Electrical Properties of The Earthing System
Electrical Properties of The Earthing System
Search
I indicated that Earthing system in any installation is normally comprised of the following components:
Follow Us on
And, I explained all these components in the following Articles:
Today I will explain the Electrical Properties of the Earthing System as follows.
Earthing systems should be constructed in such a manner and of such materials, that
they perform correctly over the whole expected lifetime, at a reasonable
construction cost. The electrical properties of earthing depend essentially on two
parameters:
1. Earthing resistance,
2. Configuration of the earth electrode and favourable earth surface potential
distribution,
3. Adequate current carrying capacity,
4. Long durability.
Earthing resistance determines the relation between earth voltage and the earth
current value.
1 of 8 16/11/2021, 14:21
Electrical Properties of the Earthing System ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/06/electrical-properties-of-ear...
1. The resistance of the ground electrode itself and the connections to the electrode,
2. The contact resistance of the surrounding earth to the electrode,
3. The resistance of the surrounding body of earth around the ground electrode.
1- The resistance of the ground electrode itself and the connections to the electrode:
The resistance of the ground electrode and it's connection is generally very low, ground rods are
generally made of highly conductive/ low resistance material such as copper of copper clad.
The Bureau of Standards has shown this resistance to be almost negligible providing that the
ground electrode is free from paint, grease etc. and that the ground electrode is in firm contact
with the earth.
The ground electrode is surrounded by earth which is made up of concentric shells all having the
same thickness. Those shells closest to the ground electrode have the smallest amount of area
resulting in the greatest degree of resistance.
Each subsequent shell incorporates a greater area resulting in lower resistance. This finally reaches
a point where the additional shells offer little resistance to the ground surrounding the ground
electrode.
2 of 8 16/11/2021, 14:21
Electrical Properties of the Earthing System ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/06/electrical-properties-of-ear...
The calculation of the earthing resistance requires a good knowledge of the soil
properties, particularly of its resistivity. Soil properties are characterised by earth
resistivity, which changes over a wide range from a few Ωm up to few thousand Ωm,
depending on the type of ground and its structure, as well as its humidity.
As a result, it is difficult to calculate an exact value of earthing resistance. All
relationships describing earthing resistance are derived with the assumption that the
ground has a homogenous structure and constant resistivity.
However, earthing resistance should not exceed the values required by guidance or
standards under the most unfavourable climatic conditions (long dry weather, heavy
frost). If there are no exact requirements, the earthing resistance should be as low as
possible.
a) Physical Composition
Table 1
Effect of soil type on resistivity
Typical resistivity
Soil type
ohm-m
Marshy Ground 2 - 2.7
Loam and clay 4 - 150
Chalk 600 - 400
Sand 90 - 8000
Peat 200 upwards
Sandy Gravel 300 - 500
Rock 1000 upwards
b) Moisture
Increased moisture content of the ground can rapidly decrease its resisitivity.
It is especially important to consider moisture content in areas of high seasonal
variation in rainfall.
Wherever possible the earth electrode should be installed deep enough to reach the
"water table" or "permanent moisture level".
Table 2
Effect of Moisture content on resistivity
3 of 8 16/11/2021, 14:21
Electrical Properties of the Earthing System ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/06/electrical-properties-of-ear...
c) Chemical Composition
Certain minerals and salts can affect soil resistivity. Their levels can vary with time
due to rainfall or flowing water.
Table 3
Effect of Salt on Resistivity For sandy loam, 15.2% moisture
0.0 107.0
0.1 18.0
1.0 4.6
5.0 1.9
10.0 1.3
20.0 1.0
Note that although the addition of salt can lower soil resistivity, they are not
recommended due to corrosion and leaching.
d) Temperature
When the ground becomes frozen, its resistivity rises dramatically. An earth that
may be effective during temperate weather may become ineffective in winter.
Table 4
Effect of Temperature on Resistivity For sandy loam, 15.2%
moisture
Temperature Resistivity ohm-m
degC degF
20 68 72
10 50 99
0 32 (water) 138
0 32 (ice) 300
-5 23 790
-15 14 3300
Please note that, if your soil temperature decreases from +20°C to -5°C, the
resistivity increases more than ten times.
The configuration of the earth electrode determines the potential distribution on the
earth surface, which occurs as a result of current flow in the earth. The potential
distribution on the earth surface is an important consideration in assessing the degree
of protection against electric shock because it determines the touch and step
potentials.
Earth surface potential distribution should be such that the touch and step voltages do
not exceed the permitted values.
4 of 8 16/11/2021, 14:21
Electrical Properties of the Earthing System ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/06/electrical-properties-of-ear...
The most favourable earth surface potential distribution concepts have horizontal earth
electrodes, especially meshed ones, whose surface potential can be controlled
relatively simply. The potential distribution of vertical electrodes is the most
unfavourable, with high values of touch potential. On the other hand, vertical
electrodes can easily reach low earthing resistance with stable values, largely
independent from seasons. Vertical electrodes are also used in combination with
horizontal ones in order to reach lower values of earthing resistance.
Please review Article " Types of Earthing System – Part One " for more information about available
Configurations of the Earth Electrode.
It is the highest current value that can be carried through the earth electrode to the
earth, without any excessive heating of the electrode elements and the surrounding
soil itself. At too high current values and current densities, the water in the soil at
the soil-electrode interface evaporates, leaving dry soil with high resistivity.
The durability of the earth electrode is its life from construction up to the time when,
due to the corrosion of metallic parts, electrical continuity is lost. The durability of an
earth electrode should exceed the expected lifetime of the installation.
For the majority of power installations, lifetime can exceed 25 years and for power
lines, 35 – 50 years. The earthing system should be included in repair and maintenance
cycles.
The durability of an earthing system depends mainly on its capability to withstand
corrosion. The earth electrodes, being directly in contact with the soil or with water,
operate in corrosive conditions. There are three main factors determining the rate of
corrosion of metal objects in the soil:
Corrosion due to DC currents occurs mainly in the neighbourhood of DC networks, (for example, DC
railway supplies). There are standards and regulations covering the requirements in such cases.
Corrosion due to chemical substances in the soil is not normally of great importance, affecting only
5 of 8 16/11/2021, 14:21
Electrical Properties of the Earthing System ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/06/electrical-properties-of-ear...
those systems in chemical factories or near the ocean. In such cases, earth electrodes should be
constructed from metals resistant to the specific chemical corrosion.
In order to minimize the chemical corrosion it is recommended, in some cases, to measure the pH
of the soil. For an alkaline soil (pH>7) copper electrodes are recommended, and for acid soil
electrodes made from aluminium, zinc or galvanised steel are preferred.
C- Galvanic Corrosion
This small DC current flowing continually causes the metal ions from anode to flow to
the cathode. Thus, metal is lost from the anode and builds up on the cathode. From this
point of view, favourable metal combinations can be deduced. For example, steel
covered by copper is a favourable solution because the amount of copper remains the
same. An opposite example is steel covered by zinc, where zinc is always the anode and
its amount continually diminishes.
Note that the electrochemical potential of steel embedded in concrete is very close to
that of copper. Thus, steel constructions in building foundations are cathodes in relation
to other steel or zinc objects located in the soil (not only earth electrodes, but also, for
example, water pipes). This means that the large foundations cause significant
corrosion of these metal objects due to electrochemical corrosion.
Mechanical strength and corrosion conditions dictate the minimum dimensions for earth
electrodes given in Table 6 in below image to be:
1. Copper 16 mm2,
2. Aluminium 35 mm2,
3. Steel 50 mm2,
6 of 8 16/11/2021, 14:21
In the next Article, I will explain Steps of Earthing Systems’ Design Process. Please, keep following.