Telemecanique LADN22 Datasheet
Telemecanique LADN22 Datasheet
Main
Commercial Status Commercialised
Range of product TeSys D
TeSys D control relay
TeSys F
Product or component Auxiliary contact block
type
Product compatibility CR1F
Auxiliary contacts oper- Instantaneous
ation
Pole contact composi- 2 NO + 2 NC
tion
Connections - terminals Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: solid - without cable end
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: solid - with cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: flexible - without cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: flexible - with cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: solid - without cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: solid - with cable end
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Screw clamp terminals 1 cable 1...2.5 mm² - cable
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
stiffness: flexible - without cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: flexible - with cable end
Complementary
Mounting location Front
[Ui] rated insulation voltage 600 V - certifications CSA
690 V - conforming to IEC 60947-5-1
600 V - certifications UL
[Ue] rated operational voltage 690 V AC 25...400 Hz
[Ith] conventional free air thermal current 10 A at <= 60 °C
Irms rated making capacity 250 A at <= 690 V DC conforming to IEC 60947-5-1
140 A at <= 690 V AC conforming to IEC 60947-5-1
Permissible short-time rating 140 A at -5...60 °C 100 ms
120 A at -5...60 °C 500 ms
100 A at -5...60 °C 1 s
Protection type GG fuse <= 10 A rating according to operational current for Ue <= 690 V
Associated fuse rating IEC 60947-5-1
Mechanical durability 30 Mcycles
Minimum switching current 5 mA
Minimum switching voltage 17 V
Non-overlap time 1.5 ms on energisation (no overlap between NC and NO contact)
1.5 ms on de-energisation (no overlap between NC and NO contact)
Overlap time 1.5 ms
Insulation resistance > 10 MOhm
Product weight 0.05 kg
RoHS compliance
RoHS EUR status Compliant
RoHS EUR conformity date(YYWW) 0629
Contractual warranty
Period 18 months