Week 4 Electrical Utility Engineering
Week 4 Electrical Utility Engineering
IA
Design factors to be considered, related IS standards. Draw SLD as per standard.
LL
Selection of power contactors, auxiliary contactors, protective devices, size of control circuit wire,
power circuit wire, busbar rating, MCCB, Air Circuit Breaker.
SU
design factors to be considered Applicable standards.
https://electricalnotes.wordpress.com/2015/10/02/calculate-size-of-main-elcb-brach-mcb-of-dis
P
tribution-box/
G
1. Design LT Distribution Box of one House and Calculation of Size of Main ELCB and branch
Circuit MCB as following Load Detail. Power Supply is 430V (P-P), 230 (P-N), 50Hz.
KV
Consider Demand Factor 0.6 for Non Continuous Load & 1 for Continuous Load for Each
Equipment.
ER
R
TU
C
LE
K
G
PA
AP
N
AN
■ Branch Circuit-1: 4 No of 1Phase, 40W, Lamp of Non Continues Load + 2 No’s of 1Ph,
60W, Fan of Non Continues Load.
■ Branch Circuit-2: 2 No of 1Ph, 200W, Computer of Non Continues Load.
■ Branch Circuit-3: 1 No of 1Ph, 200W, Freeze of Continues Load.
■ Branch Circuit-4: 8 No of 1Ph, 40W, Lamp of Non Continues Load + 2 No’s of 1Ph 60W,
Fan of Non Continues Load.
IA
LL
SU
P
G
KV
ER
Fault Current
R
230V 6KA
C
430V 10KA
LE
11KV 25KA
K
G
Class of MCB/ELCB/RCCB
PA
IA
LL
SU
Size of MCB/ELCB
P
MCB/ELCB (Amp) Load MCB/ELCB (Amp)
G
KV
1.0 to 4.0 6 16
ER
6.0 10 16
R
10.0 16 16
TU
16.0 20 20
C
20.0 25 25
LE
25.0 32 32
K
G
32.0 40 40
PA
40.0 45 45
AP
45.0 50 50
N
50.0 63 63
AN
63.0 80 80
IA
1600.0 2000 2000
LL
2000.0 3000 3000
SU
3000.0 3200 3200
P
3200.0 4000 4000
G
KV
4000.0 5000 5000
ER
5000.0 6000 6000
Calculation:
Size of MCB for Branch Circuit-1:
C
=(2X200X0.6)/230=1.04Amp
■ Branch Circuit-2 Current as per NEC = Non Continues Load+125% Continues Load
■ Branch Circuit-2 Current as per NEC =(1.04)+125%(0) =1.04Amp
■ Type of Load=Lighting Type
■ Class of MCB=B Class
Size of MCB= Full load current X Factor of safety 2=1.04 x 2)=2.08A
■ Size of MCB=6 Amp
■ Breaking Capacity: 6KA
ANNAPPA G K Lecturer K.V.G POLYTECHNIC SULLIA 4
5TH SEM Electrical & Electronics Engineering ELECTRICAL UTILITY ENGINEERING
■ No of Pole of MCB=Single Pole
Size of MCB for Branch Circuit-3:
■ Load Current of Freeze= (No X Watt X Demand Factor)/Volt =(1X200X1)/230=0.87Amp
■ Branch Circuit-3 Current as per NEC = Non Continues Load+125% Continues Load
■ Branch Circuit-3 Current as per NEC =(0)+125%(0.87) =1.08Amp
■ Type of Load=Lighting Type
■ Class of MCB=B Class
\Size of MCB= Full load current X Factor of safety 2=(1.08 x 2)=2.16A
IA
■ Size of MCB=6 Amp
LL
■ Breaking Capacity: 6KA
■ No of Pole of MCB=Single Pole
SU
Size of MCB for Branch Circuit-4:
■ Load Current of Lamp= (No X Watt X Demand Factor)/Volt =(8X40X0.6)/230=0.83Amp
P
■ Load Current of Fan= (No X Watt X Demand Factor)/Volt =(2X60X0.6)/230=0.31Amp
G
■ Branch Circuit-4 Current as per NEC = Non Continues Load+125% Continues Load
■ Branch Circuit-4 Current as per NEC =(0.83+0.31)+125%(0) =1.15Amp
KV
■ Type of Load=Lighting Type
■ Class of MCB=B Class
ER
Size of MCB= Full load current X Factor of safety 2=(1.15 x 2)=2.3A
■ Size of MCB=6 Amp
R
■ Branch Circuit-5 Current as per NEC = Non Continues Load+125% Continues Load
■ Branch Circuit-5 Current as per NEC =(0.42+0.16)+125%(0.65) =0.57+0.82=1.39Amp
G
IA
■ Class of MCB=C Class
LL
Size of MCB= Full load current X Factor of safety 2=(7.83 x 2)=16.66A
■ Size of MCB=16 Amp
SU
■ Breaking Capacity: 6KA
■ No of Pole of MCB=Single Pole
P
Size of MCB for Branch Circuit-8:
G
■ Load Current of Motor-Pump = (No X Watt X Demand Factor)/(1.732XVolt )
=(1X746X0.6)/(1.732X430)=0.60Amp
KV
■ Branch Circuit-8 Current as per NEC =Non Continues Load+125% Continues Load
■ Branch Circuit-8 Current as per NEC =(0.60)+125%(0) =0.60Amp
ER
■ Type of Load=Motor-Pump Type
■ Class of MCB=C Class
R
Total 18.04
IA
■ Total Load Current as per NEC= 18.04Amp——–(A)
■ Max Size of Branch circuit MCB=16Amp
LL
■ Total Current of Panel as per Branch Circuit= 2X Max Size of Branch circuit MCB
SU
■ Total Load Current of Panel as per Branch Circuit =2X16=32Amp——(B)
■ Total Load Current of Panel as per NEC = Maximum of (A) and (B)
■ Total Load Current of Panel as per NEC=32Amp
P
■ Min Size of ELCB/RCCB as per NEC=40Amp
G
■ Class of ELCB/RCCB= B or C Class
KV
■ No of Pole of ELCB/RCCB=TP or FP
■ Sensitivity( I∆n)=30ma
ER
■ Breaking Capacity=10KA
Size of LT Distribution Board:
R
■ To Balance Load We need to try distribute Single Phase load on each Phase.
G
Summary of Load
IA
Y Phase Load 3.5 Amp
LL
B Phase Load 7.23 Amp
SU
Total Load 18.04 Amp
P
Summary of LT Distribution Box :
G
KV
ER
R
TU
C
LE
K
G
IA
WEEK 4 DAY 2 1ST SESSION 9 AM TO 1 PM
ACB (Air Circuit Breaker) with Motorized spring charging - Parts of ACB, control circuit
LL
and its working.
SU
https://www.electricaltechnology.org/2014/11/air-circuit-breaker-operation-types-uses.html
What is a Circuit Breaker?
A circuit breaker is a device, which can
P
● Make or break a circuit manually or by remote control under normal conditions.
G
● Break a circuit automatically under fault conditions (like overcurrent, Short circuit, etc).
KV
● Make a circuit manually or by remote control under the fault conditions.
A circuit breaker is used for switching mechanism and protection of the system. Other associated
devises and components are also used for this purpose associated with circuit breakers like fuses,
ER
relays, switches etc. Circuit breakers are widely used in industries as well as power system for
controlling and protection of different parts of the circuit like switch gears, Transformers, Motors,
R
TU
C
LE
K
G
There are different types of air circuit breakers available in the market and we will discuss one by
one in detail.
AP
Air Circuit Breaker (ACB) is an electrical protection device used for short circuit and overcurrent
AN
protection up to 15kV with amperes rating of 800A to 10kA. It operates in air (where air-blast as an
arc quenching medium) at atmospheric pressure to protect the connected electric circuits. ACB has
completely replaced by oil circuit breaker because it is still a preferable choice to use an ACB
because, there is no chance of oil fire like in oil circuit breaker.
Construction of Air-Circuit Breaker
The following fig shows the main and external parts of an ACB. (ABB EMax Low Voltage, Current
Limiting and Selective (Non-Current Limiting) Air Circuit Breaker).
IA
LL
SU
P
G
KV
ER
R
TU
7. Controller
G
9. User-supplied padlock
10. Connection “,” Test “and” separation “of the position indication
AP
11. Connection (CE) Separation, (CD) Test (CT) Position indication contacts
12. Rated Name Plate
13. Digital Displays
N
IA
LL
SU
P
G
KV
ER
R
● 8. Terminal box for fixed version – Sliding Contacts for withdrawable version
● 9. Protection Trip Unit
PA
The main aim of circuit breaker is to prevent reestablishment of arcing after current zero where the
AN
contact gap will withstand the system recovery voltage. It does it same work, but in a different
manner. During interruption of arc, it creates an arc voltage instead of supply voltage. Arc voltage is
defined as the minimum voltage required for maintaining arc .The circuit breaker increases the
voltage in three different ways:
● Arc voltage can be increased by cooling arc plasma. As soon as the temperature of arc
plasma motion of particle in arc plasma is reduced, more voltage gradient will be required
to maintain the arc.
● By splitting the arc into a number of series will increases the arc voltage.
IA
There are four types of ACBs used in the control and protection to maintain and stable operation of
switch gears and indoor medium voltage.
LL
● Plain Break Type Air Break Circuit Breaker or Cross-Blast ACB
● Magnetic Blowout Type Air Break Circuit Breaker
SU
● Air Chute Air Break Circuit Breaker
● Air Blast Circuit Breaker
P
G
KV
EXAMPLE :
Design a main LT distribution panel for the following load requirements in a factory.
ER
• Machine Shop-10 HP load,
• Borewell pump-5HP x 2 nos,
R
• Painting section - 5 KW
• Lift – 5HP
Estimate the cost of the above LT panel.
K
Selection of cables, wire sizes, switchgears and accessories. Automatic phase sequence
G
Consider Demand Factor 0.6 for Non Continuous Load & 1 for Continuous Load for Each
Equipment.
N
Calculation:
AN
IA
3 3
• OLR=70% of full load current 0.7 X 7.5 =5.25A
LL
● OLR=120% of full load current 1.2 X 7.5 =9A
SU
● OLR is 5.25-9A Select
(not applicable for LT panel design)
P
G
KV
ER
R
TU
C
LE
K
G
PA
• Branch Circuit-2 Current as per NEC = Non Continuous Load+125% Continues Load
Branch Circuit-2 Current as per NEC =(3.8)+125%(0) =4 Amp
• Type of Load=Borewell pumpType
• Class of MCB=C Class
• Size of MCB=16 Amp-------2NO
• Breaking Capacity: 10KA
• No of Pole of MCB= Three Pole
• Size of cable= load current X factor of safety 2
ANNAPPA G K Lecturer K.V.G POLYTECHNIC SULLIA 13
5TH SEM Electrical & Electronics Engineering ELECTRICAL UTILITY ENGINEERING
=4 X 2 =8A Select 1.5q.mm 4 core cable
=DOL starter for 5HP Motor
● Motor load current= 4A,415V
𝑙𝑖𝑛𝑒 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 4
● Relay current= = =2.3A
3 3
So those relay selected 2-5A .Available in market ---------2 NO
• OLR=70% of full load current 0.7 X 4 =2.8A
● OLR=120% of full load current 1.2 X 4 =4.8A
IA
● OLR is 2.8--5A Select ---------2 NO
LL
(not applicable for LT panel design)
Size of MCB,Cable, for Branch Circuit-3:
SU
Office with 20 computers assume cos 𝛩=0.8, non Continuous Load
Load Current of 20 computers = (No X Watt X Demand Factor)/(Volt X Cos𝛩 ) =(60X20X1)/(230
P
X 0.8)=6.6Amp
G
• Branch Circuit-3 Current as per NEC = Non Continuous Load+125% Continues Load
Branch Circuit-3 Current as per NEC =(0)+125%(6.6) =8.25Amp
KV
• Type of Load=lighting Type
• Class of MCB=B Class
ER
• Size of MCB=10 Amp
• Breaking Capacity: 10KA
R
Load Current of Office lighting – 1 kw= (No X Watt X Demand Factor)/(Volt X Cos𝛩 )
PA
=(1X1000X1)/(230 X 1)=4.4Amp
• Branch Circuit-3 Current as per NEC = Non Continues Load+125% Continues Load
AP
IA
• Class of MCB=B Class
LL
• Size of MCB=16 Amp
• Breaking Capacity: 10KA
SU
• No of Pole of MCB= Double Pole
• Size of cable= load current X factor of safety 2
P
=7.8 X 2 =15.6 A Select 2 q.mm 3 core cable
G
• OLR=70% of full load current 0.7 X 7.8=5.5A
• OLR=120% of full load current 1.2 X 13=9.36A
KV
(not applicable for LT panel design)
Size of MCB,Cable, for Branch Circuit-6:
ER
Street light in premises– 2 kw cos 𝛩=1, non Continuous Load
Load Current of Street light in premises – 2kw= (1 X 2000 X Demand Factor)/(Volt X Cos𝛩 )
R
=(1X2000X0.6)/(230 X 1)=5.2Amp
TU
• Branch Circuit 6 Current as per NEC = Non Continues Load+125% Continues Load
Branch Circuit-6 Current as per NEC =(5.2)+125%(0) =5.2Amp
C
IA
Lift – 5HP assume cos 𝛩=0.8, Non Continuous Load
LL
Load Current of Borewell pump = (No X Watt X Demand Factor)/(1.732XVolt X Cos𝛩 )
=(5X746X0.6)/(1.732X430 X 0.8)=3.8Amp
SU
• Branch Circuit-2 Current as per NEC = Non Continues Load+125% Continues Load
Branch Circuit-2 Current as per NEC =(3.8)+125%(0) =4Amp
P
• Type of Load=Lift Type
G
• Class of MCB=C Class
• Size of MCB=16 Amp
KV
• Breaking Capacity: 10KA
• No of Pole of MCB= Three Pole
ER
• Size of cable= load current X factor of safety 2
=4 X 2 =8A Select 1.5q.mm 4 core cable
R
3 3
So those relay selected 2-5A .Available in market
LE
(Amp) MCB
(Amp)
AN
IA
circuit-8 4 6 Amp C Class 6KA TP
LL
Total 55.6 A
SU
■ Total Load Current as per NEC= 55.6Amp——–(A)
■ Total Current of Panel as per Branch Circuit= 2X Total current
P
■ Total Load Current of Panel as per Branch Circuit =2X55.6=111Amp——(B)
G
■ Total Load Current of Panel as per NEC=111 Amp
KV
■ Min Size of ELCB/RCCB as per NEC=125 Amp
■ Class of ELCB/RCCB= B or C Class
ER
■ No of Pole of ELCB/RCCB=TP or FP
■ Sensitivity( I∆n)=30ma
R
■ Breaking Capacity=100KA
TU
Models Amps/ Kva Rates: 30 Amps, 40A, 60A, 100A, 125A, 150A, 200A, 250A, 300A, 400A, 450A, Upto 630
Amps. Available in market
K
ELR-- 1 no
PA
AP
N
AN
IA
3 Current limiter 60A, 600V No 1 150.00 150.00
LL
4 MCB,16A, Class C. TP,10KV braking capacity NO 2 400.00 800.00
SU
5 MCB,16A, Class B. TP,10KV braking capacity No 1 350.00 350.00
P
6 MCB,6A, Class B. DP, 10 KV braking capacity NO 2 300.00 600.00
G
KV
7 MCB,16A, Class B. DP, 10KV braking capacity NO 2 325.00 650.00
8 Conductor : Mtr
ER
1) 25sq.mm PVC insulated 600V, 55A,
R
10 ELR No 1
K
G
PA
AP
IA
WEEK 4 DAY 4 1ST SESSION 9 AM TO 1 PM
LL
Wire-up the control circuit of LT panel and test
SU
WEEK 4 DAY 4 2ND SESSION 2 AM TO 5 PM
P
Wire-up the control circuit of LT panel and test
G
KV
WEEK 4 DAY 5 1ST SESSION 9 AM TO 1 PM
Developmental Assessment ER
WEEK 4 DAY 5 2ND SESSION 2 AM TO 5 PM
Assessment Review and corrective action
R
TU
Industry Class:
LE
K
G
PA
AP
N
AN