The document provides requirements and design parameters for smoke control and air conditioning systems in buildings. It specifies minimum pressure differences and air flow velocities for stairwells and lobbies during smoke control. It also requires descriptions of the air conditioning system and smoke containment provisions, including means to control over-pressurization. Fire safety provisions like sprinklers and manual firefighting equipment are also addressed.

Uploaded by

wael hassan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views1 page

Cover Pag

The document provides requirements and design parameters for smoke control and air conditioning systems in buildings. It specifies minimum pressure differences and air flow velocities for stairwells and lobbies during smoke control. It also requires descriptions of the air conditioning system and smoke containment provisions, including means to control over-pressurization. Fire safety provisions like sprinklers and manual firefighting equipment are also addressed.

Uploaded by

wael hassan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ACMV and SMOKE CONTROL SYSTEM FIRE PREVENTION DEPARTMENT

PROJECT DESCRIPTION FIRE SAFETY PROVISIONS FIRE SAFETY NOTES FOR ACMV SYSTEM GENERAL DIRECTORATE OF CIVIL DEFENCE
DESIGN BRIEF MINISTRY OF INTERIOR, STATE OF QATAR
(Provide descriptions and scope of works)
FIRE FIGHTING SYSTEM AIR-CONDITIONING SYSTEM:
- DESCRIBE THE SYSTEM PROVIDED FOR AIR-CONDITIONING SYSTEM OF THE ENTIRE BUILDING
AUTOMATIC SPRINKLER SYSTEM OR PROJECT. (CENTRALIZED CHILLED WATER SYSTEM, DUCTED-SPLIT SYSTEM, VAV SYSTEM,
COVERAGE : THROUGHOUT SPLIT TYPE OR WINDOW TYPE A/C, ETC.)
PARTIAL PROTECTION; SPECIFY AREAS PROTECTED: ______________
NON-SPRINKLER PROTECTED SMOKE CONTROL PROVISIONS:
MANUAL FIRE FIGHTING SYSTEM
FIRE HOSE REELS 1 in (25mm) (INDICATE LOCATION ON PLANS) SMOKE CONTAINMENT SYSTEM:
PORTABLE FIRE EXTINGUISHERS DESIGN PARAMETERS
STAIRCASE & LOBBY SMOKE CONTROL CODE/STANDARD MINIMUM PROVIDED/CONSIDERED
REQUIREMENT AS PER DESIGN
RISING MAINS (STANDPIPE SYSTEM)) DESIGN MINIMUM PRESSURE DIFFERENCE (ΔP) BETWEEN
WET STAIRS AND SMOKE ZONES (ALL DOORS CLOSED) in Pascal (Pa.)
DRY MINIMUM PRESSURE DIFFERENCE (ΔP)
BETWEEN PRESSURIZED STAIR AND PRESSURIZED LOBBY in Pascal (Pa.)
FIRE WATER TANK MINIMUM PRESSURE DIFFERENCE (ΔP) 12.5 Pa

PRESSURIZED LOBBY AND SMOKE ZONES


REINFORCED CONCRETE

D
MAXIMUM NUMBER OF DOORS OPEN
STEEL
OTHER, SPECIFY (NON-COMBUSTIBLE): ________________________ MINIMUM AIR FLOW VELOCITY ACROSS OPEN DOORS

E
V )
BREECHING INLET (FIRE DEPARTMENT CONNCTION)
YES N/A (INDICATE LOCATION ON PLANS)
OTHER AUTOMATIC SUPPRESSION SYSTEM
MAXIMUM FORCE TO OPEN DOORS (CALCULATED)

OVER-PRESSURIZATION CONTROL (DESCRIBE MEANS EMPLOYED)


APPROVING AUTHORITY

O
NOTES:
BUILDING DATA TYPE APPLICATION / AREAS PROTECTED

P
SEE LOGIC/SEQUENCE OF OPERATION AND MATRIX FOR THE COMPLETE DETAILS OF THE SYSTEM FUNCTIONALITY
WATER SPRAY SYSTEM DETAILS OF THE EQUIPMENT/MATERIALS PROVIDED IN GENERAL NOTES AND EQUIPMENT SCHEDULE APPLICATION NO : N / YYYY / #######

R S
WATER MIST SYSTEM
CLEAN AGENT SUPPRESSION SYSTEM SERVER ROOM

P (L
CONSULTANT'S ENDORSEMENT
FOAM SYSTEM
PRESSURIZATION OF ESCAPE ROUTE (PRESSURE DIFFERENTIAL P CONCEPT SCHEMATIC)
DRY CHEMICAL SYSTEM

P
WET CHEMICAL SYSTEM
KITCHEN / RANGE HOOD EXTINGUISHING SYSTEM

A AN
STAIRCASE ΔP = ___Pa LOBBY ΔP = ___Pa CORRIDOR ΔP = ___Pa SMOKE AREA
OTHER, SPECIFY: _________________________
(CHECK PROVISIONS & SPECIFY LOCATIONS PROTECTED)

E R L FIRE ALARM SYSTEM


AUTOMATIC DETECTION AND ALARM
MANUAL STAIRCASE ΔP = ___Pa LOBBY ΔP = ___Pa SMOKE AREA

P YP
SMOKE ALARMS
WIRED
MANUAL

AS ET
EMERGENCY COMMUNICATION SYSTEM
STAIRCASE ΔP = ___Pa SMOKE AREA
MAIN PANEL SUB-PANEL
LOCATION: SPECIFY LOCATION: _____________
COMMAND CENTER CAUSE AND EFFECT MATRIX
(FOR ACMV AND SMOKE CONTROL SYSTEM ONLY)

Y AF
GUARD / SECURITY ROOM
OTHER, SPECIFY : _____________________ SMOKE MANAGEMENT SYSTEM:

P
NORMAL SMOKE / FIRE
EMERGENCY LIGHTING BASEMENT CAR PARK VENTILATION OPERATION SCENARIO
LOCATION: ILLUMINATION REQUIREMENT

CO F E S
FOR DUCTED SYSTEM:
EXIT (STAIRCASE) _________________________ CONSULTANT'S SIGNATURE
VENTILATION REQUIREMENT
EXIT ACCESS _________________________ UPDA Reg. No./Grade : 000/X Qatar ID No.: 00000000000
FOR JET FAN SYSTEM:
EXIT DISCARGE _________________________
DESIGN APPROACH : Validity : 00.00.2014 Validity : 00.00.2014
ACMV & SMOKE CONTROL SYSTEM CODE/STANDARDS PROVIDED/VERIFIED CONSULTANT / COMPANY

LI
SMOKE CLEARANCE
POSITIVE PRESSURE VENTILATION SYSTEM REQUIREMENT PER CFD MODEL

STAIRWELL TIME TO CLEAR SPACE OF SMOKE (AS PER CFD MODEL)


SMOKE-STOP LOBBY
MAXIMUM TEMPERATURE OF SMOKE LAYER

LE
FIRE FIGHTING LOBBY
FIRE LIFT SHAFT
ESCAPE CORRIDOR
CODE/STANDARDS PROVIDED/VERIFIED
AREA STATEMENT OTHER, SPECIFY: _________________________ SMOKE CONTROL
REQUIREMENT PER CFD MODEL

SMOKE AND HEAT EXHAUST VENTILATION SYSTEM (SHEVS)


NATURAL
AT 1.8 M ABOVE THE FLOOR AND 10 M RADIUS OF THE DESIGN FIRE:

MINIMUM VISIBILITY UPSTREAM OF THE FIRE P


MECHANICAL
APPLICATION:
MAXIMUM TEMPERATURE OF SMOKE LAYER
M LY
BASEMENT CAR PARK
WAREHOUSE AND / OR STORAGE
MAXIMUM AREA IN THE SMOKE ZONE ALLOWED TO SMOKE LOGGED

A N HEAD OF OFFICE SIGNATURE

S O
AVAILABLE EXIT/S FROM THE SPACE DIRECTLY TO/FROM EXTERNAL UPDA Reg. No. : 000 Company Reg. Grade : A
ATRIUM
FIRE PUMP ROOM NOTES: Validity : 00.00.2014 Qatar ID No. : 00000000000
OTHER, SPECIFY: _________________________ SEE LOGIC/SEQUENCE OF OPERATION AND MATRIX FOR THE COMPLETE DETAIL OF THE SYSTEM FUNCTIONALITY
DETAILS OF THE EQUIPMENT/MATERIALS PROVIDED IN GENERAL NOTES AND EQUIPMENT SCHEDULE CLIENT / OWNER

OTHER MODE OF VENTILATION


NATURAL THRU AIR / SMOKE SHAFT
NATURAL THRU EXTERIOR WALL OPENINGS ATRIUM AND OTHER LARGE SPACES
OTHER, SPECIFY: _________________________ MODE OF VENTILATION : _______________________ (PLS. DESCRIBE; E.G. SHEV, VENTS, SMOKE PURGING, ETC)

DESIGNED PER (REFERENCE STANDARD) : ____________________________

EMERGENCY POWER SUPPLY SYSTEM DETAILS:

DIESEL-ENGINE GENERATOR SET LOCATION AND NUMBER OF EXHAUST FANS/CAPACITIES


OTHER, SPECIFY: _________________________ LOCATION AND NUMBER OF MAKE-UP AIR FANS OR OPENINGS
RATIO OF MAKE-UP AIR SUPPLY TO EXHAUSTS
OTHERS

OTHER FIRE SAFETY PROVISIONS NOTES:


(Provide descriptions and specifications) SEE LOGIC/SEQUENCE OF OPERATION AND MATRIX FOR THE COMPLETE DETAILS OF THE SYSTEM FUNCTIONALITY
PROJECT TITLE
DETAILS OF THE EQUIPMENT/MATERIALS PROVIDED IN GENERAL NOTES AND EQUIPMENT SCHEDULE

DRAWING INDEX NATURAL VENTILATION PROVISIONS:


MODE OF MIN. AREA OF LOCATION OF
FIRE PUMP AND GENERATOR ROOM NORMAL SMOKE / FIRE SPACE OR AREA IN THE BUILDING VENTILATION OF OPENINGS OPENINGS
OPERATION SCENARIO
CARPARKS / STORAGE CROSS VENTILATION/SMOKE DISPERSAL DISTRIBUTED AT TWO OPPOSING SIDES

VENTILATION REQUIREMENT
INDUSTRIAL / MANUFACTURING / FACTORY STACK VENTILATION/SMOKE DISPERSAL ALONG PERIMETER WALLS AND ROOF

LE
AIR-CONDITIONING AND VENTILATION SYSTEM DRAWING LIST NOTES:
- AT THE TOP OF THE STAIRWELL
NO. SHEET NO. DRAWING TITLE SCALE PAPER SEE LOGIC/SEQUENCE OF OPERATION AND MATRIX FOR THE COMPLETE DETAILS OF THE SYSTEM FUNCTIONALITY STAIRCASE STACK VENTILATION/SMOKE DISPERSAL
LOCATION : PIN :
- AT EACH FLOOR LEVEL
DETAILS OF THE EQUIPMENT/MATERIALS PROVIDED IN GENERAL NOTES AND EQUIPMENT SCHEDULE
GENERAL DRAWINGS:
OTHERS AREA : STREET : PLOT :
1.
2.
3.
P FIRE COMMAND CENTER
Notes:
DRAWING TITLE

M
MODE OF VENTILATION : _______________________ (PLS. DESCRIBE; E.G. POSITIVE VENTILATION, ETC.) SEE DETAILS OF THE DISTRIBUTION/ARRANGEMENT OF THE OPENINGS IN RELATED DRAWING PAGES.
4.

A ONLY
DETAILS:
5.
LOCATION AND FANS CAPACITIES
6.
7.
OPERATION:
FIRE IN THE BUILDING
GENERAL INFORMATION FOR

S ACMV and SMOKE MANAGEMENT SYSTEM


FIRE WITHIN THE FCC
8.
SUBMISSIONS AFTER LIFE SAFETY PLAN APPROVAL OTHERS
9. NOTES:
10. FIRE FIGHTING (FF) FIRE ALARM (FA) SEE LOGIC/SEQUENCE OF OPERATION AND MATRIX FOR THE COMPLETE DETAILS OF THE SYSTEM FUNCTIONALITY
DETAILS OF THE EQUIPMENT/MATERIALS PROVIDED IN GENERAL NOTES AND EQUIPMENT SCHEDULE
11. ACMV & SMOKE CONTROL SYSTEM (MV)
12.
LIFE SAFETY PLANS APPROVED APPLICATION NO.: __________________________

LOCATION OF FAN CONTROL PANELS


- LOCATION OF CONTROL PANELS RELATED TO MECHANICAL VENTILATION SHALL BE LOCATED AT
REVISION NO. : SHEET NO : DRAWING NUMBER
GROUND LEVEL - FIRE COMMAND CENTER (PLEASE INDICATE LOCATION AS SHOWN IN THE PLANS).
DATE : SCALE :