communication module using the unlock tool. The manufacturer shall not be
liable for the port damage if the module is removed without the unlock tool.
36
User Manual V1.1-2022-08-15 07 Equipment Commissioning
7 Equipment Commissioning
7.1 Check Items Before Switching Power ON
No. Check Item
The inverter is firmly installed in a clean place where is well-ventilated and easy to
1
operate.
The PE cable, DC input cable, AC output cable, and communication cable are connected
2
correctly and securely.
5 The voltage and frequency at the connection point meet the on-grid requirements.
7.2 Power On
Step 1 Turn on the AC switch between the inverter and the utility grid.
Step 2 (optional) Turn on the DC switch between the inverter and the PV string.
Step 3 Turn on the DC switch between the inverter and the PV String.
DC Switch
37
08 System Commissioning User Manual V1.1-2022-08-15
8 System Commissioning
8.1 Indicators and Button
Communication is reseting or
Single yellow blinking
restarting.
Off No communication.
38
User Manual V1.1-2022-08-15 08 System Commissioning
Communication is reseting or
Single Green Fast Blinking
restarting.
Off No communication.
Stop pressing the button for a period in any page, the LCD will get dark and go back to the initial
page, which means the parameter in that page has been saved successfully.
39
08 System Commissioning User Manual V1.1-2022-08-15
NOTICE
• Inverter software version shown in this document is V1.00.00.13. The screen shots are for
reference only. The actual display may differ.
• The name, range, and default value of the parameters is subject to change or adjust. The
actual display prevails.
• the power parameters should be set by professionals to prevent the generating capacity
from being influenced by wrong parameters
This part describes the menu structure, allowing you view inverter information and set
parameters more conveniently.
Main menu
Long press for 2s
Short press
Long press for 2s
Short press
Long press for 2s
Short press
Long press for 2s
Short press
Long press for 2s
Short press
Long press for 2s
Short press
Long press for 2s
Short press
Long press for 2s
Short press
Short press
and wait for 10s
Next page
40
User Manual V1.1-2022-08-15 08 System Commissioning
Previous page
Short press
Wait
Long press Long press for 2s Long press for 2s Long press for 2s
for 2s
Short press
4G and GPRS WiFi module Wait
module
Long press Wait
for 2s
Short press
Long press Wait
for 2s
Short press
Short press Long press for 2s Long press for 2s
Wait
Short press
Long press Long press for 2s Short press Short press Short press
for 2s Wait
Next page
41
08 System Commissioning User Manual V1.1-2022-08-15
Previous page
Long press for 2s Long press for 2s Long press for 2s Long press for 2s
Short press to select 0~1 Short press to select 0~9 Short press to select 0~9
Long press for 2s
Wait
Short press
Short press
Long press for 2s
Short press
Parameters Description
Home page. Indicates the real-time power of the inverter. Long press for 2s
Normal
to check the current safety code.
E-Today Check the generated power of the system for that day.
42
User Manual V1.1-2022-08-15 08 System Commissioning
Parameters Description
Indicates the specific inverter model. Long press for 2s to set the safety
Model code. Set the safety country in compliance with the local grid standards and
application scenario of the inverter.
Set time according to the actual time in the country/region where the
Set Time
inverter is located.
RSSI Indicates the received signal strength of the GPRS module and 4G module.
Restore the factory settings of the WiFi module. Reconfigure the WiFi
W/L Reload
module network parameters after restoring the factory settings,
PF Adjust Set the power factor of the inverter according to actual situation.
Shadow MPPT Enable the shadow scan function if the PV panels are shadowed.
Soft limit: Set the power feed into the utility grid according to local
requirements and standards.
Power Limit
Hard limit: The inverter and the utility grid will automatically disconnect
when the power feeds into the grid excesses the required limit.
Set the power feed back into the utility grid according to the actual
Set Power Limit
situation.
Set Modbus
Set the actual Modbus address.
Addr
With LVRT on, the inverter will stay connected with the utility grid when a
LVRT
short-term utility grid low voltage exception occurs.
With HVRT on, the inverter will stay connected with the utility grid when a
HVRT
short-term utility grid high voltage exception occurs.
Set the grid type according to the actual grid type. Supported grid type: star
Grid Type
grid and delta grid.
Set ARC ARC is optional and off by default. Enable or disable ARC accordingly.
USB Mode
Reserved for troubleshooting by after-sales service staff.
Select
43
08 System Commissioning User Manual V1.1-2022-08-15
SolarGo App
SolarGo App
User Manual
SEMS Portal
SEMS Portal
User Manual
44
User Manual V1.1-2022-08-15 09 Maintenance
9 Maintenance
9.1 Power Off the Inverter
DANGER
• Power off the inverter before operations and maintenance. Otherwise, the inverter may be
damaged or electric shocks may occur.
• Delayed discharge. Wait until the components are discharged after power off.
Step 1 Disconnect all the cables, including DC cables, AC cables, communication cables, the
communication module, and PE cables.
Step 2 Remove the inverter from the mounting plate.
Step 3 Remove the mounting plate.
Step 4 Store the inverter properly. If the inverter needs to be used later, ensure that the storage
conditions meet the requirements.
9.4 Troubleshooting
Perform troubleshooting according to the following methods. Contact the after-sales service if
these methods do not work.
Collect the information below before contacting the after-sales service, so tha the problems
can be solved quickly.
1. Inverter information like serial number, software version, installation date, fault time, fault
frequency, etc.
2. Installation environment, including weather conditions, whether the PV modules are
sheltered or shadowed, etc. It is recommended to provide some photos and videos to assist
in analyzing the problem.
3. Utility grid situation.
45
09 Maintenance User Manual V1.1-2022-08-15
46
User Manual V1.1-2022-08-15 09 Maintenance
47
09 Maintenance User Manual V1.1-2022-08-15
1. The inverter is
installed in a 1. Check the installation environment and
place with poor space of the inverter. Make sure that
ventilation. the ventilation meets heat dissipation
Over 2. The ambient requirements.
9
Temperature temperature is 2. Make sure that the fans are working
too high. properly and not covered or blocked.
3. The inverter 3. Check whether the operating ambient
is working temperature is too high.
improperly.
14 DC Bus High
15 SPI Fail
48
User Manual V1.1-2022-08-15 09 Maintenance
49
10 Technical Parameters User Manual V1.1-2022-08-15
10 Technical Parameters
Technical Data GW4K-DT GW5K-DT GW6K-DT GW8K-DT
Input
Output
50
User Manual V1.1-2022-08-15 10 Technical Parameters
Efficiency
Protection
PV Insulation Resistance
Integrated
Detection
DC Switch Integrated
AFCI Optional
General Data
Operating Temperature Range -30~+60 (60 °C for outdoor unconditioned with solar
(℃) effects.)
Smart Fan
Cooling Method Natural Convection
Cooling
51
10 Technical Parameters User Manual V1.1-2022-08-15
Weight (Kg) 15 16
354 × 433 ×
Dimension (W×H×Dmm) 354 × 433 × 147
155
Topology Non-isolated
Anti-corrosion Class C4
Protective class I
PV:C
The Decisive Voltage Class (DVC) AC:C
Com:A
52
User Manual V1.1-2022-08-15 10 Technical Parameters
Input
Output
53
10 Technical Parameters User Manual V1.1-2022-08-15
Efficiency
Protection
DC Switch Integrated
Type III(Type
DC Surge Protection Type III
II Optional)
AFCI Optional
General Data
Operating Temperature Range -30~60 (60 °C for outdoor unconditioned with solar
(℃) effects.)
54
User Manual V1.1-2022-08-15 10 Technical Parameters
Weight (Kg) 16 18 18 25
415 × 511 ×
Dimension (W×H×Dmm) 354 × 433 × 155
175
Topology Non-isolated
Anti-corrosion Class C4
PV:C
The Decisive Voltage Class (DVC) AC:C
Com:A
55
10 Technical Parameters User Manual V1.1-2022-08-15
Input
Output
56
User Manual V1.1-2022-08-15 10 Technical Parameters
Efficiency
Protection
DC Switch Integrated
AFCI Optional
General Data
Weight (Kg) 25
Dimension (W×H×Dmm) 415×511×175
Topology Non-isolated
57
10 Technical Parameters User Manual V1.1-2022-08-15
Anti-corrosion Class C4
AC Connector AC Connector
PV:C
The Decisive Voltage Class (DVC) AC:C
Com:A
*1: For Belgium Max. AC Active Power (W): GW4K-DT is 4000, GW5K-DT is 5000, GW6K-DT is
6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT is 15000,GW17KT-
DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is 4000,GW5000-SDT-20
is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20 is 10000, GW12K-SDT-20
is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-SDT-20 is 17000, GW20K-
SDT-20 is 20000.
*2: For Belgium Max. Output Apparent Power (VA): GW4K-DT is 4000, GW5K-DT is 5000,
GW6K-DT is 6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT
is 15000,GW17KT-DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is
4000,GW5000-SDT-20 is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20
is 10000, GW12K-SDT-20 is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-
SDT-20 is 17000, GW20K-SDT-20 is 20000.
*3: For Australia Max. Operating Altitude (m) is 3000;
*4: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive
Feedback.
58
User Manual V1.1-2022-08-15 10 Technical Parameters
Input
Output
59
10 Technical Parameters User Manual V1.1-2022-08-15
Efficiency
Protection
PV Insulation Resistance
Integrated
Detection
DC Switch Integrated
AFCI Optional
General Data
Operating Temperature Range -30~+60 (60 °C for outdoor unconditioned with solar
(℃) effects.)
60
User Manual V1.1-2022-08-15 10 Technical Parameters
Topology Non-isolated
Anti-corrosion Class C4
AC Connector AC Connector
PV:C
The Decisive Voltage Class (DVC) AC:C
Com:A
*1: For Belgium Max. AC Active Power (W): GW4K-DT is 4000, GW5K-DT is 5000, GW6K-DT is
6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT is 15000,GW17KT-
DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is 4000,GW5000-SDT-20
is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20 is 10000, GW12K-SDT-20
is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-SDT-20 is 17000, GW20K-
SDT-20 is 20000.
*2: For Belgium Max. Output Apparent Power (VA): GW4K-DT is 4000, GW5K-DT is 5000,
GW6K-DT is 6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT
is 15000,GW17KT-DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is
4000,GW5000-SDT-20 is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20
is 10000, GW12K-SDT-20 is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-
SDT-20 is 17000, GW20K-SDT-20 is 20000.
*3: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive
Feedback.
61
10 Technical Parameters User Manual V1.1-2022-08-15
Input
Output
170-240(According
Output Voltage Range (V) 180~270(According to local standard)
to local standard)
62
User Manual V1.1-2022-08-15 10 Technical Parameters
Efficiency
Protection
PV Insulation Resistance
Integrated
Detection
DC Switch Integrated
AFCI Optional
General Data
Operating Temperature Range -30~+60 (60 °C for outdoor unconditioned with solar
(℃) effects.)
63
10 Technical Parameters User Manual V1.1-2022-08-15
Topology Non-isolated
Anti-corrosion Class C4
AC Connector OT Terminal
PV: C
The Decisive Voltage Class (DVC) AC: C
Com: A
64
User Manual V1.1-2022-08-15 10 Technical Parameters
Input
Max. Short Circuit Current per MPPT (A) 37.5 37.5 37.5
Output
AC Grid Frequency Range (Hz) 45~55 / 55~65 45~55 / 55~65 45~55 / 55~65
65
10 Technical Parameters User Manual V1.1-2022-08-15
Efficiency
Protection
DC Switch Integrated
AFCI Optional
General Data
Weight (Kg) 26
66
User Manual V1.1-2022-08-15 10 Technical Parameters
Topology Non-isolated
Anti-corrosion Class C4
AC Connector OT Terminal
PV: C
The Decisive Voltage Class (DVC) AC: C
Com: A
*1: For Belgium Max. AC Active Power (W): GW4K-DT is 4000, GW5K-DT is 5000, GW6K-DT is
6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT is 15000,GW17KT-
DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is 4000,GW5000-SDT-20
is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20 is 10000, GW12K-SDT-20
is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-SDT-20 is 17000, GW20K-
SDT-20 is 20000.
*2: For Belgium Max. Output Apparent Power (VA): GW4K-DT is 4000, GW5K-DT is 5000,
GW6K-DT is 6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT
is 15000,GW17KT-DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is
4000,GW5000-SDT-20 is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20
is 10000, GW12K-SDT-20 is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-
SDT-20 is 17000, GW20K-SDT-20 is 20000.
*3: For Australia Max. Operating Altitude (m) is 3000;
*4: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive
Feedback.
67
10 Technical Parameters User Manual V1.1-2022-08-15
Input
Output
68
User Manual V1.1-2022-08-15 10 Technical Parameters
Efficiency
Protection
PV Insulation Resistance
Integrated
Detection
DC Switch Integrated
AFCI Optional
General Data
Operating Temperature Range -30~+60 (60 °C for outdoor unconditioned with solar
(℃) effects.)
69
10 Technical Parameters User Manual V1.1-2022-08-15
Weight (Kg) 15
Topology Non-isolated
Anti-corrosion Class C4
PV: C
The Decisive Voltage Class (DVC) AC: C
Com: A
*1: For Belgium Max. AC Active Power (W): GW4K-DT is 4000, GW5K-DT is 5000, GW6K-DT is
6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT is 15000,GW17KT-
DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is 4000,GW5000-SDT-20
is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20 is 10000, GW12K-SDT-20
is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-SDT-20 is 17000, GW20K-
SDT-20 is 20000.
*2: For Belgium Max. Output Apparent Power (VA): GW4K-DT is 4000, GW5K-DT is 5000,
GW6K-DT is 6000,GW8K-DT is 8000, GW10KT-DT is 10000,GW12KT-DT is 12000, GW15KT-DT
is 15000,GW17KT-DT is 17000, GW20KT-DT is 20000, GW25KT-DT is 25000,GW4000-SDT-20 is
4000,GW5000-SDT-20 is 5000,GW6000-SDT-20 is 6000,GW8000-SDT-20 is 8000, GW10K-SDT-20
is 10000, GW12K-SDT-20 is 12000,GW12KLV-SDT-20 is 12000, GW15K-SDT-20 is 15000, GW17K-
SDT-20 is 17000, GW20K-SDT-20 is 20000.
*3: For Australia Max. Operating Altitude (m) is 3000;
*4: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive
Feedback.
70
GoodWe Website