Rpi 08 FSG 1
Rpi 08 FSG 1
MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
SET FREE FSG(1)/FS3, FS5 SERIES
AND
SET FREE FXG/FX3 SERIES
Models
<Indoor Units>
• In-the-Ceiling Type
RPI-0.8FSG1 RPI-2.5FSG1 RPI-8FSG1
RPI-1.0FSG1 RPI-3.0FSG1 RPI-10FSG1
RPI-1.5FSG1 RPI-4.0FSG1
RPI-2.0FSG1 RPI-5.0FSG1
• 4-Way Cassette Type
RCI-1.0FSG2 RCI-2.5FSG2 RCI-5.0FSG2
RCI-1.5FSG2 RCI-3.0FSG2
RCI-2.0FSG2 RCI-4.0FSG2
• 2-Way Cassette Type
RCD-1.0FSG1 RCD-2.5FSG1 RCD-5.0FSG1
RCD-1.5FSG1 RCD-3.0FSG1
RCD-2.0FSG1 RCD-4.0FSG1
• Wall Type
RPK-1.0FSGM6 RPK-2.0FSGM6
RPK-1.5FSGM6 RPK-2.3FSGM6
• Floor Type
RPF-1.0FSG(E) RPF-1.5FSG(E)
• Floor Concealed Type
RPFI-1.0FSG(E) RPFI-1.5FSG(E)
• Ceiling Type
RPC-2.0FSG1 RPC-3.0FSG1 RPC-5.0FSG1
RPC-2.5FSG1 RPC-4.0FSG1
<Outdoor Units>
• FSG(1) Series
RAS-5FSG RAS-16FSG RAS-24FSG1
RAS-8FSG RAS-20FSG RAS-30FSG1
RAS-10FSG
• FS3, FS5 Series
RAS-5FS3 RAS-16FS3 RAS-24FS5
RAS-8FS3 RAS-20FS3 RAS-30FS5
RAS-10FS3
This service mamual provides the technical • FXG Series
information for the HITACHI Inverter-Driven RAS-8FXG RAS-10FXG
Multi-Split System Heat Pump Air • FX3 Series
Conditioners, “SET FREE, FSG(1)/FS3, FS5 RAS-8FX3 RAS-10FX3
and FXG/FX3 Series”.
Read this manual carefully before starting <System Equipment>
service activities. • Total Heat Exchangers
KPI-2521 KPI-5021 KPI-8021 KPI-10021
P5413553
RC
I
1. TROUBLESHOOTING
1.1 Initial Troubleshooting
1.1.1 Rotary Switch and Dip Switch Setting
(1) Indoor Unit
The PCB in the indoor unit is equipped with 7 types of dip switches and rotary switch. Before testing
unit, set these dip switches according to the following instructions. Unless these dip switches are
set in the field, the unit can not be operated.
Before setting dip switches, firstly turn OFF power source and set the position of the dip switches.
If the switches are set without turning OFF the power source, the switches can not function.
NOTE
The “” mark indicates position of dip switches. Figures show the setting before shipment.
23
7 9
8 into the groove
Rotary F 01 F 01 F 01 F 01 F 01 F 01 F 01 F 01
CD E
CD E
CD E
CD E
CD E
CD E
CD E
CD E
23
23
23
23
23
23
23
23
Switch
456
456
456
456
456
456
456
456
AB
AB
AB
AB
AB
AB
AB
AB
7 9 7 9 7 9 7 9 7 9 7 9 7 9 7 9
Setting 8 8 8 8 8 8 8 8
Rotary F 01 F 01 F 01 F 01 F 01 F 01 F 01 F 01
CD E
CD E
CD E
CD E
CD E
CD E
CD E
CD E
23
23
23
23
23
23
23
23
Switch
456
456
456
456
456
456
456
456
AB
AB
AB
AB
AB
AB
AB
AB
Setting
7 9 7 9 7 9 7 9 7 9 7 9 7 9 7 9
8 8 8 8 8 8 8 8
RPC(Before Alteration)
b. Optional Function Setting (DSW2) RPF, RPFI, RPI-8,10 and RPK RCD(Before Alteration)
No setting is required. RPI-0.8 to 1.5(Before Alteration)
Setting position before shipment is all OFF.
ON ON
1 2 3 4 5 6 7 8 OFF 1 2 OFF
c. Capacity Code Setting (DSW3)
No setting is required, due to setting before shipment. This switch is used for setting the capacity
code which corresponds to the Horse-Power of the indoor unit.
0.8 1.0 1.5 2.0 2.3 2.5 3.0 4.0 5.0 8.0 10.0
RCI
RPI
RCD
RPF and RPFI
RPK
: Available
Horsepower 0.8 1.0 1.3 1.5 1.8 2.0 2.3
ON ON ON ON ON ON ON
Setting
Position
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
OFF OFF OFF OFF OFF OFF OFF
Horsepower 2.5 2.8 3.0 4.0 5.0 8.0 10.0
ON ON ON ON ON ON ON
Setting
Position
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
OFF OFF OFF OFF OFF OFF OFF
1-1
d. Capacity Adjustment Setting (DSW4: for RPF, RPFI, RPI-8,10 and RPC(Before Alteration))
No setting is required. Setting position before shipment is all OFF.
Setting ON
Pattern 1 2 OFF
Horse-Power 0.8 to 10
Setting ON
Pattern 1 2 3 4 OFF
f. Unit Code Setting (DSW6; Except for RCI and RPK Model)
No setting is required. Setting positions of the model code for indoor units are shown below.
Setting ON
Pattern 1 2 OFF
Check to ensure that the #8 pin of DSW5 is correctly set according to the power supply of the
unit. If the setting is different from the power supply of the unit, it may cause the unit stoppage
due to alarm or the breakdown of the compressor.
NOTE
• By using switch DSW4, 7 and 8 the unit is started or stopped after 10 to 20 seconds after the switch is
operated.
• Make the outdoor unit No. clear to distinguish from other outdoor units for service and maintenance.
1-2
1 2 3 4
1 2 1 2 1 2 3 4
Set the pin at the ON side at emergency operation.
DSW10 Transmitting
Setting Item Pin No.
SR Cancellation of when fuse
Except No.1 Comp. Operation #1 B.S. Terminal Resistance is melted
Except No.2 Comp. Operation #2
ON ON ON
Except No.3 Comp. Operation #3
Except No.4 Comp. Operation #4
1 2 1 2 1 2
SEG2 SEG1
B.S.: Before Shipment, NSR: No Setting is Required, SR: Setting Required
1-3
DSW1 Ref. System No. Setting DSW2 Capacity Setting DSW3 Height Difference
SR When H-Link is used, setting NSR Each outdoor unit is set as shown SR
is required. below before shipment.
B.S.
ON ON * The O.U. is located higher than I. U.
RAS-24FSG1 RAS-30FSG1 (0 to 50m)
RAS-24FS5 RAS-30FS5 * The O.U. is located lower than I.U.
1 2 3 4 1 2
ON ON (0 to 20m)
No.0 Unit Setting Condition
Set the unit number of outdoor unit 1 2 3 4 1 2 3 4 ON
* The O.U. is located lower than I.U.
at each refrigerant cycle. (20 to 40m)
(Setting before shipment is unit 0.) 1 2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Setting Item Pin No.
Enforced Except No.1 Circulator Function of Heating Thermo-OFF #1
Compressor Compressor Night Shift (Low Noise) #2
Stop Operation
Cancellation of Outdoor Ambient Temp. Limit of Heating #3
ON ON
Cancellation of Outdoor Ambient Temp. Limit of Cooling #4
Defrosting Condition Change for Cold Area #5
1 2 3 4 5 6 1 2 3 4 5 6
Combination of Indoor Units are more than 16 #8
Setting Item Pin No. SR Set the dip switch according to your requirements.
50 to 75m 75 to 120m Except No.2 Comp. Operation #1 Setting Item Pin No.
B.S.
ON ON Except No.3 Comp. Operation #2 Power Supply
ON (415V: ON, 380V and 220V: OFF) #2
Except No.4 Comp. Operation #3
1 2 1 2 Except No.5 Comp. Operation #4 Power Supply
1 2 3 4 (220V: ON, 380V and 415V: OFF) #3
SEG2 SEG1
DSW1 DSW2 DSW3 PSW1 PSW2 PSW3
DSW4 DSW5
DSW6 DSW7 DSW8 DSW9
1-4
Before setting dip switches, firstly turn OFF power source and set the position of the dip switches.
If the dip switches are set without turning OFF the power source, the switches can not function.
NOTE
The “■” mark indicates position of dip switches. The figures below show the setting before
shipment.
DSW2
DSW5
DSW2 DSW5
ON ON
OFF OFF
1 2 3 4 5 6 1 2
1-5
Example for Electrical Wiring Connection of FSG, FS3, FSG1 and FS5 System
Outdoor Unit (5 to 20HP)
<380-415V/50Hz, 380V/60Hz>
Max. 4 Units / Power Supply Line (5, 8 and 10HP)
Outdoor Unit 1 Outdoor Unit / Power Supply Line (16 and 20 HP)
RAS-5FS3
RAS-8FS3
RAS-10FS3 No. 0 System No. 1 System No. 3 System
Outdoor Unit Outdoor Unit Outdoor Unit
RAS-16FS3
TB1 TB2 TB1 TB2 TB1 TB2
RAS-20FS3 L1 L2 L3 N 1 2 L1 L2 L3 N 1 2 L1 L2 L3 N 1 2
RAS-5FSG
RAS-8FSG
RAS-10FSG
RAS-16FSG
RAS-20FSG
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System)
ELB
ELB Distribution Box or Pull Box *2
Distribution Box or Pull Box *2
FUSE
Main Switch
ELB
3N
380V/50 Hz
415V/50 Hz
415V/60 Hz L1 L2 N L1 L2 N
TB1 TB1
No. 0 No. 1
Indoor Unit Indoor Unit
1N (3N ) TB2 Remote TB2 Remote
220V/50 Hz 1 2 A B Control 1 2 A B Control
240V/50 Hz Cable Cable
(Shielded Twist (Shielded Twist
220V/50 Hz Pair Cable) *1 Pair Cable) *1
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System) Remote Remote
Control Control
Switch Switch
TB : Terminal Board (PC-P1H) (PC-P1H)
PCB : Printed Circuit Board
: Field Wiring
: Field Supplied
No. 0 System Indoor Units No.1 System Indoor Units
: Optional Accessory (Max. 16 Units per Refrigerant Cycle)
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth.
*2: It is need for China and Australia only.
<220V/60Hz>
Outdoor Unit
RAS-5FS3 No. 0 System No. 1 System No. 3 System
Outdoor Unit Outdoor Unit Outdoor Unit
RAS-8FS3
TB1 TB2 TB1 TB2 TB1 TB2
RAS-10FS3 R S T 1 2 R S T 1 2 R S T 1 2
RAS-16FS3
RAS-20FS3
RAS-5FSG
RAS-8FSG
RAS-10FSG
RAS-16FSG
RAS-20FSG
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System)
ELB
Distribution Box or Pull Box *2
ELB
Distribution Box or Pull Box *2
FUSE
Main Switch
ELB
3
220V/60Hz
L1 L2 N L1 L2 N
TB1 TB1
No. 0 No. 1
Indoor Unit Indoor Unit
TB2 Remote TB2 Remote
1 Control Control
1 2 A B 1 2 A B
220V/60 Hz Cable Cable
(Shielded Twist (Shielded Twist
Pair Cable) *1 Pair Cable) *1
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System) Remote Remote
Control Control
Switch Switch
TB : Terminal Board (PC-P1H) (PC-P1H)
PCB : Printed Circuit Board
: Field Wiring
: Field Supplied
No. 0 System Indoor Units
: Optional Accessory No.1 System Indoor Units
(Max. 27 Units per Refrigerant Cycle...RAS-24FSG1, RAS-24FS5
Max. 32 Units per Refrigerant Cycle...RAS-30FSG1, RAS-30FS5)
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth.
*2: It is need for China and Australia only.
1-6
ELB
ELB Distribution Box or Pull Box *2
Distribution Box or Pull Box *2
FUSE
Main Switch
ELB
3N
380V/50 Hz
415V/50 Hz
415V/60 Hz L1 L2 N L1 L2 N
TB1 TB1
No. 0 No. 1
Indoor Unit Indoor Unit
1N (3N ) TB2 Remote TB2 Remote
220V/50 Hz 1 2 A B Control 1 2 A B Control
240V/50 Hz Cable Cable
(Shielded Twist (Shielded Twist
220V/50 Hz Pair Cable) *1 Pair Cable) *1
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System) Remote Remote
Control Control
Switch Switch
TB : Terminal Board (PC-P1H) (PC-P1H)
PCB : Printed Circuit Board
: Field Wiring
: Field Supplied
No. 0 System Indoor Units
: Optional Accessory
(Max. 27 Units per Refrigerant Cycle...RAS-24FSG1, RAS-24FS5
Max. 32 Units per Refrigerant Cycle...RAS-30FSG1, RAS-30FS5)
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth.
*2: It is need for China and Australia only.
<220V/60Hz>
Outdoor Unit No. 0 System
Outdoor Unit
RAS-24FSG1 TB1 TB2
RAS-30FSG1 R S T 1 2
RAS-24FS5
Operating Line (Shielded Twist Pair Cable)
RAS-30FS5 DC5V (Non-Pole Transmission H-LINK System)
ELB
Distribution Box or Pull Box *2
ELB
Distribution Box or Pull Box *2
FUSE
Main Switch
ELB
3
220V/60Hz
L1 L2 N L1 L2 N
TB1 TB1
No. 0 No. 1
Indoor Unit Indoor Unit
TB2 Remote TB2 Remote
1 Control Control
1 2 A B 1 2 A B
220V/60 Hz Cable Cable
(Shielded Twist (Shielded Twist
Pair Cable) *1 Pair Cable) *1
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System) Remote Remote
Control Control
Switch Switch
TB : Terminal Board (PC-P1H) (PC-P1H)
PCB : Printed Circuit Board
: Field Wiring
: Field Supplied
No. 0 System Indoor Units
: Optional Accessory
(Max. 27 Units per Refrigerant Cycle...RAS-24FSG1, RAS-24FS5
Max. 32 Units per Refrigerant Cycle...RAS-30FSG1, RAS-30FS5)
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth.
*2: It is need for China and Australia only.
1-7
Table 1.1 Electrical Data and Recommended Wiring, Breaker Size/1 Outdoor Unit <FS Series>
ELB
Max. Power
Running Supply Nominal Fuse
Power Nominal
Model Current Line Sensitive
Supply Current
Current
(A) (φmm) (A) (mA) (A)
RAS-5FSG
18 MLFC 0.75SQ 20 20
RAS-5FS3
RAS-8FSG
28 MLFC 2SQ
RAS-8FS3
40 40
RAS-10FSG
35 MLFC 3.5SQ 30
RAS-10FS3
RAS-16FSG 380-415V >57
57 MLFC 5.5SQ 100
RAS-16FS3 /50Hz (Ex. 100)
RAS-20FSG >71
71 MLFC 8SQ 100
RAS-20FS3 (Ex. 100)
RAS-24FSG1
74 MLFC 8SQ 100 80
RAS-24FS5
100
RAS-30FSG1
87 MLFC 14SQ 120 100
RAS-30FS5
RAS-5FSG
18 MLFC 0.75SQ 20 20
RAS-5FS3
RAS-8FSG
30 MLFC 2SQ 30 30
RAS-8FS3
RAS-10FSG
36 MLFC 3.5SQ 40 30 40
RAS-10FS3
RAS-16FSG
380V/60Hz 58 MLFC 5.5SQ 60 60
RAS-16FS3
RAS-20FSG
72 MLFC 8SQ 75 75
RAS-20FS3
RAS-24FSG1
77 MLFC 8SQ 100 80
RAS-24FS5
100
RAS-30FSG1
90 MLFC 14SQ 120 100
RAS-30FS5
RAS-5FSG
27 MLFC 2SQ 30 30
RAS-5FS3
RAS-8FSG
45 MLFC 3.5SQ 50
RAS-8FS3
60
RAS-10FSG
55 MLFC 5.5SQ 60 30
RAS-10FS3
RAS-16FSG
220V/60Hz 88 MLFC 14SQ 100 100
RAS-16FS3
RAS-20FSG
112 MLFC 14SQ 120 125
RAS-20FS3
RAS-24FSG1
132 MLFC 22SQ 150 150
RAS-24FS5
100
RAS-30FSG1
141 MLFC 22SQ 150 150
RAS-30FS5
ELB: Earth Leakage Breaker
MLFC: Flame Retardant Polyflex Wire
NOTE:
Regarding the wiring or breakers, follow to the local code.
1-8
RAS-8FXG
RAS-8FX3
RAS-10FXG No. 0 System No. 1 System No. 3 System
Outdoor Unit Outdoor Unit Outdoor Unit
RAS-10FX3
TB1 TB2 TB1 TB2 TB1 TB2
L1 L2 L3 N 1 2 L1 L2 L3 N 1 2 L1 L2 L3 N 1 2
Distribution Box or Pull Box *2 Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System)
ELB
ELB Distribution Box or Pull Box *2
FUSE
Main Switch
ELB No. 1 System
CH Units
3N
380V/50 Hz No. 0 Group No. 1 Group
415V/50 Hz CH Unit CH Unit
415V/60 Hz
1N (3N )
220V/50 Hz
240V/50 Hz
220V/50 Hz
TB : Terminal Board
L1 L2 N L1 L2 N
PCB : Printed Circuit Board
TB1 TB1
: Field Wiring
No. 0 No. 1
: Field Supplied Indoor Unit Indoor Unit
: Optional Accessory TB2 Remote TB2 Remote
1 2 A B Control 1 2 A B Control
Cable Cable
(Shielded Twist (Shielded Twist
Pair Cable) *1 Pair Cable) *1
Operating Line (Shielded Twist Pair Cable)
DC5V (Non-Pole Transmission H-LINK System) Remote Remote
Control Control
Switch Switch
(PC-P1H) (PC-P1H)
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth.
*2: It is need for China and Australia only.
Table 1.2 Electrical Data and Recommended Wiring, Breaker Size/1 Outdoor Unit <FX Series>
ELB
Max. Power
Running Supply Nominal Fuse
Power Nominal
Model Current Line Sensitive
Supply Current
Current
(A) (φmm) (A) (mA) (A)
RAS-8FXG
32 MLFC 2SQ
RAS-8FX3 380-415V 40 30 40
RAS-10FXG /50Hz
35 MLFC 3.5SQ
RAS-10FX3
ELB: Earth Leakage Breaker
MLFC: Flame Retardant Polyflex Wire
NOTE:
Regarding the wiring or breakers, follow to the local code.
1-9
1 Turn on All Indoor Units All the Indoor Units Connected to the Outdoor Unit
3 Auto-addressing Starts During auto-addressing, the following items can be checked using the
outdoor unit's on-board 7-segment LED display.
Outdoor Unit
(1) Disconnection of power supply to the indoor unit.
Printed
(2) Reverse connection of the operating line between the outdoor and
Circuit Board
indoor units.
PCB1
In this case, "03" appears after 30 seconds.
(3) Duplication of indoor unit number. See Alarm Code 35.
Normal
(1) The outdoor unit's on-board 7-segment LED display is not indicated.
Case
(2) The outdoor unit's on-board 7-segment LED display indicates as follows if there is something wrong.
Abnormal
(B) Disconnection of the
Case
operating line between the continues to flash after 30 seconds.
outdoor and indoor units.
(C) Duplicated settings of the indoor unit number DIP switch DSW1 (Refer to the description of
alarm code "35", in the item 1.2.2, "Troubleshooting by Alarm Code".)
1-10
1-11
1-12
1.1.5 Failure of Power Supply to Indoor Unit and Remote Control Switch
Lights and LCD are not Indicated.
Not Operated
If fuses are melted or a breaker is activated, investigate the cause of over current and take
necessary action.
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Measure voltage
Power Failure or Power is Not ON by volt-meter. Supply power.
Replace the AC
Failure of AC Chopper
chopper for indoor
for Indoor Fan
fan and fuse.
Replace the AC
Failure of AC Chopper
chopper for indoor
for Indoor Fan
fan and fuse.
Measure voltage
Failure of Transformer at Indoor Unit Side at secondary side. Replace the transformer.
Replace cable or
Disconnected Cable of Remote Control Switch Connect the cable. repair it.
Insufficient Connection
or Incorrect Connection
Insufficient of Indoor Unit PCB
Contacting at
Connectors of Check connectors. Correctly connect it.
Remote Control Insufficient Connection
Switch or Incorrect Connection
of PCB in Remote
Control Switch
1-13
(1.1.5 Failure of Power Supply to Indoor Unit and Remote Control Switch)
1.1.6 Abnormal Transmission between Remote Control Switch and Indoor Unit
“RUN” Lamp on Remote Control Switch:
Flickering every 2 seconds
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
1-14
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
"RUN" light is
ON and LCD Failure of
is indicated. Magnetic Measure voltage
Insufficient Replace PCB for
However, the Switch for between contacting
Contacting outdoor unit.
system does Outdoor Unit parts.
not operated. Fan Motor
(ex.
The indoor, Measure resistance
Failure of Comp. Motor
outdoor fans between two wires.
or compressor Replace compressor.
does not
operate.) Check for abnormal
Failure of Comp.
sound from comp.
Failure of
Check magnetic
Magnetic Insufficient Replace magnetic
switch activates
Switch for Contacting switch.
correctly or not.
Comp.
Disconnected
Correctly connect
Wiring to Check connections.
wiring.
Failure of PCB
One of PCBs
Failure of Check PCB by Replace PCB
PCB self-checking *1). if failed.
Failure of
Failure of Thermistor
Check it by
Air Inlet
Check Mode *2).
The Comp. Thermistor Disconnection Replace or correctly
does not Stop of Thermistor connect wires if
or Start even abnormality exists.
if the Setting
temperature Abnormality of Remote
on LCD is Check it by Test Run.
Control Switch Cord
Changed *3)
1-15
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
1-16
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Failure of
Failure of Thermistor Replace or correctly
Discharge Check thermistor by
connect wiring when
Air Temp. Disconnected self-checking *2).
it is abnormal.
Thermistor Wire of
Thermistor
Failure of Failure of
Thermistor Thermistor Replace of correctly
for Outdoor
connect when it is
Evaporating Disconnected abnormal.
Temp. during Wire of
Heating Thermistor
Disconnected
Measure resistance
4-Way Valve
of coil.
Failure of Coil
Replace 4-Way valve.
4-Way Valve Incorrect
Activation of Enforced power supply.
No Defrosting 4-Way Valve
Operation Mode
is Available
Disconnected Control Wires
during Heating Correctly connect
between Indoor Unit and Check connectors.
Operation or wiring.
Outdoor Unit and CH Unit
Defrosting
Operation is
Continued Disconnected Correctly connect
Check connectors.
Failure of Wires to PCB wiring.
Outdoor Unit
PCB Failure of Check it by Replace it when check
PCB self-checking *1). mode is not available.
Check PCB by
Light and Replace if PCB is failed.
self-checking *1).
LCD Indication
Failure of PCB in Indoor Unit
on Remote
or Remote Control Switch
Control Switch
are Kept ON
1-17
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Clogged
Strainer in
Indoor Unit Check temp. difference
Replace strainer in
or CH Unit at inlet and outlet of
indoor unit.
Clogging at strainer.
Low Pressure
Piping
Clogging at
Low Pressure Check temp. difference. Remove clogging.
Piping
1-18
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Check Clogging of
Outdoor Unit Remove clogging.
Heat Exchanger.
Obstacles at inlet or
Insufficient outlet of outdoor unit Remove obstacles.
Air Flow to heat exchanger?
Outdoor Unit
Heat Is service space for
Exchanger Secure service space.
outdoor unit sufficient?
Excessively
Check expansion valve Correctly charge
Excessively Charged
opening. refrigerant.
High Refrigerant
Discharge Non-
Pressure Check each temp. Charge refrigerant
Condensed
and pressure. after vacuum pumping.
Gas in Cycle
Clogging of
Discharge Check for clogging. Remove clogging.
Piping
Insufficient
Cooling Check for clogging. Remove clogging.
Operation
Is thermistor installed
correctly on Correctly install it.
compressor?
Failure of
Bypass Check for leakage of
Replace solenoid valve.
Solenoid solenoid valve.
Excessively Valve
Low Suction
Pressure Malfunction
Check temp. difference
or Internal
between inlet and Replace 4-way valve.
Leakage of
outlet of 4-way valve.
4-Way Valve
1-19
Indoor Heat Load is Greater Calculate heat load. Replace the unit with
than Heating Capacity a bigger unit.
Is thermistor
installed correctly Correctly install it.
on compressor?
Insufficient Clogging of
Heating Indoor Unit/ Check temp. difference Replace strainer for
Operation Excessively CH Unit/ between inlet and outlet outdoor unit, indoor
Low Outdoor Unit of strainer. unit or CH unit.
Suction Strainer
Pressure
Clogging
Check temp. difference
of Suction Remove clogging.
of each part.
Piping
Excessively
Low
Air Temp. Check for any Remove cause of
through short-circuited air short-circuited air.
Outdoor Unit to outdoor unit.
Heat
Exchanger
Defrosting is
Check thermistor for Replace thermistor
Insufficiently
defrosting. for defrosting.
Completed
1-20
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Excessively
High Air
Excessively Temp. to Check whether or not Remove cause of
High Indoor Unit short-circuited air exists. short-circuited air.
Discharge Heat
Pressure Exchanger
Excessively
Check expansion valve Correctly charge
Charged
opening. refrigerant.
Refrigerant
Non-
Condensate Check refrigerant Recharge refrigerant
Gas in Ref. quantity. *1) after vacuum pumping.
Insufficient Cycle
Heating
Operation Clogging of
Discharge Check for clogging. Remove clogging.
Pr. Piping
Failure of
Bypass Check for leakage of
Replace solenoid valve.
Solenoid solenoid valve.
Excessively Valve
High Suction
Pressure Malfunction
Check temp. difference
or Internal
between inlet and outlet Replace 4-way valve.
Leakage of
of 4-way valve.
4-Way Valve
1-21
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
1-22
44 Low Pressure Increase Protection Activating Overload to Indoor in Cooling, High Temperature of
Outdoor Air in Heating Expansion Valve Open Lock
45 Pressure High Pressure Increase Protection Activating Overload Operation. Excessive Refrigerant
Clogging of Heat Exchanger
46 High Pressure Decrease Protection Activating Insufficient Refrigerant
47 Low Pressure Decrease Protection Activating Insufficient Refrigerant. Expansion Valve Close
Lock. Refrigerant Leakage.
51 Abnormality of Current Sensor for Inverter Failure of Sensor on Inverter PCB
52 Overcurrent Protection Activating Overload, Overcurrent, Locked to Compressor
53 Inverter IPM Protection Activating Automatic Stoppage of IPM (Overcurrent, Low
Voltage or Overheating)
1-23
Alarm
Code Activation of Safety Device in Indoor Unit
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the contact between #1 and #2 of CN14 is not closed over 120
seconds during the cooling, fan or heating operation.
Yes
Faulty PCB
CN10 LED4
CN13 CN14
R24
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Faulty
Check connections. Repair connection.
Connection
Check PCB by
Faulty Indoor Unit PCB Replace it if faulty.
self-checking *1).
1-24
Alarm
Code Activation of Safety Device in Outdoor Unit
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when one of safety devices is activated during compressor running.
No Is Y52C1 of No
Does CMC1 ON 7-segments ON?
Faulty PCB1
when starting? (when in check
mode "SC")
Yes No
Yes
Is the voltage
between PCN3 #1 No (No Voltage)
and faston terminal Faulty PCB1
"N" 220V or 240V
during Y52C1 ON?
No (No Looseness)
Yes Check Wiring Connection
Except for PCB1
Normal PCB1
Check activation of the following safety devices. Remove the cause after checking.
(1) High Pressure Switch
(PSH: 3.0MPa (30 kgf/cm2G) for FS3, FS5 and FX3 Series
3.3MPa (33 kgf/cm2G) for FSG, FSG1 and FXG Series)
Check Item
Connector Faston
Power Supply
for CMC1 Terminal
380-415V/50Hz
PCN3 N
380V/60Hz
220V/60Hz PCN3 S1
1-25
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Clogging of Heat
Remove clogging.
Exchanger?
Measure discharge
Faulty
pressure.
Pressure Replace it if faulty.
Check continuity after
Switch
decreasing of pressure.
Faulty High
Pressure Insufficient Measure resistance Repair looseness.
Switch Contacting by tester. Replace connector.
Incorrect
Check connections. Repair connections.
Connection
1-26
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Check connecting
Replace connector.
wiring and connectors.
Check attaching
state of discharge Reattach thermistor.
gas thermistor.
Activation of
High Pressure Faulty Gas Bypass Replace gas bypass
Check for clogging.
Switch due to Solenoid Valve solenoid valve.
Excessively
High Discharge
Pressure Check cycle operating
Charge refrigerant
Overcharged Refrigerant temp. and expansion
correctly.
valve opening.
1-27
Alarm
Code Abnormal Transmitting between Indoor Units and Outdoor Unit
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
or the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when abnormality is maintained for 3 minutes after normal transmitting
between indoor units and outdoor unit, and also abnormality is maintained for 30 seconds after the
micro-computer is automatically reset.
The alarm is indicated when the abnormal transmitting is maintained for 30 seconds from starting of
the outdoor unit.
Investigate the cause of overcurrent and take necessary action when fuses are melted or the
breaker for the outdoor unit are activated.
Regarding RCI-FSG2, RCD-FSG1, RPI-FSG1 and RPK-FSGM* Series, non-pole checking is not
required.
1-28
Is DSW10-1P No
(Terminal Resistance) Set it correctly.
on PCB1 ON?
Yes
Is the voltage
No between faston No
Is LED1 (red) on Check the fuses of
terminal "R1" and outdoor unit power
PCB1 ON?
"N" of PCB1 220V supply.
Yes or 240V?
Yes
Remove CN2 of
PCB1. *1) Is connector (PCN1, Yes
Plug PCN1 and CN1
CN1) for transformer
correctly.
is loosened?
No Outdoor
Yes Unit
Is LED3 (yellow) Yes
on PCB1 ON? Is the fuse for
Replace fuse.
PCB1 melted?
No No
Faulty PCB1
Is LED3 (yellow) No
on PCB1 flickering
more than once in
10 seconds? PCB1: Outdoor Unit Printed Circuit Board
Yes PCB1': Indoor Unit Printed Circuit Board
Connect CN2 of
PCB1.
Is PCB1' setting No
Non-pole operating. Set it correctly.
*2)
Yes
Yes Is LED3 (yellow) Yes
Is LED3 on
ON even if CN2 of Faulty PCB1'.
PCB1' ON?
PCB1' is removed?
No
No
Check other indoor units.
Faulty PCB1.
*1): In case that terminal resistance (DSW10-1P) is OFF when H-Link Connection is performed.
Set the terminal resistance to ON when CN2 is removed.
Set the terminal resistance to OFF when CN2 is reconnected.
*2): PCB1' Factory Setting for Non-Pole Transmitting
Check Item
Item Setting Position Power Supply Faston Terminal
SW2 Left Side (New Transmission Side) 380-415V/50Hz
between R1 and N
JP1 Short Circuited 380V/60Hz
CN2 Transmission Wire Connecting 220V/60Hz between R1 and S1
CN18 Non-Occupied
1-29
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
1-30
Alarm
Code Abnormal Transmitting between Indoor Units and Outdoor Unit
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
or the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when abnormality is maintained for 3 minutes after normal transmitting
between indoor units, CH units and outdoor unit, and also abnormality is maintained for 30 seconds
after the micro-computer is automatically reset.
The alarm is indicated when the abnormal transmitting is maintained for 30 seconds from starting of
the outdoor unit.
Investigate the cause of overcurrent and take necessary action when fuses are melted or the
breaker for the outdoor unit are activated.
Regarding RCI-FSG2, RCD-FSG1, RPI-FSG1 and RPK-FSGM Series, non-pole checking is not
required.
1-31
Is DSW10-1P No
(Terminal Resistance) Set it correctly.
on PCB1 ON? *1)
Yes
Is the voltage
No between faston No
Is LED1 (red) on Check the fuses of
terminal "R1" and outdoor unit power
PCB1 ON?
"N" of PCB1 220V supply.
Yes or 240V?
Yes
Remove CN2 of
PCB1. *2) Is connector (PCN1, Yes
Plug PCN1 and CN1
CN1) for transformer
correctly.
is loosened?
No Outdoor
Yes Unit
Is LED3 (yellow) Yes
on PCB1 ON? Is the fuse for
Replace fuse.
PCB1 melted?
No No
Faulty PCB1
Is LED3 (yellow) No
on PCB1 flickering
more than once in
10 seconds? PCB1: Outdoor Unit Printed Circuit Board
Yes PCB1': Indoor Unit Printed Circuit Board
Connect CN2 of
PCB1.
Is DSW5-1P (End No
Terminal Resistance) Set it correctly.
of PCB(1) ON?
Yes
No Is voltage between No
Is LED1 (red) on "R1" and "N" of PCN1
Check CH unit wiring.
PCB(1) ON? on PCB(1) 220V
or 240V
Yes
Yes
To Next Page
1-32
Yes
Is LED2 (yellow)
on PCB(1) ON?
No
Faulty PCB(1)
Is LED2 (yellow) No No
on PCB(1) flickering Are other units in CH
more than once in same condition? Unit
10 seconds?
Yes
Yes Faulty PCB1
Connect CN8 of
PCB(1).
Is PCB1' setting No
Non-pole operating. Set it correctly.
*3)
Yes
Yes Is LED3 (yellow) Yes
Is LED3 on
ON even if CN2 of Faulty PCB1'.
PCB1' ON?
PCB1' is removed?
No
No
Check other indoor units.
Faulty PCB(1)
*2): In case that terminal resistance (DSW10-1P) is OFF when H-Link Connection is performed.
Set the terminal resistance to ON when CN2 is removed.
Set the terminal resistance to OFF when CN2 is reconnected.
*3): PCB1' Factory Setting for Non-Pole Transmitting
Check Item
Item Setting Position Power Supply Faston Terminal
SW2 Left Side (New Transmission Side) 380-415V/50Hz
between R1 and N
JP1 Short Circuited 380V/60Hz
CN2 Transmission Wire Connecting 220V/60Hz between R1 and S1
CN18 Non-Occupied
1-33
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Measure voltage
Power Failure or No Power Supply Supply power.
by tester.
Measure output
Incorrect Power Supply Circuit of PCB1 Replace PCB1.
voltage of PCB1 *2)
Disconnected Wires
Check connections. Correctly connect wires.
Faulty PCB to PCB
(Outdoor Unit,
Indoor Unit)
Faulty PCB Replace it if faulty.
1-34
Alarm
Code Abnormal Transmitting between Inverter and Outdoor PCB1, 3
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the unit
No. and alarm code are indicated on the display of the outdoor unit PCB1.
This alarm is indicated when abnormality is maintained for 30 seconds after normal transmitting between the
outdoor unit PCB1 and inverter PCB3, and also abnormality is maintained for 30 seconds after the micro-
computer is automatically reset. The alarm is indicated when the abnormal transmitting is maintained for 30
seconds from starting of the outdoor unit. (In case of 5 to 20HP)
This alarm is indicated when abnormality is maintained for 30 seconds after normal transmitting between the
outdoor unit PCB1 and ISPM, and also abnormality is maintained for 30 seconds after the micro-computer is
automatically reset. The alarm is indicated when the abnormal transmitting is maintained for 30 seconds from
starting of the outdoor unit. (In case of 24 and 30HP)
No
Is LED2 (green) on Disconnect CN14
PCB1 flickering? of PCB1.
Yes
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
1-35
Alarm
Code Abnormality of Picking up Phase Signal
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the main power source phase is reversely connected or one
phase is not connected.
Yes
Single Phase Correctly connect each phase
(Is there any phase not connected?) of power source.
PCB1 is normal
No
Yes
Correctly connect each phase
Reverse Phase Connection?
of power source.
PCB1 is normal
No
Yes
Is there any excessively voltage
Abnormality with Power Source.
decrease at power source?
PCB1 is normal
No
NOTE:
PCB1: Outdoor Unit Printed Circuit Board
Voltage for unit to
be suspended. Running Voltage:
"B" V
Power Supply "A" "B"
380-415V, 50Hz 342 to 456
323
Starting Voltage: 380V, 60Hz 342 to 418
Less than "A" V 220V, 60Hz 187 198 to 242
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
1-36
Alarm
Code Excessively Low or High Voltage for Inverter (For 5 to 20HP)
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when voltage between terminal “P” and “N” of transistor module (IPM) is
insufficient and its occurrence is three times in 30 minutes. In the case that the occurrence is smaller
than 2 times, retry is performed.
Restart operation.
Yes
*1): If capacitor has high voltage, perform the high voltage discharge work refer to item 1.3.6.
*2): Checking procedures of diode module is indicated in item 1.3.6.
*3): DC voltage measuring position:
IPM “P” Terminal to “+” Terminal of Tester, “N” Terminal to “-” Terminal of Tester
Measuring Position: DC 1000V
1-37
Alarm
Code Excessively Low or High Voltage for Inverter (For 24 and 30HP)
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the alarm code is indicated on the display of the outdoor unit PCB.
This alarm code is indicated when voltage between terminal “P” and “N” of inverter module (ISPM) is
insufficient and its occurrence is three times in 30 minutes. In the case that the occurrence is smaller
than 2 times, retry is performed.
Restart operation.
Yes
CN207 CN206
N TB2
RB
R201
N
R200
+ P ZN20
LED201
*1): If capacitor has high voltage, perform the high voltage
- P1
TB3
ZN202
discharge work refer to item 1.3.6.
P R216
R215
1-38
Alarm
Code Decrease of Discharge Gas Superheat
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
In the case that the discharge gas superheat less than 15 deg. at the top of the compressor is
maintained for 30 minutes, retry operation is performed. However, when the alarm occurs again
within 90 minutes, this alarm code is indicated.
Is the thermistor on No
Position of Thermistor
top of compressor Faulty Thermistor
good? *1) THM8(Td1) THM8(Td1) THM9(Td2)
Yes
Is the thermistor No
installed correctly Install it correctly.
on the compressor? for Inverter Drive for Inverter for Constant
Drive Speed Drive
Yes
Heating RAS-5FSG, RAS-5FS3 RAS-8FSG, RAS-8FS3
Is it at cooling or RAS-10FSG, RAS-10FS3
heating mode when the Heating Operation RAS-8FXG, RAS-8FX3
alarm has occurred? RAS-10FXG, RAS-10FX3
1-39
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Measure pressure.
Correctly charge
Overcharged Refrigerant (Refer to Figure in
refrigerant.
Test Run of TCII.)
Replace thermistor
Fault Measure resistance.
if faulty.
Faulty
Discharge Incorrect Check mounting state. Correctly mount
Gas Mounting (Refer to page 1-39.) thermistor.
Thermistor
Remove looseness,
Incorrect
Check connections. replace connector or
Connection
repair connections.
1-40
This alarm is indicated when the following conditions occurs three times within one hour;
(1) The temperature of the thermistor on the top of the compressor is maintained higher than 132°C
for 10 minutes, or (2) The temperature of the thermistor on the top of the compressor is maintained
higher than 140°C for 5 seconds.
Position of Thermistor
Is the thermistor on No
THM8 (Td1) THM8 (Td1) THM9 (Td2)
top of compressor Faulty Thermistor
good?
See page 1-53 for the
Yes thermistor resistance.
Is the thermistor No
for Inverter Drive for Inverter for Constant
installed correctly Install it correctly.
Drive Speed Drive
on the compressor?
Yes RAS-5FSG, RAS-5FS3 RAS-8FSG, RAS-8FS3
RAS-10FSG, RAS-10FS3
Heating RAS-8FXG, RAS-8FX3
Is it at cooling or RAS-10FXG, RAS-10FX3
heating mode when the Heating Operation
alarm has occurred? THM8 (Td1) THM9 (Td2) THM12 (Td3) THM13 (Td4)
20, 24, 30HP
Cooling only
Cooling Operation
Check the outdoor unit Check the outdoor unit for Inverter
Drive for Constant Speed Drive
PCB if the compressor PCB to see if the
discharge gas compressor discharge RAS-16FSG, RAS-16FS3 RAS-20FSG,
temperature is over gas temperature is RAS-20FS3
No No RAS-24FSG1,
132oC. over 132oC. RAS-24FS5,
Yes Yes RAS-30FSG1,
RAS-30FS5
<FX Series Only>
Remove sudden
Remove sudden
changes of load
changes of load like No No like short path of
short path of discharge Is the opening degree Is the opening of the
discharge air to the
air to the intake of the of ex. valve of outdoor outdoor unit ex. valve
air intake of the
outdoor unit, or the bypass 100%? 100%?
outdoor unit, or the
cause of frequent
Yes Yes cause of frequent
thermo-ON/OFF.
thermo-ON/OFF.
No Is the connector
Plug the connector Are the connectors
(CN12) for ex. valve (*1) of PCB1 of the
No
CN12 of PCB1 Plug the connectors
of outdoor bypass outdoor unit heat
properly. (*1) of PCB1
connected properly? exchanger's ex. valve properly.
Yes connected properly?
Remove sudden No *1): PCB1 Connector No. is
Is the opening of all Yes shown in the below table.
changes of indoor load the operating indoor
(short path, etc.) or units ex. valve 100%? 5 to 20HP CN10 and CN11
short path of air 24 and 30HP CN10, CN11,
Yes
between outdoor units. CN12 and CN20
No
Charge correct
Is the amount of
refrigerant volume.
refrigerant correct?
Refer to TCII.
Yes
No
Check the ex.
Is gas leaking?
valve.
Yes
1-41
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Correctly charge
Shortage of Refrigerant Check pressures.
refrigerant.
1-42
Alarm
Code Activation of Protection Device for Outdoor Fan Motor
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the temperature of the internal thermostat () for the outdoor fan
motor is higher than 130°C.
Check Item
HP Mark Power Supply
5 to 20HP ITO1, 2 380-415/380V, 220V 50/60Hz
24, 30HP ITO1, 2, 3 380-415V 50Hz, 380V 60Hz
ITO1, 3 220V 60Hz
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Measure coil
Faulty Outdoor Unit
resistance and Replace motor if faulty.
Fan Motor
insulation resistance.
Incorrect
Check connections. Repair connections.
Connection
1-43
This alarm code is indicated when the thermistor is short-circuited (less than 0.24 kΩ) or cut (greater
than 840 kΩ) during the cooling or heating operation. The system is automatically restarted when the
fault is removed.
No
Is it connected to
Connect it.
THM1 (intake) of PCB?
Yes
Is resistance of THM1 No
between 0.24kΩ and Faulty Thermistor
840kΩ?
Yes
Indoor Unit
Air Inlet Thermistor
Faulty PCB
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Replace thermistor
Fault Check resistance.
if faulty.
Faulty Intake
Air Thermistor
Repair wiring and
Incorrect Connection Check connection.
connections.
90
82
80
70
61
60
Thermistor 50 46
Resistance
(KΩ) 40 35
30 27
20.5
20 16
12.5
10
10 8 5.3 3.6 2.5
0 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
Thermistor Characteristics
NOTE:
This data is applicable to the following thermistors;
1. Indoor Unit Discharge Air Temperature, 2. Indoor Unit Liquid Refrigerant Temperature, 3 Indoor Unit
Intake Air Temperature, 4. Outdoor Air Temperature, 5. Outdoor Unit Evaporating Temperature, 6. Indoor
Unit Gas Piping
1-44
No
Is the thermistor connected
Connect it.
to THM2 of PCB?
Yes
No
Is resistance of THM2
between 0.24 and 840kΩ? Faulty Thermistor
Indoor Unit
Air Outlet Thermistor
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Replace thermistor
Fault Check resistance.
if faulty.
Faulty Air Outlet
Thermistor
Repair wiring and
Incorrect Connection Check wiring to PCB.
connections.
1-45
Freeze Protection
No Thermistor (THM3)
Is the thermistor connected
Connect it.
to THM3 of PCB?
Yes
No
Is resistance of THM3
between 0.24 and 840kΩ? Faulty Thermistor
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Replace thermistor
Fault Check resistance.
Faulty Freeze if faulty.
Protection
Thermistor Repair wiring and
Incorrect Connection Check wiring to PCB.
connections.
1-46
No
Is it connected to
Connect it.
THM5 of PCB?
Yes
Is resistance of THM5 No
between 0.24kΩ and Faulty Thermistor
840kΩ?
Refer to page 1-44 for Thermistor for
Yes thermistor resistance. Heat Exchanger
Gas Pipe
Faulty PCB In Case of 4-Way Cassette Type
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Replace thermistor
Faulty Thermistor Fault Check resistance.
if faulty.
for Indoor Unit
Heat Exchanger
Gas Pipe Temp. Repair wiring and
Incorrect Connection Check wiring to PCB.
connections.
1-47
This alarm code is indicated when the following conditions occurs three times in 30 minutes.
* Indoor fan rotates less than 70rpm for 5 seconds during operation.
Does the indoor
fan run?
No
No
Yes
Yes
Is LED4 on PCB2 Faulty PCB1 Insufficient voltage for PCB1. Replace PCB1
OFF? or Transformer or Transformer
No
No
Is the voltage between GND
of PCB1 and PC1 2# of PCB2
Yes several voltage?
Is pulse signal to Faulty PCB2 Replace PCB2
PCB2 correctly?
PCN202
No
PC1-2# PC1 Electrical
Faulty PCB1 Box
LED
CN201 CN202
CN201-3#
PCB2
Replace PCB1
TB1
CN201
TB2 CN203
PCN7 PCN11 CN1 PCN203
LED4
PCB1 CN19
Transformer
1-48
This alarm code is indicated when the temperature of the internal thermostat for the indoor fan motor
is higher than 130°C.
Yes
No Is continuity present No No
Does the indoor
at the internal thermostat Is fan motor hot? Replace the motor.
fan run?
of indoor fan motor?
Yes Yes
No
Is connection bad at Repair wiring and
the connector? connections.
Yes
No
Is the coil resistance
Replace the motor.
of fan motor normal?
Yes
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Measure coil
Faulty Indoor Unit
resistance and Replace motor if faulty.
Fan Motor
insulation resistance.
Incorrect
Check connections. Repair connections.
Connection
1-49
This alarm code is indicated when the running current of the indoor fan motor is higher than 1A.
No
Is connection bad at Repair wiring and
the connector? connections.
Yes
No
Is the coil resistance
Replace the motor.
of fan motor normal?
Yes
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Measure coil
Faulty Indoor Unit
resistance and Replace motor if faulty.
Fan Motor
insulation resistance.
Incorrect
Check connections. Repair connections.
Connection
1-50
Alarm
Code Abnormality of High Pressure Sensor for Outdoor Unit
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the pressure sensor voltage decreases lower than 0.1V or
increases higher than 4.9V during running.
Is 12 VDC applied No
across #1 and #3 of the
PCB1 defective.
connector CN7 of the
outdoor unit PCB1?
Yes
Is voltage under
0.1 VDC or over 4.9VDC No
across #2 and #3 of the
connector CN7 of the
outdoor unit PCB1?
Yes
Yes
Clogged Check Joint? Replace check joint.
No
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Indicated
Malfunction of Pressure
Pressure Value Check for clogging
Sensor due to Faulty Replace check joint.
is Excessively of check joint.
Check Joint
High or Low
1-51
This alarm code is indicated when the thermistor is short-circuited (less than 0.2 kΩ) or cut (greater
than 500 kΩ) during running. However, this alarm occurs during test running mode only. In the
case that the thermistor is abnormal during running, operation continues based on the assumption
that the outdoor temperature, is 35°C (Cooling) / 6°C (Heating).
No
Is it connected to
Connect it.
THM7 (TA) of PCB1?
Yes
Is resistance of THM7 No
between 0.2kΩ and Faulty Thermistor Outdoor
500kΩ? Unit Ambient
Refer to page 1-44. Thermistor (THM7)
Yes
Faulty PCB1
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Replace thermistor
Fault Check resistance.
Faulty Thermistor if faulty.
for Outdoor Unit
Ambient Repair wiring and
Incorrect Connection Check wiring to PCB.
connections.
1-52
This alarm code is indicated when the thermistor is short-circuited (less than 0.9 kΩ) or cut (greater
than 2,350 kΩ) during running.
No
Is the setting of DSW2 Set DSW2 on PCB1
on PCB1 right? correctly.
Yes
Characteristics of Thermistor
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Replace thermistor
Fault Check resistance.
if faulty.
Faulty Discharge
Gas Thermistor
Repair wiring and
Incorrect Connection Check wiring to PCB.
connections.
1-53
The evaporating thermistor during the heating operation is attached to the heat exchanger as shown
below figure.
If this thermistor is faulty, this alarm is indicated. The position is indicated below.
THM11
THM10
THM10 THM5
THM11
THM10 THM11 THM10
Is CN105 or CN106
No
on PCB1 connected (*1) Indication on the display
to THM10 (Te1), or Connect it. of the outdoor unit PCB.
THM11 (Te2) or
THM15 (Te3)? 1 2 4 Faulty Te1
Yes 2 2 4 Faulty Te2
3 2 4 Faulty Te3
Is resistance of the No
thermistor between Faulty Thermistor
0.2kΩ and 500kΩ?
Regarding the thermistor characteristics,
Yes refer to page 1-44.
Faulty PCB1
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
Replace thermistor
Faulty Thermistor Fault Check resistance.
if faulty.
for Evaporating
Temperature
during Heating Repair wiring and
Incorrect Connection Check wiring to PCB.
connections.
1-54
This alarm code is indicated when the pressure sensor voltage decreases lower than 0.1V or
increases higher than 4.9V during running.
Yes
Is the Check Joint
Replace the check joint.
clogged?
No
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Indicated
Malfunction of Pressure
Pressure Value Check for clogging
Sensor due to Faulty Replace check joint.
is Excessively of check joint.
Check Joint
High or Low
1-55
Alarm
Code Incorrect Wiring Connection (FX Series Only)
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when there are more than two (2) CH units connected between outdoor
unit and indoor unit due to incorrect wiring connection.
This alarm code is indicated when the outdoor unit PCB (PCB1) for FSG/FS3 series is attached
incorrectly to the FXG/FX3 series outdoor unit.
No
Is wiring connection Correct the wiring connection
correct? and start the unit again.
Outdoor Unit PCB is correct.
Yes
Incorrect Example;
Outdoor Unit Outdoor Unit Two (2) CH units between
outdoor unit and indoor unit
1-56
This alarm code is indicated when the capacity setting dip switch, DSW2 on the outdoor unit PCB1,
is not set (all the settings from #1 to #3 are OFF) or mis setting.
This alarm code is indicated when the total indoor unit capacity is smaller than 50% or greater than
150% of the combined outdoor unit capacity.
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Check combination
Incorrect Capacity Setting of Indoor Unit of indoor units and Correctly set dip switch,
capacity setting on PCB. DSW3.
Check refrigeration
Refrigeration Cycle Setting of Outdoor Unit cycle setting on
Set them correctly.
and Indoor Unit is Different outdoor unit PCB and
indoor unit PCB.
Combination
Combined Indoor Unit
Outdoor Unit Model Total Capacity Notes
Total Q'ty
(HP)
RAS-5FSG(3) 2-8 sets *1) 2.5-6.5 *1): If the capacity of one indoor unit
RAS-8FSG(3), RAS-8FXG(3) 4.0-10.4 is the same as of the outdoor
2-12 sets unit, the system can be operated.
RAS-10FSG(3), RAS-10FXG(3) 5.0-13.0
RAS-16FSG, RAS-16FS3 2-13 (16) sets *2) 8.0-20.8 *2): In case of changing the indoor
RAS-20FSG, RAS-20FS3 2-16 sets 10.0-26.0 unit capacity from 1.0HP or 1.5HP
RAS-24FSG1, RAS-24FS5 2-27 sets 12.0-31.2 to 1.3HP by dip switch setting.
RAS-30FSG1, RAS-30FS5 2-30 sets 15.0-39.0
1-57
Alarm
Code Abnormality in Transmitting of Other Indoor Units
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated on the remote control switch of other indoor unit when no transmitting
data is issued from a malfunctioning indoor unit for more than 60 minutes after receiving transmitting
data from the indoor unit.
Is there any indoor Is LED3 (yellow) Yes Check the wires between
unit whose lamp is not flickering on the PCB the indoor unit, CH unit and
lit or whose LCD is not of indoor unit? outdoor unit.
indicated at the remote
control switch? No
Yes
Yes Check connections of the
Is LED3 OFF? PCB of indoor unit, CH unit
or connector CN1.
Check the power source, No
fuse and transformer of
the indoor unit or CH unit.
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
*1): This abnormality is indicated on an indoor unit which is normal, since this is due to abnormality of transmitting of
the indoor units or power source abnormality in the same refrigeration cycle and electrical system. If the power
source is abnormal, abnormality can not be indicated by its indoor unit, so, this alarm is indicated on the remote
control switch of other indoor unit.
1-58
Alarm
Code Incorrect Indoor Unit No. Setting
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated 3 minutes after power is supplied to the outdoor unit when the indoor
unit No. connected to the outdoor unit is duplicated by setting of RSW.
In the case of H-Link System, this alarm code is indicated when DSW1 of the outdoor unit PCB and DSW5
of the indoor unit PCB are incorrectly set.
In this case, set correctly DSW1 and DSW5 after turning off Main Switch.
This alarm code is indicated when AC 220V or 240V is supplied to voltage *A or *B on PCB1 in the
outdoor unit during inverter compressor stoppage.
No
Faulty PCB1
Is 220VAC or 240VAC applied *A
during stopping? No No
Is 220VAC or 240VAC applied *B
during stoppage?
Yes
PCB1 is normal Yes
Power Supply *A *B
380-415V/50Hz Between terminal #3 of PCN14 on PCB1 Between terminal #3 of PCN2 on PCB1
380V/60Hz and faston terminal "N" on PCB1 and faston terminal "N" on PCB1
220V/60Hz Between terminal #3 of PCN14 on PCB1 Between terminal #3 of PCN2 on PCB1
and faston terminal "S" on PCB1 and faston terminal "S" on PCB1
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Abnormality of
Check voltage supplied Repair wiring
Picking up Circuit Incorrect Connection
to connectors. connections.
for Protection
1-59
Alarm
Code Abnormality of Running Current at Constant Compressor
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
No
Does the CMC2~4 Check wiring connection
turn ON? around PCB1.
Yes
Indication of 7-Segment
Abnormality of Constant Compressor
MC2
MC3
MC4
1-60
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Operate within
Excessively High or
380-415V +
− 10% (50Hz)
Low Voltage of
380V +
− 10% (60Hz)
Power Source
220V +
− 10% (60Hz)
Excessively Large
Running Current of Imbalance Among Adjust voltage between
Compressor Motor Phase at Power Source each phase.
Excessively High
Check for causes.
Discharge Pressure
Looseness of Screws
Single Phase Operation Tightly fix screws.
for Power Source
Seizure of Compressor
Locked-up? Replace compressor.
Bearing
Check continuity
Fault Replace CT when faulty.
during stoppage.
Incorrect
Check wiring. Correctly wiring.
Wiring
1-61
Alarm
Code Activation to Protect System from Low Compression Ratio
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when a compression ratio, ε= {(Pd + 0.1) / (Ps + 0.1)} is calculated from
a discharge pressure (MPa) and suction pressure (MPa) and the condition lower than
ε = 1.8 occurs more than 3 times including 3 in one hour.
No
Does the inverter operate? Check the inverter.
Yes
No
Check the compressor and
Does the compressor operate?
power cable.
Yes
Yes
Is the four-way valve spindle
Replace the four-way valve if faulty.
mounted at middle position?
No
No
Are the high-pressure sensor and Replace the high-pressure sensor
the low-pressure sensor good? or the low-pressure sensor if faulty.
Yes
Yes
Is there a leak in the Solenoid Replace the Solenoid Valve
Valve for Hot Gas Bypass (SVA)? (SVA) if faulty.
No
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
1-62
Alarm
Activation to Protect System from Excessively Low Suction Pressure
Code
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the compressor is operated under the conditions higher than
0.9 MPa of suction pressure and its occurrence is more than 3 times including 3 in one hour.
Yes
Is there a leak in the Replace the solenoid valve SVA
solenoid valve SVA? if faulty.
No
Yes
Is the four-way valve spindle
mounted at middle position? Replace the four-way valve if faulty.
No
No
Replace the low-pressure sensor
Is the low-pressure sensor good?
if faulty.
Yes
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Excessively
Abnormal Suction Check connectors of
Low Suction Replace sensor if faulty.
Pressure Sensor PCB and power source.
Pressure
1-63
Alarm
Activation to Protect System from Excessively High Discharge Pressure
Code
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the compressor is operated under the conditions higher than
2.65 MPa (26.5 kg/cm2G) of discharge pressure [ in case of FSG, FSG1 and FXG models, Pd is
higher than 2.84 MPa (28.4 kg/cm2G)] and its occurrence is more than 3 times including 3 in one
hour.
Yes
Is there a leakage of the Replace the solenoid valve SVA
solenoid valves SVA? if faulty.
No
Yes
Is the outdoor unit stop valve
Open the stop valve.
closed?
No
No Check connection of the circuit
Is the high-pressure sensor good? board connector. Replace the
high-pressure sensor if faulty.
Yes
Yes Check the circuit board and
Are ex. valves fully closed and connection of the circuit board
locked? connector. Replace the electronic
expansion valves if faulty.
No
Check the outdoor electronic expansion valve during cooling
and the indoor electronic expansion valve during heating.
Are electric wiring and refrigerant Yes
piping between the indoor and Correctly connect it.
outdoor unit incorrectly connected?
In the case of H-LINK connection,
No check the refrigeration cycle setting on
the PCB of outdoor unit and indoor unit.
Check if indoor or outdoor intake
air temperature is too high.
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Check connection.
Leakage of Solenoid Valve Check outlet temp. of
Replace solenoid valve
SVA (Outdoor Unit) solenoid valve, SVA.
SVA if faulty.
1-64
This alarm code is indicated when the compressor is operated under the conditions lower than
0.6MPa (6kgf/cm2G) for an hour.
(MPa) (V)
0.3 0.9
Discharge Voltage between
Pressure #2 and #3 of CN7
Alarm area
0.1 0.6
0 26
Outdoor Air Temperature (oC)
No
Is the amount of refrigerant
Correctly charge refrigerant.
correct?
Yes
Yes
Is the high-pressure in the
Check for leakage of refrigerant.
alarm area?
No
Yes
Is the connector CN7 of
Plug the connector CN7 correctly.
outdoor unit PCB1 loose?
No
Yes
Is the high-pressure sensor
Remove clogging.
pipe clogged?
No
1-65
Action
Phenomenon Cause Check Item
(Turn OFF Main Switch)
Incorrect
Check connection. Connect correctly.
Connection
1-66
Alarm
Abnormality of Current Transformer (0A Detection) (For 5HP to 20HP)
Code
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the current transformer is abnormal (0A detection) and its state
occurs more than 3 times in 30 minutes.
Condition of Activation: When the frequency of compressor is maintained at 15 to 18Hz after compressor
is started, one of the absolute value of running current at each phase
U+, U-, V+ and V- is less than 0.5A (including 0.5A).
No
Is the coil resistance
Replace Comp.
of comp. normal?
Yes
No
Is output of transistor
Check transistor module.
module correct? *2)
Yes
Replace PCB3
1-67
Alarm
Abnormality of Current Transformer (For 24 and 30HP)
Code
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
In case that the abnormality of alarm code 51, 52, 53 or 54 occurs three times within 30 seconds, the
alarm code of abnormality occurred for the third time is indicated. Retry operation is performed up to
second time of abnormality occurrence.
Condition of Activation: When the frequency of compressor is maintained at 15 to 18Hz after compressor
is started, one of the absolute value of running current at each phase
U+, U-, V+ and V- is less than 0.5A (including 0.5A).
Restart operation.
No
Is the coil resistance
Replace Comp.
of comp. normal?
Yes
Is output of ISPM
No
correct? *2)
Or is output of voltage Check ISPM.
between U and V,
V and W, W and U?
1-68
This alarm code is indicated when the electronic thermal relay for the inverter is activated 3 times
including 3 in 30 minutes. Retry operation is performed up to the occurrence of 2 times.
Conditions: Inverter current with 105% of the rated current, (1) runs continuously for 30 seconds or
(2) runs intermittently and the accumulated time reaches up to 3.5 minutes, in 10 minutes.
Rated Current
Model 380-415V 50Hz 220V 60Hz
380V 60Hz
RAS-5FSG(3), RAS-8FSG(3), RAS-10FSG(3) 14.0 / 25.0
RAS-16FSG(3), RAS-20FSG(3) 16.5 / 30.0
RAS-8FXG(3), RAS-10FXG(3) 14.0 / 25.0
Is the cause of
stoppage " " of "2"
troubleshooting by Refer to next page.
7-segments display
Restart operation. "2" or "4"?
"4"
Yes
Is the compressor (The circuit board is normal.)
current larger than
activation current?
Is discharge pressure
No high?
Smaller than
activation current. Check pressure and
refrigeration cycle.
Abnormal
Check the diode
Replace the diode module.
module. *1)
Normal
*1): Regarding the checking method for diode module, refer to page 1-113.
*2): Regarding replacing or the checking of inverter components, refer to page 1-111 regarding electrical discharge.
1-69
This alarm code is indicated when the instantaneous overcurrent tripping occurs 3 times including 3
in 30 minutes. Retry operation is performed up to the occurrence of 2 times.
Conditions: Inverter current is 150% of the rated current.
Are the input currents Yes (Input currents nearly equal (±3%).)
Replace the inverter
of three phases nearly
circuit board.
equal? ( +
_ 3%)
No (Input currents out of balance.)
Check the power
supply.
Is the supply voltage No
Power Supply Mark (a)
380-415V±10% or
220V±10%? 380-415V 50Hz
320
380V 60Hz
Yes
220V 60Hz 170
No Check the capacity
Is it (a)V or more
and wiring of the
during operation?
power source.
Yes
Is it (a)V more No
during operation
when other devices
are operating?
Yes
Replace the inverter
circuit board.
1*): Regarding replacing or the checking method for the diode module, refer to page 1-113.
2*): Regarding the checking method for transistor module, refer to page 1-112.
3*): Regarding the checking of inverter components, refer to page 1-111 regarding electrical discharge.
1-70
In case that the abnormality of alarm code 51, 52, 53 or 54 occurs three times within 30 seconds, the
alarm code of abnormality occurred for the third time is indicated. Retry operation is performed up to
second time of abnormality occurrence.
Conditions: Inverter current with 105% of the rated current, (1) runs continuously for 30 seconds or
(2) runs intermittently and the accumulated time reaches up to 3.5 minutes, in 10 minutes.
Rated Current
Model 380-415V 50Hz 220V 60Hz
380V 60Hz
RAS-24FSG1, RAS-30FSG1, RAS-24FS5, RAS-30FS5 14.0 / 27.5
Is the cause of
stoppage " " of "2"
troubleshooting by Refer to next page.
7-segments display
Restart operation. "2" or "4"?
"4"
Yes
Is the compressor (ISPM is normal.)
current larger than
activation current?
Is discharge pressure
No high?
Smaller than
activation current. Check pressure and
refrigeration cycle.
Replace ISPM.
Normal
ISPM is faulty.
Replace it.
*1): Regarding replacing or the checking of ISPM, refer to page 1-114 regarding electrical discharge.
1-71
In case that the abnormality of alarm code 51, 52, 53 or 54 occurs three times within 30 seconds, the
alarm code of abnormality occurred for the third time is indicated. Retry operation is performed up to
second time of abnormality occurrence.
Conditions: Inverter current is 150% of the rated current.
Turn off power and
No disconnect U, V, W
Yes No
Restart operation. from compressor
Does it trip soon? terminals.
Turn ON #1 of DSW1
No It trips on ISPM and restart.
immediately. Does it trip?
No
Yes It trips. Is there any cause
Check the
of instantaneous
compressor.
voltage decrease?
Yes
It trips after a Check the power
certain period. source capacity.
Good
Are the input currents Yes (Input currents nearly equal (±3%).)
of three phases nearly Replace ISPM. *2)
equal? ( +
_ 3%)
No (Input currents out of balance.)
Check the power
supply.
Is it (a)V more No
during operation
when other devices
are operating?
Yes
Replace ISPM. *2)
1*): Regarding replacing or the checking method for ISPM, refer to page 1-114.
2*): Before the checking of ISPM, refer to page 1-111 regarding electrical discharge.
1-72
Transistor module (5 to 20HP) or ISPM (24 and 30HP) have detecting function of abnormality.
This alarm is indicated when the transistor module detect the abnormality 3 times in 30 minutes
including 3. Retry operation is performed up to the occurrence of 2 times. (In Case of 5 to 20HP)
In case that the abnormality of alarm code 51, 52, 53 or 54 occurs three times within 30 seconds, the
alarm code of abnormality occurred for the third time is indicated. Retry operation is performed up to
second time of abnormality occurrence. (In Case of 24 and 30HP)
Conditions: Abnormal Current to the Transistor Module (5 to 20HP) or ISPM (24 and 30HP) such as
Short Circuited or Grounded
or
Abnormal Temperature of the Transistor Module (5 to 20HP) or ISPM (24 and 30HP)
or
Control Voltage Decrease
Yes
Is the heat exchanger of
Remove clogging.
outdoor unit clogged?
No
Replace the inverter
circuit board (5 to 20HP)
or ISPM (24 and 30HP).
1*): Regarding replacing or checking method for the transistor module (5 to 20HP) and the inveter components (24
and 30HP), refer to pages 1-112 and 1-114.
2*): Before the checking of inverter components, refer to page 1-111 regarding electrical discharge.
3*): Turn ON the No.1 switch of the dip switch DSW1 on PCB3/ISPM when restarting with disconnecting
theterminals of the compressor. After troubleshooting, turn OFF the No.1 switch of the dip switch DSW1 on
PCB3/ISPM (5 to 20HP/24 and 30HP).
4*): Use the silicon grease provided as accessory (Service Parts No.: P22760).
1-73
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
In case that the abnormality of alarm code 51, 52, 53 or 54 occurs three times within 30 seconds, the
alarm code of abnormality occurred for the third time is indicated. Retry operation is performed up to
second time of abnormality occurrence.
Conditions: This alarm is indicated when the temperature of the internal themostat for ISPM is higher
than 100oC.
Yes
Restart operation.
Replace the ISPM.
Does it trip soon?
No
Yes
Is the heat exchanger of
Remove clogging.
outdoor unit clogged?
No
1*): Regarding replacing or checking method for ISPM, refer to page 1-114.
2*): Use the silicon grease provided as accessory (Service Parts No.: P22760).
1-74
This alarm is indicated when the revolution pulse output from the fan motor is 10rpm or less and the
reverse revolution signal is detected. The fan motor is stopped once, and restarted after 10 seconds.
It occurs more than 10 times in 30 minutes, this alarm is indicated. The abnormality occurs when the
fan motor is stopped.
Restart operation.
Check to remove the connector CN14 on PCB1 and CN201, CN203, CN206
and CN207 on ISPM and CN15 and CN110 of trunk connector.
Faulty
Are the connectors abnormal? Connect it correctly.
Good
Restart operation.
Yes
Does the motor run? This is normal.
No
Restart operation.
Yes
Does the motor run? This is normal.
No
Alarm code is not indicated.
Replace the PCB or
the fan controller.
In the case that the fan motor does not run
even the PCB is replaced, replace ISPM.
1-75
This alarm code is indicated when a current value of AC chopper becomes (1) less than 0.5A when
outdoor unit fan is operating, or (2) more than 2A while outdoor unit fan stops.
Yes
Is the fuse of EF9 melted? Replace fuse.
No
Faulty AC chopper.
Replace the AC chopper.
1-76
Alarm
Incorrect Wiring Among Indoor Units
Code
This alarm code is indicated only when remote control switch PC-2H2 is used being connected to
indoor unit.
This alarm occurs in the case of incorrect connection like that TL terminal is connected to Vc terminal
as below when indoor units are wired.
I. U. 1
Incorrect
Wiring
Vc TG TL
Remote
Remote Control Control
Switch (yellow) Switch
The unit No. and unit code are as below regardless of the indoor unit being connected to the remote
control switch.
Indoor Unit No. 00
Cycle System 00
Unit Code E.00
No
Is wiring among indoor Repair the wiring among
units right? indoor units.
Yes
JP4
Action
Phenomenon Cause Check Item (Turn OFF Main Switch)
1-77
Alarm
Compressor Protection
Code
This alarm code appears when one of the following alarms occurs three times within 6 hours, which
may result in serious compressor damages, if the outdoor unit is continuously operated without
removing the cause.
These alarms are able to be checked by the CHECK Mode 1. Follow the action indicated in each
alarm chart.
These alarms are cleared only by turning OFF the main power switch to the system. However,
careful attention is required before starting, since there is a possibility which will result in
serious damages to the compressors.
1-78
(PC-P1H)
Use the remote control CHECK switch in the following cases. FAN HIGH SWING
LOUVER ON/OFF TIMER SET TEMP.
(2) To trace back the cause of trouble after restarting from DRY A/C
DEFROST
+ CENTRAL
SERVICE
ABNML FILTER
AUTO VENT H.STRG T. RUN CHECK
stoppage with the RUN lamp flashing.
RUN / STOP TEMP.
(3) To check during normal operation or stoppage.
(4) To monitor the temperatures of intake and discharge air.
MODE FAN SPEED ON/OFF TIMER RESET
HIGH
COOL
Alarm Code Identifying the Last Fault that has Occurred in
Unit Number and ADDS. RN the Indicated Unit.
Alarm Code Displayed A/C Unit number of connected unit or unit number for which
CHECK
checking mode was selected previously.
A/C
CHECK
To View the Next Indication
CHECK TEMP
Press for more Press
than 3 seconds.
A/C
After CHECK
7 seconds
HIGH
Check Mode 2 COOL
(See page 1-83 for
A/C
details.) CHECK
TEMP
1-79
Although the wireless remote controller is used for wall type indoor unit with built-in receiver part, the
alarm code can be checked by connecting PC-P1H to the connector (Blue) of the unit as shown below and
pressing the operation switch.
NOTES:
1. The unit is not operated by pressing operation switch.
2. The above function is available only when alarm occurs.
3. The PCB check by remote controller is not available.
4. The indication is the data when connecting PC-P1H, not the data before the alarm occurs.
>
The next indication is shown by pressing the part of “TEMP” switch. If the part of “TEMP” switch is
>
pressed the previous indication is shown.
Outdoor Unit
6 Ambient Air Temp.
(oC)
Outdoor Unit
8 Evaporating Temp.
during Heating (oC)
Discharge Gas
10 Temp. at the Top of (ex.) During two compressors operation, average
Comp. Chamber (oC) temperature of two compressors is indicated.
In case that temperature is higher than 126oC, " ".
to next page
1-80
Thermo Temp. of
11 Remote Control Heating Thermo-ON Alarm FAN HIGH SWING
LOUVER ON/OFF TIMER SET TEMP.
Micro-Computer
12 Input/Output in Y52C2 Y211 MODE FAN SPEED ON/OFF TIMER RESET
Y212 Y52C1
Indoor Unit
VENTI LOUVER CHECK
Dark TIME
Y20B
Micro-Computer Y20A
13 Input/Output in
Outdoor Unit Outdoor Fan
1-81
Discharge Pressure
20
(High) (x 0.1 MPa)
Suction Pressure
21
(Low) (x 0.01 MPa)
22 Control Information This is an indication for internal information for the remote
control switch. This does not have any specific meaning.
Operation
23 The total frequency is indicated when two compressors
Frequency (Hz)
are running.
Indoor Unit
28 Expansion Valve J3: 01~16
Opening (%) (01: when shipment (DSW5), Decimal Indication)
J4: 00~0F
(00: when shipment (DSW5), Indication with 16 numbers)
Outdoor Unit
29 Expansion Valve
MV1 Opening (%)
In case of models without Expansion Valve (MV2),
the same figure is indicated.
Outdoor Unit
30 Expansion Valve
MV2 Opening (%)
Outdoor Unit
31 Expansion Valve FX Series Only
MVB Opening (%)
Compressor
32 The total current is indicated when several
Running Current (A)
compressors are running.
In case of inverter compressor, the running current
Returns to Temperature Indication of primary side of inverter is indicated.
Temperature Indication
1-82
>
>
By pressing the part of “TEMP” switch, the next display is indicated, If the part of “TEMP” switch is
pressed, the previous display is indicated.
Evaporating Temp.
6
at Heating (oC)
Discharge Gas
8 Temp. at the Top of The average temperature is indicated when two
Comp. Chamber (oC) compressors are running.
to next page
1-83
Discharge Pressure
9
(High) (x 0.1 MPa)
Suction Pressure
10
(Low) (x 0.01 MPa)
11 Control Information This is an indication for internal information for the remote
control switch. This does not have any specific meaning.
Operating
12 The total frequency is indicated when plural compressor
Frequency (Hz)
are running.
Outdoor Unit
14 Expansion Valve
MV1 Opening (%)
Compressor
15 The total value is indicated when plural compressors
Running Current (A)
are running.
Returns to Temperature Indication
Temperature Indication
1-84
PSW3 PSW2
(Unit)
Total of Thermo-ON
2
Indoor Units Capacity PSW2 PSW3 1
~ (x
8
HP)
PSW3 PSW2
Running Frequency of
3
Inverter Compressor MC1 PSW2 PSW3
~ (Hz)
PSW3 PSW2
Number of Running
4
Compressor PSW2 PSW3
~
PSW3 PSW2
PSW3 PSW2
1-85
Discharge Pressure
10
(High) PSW2 PSW3
~ (MPa)
PSW3 PSW2
Suction Pressure
11
(Low) PSW2 PSW3
~ (MPa)
PSW3 PSW2
Discharge Gas
12 Temperature on the Top of
PSW2 PSW3
Compressor MC1 (TD1) ~ (oC)
1-86
Indoor Unit
(No.0 Unit) ~ (%)
~
24 Expansion
Valve Opening PSW3 PSW2
(No.F Unit)
PSW2 PSW3 (No.F Unit)
25 Liquid Pipe
Temperature PSW3 PSW2
(Freeze (No.F Unit)
Protection)
PSW2 PSW3 (No.F Unit)
~ (oC)
(Indicates only the units number
connected) PSW3 PSW2
26 Exchanger
Gas Pipe PSW3 PSW2
Temperature (No.F Unit)
PSW2 PSW3 (No.F Unit)
~ (oC)
(Indicates only the units number
connected)
1-87
~
27 Intake Air
Temperature PSW3 PSW2
(No.F Unit)
PSW2 PSW3 (No.F Unit)
~ (oC)
(Indicates only the units number
connected) PSW3 PSW2
~
28 Discharge Air
Temperature PSW3 PSW2
(No.F Unit)
PSW2 PSW3 (No.F Unit)
~ (oC)
(Indicates only the units number
connected) PSW3 PSW2
30 Cause of
Stoppage PSW3 PSW2
(No.F Unit)
PSW2 PSW3 (No.F Unit)
1-88
Current Protection
35 0: Degeneration Control is
Degeneration Control PSW2 PSW3 in Operation
1: Degeneration Control is not
in Operation
PSW3 PSW2
PSW3 PSW2
Total Quantity of
43
Combined Indoor Unit PSW2 PSW3
~ (sets)
PSW3 PSW2
Address of Refrigerant
44
System PSW2 PSW3
~
Indicates setting address by DSW1
Returns to START " "
1-89
35
Upper Limit
25
20 Lower Limit
15
10
5 10 15 20 25 30
Running Current of Compressor MC1
Indicated on 7- segment
Remark
Cause of Stoppage for
Code Cause Indication
Corresponding Unit
during Retry Alarm Code
Automatic Stoppage of Transistor Module
(IPM Error)
(Over Current, Decrease Voltage,
Increase Temperature)
Instantaneous Over Current
Increase Voltage
1-90
Low-Pressure Increase
Current Protection (*)
Retry
Inverter Fin Temperature High-Pressure Increase
Increase Protection
(For 24, 30HP) Retry
NOTE:
The protection control code being indicated on 7-segment display is changed to an alarm code when the
abnormal operation occurs. Also, the same alarm code is indicated on the remote control switch.
1-91
1-92
NOTES:
1. During protection control (except during alarm stoppage), the protection control code is indicated.
2. The protection control code is indicated during protection control and turns off when canceling the
protection control.
3. After retry control, the condition of monitoring is continued for 30 minutes.
4. The maximum value (*1) is as follows.
1-93
1 2
Before Alteration After Alteration
a RCI - a-2
b RPI (0.8 to 5.0HP) b-1 b-2
c RCD c-1 c-2
d RPC d-1 d-2
e RPK e-1 e-2
f RPF, RPFI f-1 -
g RPI (8, 10HP) g-1 -
h KPI - h-2
(a-2)
1 12
3
PCN4
PCN7 RSW 5
LED4
CN14 HA JP5
DSW3
PCN6
LED1
DSW5
JP1 JP2
PCN5 EF2 IC11
JP3 JP4
EF1 DSW7
CN2 TP CN19 THM5 THM4 THM3 THM2 THM1
LED3
7 11 9
PCN2
EFR1
ICI2 ICI1
DM2
EFS1
11 9 10 12 2 5 9 11 12
2 5 6 3 1 11
1-94
(e-1) (e-2)
2 1 5 2 9 10 11 12 5 1 3 2 7 9 10 12
2 2
■ Dip Switch and LED Functions on Indoor Unit Printed Circuit Board (Dip Switch/ : With, : Without)
Dip Switch
b-2
Part d-1
Contents of Functions b-1 c-2 Remarks
Name a-2 f-1 e-1 e-2
c-1 d-2
g-1
h-2
1 RSW Setting of Indoor Unit Number -
2 DSW2 Setting of Optional Functions A. a-2, b-1, b-2, c-1, c-2, d-2:
A. Self-Diagnosis No Function
B. Remote ON/OFF Control B. a-2, b-1, b-2, c-1, c-2, d-2:
C. Automatic Restart after Short Power Failure Dip Switch Setting is Not
D. Control by Field-Supplied Room Thermostat Required. (The Setting of
Remote Control Switch is
Required.)
C. a-2, b-1, b-2, c-1, c-2, d-2:
Same as B
D. a-2, b-1, b-2, c-1, c-2, d-2:
Same as B
h-2:
No Function
3 DSW3 Setting of Indoor Unit Capacity Code -
4 DSW4 Setting of Capacity Adjustment -
5 DSW5 Setting of Refrigerant Cycle No. Setting h-2:
For Option Setting
6 DSW6 Setting of Unit Code h-2:
For Refrigerant Cycle Setting
(In Case of Using H-LINK)
7 DSW7 Setting of Fuse Recover -
9 LED1 This LED1 indicates the transmission state
(Red) between the indoor unit and remote control switch.
-
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
10 LED2 This LED2 indicates the transmission state
(Green) between the indoor unit and central station.
(When Disconnected: Deactivated) -
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
11 LED3 This LED3 indicates the transmission state
(Yellow) between the indoor unit and outdoor unit.
Normal Condition: Flickering one time/
some seconds
-
Abnormal Condition: Activated or Deactivated
more than 30 seconds
or Flickering
(30 times/1 second)
12 LED4 This LED4 indicates the power supply (5V)
(Red) for micro-computer.
-
Normal Condition: Activated
Abnormal Condition: Deactivated
13 SW1 Setting of Transmission -
1-95
EF7, EF8, CT3, CMC3, NF11: Only for RAS-16FSG, RAS-16FS3, RAS-20FSG and RAS-20FS3
After Manufacturing # U4NG1002 (FSG/FS3 Series) / From First Production (FXG/ FX3 Series)
EF7, EF8, CT3, CMC3, NF11: Only for RAS-16FSG, RAS-16FS3, RAS-20FSG and RAS-20FS3
1-96
EF1
DCL CMC1
NF1 NF2 NF4
C1 NF3
Z CMC3 CMC4 TB4
EF2
PCB2 ISPM TF1
TB5
CB1 CB2 EF9 PCB1 TB3
CA2
NF7
R1 R2 CMC2 TB1
NF10
TF2
TB2
The Interior of
the Electrical Control Box
EF3
NF2 NF4
EF4 NF3 TB4
CMC3 CMC4
EF5
EF6
EF7
NF5 TB3
EF8
CMC2 TB1
NF10
TB2
CA1 CA3 C2 C3 C4 C5
RAS-5FSG, RAS-5FS3
RAS-8~20FSG, RAS-8~20FS3
1-97
EF1
DCL NF1
EF2
TB4
EF11 EF8
ISPM2 ISPM1 TB5 CMC3 CMC4 EF7
TB3
CMC1 NF10 EF12
CB EF6
EF5
CA1 TB1
EF4
CMC2 EF3 CA3 TB2
The Interior of
the Electrical Control Box
TB4
CMC3 CMC4
PCB1 TB3
TF1
CMC2 TB1
TF2
TB2
Purpose
Symbol PCB Purpose
PCB1 for Control 1. Transmitting between Indoor Unit and Outdoor Unit
2. Processing for Sensor Input
3. Processing for Dip Switch Input
4. Operation Control for Above Items 1 to 3.
Compressor Operation Control, Bypass Valve Control, Fan Control
and Overcurrent Control
5. 7-Segment Indication
6. Processing of Safety Device Input
7. Processing of Relay Output
8. Reverse Phase Detection for Power Source
PCB2 for Fan Fan Speed Control
PCB3 for Inverter 1. Inverter power part is driven by instruction of PCB1 and compressor
is driven.
2. Overcurrent Control
3. Protection Control for Inverter Part
PCB5 for "SNUBBER" 1. Restraining of Surge Voltage added to Transistor Module (IPM)
2. Absorbing for Switching Noise of Transistor Module (IPM)
1-98
G 5HP to 20HP
2 3 4 5
14
11
1
12
6 13
10
15
16 8 18 9 18
2 3 4 5
14
11
1
12
6 13
10
15
16 8 18 9 18
1-99
■ Dip Switches and LED Functions on Outdoor Unit Printed Circuit Boards
Name of Internal
Part Name Contents of Functions
Circuit Board
Controlling Board: 1 DSW1 Setting of Outdoor Unit Number
PCB1 2 DSW2 Setting of Capacity Code
Outdoor unit capacity is set according to nominal capacity (HP).
3 DSW3 Setting of Height Difference
The height difference between outdoor and indoor units is set.
4 DSW4 A. Test Running for Cooling or Heating
An outdoor unit can be run for testing. When testing has been
finished, reset the function.
B. Forced Stoppage of Compressor
When performing test running or inspection, compressors
can be forcedly stopped to ensure safety.
5 DSW5 A. Changeover of Defrosting Condition
(Optional The defrosting operation for normal areas or cold areas
Function) can be changed over.
B. #7 of Pin: 380V OFF, 415V ON
#8 of Pin: 220V ON
6 DSW6 Setting of Piping Length
The total piping length between the outdoor unit and indoor unit
is set.
7 DSW7 Setting of Emergency Operation
8 DSW8 Test Operation and Service Setting II
No setting is required.
9 DSW9 Optional Function 2
10 DSW10 Transmitting Setting
11 PSW1 Manual Defrosting Switch
The defrosting operation is manually available under the forced
defrosting area.
12 PSW2 Check Switches
13 PSW3 When checking units, checking items can be selected by these
switches.
14 LED1 Power Source for PCB1
(Red) Normal Condition: Activated
Abnormal Condition: Deactivated
15 LED2 This LED2 indicates the transmission state between the PCB1
(Green) and PCB3.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
16 LED3 This LED3 indicates the transmission state between the
(Yellow) indoor unit and outdoor unit.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
18 SGE1 These indicate the following: "alarm", "protective safety device
SGE2 has tripped" or "checking items".
1-100
LED2
DSW1
LED1
• Dip Switch and LED Functions on Outdoor Unit Inverter Printed Circuit Board
Switch Name
Function
DSW1
Normal: No.1 and No.2 of DSW1 are OFF.
Emergency Operation or Troubleshooting:
ON
No.1 of DSW1 is ON.
OFF
No.2 of DSW1 is OFF.
The above setting aims not to trip even if the CT detects 0A.
Name of Printed
Function
Circuit Board
LED1 (Red) This indicates the state of transmission.
Flickering: Normal Transmission
Activated or Deactivated: Abnormality in Transmission Circuit
* LED2 (Red) This indicates the voltage between both terminal of capacitor
CB1 and CB2 for inverter part.
Activated: The voltage between both terminals of capacitor,
CB is 50V +20V or greater.
Deactivated: The voltage between both terminals of capacitor,
CB is 50V +20V or smaller.
*: Applied to the following products;
1) RAS-8 to 20FSG/FS3
380-415V, 50Hz Model and 380V, 60Hz Model (After Manufacturing # U4NG1002)
220V, 60Hz Model (From The First Production)
2) RAS-5FSG/FS3
380-415V, 50Hz Model and 380V, 60Hz Model (After Manufacturing # U4MV0197)
3) RAS-8, 10FXG/FX3
From First Production
1-101
LED3
1-102
Press
Stop Operation FAN HIGH SWING
LOUVER ON/OFF TIMER SET TEMP.
COOL MED
ADDS RN HR
HEAT LOW NO FUNCTION UNIT
DEFROST
DRY A/C SERVICE
ABNML FILTER
+ CENTRAL
AUTO VENT H.STRG T. RUN CHECK
RUN / STOP
Simultaneously depress TEMP.
TEMP two switches for 3 seconds.
PCB Check Mode CHECK MODE FAN SPEED ON/OFF TIMER RESET
Indication of ADDS. RN
Unit Number
Indi-
Contents
After cation
7 Seconds Normal
For performing the above checking in the case that the wireless remote control switch is used with the
bulit-in receiver part of the RPK type indoor unit, perform the following procedures;
(1) Turn OFF the power supply.
(2) Disconnect the connector (CN25) on PCB(M).
(3) Connect PC-P1H to the Connectors CN12 or CN13.
(4) Turn ON the power supply.
After completion of checking, turn OFF the power supply again and make connectors as before checking.
1-103
Press
(ex.)
Repetition of Self-checking of Unit No. "0". Indication of ADDS. RN
After
7 Seconds
Result
After 1 to 5 Seconds
After 1 Second
Repetition
RESET
Release PCB
Check Mode
Press
NOTES:
1-104
2
TEMP MODE during changing
LCD indication.
MED
TEMP 2 HEAT For
A/C
DEFROST
FILTER
1 second
CENTRAL
SWING
FAN HIGH LOUVER ON/OFF TIMER SET TEMP.
COOL MED
5 HEAT LOW
ADDS RN HR
NO FUNCTION UNIT
For
DRY A/C
DEFROST
SERVICE
ABNML FILTER
3 seconds
+ CENTRAL
The LCD indication changes as AUTO VENT H.STRG T. RUN CHECK
shown below.
Depress all the switches
(13 switches) -one by one.
Every time the switch is depressed,
the number of the indication of (A)
part in the figure below increases
one by one.
A
NOTES:
1. Any order of depressing Unless all the switches are depressed,
switches is available. the checking do not proceed to the next item.
2. Depressing 2 or more switches
simultaneously is invalid and
not counted.
1-105
Cancellation of EEPROM
The LCD indication changes as
shown below. 3
9
The LCD indication changes as
After several seconds are passed, shown below and the EEPROM is
the remote control switch is automatically canceled by the
automatically activated again. remote control switch.
11
12
NOTES: After several seconds are passed,
10 1. In case that the operation is not the remote control switch is
automatically started when the automatically activated again.
remote control switch is In this case, the operation is not
activated again, the detection started automatically.
circuit for momentary stoppage
may be abnormal.
However, it would not interfere
the normal operation.
2. There is a case that the
operation is automatically
stopped after the automatic
operation when the remote
control switch is activated again.
1-106
■ Procedure
Refer to pages 1-94, 95 for location and function of DSW and LED.
b) Disconnect connectors CN5 and CN8, and set dip switch DSW2 as shown below.
Set #1 at ON side and #2 at OFF side.
ON
OFF
1 2 3 4 5 6 7 8
Dip Switch DSW2
NOTE: Before turning ON the power, see checking procedure mentioned in next page.
d) After completion of self-checking, turn OFF the power and reset the dip switch as before.
1-107
YH2
Y52H1, 2, 3
FAN Hi Me
(CN21)
COOL (CN5-3#)
COOL Thermo-ON
(CN5-2#)
HEAT (CN8-2#)
HEAT Thermo-ON
(CN8-3#)
1 2 3 4 5 6 7
(sec)
Termination Turn OFF and reset all dip switches as they were.
* for RPK
Check Item State of Mode Confirmation Method
(A) Initialize Exp. Valve Exp. Valve fully open => fully close
and Auto Louver Auto Louver is horizontally stopped.
(B) Analog Test If each thermistor for intake air, discharge air and
freeze protection is normal, proceed to the next step.
Fan (Low)
Termination Turn OFF and reset all dip switches as they were.
1-108
3 Checking of Touch Type Switch Function: By depressing a particular touch type switch,
Depress all the touch type switches one by one. the corresponding segment is activated.
Any one of the switches can be depressed. Indication
MINUTE
(PRESENT TIME) SET/RESET
NORMAL: HOUR RETURN PRESENT
(ON/OFF TIME)
OFF TIME DRY
MINUTE SET
(ON/OFF TIME) SET/
After 15 Seconds CANCEL MONITOR
HOUR ON TIME
(PRESENT TIME) SELECT
1-109
3 Checking of Touch Type Switch Function: By depressing a particular touch type switch,
Depress all the touch type switches one by one. the corresponding segment is activated.
Any one of the switches can be depressed. Temp. Indication Part
(UNIT) [blank]
NORMAL:
(UNIT) MNTR
DRY RUN/STOP
1-110
<Case 1>
Connecting
Wires
P
Plug B
N U
V W
Brazer
Transistor
<Case 2 and 3> Module
ISPM
PC208 PC207
CN8
Connecting CN9
CN207 CN206
N
C
Wires RB
TB2
LED201
R201
N
R200
Plug P ZN20
LED201
P1
ZN202
Brazer P TB3
R216
R215
RB PD P N
R S T U V W
(d) Wait for 2 or 3 minutes and measure the voltage once again. Check to ensure that no voltage is
charged.
1-111
W
U
N
P
B
B P
N
Th
Out
S1
GND
Out
S1
GND
Out
S1
GND
Out
S1
GND
Out
S1
GND
Out
S1
GND
Out
S1
GND
V
TEMP
GND
GND
GND
GND
GND
GND
GND
Vcc
Vcc
Vcc
Vcc
Vcc
Vcc
Vcc
Fo
Fo
Fo
Fo
Fo
Fo
Fo
In
In
In
In
In
In
In
W
VWPC
VUPC
VVPC
VWP
WFo
VNC
VUP
VVP
VN1
UFo
VFo
WN
WN
WP
UN
UP
VP
Fo
Br
[Case 2 and 3]
N
U
P
BNC
N P B
1
U
4
Protection Circuit
7
Over Heating
V
Pre-Driver
Pre-Driver
Pre-Driver
Pre-Driver
Pre-Driver
Pre-Driver
10
W
16
Vz
Vz
Vz
Vz
Vz
Vz
1.5kΩ
NC
11
13
10
14
15
12
16
3
4
9
7
GNDW
GNDU
GNDV
VccW
VccU
VinW
VccV
GND
VinU
VinV
VinX
VinY
VinZ
ALM
Vcc
1-112
[Case 2 and 3]
If items (a) to (d) are performed and the results are satisfactory, the diode module is normal.
Measure it under 1 kΩ range of a tester. Do not use a digital tester.
1-113
CN9
PC208 PC207
TB2
CN207 CN206
R201
N
are more than 100 kΩ, it is normal. P1 P
R200
ZN20
LED201
+
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
R, S, T
CN207 CN206
R201
N
R200
P1 P ZN20
LED201
+
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
R, S, T
1-114
CN9
CN207 CN206
TB2
N
are more than 100 kΩ, it is normal. RB
N
R201
R200
P ZN20
LED201
+
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
R, S, T
CN207 CN206
N RB
P ZN20
LED201
+
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
R, S, T
U
V
W
CN9
PC208 PC207
TB2
CN207 CN206
R201
N
are more than 100 kΩ, it is normal. P
R200
ZN20
LED201
+
P1
- ZN202
P TB3
R216
R215
RB PD P N
R S T U V W
U, V, W
CN9
TB2
CN207 CN206
R201
P
R200
ZN20
LED201
+
P1
- ZN202
P TB3
R216
R215
RB PD P N
R S T U V W
U, V, W
1-115
CN9
TB2
CN207 CN206
R201
N
R200
P ZN20
LED201
+
N P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
U, V, W
CN207 CN206
TB2
RB
R200
P ZN20
LED201
+
N P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
U, V, W
P1 PB
N
P If item (i) to (m) are performed and the results are
satisfactory, ISPM is normal.
Measure it under 1 kΩ range of a tester.
N
Do not use a digital tester.
CN9
TB2
R201
N
R200
P P ZN20
LED201
+
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
CN207 CN206
TB2
R201
N
R200
P P ZN20
LED201
+
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
1-116
CN9
PC208 PC207
RB TB2
RB
R201
N
R200
P
+ N ZN20
LED201
P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
CN9
RB TB2
RB
R201
N
R200
P ZN20
LED201
+
N P1
- ZN202
TB3
R216
R215
RB PD P N
R S T U V W
Indoor Unit Electronic Expansion Valve Outdoor Unit Electronic Expansion Valve
Locked Check for the liquid pipe temperature It is abnormal if the liquid pipe pressure
with during heating operation. does not increase during cooling
Fully Closed It is abnormal if the temperature does operation.
not increase.
Locked It is abnormal under the following It is abnormal if the liquid pipe pressure
with conditions; The temperature of freeze does not increase and the outlet
Slightly Open protection thermistor becomes lower temperature of the expansion valve
than the suction air temperature when decreases after the cooling operation
the unit under checking is stopped and is started.
other units are under cooling operation.
Locked It is abnormal under the following
with Electronic Expansion Valve conditions; After heating operation for
Fully Open Freeze Protection more than 30 min., the discharge gas
Thermistor
temperature of compressor is not 10oC
higher than the condensing temperature
and there is no other faults such as
excessive charge of refrigerant, etc.
Unit Other
Under Units
Checking
1-117
Resistance
Name of Parts Model Electrical Wiring Diagram Wiring No.
(Ω)
Fan Motor for Indoor Unit BL "1" - "3" R 21.1+10%
SF-200-60-4U R "3" - "5" W 32.2+10%
at 20oC
60W
for RPI-0.8FSG1, 1.0FSG1,
1.5FSG1
Fan Motor for Indoor Unit BL "1" - "3" R
SF-200-75-4U R "3" - "5" W
1
75W
for RPI-2.0FSG1, 2.5FSG1
Fan Motor for Indoor Unit BL "1" - "3" R 5.06+10%
SF-200-290-4RC R "3" - "5" W 6.61+10%
3 5
at 20oC
290W
for RPI-3.0FSG1, 4.0FSG1
Fan Motor for Indoor Unit BL "1" - "3" R
SF-200-290-4RB R "3" - "5" W
290W
for RPI-5.0FSG1
Fan Motor for Indoor Unit
SIC-72FV-D856
- -
56W
for RCI-1.0 to 3.0FSG2 DC Motor
Fan Motor for Indoor Unit
SIC-81F-D8108
- -
108W
for RCI-4.0FSG2, 5.0FSG2
Fan Motor for Indoor Unit BL "1" - "3" R 159.0+10%
CCC6719AH R "3" - "5" W 92.0+10%
P
at 20oC
35W
for RCD-1.0 to 2.0FSG1
Fan Motor for Indoor Unit BL "1" - "3" R 70.9+10%
CCC6720AH 3 5 1 R "3" - "5" W 51.7+10%
at 20oC
55W
for RCD-2.5FSG1, 3.0FSG1
Fan Motor for Indoor Unit BL "1" - "2" R 159.0+10%
CCC6719BH R "2" - "3" W 92.0+10%
CCC6719CH P at 20oC
35W x 2
for RCD-4.0FSG1
Fan Motor for Indoor Unit BL "1" - "2" R 70.9+10%
CCC6720BH 2 3 1 R "2" - "3" W 51.7+10%
CCC6720CH at 20oC
55W x 2
for RCD-5.0FSG1
1-118
Resistance
Name of Parts Model Electrical Wiring Diagram Wiring No.
(Ω)
Fan Motor for Indoor Unit
EHOCM2P4P30
DC Motor - -
for RPK-1.0FSGM,1.5FSGM 30W
2.0FSGM, 2.3FSGM
Fan Motor for Indoor Unit BL "1" - "3" R 127.9
TNO-KPPA 3 R "3" - "5" W 102.7
at 20oC
for RPF-1.0FSG, 75W
RPFI-1.0FSG
Fan Motor for Indoor Unit 1 BL "1" - "3" R 127.9
TNO-KPPA R "3" - "5" W 102.7
5
at 20oC
for RPF-1.5FSG, 35W
RPFI-1.5FSG
Fan Motor for Indoor Unit BL "1" - "3" R 112+10%
TNO-KPPA R "3" - "5" W 77+10%
for RPC-2.0FSG1 35W at 20oC
(Before Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 113+10%
TNO-KPPA R "3" - "5" W 91+10%
for RPC-2.5FSG1, 3.0FSG1 50W at 20oC
(Before Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 40+10%
TNO-KPPA R "3" - "5" W 54+10%
for RPC-4.0FSG1 95W at 20oC
(Before Alteration) 3
Fan Motor for Indoor Unit BL "1" - "3" R 25+10%
TNO-KPPA R "3" - "5" W 40+10%
for RPC-5.0FSG1 135W at 20oC
(Before Alteration) 1
Fan Motor for Indoor Unit BL "1" - "3" R 81.4+10%
SF-200-35-4T 5 R "3" - "5" W 99.0+10%
for RPC-2.0FSG1 35W at 20oC
(After Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 93.7+10%
SF-200-50-4W R "3" - "5" W 89.9+10%
for RPC-2.5FSG1, 3.0FSG1 50W at 20oC
(After Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 20.9+10%
SF-200-95-4A R "3" - "5" W 31.6+10%
for RPC-4.0FSG1 95W at 20oC
(After Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 23.2+10%
SF-200-135-4C R "3" - "5" W 27.1+10%
for RPC-5.0FSG1 135W at 20oC
(After Alteration)
1-119
Resistance
Name of Parts Model Electrical Wiring Diagram Wiring No.
(Ω)
Fan Motor for Outdoor Unit "4" - "1" 8.17
NF4501 "1" - "3" 7.97
160W
for RAS-5FSG, RAS-5FS3
Fan Motor for Outdoor Unit "4" - "1" 5.28/6.50
"1" - "3" 4.85/6.91
1 3
1-120
Resistance
Name of Parts Model
(Ω)
Drain-up Motor
256
ADP-1403
for RCI-1.0FSG2, 1.5FSG2, 2.0FSG2, at 20 oC
2.5FSG2, 3.0FSG2, 4.0FSG2, 5.0FSG2
Drain-up Motor
347
KJV-1004
for RCD-1.0FSG1, 1.5FSG1, 2.0FSG1, at 20 oC
2.5FSG1, 3.0FSG1, 4.0FSG1, 5.0FSG1
Drain-up Motor
447
PJD-05230HS
at 20 oC
for RPI-0.8FSG1, 1.0FSG1, 1.5FSG1
Solenoid Valve for Gas Bypass
2,018/1,245
ST10PA at 20 oC
for RAS-5FSG, 8FSG, 10FSG, 8FXG, 10FXG
(50/60Hz)
RAS-5FS3, 8FS3, 10FS3, 8FX3, 10FX3
Solenoid Valve for Gas Bypass
2,018/1,245
ST10PA at 20 oC
(50/60Hz)
for RAS-16FSG, 20FSG, 16FS3, 20FS3
4-Way Valve CHV-0407
RAS-5FSG 1,435
+
RAS-5FS3 at 20oC
CHV-01AJ503C1
RAS-8FSG, 8FXG
RAS-8FS3, 8FX3 CHV-0717 1,435
+
for RAS-5FSG, 8FSG, 10FSG, 8FXG, 10FXG RAS-10FSG, 10FXG CHV-01AJ503H1 at 20 oC
RAS-5FS3, 8FS3, 10FS3, 8FX3, 10FX3 RAS-10FS3, 10FX3
4-Way Valve
CHV-0717 1,435
+ at 20 oC
CHV-01AJ503H1
for RAS-16FSG, 20FSG, 16FS3, 20FS3
Compressor Motor
*1.436/1.436/0.395
401DHV
at 20 oC
for RAS-5FS3
Compressor Motor
*1.436/1.436/0.395
401DHVM
for RAS-8FS3, 10FS3, 16FS3, 20FS3 at 20 oC
8FX3, 10FX3
Compressor Motor
*3.29/2.68/0.74
400DHM
at 20 oC
for RAS-8FS3, 8FX3
Compressor Motor
*2.73/2.22/0.572
500DHM
at 20 oC
for RAS-10FS3, 10FX3
Compressor Motor
*2.28/1.68/0.507
600DHM
at 20 oC
for RAS-16FS3, 20FS3
1-121
Resistance
Name of Parts Model
(Ω)
Compressor Motor
*1.436/1.436/0.395
G402DHV
at 20 oC
for RAS-5FSG
Compressor Motor
*1.436/1.436/0.395
G402DHVM
for RAS-8FSG, 10FSG, 16FSG, 20FSG, at 20 oC
8FXG, 10FXG
Compressor Motor
*3.29/2.68/0.74
G401DHM
at 20 oC
for RAS-8FSG, 8FXG
Compressor Motor
*2.73/2.22/0.572
G501DHM
at 20 oC
for RAS-10FSG, 10FXG
Compressor Motor
*2.28/1.68/0.507
G601DHM
at 20 oC
for RAS-16FSG, 20FSG
Contactor for Compressor Motor A25: 501/401
FC-1S: 656/460
A25/FC-1S
for RAS-5FSG, 8FSG, 10FSG, 8FXG, 10FXG at 20 oC
RAS-5FS3, 8FS3, 10FS3, 8FX3, 10FX3 (50/60Hz)
Contactor for Compressor Motor A35: 501/401
FC-1S: 656/460
A35/FC-1S
for RAS-16FSG, 20FSG, at 20 oC
RAS-16FS3, 20FS3 (50/60Hz)
Compressor Motor
*0.944/0.944/0.211
404DHD
at 20 oC
for RAS-24FS5, 30FS5
Compressor Motor
*2.48/2.06/0.53
603DH
at 20 oC
for RAS-24FS5, 30FS5
Compressor Motor
*1.47/1.32/0.35
750EH
at 20 oC
for RAS-24FS5
Compressor Motor
*1.07/0.90/0.25
1200EH
at 20 oC
for RAS-30FS5
Compressor Motor
*0.944/0.944/0.211
G404DHD
at 20 oC
for RAS-24FSG1, 30FSG1
Compressor Motor
*2.48/2.06/0.53
G603DH
at 20 oC
for RAS-24FSG1, 30FSG1
Compressor Motor
*1.47/1.32/0.35
G750EH
at 20 oC
for RAS-24FSG1
Compressor Motor
*1.07/0.90/0.25
G1200EH
at 20 oC
for RAS-30FSG1
*: 380-415V, 50Hz / 380V, 60Hz / 220V, 60Hz
1-122
1-123
1-124
Operation Lump
If "TEST RUN" and the counting number of the
connected units to the remote control switch MODE FAN SPEED ON/OFF TIMER RESET
cable is correct.
(3)
Remote
Control Switch Fault Inspection Points after the Power Source OFF
Indication
No Indication * The power source is not turned ON. 1. Connection between the connector and the wires:
* The connection of the remote control Red Wire - No.1, Black Wire - No.2, White Wire - No.3
cable is incorrect. 2. Connecting Points of Remote Control Cable
3. Contact of Connectors of Remote Control Cable
* The connecting wires of power supply 4. Connection Order of each Terminal Boards
line are incorrect or loosened. 5. Screw Fastening of each Terminal Boards
Counting * The setting of unit number is incorrect. 6. Dip Switch Setting on Printed Circuit Board
number of * The connection of control cables between 7. Wire Connecting Order of Bridge Cable
connected units each indoor units are incorrect. 8. Connecting Points of Bridge Cable
is incorrect. (When one remote control switch controls 9. Contact of Connectors of Bridge Cable
multiple units.)
Back to (1) after checking
(4) Select TEST RUN MODE by depressing MODE switch. (COOL or HEAT)
(5) Depress RUN/STOP switch.
The "TEST RUN" operation will be started. (The "TEST RUN" operation will be finished after 2 hours
unit operation or by depressing the RUN/STOP switch again.)
If the units do not start or the operation lamp on the remote control switch is flickered, some
abnormalities exist.
(6)
Remote Control Inspection Points after the
Unit Condition Fault
Switch Indication Power Source OFF
The operation lamp The unit does not The connecting wires of operating 1. Connecting Order of each Terminal Boards.
flickers. (1 time/1 sec.) start. line are incorrect or loosened. The fuse on the PCB may be blown out
And the Unit No. and due to miswiring. (Can be recovered only
Alarm Code "03" flicker. once by the DSW on the PCB)
Procedures for Recovery When Transmitting
Circuit Fuse is Blown Out
1. Correct the wiring for the terminal board.
2. Setting position of the model code are shown below.
Indoor PCB DSW7
RPC (Before Alteration) ON Outdoor PCB
RPF, RPFI, RPI-8,10, OFF DSW10
RPK 1 2
ON
RCI-FSG2, RCD, ON OFF
RPI-0.8 to 5.0 OFF 1 2
RPC (After Alteration) 1 2
The operation lamp The unit does not The connection of remote control This is the same as item (3)-1, 2 and 3.
flickers. (1 time/2 sec.) start. cable is incorrect.
Indication of Flicker The unit does not The connection of the thermistors Check by the alarm code table in the service
different to above. start, or starts once or other connectors are incorrect. manual. (Do it by service people.)
and then stops. Tripping of protector exists, or else.
Normal The outdoor fans The connecting order of power Connecting Order of the Terminal Board:
rotate reversely. supply line is incorrect. TB1 in the Outdoor Unit
Normal The outdoor fans Some wires of power supply line Connecting Point of Power Supply Line.
do not start. is disconnected. Contact Outdoor Fan Motor Connector.
1-125
Do not touch any other electrical parts when operating switches on the PCB.
Do not attach or detach service cover when the power source for the outdoor unit is ON and
the outdoor unit is operated.
Turn all the dip switches of DSW4 OFF when the test run operation is completed.
1. Manual Defrost Operation 1. Defrost operation is available Do not repeat defrost operation
Starts Press PSW1 for more regardless of frosting condition frequently.
than 3 seconds during heating and total time of heating operation. When manual defrost operation is
operation, the defrost operation 2. Defrost operation in not performed accepted by PSW1, the time left before
is started after 2 minutes. when the temperature of outdoor starting defrost operation is indicated
Manual This function is not available heat exchanger is higher than at the 7-segment indicator on the PCB.
Defrost within 5 minutes after starting 10oC, high pressure is higher
heating operation. than 2.0MPa (20 kgf/cm2G) or
2. Manual Defrost Operation Thermo-OFF.
Finishes Defrost operation is Time left (every 4 seconds)
automatically ended and the
heating operation is started.
1-126
I.U.
Model
I.U.
Serial No.
I.U. Indoor Unit, O.U.: Outdoor Unit
Piping Length: m Additional Refrigerant Charge: kg
(1) General
a. Operation (Cooling/Heating)
b. Sampling Data
No. Check Item Result
1 After the operation for more than 20 min.
2 Check Pd and Td. Is Td-SH 20 to 40 deg.?
(In Case of 24 and 30HP, Td-SH is 25 to 50 deg.)
3 Is Ps 0.2 to 0.5?
(In Case of 24 and 30HP, Ps is 0.2 to 0.6)
4 Is Pd 1.2 to 2.2? (If the outdoor temperature is high, Pd becomes high.)
1-127
1-128
b. Heating Operation (It is applicable when outdoor temperature is higher than 0°C.)
NOTES:
1. The symbol with an underline indicates checking item and the mark “ ” indicates checking data.
2. Regarding (✴), the following value should be applied.
Mark ()
Power Supply
8HP 10HP 16, 20HP
380-415V/50Hz 50 62 70
380V/60Hz 60 75 84
220V/60Hz
1-129
Insert Insert
Screw Screw
Insert Screw
Insert
RAS-5FSG to RAS-10FSG, Insert
RAS-5FS3 to RAS-10FS3,
RAS-8FXG, RAS-10FXG, RAS-16FSG, RAS-20FSG,
RAS-8FX3, RAS-10FX3 RAS-16FS3, RAS-20FS3
Insert
Insert
Insert
Insert
Insert
RAS-24FSG1, RAS-30FSG1,
RAS-24FS5, RAS-30FS5
2-1
NOTE:
When removing screws for front service panel, remove the screw at the lower part of panel firstly.
Screw Screw
RAS-5FSG to RAS-10FSG,
RAS-5FS3 to RAS-10FS3, RAS-16FSG, RAS-20FSG,
RAS-8FXG, RAS-10FXG, RAS-16FS3, RAS-20FS3
RAS-8FX3, RAS-10FX3
Screw
RAS-24FSG1, RAS-30FSG1,
RAS-24FS5, RAS-30FS5
2-2
RAS-5FSG to RAS-10FSG,
RAS-5FS3 to RAS-10FS3, RAS-16FSG, RAS-20FSG,
RAS-8FXG, RAS-10FXG, RAS-16FS3, RAS-20FS3
RAS-8FX3, RAS-10FX3
Screw
RAS-24FSG1, RAS-30FSG1,
RAS-24FS5, RAS-30FS5
2-3
Propeller Fan
Nut
Flat Washer
Motor Shaft
2-4
Bolt
Motor Shaft
Motor
Motor Clamp
Electrical Box
Connector
NOTES:
1. Make the cord outlet of the motor directing downward when mounting the motor.
2. Firmly fix the motor wires onto the motor clamp with the plastic tie, not to touch the propeller fans.
3. Mounting Propeller Fan
Put and push the propeller fan by identifying the mark with the cut part of the motor shaft.
Firmly fix the propeller fan twice with a tightening torque from 14.55 N m to 15.0 N m after the head of
2-5
Before starting this work, collect refrigerant into a cylinder from the cycle.
(1) Remove front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Release the lace for top cap of the compressor and remove the top cap.
(3) Remove the Td thermistor on the top of the compressor.
NOTE:
The thermostat fixer, holder, thermostat holder are used again when reassembling.
Keep them in a box so that the parts are stored correctly.
Water-proof Cover
Cap
Lace
Thermostat
Holder
Holder
Td
Thermistor Thermostat
Fixer
2-6
(4) Release the lace for the water-proof cover, open the water-proof cover from the front side.
NOTE:
Remove the water-proof cover in the arrow mark direction as shown by paying attention to the cut
part of the water-proof cover in order to avoid any damages.
(5) Remove the terminal cover for the compressor and disconnect the wiring to the compressor
terminals. Check to ensure that the terminals Nos. are indicated. If the terminal Nos. are not
identified, at reassembling, the compressor will fail due to reverse rotation.
NOTES:
1. Check to ensure that the faston terminals for the compressor are normal. When a pulling force of
20N or more is required, it is normal. If abnormal, replace the faston terminals with new ones.
2. Check to ensure that wires are firmly fixed.
3. It is recommended that the faston terminals be clamped to increase a contacting force after
replacing the compressor.
Water-proof Cover
Indication of
Terminal Number
V
U
W
Mark Band
Compressor
Wires
Terminal Box
Pull upper part of the cover.
2-7
(6) Remove the heater cover and the spring for the oil heater, and release the oil heater.
Discharge Pipe
Two Spanners
2-8
Suction Pipe
(9) Remove three nuts fixing the compressor and remove the compressor.
NOTE:
When lifting the compressor, hold the discharge pipe vertically and turn it to the right, and pull the
compressor towards the front side by paying attention to the compressor leg not to touch the suction
pipe.
(10) Regarding remounting the compressor work, Adjustable Wrench or Spanner,
Tool Phillips Screwdriver
perform the above work in the reverse processes.
Suction Pipe
Front
Pull out the compressor toward the front side, Side
and remove the vibration-proof rubbers.
2-9
Before starting this work, collect refrigerant into a cylinder from the cycle.
(1) Remove front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Release the lace for top cap of the compressor and remove the top cap.
(3) Remove the Td thermistor on the top of the compressor.
NOTE:
The thermostat fixer, holder, thermostat holder are used again when reassembling.
Keep them in a box so that the parts are stored correctly.
Water-proof Cover
Cap
Lace
Thermostat
Holder
Holder
Td
Thermistor Thermostat
Fixer
2-10
(4) Release the lace for the water-proof cover, open the water-proof cover from the front side.
NOTE:
Remove the water-proof cover in the arrow mark direction as shown by paying attention to the cut
part of the water-proof cover in order to avoid any damages.
(5) Remove the terminal cover for the compressor and disconnect the wiring to the compressor
terminals. Check to ensure that the terminals Nos. are indicated. If the terminal Nos. are not
identified, at reassembling, the compressor will fail due to reverse rotation.
NOTES:
1. Check to ensure that the faston terminals for the compressor are normal. When a pulling force of
20N or more is required, it is normal. If abnormal, replace the faston terminals with new ones.
2. Check to ensure that wires are firmly fixed.
3. It is recommended that the faston terminals be clamped to increase a contacting force after
replacing the compressor.
Water-proof Cover
Indication of Indication of
Terminal Number Terminal Number
V V
U U
W W
Mark Band
Compressor Compressor
Wires Wires
Terminal Box Terminal Box
Pull upper part of the cover. Pull upper part of the cover.
2-11
(6) Remove the heater cover and the spring for the oil heater, and release the oil heater.
Discharge Pipe
Two Spanners
2-12
(8) Remove the flare-nut at the compressor side, and disconnect the feeding oil pipe.
There is a possibility that the oil may flow from the inside of the feeding oil pipe.
Therefore, prepare an oil pan, etc. to collect the oil.
NOTES:
1. Completely wipe off the oil if the oil is spread to the other parts such as the compressor cover,
wiring, bottom base, etc. If not, this will cause many problems to the unit.
2. If the oil is spilt, charge new oil equivalent to the spilt oil.
3. Check to ensure that the oil is not foul.
If foul, replace it with new one. Tool Adjustable Wrench or Spanner
Oil Separator
Oil Pan
Suction Pipe
2-13
(10) Remove three nuts fixing the compressor and remove the compressor.
There is no nut at the left rear side.
NOTES:
1. Pull out the compressor without removing the oil heater.
Remove the oil heater after the compressor is put outside the unit. (Constant Comp. Only)
2. When lifting the compressor, hold the discharge pipe vertically and turn it to the left and pull the
compressor towards the front side by paying attention to the compressor leg not to touch the
suction pipe.
(11) Regarding remounting the compressor work, perform the above work in the reverse processes.
Suction Pipe
Pull out towards
Pay attention to front side.
this part not to touch
the compressor leg.
Special Nut
Vibration-proof Rubber
Front Side
2-14
Before starting this work, collect refrigerant into a cylinder from the cycle.
(1) Remove front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Release the lace for top cap of the compressor and remove the top cap.
(3) Remove the holder for Td thermistor on the compressor.
(4) Remove the Td thermistor on the top of the compressor.
NOTE:
The thermostat fixer, holder, thermostat holder and holder for Td thermistor are used again when
reassembling.
Keep them in a box so that the parts are
stored correctly. Phillips Screwdriver, Charge-Hose,
Tool Adjustable Wrench or Spanner
MC1 MC2
MC3 MC4
Thermostat
Holder
Holder
2-15
(5) Release the lace for the water-proof cover, open the water-proof cover from the front side.
NOTE:
Remove the water-proof cover in the arrow mark direction as shown by paying attention to the cut
part of the water-proof cover in order to avoid any damages.
(6) Remove the spring for the oil heater.
Oil Heater
(MC1 Only)
Direction to Remove
Water-proof Cover
Oil Heater
(7) Remove the terminal cover for the compressor and disconnect the wiring to the compressor
terminals. Check to ensure that the terminals Nos. are indicated. If the terminal Nos. are not
identified, at reassembling, the compressor will fail due to reverse rotation.
NOTES:
1. Check to ensure that the faston terminals for the compressor are normal. When a pulling force of
20N or more is required, it is normal. If abnormal, replace the faston terminals with new ones.
2. Check to ensure that wires are firmly fixed.
3. It is recommended that the faston terminals be clamped to increase a contacting force after
replacing the compressor.
Tool Adjustable Wrench or Spanner
Indication of Indication of
Terminal Number Terminal Number
V V
U U
W W
Compressor Compressor
Wires Wires
Terminal Box Terminal Box
Pull upper part of the cover. Pull upper part of the cover.
2-16
Discharge Pipe
Double Spanners
(9) Remove the flare-nut at the compressor side, and disconnect the evacuating oil pipe.
There is a possibility that the oil may flow from the inside of the evacuating oil pipe.
Therefore, prepare an oil pan, etc. to collect the oil.
NOTES:
1. Completely wipe off the oil if the oil is spread to the other parts such as the compressor cover,
wiring, bottom base, etc. If not, this will cause many problems to the unit.
2. If the oil is spilt, charge new oil equivalent to the spilt oil.
3. Check to ensure that the oil is not foul.
If foul, replace it with new one. Tool Adjustable Wrench or Spanner
Oil Pan
2-17
(10) Remove the suction pipe of the compressor. Tool Adjustable Wrench or Spanner
Suction Pipe
(11) Remove three nuts fixing the compressor and remove the compressor.
There is no nut at the left rear side.
NOTES:
1. Pull out the compressor without removing the oil heater.
Remove the oil heater after the compressor is put outside the unit. (Constant Comp. Only)
2. When lifting the compressor, hold the discharge pipe vertically and turn it to the left and pull the
compressor towards the front side by paying attention to the compressor leg not to touch the
suction pipe.
(12) Regarding remounting the compressor work, Adjustable Wrench or Spanner,
Tool Phillips Screwdriver
perform the above work in the reverse processes.
Suction Pipe
Pull out towards
Pay attention to front side.
this part not to touch
the compressor leg.
Special Nut
Vibration-proof Rubber
Front Side
2-18
Before starting this work, collect refrigerant into a cylinder from the cycle.
(1) Remove front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Release the lace for top cap of the compressor and remove the top cap.
Water-proof Cover
2-19
(3) Remove the electrical box cover according to the item 2.1.15 “Removing Electrical Components”.
(4) Disconnect the connectors (CN57 and CN58) of oil heaters.
(5) Remove the terminal box cover of the compressor and disconnect the compressor wires.
NOTE:
Check the terminal No. and mark band at disconnecting work.
If wired wrong when reassembling, the compressor will be damaged due to reverse rotation.
Compressor Wires
(6) Remove the suction pipe (connecting flange with four bolts)
and discharge pipe (connecting with flare nut).
Adjustable Wrench or Spanner,
Tool Phillips Screwdriver
Suction Pipe
Discharge Pipe
2-20
Thermostat
Holder
Holder
Td
Thermistor Thermostat
Fixer
2-21
(10) Remove the 4 special nuts, 4 vibration proof rubbers, water-proof cover, oil heater and slide bases
from the compressor.
NOTE:
The special nuts, vibration proof rubbers, slide bases, oil heater and water-proof cover are used
again when reassembling.
Keep them in a box so that the parts are Adjustable Wrench or Spanner,
Tool Phillips Screwdriver
stored correctly.
Special Nut
Vibration-proof Rubber
Oil Heater
2-22
2.1.9 Removing High Pressure Switch, High Pressure Sensor and Low Pressure Sensor
(1) Remove the front service panel according to item 2.1.2 “Removing Front Service Panel”.
(2) Collect all refrigerant from the low pressure side check joint when the high pressure switch is
removed. Use two spanners when removing
the pressure sensor. Adjustable Wrench or Spanner
Tool and Charge-Hose
High Pressure
Low Pressure Sensor
Sensor Low Pressure
Check Joint
Union
2-23
A-1. Removing High Pressure Switch (RAS-5FSG, RAS-8FSG, RAS-10FSG, RAS-5FS3, RAS-8FS3,
RAS-10FS3, RAS-8FXG, RAS-10FXG, RAS-8FX3 and RAS-10FX3)
(1) Disconnect the faston terminals.
(2) Remove the high pressure switch from the brazing part of the discharge pipe by a burner.
NOTE:
Do not expose the refrigeration cycle to the atmosphere for a long period to avoid mixing of water
and foreign particles into the refrigeration cycle.
If exposed for a long period, seal the hole. Adjustable Wrench or Spanner,
Tool Phillips Screwdriver
High Pressure
Switch
Union
2-24
Position of Position of
Pressure Sensors Pressure Sensors
8 and 10HP
Only
20HP Only
RAS-5FSG, 5FS3 RAS-16FSG, 16FS3
8FSG, 8FS3 20FSG, 20FS3
10FSG, 10FS3
Electrical Box Water-proof
RAS-8FXG, 8FX3 Cap
10FXG, 10FX3 Low Pressure Sensor High Pressure Sensor
Screw
2-25
Do not touch the electrical parts when the LED3 (Red) on the SNUBBER PCB (PCB5) or
the LED2 (Red) on the Inverter PCB (PCB3) is lit, since the voltage is higher than 50V.
(1) Remove the front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Remove the coil for the reversing valve as shown below.
RVR1 or 211
RAS-24FSG1, 24FS5
30FSG1, 30FS5
2-26
Do not touch the electrical parts when the LED3 (Red) on the SNUBBER PCB (PCB5) or
the LED2 (Red) on the Inverter PCB (PCB3) is lit, since the voltage is higher than 50V.
(1) Remove the front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Remove the fixing screw (1 piece) for solenoid valve coil.
(3) Remove the solenoid valve coil after removing Adjustable Wrench, Spanner,
the fixing screw (1 piece) for the solenoid valve. Tool Phillips Screwdriver
RAS-5FSG, 5FS3, 8FSG, 8FS3, 10FSG, 10FS3, 16FSG, 16FS3, 20FSG and 20FS3
RAS-8FXG, 8FX3, 10FXG, 10FX3
SVA or 20A SVA
SVA or 20A
SVB
SVC
SVB: Solenoid Valve Coil for Liquid Bypass (Only for FX Series)
SVC: Solenoid Valve Coil for Liquid Bypass (Only for FX Series)
SVA3 SVF1
B B
A
B SVF2
SVE2
SVE1
Solenoid Solenoid
Valve Coil Valve Coil
SVF1, SVF2...for Oil Return SVA1 to SVA4...for Gas Bypass SVD1, SVD2...for Heat Exchanger Change
SVE1, SVE2...for Heat Exchanger
2-27
Do not touch the electrical parts when the LED3 (Red) on the SNUBBER PCB (PCB5) or
the LED2 (Red) on the Inverter PCB (PCB3) is lit, since the voltage is higher than 50V.
(1) Remove the front service panel according to the item 2.1.2 “Removing Front Service Panel”.
(2) Remove two (2) screws fixing the electrical box cover and remove the electrical box cover.
(3) Pull out the fixing plate for the thermistor from the pipe after detaching the CORK TAPE, and remove
the thermistor for the liquid pipe.
THM11
THM10
Thermistor
Thermistor
Holder
THM11
THM10 THM5 Seal completely
by cork tape.
RAS-24FSG1, 24FS5
30FSG1, 30FS5
2-28
Power Source
Terminal Board for Terminal Board
Control Circuit
Stop Valve
Brazing
RVR1 or 211
8 and 10HP
Only 20HP Only
RAS-5FSG, 5FS3 RAS-16FSG, 16FS3
8FSG, 8FS3 20FSG, 20FS3
10FSG, 10FS3
Brazing
RVR1
Brazing RVR2
8 and 10HP
Only
RAS-8FXG, 8FX3
10FXG, 10FX3
2-29
Power Source
Terminal Board for Terminal Board
Control Circuit
Stop Valve
R407
R407
Brazing
RVR2
Brazing
Brazing
RAS-24FSG1, 24FS5
30FSG1, 30FS5
2-30
Do not touch the electrical parts when the LED3 (Red) on the SNUBBER PCB (PCB5) or
the LED2 (Red) on the Inverter PCB (PCB3) is lit, since the voltage is higher than 50V.
1. When replacing transistor module (IPM) and diode module (DM) on heat radiation fins, spread silicone
grease (made by Shinetsu Chemical Co., G746) lightly over the surface touching fins.
2. Identify terminals Nos. with the mark band Nos. when reassembling. If incorrectly connected,
malfunctions or damages of electric components will occur.
3. Correctly insert two wires of U and V phases for the power cable of Inv. Comp. into the current sensor,
CTU and CTV on PCB3. Connect the U phase of the power cable and U phase of the current sensor as
a combination, and the V phase of the power cable and V phase of the current sensor as a combination
respectively. If incorrectly connected, malfunction or damages will occur.
4. Do not clamp electrical wires between a mounting electric component and plates or electric parts when a
PCB is remounted.
5. Screws, bushes and collars are used to fix the inverter PCB. Check to ensure that the bushes and
collars are used when fixing the inverter PCB again. If not used, it may cause malfunction.
6. In the case that the control PCB is replaced, set all the dip switch at the same position as the original
ones were. If not set, malfunction may occur.
7. Do not apply a strong force to electric components and PCBs to avoid damages.
PCB
Screw Collar
PCB
Screw Bush
2-31
(2) Others
Other parts located at the rear side of PCB mounting plate and AC chopper mounting plate should be
replaced as follows.
(a) Remove two (2) screws fixing the mounting plate for the PCB and turn the plate towards the front
side.
(b) Remove two (2) screws fixing the mounting plate for the AC chopper and turn the plate
towards the front side.
Tool Phillips Screwdriver
2-32
Do not touch the electrical parts when the LED201 (Red) on the ISPM(1) is lit, since the
voltage is higher than 50V.
1. When replacing inverter system power module (ISPM for 380-415/380V 50/60Hz, ISPM1 and ISPM2 for
220V 60Hz) on heat radiation fins, spread silicone grease (made by Shinetsu Chemical Co., G746)
lightly over the surface touching fins.
2. Identify terminals Nos. with the mark band Nos. when reassembling. If incorrectly connected,
malfunctions or damages of electric components will occur.
3. Connect the cables of the inverter compressor correctly to ISPM(1). If incorrectly connected,
malfunction or damages will occur.
4. Do not clamp electrical wires between a mounting electric component and plates or electric parts when a
ISPM(1) is remounted.
5. In the case that the control PCB is replaced, set all the dip switch at the same position as the original
ones were. If not set, malfunction may occur.
6. Do not apply a strong force to electric components and PCBs to avoid damages.
2-33
C12
C10
R S T
Middle Part of Holder
+
IC2 IC9
M63826P
M63826P
+ +
N
L3
1 2 3 4 1 2 3 4 1 2
DSW1 DSW2 DSW3 PSW1 PSW2 PSW3
L2
1 2 3 4 5 6 1 2 3 4 5 6 7 8
DSW4 DSW5
L1
1 2 1 2 3 4 1 2 1 2 3 4
DSW6 DSW7 DSW8 DSW9
PC1 PC2
D122
R144 PCB
R S T MP
L1 L2 L3 N
Details of A
PCB
PCB Mounting Plate Screw
for PCB Mounting Plate
32A
32A
(a)
R S T
(a)
(a)
(a)
N
L3
L2
L1
R S T MP
L1 L2 L3 N
Capacitor Noise
Filter
2-34
This example figure is 380-415V 50Hz Fuse for Fan Motor (MOF2) Fuse for Inverter
and 380V 60Hz. Reactor Magnetic Contactor Noise Filter Compressor (MC1)
CN201 R1 S1
PD P1 P N RB
RSTUVW
L1 L2 L3 N
10A
COM2
MAIN1 SUB1 COM1
Resistor
ISPM Capacitor
for Fan Motor
AC Chopper Smoothing Capacitor (MOF2) Terminal Board
for Inverter for Power Source
RB
TB3
R
CN207
S
CN206
T
for Compressor
Power Cable
LED201
U
V
Control Cable
W
for PCB
Control Cable
for ISPM2
Fixing Screw for ISPM1
Do not touch the any electrical parts during LED201 (Red) on ISPM(1) is ON.
If touched, electric shock will occur.
2-35
Control Cable
Control
for Fan Motor
Cable
PD
W
V
for Fan Motor
Power Cable
P
U
N
Do not touch the any electrical parts during LED201 (Red) on ISPM(1) is ON.
If touched, electric shock will occur.
2-36
Screws
2-37
(2) There are three (3) PCBs. The control PCB is fixed with four (4) PCB holders. Clamp the center of
the PCB holders by a long-nose plier and pull out the PCB.
(3) Remove three (3) M4 screws and remove the
AC chopper module PCB. Tool Phillips Screwdriver, Long-nose Pliers
G RPI-0.8FSG1 to RPI-2.5FSG1
PCB1 PCB1
TB TB
G RPI-3.0FSG1 to RPI-5.0FSG1
ATTENTION:
Do not touch any components on the PCB.
Do not apply excessive forces to the PCB or it will cause a malfunction.
2-38
(1) Remove the electrical box cover according to the item 2.2.2 “Removing Printed Circuit Board (PCB)”.
(2) Free the cables inside of the electrical box.
Disconnect the connector for the float switch electrical wiring. Disconnect the connectors for the
electronic expansion valve, the gas pipe thermistor, liquid pipe thermistor, discharge gas thermistor
and the fan motor from the PCB.
(There are two (2) connectors for the fan motor. One is located on the AC chopper module PCB, and
remove it.)
< Removing Indoor Fan and Fan Motor from Side (Electrical Box Side) of Unit
(Only for RPI-3.0 to 5.0FSG1>
Q’ty of Casing and Runner: Each 2 / Q’ty of Fan Motor: 1
Removing them according to the following items (3) to (10).
(3) Remove seven (7) screws fixing the
electrical box and remove the electrical box. Tool Phillips Screwdriver
Screws
(M4x7)
Electrical Box
2-39
(4) Remove the electrical box and the fan motor assembly can be seen.
Remove the wires fixed by the wire clamp on the fan motor fixing plate.
Wire
Wire Clamp
(5) Remove four (4) M4 screws fixing the casing at the side of the casing and remove the ring of the
casing.
Tool Phillips Screwdriver
Ring
Runner
(6) Loosen the screw fixing the fan runner onto the fan motor shaft by the adjustable wrench and pull out
the fan runner.
2-40
(7) Remove four (4) screws fixing the casing onto the motor fixing plate and pull out the casing.
When pulling out the casing, turn the casing by an angle of 180°.
M4 Screws
M4 Screws
(8) Remove two (2) M4 screws fixing the flange in front of the fan motor and remove the flange.
Flange
M4 Screws
2-41
(9) Remove two (2) lower M6 screws fixing the motor base and loosen the upper two (2) M6 screws.
(10) Remove four (4) M4 screws fixing the ring of the casing at the rear side of the fan motor and remove
the motor base, the ring and the runner at the
same time. Tool Phillips Screwdriver
M6 Screws
Runner
Motor Base
Motor Base
Ring
M4 Screws
Fan Motor
(11) Loosen the screw fixing the runner onto the fan motor by the adjustable wrench and pull out the
runner.
Tool Phillips Screwdriver, Adjustable Wrench
ATTENTION:
The total weight of the motor base, the fan motor, the ring and the runner is approximately 15kg.
Carefully perform the above removing work.
2-42
< Removing Indoor Fan and Fan Motor from Bottom Side (For All Models)>
Disconnect the connector for the fan motor wires according to the procedures (1) and (2) in page 2-39.
(3) Remove the lower M4 screws (Q’ty: A) fixing the suction flange.
Q’ty of Screws (A): 2 (For RPI-0.8 to 1.5FSG1)
3 (For RPI-2.0 to 4.0FSG1)
4 (For RPI-5.0FSG1) Tool Phillips Screwdriver
Suction Flange
Screws (M4x A )
(4) Remove the lower M4 screws (Q’ty: B) fixing the lower cover at the indoor fan side and remove the
lower cover.
Q’ty of Screws (B): 11 (For RPI-0.8 to 1.5FSG1)
12 (For RPI-2.0 to 5.0FSG1) Tool Phillips Screwdriver
Screws (M4x B )
Lower Cover
2-43
(5) Remove the lower cover and the fan assembly can be seen.
Remove the wires for the motor fixed by the cord clamp of the fan motor fixing plate.
Screws (M4x8)
ATTENTION:
The total weight of the motor base, the fan motor, the ring and the runner is approximately 15kg.
Carefully perform the above removing work.
2-44
Hook
Casing
(7) Remove two (2) screws fixing the motor fixing band to the motor base and remove the runner with
the motor shaft.
(8) Loosen the screws fixing the fan motor and the runner by the hexagonal wrench (for M6 screw)
and pull out remove the runner.
Tool Phillips Screwdriver, Hexagonal Wrench
Hexagonal Wrench
Motor Fixing Band
Motor Shaft
Screw
Runner
ATTENTION:
The total weight of the motor base, the fan motor, the ring and the runner is approximately 15kg.
Carefully perform the above removing work.
2-45
Screws (M4 x 8)
Service Cover
(2) Remove the cork tape, pipe insulations and the thermistor holder, the thermistors for pipes can be
removed.
Tool Phillips Screwdriver
Expansion Valve
Thermistor for
Gas Piping
Thermistor for
Liquid Piping
2-46
Float Switch
ATTENTION:
When reassembling, handle the float switch carefully.
(Tightening Torque: Approx. 0.3N-m)
If the float switch is dropped, malfunction will occur.
2-47
A
Drain Connection
Drain Pan
View from A
Drain Pump
2-48
Suction Flange
Screws (M4x A )
(2) Remove the lower M4 screws (Q’ty: B) fixing the lower cover at the indoor fan side and remove the
lower cover.
* Q’ty of Screws (B): 11 (For RPI-0.8 to 1.5FSG1)
12 (For RPI-2.0 to 5.0FSG1) Tool Phillips Screwdriver
Screws (M4x B )
Lower Cover
2-49
(3) Remove the lower M4 screws (Q’ty: D) fixing the discharge flange.
* Q’ty of Screws (D): 2 (For RPI-0.8 to 1.5FSG1)
3 (For RPI-2.0 to 4.0FSG1)
4 (For RPI-5.0FSG1) Tool Phillips Screwdriver
Discharge Flange
Screws (M4xD)
(4) Remove eight (8) M4 screws fixing the lower cover at the indoor heat exchanger side and remove the
lower cover.
(5) Remove M4 screws (eight (8) for each side) fixing the side frames at both sides and remove the side
frames.
(6) Pull the drain pan downward. Phillips Screwdriver,
Tool Bucket (approx. 5 liters content)
Screws (M4x8)
(Both Sides)
Drain Pan
Screws (M4x8)
Lower Cover
2-50
Screws
PCB
Expanded Part
of Holder
PCB
PCB Holders
ATTENTION:
Do not touch any parts on the PCB.
Do not apply a strong force to the PCB, or it will cause malfunction of the PCB.
2-51
(5) Remove three (3) screws fixing the ring and remove the ring.
(6) Loosen the screw fixing the fan runner onto the fan motor shaft and remove the near side fan runner.
(7) Remove the screw fixing the fan casing and
pull out the near side fan casing. Phillips Screwdriver,
Tool Hexagonal Wrench (M8)
Fan Casing
Fixing Screws
2-52
(8) Remove three (3) screws fixing the ring onto the
rear side fan casing and remove the ring. Tool Phillips Screwdriver
Fan Casing
Ring
Motor
Motor Base
2-53
Screws
Maintenance Cover
(3) Remove the electronic expansion valve by using two (2) spanners.
(4) Remove the thermistors attaching the pipe of
heat exchanger. Tool Phillips Screwdriver, Spanner
2-54
Knob
Hook
2-55
Electrical
Box Cover
Screws
Electrical
Box
Connector for
Louver Motor
CN17
PCB
2-56
(2) Remove the air intake grille from the optional air panel.
(3) Remove the four (4) corner pockets as below.
Insert slotted screwdriver or coin into the slot of corner pocket and unhook the hook of corner pocket
in number order of 1 to 4.
(4) Remove four (4) screws of the optional air panel and hook it by using the hinge to the hook of the
drain pan as shown in the figure.
Remove the optional air panel from the unit. Tool Phillips Screwdriver
4
Hinge
Coin or
1 Slotted Screwdriver
2
3
Lifting
Corner Position
Hook
Fixing Screw
Fixing Plate
for Electrical
Wiring
Screw for
Drain Pump Fixing Plate
Motor Connector
Float Switch Discharge Thermistor
(PCN6)
Connector (CN14) Connector (THM2)
2-57
Motor
Nut (3 pcs.)
Runner
Flat Washer
Cap Nut
Bell-Mouth
Screw (3 pcs.)
2-58
NOTE:
Do not touch electrical components on the PCBs.
If great force is applied to the PCB, it will be faulty.
Holder
PCB
Plier
PCB
2-59
Rubber Plug
Drain Pan
Bolt for
Fixing Drain Pan
2-60
Fixing Plate
Drain Hose
Screws
Drain-Up Hose Band
Mechanism
Fixing Base
Nut
2-61
Butyl Sheet
Thermistor for
Fixing Plate Liquid Piping
of Thermistor
Butyl Sheet
Fixing Plate
of Thermistor
Thermistor
2-62
Expansion Valve
2-63
(9) Tighten the lock nut with spanner after tightening lightly by hand.
The tightening torque shall be within the range of 12Nm (120kg-cm) to 15Nm (150kg-cm).
NOTE:
Do not apply the strong forces such as the rotating torque and the bending load to the motor by
holding the motor by hand when tightening the lock nut.
The direction of the eccentric part of the motor is assembled as the eccentric part of although the
motor is directed toward the counter direction of the fittings for piping at the valve body, the alteration
of this direction do not affect the open/close function of the valve. Therefore, the adjustment of the
direction of the motor part is not required if the position of the motor is moved toward the rotating
direction after replacement as shown below.
However, pay attention to the direction of the motor for the coil of the electronic expansion valve not
to touch other pipings and the side plate of the electrical box.
Tool Phillips Screwdriver
Pulse Motor
Drive Part
Gear
Output Shaft
Lock Nut
Bellows Adjustment of direction is not required.
Valve
Valve
Valve Part
Valve Body Sheet
(10) After completion of the replacement, attach the electronic expansion valve in the reverse procedures
for removing.
2-64
Screw
Corner Cover
Optional
Air Panel
Louver Shaft
Optional
Air Panel
Screw
Automatic Connector
Louver Motor
2-65
Hinges
Screw
Electrical Box
2-66
PCB2 PCB2
PCN4 TB (AC Chopper Model)
CN7
CN4
PCB PCB
Hinge
Hook
Screws
Screw x 2
(M6x30, Only for P-G46)
2-67
Screws
Bell-Mouth Bell-Mouth
Bell-Mouth Bell-Mouth
Fixing Screw Fixing Screw
Bell-Mouth
2-68
Nut
Fan Motor
Earth
Runner
Flat Washer
Cap Nut
2-69
NOTE:
Do not touch electrical components on the PCBs.
If great force is applied to the PCB, it will be faulty.
Holder Holder
AC Chopper
PCB
Module PCB
PCB
Expanded Part
Electrical Box Cover
of Holder
2-70
Screws
Service Access
Cover Fixing Plate for
Connector Fixing Screws Float Switch
2-71
Fixing Plate
Connector
Drain Hose
Drain-Up Mechanism
2-72
Enforced Plate
Drain Pan
Drain Pan
Fixing Plate for Drain Pan
Fixing Plate for Drain Pan
Support Plate
2-73
Insulation
Gas Side
Thermistor Holder
Butyl Sheet
2-74
Expansion Valve
2-75
(9) Tighten the lock nut with spanner after tightening lightly by hand.
The tightening torque shall be within the range of 12Nm (120kg-cm) to 15Nm (150kg-cm).
NOTE:
Do not apply the strong forces such as the rotating torque and the bending load to the motor by
holding the motor by hand when tightening the lock nut.
The direction of the eccentric part of the motor is assembled as the eccentric part of although the
motor is directed toward the counter direction of the fittings for piping at the valve body, the alteration
of this direction do not affect the open/close function of the valve. Therefore, the adjustment of the
direction of the motor part is not required if the position of the motor is moved toward the rotating
direction after replacement as shown below.
However, pay attention to the direction of the motor for the coil of the electronic expansion valve not
to touch other pipings and the side plate of the electrical box.
Tool Phillips Screwdriver
Pulse Motor
Drive Part
Gear
Output Shaft
Lock Nut
Bellows Adjustment of direction is not required.
Valve
Valve
Valve Part
Valve Body Sheet
(10) After completion of the replacement, attach the electronic expansion valve in the reverse procedures
for removing.
2-76
Insulation
C Cover
Assembly
Optional
Air Panel
Insulation
(3) Remove two (2) screws fixing the C cover assembly and remove the C cover assembly from the
optional air panel.
Tool Phillips Screwdriver
Screws
C Cover
Assembly
Motor
Assembly
Optional
Air Panel
2-77
(4) Remove two (2) screws fixing the motor assembly and remove two (2) stoppers by lifting the motor
assembly upwards (to the arrow direction) by hand.
The stopper can be removed by pulling. The motor assembly can be removed by removing the
connector at the same time.
Tool Phillips Screwdriver
Screws
Connector
Motor Assembly
Stopper
(5) Remove one (1) screw fixing the crank and cut the plastic tie fixing the motor cord.
Remove the motor after removing two fixing screws.
Plastic Tie
Motor Screw
Screws
Crank
2-78
(2) Slowly pull the lower side of the air intake grille toward the front side.
(3) Lift up the air filter, detach the hooks and draw the air filter downward.
Air Filter
2-79
Screws
(4) Hold both sides of the front panel, pull the front panel toward the front side slowly and lift up the front
panel with paying attention not to touch the louver at the air outlet.
(5) Lift up the front panel slightly, the three (3) catches at the upper part of the front panel are detached
from the holes of the unit body and the front panel can be removed toward the front side.
NOTE:
Do NOT hit the front panel when removing the front panel. It may break the unit body.
Front Panel
Front Panel
Extrusion
Square Hole
Unit Body
(6) For attaching the front panel, attach the front panel at the air outlet side firstly, and attach three (3)
catches at the upper part of the front panel.
(7) Open the front panel as the procedure (1), and fix the screw (1 piece) at the center of the front panel.
2-80
(8) There are three (3) catches at the inner side of the front panel. Press the catch part from the front
side and check to ensure that there is no gap between the front panel and the unit body.
NOTE:
If the gap exists between the front panel and the air outlet, it may cause air leakage and dewing may
occur at the front panel and the dew may drop.
(9) After attaching the front panel, tighten three (3) screws at the lower part of the air outlet and cover
them with the bushes.
Stoppers
No Gap
2-81
Connector (white)
Connector (black)
Screws
AS Motor
AS Motor
Connector (black)
Connector (white)
Louver (gray)
Louver (white)
2-82
2.6.4 Removing Thermistors for Liquid Pipe, Gas Pipe, Discharge Air and Suction Air
(1) Remove the front panel according to the item 2.6.2 “Removing Front Panel”.
(2) Remove the electrical box according to the item 2.6.5 “Removing Electrical Box Cover”.
(3) Removing Thermistor for Liquid Pipe
Remove the butyl sheet protecting the thermistor for liquid pipe and remove the thermistor from the
holder.
Heat Exchanger
Expansion Valve
Thermistor Holder
Lead Wire of Thermistor
Butyl Sheet
Thermistor Holder
2-83
Vertical Louver
Vertical Louver
Holder
Thermistor for
Discharge Air
Hook
Thermistor for
Discharge Air 120mm
Holder
20mm
Plastic Tie
2-84
Connector for
AS Motor
Terminal Block
(4) Remove lead wires for expansion valve, fan motor, thermistor for liquid pipe and gas pipe, AS motor
(✕2) and remote control switch from the connectors. And also remove earth wires (✕2) of the heat
exchanger.
(5) Remove the thermistor for discharge air from the holder fixed at the vertical louver of the air outlet.
(6) Draw out the electrical box toward the front side after removing two (2) screws fixing the electrical
box.
(7) For attaching the electrical box, set the electrical box, connect the connectors and perform the
reverse procedures for removing the electrical box.
2-85
PCB Base 2
Electrical Box Cover
Earth Wire
Catch
High Voltage
PCB
Catch
Low Voltage
PCB
CN17
Catch
PCB Base 1
CN11
Screw
Terminal Board
PCB Base Z
Electrical Box
PCBI (P)
Module (black)
Electrical Box
Details of PCB
(6) After the completion of replacement of PCB, connect the connectors to the PCB in the reverse
procedures of removing. And firstly set the high voltage PCB to the electrical box and then set the
low voltage PCB to the electrical box.
2-86
Phillips Screwdriver,
Tool Bucket (approx. 5 liters content)
Heat Exchanger
Heat Exchanger
Drain Pan
Release Catch (B)
2-87
Heat Exchanger
Screws
Piping Stay
Rear Side of Indoor Unit
(5) Release the catch holding the left side of the heat exchanger and remove one screw fixing the heat
exchanger.
Screw
Release Catch
2-88
(6) Remove one screw fixing the heat exchanger and release the catch holding the right side of the heat
exchanger.
Tool Phillips Screwdriver
Release Catch
Screw
(7) Lift up the heat exchanger, draw out the rear piping of the heat exchanger from the square hole by
pulling the upper part of the heat exchanger forward and remove the heat exchanger.
Unit body
Square Hole
Heat Exchanger
(8) For attaching the heat exchanger, perform the reverse procedures for removing.
NOTE:
After attaching the heat exchanger, check to ensure that the hooks and the screws at the right and
the left sides of the heat exchanger are correctly attached.
2-89
Lever
Bearing (inside)
Push levers on both sides to release catches.
(3) Remove the motor holders 1 and 2 fixing the fan motor.
For removing the motor holder, insert the screwdriver at the catch part and screw it.
(4) After removing the motor holder 1, loosen one (1) screw fixing the motor shaft and the fan.
Motor Holder 2
Fan Motor
Motor Holder 1
Screwdriver
Catch
Motor Holder 1,2
2-90
(5) Draw the fan leftward with lifting up the bearing side of the fan slightly, the fan and the fan motor are
removed.
Tool Phillips Screwdriver
Loosen Screw
(6) For attaching the fan motor and the fan, perform the reverse procedures for removing.
(7) Fix the fan at the position with 8mm clearance between the left end (bearing side) of the fan and the
partition plate.
(8) Fix the fan motor with the outlet of the lead wire at the position as shown below.
8mm
Fan Fan Motor Fan Motor
Bearing 60o
Partition Plate
2-91
Heat Exchanger
(4) Remove the butyl sheet of the surface of the piping, the coil part of the expansion valve and the part
of the valve body.
(5) Prepare two (2) spanners. Hold the part of the valve body with one spanner and loosen the lock nut
with another spanner by turning the lock nut counterclockwise.
NOTE:
Do not hold the motor part when loosening the lock nut by spanner. The base of the drive part may
turn idle and be broken.
(6) Turn the lock nut by a few turn, and the drive part is separated from the screw and can be removed.
(7) Prepare the new drive part for replacement (service part) with the position of the driver (drive screw)
already adjusted.
NOTE:
During replacement work, pay attention to the separation part and prevent the dust, foreign particle,
etc. from entering into the separation part. (The exposed part by separation is the mechanical part of
the valve.)
Do not hurt the junction part of the valve with the tools.
(8) Put the drive part onto the valve body, hold them with their axes matching and attach the lock nut to
the screw part of the valve body.
2-92
(9) Tighten the lock nut with spanner after tightening lightly by hand.
The tightening torque shall be within the range of 12Nm (120kg-cm) to 15Nm (150kg-cm).
NOTE:
Do not apply the strong forces such as the rotating torque and the bending load to the motor by
holding the motor by hand when tightening the lock nut.
The direction of the eccentric part of the motor is assembled as the eccentric part of although the
motor is directed toward the counter direction of the fittings for piping at the valve body, the alteration
of this direction do not affect the open/close function of the valve. Therefore, the adjustment of the
direction of the motor part is not required if the position of the motor is moved toward the rotating
direction after replacement as shown below.
However, pay attention to the direction of the motor for the coil of the electronic expansion valve not
to touch other pipings and the side plate of the electrical box.
Pulse Motor
Drive Part
Gear
Output Shaft
Lock Nut
Bellows Adjustment of direction is not required.
Valve
Valve
Valve Part
Valve Body Sheet
(10) Attach the removed butyl sheet to the electronic expansion valve again.
(11) After completion of the replacement, attach the electronic expansion valve in the reverse procedures
for removing.
2-93
Knob
2-94
Fixing Plate
Top Cover
Front Cover
Screws
2-95
Screws
(5) Disconnect the wiring connector for the fan motor. Remove the wiring assembly and connector.
Connector
Wiring Assembly
2-96
"1"
Catch
Casing
Motor
Hexagonal Wrench
To Loosen
(8) Remove the fan motor by sliding it backwards after removing the fixing plate.
Pay attention not to drop it.
Tool Phillips Screwdriver
Band
Fixing Screw
2-97
Side Panel
Screws
(5) Remove the electrical box cover after removing two (2) fixing screws.
Screws
2-98
(6) The electrical box can be turned up to an angle of 90° by removing two fixing screws and unhooking
the catch at the rear side of the electrical box.
(7) The PCB is supported by four holders. Pull out the PCB from the PCB hole by pushing the expanded
part of the holder using long-nose pliers and putting a finger near the hole of the PCB.
Expanded Part
of Holder
PCB
(Low Voltage)
PCB Holders
NOTES:
1. Do not touch electrical components. Do not apply a
large force to the PCB or it could result in damage.
2. When reassembling, check to ensure that each terminal
is correctly connected by referring to the wire marks
and terminal codes. If incorrectly connected,
malfunction or damage of electrical parts will occur.
2-99
Side Panel
Screws
(5) Remove the piping cover after removing two (2) fixing screws for the partition plate and four (4) fixing
screws for piping cover.
Partition Plate
Piping Cover
Screw
2-100
(6) Remove CORK TAPE and pull out the thermistor after removing the fixing plate for the thermistors.
Cork Tape
Pipe
Thermistor Holder
2-101
Air Filter
2-102
(3) Remove the front upper cover after removing eleven (11) fixing screws.
Screws
2-103
Screw
Catch
2-104
Screw
Stopper
(3) Remove the screw supporting the bearing at the left side, pull out the discharge air grille including the
bearing, and pull out the discharge air grille from the right side of the bearing.
Screw
Discharge
2 Air Grille
Bearing 1
2-105
Electrical Box
NOTE:
During this work, support the electrical box
by hands not to drop it.
(3) Open the electrical box cover and remove the connector of the fan motor wiring from the PCB.
!
CAUTION
PCN 202
Disconnect connector PCN 202
2-106
"1"
Catch
Casing
Coupling
Loosen
Hexagonal Wrench
(6) Remove the fan motor by sliding it backwards after removing the fixing band.
Pay attention not to drop it.
Tool Phillips Screwdriver
Screw
NOTE:
Pay attention to the position of the runner shaft when replacing the fan motor.
In case that the resistance is big when rotating the motor shaft by hand after replacing, remove the bearing
once according to the item 2.9.5 “Removing Bearing”, adjust the positions of the runner shaft and the motor
shaft on the straight and assemble the runner shaft again.
2-107
M8 Bolt
Casing
Bearing
Air Filter
(1) Open the air intake grille according to the item 2.9.2 “Removing Side Cover”.
(2) Remove the lower part of the casing according to the item 2.9.4 “Removing Fan Motor” and loosen
two (2) screws for the coupling by a hexagon wrench.
(3) Remove two (2) M8 screws fixing the bearing according to the item 2.9.5 “Removing Bearing”.
(4) Remove the coupling after removing the shaft and the fan runner assembly.
2-108
M4 Screws
NOTE:
When assembling, tighten two screws (A) with a torque of 0.8Nm (8kg-cm)
and one screw (B) with a torque of 0.4Nm (4kg-cm) using a torque wrench.
2.9.8 Removing Thermistors for Liquid Pipe and Gas Pipe, and Electronic Expansion Valve Coil
(1) Open the air intake grille and remove the right and left side covers according to the items 2.9.1
“Removing Air Filter and Air Intake Grille” and 2.9.2 “Removing Side Cover”.
(2) Remove the drain hose from the drain pan and remove the screws fixing the drain pan to the unit.
(3) Remove the drain pan.
Tool Phillips Screwdriver
Drain Pan
Drain Hose
2-109
(4) Remove the thermistors for the liquid pipe and gas pipe.
(5) Refer to the item 2.4.12 “Removing Electronic Expansion Valve Coil” in pages 2-63 and 2-64 for the
procedures of removing electronic expansion valve coil.
Partition Plate
Heat Exchanger
Holder
Thermistor
Checking Hole
Side Plate R
Expansion Valve
Check Cover
2-110
NOTE:
During this work, support the electrical box not to drop it.
Expanded Part
of Holder
PCB
(Low Voltage)
NOTE:
Do not touch the electrical components.
Do not apply big force to the PCB.
If applied, the PCB will be faulty.
2-111
2.10.1 Structure
The structure of the total heat exchanger is as shown in the figure.
When maintaining, use service access door of ceiling.
Exhaust Fan
Air Supply Fan
Damper Plate
Suspension Air Filter
Bracket
Motor for Total Heat Exchange
Discharge Air Element Motor for Supply Air
Screw
2-112
Filters
2-113
(6) Remove six (6) screws for fixing the fan motor for supply air and remove the fan motor for supply air.
(7) Remove four (4) screws for fixing the fan motor for discharge air and remove the fan motor for supply
air.
Tool Phillips Screwdriver
2-114
Total Heat
Exchange Element
Vacuum Cleaner
Corner (with brush attachment)
2-115
!
200
20
00
10
00
12
Transparent
Insert the bar.
Vinyl Sheet
Boss Inner Side of φ120 hole should
be covered with felt sheet to
Hose
insert the spray nozzle.
2-116
* Refer to the item 2.11.1 “Required Tools for Cleaning” for cleaning tools.
Step Procedure Required Tool
1 Remove the drain pan according to the item 2.2.8 "Removing Drain Pan"
and clean the drain pan.
2 Remove the indoor fan motor and the fan runner assembly according
to the item 2.3.3 "Removing Indoor Fan and Fan Motor".
3 Removing Fan Fixing Plate * Phillips Screwdriver
Top Plate
Side
Plate
Fan Fixing
Plate
2-117
Vinyl Sheet
NOTE:
Perform the work by wearing gloves to
prevent any injuries from touching the fins
of the heat exchanger.
Attach the vinyl sheet to protect the
insulation materials from the cleaning water.
(A transparent board is also applicable
instead of the vinyl sheet.)
6 Attaching Cleaning
Water Pan Indoor Unit
Metal Bar
Rope
Suspension
Bracket Cleaning Water
Collector
Boss
Hose
Bucket
2-118
Spray
Hose
Bucket
Pump
2-119
NOTES:
Remove the drain pan after removing drain water on the drain pan.
1. Remove the drain water on the drain pan after pulling out the rubber plug. Check to ensure that water
can flow smoothly through the hole by pricking it with a pencil.
2. Insert the rubber plug into the hole after the above checking.
3. Remove the drain pan after removing four fixing screws. Carefully remove the drain pan, since drain
water may remain at the bottom of the drain pan.
4. Clean and dry the drain pan after removing. Carefully handle the drain pan not to damage it.
2-120
(1) Scratch off the dust on the inner surface of the heat exchanger downwards using a brush. Collect all
dust in a bucket or carton box.
Tool Brush, Bucket (or Carton Box)
(2) Attach a vinyl sheet by using adhesive tape around the heat exchanger so that cleaning water will not
be splashed over the insulation surface and drain-up pump. Seal the gap between vinyl sheets by
using adhesive tape.
(3) Attach ropes to the each suspension bracket.
(4) Put the metal bars through the holes of the cleaning water collector.
(5) Attach the ropes to the four bars of the cleaning water collector and suspend the cleaning water
collector as shown in the figure.
(6) Connect a hose to the boss and put end
of hose in a bucket.
Tool Cutter Knife, Bucket
Suspension
Indoor Unit
Bolt
Rope
Suspension
Cleaning Bracket
Support Water The water
Bar Collector 20 to 30mm collector should
(8 Nos.) be located 20 to
Boss 30mm higher
Ceiling than the bottom
of the unit.
Hose Cleaning Water
Collector
Bucket
2-121
(7) Put approximately 15 liters of cleaning agent for aluminum fins in a supply tank.
(8) Insert the spray nozzle through the hole of the cleaning water collector. Operate the water pump and
clean the dust on the heat exchanger. After cleaning, spray clean water to remove the cleaning
water. Adjust the pressure of the water pump
so as not to damage the fins. Clean Water, Cleaning Agent,
Tool Water Pump, Cleaning Spray
Cleaning
Spray
Bucket
NOTES:
1. If the cleaning water remains, fins will be corroded.
2. Adjust the pressure of the pump at 2.5 to 5.0 kg/cm2 so as not to damage fins.
2-122
(9) After cleaning, mount the drain pan by extending the rope downwards.
NOTE:
In the case that the cleaning water collector is
removed, wipe off the drops from the indoor unit. Tool Phillips Screwdriver
Drain Pan
Cleaning
Water
Collector
(10) Check the insulation of the drain pump with a megohm-meter. Check to ensure that the insulation is
greater than 1 MΩ when 500V is applied.
(11) Connect wiring as it was.
(12) Neutralization Treatment after Cleaning
The cleaning agent specified in the item 2.11.1 is of the neutral type. However, the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization treatment
for the cleaning water.
2-123
Top Plate
Side
Plate
Inlet Side of
Heat Exchanger
2-124
(5) Put a vinyl sheet behind the heat exchanger so that cleaning water will not be splashed on the
insulation surface of the unit. Seal the gap
between vinyl sheets. Tool Vinyl Sheet, Tape, Cutter
Heat Exchanger
Vinyl Sheet
NOTES:
1. It is recommended that gloves be used during this
work to avoid any injury.
2. Put a vinyl sheet to avoid splashed cleaning water.
(6) Suspend the cleaning water collector from the indoor unit.
(a) Connect a rope to the suspension bracket of the indoor unit put is downwards.
(b) Insert the support bar into the cleaning water collector hole.
(c) Suspend the cleaning water collector with the rope from the indoor unit.
(d) Connect a hose to the boss for the cleaning water collector and put the other end in a bucket.
(7) Spraying Cleaning Water
Spray the cleaning water over the fins of
the heat exchanger. Tool Cleaning Water
Indoor Unit
Metal Bar
Rope
Suspension
Bracket Cleaning Water
Collector
Boss
Hose
Bucket
2-125
Nozzle
Spray
Hose
Bucket
Pump
NOTES:
1. If the cleaning water remains, fins will be
corroded.
2. Adjust the pressure of the pump at 2.5 to
5.0 kg/cm2 so as not to damage fins.
(9) Attach the fan assembly and drain pan after cleaning is completed and dropping of cleaning water is
stopped.
Tool Phillips Screwdriver, Hexagon Wrench
(10) Check the insulation of drain-up pump by megohm-meter. Check to ensure that the insulation is
greater than 1 MΩ when 500V is applied.
(11) Connect the wiring as it was. Mount the air
Tool Phillips Screwdriver, Megohm-meter
distribution chamber and optional air panel.
(12) Neutralization Treatment after Cleaning
The cleaning agent specified in the item 2.11.1 is of the neutral type. However, the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization treatment
for the cleaning water.
2-126
Nozzle
Heat
Exchanger
NOTES:
1. If the cleaning water remains, fins will be
corroded.
2. Adjust the pressure of the pump at 2.5 to
5.0 kg/cm2 so as not to damage fins.
2-127
2.11.6 Cleaning Floor Type and Floor Concealed Type Indoor Unit
Spread a vinyl sheet over the floor to protect furnitures, etc. from cleaning water before this work.
(1) Remove the front cover according to the item 2.7.4 and 2.8.2 “Removing Front Cover”.
(2) Disconnect the drain hose from the field-supplied pipe.
(3) Cover the rear side of the heat exchanger with a vinyl sheet after removing front side partition and
drain pan. After covering, remount the front
side partition and drain pan. Tool Vinyl Sheet, Tape, Cutter
Heat
Exchanger Cover it
with Vinyl
Sheet
Front Side
Partition
Drain
Pan
(4) By lifting the drain hose and put the end in a bucket.
Bucket
Drain
Hose
2-128
Bucket
(6) Spray cleaning water over the fins of the heat exchanger.
(7) Cleaning with Clean Water
Cover the wiring connectors with insulation tape. Operate the pump and clean the heat exchanger
with clean water completely. Adjust the pressure
of pump so as not to damage fins. Tool Clean Water, Pump, Spray
NOTES:
1. If the cleaning water remains, fins will be
corroded.
2. Adjust the pressure of the pump at 2.5 to
5.0 kg/cm2 so as not to damage fins.
2-129
(8) After checking that no power is supplied, connect the drain pipe and remove the insulation tape for
the wiring connectors and then mount the front cover correctly.
(9) Check the insulation of the terminal board in the electrical box.
If the insulation is greater than 1MΩ
Megohm-meter, Voltage-Checker,
by a 500 Megohm-meter, it is normal. Tool Phillips Screwdriver
2-130
(7) Remove the fixing plate for the fan after removing two screws at the left and one screw at the right
side partition.
Tool Phillips Screwdriver
2-131
(9) Cover all components except the drain pan with a vinyl sheet avoid splashed cleaning water.
NOTE:
Wear gloves to avoid any injury during this Vinyl Sheet, Tape, Cutter,
Tool Phillips Screwdriver
work due to sharp edge of fins.
(10) Spray the cleaning water over the fins from the rear side of the heat exchanger.
If the heat exchanger is heavily covered
Tool Spray, Brush
with dust, use a brush to wipe off.
(11) Cleaning with Clean Water
(a) Operate the pump and clean the heat exchanger with clean water completely.
(b) Adjust pressure of the pump so as not
to damage fins. Tool Clean Water, Pump, Cleaning Water
NOTES:
1. If the cleaning water remains, fins will be
corroded.
2. Adjust the pressure of the pump at 2.5 to
5.0 kg/cm2 so as not to damage fins.
(13) Check to ensure that water can flow smoothly after pouring water on the drain pan.
NOTE:
Pay attention to the drain pan not to overflow.
(14) Neutralization Treatment after Cleaning
The cleaning agent specified in the item 2.11.1 is of the neutral type. However, the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization treatment
for the cleaning water.
2-132
Hose
NOTES:
Connecting
Port 1. The cylinder capacity shall be equivalent
to half of the total refrigerant capacity.
2. In case of 8HP and 10HP outdoor units;
Cylinder Remove the terminals of the constant
speed compressor, and cover the
Pressure Gauge terminals of the cables by insulator.
Liquid Line Gas Line
Stop Valve Stop Valve
(5) Open the liquid line stop valve on the cylinder to collect refrigerant into it. The cylinder capacity shall
be equivalent to half of the total refrigerant capacity. Check the refrigerant quantity by measuring the
weight.
(6) Close the liquid line stop valve on the cylinder gradually during the cooling operation.
(7) Fix the opening of the liquid line stop valve at a slightly opened position. Continue the cooling
operation.
(8) Finally close the liquid line stop valve and then gas line stop valve and stop the units at the same
time when the pressure at the liquid line stop valve reaches at -400mmHg.
NOTE:
In the case that the collected refrigerant is recharged into the system, charge it by let the cylinder up
side down so that refrigerant and oil can be charged together.
2-133
3. MAIN PARTS
3.1 Inverter
3.1.1 Specifications of Inverter (For 380/415V, 50Hz and 380V, 60Hz Power Source)
(V)
400
380
300
200
24 and 30HP
100
0 50 75 100 115
f (Hz)
3-1
Protection Function
Overcurrent Protection
for Inverter
(1)
(3)
Rated Current 150%
(4)
Rated Current 105%
NOTE:
Characteristics are fluctuated by the current minimize control.
3-2
(V)
400
300
200
100
24 and 30HP
0 50 75 100 115
f (Hz)
3-3
Protection Function
Overcurrent Protection
for Inverter
(1)
(3)
Rated Current 150%
(4)
Rated Current 105%
NOTE:
Characteristics are fluctuated by the current minimize control.
3-4
1
W V U
2
B
N
4 U
255
V
A
K W
200
3-5
2 3
1
B
N
255
W
V
U
16
200
3-6
1 2 3
B
U
255
V
W
200
3-7
1 CN201 R1 S1
PD P1 P N RB
R
S
T
C
U
V
W
COM2
MAIN1 SUB1 COM1
3-8
Main Circuit
Frequency LOW
Power Source Frequency All bit 1 All bit 1 Operation
HIGH
Frequency
Instruction
Output Voltage
Soft Start-Stop
(Frequency) The changing speed
depends on the outer
setting.
Failure Signal
Output
Activation of
Protection Device Transmit Protection
Error 30sec. Activation
10sec.
Overload Signal
Activation Recovery
Charged Indication
(Red LED5 on PCB5
or LED2 on PCB2)
3-9
(b) Function
When abnormalities are detected, the inverter compressor is stopped and transmit the signal code
of stoppage cause to PCB1.
(c) Cancellation of Protection Function
Transmission for signal code of stoppage cause is cancelled when a stopping order is given or
main power source is cut off.
(2) Abnormality of Current Sensor
(a) Level of Detection
When current of the inverter compressor decreases lower than 0.5A during the inverter
compressor frequency between 15Hz and 18Hz, an abnormality is detected.
(b) Function
When abnormalities are detected, the inverter compressor is stopped, and transmit the signal code
of stoppage cause to PCB1.
(c) Cancellation of Protection Function
Transmission for signal code of stoppage cause is cancelled when a stopping order is issued or
main power source is cut off.
(3) Overcurrent Protection for Inverter
(a) Level of Detection
1 When the current detected by current sensor reaches 150% of the rated current, overcurrent is
detected. (Instantaneous Overcurrent)
2 When the current detected by current sensor exceeds 105% of the rated current continuously for
30 seconds or for 3.5 minutes in total during a 10 minutes period, overcurrent is detected. (Electric
Thermal Relay)
(b) Function
When abnormalities are detected, the inverter compressor is stopped and transmit the signal code
of stoppage cause to PCB1.
(c) Cancellation of Protection Function
Transmission for signal code of stoppage cause is canceled by stopping order is issued or main
power source is cut off.
(4) Protection of Transistor Module and ISPM
(a) Level of Detection
1 When some of the output terminals between “U” and “V”, “V” and “W”, “W” and “U” of transistor
module or ISPM are short-circuited, an abnormality is detected.
2 When the running current of transistor module or ISPM reaches (Maximum Rated Current x
105%), an abnormality is detected.
3 When an internal temperature is measured by internal thermistor of transistor module or ISPM, an
abnormality is detected.
4 When the control voltage of transistor module or ISPM decreases, an abnormality is detected.
(b) Function
When abnormalities are detected, the inverter compressor is stopped and the signal code of
stoppage cause is transmitted to PCB1.
(c) Cancellation of Protection Function
Transmission for signal code of stoppage cause is canceled when a stopping order is issued or
main power source is cut off.
3-10
3-11
3.2 AC Chopper
Reduction of Electromagnetic Sound
Fan Motor Control by AC Chopper:
Lower electromagnetic sound and vibration have been achieved by AC Chopper control than thyristor
control.
AC Chopper Control
Concept of Fan Speed Control
The voltage applied to the fan motor is controlled by chopping
(ON/OFF) the power supply voltage at a frequency of 20kHz.
Features
• Sinusoidal Wave Pattern and Remarkable Low Level of Electromagnetic Sound
• No Generation of Harmonic Current
(1) Specifications
b
Input Duty = b/a
a
d
Output Duty = d/c
0 10 50 c
Input Duty (%)
(Max. ) 4A
3.5A
3-12
(2) Structure
a. 2.1A (For Indoor Units: RCI, RCD, RPC and RPI (0.8 to 2.5HP) Models)
98 45
PCN203
PCN202
110
PCN201
CAUTION
PCN204
CN201
b. 5.6A (For Outdoor Units and Indoor Units: RPI (3.0 to 5.0HP) Models)
180 69
SUB1MAIN1 COM1
S1
CAUTION
124
COM2
R1
CN201
PCN201 PCN202
AC220-240V R 1 1
(From Control PCB) S 3 3 MFE
5 5
1
3
CN201
PCN203 C
Input Duty Signal 1
(From Control PCB) PCN204 1 3 5
3
b. 5.6A
R SUB1
R1
AC220-240V C
(From Control PCB)
S MAIN1 MFE
S1
COM1
E1
CN201
3-13
(1)
(1)
(3) Bearing AS
0 (zero) Reset
The AS stopper of the
louver (2) touches the steel
(1) Motor
plate stopper, and the louver (4) Motor
is reset to the 0 position.
3-14
Stopper
Bearing Louver Bearing Arm Arm
Shaft B
Stopper
3-15
(2) Pinion
3-16
(1) The gas is inhaled from the inlet port at the outer frame of the fixed scroll.
(3) The compression space is minimum at the center of the scroll, and
the gas compressed at the maximum is discharged from the outlet port
of at the center of the scroll.
Fixed Scroll
Rotating Scroll
Compression
Space
Suction Process
Discharge Process
Discharge Compression Process
Outlet
3-17
3.4.3 Structure
The compressor has the structure for oil supply from the outer oil separator. (8 to 20HP)
The inside of the oil separator is at high pressure, and the surface temperature of the oil separator is as
high (60Co to 110Co) as the compressor.
Suction
Fixed Scroll
Frame
Motor
Oil Separator
Discharge
Pipe
Discharge
Oil Supply
Oil Pipe
G Compressor Type
RAS-5FSG and 5FS3: Inverter Compressor x 1
RAS-8FSG, 10FSG, 8FS3, 10FS3, 8FXG, 10FXG, 8FX3 and 10FX3:
Inverter Compressor x 1 and Constant Speed Compressor x 1
RAS-16FSG and 16FS3: Inverter Compressor x 1 and Constant Speed Compressor x 2
RAS-20FSG, 24FSG1, 30FSG1, 20FS3, 24FS5 and 30FS5:
Inverter Compressor x 1 and Constant Speed Compressor x 3
Seen from the front side of the unit, the one compressor at the left is the inverter compressor and other
compressor(s) is(are) constant speed type.
3-18
RAS-5FSG, RAS-5FS3
Without 1
Q'ty: 1
RAS-8FSG, RAS-8FS3
RAS-10FSG, RAS-10FS3
RAS-10FXG, RAS-10FX3
2
Q'ty: 1 Q'ty: 1
RAS-16FSG, RAS-16FS3 3
Q'ty: 1 Q'ty: 2
RAS-20FSG, RAS-20FS3 4
Q'ty: 1 Q'ty: 3
RAS-24FSG1, RAS-24FS5
RAS-30FSG1, RAS-30FS5
4
3-19
3.5 Thermistor
3.5.1 Thermistor for Indoor Unit
(1) Position of Thermistor (In Case of 4-Way Cassette Type)
Thermistor
for Air Outlet Thermistor for Indoor Heat
Temperature Thermistor for Exchanger Liquid Pipe
(THM2) Air Inlet Temperature Temperature
(THM1) (For Freeze Protection) (THM3)
ATTENTION:
The thermo-off valve of the indoor unit air inlet thermistor is set at the temperature higher than the valve
indicated on the remote control switch by 4Co and the maximum is 30Co, because the suction air temperature
during heating operation has a tendency to become higher than that of the occupied zone, intending
comfortable heating operation.
(3) Thermistor for Indoor Discharge Air Temperature (For Discharge AIr Temperature Control)
The thermistor for indoor discharge air temperature is utilized for the control of prevention from cold
air discharge in heating operation, etc.
The resistance characteristics of thermistor is shown in the above figure.
(4) Thermistor for Liquid Pipe Temperature of Indoor Heat Exchanger
When the temperature of the heat exchanger is below 0oC, Prevention from freezing
thermostat is turned OFF automatically and over 14oC, onto the heat exchanger in
thermostat is turned ON again. COOL and DRY operation.
When the temperature of the heat exchanger is below 0oC, Prevention from freezing
thermostat is turned OFF automatically and over 14oC, onto the heat exchanger in
thermostat is turned ON again. COOL and DRY operation.
3-20
<Example: RAS-30FSG1>
Thermistor
for Outdoor Ambient
Temperature
Thermostat Holder
Holder
Thermistor for
Discharge Gas
Temperature
Thermistor
for Evaporating
Temperature
3-21
90
82
80
70
61
60
Thermistor 50 46
Resistance
(KΩ) 40 35
30 27
20.5
20 16
12.5
10
10 8 5.3 3.6 2.5
0
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
o
Ambient Temperature ( C)
Thermistor Characteristics
3-22
Micro-Computer
Pulse Signal Pulse Motor
2-Phase Permanent Magnetic Pulse Motor
Control 0 to 500 Pulse by 1 Pulse
Needle
Specifications
Items Specifications
Models to be Applied For Main Cycle of
RAS-5FSG, RAS-5FS3, RAS-8FSG, RAS-8FS3, RAS-10FSG,
RAS-10FS3, RAS-16FSG, RAS-16FS3, RAS-20FSG, RAS-20FS3,
RAS-24FSG1, RAS-24FS5, RAS-30FSG1, RAS-30FS5,
RAS-8FXG, RAS-8FX3, RAS-10FXG and RAS-10FX3
Type EKV (10.0USRT) Series / EKV (5.0USRT) Series for FX MVB
Refrigerant Used R22 or R407C
Working Temperature
Range -30oC to 65oC (Operating Time of Coil: less than 50%)
Mounting Direction Drive shaft in Vertical Direction within an Angle of 45o as Maximum
Flow Direction Reversible
Drive Method 4-Phase Pulse Motor Method
Rated Voltage DC12V+1.8V
83PPS (Pulse Width at ON: 36mm sec, OFF: 60mm sec)
Drive Condition
1, 2 Phase Excitation
Coil Resistance
46Ω+10% (at 20oC)
(each Phase)
Wiring Diagram,
Drive Circuit and
Activation Mode
ON
A OFF
M
Wiring B
Diagram A
B A B A
B
Drive Close Open
DC12V Circuit Valve
Activation
3-23
Micro-Computer
Pulse Signal Magnet
2-Phase Permanent Magnetic Pulse Motor Coil
Pulse Motor
Control 0 to 2,000 Pulse by 1 Pulse
Precise Control
Driver
Bellows
Valve
Specifications
Items Specifications
Type EDM Type
Refrigerant Used R22 or R407C
Working Temperature
Range -30oC to 70oC (With Coils Not Electrified)
Mounting Direction Drive shaft in Vertical Direction, Motor Upside and 90o in Four Direction
Flow Direction Reversible
Rated Electricity
Drive Method 4-Phase Pulse Motor Method
Rated Voltage DC12V+1.2V
100Ω+250PPS (Pulse Width Over 3mm)
Drive Condition
2 Phase Excitation
Coil Resistance
150+10% (at 20oC)
(1 Phase)
Wiring Diagram,
Drive Circuit and
Procedure
Activation Mode 1 2 3 4 1
1φ Phase
ON
M 1φ OFF
3φ Wiring 2φ
2φ 4φ Diagram
3φ
4φ
Drive Valve
DC12V Circuit Activation
Close Open
Activation
3-24
0.371
-0.1 0 3.5
(-1) (35)
(FX Series Only) Pressure MPa (kgf/cm G) 2
Cooling Operation
3-25
High Pressure
Switch
Low Pressure
Union Sensor High Pressure
Sensor
(1) For controlling the high pressure not to Gas By-pass Circuit
increase excessively during heating
operation, the gas by-pass circuit and the
air volume of the outdoor fan is controlled S
S
automatically. P
S S
3-26
For RAS-5FSG/5FS3~20FSG/FS3
Items Specifications
Model HF4020C-DV
Rated Current AC415V 20A
Permissible Temperature Range -20oC to 65oC
Circuit Diagram
IN OUT
Z5
E
L1 L5 N
N
Z4
L2 L6 L1
L1
Z1 Z2 C10
C11
L3 L7 L2
L2
Z3 C12
C13
L3 L4 L8 L3
C14
C15
C1 C2 C3 C4 C5 C6 C7 C8 C9
250
N N
L1 EMI FILTER L1
TYPE
120
100
RATING
L2 T.V L2
LOT No.
L3 L3
260
270
18
93
75
3-27
250
7.0 ± 0.3 118 ± 0.3 118 ± 0.3
7.0 ± 0.3
Date Code
20PTT10-H 415VAC/20A
Cy1 Cy1
E E Cy2
E'
Cx Cy2 Cx E'
N N N' N'
L L
106 ± 0.3
I O
N Cx Cx A
120
L3 Z L3 L3' L3'
E D
L2 L2'
Z L2 L2'
L1 Z
L1 Cx Cx L1' L1'
L Cy1 L
5 - φ4.2
Unit: mm
30 Max.
70 Max.
250
7.0 ± 0.3 118 ± 0.3 118 ± 0.3
7.0 ± 0.3
Date Code
4LFB-12822-2F 415VAC/22A
Cy1 Cy1
E E Cy2
E'
Cx Cy2 Cx E'
N N N' N'
L L
106 ± 0.3
I O
N Cx Cx A
120
L3 Z L3 L3' L3'
E D
L2 L2'
Z L2 L2'
L1 Z
L1 Cx Cx L1' L1'
L Cy1 L
5 - φ4.2
Unit: mm
30 Max.
70 Max.
3-28
Specifications
Items Specifications
Models 400LGSN2700M
Capacity of Static Electricity 2700µF
Rated Voltage 400V
Permissible Temperature Range -25oC to 95oC
140
φ84
−
3.11 Reactor (DCL)
This part is used for changing the alternative current to the direct current for the inverter.
76.2
3-29
MAX. 80
47.5±2
66±2
74±2
60±0.5
86±2
60±0.5
86±2
3-30
NOTE:
Indoor Unit PCB When the unit is started by the remote ON/OFF switch,
the fan speed is subject to the mode memorized in
CN4 the remote control switch.
3
2 SS3: Remote Control ON/OFF
X1 SS3
Power
3 Source
2
X1
Control Circuit
3P Connector
Wiring Diagram Example of Remote Control 1
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
4-1
Turn OFF the power source before setting the dip switch.
NOTES:
1. When the unit is started by the remote ON/OFF switch,
Indoor Unit PCB the fan speed is subject to the mode memorized in
the remote control switch.
CN4
2. The pulse width shall be wider than 200ms.
3
2
1
X1 ON OFF
Power
3 Source
2
1 X1 X2
X2 Control Circuit
3P Connector
Wiring Diagram Example of Remote Control 2
Control by R.C.S
Unit Operation
NOTE:
Time
Operation priority is given to the remote
ON/OFF signal or remote control switch
signal which is given last. Time Chart
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
4-2
Turn OFF the power source before setting the dip switch.
OFF
Power
2 Source
1 X1 X1
Control Circuit
3P Connector
Wiring Diagram Example of Remote Control 3
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
4-3
CN4
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
(*) Only for RPK (After Alteration): PCC-1A (Connector XARP-3), 12V
NOTE:
Make the wires CN4 as short as possible. Do not install the wires along the 200-400V power line.
Separately install them at a distance of more than 30cm. (Intersecting as applicable.)
If the wires are installed along the power line, put the wires in a metal tube and connect a wire to an end for
grounding. The maximum wiring length is 70m.
In the case that this function is used, it is recommended that safety devices such as electric leakage
breaker or smoke detector, etc. be used.
4-4
Turn OFF the power source before setting the dip switch.
NOTES:
Indoor Unit PCB The unit is started and stopped according to the power
Set No.5 at ON side. supply ON/OFF due to the power failure.
DSW2 When the power failure is occurred during stoppage by
ON the remote control switch operation, the unit is started
OFF
again automatically after the power supply is recovered.
In case of RPK-FSGM* (After Alteration) controlled by
1 2 3 4 5 6 7 8 PC-P1H, set by PC-P1H. Refer to the item 4.4.4
Optional Function Setting "item d1".
Turn OFF the power source before setting the dip switch.
4-5
Turn OFF the power source before setting the dip switch.
3P Connector
3
2
1 Thermostat
3 CN3
2
1 Temperature Indoor Unit
Increase Set No.3 at ON side.
DSW2
ON
Indoor Unit PCB OFF
1 2 3 4 5 6 7 8
Operation
Cooling Operation: Compressor is ON by closing terminals 2 and 3 at CN3
Compressor is OFF by opening terminals 2 and 3 at CN3
Heating Operation: Compressor is ON by closing terminals 1 and 2 at CN3
Compressor is OFF by opening terminals 1 and 2 at CN3
NOTES:
1. When a field-supplied room thermostat is used, select the specified thermostat as below.
Contactor Load: DC24V 50 to 6 mA (*)
Differential: more than 1.5 degree
(*) Only for RPK (After Alteration): DC 12V
2. Do not use a thermostat utilizing mercury.
3. This function can be used together with “4.1.1 Remote Control ON/OFF Function”.
4-6
NOTES:
1. The remote temperature sensor can not be used together with the remote control thermistor.
(Refer to the item 4.4.5 (17).)
2. During the heating operation, “Heating Temperature Calibration” is automatically cancelled.
(Refer to the item 4.4.5 (1).)
4.1.6 Cooling or Heating Operation Mode Setting Change by External Input (Level Signal Input)
By utilizing this function, the cooling or heating operation mode can be changed by giving a contact signal
from the outside to the unit. The operation mode is followed by the field-supplied switch or the remote
control switch, which is used last.
CN4
CN4
NOTES:
1. This function can not be used together with the following functions; “Remote Control 2”, “Remote Control
3” and “Cancellation of Commands from Remote Control Switch after Forced Stoppage”.
2. Remote Control Switch is required for this function.
4-7
CN6 CN7
2 1
RY
(JST-XHP-3) (*)
(*) Only for RPK (After Alteration):
Picking Up Alarm Signal JST XARP-3
4-8
CN8 Connector
CN8
(JST-XHP-3)
(4) Picking Up “Thermo-ON” Signal during Heating Operation (Except for RPK-FSGM Series)
This function is utilized to pick up the heating “Thermo-ON” signal of compressor running to control a
circulator or a humidifier. Connect wires as shown below. The required parts are indicated in Table
4.3. The contact of RYa is closed when “THERMOSTAT” is ON during heating operation mode.
(JST-XHP-3)
NOTE:
“Thermo-ON” indicates that one of the micro-computer control function “THERMOSTAT” is ON as a
thermostat.
4-9
CN5 Connector
CN5
(JST-XHP-3)
(6) Picking Up “Thermo-ON” Signal during Cooling Operation (Except for RPK-FSGM Series)
This function is utilized to pick up the cooling “Thermo-ON” signal of compressor running. Connect
the wires as shown below. The required parts are indicated in Table 4.3. The contact of RYa is
closed when “THERMOSTAT” is ON during cooling operation mode.
CN5 Connector
CN5
(JST-XHP-3)
Picking Up "Thermo-ON" during Cooling Operation
NOTE:
“Thermo-ON” indicates that one of the micro-computer control function “THERMOSTAT” is ON as a
thermostat.
4-10
>
At the field setting mode as described in the above item (1), press the “TEMP ” switch or the
>
“TEMP ” switch and the number flickering below the “SERVICE” indication is changed as
(01 <=> 02).
Set the flickering number at “02”, leave this condition for 7 seconds or press the “CHECK” switch, and
the remote control switch is changed to the mode for input and output setting of indoor unit.
(3) Selection of Indoor Unit
(a) At the input and output setting mode, the
indication on the remote control switch is
changed as shown in the right figure.
1 The indication of “02” is turned ON.
2 The address of the indoor unit which
at the segments for timer setting time indication, and the “RN” is indicated below.
4 The indication of the setting temperature is turned OFF. >
>
(b) At the condition of the above item (a), press the “TEMP ” switch or the “TEMP ” switch of the
remote control switch and the indoor unit for the input and output setting, can be changed.
NOTES:
1. The indoor unit can be selected among the indoor units connected to the remote control switch.
2. In case that both the indications of the address and the refrigerant cycle number is “AA”, all the indoor
units connected to the remote control switch are selected. In this case, the individual setting for each
indoor unit can not be performed.
(c) After selecting the indoor unit, leave the condition for 7 seconds or press the “CHECK” switch, the
remote control switch is changed to the input and output setting mode.
4-11
4-12
(b) Press the “TIME ” switch or the “TIME ” switch, the indication of port at the segments for timer
setting time indication is changed as shown below.
Select the port for allocating the input and output signal.
(c) Press the “CHECK” switch, and the code of the input and output signal at the segments for setting
temperature indication is changed as shown below.
Select the input and output signal to be allocated to the port.
00 01 02 03 04 05 06 07 08
>
>
At the input and output setting mode, press the “TEMP ” switch or the “TEMP ” switch, the
condition of the remote control switch is changed so that the indoor unit can be selected for the input
and output setting described in the item (3).
(6) Return from Input and Output Setting Mode
Press the “RESET” switch, the input and output setting is memorized and the mode is returned to the
normal condition.
NOTES:
1. Even in case of controlling temperature by the remote control thermistor, the detected temperature by
the thermistor for the suction air of the indoor unit is applied for the activation of the protective devices in
relation with the thermostat for the suction air of the indoor unit.
2. In temperature control by the remote control thermistor, when the detecting temperature is abnormal due
to the failure of the remote control thermistor, etc., the thermistor to be used is changed to the thermistor
for suction air of the indoor unit automatically.
3. In case of using this remote control thermistor function, select the location for installing the remote
control thermistor as follows;
* where the average temperature of the room can be detected.
* where the thermistor is not exposed to the sunlight directly.
* where the heat source is not near the thermistor.
* where the outdoor air do not affect the room temperature by opening and closing the door, etc.
4. In case of using two remote control switches (Main and Sub), this remote control thermistor function is
available only for the main remote control switch.
Refer to the item 4.4.4 “Optional Function Setting” for the setting procedures of optional functions.
5. This function is not available while the remote sensor is utilizing. (Priority of Remote Sensor)
4-13
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
3. KPI series is applicable for “A/C + VENTI Mode” only.
4-14
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
3. KPI series is applicable for “A/C + VENTI Mode” only.
4-15
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
4-16
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
At this function, the B contact can be used by the optional setting (item 4.4.5 (20)) of the remote control
switch. The time chart when using the B contact is shown below.
Time Chart
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
4-17
NOTE:
Make the wires CN3 as short as possible. Do not install the wires along the 200-400V power line.
Separately install them at a distance of more than 30cm. (Intersecting as applicable.)
If the wires are installed along the power line, put the wires in a metal tube and connect a wire to an end for
grounding. The maximum wiring length is 70m.
In the case that this function is used, it is recommended that safety devices such as electric leakage
breaker or smoke detector, etc. be used.
4.2.4 Power Supply ON/OFF 1 (Automatic Operation When Power Supply ON)
Set the optional function of the remote control switch as shown in the item 4.4.5 (22) to start and stop the
system automatically according to the power supply ON/OFF.
When this function is utilized in the condition that there is no person to operate the unit, make the system
with monitoring for disaster prevention.
NOTE:
The unit is started and stopped according to the power supply ON/OFF due to the power failure.
When the power failure is occurred during operation, the unit is started again automatically after the power
supply is recovered.
Remote Control Switch is required for this function.
4-18
Operation
Cooling Operation: Compressor is ON by closing terminals 2 and 3 at CN3
Compressor is OFF by opening terminals 2 and 3 at CN3
Heating Operation: Compressor is ON by closing terminals 1 and 2 at CN3
Compressor is OFF by opening terminals 1 and 2 at CN3
NOTES:
1. When setting the dip switch DSW2, turn OFF power source and set the dip switch. If the dip switch is
set without turning OFF the power source, it does not correctly function.
2. When a field-supplied room thermostat is used, select the specified thermostat as below.
Contactor Load: DC12V
Differential: more than 1.5 degree
3. Do not use a thermostat utilizing mercury.
4. This function can be used together with “4.2.3 Remote Control ON/OFF Function”.
4-19
NOTES:
1. The remote temperature sensor can not be used together with the remote control thermistor.
(Refer to the item 4.4.5 (17).)
2. During the heating operation, “Heating Temperature Calibration” is automatically cancelled.
(Refer to the item 4.4.5 (1).)
4.2.8 Cooling or Heating Operation Mode Setting Change by External Input (Except for KPI Series)
By utilizing this function, the cooling or heating operation mode can be changed by giving a contact signal
from the outside to the unit. The operation mode is followed by the field-supplied switch or the remote
control switch, which is used last.
(In Case of “Cooling or Heating Operation Mode Setting Change by External Input” Signal Input to 1# and
2# of CN3)
NOTES:
1. This function can not be used together with the following functions; “Remote ON/OFF 2”, “Remote ON/
OFF 3” and “Cancellation of Commands from Remote Control Switch after Forced Stoppage”.
2. Remote Control Switch is required for this function.
4-20
4-21
4-22
NOTE:
“Thermo-ON” indicates that one of the micro-computer control function “THERMOSTAT” is ON as a
thermostat.
4-23
NOTES:
1. “Thermo-ON” indicates that one of the micro-computer control function “THERMOSTAT” is ON as a
thermostat.
2. See the item 4.2.1 regarding remote control switch setting for wiring and output signal.
4-24
Each input terminal and output terminal are set before shipment as shown below.
Input/Output
Connector Pin No. Setting Function (No.)
Name
Input 1 CN17 (1-2) Fixed Heating Mode (1)
Input 2 CN17 (2-3) Fixed Cooling Mode (2)
Input 3 CN18 (1-2) Demand (3)
Output 1 CN16 (1-2) Operation (1)
Output 2 CN16 (1-3) Alarm (2)
In the case that the above setting change is required at site, perform the following procedures.
(1) Set No. 1 pin on the dip-switch, DSW8 on the outdoor printed circuit board at the “ON” side while the
main power to the outdoor unit is being supplied. By setting, function selection mode is available and
the following appears on the 7-segment display.
SEG2 SEG1
This display indicates that the function No. 1 (Fixed Heating Mode) is set at input 1.
4-25
PSW3
Indication
for Input 1
PSW2 PSW3
Indication
for Input 2
PSW2 PSW3
Indication
for Input 3
PSW2 PSW3
Indication
for Output 1
PSW2 PSW3
Indication
for Output 2
PSW2
(3) After the input/output terminal name is selected, select your required function No. by pushing PSW2 or
PSW3 while PSW1 is being pushed.
(4) After selecting the function No., return No. 1 pin at the “OFF” side on the DSW8. The selected contents
are memorized in the outdoor unit printed circuit board and the function selection mode is stopped. The
memorized data is maintained even power source lines are disconnected. The connecting details of
each function are described below, and the required parts are also indicated below.
4-26
4-27
Outdoor Unit
4-28
Auxiliary Relay (X1, X2) Mini-Power Relay, MY1F (or 2F) made 220/240V
by OMRON
Changeover Switch (SS2, SS3) Manual Switch 220/240V
3 Pin Connector PCC-1A Five Cords with
Cord (Connected to JST Connector, XARP-3) Connectors as One Set
Cord Low Volt. 0.3mm2 lower than 24V
(Inside of Unit) 220/240V 0.5 to 0.75mm2
Cord Low Volt. 0.5 to 0.75mm2 lower than 24V
(Outside of Unit) 220/240V 2mm2
NOTES:
1. Make the wire to the terminals as short as possible.
2. Do not run the wires along high voltage cable. (crossing is applicable.)
If necessary to run wires along high voltage cable, insert the low voltage cable(s) into metal tube
and ground it at one end. If sealed wires are used at the low voltage wire side, ground it at one
end of shield wires. The maximum length should be 70m.
4-29
Dip Switch
Setting
15 15
Defrosting Operation Defrosting Operation
Stop Area Stop Area
10 10
Outdoor Evaporating Outdoor Evaporating
Temperature Temperature Temperature
5 5
Conditions (Pipe) (Pipe)
under -15 -10 -5 0 5
6
10 15 -15 -10 -5 0 5
6
10 15
Defrosting
Outdoor Temp. Outdoor Temp.
Operation -4 -4
-7
-8.7 Defrosting Operation
-10 -10
Start Area
Defrosting Operation
-15 -15 Start Area
NOTE:
When the indoor fan is stopped by another control, it is not available to operate indoor fans.
4-30
NOTE:
The operation may be OFF due to high outdoor temperature protection control, since protection control is
not cancelled.
NOTE:
The operation may be OFF due to low outdoor temperature protection control since protection control is not
cancelled.
4-31
NOTE:
The maximum rotation is always 100% (rotation ratio) for the standard unit.
(No limitation of the outdoor temperature)
4-32
4-33
4-34
" "(Up & Down Panel Operation) Switch *ON / OFF TIMER Switch
(This function is not available.)
*TIME (Time Setting) Switch
*VENTI (Ventilator Operation) Switch
4-35
Up to 16 indoor units can be simultaneously controlled using one remote control switch. The operation
mode such as fan, cooling or heating, the setting of air flow, the setting of temperature and the setting of
run/stop can only be set uniformly for all units. However, on/off operation of each thermostat can be done
individually. Defrosting, protective devices function, etc. are individually performed.
<PC-2H2>
* The total length of the wire shall be 200m or F 01
CD E
23
456
AB
shorter. (for 0.75mm2 wire 500m or shorter) 7 9
8
DEFROST
+ CENTRAL
AUTO VENT H.STRG
ON/OFF TIMER
ADDS RN HR
NO FUNCTION
SERVICE
ABNML
SET TEMP.
T. RUN CHECK
FILTER
UNIT
F 01
CD E
23
CN13 (Blue)
456
AB
Controller 7 9 1st Branch Unit PCB
8
In case of using 0.32mm2 cable, the
RSW
total length of the cable must be within 200m.
Set the rotary switch to No.1
<PC-P1H>
* Simultaneous Indoor Units Operation in Same Refrigerant Piping System
Control Cable
(H-LINK)
Main Switch
(PC-P1H)
Main Switch
(PC-P1H)
NOTE:
Pay attention not to overlap the indoor units’ addresses in case that each of intoor units have a different
refrigerant system.
(1) Perform wiring between indoor units as shown in the following figure.
ATTENTION:
Indoor Unit Indoor Unit
1 2 A B 1 2 A B 1. Use shielded twist pair cable for indoor
unit - remote control switch and indoor
unit - indoor unit.
Shielded Twist Pair Cable 2. The total length between each indoor
for Remote Control Switch units, indoor unit and the remote control
Control Cable between switch must be 500m or shorter.
Outdoor Unit and Indoor Units
(H-Link Control Cable) 3. In case the remote control switch cables
connect, pay attention to check the cables
Use 0.75mm2 shielded
A B twist pair cable. lest the H-LINK control cable is connected
Remote Control Switch accidentally.
4-36
<Setting of Rotary Switches> When indoor units are connected to the same outdoor unit, it is
unnecessary to set rotary switches, because they are automatically addressed.
Main Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit
( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )
F 01 F 01 F 01 F 01 F 01 F 01 F 01 F 01
Rotary
CD E
CD E
CD E
CD E
CD E
CD E
CD E
CD E
23
23
23
23
23
23
23
23
Switch
456
456
456
456
456
456
456
456
AB
AB
AB
AB
AB
AB
AB
AB
Setting
7 9 7 9 7 9 7 9 7 9 7 9 7 9 7 9
8 8 8 8 8 8 8 8
No. 8 Unit No. 9 Unit No.10 Unit No.11 Unit No.12 Unit No.13 Unit No.14 Unit No.15 Unit
( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )
Rotary F 01 F 01 F 01 F 01 F 01 F 01 F 01 F 01
CD E
CD E
CD E
CD E
CD E
CD E
CD E
CD E
23
23
23
23
23
23
23
23
Switch
456
456
456
456
456
456
456
456
AB
AB
AB
AB
AB
AB
AB
AB
Setting 7 9
8
7 9
8
7 9
8
7 9
8
7 9
8
7 9
8
7 9
8
7 9
8
( ): Address Indication
ATTENTION:
* Pay attention not to overlap addresses.
* Check the number of connected units by using “Test Run Mode”. Test run mode shall be performed after
finishing wiring, refrigerant piping, additional refrigerant charge and other items required for operation.
4-37
<PC-2H2>
(1) By installing an additional remote control switch, a maximum of 16 units can be controlled from two
different locations. Altering Method to Sub Control Switch
Cut Jumper Wire JP01 with Nipper.
Remote Remote
Control Control
Switch Switch
(b) Decide the number of units. The method should be the same as in “Simultaneous Indoor Unit
Operation with One Remote Control Switch”.
ATTENTION:
1. When a main remote control switch malfunctions, unit operation stops. The units cannot be operated
with only a sub-remote control switch.
2. When a main switch and a sub-switch are simultaneously operated, the units will operate according to
either one of the modes after 30 seconds.
4-38
<PC-P1H>
(1) By installing an additional remote control switch, a maximum of 16 units can be controlled from two
different locations.
Control Cable
(H-LINK)
Main Switch
Connector Cable
(Remote
Control Switch) Between Units
Sub Switch
(Remote
Control Switch)
(b) Decide the number of units. The method should be the same as in “Simultaneous Indoor Unit
Operation with One Remote Control Switch”.
* Simultaneous Indoor Units Operation in Plural Refrigerant Piping Systems
Main Switch
(Remote Connector Cable
Control Switch) Between Units
ATTENTION:
1. When a main remote control switch malfunctions, unit operation stops. The units cannot be operated
with only a sub-remote control switch.
2. When a main switch and a sub-switch are simultaneously operated, the units will operate according to
either one of the modes after 30 seconds.
4-39
>
At the field setting mode as described in the above item (1), press the “TEMP ” switch or the
>
“TEMP ” switch and the number flickering below the “SERVICE” indication is changed (01 <=> 02).
Set the flickering number at “01”, leave this condition for 7 seconds or press the “CHECK” switch, and
the remote control switch is changed to the optional setting mode.
(3) Selection of Indoor Unit
(a) At the optional setting mode, the indication on
the remote control switch is changed as shown
in the right figure.
1 The indication of “01” is turned ON.
2 The address of the indoor unit which
the optional function is to be set, is
indicated at the segments for time
setting time indication, and the
“ADDS” is indicated below.
3 The refrigerant cycle number of the indoor unit for which the optional function is to be set, is
indicated at the segments for timer setting time indication, and the “RN” is indicated below.
4 The indication of the setting temperature is turned OFF.
>
>
(b) At the condition of the above item (a), press the “TEMP ” switch or the “TEMP ” switch of the
remote control switch and the indoor unit for which the optional function is to be set, can be
changed.
NOTES:
1. The indoor unit can be selected among the indoor units connected to the remote control switch.
2. In case that both the indications of the address and the refrigerant cycle number is “AA”, the
settings of all the indoor units is same.
(c) After selecting the indoor unit, leave the condition for 7 seconds or press the “CHECK” switch, the
remote control switch is changed to the optional setting mode.
(4) Changing of Optional Functions and Setting Conditions
(a) At the optional setting mode, the indication on
the remote control switch is changed as shown
in the right figure.
1 The indications of “ADDS” and “RN”
are turned OFF.
2 The item number of the optional
function is indicated at the segment
for the setting temperature indication.
Refer to the table in the next pages for the item numbers and the contents of the optional
functions.
4-40
(c) Press the “CHECK” switch, and the setting condition of the optional function is changed as shown
below.
When pressing the “CHECK” switch
00 01 ~
>
>
At the optional setting mode, press the “TEMP ” switch or the “TEMP ” switch, the condition of
the remote control switch is changed so that the indoor unit can be selected to set the optional
function described in the item (3).
(6) Return from Optional Function Setting Mode
Press the “RESET” switch, the optional function setting is memorized and the mode is returned to the
normal condition.
4-41
NOTES:
1. (*1): This function is applicable for RCI and RCD models. In case of RPI-0.8 to 5.0FSG1 series,
“Hi Speed 1” is “High External Pressure Setting” and “Hi Speed 2” is “Low External Pressure Setting”.
2. As for the optional functions with “ X ” at the individual setting, only when the “All Rooms” is selected to set
the optional function, the setting condition can be changed.
3. The items “C1” and “C3” are not available. Do not change the setting condition “00”.
4. For the models RPF(I)-FSG(E), RPI-8, 10HP, RPC-FSG1 (Before Alternation) and RPK-FSGM (Before
Alternation), only the function setting of No.1 to No.9, No.17 and No.30 are available.
(No.17 is settable “01” only.)
4-42
18 20 22 24
Indicated Temperature
ON OFF ON OFF ON OFF ON OFF
When Cooling - - 22 20 24 22 26 24
Activating
Standard 22 24 24 26 26 28 28 30
Temperature When For
(oC) Heating Comp. After 18 20 20 22 22 24 24 26
Removal
26 28 30
Indicated Temperature
ON OFF ON OFF ON OFF
When Cooling 28 26 30 28 32 30
Activating
Standard 30 32 30 32 30 32
Temperature When For
(oC) Heating Comp. After 26 28 28 30 30 32
Removal
4-43
: Factory-Setting
: Changed Setting Period
* : In the case of RPK model, the factory setting is 200 hrs.
4-44
4-45
Setting Air Flow Mode by Remote Control Switch Air Flow of Total Heat Exchanger
LOW MED
MED HIGH
HIGH HIGH
NOTE:
In case that the setting air flow mode by the remote control switch is “HIGH”, the air flow of the total heat
exchanger is “HIGH” even when this function is set.
4-46
>
>
During operation or stoppage in normal condition, press the “TEMP ” switch and “TEMP ” switch
simultaneously for more than 3 seconds.
The remote control switch is changed to the model indication mode.
(2) Indication of Unit Model
(a) At the model indication mode, the following items of information about the indoor unit connected to
the remote control switch are indicated for 3 seconds serially.
1 Address and Refrigerant Cycle Number
2 Model Code of Outdoor Unit
In case of group setting for the plural indoor units by the remote control switch, the above
items 1 ~ 2 are indicated for each indoor unit.
The indication of the above items 1 ~ 2 for all the indoor units connected the remote control
switch is completed, the remote control switch is returned to the normal condition.
(b) Indication of Address and Refrigerant Cycle Number
The indication of the address and
the refrigerant cycle number of the indoor unit
is shown in the right figure.
1 The address of the indoor unit is indicated
at the segments for timer setting time
indication and the “ADDS” is indicated
below the address indication.
2 The refrigerant cycle number of the indoor unit is indicated at the segments for timer setting
time indication and the “RN” is indicated below the refrigerant cycle indication.
3 The indication of the setting temperature is turned OFF.
4-47
4-48
Turn OFF the power source before performing the following procedures.
23
right figure. 7 9
8
e. When the above procedures b, c and d are performed, only the identified indoor unit corresponds
to the commands from the identified wireless remote control switch.
f. When canceling the identification of the unit, set the dip switches of the receiver part and the
setting of the rotary switch (RSW) on the indoor PCB at the former position and cancel the
identification of the unit.
4-49
Turn OFF all the power sources before wiring and setting the dip switches.
Standard Panel
or
Wireless Panel
Wireless
Controller Should be Standard Panel
In case of applying two (2) air panels for wireless control, the setting of main and sub receiver part is
required. Refer to the item 4.5.5 “Optional Function Setting” of the table for the dip switch setting
procedures.
(2) Perform wiring between indoor units by referring to the receiver kit installation manual.
4-50
Setting Position
F 01
CD E
23
Set by inserting slotted screwdriver
456
AB 7 9
8 into the groove
Rotary F 01 F 01 F 01 F 01 F 01 F 01 F 01 F 01
CD E
CD E
CD E
CD E
CD E
CD E
CD E
CD E
23
23
23
23
23
23
23
23
Switch
456
456
456
456
456
456
456
456
AB
AB
AB
AB
AB
AB
AB
AB
7 9 7 9 7 9 7 9 7 9 7 9 7 9 7 9
Setting 8 8 8 8 8 8 8 8
Rotary F 01 F 01 F 01 F 01 F 01 F 01 F 01 F 01
CD E
CD E
CD E
CD E
CD E
CD E
CD E
CD E
23
23
23
23
23
23
23
23
Switch
456
456
456
456
456
456
456
456
AB
AB
AB
AB
AB
AB
AB
AB
Setting
7 9 7 9 7 9 7 9 7 9 7 9 7 9 7 9
8 8 8 8 8 8 8 8
ATTENTION:
If the setting of the rotary switches (RSW) is not performed correctly, the operation LED (Red) on the panel
flickers and the unit can not be operated due to the abnormal setting of the indoor unit number.
Receiver Part
(5) Identify the indoor units by attaching the
nameplates of unit number (field-supplied)
to the indoor units when setting the rotary
switches (RSW) for each indoor unit.
Receiver Part
Unit Number Nameplates
4-51
Turn OFF the power source of the unit before performing the emergency operation.
* When operating the unit by the wireless remote control switch again, set the switch 2 (emergency
operation switch) to the “NORMAL” position.
NOTE:
For stopping the unit operated by the wireless remote control switch, the unit can be stopped by setting the
switch 2 (emergency operation switch) to the “STOP” position instead of turning OFF the power source of
the unit.
In case that PC-LH3 is unusable by batteries shortage, etc., perform emergency operation as follows.
1 Switch “COOL”: Press “COOL” so that the cooling operation is started.
NOTE:
During the emergency operation, the LED (yellow)
blinks (0.5 second ON / 0.5 second OFF).
4-52
Turn OFF all the power sources before setting the dip switches.
Dip Switch
Optional Function
1 2 3 4 5 6 7 8
Standard − − − − −
100 hours − − − − −
Filter Option 1,200 hours − − − − −
2,500 hours − − − − −
No Indication − − − − −
Muffling Buzzer Sound − − − − − − −
Removal of Heating Temperature Calibration − − − − − − −
Circulator Function at Heating Thermo-OFF − − − − − − −
Setting of Sub Receiver Part − − − − − − −
Identifying of Indoor Units − − − − − − −
: ON, : OFF, −: ON or OFF (both available)
4-53
The following optional functions can be set by the dip switches of the receiver kit.
1 Identifying of Indoor Units Installed Side by Side
: ON, : OFF
4-54
<Name of Parts>
Liquid Crystal Display Section The figure below shows all the indications for reference.
The actual display during operation is different.
Indication of Indication of
Mode Selection Pattern Setting
Indication of
Present Day
Indication of
Running Day
of A Week
Run Indicator
(Red Lamp)
Setting Switch of
Change Switch of ON/OFF Time
Operation Mode
Setting Switch of
Present Time
Operation Switch Section The above figure shows the control timer with the cover opened.
The present time and the ON/OFF setting time are indicated
by 12 hour units (AM0:00 – 12:00, PM0:00 – 12:00).
4-55
<Name of Parts>
Indication of
Indication of Indication of Indication of Setting
Group Number Timer Demand Control Temperature
AUTO LOW 9 10 11 12 13 14 15 16
Group Selection
ABNML FILTER
Switch
Run Indicator
(Red Lamp) RUN/STOP GROUP
“FILTER”
RUN/STOP Switch Indication Reset
Switch
MODE FAN SPEED RESET
Fan Speed
Selection Switch Check Switch
Do not touch.
TIMER RMT. SW NAVAL LOUVER CHECK This switch is only
Operation Mode for service use.
TEMP
Selection Switch
Timer Selection
Switch
“Remote Control
Switch Not
Available” Switch
Auto Louver Switch Temperature This switch is not used.
Setting Switch
NOTE:
In the case that the unit is operated under the following conditions, “REMOTE” is indicated on the LCD and
control by the remote control switch is not available.
(1) NAVL is selected by the control station.
(2) Two minutes after resetting of the Central Station even if AVL is selected.
4-56
[Phenomenon]
After commissioning, alarm code “08” sometimes occurred and compressors were burnt out after
2 month operation.
[Cause]
Refrigerant piping work was performed during summer season. Additional refrigerant was not
sufficiently charged from the discharge side.
This insufficient refrigerant charge resulted in discharge gas overheating and oil deterioration finally
due to separated operation despite “08” alarm.
[Countermeasure]
1. The compressor was replaced with a new one.
2. Correct refrigerant amount was charged according to refrigerant piping length and connected indoor
units.
[Remarks]
Additional Refrigerant Charging:
Open the liquid stop valve slightly when the additional refrigerant is charged from the check joint of
the liquid stop valve (discharge side) during the cooling operation. If the liquid valve is fully open, it is
difficult to charge the additional refrigerant. Do not charge refrigerant from the gas stop valve.
5-1
[Phenomenon]
Sufficient cooling was not available for an indoor unit which located at the farthest position.
[Cause]
In the case that an outdoor unit is located 20 meters lower than indoor units, resetting of the dip
switch, DSW3 is required.
However, no setting was performed. Therefore, the target discharge pressure was not increased,
resulting in insufficient cooling performance for the indoor.
I.U.
Insufficient
Cooling
O.U.
DSW3
[Countermeasure]
Setting for DSW3 was changed.
[Remarks]
Pay a special attention to the liquid pipe size if the lift between the indoor units and outdoor unit is
higher than 20 meters. For details, see the “Piping Work” in TCII.
5-2
[Phenomenon]
Operating sound during “Hi” speed was abnormally high.
[Cause]
The indoor units was installed without ducts of inlet side and outlet side. Due to almost no external
static pressure, abnormally big air volume was supplied, resulting in higher air speed through the
heat exchanger.
Damper
Indoor Unit
Air Filter
[Countermeasure]
In order to reduce air flow, a plate as a damper at the discharge side was added.
Another solution is at inlet side and outlet side.
[Remarks]
Please note that running current is increased when no external pressure is given to the indoor unit,
resulting in overheating.
5-3
[Phenomenon]
Alarm code “31” sometimes occurred and the system was stopped.
[Cause]
Combination of the indoor and outdoor unit was as follows.
ON
ON OFF ON ON ON
[Countermeasure]
All the main power switches for the indoor units were always ON.
5-4
5.5 Not Cooling Well due to Insufficient Installation Space for Outdoor Unit
[Phenomenon]
Cooling operation was well performed through the intermediate season. However, the cooling
operation was not well available when the outdoor temperature was higher than 35°C.
[Cause]
As the outdoor units were installed without a sufficient installation space, the hot discharge air from
other outdoor units was circulated.
In this case, though the outdoor temperature was 35°C, the actual suction air temperature was nearly
50°C and Protection System from Excessively High Suction Pressure was activated, the frequency of
the compressor was decreased and the cooling capacity was also decreased accordingly.
As the outdoor units in-line were installed back to back with a distance of 600mm between each
outdoor unit’s back, the hot discharged air from other outdoor units was circulated.
[Countermeasure]
To protect the unit from a short circuit, fences were mounted at the discharge air side as shown
below.
Min.
300mm
Fence
Min.
300mm
5-5
* The SET-FREE FXG/FX3 series is for general office building air conditioning. Therefore, it is
recommended that different air conditioning systems be selected in a place where systems are utilized for
(i) machine rooms or computer rooms, providing big heat load and (ii) thermostatic chamber, requiring
precise temperature control.
* By operating this unit with other cooling/heating equipment at the same time, thermo-ON/OFF may occur
frequently or the heat load change may be big, and it may cause the decrease of the unit performance or
shorten the lifetime of the unit. Do not install the unit in a place where operation with other cooling/heating
equipment is required.
100 100
Heating Capacity (%)
Cooling Capacity (%)
80 80
0 0
0 (5) 21 0 (5) 21
Outdoor Air Temperature (˚C DB) Outdoor Air Temperature (˚C DB)
5-6
[Countermeasure]
Perform the heat load calculation with the decreased capacity as shown in the graph in page 5-8.
Do not install the unit in such a place where temperature difference among rooms is big and the heat
load when cooling and heating is excessively big during simultaneous COOL/HEAT operation.
CH Unit
Mainly Mainly
Cooling Heating
ON OFF ON OFF ON
100%
Capacity
Approx. 10min.
100%
Capacity
5-7
Max. 30m
L (m)
L (m) < 5m
...Multi-kit
L (m) > 5m
...T-branch at the
Liquid Pipe only
CH Unit
Outdoor Unit
CH Unit
Outdoor Unit
CH Unit
Horizontal
CH Unit
5-8
[Example]
* In Case of Start-Up in Simultaneous COOL/HEAT Operation Mode
Cooling
Capacity
Heating
ON
Cooling
Capacity
Heating
ON
10 to 20min.
Cooling Heating
CH Unit
CH Unit
Outdoor Outdoor
Unit Unit
5-9
Correct
Outdoor Unit Outdoor Unit
l: Max. 30m
Max. 40m
H2: Max. 15m
Max. 40m
l: Max. 30m
l0
l2
l0
l4
l2
1 2 3 1 2 3
l4
l1
l1
l3
l5
l3
H2: Max. 15m
Indoor Unit
Indoor Unit L: Max. 100m (Actual)
l0+l1, l2+l3, l0+l1, l2+l3, Max. 125m (Equivalent)
l4: Max 30m H2: Max. 4m l4+l5: Max. 30m
5-10
Unit
Rising Part
Incorrect
Drain Piping
Connection
1/25 to 1/100 Down-Slope
Correct
Common Drain Piping
5-11
5-12
<Example>
System A System B
Outdoor Unit Outdoor Unit
20HP 18HP
System A System B
Refrigerant: 60kg Refrigerant: 50kg
2 4 4 5 5 5 5 3 3
Height
E D D B A 2.5m
Floor Floor Floor Floor Floor
40m2 70m2 70m2 400m2 120m2
<Example>
British Standard BS4434 1989
R22 Commercial Office Building Class D Occupancy
MR = C✕V
MR: Maximum Charge or Leakage of Refrigerant (kg)
C: Maximum Allowable Concentration = 0.17 (kg/m3)
V: Volume of Space (m3)
5-13
5-14
FAN2 RS 20A 211 212 OH FAN2 RS 20A 211 212 OH FAN2 RS 20A 211 212 OH FAN2 RS 20A 211 212 OH FAN2 RS 20A 211 212 OH
5-15
5-16
5-17
0DUN 1DPH
CA 1 Capacitor
CB 1,2 Capacitor
CH, CH 2 Crankcase Heater
CMC1,2 Contactor for Compressor Motor
CN, PCN Connector
CS 1,2 Capacitor
CT 2, 5, U, V Current Transformer
DCL Reactor
DM Diode Module
DS 3,4,9∼12 I.F. Connector
DSW 1~10 Dip Switch on PCB1
DSW 1 Dip Switch on PCB3
EF1~4 Fuse
IPM Transistor Module
ITO 1 Internal Thermostat for Outdoor Fan Motor
LED Light Emitting Diode
MC 1,2 Motor for Compressor
MOF1 Motor for Outdoor Fan
MV 1,2,B Micro-Computer Control Expansion Valve
NF 1~10 Noise Filter
OH 1 Oil Heater for Oil Separator
PCB 1~3 Printed Circuit Board
Pd, Ps Sensor for Refrigerant Pressure
PSH Pressure Switch for Protection
PSW1~3 Push Switch on PCB1
R 1,2 Resistor
RS 1,2 Resistor for Starting
RVR 1,2 Reversing Valve Relay
SVA Solenoid Valve for Hot Gas Bypass
TB 1,2 Terminal Board
TF Transformer
THM 7~10 Thermistor
Y Auxiliary Relay on PCB1
ZNR Surge Absorber
Terminals
1RWH $OOWKHILHOGZLULQJDQGHTXLSPHQWPXVW
FRPSO\ZLWKQDWLRQDODQGORFDOFRGHV
ElectricFactory Wiring
Earth Wiring
Field Wiring